Modbus Map: Conext System Control Panel (SCP) Device

Similar documents
Modbus Map: System Control Panel (SCP) Device

Modbus Map: Automatic Generator Start (AGS) Device

Modbus Map: Conext MPPT Device

Modbus Map: MPPT60 Device

Modbus Map: Conext XW/XW+ Device

Conext TM ComBox USB Application Note - copy_settings

Conext TM ComBox USB Application Note reset_logs.lux, reset_logs_cfgs.lux

DRAFT. Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters. 1.0 Introduction DANGER. 1.1 Related Documents

Conext CL-60 Inverter Firmware Upgrade Process

Application Note on Modifying Disconnect Settings for Xantrex GT Series Single Phase Inverters and Conext TX Series Inverters

Technical Note: XW/Conext XW+

Application Note: Using Modbus With the Conext CL Series. Important Safety Instructions

Version 3.00 User s Guide

Using the AUX Port on the Conext XW+ to Connect to a Generator or the Grid

SCADAPack E Idec PLC Interface Manual

Galaxy Shore Connection 500 kva. Operation 04/

VP Process Inc. Model: VP-EC-RDU Modbus RTU LCD Display

Conext ComBox Communication and Monitoring Device

MySonicWall Secure Upgrade Plus

Conext ComBox Communication and Monitoring Device

Conext EasyConfig Tool

SERVICE BULLETIN DEPARTMENT OF COMPLIANCE VEHICLE SAFETY AND RECALL MANAGEMENT BUILDING N MAIN ST MIDDLEBURY, INDIANA

Servo press kit YJKP - Host interface

2 Upgrading the ComBox Firmware

Gastrack Gas Analyser

Version Action Author Date

Ethernet Modbus X80 Gateway Device Type Manager

Conext CL-60 EasyConfig Tool

ArduCAM-M-2MP Camera Shield

Symmetra MW kw 380/400/480 V Operation. UPS System with External Bypass 01/

AN NTAG I²C plus memory configuration options. Application note COMPANY PUBLIC. Rev June Document information

LCD Module with I2C / Serial Interface and Keypad Control «LCD I2C/Serial» User s Guide. Copyright 2008 IMS

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E

Multi-Loader. User manual VW3A / BBV48778

Softstarters. Type PSE Fieldbus Communication Fieldbus Plug DeviceNet. 1SFC132066M0201 January SFC132066M0201 1

DATASHEET 4D SYSTEMS. 4D Arduino Adaptor Shield TURNING TECHNOLOGY INTO ART. 4Display-Adaptor-Shield

Conext ComBox. Installation and Configuration Manual.

BFR3000 Modbus Router

AN CBTL08GP053 Programmer's Guide. Document information. Keywords Abstract

T7 Modbus Communication User Guide

SCADAPack E Target 5 DF1 PLC Interface

TeSys Programmer. Firmware Update Utility for LTMR & LTMCU User Manual. January 2017

Multi-Loader. User manual 06/ BBV48778

Owner s Guide. System Control Panel

PowerLogic ION7550 RTU option

For more information Contact with details of the application.

Modbus Register Map: Galaxy 300

Modbus Register Map: Galaxy 5000 & Galaxy 5500

SIMATIC IPC Wizard for. Widescreen devices with multitouch SIMATIC. Industrial PC SIMATIC IPC Wizard for. Preface.

FNL Modbus TCP Interface

DataVU 5 - Interface Manual Modbus

DataVU 5 - Interface Manual Modbus

JUMO di 308. Digital Indicator. B Interface Description Modbus 12.07/

Change Report Colors and Logo

DL-10. User Manual. RS-485 Remote Temperature and Humidity. English Ver. 1.0, Jul. 2017

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

XS/SC26-2 Safety Controller Quick Start Guide

DATASHEET 4D SYSTEMS. 4D Raspberry Pi Serial Adaptor TURNING TECHNOLOGY INTO ART. 4D-Serial-Pi-Adaptor

1602 SMART LCD DISPLAY MODULE HCMODU0122

4D SYSTEMS TURNING TECHNOLOGY INTO ART. Application Note: 4D-AN-G5002

PRELIMINARY DESCRIPTION. (*)Coil (Hex) 0x00A1 0x00A2 0x00A3

MTN MTN

hdpv.org Ampt Communications Unit Installation Manual D

DATASHEET 4D SYSTEMS. 4D Raspberry Pi Serial Adaptor TURNING TECHNOLOGY INTO ART. 4D-Serial-Pi-Adaptor

Grundfos MAGNA, GENI Module

ZBRN2 Modbus Serial Line Communication

Flarm LED indicator. Version 1.1

DATASHEET 4D SYSTEMS. 4D Raspberry Pi Serial Adaptor TURNING TECHNOLOGY INTO ART. 4D-Serial-Pi-Adaptor

DeviceNet Expansion Board

Unity Pro OSLoader User Manual

Operator Manual for Profibus

AND8386/D. Bootloading BelaSigna 250 Using the I 2 C Interface APPLICATION NOTE

Utilizing Extra FC Credits for PCI Express Inbound Posted Memory Write Transactions in PowerQUICC III Devices

EtherCAT. CDG025D2 CDG045D CDG045D2 CDG045Dhs CDG100D CDG100D2 CDG100Dhs CDG160D CDG160Dhs CDG200D CDG200Dhs. Communication Protocol

On Control SUSA v1.1 MODBUS Functions

Overview This section describes how to use the LTM R controller via the network port using the Modbus protocol.

SonicWall Mobile Connect for Chrome OS

COOLMAX SR MAXIMIZER WALLMOUNT

IO-Link parameter description

ENGLISH ENGLISH ENGLISH ENGLISH

CTT MODBUS-RTU COMMUNICATION PROTOCOL TEMPERATURE MONITOR DEVICE

POWERKEY PRO & POWERKEY

Application Note AN0003. Binary Messages. SkyTraq Venus 5 GPS Receiver

PRELIMINARY DESCRIPTION

StruxureWare Power Monitoring 7.0

PF MODBUS REGISTER MAP. v1.4 Revised Nov 29, 2016

TeSys U Communication Variables

deltadue DY-5030 Protocol Converter CANopen/Modbus Master User Manual M.U. DY /09.05 Cod. J ADY E

EZ-LIGHT K50 Modbus Series Pick-to-Light Sensors

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

L-Series and SkyPanel

USER MANUAL Z-SG / Z-SG-L. Advanced Digital Strain gauge converter. Via Austria, PADOVA ITALY

DATASHEET 4D SYSTEMS. 4Display Shield with 2.2 Display TURNING TECHNOLOGY INTO ART. 4Display-Shield-22

Configuration limits for products of the SIMATIC NET PC Software V8.1 SIMATIC NET

Manual for disconnecting from the internet.

The power supply input should be connected via a rated VAC/VDC power supply and properly isolated from the line voltage.

SonicWall SonicOS 5.9

Readme SiVArc V14 SP1 Update 6

AFRecorder 4800R Serial Port Programming Interface Description For Software Version 9.5 (Last Revision )

FnIO S-Series. FnIO MODBUS Adapter Specification Rev 1.00 NA-9473 (MODBUS/RS485) Page 1 of 30. NA-9473 (MODBUS/RS485) Adapter

Transcription:

Modbus Map: Conext System Control Panel (SCP) Device 503-0251-01-01 Revision A.3 UNINTENDED OPERATION WARNING The use of this product with Modbus communications requires expertise in the design, operation, and programming of the device. Only qualified persons should program, install, alter, and commission this product. When writing values to the device, you must ensure other persons are not working with the device. Failure to follow these instructions can result in death or serious injury, and/or equipment damage. LOSS OF CONTROL WARNING Do not assign the same address to two Modbus devices. The entire serial bus may behave unexpectedly if the master device cannot communicate with all the slave devices on the bus. Failure to follow these instructions can result in death or serious injury, and/or equipment damage. Overview This document describes the structure of the Modbus register address map, which is used to configure, control, and monitor the Conext System Control Panel (Conext SCP). Use this document with the Modbus Converter Owner s Guide (975-0685-01-01 Revision A or later) or the Conext ComBox Owner s Guide (975-0679-01-01 Revision A or later). The information in this document is intended for use only by qualified persons who have a detailed technical understanding of the Modbus protocol. The Modbus map is divided into rows of Modbus registers. Each row indicates the Modbus register address, its name, data type, access type, units, scale, offset, and applicable notes as required. External Modbus Master devices, such as the Schneider Electric M340 PLC, can read and write the Modbus registers to configure, control, or monitor the device remotely. Document Applicability The Conext SCP Device Modbus map applies to the following products, as listed in Table 1.

Table 1 Applicable Products Product ID Product Description 865-1050-01 Conext System Control Panel 865-1050 XW System Control Panel Supported Modbus Data Types Table 2 lists the supported data types. Table 2 Modbus Data Types Data Type Description uint16 unsigned 16-bit integer [0,65535] uint32 unsigned 32-bit integer [0,4294967295] str<nn> packed 8-bit character string, where <nn> is the length of characters in the string. Two characters are packed into each Modbus register. Example: str20 = 20-character string (packed into 10 Modbus registers) str16 = 16-character string (packed into 8 Modbus registers) Writing Modbus Registers Modbus does not provide an error response when data written to a Modbus Register is out of range or invalid. To confirm that a Modbus Register is correctly written, you should read it back and compare it with the expected value. For descriptions of settings and their valid values, refer to the product s user manual (975-0298-01-01). Conext SCP Device Modbus Map Table 3 Configuration and Status Registers Modbus Address Name Type read/write (r/w) Units Scale Offset Notes 0x0000 Device Name str16 r/w 0x000A FGA Number str20 r 0x0014 Unique ID Number str20 r 0x001E Firmware Version str20 r 0x0028 Modbus Address uint16 r/w 1.0 0.0 0x0029 Device Number uint16 r/w 1.0 0.0 0x002A System Instance uint16 r/w 1.0 0.0 0x002B Hardware Serial Number str20 r 0x0040 Device State uint16 r 1.0 0.0 See Operating State 2 503-0251-01-01 Revision A.3

Table 3 Configuration and Status Registers Modbus Address Name Type read/write (r/w) Units Scale Offset Notes 0x0041 Device Present uint16 r 1.0 0.0 0=Inactive (all data invalid) 1=Active (data valid) 0x0042 Active Faults Flag uint16 r 1.0 0.0 0=No Active Faults 1=Has Active Faults 0x0043 Active Warnings Flag uint16 r 1.0 0.0 0=No Warnings 1=Unit has Active Warnings 0x0044 Fault Bitmap 0 uint16 r 1.0 0.0 See Fault Bits 0x0045 Warning Bitmap 0 uint16 r 1.0 0.0 See Warning Bits 0x0046 Configuration Errors uint32 r 1.0 0.0 0x0048 Reset uint16 r/w 1.0 0.0 0=Reboot 2=Reset to Factory 0x0049 Operating Mode uint16 r/w 1.0 0.0 2=Standby 3=Operating 0x004A Clear uint16 r/w 1.0 0.0 See Clear Command 0x004B Display Brightness uint16 r/w 1.0 0.0 0x004C Display Contrast uint16 r/w 1.0 0.0 0x004D Backlight Timeout uint16 r/w 1.0 0.0 0x004E Button Beep uint16 r/w 1.0 0.0 0=Disabled 1=Enabled 0x004F Fault Alarm uint16 r/w 1.0 0.0 0=Disabled 1=Enabled 0x0050 Set Degrees uint16 r/w 1.0 0.0 0=Fahrenheit 1=Celsius 0x0051 Time Format uint16 r/w 1.0 0.0 0=AM/PM 1=24-Hour 0x0052 Identify Enable uint16 r/w 1.0 0.0 0=Disable 1=Enable 0x0053 Refresh Configuration Data uint16 r/w 1.0 0.0 1=Refresh Operating State Device State can report one of the following values: 0=Hibernate 1=Power Save 2=Safe Mode 3=Operating 4=Diagnostic Mode 503-0251-01-01 Revision A.3 3

5=Remote Power Off 255=Data Not Available Fault Bits Fault Bitmap 0 can report one or more of the following values: bit0=f250 System clock not set bit1=f251 A device is lost bit2=f252 New device detected bit3=f500 Internal failure bit4=f501 Memory failure bit5=f503 Internal reset bit6=f504 Lost network connection bit7=f505 Internal failure Warning Bits Warning Bitmap 0 can report one or more of the following values: bit0=w250 The value failed to change bit1=w251 User confirm prompt: Equalization process bit2=w252 User confirm prompt: Restore default settings bit3=w254 The value failed to change bit4=w255 System clock not set bit5=w256 A device is lost bit6=w257 New device detected bit7=w258 Device instance is duplicated bit8=w298 Caution: changing frequency can damage loads bit9=w501 SCP has fixed a memory problem - restored defaults Clear Command The Clear command clears the fault, warning, event, and communication logs. Configure Clear using one of the following values: 1=Fault Log 2=Active Faults 4=Warning Log 8=Active Warnings 16=State Event Log 32=Communication Statistics 64=Statistics 128=User Statistics 255=All 4 503-0251-01-01 Revision A.3

Copyright 2014 Schneider Electric. All Rights Reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. Exclusion for Documentation Unless specifically agreed to in writing, seller (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER S RISK; AND (C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT WWW.SCHNEIDER-ELECTRIC.COM. Document Number: 503-0251-01-01 Revision Number: A.3 Date: June 2014 Contact Information www.schneider-electric.com For country details please contact your local Schneider Electric Sales Representative or visit the Schneider Electric website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page 503-0251-01-01 Revision A.3 5