Operating Instructions OPTISWITCH 5200 C, 5250 C with relay output

Similar documents
Operating Instructions April 2008 SITRANS LVL200S

Operating Instructions April 2008 SITRANS LVL200E

LS 5000 series Vibration Level Switch for liquids

OPTISWITCH 4000 C 5100 C, 5150 C 5200 C, 5250 C

Operating Instruction

Technical Data Sheet. OPTISWITCH 5000 series Vibration Level Switch. for liquids

Technical Data Sheet. OPTISWITCH 3000 series Vibration level switch. for solids

Technical Data Sheet. OPTISWITCH 3000 series Vibration level switch. for solids

Operating Instructions VEGAMET 381

Indication and adjustment. LG Remote Interface Operating Instructions 06/2015

Assembly. 1 Compact version with valve plug 2 Short tube version with cable 3 Compact version with M12 plug 4 Short tube version with M12 plug

Signal conditioning instruments for level switches. Conductive VEGATOR 256C VEGATOR 532 VEGATOR 631. Product Information

Operating Instructions

Operating Instructions SU 600 Ex

Liquipoint T FTW31, FTW32

Liquiphant T FTL20. Technical Information. Level limit switch for liquids

Operating Instructions VEGABAR 17. Process pressure transmitter with metallic measuring cell ma. Document ID: 27636

Indication and Adjustment Product Information VEGADIS 61. Level Switching Pressure

Float Switches with Permanent Magnet For Vertical Installation Model RSM

LS 6600 Technical Datasheet

CombiTemp TFRN/TFRH. Operating instructions. Temperature sensor. Operating Instructions: EN.

Liquipoint T FTW 31, FTW 32 Level limit switch for multiple point detection in conductive liquids

Operating Instructions VEGAWAVE 63 - Relay (DPDT)

Operating Instructions VEGAWAVE 61 - Relay (DPDT)

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

DT1102 V (PS) Fully Configurable Galvanic Isolator. Operating Instructions

Operating Instructions for Level Switch for Liquids. Model: RFS

PI-EX-ME-2NAM/COC-24VDC

PI-EX-ME-2NAM/COC-120VAC

Operating Instructions VEGAVIB 61 - Relay (DPDT)

INSTRUCTION MANUAL. Universal AC Input Switching Power Supply 24 Vdc Output DIN-Rail Models PSD1000, PSD1000F PSD PSD1000F

YT-870 / 875 Series. Rotork YTC Limited VERSION 1.06

PHOENIX CONTACT - 12/2007

Series 3730 Type Electropneumatic Positioner

Series 3730 Electropneumatic Positioner Type

SolConeX extra-low voltage flange socket

InBin-P Pressure switches from 5 Pa Pa

T EN TROVIS Electropneumatic Positioner

3/2 Directional control valves Direct solenoid operated poppet valves Internal thread G 1/2, 1/2 NPT or flanged with NAMUR interface

Material pressure (bar) (Cv (US) kv x 1,2 Seat

21D Allfluid pressure switch, electromechanically actuated

Technical Information Promonitor NRF560

Supplementary instructions. Plug connector ISO for level sensors. Document ID: 30380

English. Operating Manual. Conductive point level switch MLR120. Retain for later reference. Companies / brands of GHM

Operating Instructions (Translation) 3. Safety Information. 1. Description. 2. Explosion Protection. Supply module Type 17-21BB-170x

Magnetic field sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X

INSTRUCTION MANUAL. SIL 3 Relay Output Module DIN-Rail Models D1092S-069, D1092D-069 D1092S D1092D-069

Temperature Measurement SITRANS TS300

Level sensor Stainless steel version Model RLT-1000, for industrial applications

Supplementary instructions. Plug connector Harting HAN 8D. for continuously measuring sensors. Document ID: 30376

FlexBar HRT Pressure Transmitter

INSTRUCTION MANUAL. SIL 3 Switch/Proximity Detector Repeater Relay Output, Termination Board Models D6032S, D6032D

SIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006

External level devices for conductive point level switch

Indicating Digital Transmitter for Differential Pressure and Flow. Media 6 with LCD Media 6 with LED

KROHNE 12/ GR Installation and Operating Instructions BM 500

Inductive dual sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933

Guided Wave Radar SITRANS LG250

Technical Information Liquipoint FTW23

Inductive sensor NI3-EG08K-Y1-H1341

Inductive sensor BI1.5-EG08-Y1-H1341

Supplementary instructions. Plug connector Harting HAN 7D. For point level sensors. Document ID: 34456

Supplementary instructions. Plug connector ISO for continuously measuring sensors. Document ID: 30375

Level measurement. Applications. Special features. Description

Level. Conductive. Level detection. Overview Page 142 VEGAKON series 60 Page 144 EL 1 EL 8 Page 148 Limit switches VEGATOR Page 157

Operating Instructions VEGAVIB 61 - transistor (NPN/PNP)

TFR5. Room or outdoor temperature sensor. Operating instructions for temperature sensor. English page 1...5

Float Switches with Permanent Magnet For Horizontal Installation Model HIF

MANUAL LML-P, LML-S, LML-Ex

Inductive sensor BI1.5-EG08-Y1-H1341

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

Functional safety manual Liquiphant M/S with FEL58 and Nivotester FTL325N

Guided Wave Radar SITRANS LG270

LMP 308. Separable Stainless Steel Probe. Stainless Steel Sensor. accuracy according to IEC 60770: standard: 0.35 % FSO option: 0.25 % FSO / 0.

Inductive sensor For rotary actuators NI4-DSU35TC-2Y1X2/S933

Installation manual plugs and connectors with screw connection (16/32 A)

MAXIMA+ Series Rotary Level Indicator

NIVOSWITCH VIBRATING FORK LEVEL SWITCHES

Operating Manual / IEC. Explosion-Proofed Junction Boxes, Polyester. Wallücker Bahndamm 7 DE Kirchlengern

Operating Instructions Soliswitch FTE20

Operating Instructions VEGABAR 83. Pressure transmitter with metallic measuring cell. Profibus PA. Document ID: 45037

ExBin-D Transducers for ExPro-B... sensors (probes) ExPro-B... Thermostats / humidistats ( C, % rh)

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

OPTISWITCH 6600 C Technical Datasheet

Magnetic float switch For vertical installation Model FLS

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

Inductive sensor Dual sensors with extended temperature range NI4-DSU35TC-2Y1X2/S97

Operating Instructions VEGAFLEX 81. TDR sensor for continuous level and interface measurement of liquids. Two-wire 4 20 ma/hart Rod and cable probe

TECHNICAL INFORMATION Vibracon LVL-A7

MAXIMA + Series ROTARY LEVEL CONTROL

Operating instructions. Standstill monitor A / / 2011

Vane wheel probe BFA25 for flow measurement of gases and liquids with integrated, configurable transducer UFA in Ex-d housing

Product manual plug, sockets and coupler 16 A.- Z0251

Magnetic Field Sensor Magnetic-inductive Proximity Sensor BIM-M12E-Y1X-H1141

Capacitive. Overview 116 VEGACAP series VEGACAP 27, 35, Capacitive VEGACAP

Assembly. max Example: 2-wire connection IH More connection types see section electrical connections. Auxiliary voltage.

Miniaturised pressure sensor Model M-10, standard version Model M-11, version with flush diaphragm

Operating Instructions VEGABAR 82. Pressure transmitter with ceramic measuring cell. Profibus PA. Document ID: 45031

D5090S INSTRUCTION MANUAL. D A SIL 3 Relay Output Module for NE Load. DIN-Rail and Termination Board, Model D5090S

FOR LIQUIDS AND SOLIDS

Transcription:

Operating Instructions OPTISWITCH 5200 C, 5250 C with relay output

Contents Contents 1 About this document 1.1 Function... 4 1.2 Target group... 4 1.3 Symbolism used... 4 2 For your safety 2.1 Authorised personnel... 5 2.2 Appropriate use.... 5 2.3 Warning about misuse... 5 2.4 CE conformity... 5 2.5 SIL conformity... 6 2.6 Safety instructions for Ex areas... 6 3 Product description 3.1 Configuration.... 7 3.2 Principle of operation.... 7 3.3 Operation... 9 3.4 Storage and transport... 9 4 Mounting 4.1 General instructions.... 10 4.2 Mounting instructions.... 13 5 Connecting to voltage supply 5.1 Preparing the connection... 16 5.2 Connection steps.... 16 5.3 Wiring plan, single chamber housing.... 17 6 Set up 6.1 General.... 19 6.2 Adjustment elements... 19 6.3 Function chart... 20 7 Maintenance and fault rectification 7.1 Maintenance... 22 7.2 Rectify faults... 22 7.3 Instrument repair... 23 8 Dismounting 8.1 Dismounting procedure... 24 8.2 Disposal... 24 2 OPTISWITCH 5200 C, 5250 C - with relay output

Contents 9 Supplement 9.1 Technical data.... 25 9.2 Dimensions... 30 OPTISWITCH 5200 C, 5250 C - with relay output 3

About this document 1 About this document 1.1 Function This operating instructions manual has all the information you need for quick setup and safe operation. Please read this manual before you start setup. 1.2 Target group This operating instructions manual is directed to trained, qualified personnel. The contents of this manual should be made available to these personnel and put into practice by them. 1.3 Symbolism used Information, tip, note This symbol indicates helpful additional information. Caution: If this warning is ignored, faults or malfunctions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result. Ex applications This symbol indicates special instructions for Ex applications. l à List The dot set in front indicates a list with no implied sequence. Action This arrow indicates a single action. 1 Sequence Numbers set in front indicate successive steps in a procedure. 4 OPTISWITCH 5200 C, 5250 C - with relay output

For your safety 2 For your safety 2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel authorised by the manufacturer. 2.2 Appropriate use OPTISWITCH 5200 C, 5250 C is a sensor for level detection. Detailed information on the application range of OPTISWITCH 5200 C, 5250 C is available in chapter "Product description". 2.3 Warning about misuse Inappropriate or incorrect use of the instrument can give rise to application-specific hazards, e.g. vessel overfill or damage to system components through incorrect mounting or adjustment. 2.4 General safety instructions OPTISWITCH 5200 C, 5250 C is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and accident prevention rules. 2.5 CE conformity OPTISWITCH 5200 C, 5250 C is in CE conformity with EMC (89/336/EWG), fulfils NAMUR recommendation NE 21 and is in CE conformity with LVD (73/23/EWG). Conformity has been judged according to the following standards: l EMC: - Emission EN 61326/A1: 1998 (class B) - Susceptibility EN 61326: 1997/A1:1998 l LVD: EN 61010-1: 1993 OPTISWITCH 5200 C, 5250 C - with relay output 5

For your safety 2.6 SIL conformity OPTISWITCH 5200 C, 5250 C fulfills the requirements of functional safety according to IEC 61508/IEC 61511. You can find further information in the supplementary instructions manual "Safety Manual - Functional safety (SIL) OPTISWITCH 5XXX". 2.7 Safety instructions for Ex areas Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Exapproved instruments. 6 OPTISWITCH 5200 C, 5250 C - with relay output

Product description 3 Product description 3.1 Configuration Scope of delivery Components The scope of delivery encompasses: l l OPTISWITCH 5200 C, 5250 C level sensor Documentation - this operating instructions manual - Ex specific safety instructions (with Ex versions), if necessary further certificates OPTISWITCH 5200 C, 5250 C consists of the following components: l l l Housing cover Housing with electronics process fitting with tuning fork 1 2 3 Fig. 1: OPTISWITCH 5200 C, 5250 C with plastic housing 1 Housing cover 2 Housing with electronics 3 Process fitting 3.2 Principle of operation Area of application OPTISWITCH 5200 C, 5250 C is a level sensor with tuning fork for level detection. OPTISWITCH 5200 C, 5250 C - with relay output 7

Product description It is designed for industrial use in all areas of process technology and can be used in liquids. Typical applications are overfill and dry run protection. With a tuning fork of only 40 mm length, OPTISWITCH 5200 C, 5250 C can be also mounted, e.g. in pipelines from DN 25. The small tuning fork allows use in vessels, tanks and pipes. Thanks to its simple and robust measuring system, OPTI- SWITCH 5200 C, 5250 C is virtually unaffected by the chemical and physical properties of the liquid. It functions even under difficult conditions such as turbulence, air bubbles, foam generation, buildup, strong external vibration or changing products. Fault monitoring The electronics module of OPTISWITCH 5200 C, 5250 C continuously monitors via frequency evaluation the following criteria: l Strong corrosion or damage on the tuning fork l loss of vibration l Line break to the piezo drive If a malfunction is detected or in case of power failure, the electronics takes on a defined switching condition, i.e. the relay deenergises (safe condition). Physical principle Power supply The tuning fork is piezoelectrically energised and vibrates at its mechanical resonance frequency of approx. 1200 Hz. The piezos are fixed mechanically and are hence not subject to temperature shock limitations. The frequency changes when the tuning fork is covered by the medium. This change is detected by the integrated oscillator and converted into a switching command. OPTISWITCH 5200 C, 5250 C is a compact instrument, i.e. it can be operated without external evaluation system. The integrated electronics evaluates the level signal and outputs a switching signal. With this switching signal, a connected device can be directly activated (e.g. a warning system, a PLC, a pump etc.). The exact range of the power supply is stated in the "Technical data" in the "Supplement". 8 OPTISWITCH 5200 C, 5250 C - with relay output

Product description 3.3 Operation The switching condition of OPTISWITCH 5200 C, 5250 C with plastic housing can be checked when the housing is closed (signal lamp). With the basic setting, products with a density >0.7 g/cm³ (>0.025 lbs/in³) can be detected. The instrument can be adapted if products with lower density should be measured. On the electronics module you will find the following indicating and adjustment elements: l l l signal lamp for indication of the switching condition (green/ red) DIL switch for sensitivity adjustment Mode switch for selection of the switching condition (A/B) 3.4 Storage and transport Packaging Storage and transport temperature Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN 55439. The packaging of standard instruments consists of environment-friendly, recyclable cardboard. In addition, the sensor is provided with a protective cover of ABS. For special versions PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies. l Storage and transport temperature see "Supplement - Technical data - Ambient conditions" l Relative humidity 20 85 % OPTISWITCH 5200 C, 5250 C - with relay output 9

Mounting 4 Mounting 4.1 General instructions Switching point In general, OPTISWITCH 5200 C, 5250 C can be mounted in any position. The instrument must be mounted in such a way that the tuning fork is at the height of the requested switching point. The tuning fork has lateral markings (notches), marking the switching point with vertical mounting. The switching point refers to water with the basic setting of the sensitivity switch >=0.7 g/cm³ (>=0.025 lbs/in³). When mounting OPTISWITCH 5200 C, 5250 C, make sure that this marking is at the height of the requested switching point. Keep in mind that the switching point of the instrument is shifted if the medium has a density other than water - water =1 g/cm³ (=0.036 lbs/in³). For products <0.7 g/cm³ (<0.025 lbs/in³) and >0.5 g/cm³ (>0.018 lbs/in³) the density switch must be set to >=0.5 g/cm³. 2 1 3 4 Fig. 2: Vertical mounting 1 Switching point approx. 13 mm (approx. 0.51 in) 2 Switching point with lower density 3 Switching point with higher density 4 Switching point approx. 27 mm (approx. 1.06 in) 10 OPTISWITCH 5200 C, 5250 C - with relay output

Mounting 1 Fig. 3: Horizontal mounting 1 Switching point 1 2 Fig. 4: Horizontal mounting (recommended installation location - particularly for adhesive products) 1 Switching point 2 Marking with screwed version on top - with flange versions directed to the flange holes With flange versions, the fork is directed to the flange holes in the following way. Fig. 5: Fork position with flange versions Moisture Use the recommended cables (see chapter "Connecting to power supply") and tighten the cable gland. You can give your OPTISWITCH 5200 C, 5250 C additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and OPTISWITCH 5200 C, 5250 C - with relay output 11

Mounting condensation water can thus drain off. This applies mainly to mounting outdoors, in areas where moisture is expected (e.g. by cleaning processes) or on cooled or heated vessels. Fig. 6: Measures against moisture penetration Transport Pressure/Vacuum Handling Do not hold OPTISWITCH 5200 C, 5250 C on the tuning fork. Particularly with flange or tube versions, the tuning fork can be damaged by the instrument weight. Transport coated instruments very carefully and avoid touching the tuning fork. Remove the protective cover just before mounting. The process fitting must be sealed if there is gauge or low pressure in the vessel. Before use, check if the seal material is resistant against the measured product and the process temperature. The max. permissible pressure is stated in the "Technical data" in the "Supplement" or on the type label of the sensor. The vibrating level switch is a measuring instrument and must be treated accordingly. Bending the vibrating element will destroy the instrument. Warning: The housing must not be used to screw in the instrument! Applying tightening force on the housing can damage its internal mechanical parts. To screw in, use the hexagon above the thread. 12 OPTISWITCH 5200 C, 5250 C - with relay output

Mounting 4.2 Mounting instructions Welded socket OPTISWITCH 5200 C, 5250 C has a defined thread starting point. This means that every OPTISWITCH 5200 C, 5250 C is in the same fork position after being screwed in. Remove therefore the supplied seal from the thread of OPTISWITCH 5200 C, 5250 C. This seal is not required when using a welded socket with O-ring in front. Keep in mind that this welded socket is not suitable for coated instrument versions. Screw OPTISWITCH 5200 C, 5250 C completely into the welded socket. The later position can be determined already before welding. Mark the appropriate position of the welded socket. Before welding, unscrew OPTISWITCH 5200 C, 5250 C and remove the rubber ring from the welded socket. The welded socket has a marking (notch). Weld the socket with the notch facing upward, or in case of pipelines, aligned with the direction of flow. 1 Fig. 7: Marking on the welded socket 1 Marking Adhesive products In case of horizontal mounting in adhesive and viscous products, the surfaces of the tuning fork should be vertical in order to reduce buildup on the tuning fork. On the screwed version you will find a marking on the hexagon. With this, you can check the position of the tuning fork when screwing it in. When the hexagon touches the seal, the thread can still be turned by approx. half a turn. This is sufficient to reach the recommended installation position. With flange versions, the fork is directed to the flange holes. OPTISWITCH 5200 C, 5250 C - with relay output 13

Mounting When used in adhesive and viscous products, the tuning fork should protrude into the vessel to avoid buildup. For that reason, sockets for flanges and mounting bosses should be avoided when mounting horizontally. Inflowing medium If OPTISWITCH 5200 C, 5250 C is mounted in the filling stream, unwanted switching signals may be generated. Mount OPTISWITCH 5200 C, 5250 C at a location in the vessel where no disturbing influence from e.g. filling openings, agitators etc. can occur. This applies particularly to instrument types with long extension tube. Fig. 8: Inflowing medium Flows To minimise flow resistance caused by the tuning fork, OPTISWITCH 5200 C, 5250 C should be mounted in such a way that the surfaces of the blades are parallel to the product movement. Agitators Due to agitators, vibrations or similar, the level switch can be subjected to strong lateral forces. For this reason, do not use an overly long extension tube for OPTISWITCH 5200 C, 5250 C, but check if you can mount an OPTISWITCH 5100 C, 5150 C level switch on the side of the vessel in horizontal position. Extreme vibration caused by the process or the equipment, e. g. agitators or turbulence in the vessel can cause the extension tube of OPTISWITCH 5200 C, 5250 C to vibrate in resonance. This leads to increased stress on the upper weld joint. Should 14 OPTISWITCH 5200 C, 5250 C - with relay output

Mounting a longer tube version be necessary, you can provide a suitable support or guy directly above the tuning fork to secure the extension tube. This measure applies particularly to applications in Ex areas category 1G or WHG. Make sure that the tube is not bent by this measure. Fig. 9: Lateral straining of OPTISWITCH 5200 C, 5250 C Enamel coating Instruments with enamel coating should be treated very carefully and shocks should be avoided. Unpack OPTI- SWITCH 5200 C, 5250 C directly before installation. Insert OPTISWITCH 5200 C, 5250 C carefully into the vessel opening and avoid touching any sharp vessel parts. OPTISWITCH 5200 C, 5250 C - with relay output 15

Connecting to voltage supply 5 Connecting to voltage supply 5.1 Preparing the connection Note safety instructions Take note of safety instructions for Ex applications Select power supply Selecting the connection cable Generally not the following safety instructions: l Connect only in the complete absence of line voltage In hazardous areas you should take note of the appropriate regulations, conformity and type approval certificates of the sensors and power supply units. Connect the power supply according to the following diagrams. Oscillator SWE60R is designed in protection class 1. To maintain this protection class, it is absolutely necessary that the ground conductor be connected to the internal ground terminal. Take note of the general installation regulations. As a rule, connect OPTISWITCH 5200 C, 5250 C to vessel ground (PA), or in case of plastic vessels, to the next ground potential. On the side of the housing there is a ground terminal between the cable entries. This connection serves to drain off electrostatic charges. In Ex applications, the installation regulations for hazardous areas must be given priority. The data for power supply are stated in the "Technical data" in the "Supplement". OPTISWITCH 5200 C, 5250 C is connected with standard cable with round cross-section. An outer cable diameter of 5 9 mm (0.2 0.35 in) ensures the seal effect of the cable entry. If cable with a different diameter or wire cross section is used, exchange the seal or use an appropriate cable connection. In hazardous areas, only use approved cable connections for OPTISWITCH 5200 C, 5250 C. Select connection cable for Ex applications Take note of the corresponding installation regulations for Ex applications. 5.2 Connection steps With Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present. Proceed as follows: 16 OPTISWITCH 5200 C, 5250 C - with relay output

Connecting to voltage supply 1 Unscrew the housing cover 2 Loosen compression nut of the cable entry 3 Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) insulation from the ends of the individual wires 4 Insert the cable into the sensor through the cable entry 5 Open the terminals with a screwdriver 6 Insert the wire ends into the open terminals according to the wiring plan 7 Tighten the terminals with a screwdriver 8 Check the hold of the wires in the terminals by lightly pulling on them 9 Tighten the compression nut of the cable entry, the seal ring must completely encircle the cable 10 Screw the housing cover back on The electrical connection is hence finished. 5.3 Wiring plan, single chamber housing The following illustrations apply to the non-ex as well as to the EEx d version. Housing overview 4 4 4 1 2 3 Fig. 10: Material versions, single chamber housing 1 Plastic (not with EEx d) 2 Aluminium 3 Stainless steel (not with EEx d) 4 Filter element for pressure compensation (not with EEx d) OPTISWITCH 5200 C, 5250 C - with relay output 17

Connecting to voltage supply Electronics and connection compartment SW E60R 3 4 5 6 7 8 A 20-72V DC 20-253V AC + B L N 0,5 g / cm 3 0,7 g / cm 3 1 2 5 1 2 3 4 5 6 7 8 3 4 Fig. 11: Electronics and connection compartment, single chamber housing 1 Control lamp 2 DIL switch for mode adjustment 3 DIL switch for switching point adaptation 4 Ground terminal 5 Screwed terminals Wiring plan We recommend connecting OPTISWITCH 5200 C, 5250 C in such a way that the switching circuit is open when there is a level signal, line break or failure (safe condition). The relays are always shown in non-operative condition. + L1 - N 1 2 3 4 5 6 7 8 1 2 3 Fig. 12: Wiring plan, single chamber housing 1 Relay output 2 Relay output 3 Voltage supply 18 OPTISWITCH 5200 C, 5250 C - with relay output

Set up 6 Set up 6.1 General The numbers in brackets refer to the following illustrations. Function/Configuration The switching condition of the electronics can be checked on the plastic housing with closed housing cover (control lamp). In the basic setting, products with a density >0.7 g/cm³ (>0.025 lbs/in³) can be detected. For products with lower density, the switch must be set to >0.5 g/cm³ (>0.018 lbs/in³). On the electronics module you will find the following indicating and adjustment elements: l Signal lamp (1) l DIL switch for mode adjustment - A/B (2) l DIL switch for sensitivity adjustment (3) Note: For test purposes, immerse the tuning fork of OPTISWITCH 5200 C, 5250 C always in liquids. Do not test the function of OPTISWITCH 5200 C, 5250 C with the hand. This can damage the sensor. 6.2 Adjustment elements 1 2 3 4 5 6 7 8 1 2 3 Fig. 13: Oscillator SWE60R - Relay output 1 Signal lamp (LED) 2 DIL switch for mode adjustment 3 DIL switch for sensitivity adjustment OPTISWITCH 5200 C, 5250 C - with relay output 19

Set up Signal lamp (1) Mode adjustment (2) Sensitivity adjustment (3) Control lamp (LED) for indication of the switching condition l green = relay energized l red = relay deenergized l red (flashing) = failure With the mode adjustment (A/B) you can change the switching condition of the relay. You can set the required mode acc. to the "Function chart" (A - max. detection or overfill protection, B - min. detection or dry run protection). With this DIL switch (3) you can set the switching point to liquids having a density between 0.5 and 0.7 g/cm³ (0.018 and 0.025 lbs/in³). With the basic setting, liquids with a density of >0.7 g/cm³ (>0.025 lbs/in³) can be detected. In liquids with lower density, you must set the switch to >0.5 g/cm³ (>0.018 lbs/in³). The specifications for the position of the switching point relate to water - density value 1.0 g/cm³ (0.036 lbs/in³). In products with a different density, the switching point will shift in the direction of the housing or tuning fork end depending on the density and type of installation. 6.3 Function chart The following chart provides an overview of the switching conditions depending on the adjusted mode and level. Mode A Overfill protection Level Switching status Control lamp 3 4 5 (6) (7) (8) Mode A Overfill protection Mode B Dry run protection Relay energized 3 4 5 (6) (7) (8) Relay deenergized 3 4 5 (6) (7) (8) Green red Mode B Dry run protection Relay energized 3 4 (6) (7) 5 (8) Relay deenergized Green 20 OPTISWITCH 5200 C, 5250 C - with relay output red

Set up Failure of the supply voltage (mode A/B) Level Switching status Control lamp any 3 4 5 (6) (7) (8) Relay deenergized Failure any 3 4 (6) (7) 5 (8) Relay deenergized flashes red OPTISWITCH 5200 C, 5250 C - with relay output 21

Maintenance and fault rectification 7 Maintenance and fault rectification 7.1 Maintenance When used as directed in normal operation, OPTISWITCH 5200 C, 5250 C is completely maintenance free. 7.2 Rectify faults Causes of malfunction Fault rectification OPTISWITCH 5200 C, 5250 C offers maximum reliability. Nevertheless faults can occur during operation. These may be caused by the following, e.g.: l Sensor l Process l Power supply l Signal processing The first measure to be taken is to check the output signal. In many cases, the causes can be determined this way and the faults rectified. Checking the switching signal? OPTISWITCH 5200 C, 5250 C signals "covered" when the vibrating element is not submerged (overfill protection)? OPTISWITCH 5200 C, 5250 C signals "uncovered" when the vibrating element is submerged (dry run protection) l Supply voltage too low à Check the power supply l Electronics defective à Press the mode switch (min./max.). If the instrument then changes the mode, the instrument may be mechanically damaged. Should the switching function in the correct mode still be faulty, return the instrument for repair. à Push the mode switch. If the instrument then does not change the mode, the oscillator may be defective. Exchange the oscillator. à Check if there is buildup on the vibrating element, and if so, remove it. l Unfavourable installation location à Mount the instrument at a location in the vessel where no dead zones or air bubbles can form. 22 OPTISWITCH 5200 C, 5250 C - with relay output

Maintenance and fault rectification l Wrong mode selected à Set the correct mode on the mode switch (max.: overfill protection; min.: dry run protection). Wiring should be carried out according to the quiescent current principle.? Signal lamp flashes red l Electronics has detected a failure à Exchange instrument or return instrument for repair? The signal lamp flashes alternately red and green l instrument defective à Exchange instrument or return instrument for repair 7.3 Instrument repair If a repair is necessary, please proceed as follows: You can download a return form from our website http://www. krohne-mar.com/fileadmin/media-lounge/pdf-download/ Specimen_e.pdf. By doing this you help us carry out the repair quickly and without having to call back for needed information. l l l Print and fill out one form per instrument Clean the instrument and pack it damage-proof Attach the completed form and possibly also a safety data sheet to the instrument OPTISWITCH 5200 C, 5250 C - with relay output 23

Dismounting 8 Dismounting 8.1 Dismounting procedure Warning: Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order. With Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present. 8.2 Disposal The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronic modules to be easily separable. WEEE directive 2002/96/EG This instrument is not subject to the WEEE directive 2002/96/ EG and the respective national laws (in Germany, e.g. ElektroG). Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see "Technical data" If you cannot dispose of the instrument properly, please contact us about disposal methods or return. 24 OPTISWITCH 5200 C, 5250 C - with relay output

Supplement 9 Supplement 9.1 Technical data General data Material 316L corresponds to 1.4404 or 1.4435 Materials, wetted parts - Process fitting - thread 316L, Hastelloy C4 (2.4602) - Process fitting - flange 316L, 316L with Hastelloy C4 plated, enamelled steel, 316L with ECTFE coated, 316L with PFA coated - Process seal Klingersil C-4400 - Tuning fork 316L, Hastelloy C4 (2.4610) - Extension tube ø 21.3 mm (0.84 in) 316L, Hastelloy C4 (2.4610), Hastelloy C4 (2.4610) enamelled, 316L with ECTFE coating, 316L with PFA coating Materials, non-wetted parts - Housing Plastic PBT (Polyester), Alu die-casting powder-coated, 316L - Seal ring between housing and housing cover - waveguide in the housing cover PMMA (Makrolon) - Ground terminal 316L - Temperature adapter (optional) 316L - Gas-tight leadthrough (optional) 316L/glass NBR (stainless steel housing), silicone (Alu/ plastic housing) Lengths - 316L, Hastelloy C4 (2.4610) 80 6000 mm (3 236 in) - Hastelloy C4 (2.4610) enamelled 80 1500 mm (3 59 in) - 316L, ECTFE coated 80 3000 mm (3 118 in) - 316L, PFA coated 80 3000 mm (3 118 in) Weights - Plastic housing 760 g (27 oz) - Aluminium housing 1170 g (41 oz) - Stainless steel housing 1530 g (54 oz) - Tube extension approx. 110 g/m (1.2 oz/ft) OPTISWITCH 5200 C, 5250 C - with relay output 25

Supplement Layer thickness - Enamel approx. 0.8 mm (0.03 in) - ECTFE approx. 0.5 mm (approx. 0.02 in) - PFA approx. 0.5 mm (approx. 0.02 in) Surface quality - Standard R a approx. 3 µm (approx. 1.18-4 in) - Hygienic version 3A (OPTISWITCH 5250 C) R a <0.8 µm (<3.15-5 in) Process fittings - Thread G¾ A, ¾ NPT, G1 A, 1 NPT - Flanges DIN from DN 25, ANSI from 1" - hygienic fittings Bolting DN 40 PN 40, Tri-Clamp 1", Tri-Clamp 1½" PN 10, conus DN 25 PN 40, Tuchenhagen Varivent DN 50 PN 10 High voltage test (enamel) max. 5 KV Gas-tight leadthrough (optional) - leakage rate <10-6 mbar l/s - pressure resistance PN 64 - hygienic fittings Bolting DN 40 PN 40, Tri-Clamp 1", Tri-Clamp 1½" PN 10, conus DN 25 PN 40, Tuchenhagen Varivent DN 50 PN 10 Output variable Output relay output (DPDT), 2 floating spdts Turn-on voltage - min. 10 mv - max. 253 VAC, 253 VDC Switching current - min. 10 µa - max. 3 AAC, 1 ADC 26 OPTISWITCH 5200 C, 5250 C - with relay output

Supplement Breaking capacity - min. 50 mw - max. 750 VA AC, 54 WDC If inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be permanently damaged. The contact is then no longer suitable for switching low-level signal circuits. Contact material (relay contacts) AgNi oragsno and Au plated Modes (adjustable) - A Max. detection or overflow/overfill protection - B Min. detection or dry run protection Measuring accuracy Hysteresis Integration time Frequency Ambient conditions Ambient temperature on the housing Storage and transport temperature approx. 2 mm (0.08 in) with vertical installation approx. 500 ms approx. 1200 Hz -40 +70 C (-40 +158 F) -40 +80 C (-40 +176 F) Process conditions Parameter Process pressure OPTISWITCH 5200 C, 5250 C of 316L/ Hastelloy C4 (2.4610) Process temperature (thread or flange temperature) with temperature adapter (option) - OPTISWITCH 5200 C, 5250 C of 316L/Hastelloy C4 - OPTISWITCH 5200 C, 5250 C enamelled Limit level of liquids -1 64 bar (-14.5 938 psi) depending on the process fitting, e.g. flange -50 +150 C (-58 +302 F) -50 +250 C (-58 +482 F) -50 +200 C (-58 +392 F) OPTISWITCH 5200 C, 5250 C - with relay output 27

Supplement - OPTISWITCH 5200 C, 5250 C with ECTFE coating - OPTISWITCH 5200 C, 5250 C with PFA coating -50 +150 C (-58 +302 F) -50 +150 C (-58 +302 F) 2 70 C (158 F) 3 40 C (104 F) 0 C (32 F) -50 C (-58 F) -40 C (-40 F) 50 C (122 F) 100 C (212 F) 150 C (302 F) 200 C (392 F) 1 250 C (482 F) Fig. 14: Ambient temperature - Product temperature 1 Product temperature 2 Ambient temperature 3 Temperature range with temperature adapter Viscosity - dynamic Density 0.1 10,000 mpa s(requirement: with density 1) 0.7 2.5 g/cm³ (0.025 0.09 lbs/in³); 0.5 2.5 g/cm³ (0.018 0.09 lbs/in³) by switching over Electromechanical data Cable entry/plug (dependent on the version) - Single chamber housing l 1x cable entry M20x1.5 (cable-ø 5 9 mm), 1x blind stopper M20x1.5, attached 1x cable entry M20x1.5 or: l 1x cable entry ½ NPT, 1x blind stopper ½ NPT, 1x cable entry ½ NPT or: Screw terminals l 1x plug M12x1, 1x blind stopper M20x1.5 for wire cross-section up to 1.5 mm² (0.0023 in²) 28 OPTISWITCH 5200 C, 5250 C - with relay output

Supplement Adjustment elements Mode switch - A Max. detection or overflow/overfill protection - B Min. detection or dry run protection Density switch - 0.5 0.5 2.5 g/cm³ (0.018 0.9 oz/in³) - 0.7 0.7 2.5 g/cm³ (0.025 0.9 oz/in³) Voltage supply Supply voltage Power consumption 20 253 VAC, 50/60 Hz, 20 72 VDC(at U >60 VDC, the ambient temperature can be max. 50 C/122 F) 1 8 VA (AC), approx. 1.3 W (DC) Electrical protective measures Protection IP 66/IP 67 Overvoltage category III Protection class I Approvals 1) ATEX II 1/2G, 2G EExd d IIC T6 2) Overfill protection acc. to WHG Ship approvals 1) Deviating data in Ex applications: see separate safety instructions. 2) Only with Aluminium housing. OPTISWITCH 5200 C, 5250 C - with relay output 29

Supplement 9.2 Dimensions OPTISWITCH 5200 C, 5250 C ~ 69mm (2 23/ 32") ø 77mm (3 1/ 32") ~ 69mm (2 23/ 32") ø 77mm (3 1/ 32") ~ 116mm (4 9/ 16") ø 84mm (3 5/ 16") 112mm (4 13/32") 117mm (4 39/64") 114mm (4 31/64") ½ M20x1,5/ ½ NPT M20x1,5/ ½ NPT M20x1,5 1 2 3 Fig. 15: Housing versions 1 Plastic housing 2 Stainless steel housing 3 Aluminium housing 30 OPTISWITCH 5200 C, 5250 C - with relay output

Supplement OPTISWITCH 5200 C, 5250 C 18,5mm (47/64") 32 (G3/ 4 A, 3/ 4 "NPT) 41 (G1A, 1"NPT) G3/ 4 A, 3/ 4 "NPT G1A, 1"NPT 36mm (1 27/64") 57mm (2 1/4") L 1 2 3 50mm (1 31/32") L L L L ø33,7mm (1 21/ 64 ") 19mm (3/4") 34mm (1 11/32") 6 175mm (6 57/64") 7 4 5 Fig. 16: OPTISWITCH 5200 C, 5250 C, threaded version 1 Thread 2 Tri-Clamp 3 Cone DN 25 4 Bolting DN 40 5 Flange 6 Gas-tight leadthrough 7 Temperature adapter L = Sensor length, see "Technical data" OPTISWITCH 5200 C, 5250 C - with relay output 31

Supplement 32 OPTISWITCH 5200 C, 5250 C - with relay output

Supplement OPTISWITCH 5200 C, 5250 C - with relay output 33

Supplement 34 OPTISWITCH 5200 C, 5250 C - with relay output

Supplement OPTISWITCH 5200 C, 5250 C - with relay output 35

Subject to change without notice