Real Time Digital Simulator Testing of an On Line Integrated Stability Control System

Similar documents
Revised Generation Interconnection Impact Study Report. For. Queue Position 31 ( Interconnection Customer )

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online):

Advanced SIPS using PMU and SCADA data

HVDC Control and Protection Testing Using the RTDS Simulator

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI EE-2401 POWER SYSTEM OPERATION AND CONTROL UNIT-III REACTIVE POWER VOLTAGE CONTROL

Small Generator Interconnection System Impact Study Report. Completed For Q0047

Power System Stabilization Solutions in North America and Future Outlook

Generator Interconnection Impact Study Report Pamlico County, NC 200 MW Wind Farm Queue #281

RTDS Simulation and Testing of a Remedial Action Scheme at Southern California Edison

FACTS and HVDC for Grid Connection of Large Wind Farms

FURNAS Strategy Regarding Real-Time Tests: A Practical Case Campos Static VAr Compensator

LAB1 INTRODUCTION TO PSS/E EE461: POWER SYSTEMS COLORADO STATE UNIVERSITY

Transient Stability Improvement of Long Transmission Line System by Using SVC

POWER SYSTEM SECURITY CONCEPTS

Interconnection Feasibility Study Report GIP-IR377-FEAS-R1

Flexible High-Speed Load Shedding Using a Crosspoint Switch

Reliability Standard Audit Worksheet 1

Final Report. Mini Project TET Group nr 7 - Project nr 4. Students: Hans Lavoll Halvorson, NTNU

Distribution Static Var Compensators and Static Synchronous Compensators for Suppressing Voltage Fluctuation

Approval...6. Current Revision...7. Introduction... 8 About PJM Manuals... 8 About This Manual... 8 Using This Manual...9

Enhancing the Grid Compliance of Wind Farms by Means of Hybrid SVC

Requirements for Data for Power System Modeling and Analysis (MOD-032-1) Arizona Public Service Company

SMUD Model Data Requirements & Reporting Procedures MOD VERSION 1.2

Study of Transient Stability Improvement of IEEE 9-Bus System by using SVC

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s)

Power System Network Simulator (PSNsim)

Hybrid STATCOM / SVC Workgroup 15 th May 2014

Mehr Spannungsqualität im Netz mit SVC PLUS. Improvement in Voltage Quality for Power Systems with SVC PLUS

BC HYDRO REAL TIME OPERATIONS SYSTEM OPERATING ORDER 7T - 50

Concept of Automation in Management of Electric Power Systems Richard Joseph, Nerey Mvungi

USE CASE 14 CONTROLLED ISLANDING

Supplemental Information

PROTECTION, AUTOMATION & CONTROL

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s)

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Christian PAYERL, Poznan, 20 th May, 2009 ABB FACTS Grid connection of Wind Farms. ABB Group May 22, 2009 Slide 1

Demonstration Test Bed for Advanced Control Systems

Power System Enterprise Solution

WECC Criterion MOD-(11 and 13)-WECC-CRT-1.1

DRAFT Reliability Guideline: Modeling Distributed Energy Resources in Dynamic Load Models

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

PG&E Transmission Interconnection Handbook

Synchrophasor-Based Monitoring, Analysis, and Control

HIGH LEVEL REQUIREMENTS OF FAST SIMULATION AND MODELLING SUITE OF TOOLS FOR FUTURE SELF-HEALING DISTRIBUTION POWER SYSTEM

Utility Interconnection. Highlights of the New Fast Track Process Proposed by FERC and Changes to IEEE 1547

Lecture 5 Substation Automation Systems. Course map

Tutorials. Tutorial: Creating a New Case Page 1 of 13

Haidar Samet, and Mohammad Amin Jarrahi School of Electrical and Computer Engineering Shiraz University Shiraz, Iran

SCADA Training - T&D Automation

Requests for Clarifications And Responses Order No. 754 Data Request The Study of Single Point of Failure

AUTOMATION OF POWER DISTRIBUTION USING SCADA

Medium Voltage Metal-Enclosed Power Capacitor Banks

Medium Voltage Metal-Enclosed Harmonic Filter Systems

Modeling and Simulation of Static VAR Compensator Controller for Improvement of Voltage Level in Transmission Lines

ENGINEERING AND SERVICES FIRM THAT SPECIALIZES IN HYDROELECTRIC POWER AND CONTROL SYSTEM DESIGN, OUR TEAM OF PROFESSIONALS HAVE WORKED TOGETHER

1 Description of Methodology for Volt / Var Optimization

Main Components of a Static Var Compensator (SVC)

Introduction to new ABB STATCOM portfolio Power Grid Integration FACTS

Using WECC Composite Load Model and PowerWorld Time Step Simulation Tool. Eleanor Ewry

Feasibility Study on Load Flow and Short Circuit Project

Evolution of Control for the Power Grid

ISO New England Data Modeling Requirements

ABB static var compensator stabilizes Namibian grid voltage

This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective.

High and Medium Voltage Substation Design, Testing and Maintenance. KSA, Jeddah, Holiday Inn Jeddah Gateway Hotel.

empowering power system engineers

NYPA FACTS CSC System

AUAS SVC, PERFORMANCE VERIFICATION BY RTDS AND FIELD TESTS. S. Boshoff C. van Dyk L Becker M Halonen, S Rudin, J Lidholm Dr T Maguire

Your Power Grid Your Conditions

ELECTRICAL, INSTRUMENTATION & CONTROL SYSTEMS

Generation, Transmission, and End User Facilities

Small Generator Interconnection Facilities Study Report. Completed for Q0314 ( Interconnection Customer ) A Qualified Facility

NERC Event Analysis Update Webinar. Hassan Hamdar Chair, Event Analysis Subcommittee October 20, 2016

Substation Automation Products. Transformer protection RET670/650 Relion 670 and 650 series

ONLINE CLOSED-LOOP OPTIMIZATION OF DISTRIBUTION NETWORKS

Static Var Compensator: Effect of Fuzzy Controller and Changing Membership Functions in its operation

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

JEA. Facility Connection Requirements

Substation SCADA Monitoring

Power System Studies. The Power of Trust. The Future of Energy.

Wind Farm Volt/VAR Control Using a Real-Time Automation Controller

International Journal of Scientific & Engineering Research Volume 4, Issue 2, February ISSN

Transient Stability Improvement in Transmission System Using SVC with fuzzy logic Control

Lecture 6 Substation Automation Systems

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

A guide on PowerWorld Simulator ver. 12.0

SCADA and Central Applications An introduction

A Svc Light Based Technique for Power Quality Improvement for Grid Connected Wind Energy System

RTDS Training course

IX SIMPÓSIO DE ESPECIALISTAS EM PLANEJAMENTO DA OPERAÇÃO E EXPANSÃO ELÉTRICA

Real-time Power System Operation. Energy Management Systems. Introduction

The Efficient Way. SVC PLUS Innovation meets experience. Answers for energy.

Testing of Real Time Power System Control Software

Sacramen Sacr t amen o t Municipal Utility Dis t Dis rict t SMUD May Ma 10,

SVC static var compensator

Dispatcher Training Simulator (DTS) JOB AIDE

IMS INTERFACE MARKET PROCEDURE NETWORK OPERATORS AND AEMO

Grid Interconnection of Renewable Generation

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

Blackstart Hardware-in-the-loop Relay Testing Platform

Transcription:

Real Time Digital Simulator Testing of an On Line Integrated Stability Control System R.P. Wierckx, M. Kawasaki, N. Saito, K. Anzai, S.C. Verma Abstract The paper describes the testing of an on line integrated stability control system that is to be used to maximize the total power transfer capability of an existing transmission corridor in Japan. The prototype controller which includes the control algorithm of the integrated stability control system is interfaced to a real time digital simulator for testing. I. INTRODUCTION A 2380 MW thermal power plant located approximately 300 km from the interconnection into the main power grid is planned for the Chubu Electric Power System in Japan. Existing transmission facilities will be used to transfer the power from the generating plant into the grid. In an effort to maximize the total transfer capability of the existing lines and yet maintain security of the interconnection, a 450 MVA STATCOM and a special protection system (SPS) will be included. The SPS includes an on line transient stability algorithm, details of which are included in [1][2]. The SPS is implemented using a central controller which communicates with terminal control equipment installed in remote substations. The SPS issues control commands to the power system elements under its control. The terminal control equipment also monitors local conditions and provides those measurements back to the central controller. By installing the SPS and a 450 MVAr (3 x 150 MVAr units) STATCOM, it is expected that the total transfer capability of the twin circuit 275 kv line used to transfer the power from the new generation plant can be almost doubled. Due to the complex nature of the controller and the number of system elements under its control, testing of the SPS was done by interconnecting the prototype controller of the SPS to an RTDSt real time digital simulator. The RTDS was used to model the new thermal power plant, as well as, the power system network between the plant and the grid. The interconnection between the controller and simulator is shown in Figure 1 and details of the power system modeled on the simulator are shown in Figure 2. II. DIITAL SIMULATION IN REAL TIME Digital power system simulators capable of sustained real time operation may be used to test physical control and protection equipment. Digital simulators such as the RTDS use the electromagnetic transients (EMT) algorithm with time steps in the range of 50 micro seconds. Using parallel processing techniques permits detailed representation of significant portions of the power system. Interfacing the simulator with external control and protection equipment, which controls or protects components located physically close to the device, is normally accomplished using digital to analog converters and digital input and output ports available on the simulator. The prototype control equipment uses network based packet communication to send and receive data. DNP3 is one of the communication protocols supported by the prototype controller. DNP3 is also supported by the RTDS, and as such, the DNP3 protocol was used for the communication medium between the RTDS and the prototype controller during the testing. A protocol converter board, referred to as the TNET, is available with the RTDS to handle the sending and receiving of data over a LAN connection using the DNP3 protocol. Figure 1 shows the arrangement of the hardware required to implement the LAN communications using DNP3 protocol between the simulator and the external control equipment. Measured signals from the power system are sent from processor cards on the RTDS to the communications card via a fiber connection. Firmware on the TNET card forms the DNP3 packets and sends it over the LAN. Data coming from the controller is received by 1

COMMUNICATION INTERFACE USIN DNP3 OVER LAN LAN Switch LAN LAN simulator LAN communication card fiber controller processor card 1 of 20 installed Figure 1: Communication between the Simulator and Controller the TNET card which then extracts information from the incoming packets and sends the data to the processor card. III. SYSTEM MODEL DETAILS The general structure of the power system representation used to test the SPS algorithm is shown in Figure 2. A simulator comprising 20 processor cards (40 processors) installed over four racks in two cubicles was required to represent the network and its components. Detailed representation of the generator plant including models of 12 generators each with governor/turbine, AVR and stabilizer functions was included in the model. Models of the over and under excitation limiters (OEL, UEL) were also included for each generator. Four groups of three generators were connected to the transmission grid via a three winding transformer model. Individual generators could be tripped via a unit connection breaker included as part of the power system model. Representation of loads was done using a dynamic load model where the loads are characterized according to the types of loads (eg. residential, industrial) found in the actual system. The amount of real and reactive load at each load location can be changed dynamically while the simulation is running. Data collected from the real system were used to vary the dynamic load model while the simulation was running so that realistic load cycles were represented. COM- TRADE compliant files contained the recorded data used as input to the load models. Elements of the power system which were under the control of the controller included Transformer taps breaker operation switching of shunt reactors switching of shunt capacitors generator terminal voltage control (AVR) generator shedding Signals required as input to the controller include transmission Line P,Q generator P,Q generator terminal Voltage 2

sinatosi tosisina tosisiho joetusen 500 kv system nankan sinakan SVC sinachu sinasaku matsubun 3 x STATCOM 2 or 3 winding transformer with on load tap changer switched reactor and capacitor banks (up to 12 banks) generator including governor, turbine, exciter and stabilizer twin circuit travelling wave transmission line Figure 2: Structure of the Power System Model STATCOM Q substation Bus Voltages transformer tap positions breaker status All of the above signals are sent from the simulator to the controller using the DNP3 protocol over the LAN connection. Named signals representing those that need to be communicated over the DNP3 link are stored in a file accessed by the DNP3 component allocated on the simulator. In all 808 signals are exchanged between the RTDS and the special protection system, 164 Binary Status Signals 512 Binary Control Signals 132 Analog Status Signals IV. RUNNIN THE SYSTEM MODEL Simulation runs are started from a pre determined load flow condition, or with the system or portions of the system in a shutdown state. In order to test the full functionality of the SPS, the new generation plant was started in shutdown mode and brought online as the system loads increased. Simulation runs lasting an hour or more were run so that the response of the con- 3

Figure 3: Operator s Console view trol system to the changing generation and loading conditions could be observed. Large voltage fluctuations can occur in response to significant load changes when the power is being transferred over long transmission lines. In order to control the voltage fluctuations, the SPS monitors all of the associated substation voltages and determines which of the 45 shunt capacitor and 20 shunt reactor branches should be switched in or out. Set points for the generator s voltage regulators are also adjusted based on system conditions. System quantities such as bus voltages, power flows and the state of controlled elements are monitored using the the simulator s operator s console (Figure 3). Both directly monitored quantities, as well as, computed quantities such as positive sequence values are available. Visual and audio cues are provided from the operator s console to indicate when the controller initiates a control change. Over or under voltage conditions in a particular area of the system are indicated by changing the color of the icon representing the bus so that the operators can more easily understand system conditions and corresponding control actions. Two instances of the operator s console were created, one used for direct monitoring and interaction with the simulation and the second to record events for later evaluation. In order to test the response of the SPS to severe disturbances, various fault conditions with associated breaker operation sequences were simulated. Faults at various locations in the system with varying fault types and point on wave inception points were applied. The large number of simulation runs required to thoroughly test the SPS were managed using the simulator s script file feature. Script files contain C code which control sequences of events such as fault application and removal, breaker operation etc. FOR and WHILE loops can be placed around the control sequences to cycle through a large variety of conditions. Script files may include instructions to capture, record and analyze data produced by the simulation. In this way the simulator may be set to operate in an automated mode and the operator alerted to results that fall outside of a pre defined set of criteria. Such simulation cases can then be re run for closer inspection. Scripts were also used to initialize the power system model to the many different power flow conditions under which the SPS was tested. 4

Figure 4a: Response to fault with SPS Off Figure 4b: Response to fault with SPS On Digital simulators can be used to model power systems with enough detail to verify the operation of complex power system control and protection equipment prior to its installation into the field. Communication protocols such as DNP3 may be used for communication between the external controller and simulator. Large numbers of simulation cases may be run over extended periods in order to validate the operation of the equipment under test. V. SIMULATION RESULTS Figure 4 shows the unstable simulated system response to a fault in which 3 phases of one circuit and one phase of a second circuit on a parallel line are grounded. The SPS is not active for the results shown in Figure 4a. The fault is repeated with the SPS active and the results shown in Figure 4b. In response to the fault, the SPS issues signals to shed generation and adjust reactive power support. As a result of the SPS action the system remains stable. VI. CONCLUSIONS VII. REFERENCES [1] K. Suzuki, N. Saito, H, Nishiiri, T. Kawahara, T. Maeda, Real time dynamic security assessment and control by combining FACTS and SPS, paper C2 109 CIRE 2010. [2] H. Ota, Y. Kitayama, N. Fukushima, K. Omata, K. Morita, Y. Kokai, Development of Transient Stability Control System (TSC System) Based on On LineStability Calculation, IEEE Transactions on Power Systems, Aug. 1996, Vol 11, No.3 pp. 1463 1172. [3] Brandt, Wachal, Valiquette, Wierckx, Closed Loop Testing of a Joint VAR Controller, IEEE Transactions on Power Systems, Aug. 1991, Vol 6, No.3 pp. 1140 1146. 5

VIII. BIORAPHIES Rudi Wierckx received B.Sc 1983 and M.Sc 1985 degrees from the University of Manitoba. Between 1985 and 1993, he was employed by the Manitoba HVDC Research Center, working on the development of the Real Time Digital Simulator (RTDS). In 1993 he left the Research Center to form RTDS Technologies Inc. and is currently a director of that company. Mr. Wierckx is a Registered Professional Engineer in the Province of Manitoba. Mamoru Kawasaki received the M.S. degree in electrical engineering from Tokyo Institute of Technology in 1989. The same year, he joined Chubu Electric Power Co., Inc., where he has been engaged in development of stabilizing technology for power system. He is a member of the IEE of Japan. Nobutoshi Saito received his M.S. degree in engineering from Yamanashi University in 1993. The same year, he joined Chubu Electric Power Co., Inc., where he has been engaged in development of stabilizing technology for power system. He is a member of the IEE of Japan. Kuniaki Anzai received the B.S. and M.S. degrees in electrical engineering from Tohoku University in2004 and 2006. In 2006, he joined Chubu Electric Power Co., Inc., where he has been engaged indevelopment of stabilizing technology for power system. S. C. Verma received his M. E. degree from IIT Roorkee, India, in 1986. He completed his Ph. D. inelectrical Engineering from Nagoya Institute of Technology, Japan, in 1994. Before coming to Japan, in1990, he has been working in an electric power company in India. In 1994, he joined Chubu ElectricPower Co., Inc. Nagoya and since then, he has been engaged in R&D studies concerning power system analysis. 6