SIPROTEC easy 7SJ45 Numerical Overcurrent Protection Relay Powered by CTs

Similar documents
Relays for Various Protection Applications / 7SV600

SIPROTEC 7SV600 Numerical Circuit-Breaker Failure Protection Relay

Arc protection relay. Features Three-phase overcurrent function. Application

Protection Relays PHASE & RESIDUAL OVERCURRENT

Tripping Matrix Device 7UW5010. As of Tripping Circuit Management Unit or Non-electric Protection Device. Catalog 1.0. Answers for energy.

Relion 611 series. 611 series Type Test Certificate

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

Arc protection relay. Features Three-phase overcurrent function. Application

XU1-E Earth fault voltage relay. (August 1996) Manual XU1-E (Revision New)

IRI1-ES Sensitive Earth Fault Current Relay. Manual IRI1-ES (Revision A)

02/11/2015

High-Tech Range IRI1-ES- Sensitive Earth Fault Current Relay

02/11/2015

Feeder protection relay SPAA 121 C. Product Guide

SIPROTEC 4 6MD66 High-Voltage Bay Control Unit

Electronic timer CT-ARS.11

Electronic timer CT-ERS.12 ON-delayed with 1 c/o contact Data sheet

Contact protection relay

Electronic timer CT-AHD.22

Electronic timer CT-ERS.21

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

Earth-fault Relay SPAJ 110 C. Product Guide

RE17LAMW on-delay timing relay - 1 s..100 h V AC/ DC - solid state output

08/07/2015

RE17LAMW on-delay timing relay - 1 s..100 h V AC/DC - solid state output

TU531, TU532 Terminal Unit

Electronic timer CT-ARE OFF-delayed without auxiliary voltage, 1 c/o (SPDT) contact

Published by and copyright 2015 Siemens AG Energy Management Freyeslebenstr Erlangen, Germany

Electronic timer CT-ERD.12

Electronic timer CT-APS.21 OFF-delayed with 2 c/o (SPDT) contacts

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

Electronic timer CT-ARS.11 OFF-delayed without auxiliary voltage with 1 c/o (SPDT) contact

RE17LCBM off-delay timing relay - control - 1 s..100 h V - solid state output

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

RE11RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

Electronic timer CT-EBD.12 Flasher starting with ON with 1 c/o (SPDT) contact

Part No. Description Product Life Cycle Phase *) unit, 24 VDC, spring terminals. unit, 24 VDC, spring terminals, XC version

Electronic timer CT-SDD.22 Star-delta change-over with 2 n/o contacts

XU1-DC DC voltage relay. (June 1998) Manual XU1-DC (Revision New)

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

Electronic timer CT-ERS.12 ON-delayed with 1 c/o (SPDT) contact

RE Product data sheet Characteristics. universal plug-in timing relay - flashing s..60 mn V AC - 2 OC. Main.

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

RT4B-110V/12A RECTIFIER

Output Voltage* (nom.)(adjustable)

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

RT4F-48V/50A-WAC RECTIFIER

TF501, TF521 Terminal Bases

Feeder protection relay SPAA 341 C. Product Guide

XE2 DC current relay for loss of excitation protection. Manual XE2 (Revision A)

Sensitive definite time or inverse time earth-fault stage for back-up residual earthfault

Sensitive Earth-fault Relay SPAJ 111 C. Product Guide

Combined Overcurrent and Earth-fault Relay SPAJ 141 C. Product Guide

Output Voltage* (nom.)(adjustable)

SIPROTEC 4 7SS52 Distributed Numerical Busbar and Breaker Failure Protection

Electronic timer CT-SDS.23 Star-delta change-over with 2 n/o contacts

PCD3.C90. Date Modification Asked by: Version E/A Bus Connector PCD2.K106 change to PCD3.K106 Müller.R 1.1

AO523 Analog Input Module

DC561, digital input/output module,

DI572 Digital Input Module

TM3DI16 module TM3-16 inputs

RM4JA01F current measurement relay RM4-J - range ma V AC

Feeder protection relay

Conforms to VDE0435/2021 C/250, VDE0110, VDE0106/P100 Conforms to EN , pren

TM3AI4 module TM3-4 analog inputs

DC522 Digital Input/Output Module

Switching relay CT-IRE with 1 c/o (SPDT) contact

RT4F-110V/25A RECTIFIER

PHOENIX CONTACT - 07/2006

DI561 Digital Input Module

Electronic timer CT-AHS OFF-delayed with 2 c/o contacts Data sheet

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

DC562, digital input/output module,

Feeder Protection Relay REF 610. Product Guide

AI561 Analog Input Module

TM3SAF. Main. Device short name

AI531 Analog Input Module

20A DRR Module / 40A DRR Module

TM3SAC5RG SAFETY MODULE FOR PLC TM2xx, 1 FUNCTION, CAT3, SPRING TERMINALS

Solid-state Timer H3YN

Busbar Differential Protection

DC541 Digital Input/Output Module

MINI-PS AC/10-15DC/8

RM4JA32MW current measurement relay RM4-J - range A V AC DC

Electronic timer CT-ARS.21 OFF-delayed without auxiliary voltage with 2 c/o (SPDT) contacts

1S20. Arc Fault Monitor Relay. Features. Introduction. ARC Fault Protection

Thermistor motor protection relays CM-MSS.12 and CM-MSS.13

Technical specifications

RE22R2AMR On-delay Timing Relay s 300h V AC/DC - 2C/O

RE Product data sheet Characteristics. time delay relay for star-delta starter ms - 230/380 V AC - 1 contact. Main.

Model Number Structure

Millenium 3. General Characteristics. General environment characteristics for CB, CD, XD, XR and XE product types

RE48ATM12MW on-delay timing relay s..300 h V AC - 2 OC

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

RE7RB13MW adjustable off-delay timing relay s V AC DC - 2OC

CD522 Encoder, Counter and PWM Module

RT7-48V/6kW Specification

Synchro-check relay. Application

Safety Standards. Model Number: Unit Weight:

Transcription:

SIPROTEC easy 7SJ4 Numerical Overcurrent Protection Relay Powered by CTs Function overview Fig. /1 Description The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended as a radial feeder or transformer protection (backup) in electrical networks. It provides definite-time and inverse-time overcurrent protection according to IEC and ANSI standards. The 7SJ4 relay does not require auxiliary voltage supply. It imports its power supply from the current transformers. LSP2339-afp.tif SIPROTEC easy 7SJ4 numerical overcurrent protection relay powered by current transformers (CT) Operation without auxiliary voltage via integrated CT power supply Standard current transformers (1 A/ A) Low power consumption: 1.4 VA at IN (of the relay) Easy mounting due to compact housing Easy connection via screw-type terminals Protection functions 2-stage overcurrent protection Definite-time and inverse-time characteristics (IEC/ANSI) High-current stage I>> or calculated earth-current stage IE>orIEp> selectable Trip with pulse output (24 V DC / 0.1 Ws) or relay output (changeover contact) Repetition of trip during circuit-breaker failure (relays with pulse output) Combination with electromechanical relays is possible due to the emulation algorithm Monitoring functions Hardware and software are continuously monitored during operation Front design Simple setting via DIP switches (self-explaining) Settings can be executed without auxiliary voltage no PC Integrated mechanical trip indication optionally Additional features Optional version available for most adverse environmental conditions (condensation permissible) Flush mounting or surface (rail) mounting /3

Application The SIPROTEC easy 7SJ4 is a numerical overcurrent protection relay which is primarily intended as a radial feeder or transformer protection (backup) in electrical networks. It provides definite-time and inverse-time overcurrent protection according to IEC and ANSI standards. The convenient setting with DIP switches is self-explanatory and simple. The 7SJ4 relay does not require auxiliary voltage supply. It imports its power supply (1.4 VA at I N, sum of all phases) from the current transformers. Impulse output for low-energy trip release or contact output for additional auxiliary transformer are available. An optional integrated trip indication shows that a trip occurred. ANSI IEC Protection functions Fig. /2 Typical application 0 I>> Instantaneous overcurrent protection 0, 1 I>t, I p Time-overcurrent protection (phase) 0N, 1N I E>t, I Ep Time-overcurrent protection (earth) Construction Within its compact housing the protection relay contains all required components for: Measuring and processing Alarm and command output Operation and indication (without a PC) Optional mechanical trip indication Auxiliary supply from current transformers Maintenance not necessary Fig. /3 Application in distribution switchgear LSP2391-afp.tif The housing dimensions of the units are such that the 7SJ4 relays can in general be installed into the existing cutouts in cubicles. Alternative constructions are available (surface mounting and flush mounting). The compact housing permits easy mounting, and a version for the most adverse environmental conditions, even with extreme humidity, is also available. LSP2340-afp.tif Fig. /4 Screw-type terminals /4

Protection functions The overcurrent function is based on phase-selective measurement of the three phase currents. The earth (ground) current I E (Gnd) is calculated from the three line currents I L1 (A), I L2 (B), and I L3 (C). The relay has always a normal stage for phase currents I> (0/1). For the second stage, the user can choose between a high-current stage for phase currents I>> (0) or a normal stage for calculated earth currents I E> (0N/1N). The inverse-time overcurrent protection with integrating measurement method (disk emulation) emulates the behaviour of electromechanical relays. The influence of high-frequency transients and transient DC components is largely suppressed by the implementation of numerical measured-value processing. Fig. / Definite-time overcurrent characteristic Fig. /6 Inverse-time overcurrent characteristic Available inverse-time characteristics Characteristics acc. to ANSI/IEEE IEC 602-3 Moderately inverse/normal inverse Very inverse Extremely inverse /

Connection diagrams Pulse output or relay output are optionally available. Pulse output These relays require a low-energy trip release (24 V DC/0.1 Ws) in the circuitbreaker, and are intended for modern switchgear. In case of circuit-breaker failure, a repetition of the tripping signal is initiated. Fig. /7 Connection of 3 CTs with pulse output Fig. /8 Connection diagram 7SJ4 with impulse output Relay output These relays can be applied with all conventional switchgear. A transformer that provides the trip circuit energy, must be connected in the current transformer circuit. Fig. /9 Connection of 3 CTs with trigger transformer and relay output Fig. /10 Connection diagram 7SJ4 with relay output /6

Technical data General unit data Analog input System frequency I N Current transformer inputs Rated current, normal earth current I N Power consumption At I N = 1 / A Rating of current transformer circuit Thermal (r.m.s.) Dynamic (peak) Recommended primary current transformers Output relays Pulse output (7SJ4XX-0*) Number 0 or 60 Hz (selectable) 1orA Approx. 1.4 VA at I N (relay) 0 I N for 1 s 1 I N for 10 s 2 I N continuous 100 I N for half a cycle 10 P 10, 2. VA or according to the requirements and required tripping power 1 pulse output 24VDC/0.1Ws Relay output (7SJ4XX-1*) Number 1 changeover contact Contact rating Make 1000 W/VA Break 30 VA 40 W resistive 2 VA at L/R 0 ms Rated contact voltage 20VDCor 240VAC Permissible current per contact A continuous 30 A for 0. s (inrush current) Unit design Housing Flush mounting DIN 43700/IEC 614 Adaptable for rail mounting (recommended for local mounting only) Dimensions (WxHxD) in mm 78. x 147 x 20.8 (incl. transparent cover and terminal blocks) Weight (mass) approx. 1. kg Degree of protection according to IEC 6029 Housing Front Rear Protection of personnel U L -listing Listed under 69CA. Electrical tests Specifications Standards IP 1 IP 20 IP1X IEC 602 (product standards) ANSI C37.90.0/.1/.2; UL08 See also standards for individual tests Insulation tests Standards IEC 602- Voltage test (routine test) 2. kv (r.m.s.), 0 Hz, 1 min All circuits except for pulse output-earth Voltage test (type test) across open command contacts 1.0 kv (r.m.s.), 0 Hz, 1 min Impulse voltage test (type test) all circuits, class III kv (peak); 1.2/0 µs; 0. J; 3 positive and 3 negative impulses in intervals of 1 s EMC tests for interference immunity; type tests Standards IEC 602-6, IEC 602-22, EN 0263 (product standards) EN 0082-2 (generic standard) EN 61000-6-2 IEC 61000-4 (basic standards) High-frequency test IEC 602-22-1, class III Electrostatic discharge IEC 602-22-2, class III EN 61000-4-2, class III 2.kV(peak);1MHz;τ =1ms; R i = 200 Ω; 400 surges/s; duration 2 s 4kV/6kVcontactdischarge; 8kVairdischarge;bothpolarities; 10 pf; R i = 330 Ω Irradiation with radio-frequency 10 V/m; 80 to 1000 MHz; field, amplitude-modulated 80 %; 1 khz; AM IEC 602-22-3 and IEC 61000-4-3, class III Irradiation with radio-frequency field, pulse-modulated IEC 61000-4-3/ENV 0204, class III Fast transient interference/bursts IEC 602-22-4 and IEC 61000-4-4, class IV High-energy surge voltage, IEC 61000-4- installation, class III Measuring inputs, binary outputs Line-conducted HF, amplitude-modulated, IEC 602-22-6 and IEC 61000-4-6, class III Power frequency magnetic field IEC 61000-4-8, class IV IEC 602-6 Damped wave IEC 60694, IEC 61000-4-12, class III Oscillatory surge withstand capability ANSI/IEEE C37.90.1 Not across open contacts Fast transient surge withstand capability ANSI/IEEE C37.90.1 not across open contacts Radiated electromagnetic interference ANSI/IEEE C37.90.2 EMC tests for interference emission; type test Standard Interference field strength IEC CISPR 22 10 V/m; 900 MHz; repetition frequency 200 Hz; duty cycle 0 % 30 V/M; 1890 MHz; repetition frequency 200 Hz; duty cycle 0 % 4 kv; /0 ns; khz; burst duration = 1 ms; repetition rate 300 ms; both polarities; R i =0Ω; duration 1 min Impulse: 1.2/0 µs Circuit groups to earth: 2 kv; 42 Ω,0.µF Across circuit groups: 1 kv; 42 Ω,0.µF 10 V; 10 khz to 80 MHz; 80 %; 1kHz;R i = 10 Ω 30 A/m continuous; 300A/mfors;0Hz 0. mt; 0 Hz 2.kV(peak,polarityalternating) 100kHz,1MHz,10MHzand 0 MHz, R i = 200 Ω, duration 2s 2. to 3 kv (peak); 1 to 1. MHz damped wave; 0 shots per s; duration 2s;R i = 10 Ω to 200 Ω 4 to kv; 10/10 ns; 0 and 120 surges per 2s; both polarities; duration 2s;R i = 80 Ω 3 V/m; 2 to 1000 MHz amplitude and pulse-modulated EN 0081 * (generic) 30 to 1000 MHz, class B /7

Technical data Mechanical stress tests Vibration, shock stress and seismic vibration Duringoperation Standards IEC 602-21 and IEC 60068-2 Vibration IEC 602-21-1, class II IEC 60068-2-6 Shock IEC 6022-21-2; class I Seismic vibration IEC 602-21-3; class I IEC 60068-3-3 Sinusoidal 10 to 60 Hz ± 0.07 mm amplitude: 60 to 10 Hz; 1 g acceleration Frequency sweep 1 octave/min 20 cycles in 3 perpendicular axes Semi-sinusoidal g acceleration, duration 11 ms, each 3 shocks in both directions of the 3 axes Sinusoidal 1to8Hz:±4.0mmamplitude (horizontal vector) 1to8Hz:±2.0mmamplitude (vertical vector) 8to3Hz:1g acceleration (horizontal vector) 8to3Hz:0.g acceleration (vertical vector) Frequency sweep 1 octave/min 1 cycle in 3 perpendicular axes During transport (flush mounting) Standards IEC 602-21 and IEC 60068-2 Vibration IEC 602-21-1, class 2 IEC 60068-2-6 Shock IEC 602-21-2, class 1 IEC 60068-2-27 Continuous shock IEC 602-21-2, class 1 IEC 60068-2-29 Sinusoidal Hzto8Hz:±7.mmamplitude; 8 Hz to 10 Hz: 2 g acceleration frequency sweep 1 octave/min 20 cycles in 3 perpendicular axes Semi-sinusoidal 1 g acceleration, duration 11 ms, each 3 shocks in both directions of the 3 axes Semi-sinusoidal 10 g acceleration, duration 16 ms, each 1000 shocks in both directions of the 3 axes Climatic stress tests Temperatures Temperatures during service 20 C to +70 C / 4 F to +18 F With continuous current 2I N: 20 C to + C / 4 F to +131 F Permissible temperature during storage Permissible temperature during transport Humidity Permissible humidity class (standard) Permissible humidity class (condensation proof) 2 C to + C / 13 F to +131 F 2 C to +8 C / 13 F to +18 F Annual mean value 7 % relative humidity; on 30 days per year up to 9 % relative humidity; condensation not permissible. Condensation is permissible according to IEC 6064-1, class III Functions Overcurrent protection Definite time (DT O/C ANSI 0/1) Setting range / steps Current pickup I>> (phases) Current pickup I>(phases) 3-phase supply: see note* Current pickup I E> 3-phase supply: see note* Delay times T I>> Delay times T I> The set time delays are pure delay times. Inversetime(IECorANSI1) Setting range / steps Current pickup I p (phases) 3-phase supply: see note* Current pickup I Ep> (earth calculated) 3-phase supply: see note* Delay times T Ip (IEC) Delay times D (ANSI) Trip times Total time delay impulse output Total time delay relay output Reset ratio Tolerances Definite time (DT O/C 0/1) Current pickup I>>, I>, I E> Delay times T Inverse time (IEC or ANSI 1) Pickup thresholds 2 I N to 20 I N or deactivated, step 0. I N 0. I N to 6.2 I N or deactivated, step 0.1 I N 0. I N to 6.2 I N or deactivated, step 0.1 I N 0 to 17 ms, step 2 ms 0 to 6300 ms, step 100 ms 0. I N to 4 I N or deactivated, step 0.1 I N 0. I N to 4 I N or deactivated, step 0.1 I N 0.0 to 3.1 s, step 0.0 s 0. to 1.00 s, step 0.2 s Time behavior for 2 I/I p 20 %or0ms Deviation of the measured values as a result of various interferences Frequency in the range of <2.% 0.9 <f/f N <1.0 Frequency in the range of <10% 0.9 <f/f N <1.1 Harmonics <1% up to 10 % 3 rd and th harmonic DC components <% Temperature in the range of <0.%/10K C to 70 C / 23 F to 18 F Approx. 32 ms Approx. 38 ms Approx. 0.9 (with definite time) Approx. 0.91 (with inverse time) %ofthesetvalueor %ofi N (at threshold < I N) 1%or30ms %ofthesetvalueor %ofi N (at threshold < I N) * Note: The device allows minimum setting values of 0. I N (3-phase). With single supply, operation is ensured from 0.8 I N (7SJ4XX-0*; pulse output) or 1.3 I N (7SJ4XX-1*; relay output) onwards (printed on the front). /8

Technical data CE conformity This product is in conformity with the Directives of the European Communities on the harmonization of the laws of the Member States relating to electromagnetic compatibility (EMC Council Directive 89/336/EEC). This unit conforms to the international standard IEC 602. The unit has been developed and manufactured for application in an industrial environment according to the EMC standards. This conformity is the result of a test that was performed by Siemens AG in accordance with Article 10 of the Council Directive complying with the generic standards EN 0081-2 and EN 0082-2. Selection and ordering data Description SIPROTEC easy 7SJ4 numerical overcurrent protection relay powered by CTs Order No. 7SJ40 00 AA Current transformer I N 1A 1 A Trip Pulse output (for further details refer to Accessories ) 0 Relay output (for further details refer to Accessories ) 1 Unit design For rail mounting For panel flush mounting B E Region-specific functions Region World, 0/60 Hz; standard Region World, 0/60 Hz; condensation-proof A B IEC /ANSI IEC 0 ANSI 1 Indication (flag) Without 0 With 1 Accessories Protection relay with pulse output Low energy trip release 3AX1104-2B Protection relay with relay output Auxiliary transformers for the trip circuit (30 VA CTs recommended) 1A 4AM06-2CB00-0AN2 A 4AM070-8AB00-0AN2 Current transformer-operated trip release 0. A (rated operating current) 3AX1102-2A 1 A (rated operating current) 3AX1102-2B /9

Dimension drawings in mm / inch Dimension drawings for SIPROTEC easy Fig. 16/20 7SJ4, 7SJ46 housing for panel flush mounting Panel cutout Fig. 16/21 7SJ4, 7SJ46 housing for rail mounting /10