DSE2510/20 REMOTE DISPLAY MODULES. DSEGenset DSE2510/20 COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF GEN-SET APPLICATIONS FEATURES

Similar documents
DSE2548 DSENET OUTPUT EXPANSION MODULE. DSEGenset DSE2548 COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF GEN-SET APPLICATIONS

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC DSE103 MK II Speed Switch Operators Manual

DEEP SEA ELECTRONICS PLC DSE334 ATS Controller Operators Manual

DEEP SEA ELECTRONICS PLC

DSEULTRA DSE6100 Series Control Module Document Number

DSEPOWER. DSE8721 Colour Remote Display Module. Document number Author : Anthony Manton

DEEP SEA ELECTRONICS PLC

DSE2548 LED expansion module INTRODUCTION

DEEP SEA ELECTRONICS DSE890 / DSE891 GATEWAY INSTALLATION INSTRUCTIONS

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC

DSEULTRA DSE3110 Series Control Module

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC DSE334 Configuration Suite Software Manual

DSEPOWER. DSE7520 MK1 Mains Control Module. Document Number Author : Anthony Manton

DEEP SEA ELECTRONICS PLC

DSEPOWER DSE7510 Control Module Document Number

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS

DEEP SEA ELECTRONICS PLC DSE8005 SCADA Suite PC Software Manual

DEEP SEA ELECTRONICS PLC DSE8610 Control Module

DATA SHEET Compact Genset Controller, CGC 200

DSEM870. DSEControl PROGRAMMABLE DISPLAY FOR USE IN VEHICLES AND OFF-HIGHWAY MACHINERY

DEEP SEA ELECTRONICS PLC DSEE800 Operator Manual

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC DSE8860 Controller Operators Manual

DEEP SEA ELECTRONICS

DEEP SEA ELECTRONICS PLC

DIN16A DIGITAL INPUT MODULE USER MANUAL

OS-TSC13 TSC Commercial Basic Panel User Manual OPERATOR S MANUAL. Marine Generators Marine Diesel Engines Land-Based Generators

F1000 User's Manual. (Version: V1.01)

DSEEXTRA. DSE860 RS232 Ethernet Adaptor DSE865 RS485 Ethernet Adaptor Document Number Author : Anthony Manton

HGM9580 Bus Tie Bus Parallel Unit USER MANUAL. Smartgen Technology

Instruction Manual. EXDC Turbomolecular Pump Drive Modules. Item Number

The Programmable 4-Way Relay Card is an optional peripheral unit that provides four individually programmable relay output circuits.

Standards. Electromechanical Safety Switches. Industrial Safety Products 179

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

Operating Manual RISH DPM Hz

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

CliQ II DC-UPS Module 24V 40A / DRU-24V40ABN

7511 / / / 711 / / 731 / Preset 27

DEEP SEA ELECTRONICS PLC DSEWebNet PC Internet Browser Software Manual

IO-AO6X I/O Expansion Module 6 Isolated Analog Outputs

TYPICAL WIRING DIAGRAM A larger diagram is available in the operators manual. SEA ELECTRONICS 8620 INSTALLATION INSTRUCTIONS ISSUE 1

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Speed monitor D / / 2014

FL MC 2000E (SM40) LC

LED W RGBA User Manual

HAT560NC SERIES (HAT560NC /HAT560NBC) ATS CONTROLLER USER MANUAL

Installation Guide. QBox-V6. Standalone/Spare V6 SDI QBox. Standalone/Spare V6 SDI QBox. Part No. A

Ultra Slim Relays 24

RT12-240V/2.4kW Rectifier Specification

PowerView TM Model PV350 and PV380. Operations Manual Section 78

LCI User Manual mantracourt.com

Professional Entertainment Technology. imove 50SR. Innovation, Quality, Performance 21-

Conveyor Belt Alignment Switches from IDEM

PanelView Plus/VersaView CE Terminals and Display Modules

TABLE OF CONTENTS. IEC and IEC Pin and Sleeve Devices. IEC and IEC Mechanical Interlocks. Manual Disconnect Switches

DSE8610 SYNCHRONISING AUTO START LOAD SHARE CONTROL MODULE DSE COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF LOAD SHARE APPLICATIONS FEATURES

TF501, TF521 Terminal Bases

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

Level sensor Stainless steel version Model RLT-1000, for industrial applications

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

IWMR-3002 Industrial Multifunction VPN Router w/up to 2x WiFi 11ac + up to 2 LTE 4G + 2/4 serial ports + 2 Gigabit Ethernet Switch

EX-RC1 Remote I/O Adapter

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

CNVT-USB-RS485 MODBUS TO USB CONVERTER. Operating instructions

DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

TABLE OF CONTENTS INTRODUCTION. 3. Analog Input Analog Output Digital Input Digital Output OPERATIONAL DESCRIPITON.. 7 PROGRAMMING AND INITIAL SETUP.

PRODUCT SPECIFICATION. PC Board Relays. Series.

Power Meter PowerMonitor 500

RT4B-110V/12A RECTIFIER

RT4F-110V/25A RECTIFIER

CUS150M1 Instruction Manual

ELV12 Series. Instruction Manual

Multiple Generator Automatic Synchronising System

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

Engine Control Unit, ECU 100 Engine control Engine monitoring and protection Easy-to-read graphical display Integrated emulation software solution

LED BEAM 300 LED-MB50. User. Guide. Professional Entertainment Technology

Professional Entertainment Technology LED BEAM 300 LED-MB50. Innovation, Quality, Performance 23-

1.6. Counters, Panel Meters, Tachometers and Timers. Contents Description Fusion Integrated Machine Control Standards and Certifications...

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

Professional Entertainment Technology LED BEAM 300 LED-MB50. User. Guide

User Interface Terminal for nvent RAYCHEM NGC Systems Installation Instructions DESCRIPTION TOOLS REQUIRED. Nonhazardous Locations LR67275

Vigil 3 Amplifiers. Installation Instructions

LED PANEL. User Manual Please read the instructions carefully before use LED-7TC. Innovation, Quality, Performance 15-

This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).

MATRIX LED LED User Manual Please read the instructions carefully before use

SAMURAI SCAN 50 LED-SC50D. User Guide. Innovation, Quality, Performance. Professional Entertainment Technology 19-

Kinetix 300 Memory Module Programmer

V E1B Snap-in I/O Module

Product Description. Contents. Fusion Series. New Information December 2003

IPES/IES-0208 Series

HAT600 Series HAT600/HAT600I/HAT600B/HAT600BI ATS CONTROLLER USER MANUAL

New Product Release Summary for 3M Authorized Sales Reps and Distributors 3M Industrial M12 Wiremount Connectors, 3N104 and 3N304 Series

Model HM-535 Power Supply Installation and Service Instructions

Operating instructions Evaluation system for flow sensors VS / / 2013

Transcription:

DSEGenset DSE2510/20 REMOTE DISPLAY MODULES FEATURES The DSE2510 and DSE2520 are display modules designed to work with the DSE7310 Auto Start and DSE7320 Auto Mains (utility) Failure control modules. Up to three display modules can be connected to one host control module, and can be positioned up to a maximum distance of 1km away. All remote displays connected to the same system, will show the same information at any one time, while the host controller is able to display different information. The modules are simple to operate and feature the same user-friendly menu layout as the host module. ENVIRONMENTAL TESTING STANDARDS ELECTRO-MAGNETIC COMPATIBILITY BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment ELECTRICAL SAFETY BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment TEMPERATURE BS EN 60068-2-1 Ab/Ae Cold Test -30 o C BS EN 60068-2-2 Bb/Be Dry Heat +70 o C VIBRATION BS EN 60068-2-6 Ten sweeps in each of three major axes 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn The remote displays offer exactly the same instrumentation, control and monitoring capabilities as the host control module, including starting and stopping of the engine. All communications and configuration are done via the host module only. The remote devices simply mirror the configuration of the host module, making the system quick and easy to install. HUMIDITY BS EN 60068-2-30 Db Damp Heat Cyclic 20/55 o C @ 95% RH 48 Hours BS EN 60068-2-78 Cab Damp Heat Static 40 o C @ 93% RH 48 Hours SHOCK BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 ms DEGREES OF PROTECTION PROVIDED BY ENCLOSURES BS EN 60529 IP65 - Front of module when installed into the control panel with the supplied sealing gasket. COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF GEN-SET APPLICATIONS HOST MODULE (1) 1 DSENET EXPANSION DC POWER SUPPLY 8-35V COMPATIBLE WITH DSE7310/20 DSE2510/20 7 DSENET HOST MODULE 2157 2130 2510/20 2548 OTHER VOLT FREE OUTPUTS AUDIBLE ALARM 2 ISSUE 2

DSEGenset DSE2510/20 REMOTE DISPLAY MODULES FEATURES SPECIFICATION DC SUPPLY CONTINUOUS VOLTAGE RATING 8 V to 35 V Continuous CRANKING DROPOUTS Able to survive 0 V for 50 ms, providing supply was at least 10 V before dropout and supply recovers to 5 V. This is achieved without the need for internal batteries. LEDs and backlight will not be maintained during cranking. MAXIMUM OPERATING CURRENT 340mA at 12V 160mA at 24V MAXIMUM STANDBY CURRENT 160mA at 12V 80mA at 24V DIMENSIONS OVERALL 240mm x 181.1mm x 41.7mm 9.4 x 7.1 x 1.6 PANEL CUT-OUT 220mm x 160mm 8.7 x 6.3 MAXIMUM PANEL THICKNESS 8 mm 0.3 KEY FEATURE Expands the application possibilities of the DSE7300 Series by offering remote control and monitoring from up to 3 seperate locations. OPERATION The remote displays are operated via the START, STOP, AUTO and MANUAL soft touch membrane buttons on the front panel. The DSE2520 also has a TEST button. Both versions include load switch buttons. The main menu system is accessed using the five navigation buttons to the left of the LCD display. For a more detailed list of module features, please refer to the DSE7310 & DSE7320 Data Sheet. RELATED MATERIALS TITLE PART NO S DSE2510/20 Installation Instructions 053-064 DSE2510/20 Operator Manual 057-107 DSE7310/20 Data Sheet 055-051 DEEP SEA ELECTRONICS PLC UK Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com DEEP SEA ELECTRONICS INC USA 3230 Williams Avenue, Rockford, IL 61101-2668 USA TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708 EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change the details shown on this data sheet without prior notice. The contents are intended for guidance only. Registered in England & Wales No.01319649 VAT No.316923457 055-074/10/10 (2)

COMPLEX SOLUTIONS MADE SIMPLE DEEP SEA ELECTRONICS DSEEXTRA DSE2510 / DSE2520 Display Module Document Number 057-105 Author : Anthony Manton

Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 890099 Sales Fax: +44 (0) 1723 893303 E-mail : sales@deepseaplc.com Website : www.deepseaplc.com DSE2510 / DSE2520 Display Module Operator Manual Deep Sea Electronics Plc All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents Act 1988. Applications for the copyright holder s written permission to reproduce any part of this publication should be addressed to Deep Sea Electronics Plc at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies. Deep Sea Electronics Plc reserves the right to change the contents of this document without prior notice. Amendments since last publication Amd. No. Comments Typeface : The typeface used in this document is Arial. Care should be taken not to mistake the upper case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion. 2 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

1 BIBLIOGRAPHY... 5 1.1 INSTALLATION INSTRUCTIONS... 5 1.2 MANUALS... 5 2 INTRODUCTION... 5 3 SPECIFICATIONS... 6 3.1 PART NUMBERING... 6 3.2 POWER SUPPLY... 7 3.3 TERMINAL SPECIFICATION... 7 3.4 RS485... 8 3.5 OUTPUTS C & D... 8 3.6 SOUNDER... 8 3.7 DIMENSIONS AND MOUNTING... 9 3.8 FIXING CLIPS... 10 3.9 SILICON SEALING GASKET... 11 3.10 APPLICABLE STANDARDS... 11 3.10.1 ENCLOSURE CLASSIFICATIONS... 12 3.10.1.1 IP CLASSIFICATIONS... 12 3.10.1.2 NEMA CLASSIFICATIONS... 12 4 INSTALLATION... 13 4.1 USER CONNECTIONS... 13 4.1.1 DC SUPPLY... 13 4.1.2 RS485... 13 4.1.3 OUTPUTS... 13 4.2 TYPICAL CONNECTION DIAGRAMS... 14 4.2.1 MULTIPLE EXPANSION MODULES... 14 5 CONTROLS AND INDICATIONS... 15 5.1 DSE2510 DISPLAY FOR REMOTE START/AUTOSTART... 15 5.2 DSE2520... 17 5.4 ID SELECTION... 19 5.5 QUICKSTART GUIDE... 20 5.5.1 STARTING THE ENGINE... 20 5.5.2 STOPPING THE ENGINE... 20 5.6 VIEWING THE INSTRUMENT PAGES... 21 5.7 CONFIGURABLE INDICATORS... 21 5.8 CONTROLS... 22 6 OPERATION... 24 6.1 STOP MODE... 25 6.1.1 ECU OVERRIDE... 25 6.2 AUTOMATIC MODE... 25 6.3 MANUAL MODE... 25 6.4 TEST MODE... 25 7 PROTECTIONS... 26 7.1 PROTECTIONS DISABLED... 26 7.2 INDICATIONS... 26 7.3 WARNINGS... 26 7.4 SHUTDOWNS... 27 7.5 ELECTRICAL TRIPS... 27 7.6 MAINTENANCE ALARM... 27 7.7 FRONT PANEL CONFIGURATION... 28 7.8 ACCESSING THE RUNNING CONFIGURATION EDITOR... 29 7.8.1 EDITING A PARAMETER... 29 7.8.2 ADJUSTABLE PARAMETERS (RUNNING EDITOR)... 29 8 MAINTENANCE, SPARES, REPAIR AND SERVICING... 30 8.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE... 30 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 3

8.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE... 30 8.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE... 30 9 FAULT DIAGNOSIS... 31 10 MAINTENANCE, SPARES, REPAIR AND SERVICING... 31 11 WARRANTY... 31 12 DISPOSAL... 31 12.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)... 31 12.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES... 31 4 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

1 BIBLIOGRAPHY This document refers to and is reffered to by the following DSE publications which can be obtained from the DSE website www.deepseaplc.com This document refers to and is referred to by the following DSE publications which can be obtained from the DSE website www.deepseaplc.com 1.1 INSTALLATION INSTRUCTIONS Installation instructions are supplied with the product in the box and are intended as a quick start guide only. DSE PART DESCRIPTION 053-028 DSE7310 installation instructions 053-029 DSE7320 installation instructions 1.2 MANUALS This document contains only a subset of the operator instructions for the system. For full operating instructions, consult the relevant documents below. DSE PART DESCRIPTION 057-004 Electronic Engines and DSE wiring manual 057-074 DSE7000 Series operator manual 057-077 DSE7000 Series configuration software manual 2 INTRODUCTION This document details the installation and operation requirements of the DSE2510 and DSE2520 Display modules, part of the DSEExtra range of ancilliary devices. The manual forms part of the product and should be kept for the entire life of the product. If the product is passed or supplied to another party, ensure that this document is passed to them for reference purposes. This is not a controlled document. You will not be automatically informed of updates. Any future updates of this document will be included to the DSE website at www.deepseaplc.com DSE2500 Display Module is used in conjunction with supported DSE controllers to provide up to three displays. Configuration is made in the configuration of the host controller, not the display module itself. For further details on configuring the host controller you are referred to the relevant configuration software manual (refer to the section entitled Bibliography elsewhere in this document). The DSE2500 series display operates independently of the host controller. This means that the display shows different information than the screen of the host controller, depending upon what buttons have been pressed. For instance, the host controller may be showing the status display, while the display shows engine instruments as the operator has pressed the buttons to navigate to this display. When multiple DSE2500 displays are connected to the host controller, each will display the same information. For instance, selecting engine instruments on one DSE2500 will also display engine instruments on any other DSE2500 connected to the host controller. Monitoring of the communications link to the host controller is provided to allow an alarm to be generated in the case of a communications link failure. This alarm is configurable in the host controller. 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 5

3 SPECIFICATIONS 3.1 PART NUMBERING 2510-001 - 00 Product type DSE 2510 Remote Display Module for autostart/remote start 2510 Variant Standard product 00 Hardware revision DSE 2520 Remote Display Module for AMF(Automatic mains failure) 2520 Revision 1 001 At the time of this document production, there are no variants of this product and there have been no revisions of the module hardware. 6 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

3.2 POWER SUPPLY Minimum supply voltage Cranking dropouts Maximum supply voltage Reverse polarity protection Maximum operating current 8V continuous Able to survive 0V for 50mS providing the supply was at least 10V before the dropout and recovers to 5V afterwards. This is more than sufficient to allow the module to operate during engine cranking where the battery supply often falls as low as 4V (on a 12V system!) This is achieved without the need for internal batteries or other external requirements. 35V continuous (60V protection for surges) -35V continuous 160mA at 24V 340mA at 12V 3.3 TERMINAL SPECIFICATION Connection type Two part connector. Male part fitted to module Female part supplied in module packing case - Screw terminal, rising clamp, no internal spring. Minimum cable size 0.5mm² (AWG 24) Maximum cable 2.5mm² (AWG 10) size Example showing cable entry and screw terminals of a 10 way connector NOTE : For purchasing additional connector plugs from DSE, please see the section entitled Maintenance, Spares, Repair and Servicing elsewhere in this document. 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 7

3.4 RS485 NOTE : The DSE2500 Display operates using the Host Controller s DSENet connected to the RS485 port. Ensure your module is compatible with DSENet interface. At the time of writing this manual, only the DSE7300 series supports DSENet. DSEnet is the interconnection cable between the host controller and the expansion module(s) and must not be connect to any device other than DSE equipment designed for connection to the DSEnet. Cable type Two core screened twisted pair Cable characteristic impedance 120Ω Recommended cable Belden 9841 Belden 9271 Maximum cable length 1000m (1km) when using Belden 9841 or direct equivalent. 500m (0.5km) when using Belden 9271 or direct equivalent. DSEnet topology Bus with no stubs (spurs) DSEnet termination 120Ω. Fitted internally to host controller. Must be fitted externally to the last expansion module by the customer. Maximum expansion modules Refer to host controller documentation NOTE : As a termination resistor is internally fitted to the host controller, the host controller must be the first unit on the DSEnet. A termination resistor MUST be fitted to the last unit on the DSEnet. For connection details, you are referred to the section entitled typical wiring diagram elsewhere in this document. 3.5 OUTPUTS C & D Type Rating Voltage free relays, factory set to audible alarm 8A resistive @ 250 V AC NOTE : Outputs A & B are not fitted to the DSE2500 series module. 3.6 SOUNDER The display features an internal sounder to draw attention to warning, shutdown and electrical trip alarms. This operates at the same time as the host controller s internal sounder and can be muted locally. Operation of the mute function is subject to the configuration of the host controller and may be either follow main unit or local. When follow main unit is selected, pressing any mute button in the system on the host controller or on any other DSENet module configured to follow main unit will silence the host controller and all modules configured to follow main unit. When follow main unit is not selected, the display mute button operates independant of any other DSENet or host controller mute button. Sounder level 84db @ 1m 8 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

3.7 DIMENSIONS AND MOUNTING DIMENSIONS 240.0mm x 181.1mm x 41.7mm (9.4 x 7.1 x 1.6 ) PANEL CUTOUT 220mm x 160mm (8.7 x 6.3 ) WEIGHT 0.7kg (1.4lb) 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 9

3.8 FIXING CLIPS Supplied fixing clips hold the module into the panel fascia. Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the clip. Insert the three prongs of the fixing clip into the slots in the side of the DSE2500 series module case. Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the clip are inside their allotted slots. Turn the fixing clip screws clockwise until they make contact with the panel fascia. Turn the screws a little more to secure the module into the panel fascia. Take care not to over tighten the fixing clip screws. Fixing clip Fixing clip fitted to module NOTE:- In conditions of excessive vibration, mount the module on suitable anti-vibration mountings. 10 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

3.9 SILICON SEALING GASKET The supplied silicon gasket provides improved sealing between the DSE2500 series module and the panel fascia. The gasket is fitted to the module before installation into the panel fascia. Take care to ensure the gasket is correctly fitted to the module to maintain the integrity of the seal. Sealing gasket Gasket fitted to module 3.10 APPLICABLE STANDARDS BS 4884-1 BS 4884-2 BS 4884-3 BS EN 60068-2-1 (Minimum temperature) BS EN 60068-2-2 (Maximum temperature) BS EN 60950 BS EN 61000-6-2 BS EN 61000-6-4 BS EN 60529 (Degrees of protection provided by enclosures) (see overleaf) UL508 NEMA rating (Approximate) (see overleaf) This document conforms to BS4884-1 1992 Specification for presentation of essential information. This document conforms to BS4884-2 1993 Guide to content This document conforms to BS4884-3 1993 Guide to presentation -30 C (-22 F) +70 C (158 F) Safety of information technology equipment, including electrical business equipment EMC Generic Immunity Standard (Industrial) EMC Generic Emission Standard (Industrial) IP65 (front of module when installed into the control panel with the supplied sealing gasket) IP42 (front of module when installed into the control panel WITHOUT being sealed to the panel) 12 (Front of module when installed into the control panel with the supplied sealing gasket). 2 (Front of module when installed into the control panel WITHOUT being sealed to the panel) In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice. 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 11

3.10.1 ENCLOSURE CLASSIFICATIONS 3.10.1.1 IP CLASSIFICATIONS DSE2500 series specification under BS EN 60529 Degrees of protection provided by enclosures IP65 (Front of module when module is installed into the control panel with the optional sealing gasket). IP42 (front of module when module is installed into the control panel WITHOUT being sealed to the panel) First Digit Second Digit Protection against contact and ingress of solid objects Protection against ingress of water 0 No protection 0 No protection 1 Protected against ingress solid objects with a diameter of more than 50 mm. No protection against deliberate access, e.g. with a hand, but large surfaces of the body are prevented from approach. 1 Protection against dripping water falling vertically. No harmful effect must be produced (vertically falling drops). 2 Protected against penetration by solid objects with a diameter of more than 12 mm. Fingers or similar objects prevented from approach. 3 Protected against ingress of solid objects with a diameter of more than 2.5 mm. Tools, wires etc. with a thickness of more than 2.5 mm are prevented from approach. 4 Protected against ingress of solid objects with a diameter of more than 1 mm. Tools, wires etc. with a thickness of more than 1 mm are prevented from approach. 5 Protected against harmful dust deposits. Ingress of dust is not totally prevented but the dust must not enter in sufficient quantity to interface with satisfactory operation of the equipment. Complete protection against contact. 6 Protection against ingress of dust (dust tight). Complete protection against contact. 2 Protection against dripping water falling vertically. There must be no harmful effect when the equipment (enclosure) is tilted at an angle up to 15 from its normal pos ition (drops falling at an angle). 3 Protection against water falling at any angle up to 60 from the vertical. There must be no harmful effect (spray water). 4 Protection against water splashed against the equipment (enclosure) from any direction. There must be no harmful effect (splashing water). 5 Protection against water projected from a nozzle against the equipment (enclosure) from any direction. There must be no harmful effect (water jet). 6 Protection against heavy seas or powerful water jets. Water must not enter the equipment (enclosure) in harmful quantities (splashing over). 3.10.1.2 NEMA CLASSIFICATIONS DSE2500 series NEMA Rating (Approximate) 12 (Front of module when module is installed into the control panel with the optional sealing gasket). 2 (front of module when module is installed into the control panel WITHOUT being sealed to the panel) NOTE: - There is no direct equivalence between IP / NEMA ratings. IP figures shown are approximate only. 1 IP30 2 IP31 3 IP64 3R IP32 4 (X) IP66 12/12K IP65 13 IP65 Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt. Provides a degree of protection against limited amounts of falling water and dirt. Provides a degree of protection against windblown dust, rain and sleet; undamaged by the formation of ice on the enclosure. Provides a degree of protection against rain and sleet:; undamaged by the formation of ice on the enclosure. Provides a degree of protection against splashing water, windblown dust and rain, hose directed water; undamaged by the formation of ice on the enclosure. (Resist corrosion). Provides a degree of protection against dust, falling dirt and dripping non corrosive liquids. Provides a degree of protection against dust and spraying of water, oil and non corrosive coolants. 12 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

4 INSTALLATION 4.1 USER CONNECTIONS 4.1.1 DC SUPPLY Icon PIN No DESCRIPTION CABLE SIZE NOTES 1 DC Plant Supply Input (Negative) 2.5mm² AWG 13 2 DC Plant Supply Input (Positive) 2.5 mm² AWG 13 (Recommended Maximum Fuse 2A anti-surge) NOTE:- Terminal 3 is not fitted to the DSE2500 series module 4.1.2 RS485 PIN No DESCRIPTION CABLE SIZE NOTES A + 0.5mm² AWG 20 Use only 120Ω RS485 approved cable B - 0.5mm² AWG 20 Use only 120Ω RS485 approved cable 30 SCR 0.5mm² AWG 20 Use only 120Ω RS485 approved cable 4.1.3 OUTPUTS Icon PIN No DESCRIPTION 39 Output relay C 40 Output relay C 41 Output relay D 42 Output relay D CABLE SIZE 1.0mm AWG 18 1.0mm AWG 18 1.0mm AWG 18 1.0mm AWG 18 NOTES Factory configured to Audible Alarm (Recommend 10A fuse) Factory configured to Audible Alarm Factory configured to Audible Alarm (Recommend 10A fuse) Factory configured to Audible Alarm NOTE:- Terminals 3 to 38 are not fitted to the DSE2500 series controller NOTE:- Terminals 43 to 69 are not fitted to the DSE2500 series controller NOTE:- Screened 120Ω impedance cable specified for use with RS485 must be used for the RS485 to DSENET connections. DSE stock and supply Belden cable 9841 which is a high quality 120Ω impedance cable suitable for RS485 and DSENET use (DSE part number 016-030) 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 13

4.2 TYPICAL CONNECTION DIAGRAMS 4.2.1 MULTIPLE EXPANSION MODULES This diagram shows how the DSE2510 / DSE2520 Display Module can be installed as part of a larger scheme of expansion modules. NOTE : The connections from one module to another MUST be in a daisy chain fashion as shown. The cable must run IN to the terminals, then OUT again. Spurs should be avoided where possible. If this is not possible, they should be no longer than one metre (one yard). Failure to observe this may lead to intermittent or broken communications link. 14 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

5 CONTROLS AND INDICATIONS 5.1 DSE2510 DISPLAY FOR REMOTE START/AUTOSTART Main status and instrumentation display Menu navigation buttons Four configurable LEDs Open generator (manual mode only) Close generator (manual mode only) Start engine (when in manual mode) Select Stop mode Select Manual mode Select Auto mode Mute alarm / Lamp test 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 15

Close Generator LED. On When The Generator Is Required To Be On Load. Generator Available LED. On when the generator is within limits and able to take load. NOTE:- Generator on load LED has two modes of operation depending upon the configuration of the host controllers digital inputs. 1) Digital input configured for Generator closed auxiliary The LED illuminates when the generator closed auxiliary input is active The LED shows the state of the auxiliary contact. 2) There is NO input configured for Generator closed auxiliary (factory default setting) The LED illuminates when the host gives the loading signal to the generator The LED shows the state of the host s loading request. 16 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

5.2 DSE2520 NOTE: This sections contains only a subset of the information. The relevant host controller operator manual contains full detailed description of the system s controls, indications and operation. Main status and instrumentation display Menu navigation buttons Four configurable LEDs Transfer to mains (manual mode only) Transfer to generator (manual mode only) Start engine (when in manual mode) Select Stop mode Select Manual mode Select Test on load mode Select Auto mode Mute alarm / Lamp test Continued overleaf. 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 17

Mains Available LED. On when the mains is within limits and able to take load. Close Mains LED. On When The Generator Is Required To Be On Load. Close Generator LED. On When The Generator Is Required To Be On Load. Generator Available LED. On when the generator is within limits and able to take load. NOTE:- Generator on load LED has two modes of operation depending upon the configuration of the host controllers digital inputs. 3) Digital input configured for Generator closed auxiliary The LED illuminates when the generator closed auxiliary input is active The LED shows the state of the auxiliary contact. 4) There is NO input configured for Generator closed auxiliary (factory default setting) The LED illuminates when the host controller gives the loading signal to the generator The LED shows the state of the host s loading request. NOTE:- Mains on load LED has two modes of operation depending upon the configuration of the host controllers digital inputs. 5) Digital input configured for Mains closed auxiliary The LED illuminates when the mains closed auxiliary input is active The LED shows the state of the auxiliary contact. 6) There is NO input configured for Mains closed auxiliary (factory default setting) The LED illuminates when the host gives the loading signal to the mains The LED shows the state of the hosts loading request. 18 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

5.4 ID SELECTION The Display s running editor is used to select the Identification of the display module as the host controller is capable of giving instructions to a number of expansion modules at the same time. Consult the relevant host module s operating instructions for further details on number of supported expansion units (refer to the section entitled Bibliography elsewhere in this document). NOTE : The ID must be set to be a unique number, different from the ID of any other Display connected on the DSEnet. The ID of the DSE2500 will not interfere with the ID of any other type of expansion module. For instance it s OK to have a DSE2500 with ID1 and a DSE2157 with ID1. As the two modules are different type 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 19

5.5 QUICKSTART GUIDE This section provides a quick start guide to the module s operation. 5.5.1 STARTING THE ENGINE First, select manual mode then press the Start button to crank the engine. NOTE:- For further details, see the section entitled OPERATION elsewhere in this manual. 5.5.2 STOPPING THE ENGINE Select Stop/Reset mode. The generator is stopped. NOTE:- For further details, see the section entitled OPERATION elsewhere in this manual. 20 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

5.6 VIEWING THE INSTRUMENT PAGES NOTE: This sections contains only a subset of the information. The relevant host controller operator manual contains full detailed description of the system s controls, indications and operation. It is possible to scroll to display the different pages of information by repeatedly operating the next / previous page buttons Example If you want to view one of the instrument pages towards the end of the list, it may be quicker to scroll left through the pages rather than right! Status Engine Generator And so on until the last page is reached. A Further press of the scroll right button, returns the display to the Status page. The complete order and contents of each information page are given in the following sections Once selected the page will remain on the LCD display until the user selects a different page, or after an extended period of inactivity (LCD Page Timer), the module will revert to the status display. If no buttons are pressed upon entering an instrumentation page, the instruments will be displayed automatically subject to the setting of the LCD Scroll Timer. Alternatively, to scroll manually through all instruments on the currently selected page, press the scroll buttons. The autoscroll is disabled. If you want to view one of the instruments towards the end of the list, it may be quicker to scroll up through the instruments rather than down! To re-enable autoscroll press the scroll buttons to scroll to the title of the instrumentation page (ie Engine). A short time later (the duration of the LCD Scroll Timer) the instrumentation display will begin to autoscroll. When scrolling manually, the display will automatically return to the Status page if no buttons are pressed for the duration of the configurable LCD Page Timer. If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw the operator s attention to the alarm condition. 5.7 CONFIGURABLE INDICATORS The DSE2500 display LEDs mimic the configurable LED indicators of the host controller. Configurable indicators 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 21

5.8 CONTROLS Stop / Reset This button places the module into its Stop/Reset mode. This will clear any alarm conditions for which the triggering criteria have been removed. If the engine is running and the module is in Stop mode, the module will automatically instruct the changeover device to unload the generator ( Close Generator becomes inactive (if used)). The fuel supply de-energises and the engine comes to a standstill. Should a remote start signal be present while operating in this mode, a remote start will not occur. Manual This mode allows manual control of the generator functions. Once in Manual mode the module will respond to the start button, start the engine, and run off load. If the engine is running off-load in the Manual mode and a remote start signal becomes present, the module will automatically instruct the changeover device to place the generator on load ( Close Generator becomes active (if used)). Upon removal of the remote start signal, the generator remains on load until either selection of the STOP/RESET or AUTO modes. For further details, please see the more detailed description of Manual operation elsewhere in this manual. Auto This button places the module into its Automatic mode. This mode allows the module to control the function of the generator automatically. The module will monitor the remote start input and mains supply status and once a start request is made, the set will be automatically started and placed on load. Upon removal of the starting signal, the module will automatically transfer the load from the generator and shut the set down observing the stop delay timer and cooling timer as necessary. The module will then await the next start event. For further details, please see the more detailed description of Auto operation elsewhere in this manual. Test (DSE2520 only) This button places the module into its Test mode. This allows an on load test of the generator. Once in Test mode the module will respond to the start button, start the engine, and run on load. For further details, please see the more detailed description of Test operation elsewhere in this manual. Start This button is only active in STOP/RESET or MANUAL mode. Pressing this button in manual or test mode will start the engine and run off load (manual) or on load (test). Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly configured and fitted to a compatible engine ECU) Mute / Lamp Test This button silences the audible alarm if it is sounding and illuminates all of the LEDs as a lamp test feature/ When correctly configured and fitted to a compatible engine ECU, pressing this button in STOP/RESET mode after pressing the START cancel any passive alarms on the engine ECU. button (to power the ECU) will 22 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

Transfer to generator Allows the operator to transfer the load to the generator (when in Manual mode only) Open generator (DSE2510 only) Allows the operator to open the generator (when in Manual mode only) Transfer to mains (DSE2520 only) Allows the operator to transfer the load to the mains (when in Manual mode only) Menu navigation Used for navigating the instrumentation, event log and configuration screens. For further details, please see the more detailed description of these items elsewhere in this manual. 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 23

6 OPERATION NOTE: This section contains only a subset of the total information. The relevant host controller operator manual contains full detailed description of the system s controls, indications and operation. Remember that if you have purchased a completed generator set or control panel from your supplier, the module s configuration will probably have been changed by them to suit their particular requirements. Always refer to your configuration source for the exact sequences and timers observed by any particular module in the field. The DSE2500 series display operates independently of the host controller. This means that the display shows different information than the screen of the host controller, depending upon what buttons have been pressed. For instance, the host controller may be showing the status display, while the DSE2500 display shows engine instruments as the operator has pressed the buttons to navigate to this display. When multiple DSE2500 displays are connected to the host controller, each will display the same information. For instance, selecting engine instruments on one DSE2500 will also display engine instruments on any other DSE2500 connected to the host controller. As the DSE2500 series displays information from the host controller, you are referred to the host controller operator manual for detail operation of the system. 24 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

6.1 STOP MODE STOP mode is activated by pressing the button. In STOP mode, the module will remove the generator from load (if necessary) before stopping the engine if it is already running. Any latched alarms that have been cleared will be reset when STOP mode is entered. The engine will not be started when in STOP mode. If remote start signals are given, the input is ignored until AUTO mode is entered. 6.1.1 ECU OVERRIDE NOTE:- ECU Override function is only applicable when the host controller is connected to a compatible electronic engine ECU (CAN or Modbus engine) As the ECU is usually unpowered when the engine is not running, it must be turned on manually as follows : Select STOP mode on the DSE controller. Press and hold the START button to power the ECU. As the controller is in STOP mode, the engine will not be started. Continue to hold the start button for as long as you need the ECU to be powered. The ECU will remain powered until a few seconds after the START button is released. 6.2 AUTOMATIC MODE Activate auto mode by pressing the action. pushbutton. An LED indicator beside the button confirms this Auto mode will allow the generator to operate fully automatically, starting and stopping as required with no user intervention. 6.3 MANUAL MODE Activate Manual mode be pressing the this action. pushbutton. An LED indicator beside the button confirms Manual mode allows the operator to start and stop the set manually, and if required change the state of the load switching devices. 6.4 TEST MODE NOTE:- Test Mode is only applicable to DSE7320 controllers. Activate test mode be pressing the action. pushbutton. An LED indicator beside the button confirms this Test mode will start the set and transfer the load to the generator to provide a Test on load function. 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 25

7 PROTECTIONS NOTE: This section contains only a subset of the total information. The relevant host controller operator manual contains full detailed description of the system s controls, indications and operation. When an alarm is present, the Audible Alarm will sound and the Common alarm LED if configured will illuminate. The audible alarm can be silenced by pressing the Mute button In the event of an alarm the LCD will jump to the alarms page, and scroll through all active warnings, shutdowns and electrical trips. 7.1 PROTECTIONS DISABLED User configuration of the DSE7300 series controller (version 4 and above) is possible to prevent Shutdown / Electrical Trip alarms from stopping the engine. Under such conditions, Protections Disabled will appear on the module display to inform the operator of this status. 7.2 INDICATIONS Indications are non-critical and are often status conditions. They do not appear on the LCD of the module as a text message. However an output or LED indicator can be configured to draw the operators attention to the event. 7.3 WARNINGS Warnings are non-critical alarm conditions and do not affect the operation of the generator system, they serve to draw the operators attention to an undesirable condition. By default, warning alarms are self-resetting when the fault condition is removed. However DSE7300 series can be set to all warnings are latched to make warning alarms to latch until reset manually. If the module is configured for CAN or Modbus ECU and receives an error message from the engine control unit, Can ECU Warning is shown on the module s display and a warning alarm is generated. 26 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

7.4 SHUTDOWNS NOTE:- Shutdown and Electrical Trip alarms can be disabled by user configuration. See the section entitled Protections Disabled elsewhere in this document. Shutdowns are latching alarms and stop the Generator. Clear the alarm and remove the fault then press Stop/Reset to reset the module. NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm condition remains, it will not be possible to reset the unit (The exception to this is the Low Oil Pressure alarm and similar active from safety on alarms, as the oil pressure will be low with the engine at rest). 7.5 ELECTRICAL TRIPS NOTE:- Shutdown and Electrical Trip alarms can be disabled by user configuration. See the section entitled Protections Disabled elsewhere in this document. Electrical trips are latching and stop the Generator but in a controlled manner. On initiation of the electrical trip condition the module will de-energise the Close Generator Output to remove the load from the generator. Once this has occurred the module will start the Cooling timer and allow the engine to cool off-load before shutting down the engine. The alarm must be accepted and cleared, and the fault removed to reset the module. Electrical trips are latching alarms and stop the Generator. Remove the fault then press Stop/Reset to reset the module. 7.6 MAINTENANCE ALARM Depending upon module configuration one or more levels of maintenance alarm may occur based upon a configurable schedule. There are three maintenance alarms in the DSE7300 series V3 and above, and one level of maintenance alarm in prior versions. Consult your system provider in the case of Maintenance Alarms. 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 27

7.7 FRONT PANEL CONFIGURATION This configuration mode allows the operator limited customising of the way the display module operates. Host controller configuration is not available from the fascia of the DSE2500 series display module. Use the module s navigation buttons to traverse the menu and make value changes to the parameters: Increase value / next item Accept Decrease value / next item 28 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

7.8 ACCESSING THE RUNNING CONFIGURATION EDITOR The running editor can be entered while the engine is running. All protections remain active if the engine is running while the running editor is entered. Press and hold the 7.8.1 EDITING A PARAMETER Enter the editor as described above. button to enter the running editor. Press the view/change. (up or down) buttons to select the parameter you wish to To edit the parameter, press to enter edit mode. The parameter begins to flash to indicate that you are editing the value. Press the value. (up or down) buttons to change the parameter to the required Press to save the value. The parameter ceases flashing to indicate that it has been saved. To exit the editor at any time, press and hold the button. 7.8.2 ADJUSTABLE PARAMETERS (RUNNING EDITOR) Running Editor (Factory default settings are shown in bold italicised text) Section Parameter as shown on display Factory Setting DISPLAY Contrast 50% Language DSEN DSENet ID selection 0 English 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 29

8 MAINTENANCE, SPARES, REPAIR AND SERVICING The DSE2500 Series controller is designed to be Fit and Forget. As such, there are no user serviceable parts within the controller. In the case of malfunction, you should contact your original equipment supplier (OEM). 8.1 PURCHASING ADDITIONAL CONNECTOR PLUGS FROM DSE If you require additional plugs from DSE, please contact our Sales department using the part numbers below. 7000 series terminal designation Plug description Part No. 1-2 2 way 5.08mm 007-443 39-42 4 way 7.62mm 007-171 RS485 3 way 5.08mm 007-174 NOTE:- Terminals 3-27 are not fitted to the DSE2500 series controller NOTE:- Terminals 31 to 38 are not fitted to the DSE2500 series controller 8.2 PURCHASING ADDITIONAL FIXING CLIPS FROM DSE Item Description Part No. 7000 series fixing clips (packet of 4) 020-294 8.3 PURCHASING ADDITIONAL SEALING GASKET FROM DSE Item Description Part No. 7000 series silicon sealing gasket 020-507 30 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual

9 FAULT DIAGNOSIS Nature of problem Module appears to be dead Host controller indicates there is a fault with communications with the DSENet controller. Suggestion Check polarity and size of the connected DC supply are within the specifications of the DSE2130 Check the connection of the DSEnet paying particular attention to the cable type being used and the positioning of the termination resistors. 10 MAINTENANCE, SPARES, REPAIR AND SERVICING The DSE2500 is designed to be Fit and Forget. As such, there are no user serviceable parts. In the case of malfunction you should contact your original equipment supplier (OEM). 11 WARRANTY DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any applicable warranty, you are referred to your original equipment supplier (OEM). 12 DISPOSAL 12.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) Directive 2002/96/EC If you use electrical and electronic equipment you must store, collect, treat, recycle and dispose of WEEE separately from your other waste. 12.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES Directive 2002/95/EC:2006 To remove specified hazardous substances (Lead, Mercury, Hexavalent Chromium, Cadmium, PBB & PBDE s) Exemption Note: Category 9. (Monitoring & Control Instruments) as defined in Annex 1B of the WEEE directive will be exempt from the RoHS legislation. This was confirmed in the August 2005 UK s Department of Trade and Industry RoHS REGULATIONS Guide (Para 11). Despite this exemption DSE has been carefully removing all non RoHS compliant components from our supply chain and products. When this is completed a Lead Free & RoHS compatible manufacturing process will be phased into DSE production. This is a process that is almost complete and is being phased through different product groups. 057-105 Issue 1 DSE2510 / DSE2520 Display Module Operator Manual 31