Protocol Implementation Conformance Statement ED 15079-0 Group: Controls Part Number: ED15079-0 Date: September 2003 MicroTech II Multiple Air Handler Controller BACnet Networks Protocol Implementation Conformance Statement ANSI/ASHRAE 135-2001, BACnet This document contains the Protocol Implementation Conformance Statement (PICS) for the MicroTech II Multiple Air Handler Controller and for the MicroTech II Self-Contained Unit Controller from McQuay International as required by ANSI/ ASHRAE (American National Standards Institute/American Society of Heating, Refrigeration, and Air Conditioning Engineers) Standard 135-2001, BACnet; A Data Communication Protocol for Building Automation and Control Networks. Contents BACnet Protocol Implementation Conformance Statement.................................................2 Product...............................................................................2 BACnet Standardized Device Profile..................................................................2 BACnet Interoperability Building Blocks (BIBBs) Supported..............................................2 Standard Object Types Supported....................................................................3 Segmentation Capability............................................................................6 Data Link Layer Options........................................................................... 6 Networking Options............................................................................... 6 Device Address Binding............................................................................6 Character Sets Supported...........................................................................6 2003 McQuay International ED-15079 Page 1
BACnet Protocol Implementation Conformance Statement Date: May, 2003 Vendor Name: McQuay International Product Name: Multiple Air Handler Controller Product Model Number: MTII-UC-0-MAC01.0 Applications Software Version: 01.0 BACnet Protocol Revision: Version 1 Revision 0 Product The MicroTech II Multiple Air Handler Controller is a controller designed to control a maximum of 8 MicroTech II applied rooftop or self contained units in up to 4 seperate multiple-unit control groups and be integrated into BACnet building automation systems. The controller provides three control stategies: 1) Common Outdoor Air Temperature, 2) Common Control Temperature and 3) Common Duct Static Pressure. Access to temperatures, pressures and control parameters is available using Internet Explorer (read/ write) and the BACnet control network (read only). BACnet Standardized Device Profile Based on BIBBs supported, the MicroTech II Multiple Air Hander is a BACnet Advanced Application Controller (B-AAC). Refer to the section below entitled BACnet Interoperability Building Blocks (BIBBs) Supported for a complete listing of BIBBS. BACnet Interoperability Building Blocks (BIBBs) Supported BIBB Name Data Sharing - ReadProperty - A Data Sharing - ReadProperty - B Data Sharing - ReadPropertyMultiple - A Data Sharing - ReadPropertyMultiple - B Data Sharing - Write Property - A Data Sharing - WriteProperty - B Data Sharing - WritePropertyMultiple - A Data Sharing - WritePropertyMultiple - B Data Sharing - COV- A Data Sharing - COV - Unsolicited - A Alarm and Event - Notification - A Alarm and Event - Notification - B Alarm and Event - ACK - A Alarm and Event - ACK - B Alarm and Event - Alarm Summary - A Alarm and Event - Alarm Summary - B Scheduling - B Trending-Viewing and Modifying Trends - B Device Management - Dynamic Device Binding - A Device Management - Dynamic Device Binding - B Device Management - Dynamic Object Binding - A Device Management - Dynamic Object Binding - B Device Management - Router Configuration - A DS-RP-A DS-RP-B DS-RPM-A DS-RPM-B DS-WP-A DS-WP-B DS-WPM-A DS-WPM-B DS-COV-A DS-COVU-A AE-N-A AE-N-B AE-ACK-A AE-ACK-B AE-ASUM-A AE-ASUM-B SCHED-B T-VMT-B DM-DDB-A DM-DDB-B DM-DOB-A DM-DOB-B NM-RC-A Designation Page 2 ED-15079
Standard Object Types Supported Object-Type Creatable Deletable Optional Properties Supported Analog Input Update_Interval lmin_pres_value Max_Pres_Value Resolution Analog Output Min_Pres_Value Resolution High_Limi t Analog Value Relinquish_Default Notifiy_Type Writable Properties Not Required To Be Writable Update_Interval Min_Pres_ValueMax_Pres_Value Resolution Units Units Min_Pres_Value Max_Pres_Value Resolution Units vent_enable Notifiy_Type ED-15079 Page 3
Object-Type Creatable Deletable Optional Properties Supported Binary Input Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Alarm_Value Binary Output Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Minimum_Off_Time Minimum_On_Time Feedback_Value Binary Value Relinquish_Default Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_Reset Elapsed_Active_Time Time_Of_Active_Time_Reset Minimum_Off_Time Minimum_On_Time Alarm_Value Schedule (exported as read only) Calendar (exported as read only) Trend Log (exported as read only) Writable Properties Not Required To Be Writable Polarity Polarity Inactive_Text Active_Text Page 4 ED-15079
Object-Type Creatable Deletable Optional Properties Supported Multi-state Input (8 States Max) Multi-state Output (8 States Max) Multi-State Value (8 States Max) State_Text Alarm_Values Fault_Values State_Text Feedback_Value DeviceType State_Text Relinquish_Default Alarm_Values Fault_Values Writable Properties Not Required To Be Writable DeviceType ED-15079 Page 5
Segmentation Capability Segmented requests supported Window Size: Any Segmented responses supported Window Size: Any Data Link Layer Options BACnet IP, (Annex J) ISO 8802-3, Ethernet (Clause 7) Networking Options MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400 bps Router, Clause 6 - Ethernet IP-Ethernet, Ethernet-MS/TP, Ethernet IP-MS/TP Annex H, BACnet Tunneling Router over IP BACnet/IP Broadcast Management Device (BBMD)Does the BBMD support registrations by Foreign Devices? Yes No Device Address Binding Static Device Binding Yes No Character Sets Supported ANSI X3.4 BM /Microsoft DBCS ISO 8859-1 ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226 Note: Support for multiple character sets does not imply they can be supported simultaneously. Page 6 ED-15079
2003 McQuay International www.mcquay.com 800-432-1342