Point Level Transmitters. Pointek CLS200 (Standard) Functional Safety Manual 02/2015. Milltronics

Similar documents
Type Switching repeater. Safety manual

Type 9160 / Transmitter supply unit / Isolating repeater. Safety manual

MANUAL Functional Safety

Functional safety manual RB223

Mobrey Hydratect 2462

Safety manual. This safety manual is valid for the following product versions: Version No. V1R0

Team engineering via Inter Project. Engineering. TIA Portal. Team engineering via Inter Project Engineering. Basics of "Inter Project Engineering"

MANUAL Functional Safety

PROFIsafe SITRANS. Pressure transmitter SITRANS P, DS III PROFIsafe series. Product Information 7MF4*34 04/2008 A5E

Rosemount Functional Safety Manual. Manual Supplement , Rev AG March 2015

Creating the program. TIA Portal. SIMATIC Creating the program. Loading the block library 1. Deleting program block Main [OB1]

Proline Prowirl 72, 73

Readme SiVArc V14 SP1 Update 6

MANUAL Functional Safety

Class documentation. COMOSKDictionary COMOS. Platform Class documentation COMOSKDictionary. Trademarks. General. KDictionary. Programming Manual

SIMATIC. Communications processor CP First Steps in Commissioning. Getting Started 09/2008 A5E

Failure Modes, Effects and Diagnostic Analysis

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

COMOS. Platform Class documentation RevisionMaster_dll. Class: RevisionInfo 1. Class: RevisionMaster 2. Programming Manual

SAFETY MANUAL SIL Switch Amplifier

Soliphant M with electronic insert FEM54

Special Documentation Liquicap M FMI51, FMI52

SIMATIC. Process Control System PCS 7 Product Brief on Software Updates from V5.1/V5.2 to PCS 7 V7.0 SP1. Preface 1

Performance data abgn SCALANCE W770/W730 SIMATIC NET. Industrial Wireless LAN Performance data abgn SCALANCE W770/W730.

Safety Manual. Vibration Control Type 663. Standard Zone-1-21 Zone Edition: English

Performance data abgn PCIe Minicard MPCIE-R1-ABGN-U3 SIMATIC NET

SIMATIC. Process Control System PCS 7 VT Readme V8.2 (online) Security information 1. Overview 2. Notes on Installation 3. Notes on usage 4.

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5A ST (6ES7132-4BD02-0AA0) Preface. Properties 2. Diagnostics 3.

S7-300 Getting Started - Commissioning a CPU 31xC: Closed-loop control

Vibrating Switches SITRANS LVL 200S, LVL 200E. Relay (DPDT) With SIL qualification. Safety Manual. Siemens Parts

SIMATIC. ET 200S distributed I/O Digital electronic module 4DO DC24V/0.5 A ST (6ES7132-4BD01-0AA0) Preface. Properties 1. Diagnostics 2.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

ACT20X-(2)HTI-(2)SAO Temperature/mA converter. Safety Manual

Failure Modes, Effects and Diagnostic Analysis

MANUAL Functional Safety

Failure Modes, Effects and Diagnostic Analysis

SIMATIC. Process Control System PCS 7 PCS 7 system documentation - Readme V8.0 SP2 (Update 1) Options for Accessing Documentation 1

SIMATIC. Process Control System PCS 7 Configuration McAfee Endpoint Security Security information 1. Preface 2.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

Removal of Hardware ESD, Independent of Safety Logic Solver

SIMATIC. Industrial PC Microsoft Windows 7 (USB stick) Safety instructions 1. Initial startup: Commissioning the operating system

Siemens Drives & PLCs

MindSphere. Visual Explorer. Introduction. User roles for "Visual Explorer" Connecting "Visual Explorer" to MindSphere data. Creating Visualizations

General Information 1. Connection 2. User Interface 3 ATC5300. Menus 4. Automatic Transfer Controller. Remote Control Software Manual A5E

Operating Instructions (Compact) SIMATIC. Industrial PC SIMATIC Microbox PC 420. Siemens. Release 11/2006 A5E

SIMATIC. Communications processor CP 340 first commissioning steps. Getting Started 04/2005 A5E

Functional safety manual Liquiphant M/S with FEL58 and Nivotester FTL325N

English. SIMATIC Sensors. RFID-Systems RF600. Getting Started. Edition 11/2005; J31069-D0172-U001-A1-7618

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

Products Solutions Services. Functional Safety. How to determine a Safety integrity Level (SIL 1,2 or 3)

SIMATIC Ident RFID systems MDS D423 Compact Operating Instructions

Failure Modes, Effects and Diagnostic Analysis

HART Temperature Transmitter for up to SIL 2 applications

First Steps in Commissioning CPU. 31xC: Positioning with digital output SIMATIC

HART Temperature Transmitter for up to SIL 2 applications

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SIMATIC. ET 200S distributed I/O Power module PM-E DC24..48V (6ES7138-4CA50-0AB0) Preface. Properties 1. Parameters 2. Diagnostics 3.

Industrial Controls. Motor management and control devices SIMOCODE pro - Application examples. Introduction 1. Application example

SITOP UPS1600 under STEP 7 V5. SITOP UPS1600 under STEP 7 V5. Introduction. Safety notes. Description 3. Assigning the IP address

Description. SIMATIC Sensors. RF systems Wide-range power supply unit for SIMATIC RF systems. Operating Instructions 11/2007 J31069-D0169-U001-A4-7618

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

SIMATIC HMI. Software RemoteOperate V2. Preface. Overview 1. Range of functions of the RemoteOperate software. Hardware and software requirements

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S

SIMATIC. Process Control System PCS 7 Licenses and quantity structures (V8.0) Preface 1. Selecting the correct license keys 2

SIMATIC. Digital Input Module SM DI, DC24V - Sinking/Sourcing. Product information. Product Information

SIMATIC. SIMATIC Logon V User management and electronic signatures 1. Hardware and Software Requirements 2. Scope of delivery 3.

SITOP UPS1600 under STEP 7 V13. SITOP UPS1600 under STEP 7 V13. Introduction. Safety notes. Description. Assigning the IP address

First Steps with S7-PDIAG and ProAgent

ST (6ES7132-6FD00-0BB1)

party software COMOS Platform Third-party software Trademarks 1 Requirements for the system environment Third-party software releases Operating Manual

Failure Modes, Effects and Diagnostic Analysis

Serial Communications Accessories SITRANS RD200/300. Operating Instructions 05/2013 SITRANS

Siemens Industrial SIMATIC. Process Control System PCS 7 Configuration Trend Micro OfficeScan Server XG. Security information 1.

Configuration limits for products of the SIMATIC NET PC Software V8.1 SIMATIC NET

Operator Station (V8.0) SIMATIC. Process Control System PCS 7 Operator Station (V8.0) Preface 1. The PCS 7 Operator Station

Key Panels Library SIMATIC HMI. Key Panels Library. Preface 1. Installation of Key Panels Library. Working with the Key Panels Library

ET 200S distributed I/O Digital electronic module 2DO AC V (6ES7132-4FB01-0AB0)

FMEDA and Prior-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

Class: DocumentManager 1 COMOS. Platform Class documentation DocumentManager_dll. Programming Manual 03/2017 V10.2.

SIMATIC. S7/HMI SIMATIC Automation Tool V3.1 SP1 product information. SIMATIC Automation Tool features 1. Known problems. Product Information

SIMATIC. WinCC Readme Runtime Professional. Validity 1. Improvements in Update 2 2. Improvements in Update 1 3

SINEMA Remote Connect - Client SIMATIC NET. Industrial Remote Communication SINEMA Remote Connect - Client. Preface. Requirements for operation

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

Soliphant M with electronic insert FEM57 + Nivotester FTL325P

Converter SINAMICS G150. Type 6SL37102G

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

Technical Report Reliability Analyses

HawkEye 45T Display User Manual

SIMATIC. Industrial PC Microsoft Windows 7. Safety instructions 1. Initial startup: Commissioning the operating. system

Commissioning and safety manual SIL2

SIMATIC IPC Wizard for. Widescreen devices with multitouch SIMATIC. Industrial PC SIMATIC IPC Wizard for. Preface.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

Industrial Controls. SIMOCODE pro SIMOCODE pro PCS 7 Library. Preface. Security information. Product specific security. information.

SIMATIC. ET 200S distributed I/O Power module PM-E DC24..48V/AC V (6ES7138-4CB11-0AB0) Preface. Properties 1. Parameters 2.

SIMATIC. Process Control System PCS 7 Trend Micro OfficeScan (V8.0; V8.0 SP1) Configuration. Using virus scanners 1.

DI 8x24VDC ST digital input module SIMATIC. ET 200SP DI 8x24VDC ST digital input module (6ES7131-6BF00-0BA0) Preface. Documentation guide

MindSphere. MindConnect IoT Extension Getting Started. Introduction to MindSphere. Prerequisites 2. Preparations 3. MindConnect IoT Extension

Siemens Spares. Setting up security in STEP 7. Professional SIMATIC NET. Industrial Ethernet Security Setting up security in STEP 7 Professional

Transcription:

Point Level Transmitters Pointek CLS200 (Standard) Functional Safety Manual 02/2015 Milltronics

Introduction 1 General safety instructions 2 Pointek Level Instruments Device-specific safety instructions 3 List of Abbreviations / Acronyms A Functional safety for Pointek CLS200 Standard Product Information Pointek CLS200 Standard: 7ML5630-xxxxx-xxx0-Z C20 7ML5631-xxxxx-xxx0-Z C20 7ML5632-xxxxx-xxx0-Z C20 7ML5633-xxxxx-xxx0-Z C20 7ML5634-xxxxx-xxx0-Z C20 Ordering Number: A5E35637149 02/2015

Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. Danger indicates that death or severe personal injury will result if proper precautions are not taken. Warning indicates that death or severe personal injury may result if proper precautions are not taken. Caution with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. Caution without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. Notice indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. Qualified Personnel The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards. Prescribed Usage Note the following: Warning This device may only be used for the applications described in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance. Trademarks All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. Disclaimer of liability While we have verified the contents of this manual for agreement with the hardware and software described, variations remain possible. Thus we cannot guarantee full agreement. The contents of this manual are regularly reviewed and corrections are included in subsequent editions. We welcome all suggestions for improvement. Copyright SIEMENS AG 2014 Subject to change without further notice 2 of 16 Functional Safety for Pointek CLS200 Standard

Table of contents 1 Introduction... 4 1.1 Safety Manual Revision History... 4 1.2 General... 4 1.3 Purpose of this document... 4 1.4 Required documentation... 4 2 General safety instructions... 6 2.1 Safety-instrumented system (SIS)... 6 2.2 Safety Integrity Level (SIL)... 7 3 Device-specific safety instructions... 9 3.1 Applications... 9 3.2 Safety function... 9 3.3 Application restrictions... 10 3.4 Settings... 10 3.5 Behavior in case of faults... 11 3.6 Maintenance/Testing... 12 3.7 Safety characteristics... 13 A List of Abbreviations/Acronyms... 15 A.1 Abbreviations... 15 Glossary... 16 3 of 16 Functional Safety for Pointek CLS200 Standard

1 1 1 Introduction 1.1 Safety Manual Revision History Revision* Document Part Number Release Date Revision Comments AA A5E35637149 02/2015 Initial Release * See Operating Instructions for additional revision information. 1.2 General The following table lists all available Pointek CLS200 Standard models: Product Number 7ML5630-xxxxx-xxx0 -Z C20 7ML5631-xxxxx-xxx0 -Z C20 7ML5632-xxxxx-xxx0 -Z C20 7ML5633-xxxxx-xxx0 -Z C20 7ML5634-xxxxx-xxx0 -Z C20 The term CLS200 Standard is used in the following text for all device models. 1.3 Purpose of this document This document contains information and safety instructions required when using the CLS200 Standard in safety-instrumented systems. It is aimed at system planners, plant managers, service and maintenance engineers and personnel who will commission the device. 1.4 Required documentation This document deals with the Pointek CLS200 Standard exclusively as part of a safety function. This document only applies in conjunction with the following documentation: Name Pointek CLS200/CLS300 (Standard) Operating Instructions * Operating Instructions are located at the following web site: https://www.siemens.com/level Order No* 7ML19985JH04 (English) 7ML19985JH34 (German) 4 of 16 Functional Safety for Pointek CLS200 Standard

More information Information The contents of these instructions shall not become part of or modify any prior or existing agreement, commitment, or legal relationship. All obligations on the part of Siemens AG are contained in the respective sales contract which also contains the complete and solely applicable warranty conditions. Any statements contained herein do not create new warranties or modify the existing warranty. The content reflects the technical status at the time of printing. We reserve the right to make technical changes in the course of further development. Siemens regional offices If you need more information or have particular problems which are not covered sufficiently by the operating instructions, contact your local Siemens Regional Office. You will find the address of your local Siemens Regional Office on the Internet at https://www.siemens.com/processinstrumentation under the tab Contacts and Partners. Product information on the Internet The Operating Instructions are on the supplied CD and are also available on the Siemens Level homepage on the Internet: https://www.siemens.com/level On the supplied CD, you will also find the product catalog sheet containing the ordering data, the Device Install software for SIMATIC PDM for subsequent installation, and the generic station description (GSD). See also Siemens Regional Offices (https://www.siemens.com/processinstrumentation) under the tab Contact Product information and Operating Instructions on the Internet (https://www.siemens.com/level) Functional Safety (SIL) Information on the internet (https://www.siemens.com/sil) 5 of 16 Functional Safety for Pointek CLS200 Standard

2 2 2 General safety instructions 2.1 Safety-instrumented system (SIS) Description A safety-instrumented system used to implement one or more safety-instrumented functions. A SIS is composed of any combination of sensor, logic solvers or control systems (PLCs), and final elements. Control system Figure 2-1: Example of a safety-instrumented system 6 of 16 Functional Safety for Pointek CLS200 Standard

Device operation The CLS200 Standard is a point level measuring instrument. When the probe becomes covered in process material the output relay (K2) and the solid-state switch (K3) change state. The safety PLC monitors the state of the relay or solid-state switch to perform a specified action based on the level measurement (example: bring the valve to the defined safe position). 2.2 Safety Integrity Level (SIL) Definition: SIL The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from SIL 1 to SIL 4. Each level corresponds to the probability range for the failure in a safety function. The higher the level of safety integrity of the safety-related system, the lower the probability that the safety-related system will fail to carry out the required safety function. The achievable SIL is determined by the following safety characteristics: Average probability of dangerous failure of a safety function in case of demand (PFD AVG ) Hardware fault tolerance (HFT) Safe failure fraction (SFF) Description The following table shows the dependency of the SIL on the average probability of dangerous failure of a safety function of the entire safety-instrumented system (PFD AVG ). The table deals with Low demand mode, i.e. the safety function is required to act a maximum of once per year on average. Table 2-1 Safety Integrity Level SIL PFD AVG 4 10-5 PFD AVG < 10-4 3 10-4 PFD AVG < 10-3 2 10-3 PFD AVG < 10-2 1 10-2 PFD AVG < 10-1 7 of 16 Functional Safety for Pointek CLS200 Standard

The average probability of dangerous failures of the entire safety instrumented system (PFD AVG ) is normally split between the three subsystems in the following figure. Sensor e.g. point level instrument Control system or logic unit e.g. PLC Final control-ling element e.g. valve PFDAVG component < 35% < 15% < 50% Figure 2-2 Example of PFD distribution The following table shows the achievable Safety Integrity Level (SIL) for the entire safety-instrumented system for type A subsystems depending on the safe failure fraction (SFF) and the hardware fault tolerance (HFT). Type A subsystems include devices for which the failure modes of all constituent components are well known and the behaviour of the element under fault conditions can be completely determined (see also IEC 61508, Section 2). SFF HFT 0 1 2 < 60 % SIL 1 SIL 2 SIL 3 60 to 90 % SIL 2 SIL 3 SIL 4 90 to 99 % SIL 3 SIL 4 SIL 4 > 99 % SIL 3 SIL 4 SIL 4 8 of 16 Functional Safety for Pointek CLS200 Standard

3 Device-specific safety instructions 3 3.1 Applications The CLS200 Standard is suitable for use in a safety instrumented function of Safety Integrity Level (SIL) 2 with a low demand mode 1oo1 architecture. The proven in-use-assessment was carried out by RISKNOWLOGY according to IEC 61508 / IEC 61511. Product revisions will be carried out by the manufacturer in accordance with IEC 61508. 3.2 Safety function Overfill detection is the Safety Function for the CLS200 Standard. The relay output (K2) or the solid-state switch (K3) may be used as part of a safety instrumented function (SIF), but not both. The difference in capacitance between an uncovered probe and a covered probe (for example, between a probe in air and a probe in water) is used to detect level, and to protect the process from a level that is too high. The output (relay K2 or solid-state switch K3) de-energizes when the change in capacitance is greater than the setting at the trip point. This causes the control system to bring the process into a safe state. The trip point is set by potentiometer P2. This determines how large the difference in capacitance needs to be before the output is switched. When the probe is covered, indicating an overfill condition, the relay and solid-state switch are de-energized: Relay contact between K2 pins 1 and 2 is open (recommended) Relay contact between K2 pins 2 and 3 is closed Solid-state switch between K3 pins 1 and 2 is open Note The normally closed relay contact between K2 pins 2 and 3 may be used, but this will mean that if power to the device is lost or an alarm condition occurs, the contact will be closed. Warning The settings and conditions listed in the Settings and Safety characteristics sections of this document must be met for the safety function specification to be valid. 9 of 16 Functional Safety for Pointek CLS200 Standard

Reference See also The failure rates, SFF and PFD AVG published in the SIL Declaration of Conformity are only valid for 10 years of operation. Required documentation (Chapter 1.4) Settings (Chapter 3.4) 3.3 Application restrictions 3.4 Settings Installation and configuration of the CLS200 Standard must be completed following the instructions detailed in the Setup Procedure in this manual (see Chapter 3.4). All application limitations and restrictions described in that manual must be observed. In addition: When the device is mounted in a vertical or diagonal position the maximum trip point level will be at the level where 100 mm of the probe is covered in material. When the device is mounted horizontally in the process the maximum trip point level will be when the process material is 50 mm above the top surface of the probe. When commissioning in line with the device manual, the following device settings shall be made when the device is used as part of a SIF: Setup Procedure The following steps outline the setup procedure for the CLS200 Standard for overfill detection: 1. Set up the dip switches on the device to the following values: Switch Setting Comment S1 On (rocker up) Disables delay of alarm de-activation (alarm OFF) S2 On (rocker up) Disables delay of alarm activation (alarm ON) S3 On (rocker up) Sets device to high alarm / overfill protection S4 Off (rocker down) Test delay settings disabled S5 On (rocker up) Setup mode enabled 2. Turn potentiometer P1 fully counter clockwise. 3. Bring the process material to a level that is at least 250 mm below the lowest surface of the probe. 4. If the yellow Light Emitting Diode (LED), L1, is on skip to step 6. 5. Turn potentiometer P2 counter clockwise until the yellow LED, L1, is on. 10 of 16 Functional Safety for Pointek CLS200 Standard

6. Slowly turn potentiometer P2 clockwise until the yellow LED, L1, just turns off. 7. Set dip switch S5 to the off position (rocker down) to enable run mode. Safety parameters During device operation please ensure the switch bank on the CLS200 Standard is set to the following values: Switch Setting Comment S1 On (rocker up) Disables delay of alarm de-activation (alarm OFF) S2 On (rocker up) Disables delay of alarm activation (alarm ON) S3 On (rocker up) Sets device to high alarm / overfill protection S4 Off (rocker down) Test delay settings disabled S5 Off (rocker down) Run mode enabled Also ensure that potentiometer P1 is turned fully counter-clockwise. Reference Required documentation (see Chapter 1.4) Protection against configuration changes After configuration, fix the housing cover on the CLS200 Standard so that the device is protected against unwanted and unauthorized changes/operation. Checking the safety function after installation After installation of the CLS200 Standard, a safety function proof test must be carried out (see Chapter 3.6). 3.5 Behavior in case of faults Fault The procedure in case of faults is described in the device Operating Instructions. Repairs Defective devices should be sent to the Repair Department with details of the fault and the cause. When ordering replacement devices, please specify the serial number of the original device. The serial number can be found on the nameplate. 11 of 16 Functional Safety for Pointek CLS200 Standard

See also Services & Support (https://www.siemens.com/automation/services&support) Partner (https://www.automation.siemens.com/partner) 3.6 Maintenance/Testing Interval We recommend that the functioning of the level transmitter be checked at regular intervals of one year. Functional test To ensure the proper operation of the CLS200 Standard, we recommend that the basic functions of the CLS200 Standard are tested as described below: 1. Ensure that the process material is at least 250 mm below the lowest surface of the probe. Verify that the relay output or the solid-state switch is in the energized state. Note that the process material level required for the probe to indicate uncovered will vary depending on the user specific installation. The probe is considered uncovered when the yellow LED, L1, is off with the settings described in this manual. 2. Bring the process material level up to cover the probe and verify that the relay output or the solid-switch is in the de-energized state. When the device is mounted in a vertical or diagonal position the trip point level shall be at the level where 100mm of the probe is covered in material or lower. When the device is mounted horizontally in the process the trip point level shall be when the process material is 50 mm above the top surface of the probe or lower. The probe is considered covered when the yellow LED, L1, is on with the settings described in this manual. 12 of 16 Functional Safety for Pointek CLS200 Standard

Functional safety proof test To reveal possible undetected faults of the safety function, the entire SIF shall be tested according to IEC 61508 or 61511. To reveal dangerous undetected faults the CLS200 Standard relay or solid-state switch output shall be tested using the following procedure: Step Action 1 Bypass the safety PLC or take other appropriate action to avoid a false trip. 2 Inspect the product for signs of physical damage/defects or loose parts and replace/repair product as required. 3 Inspect the probe of the device for and verify that no build up of material has occurred. Clean the probe if necessary according to the Operating Instructions. Note that the probe will trip earlier than expected when there is material build up so this step will help reduce the likelihood of nuisance trips. 4 Perform the Functional Test as described in the section above. 8 Restore the loop to full operation. 9 Remove the bypass from the safety PLC or otherwise restore normal operation. Table 3-1 Steps for Proof Test The proof test interval (TI) is specified for the failure rate calculation of each individual SIF in a system (PFD AVG ). We recommend the Proof Test be performed at least once per year. The Internet Product Page (https://www.siemens.com/pointekcls200) will be used to communicate additional Safety Information, and should be checked regularly. 3.7 Safety characteristics The safety characteristics necessary for use of the system are listed in the SIL declaration of conformity. These values apply under the following conditions: The CLS200 Standard is only used for overfill protection in safety related applications. The CLS200 Standard is only used in safety-related systems with a low demand mode for the SIF. The safety-related settings (see Settings section) have been entered by local operation and checked before commencing safety-instrumented operation. The DIP switches must be in the safety positions described in the "Safety Parameters" section of chapter 3.4. The CLS200 Standard is blocked against unwanted and unauthorized changes / operation. The listed failure rates are valid for operating stress conditions typical of an industrial field environment similar to IEC 60654-1 class C with an average temperature over a long period of time of 40 C. For a higher average temperature of 60 C, the failure rates should be multiplied with an experience based factor of 2.5. A similar multiplier should be used if frequent temperature fluctuation must be assumed. All used materials are compatible with process conditions. 13 of 16 Functional Safety for Pointek CLS200 Standard

Using the CLS200 Standard correctly there are no known wear out mechanisms. The minimum lifetime of the relay output is 50,000 switching cycles. The MTTR after a device fault is 8 hours. The logic solver (PLC) has to be configured to detect one of the following conditions as an overfill condition: Relay contact between K2 pins 1 and 2 is open (recommended) Relay contact between K2 pins 2 and 3 is closed Solid-state switch between K3 pins 1 and 2 is open A dangerous failure of the CLS200 Standard is a failure where the safety position is not activated, (high level alarm). The output relay stays on while the sensor is covered. See also Settings (Chapter 3.4) SIL Declaration of Conformity on the Internet Product Page (https://www.siemens.com/pointekcls200). Go to Support > Approvals / Certificates. https://www.siemens.com/sil 14 of 16 Functional Safety for Pointek CLS200 Standard

A List of Abbreviations/Acronyms A A.1 Abbreviations Abbreviation Full term in English Meaning FIT Failures in Time Failure rates have the dimension one over time. Failure rates are specified in FIT (Failures in Time), ie. the number of failures in 10 9 component hours. HFT Hardware Fault Tolerance Hardware fault tolerance: Capability of a function unit to continue executing a required function in the presence of faults or deviations. LED Light Emitting Diode MooN "M out of N" voting In terms of redundancy and the selection procedure used: A safety-instrumented system, or part of a system, that consists of N independent channels. The channels are connected to each other in such a way that M channels are in each case sufficient to perform the safetyinstrumented function. Example: Pressure measurement: 1oo2 architecture. A safety instrumented system decides that a specified pressure limit has been exceeded if one out of two pressure sensors reaches this limit. In a 1oo1 architecture, there is only one pressure sensor. MTBF Mean Time Between Failures Average period between two failures. MTTR Mean Time To Restoration Average period between the occurrence of a fault on a device or system and the repair. PFD Probability of Failure on Demand Probability of dangerous failures of a safety function on demand. PFD AVG Average Probability of Failure on Average probability of dangerous failures of a safety Demand function on demand. PLC Programmable Logic Controller SFF Safe Failure Fraction Proportion of safe failures: Proportion of failures without the potential to bring the safety instrumented system into a dangerous or not permissible functional status. SIF Safety Instrumented Function A portion of a safety instrumented system consisting of a sensor, logic solver/plc and final element used to reduce the risk of occurrence of one hazardous event. SIL Safety Integrity Level The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL 1 to SIL 4). Each level corresponds to a range of probability for failure of a safety function. The higher the Safety Integrity Level of the safetyinstrumented system, the lower the probability that it will not execute the required safety functions. TI Proof Test Interval Interval at which the test to reveal undetected faults is performed. 15 of 16 Functional Safety for Pointek CLS200 Standard

Glossary Dangerous failure A failure with the potential to bring the safety-instrumented system into a dangerous or non-functional status. Example: The measurement device reports a value 10% below the actual value, preventing the safety function from acting on a value, which is too high. Low Demand Mode The frequency of demands for operation made on a safety related system is no greater than one per year and no greater than twice the proof-test frequency. Safety function Defined function of a device or system with the objective of achieving or maintaining a safe state of a system taking into account a defined dangerous occurrence. Example: Level/pressure/temperature measurement using 4 to 20 ma output. Safety Integrity Level SIL Safety-instrumented system A safety-instrumented system executes the safety functions that are required to achieve or maintain a safe status in a system. It consists of a sensor, logic solver/ control system (PLC) and final element. Definition: Safety Instrumented Function (SIF) A portion of a safety instrumented system consisting of a sensor, logic solver/ control system (PLC) and final element used to reduce the risk of occurrence of one hazardous event. Example: A safety PLC will close a valve if the measured value exceeds a specified value. SIL The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from SIL 1 to SIL 4. Each level corresponds to the probability range for the failure of a safety function. The higher the SIL of the safety-instrumented system, the higher the probability that the required safety function will work. The achievable SIL is determined by the following safety characteristics: Average probability of dangerous failure of a safety function in case of demand (PFD AVG ) Hardware fault tolerance (HFT) Safe failure fraction (SFF) 16 of 16 Functional Safety for Pointek CLS200 Standard

www.siemens.com/processautomation For more information www.siemens.com/level www.siemens.com/weighing Siemens AG Industry Sector 1954 Technology Drive P.O. Box 4225 Peterborough, ON Canada K9J 7B1 email: techpubs.smpi@siemens.com Subject to change without prior notice A5E35637149 Rev. AA Siemens AG 2015 *A5E35637149* Printed in Canada www.siemens.com/processautomation