Station Automation based on IEC 61850

Similar documents
IDS SAS. Station Automation System for Complex Applications

Sturdy and Powerful ACOS 750

ROCON RPC 116. SUBSTATION AUTOMATION Central unit for substation automation

Automation System Solutions

ProField-GW Description

Electrical Integration with Smart Communication

Telecontrol and Automation Systems

Designing a new IEC substation architecture

I/A Series HARDWARE Product Specifications

The System for Power Automation

ACOS 300. Reliable protection for network and constructions in medium- and high voltage

Advanced Test Equipment Rentals ATEC (2832) DANEO 400. Hybrid Signal Analyzer for Power Utility Automation Systems

Substation Configuration Language. Summary August 2006

SEL Real-Time Automation Controller (RTAC)

Substation automation products. MicroSCADA Pro for substation automation

////// SUBSTATIONS. Control command and local Scada

SIPROTEC 5 V7.8 Protection, automation and monitoring for digital substations

Plant / field level Process

REALISATION OF AN INTELLIGENT AND CONTINUOUS PROCESS CONNECTION IN SUBSTATIONS

Redundancy. For maximum plant availability.

How smart can the grid really be?

Inform IT Information Management Tenore. SCADA Extension ABB

COMMUNICATION NETWORKS. FOX615/612 TEGO1 IEC GOOSE Proxy Gateway interface module.

EXPERIENCE WITH IEC IN THE REFURBISHMENT OF AN IMPORTANT EUROPEAN 380 KV SUBSTATION. Switzerland

IP67 IP20. Controllers Open Flexible Compact SPEEDWAY. Programmable. Fieldbus Couplers. Programmable. Fieldbus Controllers

Sigbert Reimann, Remote Control Forum, Datum 9. October 2013 RTU - Review and News. ABB Network Management Forum December 10, 2013 Slide 1

Real-Time Automation Controller (RTAC) Powerful, reliable, and secure multifunction controller

SWT 3000 Teleprotection siemens.com

Substation Automation based on IEC Claes Rytoft ABB Power Systems

Pushing the limits. ABB product development based on the IEC standard

Trends, Lessons and Benchmarks

The PowerLogic range. Gain energy insight and control

Presentation to the TEXAS RENEWABLE ENERGY INDUSTRIES ASSOCIATION November 7, 2010

Overview and Application

TFS 2100 Traveling Wave Fault Location System

A Collation & Analysis Methodology for Substation Event Data via a Web Interface (supporting COMTRADE, GOOSE & MMS Data Sources from Multiple Vendors)

Communication Networks

/ sicam SICAM CMIC The smart cube for your distribution network Answers for infrastructure and cities.

Remote Terminal Unit ER1000 APPLICATION FEATURES

Abstract. Randy Kimura GE Digital Energy

Turbine Controller.

Automate and Preserve Electromechanical Relay Investment Part 3 of 3 Using the Bitronics 70 Series to Improve Remote Monitoring and Control

SEL-2730M. Reliably Control and Monitor Your Substation and Plant Networks. Managed 24-Port Ethernet Switch

Digital Substation Overview of Technology, Industry

Substation to substation (ss2ss) GOOSE exchange for critical relay operations

Development of remote monitoring and control equipment with advanced communication functions

Industrial & Plant Communication Applications Seminar. April 3, 2006 College Station TX

ISIO 200. Binary Input/Output (I/O) terminal with IEC interface

Ovation Ethernet Link Controller Module Data Sheet

Airfield Lighting Control System

Importance of Interoperability in High Speed Seamless Redundancy (HSR) Communication Networks

Power Transmission and Distribution. I m on guard here! SIMEAS R reports power system weaknesses quickly and accurately

Engineering Approach for the End User in IEC applications

BMS-Ethernet-Gateway COM460IP

NEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector

FDDI. L26 - Fibre Distributed Data Interface (FDDI) L26 - Fibre Distributed Data Interface (FDDI) FDDI - Fiber Distributed Data Interface

PRODUCT INFORMATION. DeviceNet Triple Play Digital Communications Board. SA Actuator with AUMA Matic Motor Controls

IDM DATA ACQUISITION SYSTEM

AUDIO MANAGEMENT SYSTEM

Automation Unit TM 1703 ACP. SICAM 1703 flexible for all applications. Answers for energy.

Digital Grid Products At a Glance Protection, Substation Automation, Power Quality

Modicon M580 MUCH MORE than a PLC. the first epac!

IEC Test Equipment Requirements

Sub-Station Station. Secondary Sub. Sub- Distribution. Network. Distribution Panel. Distribution. Panel

TCP. Control and Protection Terminal Data sheet

IEEE 1588v2 Time Synchronization in Energy Automation Applications Case Studies from China

PRODUCT INFORMATION. AUMA Actuators, Inc. Pittsburgh PA USA. Triple Play Digital Communications Board DeviceNet / Modbus CDN455

AMA ServerSim-G Server-Simulator for IEC Data Sheet

Performance. Simplicity. Sepam, over 20 years of experience of the world leader. Sepam protection relays. For your peace of mind

CPU 319F-3 PN/DP. Page 1682 Mar 2008 Siemens ITS

IEC Engineering Process and Multi-Vendor System Configuration Tools Reduce Engineering Costs of Substation Automation Projects

CMC The Compact. The Compact and Versatile Three-Phase Relay Testing Solution

Answers for energy. SIPROTEC 5 the new benchmark for protection, automation, and monitoring of transmission grids

Address. Supply 24 V 0 V Fieldbus connection RJ-45. Fieldbus connection RJ-45. Configuration and programming interface. Pack. System Data.

Perfect protection smallest space

COMTRAXX COM460IP. BMS-Ethernet-Gateway

Industrial Switches Industrial Switches

Relion 630 series. Load-shedding controller PML630 High performing load-shedding solution for industrial and utility power networks

Smart Controller / Meter Concentrator

INDUSTRIAL ETHERNET SWITCHES WAGO Solutions at the Heart of the Industrial ETHERNET

Substation Automation Products. Line differential protection RED670 Relion 670 series

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

PLC PFC200 Controller PFC200 CS 2ETH RS

SA2WEB24. Central unit module. Benefits. Description

DC Substations / Supply Program

High-performance Digital Protection and Control Unit for Distribution Substations

Grid Automation Controller COM600 How it fits into the Smart Grid?

Automation & Control.

Substation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series

Industrial 1-port RS422/485 Modbus Gateway

C I R E D 22 nd International Conference on Electricity Distribution Stockholm, June 2013

Real-Time Automation Controllers (RTACs) Economical, multifunctional, compact real-time automation control

L-force remote maintenance

Protection, Automation, and Control System. Combine subcycle line protection with complete substation bay control

Modular Real-Time Automation Controller. Dependable control for harsh environments in a fully integrated, flexible platform

Scout-S Station Controller

Power Products. Protection and Control IED Manager PCM600 Product Guide

System Engineer Configures IEC Gateway to DNP3 Substation

GRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM All rights reserved.

PC-based Control for the Field Installation of PV and CSP Systems

Transcription:

IDS SAS Station Automation based on IEC 61850

IDS SAS Station automation based on IEC 61850 The IDS SAS station automation system was developed on the basis of the IEC 61850 standard. With this system, users gain a future-proof solution, which is able to cut the costs of station automation in the long term, since the time and expenditure for configuration and engineering is reduced and fast, low-price communication channels based on Ethernet and TCP/IP can be employed. Carefully devised migration solutions and gateway functions provide an entry to newcomers at any time. The IEC 61850 standards The IEC 61850 series of standards covers communications as a whole at process, field control and station control level, and includes both operation and engineering. This comprehensive application of standards enables smooth communication between systems from different manufacturers, and reduces the time spent on configuration. Moreover, the standard creates long-term flexibility, as the applications are no longer tied to a particular communication technology. Therefore, traditional communication based on point-to-point connections is currently being replaced to an increasing extent by modern network communications based on Ethernet and TCP/IP. This gives rise to considerable savings potentials for operators. IDS SAS equipment and system technology IDS SAS offers a comprehensive solution portfolio for digital station automation based on IEC 61850, as shown by a glance at the possible system configuration (see illustration below). Network control layer (IEC60870-5-101/104 or proprietary protocol) System architecture

The modular, scalable system concept is based on the IDS 650 and IDS 850 device families, which are employed at both field and station level. An IDS HIGH-LEIT control system is used as the station operator terminal. The IDS ACOS ET graphic engineering tool is provided for engineering and diagnosis. Communication with the network control level takes place using the IEC 60870-101/104 standards or manufacturer-specific procedures. Features of the IDS implementation Flexible device modeling True to its modular, scalable system design, the IDS implementation of the IEC 61850 provides maximum degrees of freedom with regard to device modeling. The standard defines approximately 92 logical nodes which depending on the application can be combined to form logical and physical devices. In the IDS implementation, these logical nodes can be distributed among the logical and physical devices with absolute freedom. Likewise, there are no restrictions whatsoever regarding the assignment of operationrelevant information to context-specific IEC- 61850 objects or attributes. Dynamic report functions Static and dynamic reports are supported, enabling simple, rapid configuration both in the engineering phase and during plant operation. Inter-device communication As communication is assisted by GOOSE (Generic Object Oriented Substation Event), information can be exchanged with high priority between devices (IEDs Intelligent Electronic Devices). Interoperability A connection to other-make IEC 61850 systems can be established without problem, both as server (connection to other-make systems) and as client (connection from other-make devices). IDS 650 The IDS 650 system is currently the most compact IEC 61850 system available on the market. It can be employed as a field unit (server) and a station unit (client). Typical applications are its use both as a central station unit and gateway, and a field unit for controlling and monitoring medium-voltage systems. Flexible device modeling: Example message Machine tripping voltage transformer

The network interface can be operated in accordance with IEC 61850 (Server and Client) and via IEC 60870-5-104 (Server and Client). Apart from the Ethernet port, there are two RJ45 jacks as serial interfaces are available on the module as serial interfaces; they support the communication standards IEC 60870-5-101/-103 and Modbus Master. IDS 650 compact system The IDS 650 system in brief: GOOSE-compatible SAS and PLC function (IEC 61131) Time synchronization via SNTP / NTP Gateway to IEC 60870-5-101 /-104 and proprietary systems Proxy gateway from IEC 60870-5-103 systems 1 ms time accuracy Fault data concentration IDS 850 The IDS 850 modular, scalable system can be used without restriction both at field and station level. Typical examples of applications are its use as a field unit for high and ultra-high voltage systems, communication nodes and gateways to IEC 60870-5-101 /-104 and proprietary systems. Ethernet communication module As the Ethernet communication module in the IDS 650 system, a powerful communication processor with 10/100 mbits per s Ethernet connection, in the form of the CC68A, is used. The heart of the processor component is a type MPC852T PowerPC chip with 64 MB RAM. Serial communication interface COM RUN ERR RES COM1/2 ETHERNET Status LED Reset-Taster Ethernet interface IDS 850 system The IDS 850 system in brief: GOOSE-compatible SAS and PLC function (IEC 61131) Time synchronization via SNTP / NTP Gateway to IEC 60870-5-101 /-104 and proprietary systems Proxy gateway from IEC 60870-5-103 systems Universal connection of other-make systems 1 ms time accuracy Fault data concentration CC68A communication processor

Ethernet communication modules OC88A In the 850 system, too, the CC88A Ethernet communication module and OC88A fiberoptic version are available as highperformance communication processors based on PowerPC (also equipped with MPC852T with 64 MB RAM). Status LED Ethernet interface Twisted Wire Ethernet interface optical TX RX SERVICE 1 2 3 4 L A TX1 Switch Service interface Status LED LINK/ACTIVITY The CC88A module has a 10/100 mbits per s Ethernet connection, which is connected to an RJ45 jack by means of a shielded CAT5 cable. As in the 650 system, communication is achieved either via IEC 61850 server and client or IEC 60870-5-104 server and client. Furthermore, four serial interfaces are provided, on which various data link protocols can be run. The communication standards IEC 60870-5-101/ -103 and Modbus Master are supported. Communication interface RxD/TxD LWL OC88A communication processor Flexible network structures IDS SAS enables you to create diverse network structures, which satisfy the most demanding requirements in terms of availability. RX1 TX2 RX2 TX3 RX3 TX4 RX4 CC88A Status LED Reset-Taster Service interface SERVICE COM 1-4 serial communication interface Possible network structures Ethernet interface ETHERNET Migration solutions CC88A communication processor The OC88A communication processor functions in an identical manner to the CC88A. The difference consists in the fact that the Ethernet connection can be operated either via the RJ45 jack or via an optical fiber-optic ST interface. The interface is switched over by the software. The serial communication interfaces also take the optical form in the OC88A module. IDS SAS offers various solutions for the stepby-step introduction of the IEC 61850 standard in existing systems, and these enable existing equipment to be reused and even permit the integration of devices from other manufacturers. With this concept, users can enjoy comprehensive support, from the formulation of the migration strategy right up to its implementation using intelligent gateway functions. All aspects of migration are supported, from the replacement of individual devices through the upgrading of existing systems to the complete system retrofit.

Gateway and proxy solutions Different gateway and proxy solutions enable IDS SAS to be linked to other-make systems or existing protective relaying based on IEC 60870-5-103 to be integrated. These solutions have a functionality that greatly exceeds the pure application of protocols. They provide: Completely separate protocol stacks Backup storage of data Fault log conversion to COMTRADE FTP and web server function The gateways are available as integrated system functions or as autonomous components (dedicated gateways). Engineering One of the IEC 61850 standard s major features is that in addition to operation, it also includes engineering in the application of the standard. In other words, not only has a uniform data model for the communication of operating information been created - now, for the first time, a uniform, standardized descriptive formalism exists for the configuration of equipment and the entire substation. The descriptive language SCL (Substation Configuration Language) is used as the formal representation of information. Requirement data System - spezification Function - spezification Communication (IEC 61850) Application System - konfiguration Function - configuration Steps in IDS system and device configuration Devicespezifikation Deviceparamete - rization The following individual steps are carried out during system and device configuration, with the assistance of the tools SCT and IDS ACOS ET: Communication level: System specification During this step, the primary technology is input and linked to the secondary technology. In practical terms, this is achieved by entering the primary system graphically in the form of single-line diagrams with the aid of the SCT tool. Next, the functions of the secondary technology are defined and linked to the primary system. The result of this system specification phase is the SSD (Substation Specification Description) file. Application level: Function specification On the application level, the applicationspecific data models are constructed on the basis of functional and operational requirements. Here, it is necessary to define which information is to be exchanged between the devices, in order that switching devices throughout field level can be locked, for example. Communication level: Device specification The application-specific data model is mapped in line with the IEC 61850 in a device-based manner in the form of ICD (IED Capability Description) files using the IDS ACOS ET engineering tool. Communication level: System configuration During this step, a system configuration is derived from the system and device configurations. The SSD and ICD files are imported into SCT for this purpose. Here, the communication services are configured (compilation of reports and their transmission parameters). This step produces the SCD (Substation Configuration Description) file.

Application level: Function configuration with ACOS ET Application level: Function configuration The individual functions of the application are now configured using the IDS ACOS ET engineering tool (locking functions, control rights, switching sequences... ) and process and function parameters are set. Other engineering components The IDS ACOS ET engineering tool lends support to users beyond the parameterization of system and devices. On the one hand, it produces detailed documentation in the form of circuit diagrams, test documents and SCL system configurations (SCD files); on the other hand, it provides an array of testing and diagnostic functions (tracing, simulation). Device parameterization During the concluding device parameterization, the system configuration (the SCD file from SCT) is imported into IDS ACOS ET and the device-specific CID part (CID = Configured IED Description) is transmitted to the respective device together with the function configuration. Device parameterization with IDS ACOS ET

Application examples Central station unit and gateway for MS systems 101 104 Signals The task of the field unit is the acquisition of galvanic process information such as state information, measured values and commands. A transfer initiated by the higher-level protective device is transmitted to the field unit via GOOSE, where it results in the tripping of the circuit-breaker. Station automation system for highvoltage systems 101 104 X IEC 61850 X X X Signals IEC 61850 The combined protective devices are connected to the IDS 650 station unit by means of a network ring with IEC 61850. The station unit records further pieces of galvanic process information via I/O modules. Moreover, the station unit maps the IEC 61850 information and services on the network control center data link in accordance with IEC 60870-5- 101/-104. Fault logs are gathered centrally from the protective devices and made available in the station unit for retrieval by file transfer. Field unit for low-voltage supplies with transfer function Station unit MS 103 103 The IDS 850 field units are connected to the IDS 850 station unit via a network ring with IEC 61850. Existing protective devices with IEC 60870-5-103 interface are integrated in the IEC 61850 station bus by means of the proxy function of the field units. The station unit maps the IEC 61850 information and services on the network control center data link in accordance with IEC 60870-5-101 /- 104, or on proprietary protocols. Further devices/systems can be connected to the station unit. Goose Signals, commands NS IDS GmbH November 2007, IDS GmbH Ettlingen. We reserve the right to make technical changes. Nobelstraße 18 D-76275 Ettlingen Postfach 10 05 06 D-76259 Ettlingen Tel. +49 7243 218-0 Fax +49 7243 218-100 E-Mail: info@ids.de Internet: www.ids.de 09097 VPM.10351.