S Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions

Similar documents
S Reclosers Form 4C Microprocessor-Based Recloser Control KME (120V) and KME (240V) Analog Current Metering Accessory Design II

S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME

S Reclosers. Contents. Form 6 Recloser Control Disassembly, Reassembly, and Testing Instructions

S Reclosers. Contents. Form 4C Recloser Control Protocol Conversion Kits KME , -7002, and Installation Instructions

S Sectionalizers Types TVS15 and TVS27 Time Voltage Sectionalizer Installation and Operation Instructions. Contents

COOPER POWER SERIES. Form 4C microprocessor-based recloser control standard and automation power supply kit installation and operation instructions

COOPER POWER SERIES. RS-485 digital communications accessory board installation and operation instructions. Voltage Regulators MN225074EN

Wiring Inside the card reader you will see a circuit board. The connections are as follows:

PS/IO Circuit Board Retrofit

COOPER POWER SERIES. Input/Output (I/O) module installation instructions. Voltage Regulators MN225067EN

S Sectionalizers

COOPER POWER SERIES. DC motor operator control installation and operation instructions. Padmounted Switchgear MN285018EN

INSTALLATION INSTRUCTIONS

XDBKITS5 Bus / DB Terminal Kit (Size 5) Installation Manual DPD00116

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

Troubleshooting Guide

MODEL SST3-MV INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST3-MV SELECTABLE SIRENTONE-MULTI VOLT

S Reclosers Types NOVA 15, NOVA 27, and NOVA 38; Three-Phase Microprocessor-Controlled; Installation and Operation Instructions.

Connecting a Cisco Input Module

AutoScan to MultiScan Replacement Kit

MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS

Installation Instructions

AC300/AC400 SERIES DYNAMIC BRAKING and ADDITIONAL FORM C RELAY. INSTALLATION INSTRUCTIONS Document Number:

GV3000/SE AC Drive ControlNet Network Communication Option Board M/N 2CN3000

GPIB-232CT-A IBCL EPROM Installation Guide

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

Installation & Operation Guide

Source-Transfer Application Guide

CONNECTOR AND RECEPTACLE WIRE/CABLE ASSEMBLY INSTRUCTIONS

CONTACTOR DRIVER BOARD. DS200CDBAG1A and DS200CDBAG1B

CONSOLE CONNECTOR KIT 9501 INSTALLATION INSTRUCTIONS

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter

Multi Unit Enclosed Meter

WARNING ELECTRICAL SHOCK HAZARD

Technical Manual SMART TRAC PS Card

S Reclosers Types NOVA 15, NOVA 27, and NOVA 38; Three-Phase Microprocessor-Controlled; Installation and Operation Instructions

Removal and Installation8

This 4200-RM Rack Mount Kit is for installation in 4200-CAB series cabinets only.

AirTest Model CN9000 Series Sensor Controller

LCI AUXILIARY I/O TERMINAL BOARD DS200DDTBG_A

PoE/FPR Kit for Auto-Sync Time Clock. The Auto-Sync Time Clock is a validated time system with a Web interface and auto discovery.

Cab Box Kit Dome Plug Cab Box Cab Box Lid

ABM International, Inc. Lightning Stitch Checklist 9/13/2013

Procedure to Install an IO Expansion Cage Assembly in a Maxum II Modular Oven Analyzer

INSTALLATION INSTRUCTIONS

Installing a Power over Ethernet injector

INSTALLATION INSTRUCTIONS

Megatouch FORCE Monitor Chassis Board Replacement

ControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet

SEM3 - Embedded Micro Metering Module

Outdoor PTZ. Mounting on the Ceiling Using Pendant Mount. Installation Guide. For Models: I93, I94, I95, I96, KCM /12/03

PowerLogic High Density Metering System 1-Meter Enclosure

High Frequency Power Supply Board IS200HFPRG_A

H704-42(H)(E), H704-42/1(H)(E)

SERIES 5 TABLES/BENCH

Ink-Dot Series II Driver

Single Phase Vacuum Capacitor Switch. UltraVacLT 15kV 95kV or 125kV BIL

Installation Instructions 4291 and 4292 Keypads

Power Cable. Low-Voltage Cable

Power Supply and Fan Module Installation

Installation Instructions

AutoMax Network Communication Option Board for use with GV3000/SE AC Drives M/N 2AX3000

Voice Evacuation Control Panel Main Circuit Board Replacement Product Installation Document

Lightning Stitch Assembly

SITRANS F. Flowmeters SysCom Upgrade Kit IP65 (NEMA 4X) Multi-Channel. Introduction 1. Installing/Mounting 2. Hardware Installation Instructions

Series 3700 Screw Terminal Assemblies Installation Instructions

1. Mount the echo and tremolo control switches under the keyboard shelf, in a position convenient for the organist.

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Phenix Technologies Inc. 75 Speicher Drive Accident, Maryland 21520

This Datasheet for the IC697CHS790. Rack, 9 Slots, Rear Mount.

SPECIAL INSTRUCTIONS FOR CAPACITORS COMPACT GENERATORS

Quick Start Guide TS A

R147 WIRELESS ANTI-TWO-BLOCK INDICATOR

PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board

Ag Leader Technology Insight. Direct Command Installation Spra-Coupe 7000 Series

Phase Loss Protection Upgrade. Phase Loss Protection Upgrade. In this bulletin:

COOPER POWER SERIES. Visible-Break switch accessory operation instructions. Padmounted switchgear MN285011EN

INSTALLATION INSTRUCTIONS

FC-25/50DA Main Circuit Board Replacement Product Installation Document

S7999D SOLA Operator Interface Display

edrive RAM Battery Alternate Replacement Procedure

CONTROL MICROSYSTEMS Thermocouple Analog Input Module. Hardware Manual

Installation Instructions

INSTALLATION INSTRUCTIONS

COOPER POWER SERIES. Type GN3E and GN3VE sectionalizers installation and operation instructions

Advanced Distribution Cable Junction Box For Spectra RMS Molded-Case Circuit Breakers with Advanced Feature microentelliguard TM Trip Units

Model 2657A-LIM-3 LO Interconnect Module

Secured Series: Hub Plus Kit Single Door Controller Package Installation Manual

5504 Thermocouple Analog Input Module

EASTERN LABS. Instructions Model RM /25/2007. Operation. Junction Box Assembly. Different Types of Switch Installations

Installation Manual Updated May 2017

INCOM communications adapter module

CONTROLLER BOARD CONVERSION KIT Rev Installation Instructions Part Number: PUPKIT

ABB Drives. User s Manual. Digital I/O Extension Module RDIO-01

Marina HDMI Install Instructions

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

Rotork Fairchild PAX1 Linear Actuator User s Manual

Amano (itrt) Intelligent Twin Reader Terminal INSTALLATION MANUAL

PowerFlex DC Drive Frame B Pulse Transformer Circuit Board

Outdoor Dome. Mounting on a Tilted Wall with Gang Box (Face Down / Face Forward) Installation Guide. For Models: B81, B84, B85, B /01/13

Transcription:

Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions Cooper Power Systems Service Information S0-6- Applicable to VXE5 reclosers serial number 006 and above, VXE reclosers serial number 6 and above. Figure. SCADA I/O Board Contents Description... Safety Information... Hazard Statements... Safety Instructions... Additional Information... Connections... Kit Parts... Operation... Field Installation... Shop Testing...6 Wiring Schematic... DESCRIPTION The SCADA input/output circuit board provides remote operation and status functions for the VXE recloser control. Connections to the SCADA board are made through a 9 pin receptacle located in the bottom of the control box. Customer provided wiring and contacts allow remote operation of Lockout, Close with Cold Load Pickup, and Non-Reclose Set and Reset functions. Local operation of the non-reclose function is also possible by manually setting the appropriate switch on the control box or recloser. Neither the remote non-reclosing contacts nor the local non-reclose selector switches can override the operation of the other. The accessory also provides monitoring contacts for the purpose of remotely monitoring the recloser contact status and non-reclose status. Remote monitoring of line current is also available with the use of the SCADA accessory. A DC output current equivalent to the actual line current is available for monitoring purposes. The SCADA accessory requires either a continuous line current above amps, or the use of the internal 9 Vdc battery. April 99 New Issue Printed in USA

VXE SCADA Input/Output Board Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statements This manual contains two types of hazard statements: WARNING: Refers to hazards or unsafe practices which could result in severe personal injury, or death, and equipment damage. CAUTION: Refers to hazards or unsafe practices which could result in damage to equipment or in personal injury. Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. WARNING: Hazardous voltage. Contact with high voltage will cause severe personal injury or death. Follow all locally approved safety procedures when working around high voltage lines and equipment. G0. WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G0.0 SAFETY INFORMATION CAUTION: Recloser misoperation. The control must be removed from service prior to performing any maintenance, testing, or programming changes. Failure to comply may result in mis-operation (unintentional operation) of the recloser. T6. CAUTION: Equipment damage; misoperation. External leads must be shielded and the shield must be grounded at both ends. Terminate each lead with a GE V50LA0A metal oxide varistor (MOV), or equivalent, at the remote end. Attach MOV s between the leads and ground. Failure to properly shield and protect leads can result in equipment damage and/or unintentional operation. G. CAUTION: Follow all locally approved safety practices when lifting and mounting the equipment. Use the lifting lugs provided. Lift the load smoothly and do not allow the load to shift. Improper lifting may result in equipment damage. G06.0 Additional Information These instructions do not claim to cover all details or variations in the equipment, procedures, or process described, nor to provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user's purpose, please contact your Cooper Power Systems sales engineer. Refer to Installation and Operation Instruction S0-6- (KA0-5) for information on VXE Reclosers. TABLE Ordering Information VXE SCADA Input/Output Board Service Kit, field installed. VXE SCADA Input/Output Board, factory installed. KVXE00 KVXE56 CONNECTIONS When installed in a VXE control, the SCADA board is internally interconnected to the existing main board using supplied cables and mounting hardware. Refer to figure for a layout of the main accessory components. Leads from the customer s remote actuating and monitoring devices are connected to receptacle (P) located in the bottom of the control cabinet. An optional 9 pin cable assembly (VXE-5-ft. length) is available for direct interconnection to receptacle P.

S0-6- Figure. SCADA I/O Board Kit Parts KIT PARTS Item Part No. Description Qty.. SEC- Shield Box. SEC- SCADA Circuit Board. SEC- SCADA Control Cable Assembly. SEC- Cable Assembly Hardware Bag (Not Shown): Machine Screw, Round Head, #6-UNC-A x / Lockwasher, External Tooth, #6, Nut, Hex, Machine, #6-UNC-B Note: Above part numbers are for identification purposes only. Individual parts cannot be purchased separately. OPERATION Remote Trip to Lockout provides the ability to trip and lockout the recloser from a remote signal. Operation requires a momentary contact closure (. to SEC.) between pins D and B at receptacle P. Remote Close with Cold Load Pickup provides remote closing from lockout by a momentary contact closure (. to SEC.) between pins E and B at receptacle P. Once closed the control will be in Cold Load Pickup for the duration programmed by switch S9 on the control. Remote Non-Reclose Set provides remote non-reclosing by a momentary contact closure (. to SEC.) between pins F and B at receptacle P. The non-reclose function can be obtained in three ways:. by lowering the non-reclose handle on the mechanism;. by setting the operations to lockout switch (S) in the control to ;. by supplying a momentary contact closure to the SCADA non-reclose set pins. Any of the above three conditions will place the control in non-reclose mode independent of each other. Remote Non-Reclose Reset provides to return to normal reclosing by a momentary contact closure (. to SEC.) between pins G and B at receptacle P. Remote Recloser Open/Close Status indicator provides a dry contact closure between pins H and K at receptacle P when the recloser is closed. Contact rated amp @ Vdc. Remote Lockout Status provides a closed contact between pins L and K at receptacle P when the recloser is in LOCKOUT and a closed contact between pins M and K when the recloser is NOT in lockout. Contacts rated amp @ 0 Vdc. Remote Non-Reclose Status indicator provides a closed contact between pins J and K at receptacle P when the control is in the Reclose mode. Contacts rated amp @ Vdc. Note: Remote non-reclose status does not reflect status of local non-reclose switches. Remote Analog Current Monitor supplies a 0 to.5 ma DC signal, corresponding to 0 to 500 amps of recloser current, between pins C (+) and B ( ) at receptacle P. Output is calibrated to ±5% from 5 to 500 amps of primary current.

VXE SCADA Input/Output Board FIELD INSTALLATION. Remove the VXE control from operation.. Loosen control door screws and open the control box lid.. Refer to figure. Remove the battery cable from connector J, control cable from connector J, and control lockout indicator cable from connector J on the original circuit board. Do not bend the tabs or terminal pins on the connectors.. Remove the four mounting screws securing the circuit board to control box. Retain the screws for reassembly. Top Mounting Screws 5. Remove the circuit board and position on top of shield box as shown in figure. The box must be positioned so that the gap and terminal strips are towards the bottom and the cutouts are towards the top as shown in figure. Use the existing mounting screws removed in step to secure circuit board to box. 6. Remove plastic holes plugs from control box and install SCADA control cable assembly (SEC-). To eliminate cable twisting, install SCADA control cable (9 pin connector end) with key way towards the bottom of control box. Secure with four / machine screws and lockwashers and nuts on inside of control box. Note: If control will not be put in operation immediately, install plastic cap on end of cable connector.. In lower left hand corner of control box, remove top nut and star washer securing ground connector to control box. Add the braided wire terminal from control cable assembly to screw and reinstall star washer and nut. Move the cable assembly out of the way for SCADA board installation. MIN. TRIP (AMPS) (SUM+0) S 0 0 0 0 60 0 60 ON RECLOSE TIME (SECONDS) (SUM+) S 6 TCC TCC Circuit Board Cutout RESET TIME OPER. TO L.O. (SELECT ONE) S (SECONDS) (SUM+) S 6 6 OPER. ON TCC (SELECT ONE) S 0 MIN. RESP. ENABLE (SELECT OPERATIONS) COLD LOAD TIME (SECONDS) (SUM) S9.5 6 6 S MIN. RESP. TIME (MILLISECONDS) (SUM+0) S5 0 0 0 0 60 0 60 TCC MODIFIER (SUM) S6 TCC TCC Battery Cable Control Cable J J Control Lockout Indicator Cable J Gap Terminal Strips Bottom Figure. Mounted Circuit Board to Shield Box P Bottom Mounting Screws Figure. Programmable Circuit Board

S0-6-. Position SCADA board (SEC-9) in control box using existing mounting holes and hardware as shown in figure 5. The terminal strips should be towards the bottom and the transformer towards the top of control box. Secure board with four / machine screws and lockwashers. 9. Refer to figure 5. Connect the cable assemblies to SCADA board as follows: a. Connect original control cable (from P) to connector J0. b. Connect one end of cable assembly (SEC-) to connector J0. c. Connect SCADA control cable assembly (SEC- ) from P to. Transformer Mounting Screws 0. Position shield box/circuit board assembly into control box with terminal strips towards bottom as shown in figure 6. Secure with four machine screws and lockwashers. CAUTION: Control mis-operation. Make sure wires are not pinched or insulation cut by shield box. Damage to wire insulation could result in control mis-operation.. Connect SCADA board cable to connector J on control circuit board.. Connect control lockout indicator cable to J.. Connect battery cable to connector J. Note: If testing is not to be performed immediately, do not connect battery cable to J until testing is to be performed or control is put into operation. Battery must be disconnected when control is not in operation..test operation of the SCADA board per shop testing procedures before putting control into operation. Mounting Screws SCADA Circuit Board J0 J0 Figure 5. SCADA Board Cables J J J Do not connect battery cable to J until control is put into operation. Figure 6. Circuit Board/Box Installation 5

VXE SCADA Input/Output Board SHOP TESTING The functional testing of the VXE Control SCADA I/O circuit board will require connection to a properly operating VXE recloser. A high current source and manual closing handle will also be required. Note: The manual closing handle will only be required for VXE reclosers where potential closing power is not readily available. Reference VXE installation manual S0-6- for further information on using closing handle.. Initial Set-Up: a. Set control dip switches as follows: S = 50 amps...min-trip S = operations...operations to Lockout S = operations...operations on TCC S = All Off...Min-Response Enable S5 = 0 ms (all off)...min-response Time S6 = All Off...TCC Modifier S = seconds...reclose Time S = 9 seconds...reset Time S9 = 0 seconds (all off)...cold Load Pickup Time b. Verify that both TCC plugs are properly installed on the control circuit board. c. Connect control to VXE recloser. d. Verify non-reclose handle is in the up (reclose) position on recloser. e. Connect the control battery to the J connector.. Remote Recloser Open/Close Status: a. Open Status: with the yellow manual operating handle of the recloser pulled to the lockout position, check for an open circuit between pins H and K at receptacle P. b. Manually close the recloser. The de-energized recloser is manually closed by raising the yellow manual operating handle to the closed position and using the manual closing tool to rotate the main operating shaft of the recloser mechanism 90. c. Closed Status: check for continuity between pins H and K at connector P.. Remote Trip to Lockout: a. With the recloser closed, momentarily short pins D and B at receptacle P. Verify that the recloser opened and the lockout indicator flag on the bottom of the control box indicates lockout.. Remote Close: a. With the recloser open and the yellow manual operating handle in the closed position, momentarily short pins E and B at receptacle P. If the recloser has closing power available, unit should close. For units without closing power, listen for an audible thump inside the recloser which indicates the reclose mechanism has been properly energized. Yellow handle should drop in approximately 0 seconds indicating an under voltage lockout. 5. Remote Lockout Status: a. Recloser Lockout Status: with the recloser in a lockout state, check for continuity between pins L and K at receptacle P. b. Manually close recloser. The de-energized recloser is manually closed by raising the yellow manual operating handle to the closed position and using the manual closing tool to rotate the main operating shaft of the recloser mechanism 90. c. Recloser Status Not Locked Out: check for continuity between pins M and K at receptacle P. 6. Remote Non-Reclose Set: a. With the unit closed, momentarily short Pins F and B at receptacle P. b. Apply 00 amps of current through the recloser and verify that the recloser trips OPEN time and the lockout flag indicates on the bottom of the control box.. Remote Non-Reclose Reset: a. With the control still in a locked out condition, momentarily short pins G and B at receptacle P. b. Manually close recloser (no load current applied). c. Again apply the 00 amp load current to the recloser. The recloser should operate through program sequence. Note: Because primary closing power may not be available, manual closing with the use of the closing tool may be required after each trip operation. Listen for an internal thump inside the recloser, once heard use the manual closing tool to close recloser.. Remote Non-Reclose Status: a. Remote non-reclose status is verified by checking for an open circuit between pins J and K at receptacle P when the unit is in the non-reclose mode, and a closed contact between pins J and K when the unit is in the normal reclose mode. 9. Remote Analog Current Monitor: a. Set control min-trip, switch (S) to 0 amps (position 6 only in ON position). b. Manually close the recloser. c. Calibrate primary current source to 50 amps. d. Connect a 0-00 micro amp DC ammeter between pins C (+) and B ( ) at receptacle P. Verify that ammeter reads between 5 and 55 micro amps. 0. If control or SCADA board fails to perform properly, double check all wiring connections and re-test. If control or SCADA board still fails to operate properly, contact your Cooper Power Systems sales engineer or the Kyle Service Department. 6

S0-6- JMP L.mH,A L5.mH,A K 9 C.uF C.uF L.mH,A L6.mH,A D 9 N00 D N00 0 L L.mH,A C.uF.mH,A RESET SET K 5 K 6 K 0 K D N00 K K D N00 K C9 uf 5V 0 R C0 uf 5V 0 R J0 K J0 J0 J0 D5 N5A W V NON-RECLOSE STATUS READ (OPEN IN NON- RECLOSE MODE) JMP C 0uf 0V 0f CLOSE S.C. RETURN K (P-N) C5 0 STATUS READ COMMON OPEN/CLOSED (5A) STATUS READ R6 K C 0uf 0V 0f uf 0 C6 uf 0 C D N00 R K K 0 D N00 R K K 5 SET L.mH,A 5 6 uf 5V 0 C N00 R9 K K 0 6 RESET uf 5V 0 K D0 N00 R0 K K 9 C uf 05A R R /W W R.5K /W W V V50LA0A R5 (P-A) (P-D) (P-E) (P-F) (P-G) (P-L) (P-M) (P-C) (P-B) D T D6 R 6.K /W D D N5A V W W (P-J) (P-K) (P-H) L.mH,A C 0uf 0V 0f D9 50K 9.K RTU POWER (9-0VDC) TRIP (TO LOCKOUT) S.C. CLOSE (WITH COLD LOAD PICKUP)S.C. NON-RECLOSE SET S.C. NON-RECLOSE RESET S.C. LOCKOUT S.R. (N.O.) (CLOSED IN LOCKOUT) LOCKOUT S.R. (N.C.) (OPEN IN LOCKOUT) D J0 6 J0 6 J0 J0 J0 J0 J0 J0 J0 5 J0 5 J0 6 J0 6 J0 J0 J0 J0 J0 J0 J0 J0 J0 J0 J0 J0 K C.T. :00 ANALOG CURRENT MONITOR RTU COMMON Wiring Schematic

VXE SCADA Input/Output Board Cooper Power Systems 99 Cooper Power Systems, Inc. Kyle is a registered trademark of Cooper Industries, Inc. Quality from Cooper Industries P.O. Box 50, Pittsburgh, PA 50 KA0-90