DEIF A/S. Description of options. Option C1 Generator add-on protection package Multi-line 2 version 2. Description of options. Functional description

Similar documents
DEIF A/S. Description of options. Option C2, Generator add-on protection package Automatic Gen-set Controller. Description of option

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options

DEIF A/S. Description of options. Option P1, Event and alarm printer Automatic Gen-set Controller. Description of option. Functional description

Option H10, Multi-line 2 unit with USB service port. To be used when the multi-line 2 unit service port is USB type

MULTI-LINE 2 APPLICATION NOTES. Converting PPU-2 to PPU-3 Parameter conversion Wiring Options I/O list. Document no.: A SW version:

Compact Genset Controller, CGC 400 What's in the delivery? The first steps Push-buttons and LEDs

Option P1 Event and alarm printer Description of option Functional description Parameter list

AGC 200 Advanced Gen-set Controller What s in the delivery? Getting started The first steps Using the AGC 200

Option X4 Additional Operator Panel AOP-2 Description of option Functional description

Automatic Genset Controller, AGC-3 What's in the delivery Getting started The first steps Using the AGC

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

APPLICATION NOTES H-coupling

Automatic Genset Controller, AGC-4 What s in the delivery? Getting started The first steps Using the AGC

QUICK START GUIDE Generator Paralleling Controller, GPC-3 Generator Protection Unit, GPU-3/GPU-3 Hydro Paralleling and Protection Unit, PPU-3

DEIF A/S. Description of options. Option H4 Serial comm. CAT CCM communication Multi-line 2 version 2. Description of option Functional description

Getting started - USW 3.x Software download from internet Software installation Device setup Data backup

OPERATOR'S MANUAL Generator Paralleling Controller, GPC-3 - Generator Protection Unit, GPU-3/GPU-3 Hydro - Paralleling and Protection Unit, PPU-3

MULTI-LINE 2 APPLICATION NOTES

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Option M2 Configurable engine control cards Multi-line 2 version B SW version 2.4X.X

Multi-instrument Communication, MIC-2 MKII DIN Quick Start Guide

Engines & Gen-sets N, page 1 of 6

APPLICATION NOTES Translations

Inverter Interface Interface examples Wiring examples Communication topology

CODESYS v. 2.3, Ethernet driver for AGI 3xx Use the CODESYS Ethernet driver in the AGI Creator Set up the CODESYS for use with the AGI Creator

Option H3 Serial communication Profibus DP

Genset control and protection with safety system

Generator Protection Unit, GPU Hydro Multi-line A SW version 2.4X.X

QUICK START GUIDE Generator Protection Unit GPU 300

APPLICATION NOTES DELOMATIC 4, DM-4 GAS/HYDRO

Option H8.x and H12.x External I/O modules Description of option Functional description

MULTI-LINE 2 DESCRIPTION OF OPTIONS

QUICK START GUIDE Paralleling and Protection Unit PPU 300

QUICK START GUIDE Paralleling and Protection Unit PPU 300

SPARE PART ONLY. Basic Gen-set Controller Multi-line H SW version 2.31.X or later. Data sheet. Standard functions

Basic Gen-set Controller multi-line F SW version 2.31.X or later

DEIF A/S. Generator Paralleling Controller multi-line L. Type GPC / GS. Compact system in one unit

Compact Genset Controller, CGC 200 Mounting Terminals and wiring Commissioning, using the Utility Software and/or the front panel

Advanced Graphical Interface, AGI 100

MULTI-LINE 2 APPLICATION NOTES. Converting PPM-2 to PPM-3 Parameter conversion Wiring Options I/O list Modbus. Document no.: A SW version:

EAP 300 REMOTE ANNUNCIATOR INSTALLATION MANUAL. r.0454a

Basic Gen-set Controller G (UK) SW version 2.1X.X. Terminal strip overview

Installation Manual. Multi Power Controller MPC-1 multi-line D

AGC 200 Automatic Advanced Gen-set Controller DATA SHEET

for Energy and Power meters AEM and APM with Modbus interface

Automatic Gen-set Controller Multi-line D

Delomatic 4, DM-4 Marine & Offshore DATA SHEET

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S

Generator Protection Unit, GPU-3 DATA SHEET

MIC-2 Multi-instrument DATA SHEET

Application Note (Revision NEW) Original Instructions. EGCP-2 Differences

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

Engine Controller EC-1

Generator Controller GC-1

No longer for sale. Generator Controller GC-1. Data sheet. Standard functions

Generator Paralleling Controller, GPC-3 DATA SHEET

MIC-2 MKII I/O module user s manual

Generator Protection Unit, GPU-3 DATA SHEET

Compact Genset Controller, CGC 400 Generator control and protection Engine monitoring and protection Generator and mains breaker control RS485 Modbus

APPLICATION NOTES. Advanced Graphical Interface - AGI Internal PLC (CODESYS V3) SHENDONG

TYPE APPROVAL CERTIFICATE

TT /12b INSTALLATION INSTRUCTIONS. Introduction

PPU Power Management (PPM)

Generator Controller GC-1F

DEIF A/S. TAS-331DG Selectable AC transducer G (UK) Installation and start up instructions. Watt or var transducer

INSTALLATION INSTRUCTIONS

MULTI-LINE 2 DESCRIPTION OF OPTIONS. Option N Modbus TCP/IP SMS/ alarms NTP time synchronisation. Document no.: D SW version:

MULTI-LINE 2 DESCRIPTION OF OPTIONS. Option N Modbus TCP/IP SMS/ alarms NTP time synchronisation. Document no.: C SW version:

PARAMETER LIST DELOMATIC 4, DM-4 GAS CHP CONTROLLER

Advanced Genset Controller, AGC 200 Operation modes Display and unit front General Engine control M-Logic Optional applications

DATA SHEET Selectable AC transducer, TAS-331DG

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Monitoring Technique. VARIMETER PRO Multifunction Measuring Relay MK 9300N, MH 9300

Using the proconx GCP-MG Communication Gateway with the GCP-30 and LS-4 Controls. Application Note 51306

Description of options. user s manual. DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: Fax:

NOT RECOMMENDED FOR NEW DESIGNS

EGCP-3 LS Revision R Software Revision M. Application Note (Revision NEW, 6/2009) Original Instructions

Multiple Generator Automatic Synchronising System

AGC 200 Advanced Gen-set Controller DATA SHEET

DATA SHEET Compact Genset Controller, CGC 200

Application Note (Revision NEW) Original Instructions. Using the proconx GCP-MG Communication Gateway with the GCP-30 and LS-4 Controls

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

VMD420-DM Voltage and frequency monitor

Content FPC 200. USER MANUAL Mar Feeder F1 and F3 Motor M1 and M3 Busbar B2 and B3 Transformer T1 and T3

Genset Controller Unit Model EMS - GC10. Installation Manual Section

STARDELTA-EN - User Manual

FP6000. Type ID Units Writable Possible Values. Count. TCP Register

Galaxy Shore Connection 500 kva. Operation 04/

Delomatic 4, DM-4 Land DATA SHEET

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

Industrial motor controller for brushed DC motors 24 VDC

REACTIVE ENERGY REGULATORS

PPM Protection and Power Management DATA SHEET

Installation Instructions

DATA SHEET Selectable AC transducer, TAS-321 DG

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

GC2000 Generator Controller Power Management and Protection

ILUMEN PID SOLUTION INDOOR OUTDOOR ILUMEN PIDBOX MINI INSTALLATION MANUAL. Ilumen PIDbox mini Version 1.5

Content FPC 400. USER MANUAL Apr Feeder F3 Motor M4 Busbar B3 Transformer T4

DATA SHEET Genset Controller, GC-1F

Transcription:

Description of options Option C1 Generator add-on protection package Multi-line 2 version 2 4189340267E SW version 2.42.X Description of options DEIF A/S Functional description Parameter list DEIF A/S, Frisenborgvej 33 Tel.: +45 9614 9614, Fax: +45 9614 9615 DK-7800 Skive, Denmark E-mail: deif@deif.com, URL: www.deif.com

Table of contents 1. WARNINGS AND LEGAL INFORMATION... 3 LEGAL INFORMATION AND RESPONSIBILITY... 3 ELECTROSTATIC DISCHARGE AWARENESS... 3 SAFETY ISSUES... 3 DEFINITIONS...3 2. DESCRIPTION OF OPTION... 4 C1 OPTION... 4 3. FUNCTIONAL DESCRIPTIONS... 5 VOLTAGE AND FREQUENCY... 5 ALARM INHIBIT... 5 4. PARAMETER LIST... 6 PARAMETER TABLE DESCRIPTION... 6 FAST OVERCURRENT PROTECTION... 6 VOLTAGE PROTECTIONS... 7 FREQUENCY PROTECTIONS... 8 OVERLOAD PROTECTION... 9 CURRENT UNBALANCE PROTECTION... 9 VOLTAGE ASYMMETRY PROTECTION... 10 VAR IMPORT (LOSS OF EXCITATION) PROTECTION... 10 VAR EXPORT (OVEREXCITATION) PROTECTION... 10 This paper relates to multi-line 2 ver. 2 PPU/GPU/GPC units with application software version 2.42.1 or later. DEIF A/S Page 2 of 10

1. Warnings and legal information Legal information and responsibility DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the generator set controlled by the unit, the company responsible for the installation or the operation of the set must be contacted. The units are not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost. Electrostatic discharge awareness Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary. Safety issues Installing the unit implies work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment. Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death. Definitions Throughout this document a number of notes and warnings will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text. Notes The notes provide general information which will be helpful for the reader to bear in mind. Warning The warnings indicate a potentially dangerous situation which could result in death, personal injury or damaged equipment, if certain guidelines are not followed. DEIF A/S Page 3 of 10

2. Description of option C1 option Option C1 is a software option and therefore not related to any hardware apart from the standard-installed hardware. Option C1 is a mix of frequency, voltage, overload, overcurrent, unbalance alarms and reactive power import/export protections as follows: Protection ANSI no. Overvoltage 59 Undervoltage 27 Overfrequency 81 Underfrequency 81 Overload 32 Fast overcurrent 50/51 Current unbalance 60 Voltage asymmetry 60 Loss of excitation (reactive power import) 40 Overexcitation (reactive power export) 40 DEIF A/S Page 4 of 10

3. Functional descriptions Voltage and frequency Voltage and frequency is set in % of nominal generator value. The delay s are all of the definite time type, meaning that a set point and time is selected. If the function is e.g. overvoltage, then the timer will be activated, if the set point is exceeded. If the voltage value goes below the set point value before the timer runs out, then the timer will be stopped and reset. Set point Timer Measured value Timer start Timer reset Timer start Alarm Time When the timer runs out, the output is activated. The total delay will be the delay + the reaction time. Alarm inhibit Some of the alarms included in the option C1 can be inhibited in order to avoid nuisance alarms during controlled conditions such as start/stop of the gen-set and breaker operations. For general information about the inhibit function, please refer to the Designer s Reference Handbook. DEIF A/S Page 5 of 10

4. Parameter list Parameter table description The table consists of the following possible adjustments: Set point: Timer: The alarm set point is adjusted in the set point menu. The is in Hz/sec. The timer indicates the duration of the period between the alarm situation and the alarm occurrence. Relay output A: A relay can be activated by the output A. Relay output B: A relay can be activated by the output B. Enable: The alarm can be activated or deactivated. ON means always activated, RUN means that the alarm has run status. This means it is activated when the running signal is present. For further information about the structure of the parameter descriptions, please see the Designer s Reference Handbook. Fast overcurrent protection Alarm s relate to the nominal current (menu 4013). 1070 Generator fast overcurrent 1 protection 1071 Fast overcurr. 1 Set point 150.0% 350.0% 150.0% 1072 Fast overcurr. 1 Delay 0.0 s 100.0 s 0.0 s 1073 Fast overcurr. 1 Relay output A R0 (none) Option R1 (relay 1) 1074 Fast overcurr. 1 Relay output B R0 (none) dependent R0 (none) 1075 Fast overcurr. 1 Enable OFF ON ON 1080 Generator fast overcurrent 2 protection 1081 Fast overcurr. 2 Set point 150.0% 350.0% 150.0% 1082 Fast overcurr. 2 Delay 0.0 s 100.0 s 1.0 s 1083 Fast overcurr. 2 Relay output A R0 (none) Option R1 (relay 1) 1084 Fast overcurr. 2 Relay output B R0 (none) dependent R0 (none) 1085 Fast overcurr. 2 Enable OFF ON ON DEIF A/S Page 6 of 10

Voltage protections Alarm s relate to the nominal voltage (menu 4014), phase-phase measurements. 1100 Generator high voltage 1 protection 1101 Gen. high volt. 1 Set point 90.0% 120.0% 103.0% 1102 Gen. high volt. 1 Delay 0.1 s 100.0 s 10.0 s 1103 Gen. high volt. 1 Relay output A R0 (none) Option R0 (none) 1104 Gen. high volt. 1 Relay output B R0 (none) dependent R0 (none) 1105 Gen. high volt. 1 Enable OFF ON OFF 1110 Generator high voltage 2 protection 1111 Gen. high volt. 2 Set point 90.0% 120.0% 105.0% 1112 Gen. high volt. 2 Delay 0.1 s 100.0 s 5.0 s 1113 Gen. high volt. 2 Relay output A R0 (none) Option R0 (none) 1114 Gen. high volt. 2 Relay output B R0 (none) dependent R0 (none) 1115 Gen. high volt. 2 Enable OFF ON OFF 1120 Generator low voltage 1 protection 1121 Gen. low volt. 1 Set point 80.0% 100.0% 97.0% 1122 Gen. low volt. 1 Delay 0.1 s 100.0 s 10.0 s 1123 Gen. low volt. 1 Relay output A R0 (none) Option R0 (none) 1124 Gen. low volt. 1 Relay output B R0 (none) dependent R0 (none) 1125 Gen. low volt. 1 Enable OFF ON OFF 1130 Generator high voltage 2 protection 1131 Gen. low volt. 2 Set point 50.0% 100.0% 95.0% 1132 Gen. low volt. 2 Delay 0.1 s 100.0 s 5.0 s 1133 Gen. low volt. 2 Relay output A R0 (none) Option R0 (none) 1134 Gen. low volt. 2 Relay output B R0 (none) dependent R0 (none) 1135 Gen. low volt. 2 Enable OFF ON OFF DEIF A/S Page 7 of 10

Frequency protections Alarm s relate to the nominal frequency (menu 4011). 1140 Generator high frequency 1 protection 1141 Gen. high freq. 1 Set point 90.0% 120.0% 103.0% 1142 Gen. high freq. 1 Delay 0.2 s 100.0 s 10.0 s 1143 Gen. high freq. 1 Relay output A R0 (none) Option R0 (none) 1144 Gen. high freq. 1 Relay output B R0 (none) dependent R0 (none) 1145 Gen. high freq. 1 Enable OFF ON OFF 1150 Generator high frequency 2 protection 1151 Gen. high freq. 2 Set point 90.0% 120.0% 105.0% 1152 Gen. high freq. 2 Delay 0.2 s 100.0 s 5.0 s 1153 Gen. high freq. 2 Relay output A R0 (none) Option R0 (none) 1154 Gen. high freq. 2 Relay output B R0 (none) dependent R0 (none) 1155 Gen. high freq. 2 Enable OFF ON OFF 1160 Generator low frequency 1 protection 1161 Gen. low freq. 1 Set point 80.0% 100.0% 97.0% 1162 Gen. low freq. 1 Delay 0.2 s 100.0 s 10.0 s 1163 Gen. low freq. 1 Relay output A R0 (none) Option R0 (none) 1164 Gen. low freq. 1 Relay output B R0 (none) dependent R0 (none) 1165 Gen. low freq. 1 Enable OFF ON OFF 1170 Generator low frequency 2 protection 1171 Gen. low freq. 2 Set point 80.0% 100.0% 95.0% 1172 Gen. low freq. 2 Delay 0.2 s 100.0 s 5.0 s 1173 Gen. low freq. 2 Relay output A R0 (none) Option R0 (none) 1174 Gen. low freq. 2 Relay output B R0 (none) dependent R0 (none) 1175 Gen. low freq. 2 Enable OFF ON OFF DEIF A/S Page 8 of 10

Overload protection Alarm s relate to the nominal power (menu 4012). 1260 Generator overload 1 protection 1261 Overload 1 Set point 10.0% 200.0% 100.0% 1262 Overload 1 Delay 0.1 s 100.0 s 10.0 s 1263 Overload 1 Relay output A R0 (none) Option R2 (relay 2) 1264 Overload 1 Relay output B R0 (none) dependent R0 (none) 1265 Overload 1 Enable OFF ON OFF 1270 Generator overload 2 protection 1271 Overload 2 Set point 10.0% 200.0% 110.0% 1272 Overload 2 Delay 0.1 s 100.0 s 5.0 s 1273 Overload 2 Relay output A R0 (none) Option R2 (relay 2) 1274 Overload 2 Relay output B R0 (none) dependent R0 (none) 1275 Overload 2 Enable OFF ON OFF 1390 Generator overload 3 protection 1391 Overload 3 Set point 10.0% 200.0% 120.0% 1392 Overload 3 Delay 0.1 s 100.0 s 5.0 s 1393 Overload 3 Relay output A R0 (none) Option R2 (relay 2) 1394 Overload 3 Relay output B R0 (none) dependent R0 (none) 1395 Overload 3 Enable OFF ON OFF Overload 3 is not included in the parameter shift function. (Please refer to the Designers Reference Handbook.) Current unbalance protection Alarm s relate to the nominal current (menu 4013). 1280 Generator current unbalance protection 1281 Current unbalance Set point 0.0% 100.0% 30.0% 1282 Current unbalance Delay 0.1 s 100.0 s 10.0 s 1283 Current unbalance Relay output A R0 (none) Option R2 (relay 2) 1284 Current unbalance Relay output B R0 (none) dependent R0 (none) 1285 Current unbalance Enable OFF ON OFF DEIF A/S Page 9 of 10

Voltage asymmetry protection Alarm s relate to the nominal voltage (menu 4014). 1290 Generator voltage unbalance protection 1291 Voltage unbalance Set point 0.0% 50.0% 10.0% 1292 Voltage unbalance Delay 0.1 s 100.0 s 10.0 s 1293 Voltage unbalance Relay output A R0 (none) Option R2 (relay 2) 1294 Voltage unbalance Relay output B R0 (none) dependent R0 (none) 1295 Voltage unbalance Enable OFF ON OFF VAr import (loss of excitation) protection Alarm s relate to the nominal power in kw (menu 4012). 1300 Generator VAr import protection 1301 VAr import Set point 0.0% 150.0% 10.0% 1302 VAr import Delay 0.1 s 100.0 s 10.0 s 1303 VAr import Relay output A R0 (none) Option R1 (relay 1) 1304 VAr import Relay output B R0 (none) dependent R0 (none) 1305 VAr import Enable OFF ON OFF VAr export (overexcitation) protection Alarm s relate to the nominal power in kw (menu 4012). 1310 Generator VAr export protection 1311 VAr export Set point 0.0% 100.0% 75.0% 1312 VAr export Delay 0.1 s 100.0 s 10.0 s 1313 VAr export Relay output A R0 (none) Option R2 (relay 2) 1314 VAr export Relay output B R0 (none) dependent R0 (none) 1315 VAr export Enable OFF ON OFF DEIF A/S reserves the right to change any of the above DEIF A/S Page 10 of 10