Installation Instructions PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board!!! ATTENTION: Only qualified personnel familiar with DC drives and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage. ATTENTION: To avoid an electric shock hazard, ensure that all power to the drive has been removed before performing the following. ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference A-B publication 8000-4.5.2, uarding Against Electrostatic Damage or any other applicable ESD protection handbook. What This it Includes SCR modules (3 for non-regenerative drives, 6 for regenerative drives) Mounting screws and washers (6 for non-regenerative drives, 12 for regenerative drives) ate leads (6 for non-regenerative drives, 12 for regenerative drives) Thermal rease Static strap Important: The SCR Modules supplied with this kit should only be used in the following Frame A drives: 230V AC Input 460V AC Input Drive Current Rating Code DC Amps AC Line Amps HP Drive Current Rating Code DC Amps AC Line Amps HP 7P0 7 5.7 1.5 4P1 4.1 3.3 2 9P0 9 7.4 2 6P0 6 4.9 3 012 12 9.8 3 010 10 8.2 5 020 20 16 5 014 14 11.4 7.5 029 29 24 7.5 019 19 15.5 10 038 38 31 10 027 27 22.1 15 055 55 45 15 035 35 28.6 20 045 45 36.8 25 052 52 42.5 30
2 PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board Tools That You Need Phillips screwdriver Flathead screwdriver Nut driver or wrench for hex stand-offs Torque wrench Phillips is a registered trademark of Phillips Screw Company. What You Need to Do The SCR modules are located on the heat sink of the drive chassis, below all circuit boards and components. To install the SCR modules: Step 1: Step 2: Step 3: Step 4: Step 5: Step 6: Step 7: Step 8: Step 9: Remove power from the drive Remove the protective covers Remove the Control EMI shield and Control board Remove the Pulse Transformer and Switching Power Supply boards Remove the Power Traces board and AC Current Transducers Remove the existing SCR modules Install the new SCR modules Install the Power Traces board and AC Current Transducers Install the Pulse Transformer and Switching Power Supply boards Step 10: Install the Control EMI Shield and Control board Step 11: Replace the protective covers and document the change
PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 3 Step 1: Remove Power from the Drive! ATTENTION: Remove power before making or breaking cable connections. When you remove or insert a cable connector with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by: sending an erroneous signal to your system s field devices, causing unintended machine motion causing an explosion in a hazardous environment Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance. 1. Remove and lock-out all incoming power to the drive. L1 L2 L3 I O Step 2: Remove the Protective Covers 1. Remove the two screws that secure the power terminal cover to the drive and slide the cover down and off the drive chassis.
4 PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 2. Disconnect the DPI cable from the HIM assembly (if present). 3. Remove the screws that secure the bottom cover to the drive, then slide the cover down and off the drive chassis. = Disconnect DPI cable Tightening torque: 1.5 N m (13.3 lb in) 4. Press in on the sides at the bottom edge of the top cover and at the same time pull the cover toward you to pull it partially off the drive chassis. 5. At the top of the drive, pull the cover forward, away from the drive, until the pins fit in the keyhole in the top of the cover, then carefully lift the cover off of the drive chassis. Important: The HIM assembly is connected via a cable to the Control board and therefore will not pull free from the drive until disconnected. See page 5 for instructions. 3. 4. When metal pin fits in keyhole, lift cover off drive chassis.
PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 5 6. Disconnect the HIM Communication cable from the connector on the upper right corner of the Control board and set the cover aside. Pull tabs out to disconnect cable.
6 PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board Step 3: Remove the Control EMI Shield and Control Board Note: The SCR Modules are located on the heat sink of the drive, behind the Control, Pulse Transformer, Switching Power Supply and Power Traces boards. All of these boards must be removed in order to replace the SCR Modules. 1. Carefully disconnect the cables from connectors XA, XR and XFCD on the Control board. 2. Remove all appropriate I/O and control wiring including: digital and analog I/O plug-in terminal blocks on the Control board analog tachometer terminal block on the Control board encoder terminal block on the Control board cable shields that are grounded to the Control EMI shield I/O terminal blocks on the I/O Expansion board I/O terminal blocks on the 115V AC to 24V DC I/O Converter board = Disconnect cables from XA, XR and XFCD Disconnect I/O and control wiring Note: Control board shown with Communication Adapter and optional boards removed.
PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 7 3. Remove the four screws (and ground wire on the lower left corner of board) that secure the Control EMI shield and Control board to the chassis and slide the Control EMI shield and Control board up and out of the drive. Important: Be careful when removing the EMI shield not to pull free any of the gate leads or other cables on the Pulse Transformer circuit board below the EMI shield. Remove screws Remove screw and ground wire
8 PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board Step 4: Remove the Pulse Transformer and Switching Power Supply Boards Note: The Switching Power Supply circuit board is secured to the back of the Pulse Transformer circuit board. 1. Remove the slotted air flow plate from the top of the drive. For 38A/10 HP and 55A/15 HP drives with 230V AC input and 35A/20 HP, 45A/25 HP, and 52A/30 HP drives with 460V AC input, remove the four screws that secure the slotted air flow plate to the top of the drive, remove the fan cable from connector XV on the Switching Power Supply board and remove the plate. = Remove screws
PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 9 For all other drives, remove the two screws that secure the slotted air flow plate to the top of the drive and remove the plate. = Remove screw Air flow plate Remove screw Important: Mark all connections and wires before removal to avoid incorrect wiring during reassembly.
10 PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board Figure 1 Pulse Transformer Circuit Board Layout Components shown within dashed lines are only on the Pulse Transformer board for regenerative drives. XSW XP X3 XSW1 TR2 TR1 X4 XR XCD_IO XY TO1 TO4 TO2 TO5 TO3 TO6 O1 O4 O2 O5 O3 O6 T1 T4 T2 T5 T3 T6 1 4 2 5 3 6 XTA S4 1 1 78 79 35 36 75 76 U2 V2 FIR1-XX rev. Q and higher S3 U C V W T04 T01 04 01 T1 T4 1 4 W V C U X3 1 XSW1 1 XSW 6 1 XP 1 TR2 TR1 X4 2 XR 1 34 1 33 0V1 XY 1 T02 T05 T03 T06 02 05 03 T2 T3 T5 T6 2 5 3 6 FIR1-XX rev. P and lower 06 XTA 1 TA 78 79 35 36 75 76 U2 V2
PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 11 2. Remove the plug-in control power terminal block from the Pulse Transformer circuit board (refer to Figure 1 on page 10 for location). Remove plug-in terminal block 3. Remove the cables from connectors X3 and XP on the Pulse Transformer board (refer to Figure 1 on page 10 for location). 4. For drives with a fan, remove the cable from connector X4 on the Pulse Transformer board. Remove cables from X3 and XP Remove cable from X4 for drives with a fan 5. For Pulse Transformer boards with an armature voltage feedback terminal block, FIR1-XX, rev Q and higher, remove the connector from XCD_IO on the upper left corner of the board. X3 XSW1 XSW XP Remove connector from XCD_IO X4 TR2 TR1 XR XCD_IO XY
12 PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 6. Remove the appropriate gate leads (refer to Figure 1 on page 10 for location): For regenerative drives, remove each pair of (orange and yellow) gate lead cables from connectors 01 06 and 1 6 and push each lead through the appropriate opening in the board. For non-regenerative drives, remove each pair of (orange and yellow) gate lead cables from connectors 01 06 and push each lead through the appropriate opening in the board. Important: Remove the gate leads by grasping the connector and pulling up. DO NOT pull the gate leads off by pulling on the wires. 7. Remove the cable from connectors XTA on the Pulse Transformer board (refer to Figure 1 on page 10 for location). For regenerative drives, remove 12 gate leads and push through holes in board Remove cable from XTA For non-regenerative drives, remove six gate leads and push through holes in board Remove cable from XTA
PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 13 8. Remove the six screws that secure the Pulse Transformer board (and Switching Power Supply board) to the drive and, while lifting up slightly on the board, slide the Pulse Transformer and Switching Power Supply boards toward the top of the drive and out of the chassis. Important: The cables from connectors X4 (if present) and XTA must slide through the openings in the board as it is lifted out of the drive chassis. Take care not to damage these cables and connectors. Remove six screws Carefully route cables through openings as the board is removed. Regenerative drive shown
14 PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board Step 5: Remove the Power Traces Board 1. Remove the screws that secure the terminal lugs (if present) and power and ground wiring to terminals U, V, W, C, D and PE at the bottom of the drive. = Remove screws Note: Non-regenerative drive without terminal lugs shown. 2. Remove the six stand-offs (and the ground wire) from the Power Traces circuit board.
PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 15 3. Remove all screws and washers that secure the board to the SCR Modules and power terminal isolation strip and remove the Power Traces board from the drive. = Non-Regenerative drive Remove all screws and washers Remove six stand-offs and PE ground wire Remove six screws Regenerative drive Remove all screws and washers Remove six stand-offs and PE ground wire Remove six screws
16 PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board Step 6: Remove the Existing SCR Modules 1. Remove the two screws and washers that secure each SCR Module to the heatsink and remove the SCR Modules. = Non-Regenerative drive Remove screws Regenerative drive Remove screws Step 7: Install the New SCR Modules Install the new SCR modules in reverse order of removal as detailed in Step 6: Remove the Existing SCR Modules above. Important: Verify that each SCR Module is orientated in the same position as it was prior to removal. Important: Thermal grease must be applied to the bottom of the SCR modules before securing them to the heatsink. Use the following table to determine the proper tightening torque for the SCR Modules installed. 230V AC Input 460V AC Input Part Number Final Torque Part Number Final Torque S-20P-S7F44 2.5 4 N m (22 35.4 lb in) S-20P-S7F73 2.5 4 N m (22 35.4 lb in) S-20P-S7F45 2.5 4 N m (22 35.4 lb in) S-20P-S7F74 2.5 4 N m (22 35.4 lb in)
PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board 17 Step 8: Install the Power Traces Board Install the Power Traces board in reverse order of removal as detailed in Step 5: Remove the Power Traces Board on page 14. Verify that the connecting wire on the board is placed in the exact location as previously installed. Non-Regenerative drive Regenerative drive Use the following table to determine the proper tightening torque for the Power Traces board to SCR Modules connections. 230V AC Input 460V AC Input Part Number Final Torque Part Number Final Torque S-20P-S7F44 2.5 4 N m (22 35.4 lb in) S-20P-S7F73 2.5 4 N m (22 35.4 lb in) S-20P-S7F45 2.5 4 N m (22 35.4 lb in) S-20P-S7F74 2.5 4 N m (22 35.4 lb in) Step 9: Install the Pulse Transformer and Switching Power Supply Boards Install the Pulse Transformer and Switching Power Supply boards in reverse order of removal as detailed in Step 4: Remove the Pulse Transformer and Switching Power Supply Boards on page 8.! ATTENTION: Each gate lead cable must be connected to the exact connector from which it was removed on the Pulse Transformer circuit board or damage to the drive may occur. Step 10: Install the Control EMI Shield and Control Board Install the Control EMI Shield and Control board in the reverse order of removal as detailed in Step 3: Remove the Control EMI Shield and Control Board on page 6.
Step 11: Replace the Protective Covers and Documenting the Change 1. Replace the protective covers in the reverse order of removal as described in Step 2: Remove the Protective Covers on page 3. 2. Install the DPI cable (if present). 3. Record the installation of the new SCRs and date of installation on the Field Installed Option label on the side of the drive (as shown below). Related Documentation Allen-Bradley publications are available on the internet at www.rockwellautomation.com/literature. For... Read this document Publication Number In depth information regarding the User Manual - PowerFlex Digital DC Drives 20P-UM001 operation of PowerFlex Digital DC drives 1S7A33 www.rockwellautomation.com Power, Control and Information Solutions Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation SA/NV, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong ong, Tel: (852) 2887 4788, Fax: (852) 2508 1846 Publication 20P-IN020B-EN-P - December 2009 Supersedes 20P-IN020A-EN-P - March 2009 Copyright 2009 Rockwell Automation. All rights reserved. Printed in USA.