Circuit Breaker Operation & its load calculations

Similar documents
LED LIGHTING INRUSH CURRENT AND OVERCURRENT PROTECTION DEVICES

C C CIRCUIT-BREAKERS Moulded-case (MCCB), general. 1. Introduction. 2. General description

How to Handle Non-Linear Loads on a Power Supply

The PCI Series. Precise power control for complex SCR applications. Phase Angle Fired SCR Power Controls AMPS VAC

Section 4 Ground-Fault Protection Devices

MiCOM P124 T&D. Self and Dual Powered Overcurrent Relays

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters (1 of 2) Lecture 6 Contactors and Motor Starters

Miniature circuit-breaker versus electronic selectivity module Selective monitoring of 24 V DC load circuits

Applying branch circuit breakers and supplementary protectors in North America

Voltage Sag Simulator

CUS150M1 Instruction Manual

Power supply CP-C 24/5.0

WHITE PAPER. Overload or Short Circuit Protection? How to protect your design against both dangers. E-T-A Circuit Breakers USA. E-T-A Circuit Breakers

Bulletin 1489 Circuit Breakers. Selection Guide

F550e E-learning course Residual current devices basics RCDs Standards. ABB Group April 2, 2009 Slide 1

IELR Rail-Mount Series Magnetic Circuit Protectors

Applying branch circuit breakers and supplementary protectors in North America

DIN Series MINIATURE CIRCUIT BREAKERS, RESIDUAL CURRENT CIRCUIT BREAKERS. Introducing the DIN Series High-quality, high-performance circuit breakers

OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) OTEC Miniature Circuit Breakers (MCB) Areas of Application

Miniature Circuit-Breaker IEC Series 8562

BE1-50/51M TIME OVERCURRENT RELAY ADVANTAGES

1. Coordination of series-rated devices is permitted where indicated on Drawings.

ECE 528 Understanding Power Quality. Paul Ortmann (voice) Lecture 23

1. Micro Drive Load sharing application note

IELR Series

CP30F Series Circuit Protector for Improving Safety and Wiring Workability

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

BE1-51 BE1-51/27C BE1-51/27R TIME OVERCURRENT RELAY

Solid-State Switching Devices

ESS20 Electronic Circuit Breaker

Issued February DATA SHEET 5SX2 MCB. Based on Siemens Industrial Control Catalog

MiCOM P124. Self and Dual Powered Overcurrent Relays. Protection Relays

Voltage Dip-Proofing Inverter

ATS22C11S6U soft starter-ats22-control110vpower208v(30hp)/230v(40hp)/460v(75hp)/575v(100h

RTU500 series Data Sheet Power Supply CP-E 24/2.5

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

Ihr autorisierter Distributor: Neumüller Elektronik GmbH

selectivity module Selective monitoring of 24 V DC load circuits

ATS22C21S6U softstarter-ats22-control110vpower208v(60hp)/230v(75hp)/460v(150hp)/575v(200hp)

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. MOTOR SYMBOLS. 2010, The McGraw-Hill Companies, Inc.

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

low voltage GLOBAL CATALOGUE RANGE Motor Control Contactors - Thermal Overload Relay s - Manual Motor Starters

Relay Contact Output Modules

209/219/229 Multi-Pole Circuit Protectors 202 branch circuit applications such as EDP, air conditioners, panel boards

Power supplies CP-E, CP-S and CP-C range NEW! CP-E Range

Feeder protection relay SPAA 121 C. Product Guide

RL Line/Load Reactors

Installation Instructions

Switching Control Sentinel (SCS) TM For all ABB independent pole operated circuit breakers

Technical Requirements for High-voltage DC Power Feeding Interfaces of ICT equipment

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

Study on Power Transformer Inrush Current

ATS22D88S6U. ATS22D88S6U soft starter-ats22-control110v-power 208V(25hp)/230V(30hp)/460V(60hp)/575V(75hp) Product data sheet Characteristics.

Safety Standards. Model Number:

Table of Contents. Safety. Attention. Warnings

Voltage Dip-Proofing Inverter

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Magnetic Circuit Protectors 153. Multi-Pole Circuit Protectors 154. APL/UPL, 205/295 Barriers 155. Configurations 156. Operating Characteristics 158

ATS22C41Q soft starter-ats22-control 220V-power 230V(110kW)/ V(220kW)

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

IS Series Manual. 19 Pro Series Rack Mount (RK) Faceplate. 17 Consumer Series (C) Faceplate Available in Black (B) and Silver (S) colours

4. CIRCUIT BREAKERS. Functional Emergency Switching

NTC thermistors for inrush current limiting

ATS22D75Q soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)

MSR 2400R. Rugged Power System for Military and Heavy Duty Applications

CPS Industrial Power Supply

Safety Standards. Model Number:

ATV32HU11M2437 variable speed drive ATV32-1.1kW 200V - 1P - Bluetooth built-in - w heat sink

ATS22D75S6 soft starter-ats22-control 220V-power 230V(18.5kW)/ V(37kW)/500V(45kW)

Home Inrush Current Sensing Thermistor Tools About Video Library Blog. High Inrush Current Protection for Industrial Equipment

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

Selection Guide. Control Circuit and Load Protection. Allen-Bradley 1489-M2C020

White Paper. AC Surge Protection. Evaluation of Series Element Surge Protective Device for Protection of Electronic Equipment and Systems

APL/UPL, 205/295 Series Magnetic Circuit Protectors

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

APPLICATION NOTE. Controlling Inrush Current in DC-DC Power Converters. Inrush Current Waveform

CIRCUIT BREAKER TYPE DISCONNECTOR for OVERVOLTAGE PROTECTOR

Buffer module CP-B 24/20.0, ultra-capacitor based Accessory for power supplies (e.g. switch mode power supplies CP range)

Control Transformers Control transformers

Table of Contents. 1 General 1.1 Scope

LL1x50-E-DA. 1x50 W Dimmable DALI LED driver. 50 W V 0 / 50 Hz 60 Hz. Functional description. Mains characteristics

Combined Overcurrent and Earth-fault Relay SPAJ 140 C. Product Guide

VLT 2800 DRIVE SPECIFICATIONS

PG Softstarter Installation Manual for 5A, 9A and 16A Controllers

Understanding Solid-state relays

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04

EF

Standards Update Notice (SUN) Issued: April 25, 2017

Wiring diagrams. Content. Information for reading and graphic symbols... 5/2. Wiring diagrams of the circuit-breakers... 5/3

ELV12 Series. Instruction Manual

SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD

Capacitor Switching Contactors

VS Series 120V 600VA 300W Line-Interactive Desktop UPS, Tower, 6 Outlets

ELG4125: System Protection

Earth-fault Relay SPAJ 110 C. Product Guide

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

Always "On" UPS Systems Inc. USER MANUAL

I-Line Panelboards. Innovative design, smart bus technology, and simple installation

OVERCURRENT / GROUND FAULT PROTECTION RELAY MPRB GF. (Code ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

Series AMEPR60C-AZ up to 5A AC-DC / DC-DC LED Driver / Converter

Transcription:

Circuit Breaker Operation & its load calculations Abstract Circuit breaker is very effective protection device in any lighting application. Improper loading of MCB might lead to Nuisance Tripping, damage the application or damage the circuit breaker and even cause fire breakout. This document will drive you through the brief introduction of circuit breaker, its operation and load calculations. trip unit is temperature sensitive and the magnetic trip unit is current sensitive. These thermal and magnetic trip units are independent and act mechanically with the MCB trip mechanism to open the MCB contacts. Miniature Circuit Breaker (MCB) A circuit breaker is a protective device to protect the application during an overcurrent condition. MCB is a resettable protective device that protects against situations like Overload and Short Circuit. In other words: Under normal condition the device will carry the load current and during the fault/abnormal condition the device will automatically break and automatically reset as the fault condition is eliminated a. Cross Sectional Diagram Figure 2. Cross Sectional view to show Magnetic and Thermal Trip functions Thermal / Overload protection: Fig 1. Cross Sectional view of a MCB b. Modes of Operation Thermal and Magnetic trip definition During continuous overload condition thermal trip unit gets activated and protects the circuit. The thermal unit is comprised of a bimetal lever located behind the MCB trip bar and is in the direct current carrying path. During overload, the increased current flow heats the bimetal lever causing it to bend. As the lever bends it pulls the tripping element which opens the MCB contacts. The overload current and time required for the bimetal to bend and trip the breaker are inversely proportional. Hence, as current increases the tripping time reduces. MCB uses an electromechanical trip unit to open the contacts during an overcurrent condition. The thermal ERP Power, LLC - 1 - April 2018

Magnetic / short circuit protection: A short circuit current activates the magnetic trip function. The magnetic trip unit is comprised of an electromagnet coil, an armature and movable contact. Figure 3. Cross Sectional view to show Magnetic Trip functions With short circuit condition, a high magnitude of current passes through the coils creating a magnetic field that attracts the movable armature towards the fixed armature. The tripping lever is pushed against the movable contact and the contacts are opened. Manual Protection: User can manually control the Circuit On/Off Conditions, by dropping the operator control switch. c. Trip Curves: The tripping characteristic of MCB is plotted as tripping time Vs. current level. The curve shows the amount of time required for a MCB to trip at a given overcurrent or short circuit condition. As per IEC 60898-2, Electrical accessories Circuitbreakers for overcurrent protection for household and similar installations, Part 2: Circuit-breakers for AC and DC operation. The trip curve plotted as below, Figure 4. Trip Curve as per IEC 60898-2 The above picture defines tripping and non-tripping region. If the In-rush falls under tripping region, the MCB will trip instantaneously and Inrush current under non tripping region is safe for operation. d. MCB Types: TYPE B: The tripping limits are between 3 and 5 times the current rating of the MCB. Example: 10A MCB will trip between 30A and 50A in an overcurrent condition. TYPE C: The tripping limits are between 5 and 10 times the current rating of the MCB. Example: 10A MCB will trip between 50A and 100A in an overcurrent condition. TYPE D: The tripping limits are between 10 and 50 times the current rating of the MCB. Here applications are with products generating very high inrush currents. Such as Heavy Motors and Solenoids *Limits as per IEC/EN 60898 **Electrician s usually consider Type B for Household lighting and Type C for commercial lighting application - 2 - erp-power.com

Inrush Current Input current of short duration during initial start-up that is much greater than the operating or steady state current. We can say that during start-up LED driver draw higher than normal operating current for a short duration. This current occurs because of various capacitors distributed throughout the design. These capacitors perform different functions in the design like limit electromagnetic interference, filter switching noise, and/or store energy. By and large the greatest contributors to inrush are the energy storage capacitors. Simply put, a capacitance value times the change in voltage across it divided by the time it takes for that voltage to change causes a current pulse to flow that is of the same time duration as the voltage change. This is given in the equation below. C x V(t) / t = i(t) So if the capacitor value and voltage change are large but occur in a very short amount of time, there is a large current flow through the capacitor. That current drawn from the AC line is inrush. A turn-on at zero voltage is relatively soft. The change in capacitor voltage can be muted. In this case the inrush current is drawn during the normal change of the line voltage in the appropriate line cycle time and/or with any additional circuitry that may try to push a higher voltage in a shorter amount of time across internal capacitors; however, here the inrush will be much less than if turn-on is at 90 or 270. Of course, turn-on at the 90 maximum or 270 minimum means the change in the capacitor voltage expected is near instantaneous; hence, a large positive (at maximum) or negative (at minimum) current spike must occur that is more or less superimposed upon that which would have occurred if turn-on was at the zero voltage crossing. The inrush current spike itself has a magnitude and a width. It s normally characterized for its peak and time width (the time at which 10% magnitude occurs). It s also measured at some source impedance, the highest nominal AC line voltage of specified driver operation, full load, a nominal 25 C temperature, and a time at which it has not been recently switched on. The source impedance is a standard value given in NEMA 410. a. Waveform: LED Drivers powered by the AC line see a sinusoidal waveform (as in the figure below). There are 360 to one complete AC line cycle, just as a circle or a compass has 360. When a LED Driver is energized (start-up) by the power line, it occurs (turn-on) at approximately 1 of the 360 line cycle. In real life and with manual switches you never know what degree that turn-on will occur; but it matters. A sine wave has a peak and a trough at 90 and 270. These degrees are where the varying magnitude sine wave respectively reaches its maximum and minimum peak voltage values. Also, the 0, 180, and 360 points are where the sine wave voltage is exactly zero. Figure 6. Inrush current waveform of ESS020W-0700-24 b. Effects of high inrush current: High inrush current can create potential negative effects. NEMA 410 defines limits of acceptable inrush currents to prevent this. Usually drivers are designed to stay within the limits. The highest nominal voltage on a universal driver would be 277 Vac, this will obviously vary for drivers with other operating voltages. Full load is the normal test load. A 25 C cold start is considered worst case. Lastly, you want all the internal capacitors to be fully discharged so that no residual voltages present. Figure 5. Standard Sine Wave - 3 - erp-power.com

Unacceptable inrush can potentially damage relays. Standard relays can switch anywhere in a standard line cycle. As discussed above, switching at certain parts of the line cycle will allow for a maximum inrush. This can cause damage by degrading relay contacts and sometimes welding them closed, due to arcing at the contact. Standard component analysis techniques must be employed to determine the load derating to use on a relay, as well as the kind of inrush it can accept. c. Relation of Inrush Current to MCB Trip Curve: Under high inrush current circumstances MCB can be a utilized as a protection device, it can open the circuit instantaneously and later can be returned to nominal operating condition without causing any damage to the application, once the circuit recovers from overcurrent condition. For LED lighting application, usually user prefers type B, as per Fig 4 for instantaneous pick up trip point time is less than 0.002S. if the LED driver inrush current lower than 100A ( T = 0.002S). Then you can neglect considering the inrush current for the MCB load calculations. MCB Load Calculation Considering as example ERP LED driver model ESS020W-0700-24, below are listed parameters Nominal Input Voltage: 230 Vac Input Current: 0.083 A Inrush Current: 10.71 A (as per Picture. 6) T (Inrush current): 0.0006S MCB Type: 10A rated current, Type B Check if the inrush current is less than 0.002S, if yes proceed as below Non tripping current of 10A, Type B, MCB (Int): 1.13 x MCB rated current 1.13 x 10 = 11.3 A Number of load per MCB = Int / Input current 11.3 / 0.083 = 136.1 136 units per MCB (100% load) 80% MCB load calculation = Int x 0.8 (Considering the safety factor of 20% and not loading the MCB to its 100%) 11.3 x 0.8 = 9.04 A 9.04 / 0.083 = 108.9 109 units per MCB Concluding on 109 units per 10A, Type B MCB In case of inrush current higher than 100A with T 0.002 S, then follow procedure as below, Correlate the T with I/IN from Fig 4 Compute the Multiplication factor for the MCB Current rating Divide the value by In-rush current Final value will be the No. of units per MCB For example, consider inrush 120 A with T of 0.1 S, MCB Load calculation would be as below, Correlating above value from Fig 4, at T = 0.1 S 10A, type B MCB will trip between 30 to 50 A load current, hence the example application, will instantaneously trip on turn on. So selecting 32 A, Type C MCB will trip between 160 to 320A load current, hence user can load max of 1 unit on this MCB High inrush current application examples Inrush Current of a Motor Inrush Current of a Solenoid - 4 - erp-power.com

Here you can observe from the above, that the peak current remains for a longer duration, then stabilizes over time Hence selection of Circuit Breaker depends on the Inrush current, else it might lead to Nuisance Tripping Effects of improper MCB loading Danger of fire: if the MCB is oversized and the wire gauge used in the electrical system is not appropriate, the MCB will not trip and lead to fire breakout Nuisance Tripping: This might be due to High Inrush Current and result of not considering for MCB load calculation Damage the MCB Damage the application circuit Summary Consider inrush current of the device or equipment, while selecting MCB type and its load. Inrush current with T 0.002S can be neglected for MCB load calculation. Compute the MCB load considering the continuous input current. For higher inrush current applications, correlate the inrush current with the MCB trip curve and conclude the MCB load. References ABB Miniature Circuit Breaker, Application Guide Schneider Electric - Circuit Breaker Characteristic Trip Curves and Coordination Data Bulletin # 0600DB0105 MK by Honeywell Sentry Technical Circuit Protection Thomas Research Products Inrush white paper The information in this document is subject to change without notice. Other trademarks, product, and company names are the property of their respective owners and do not imply specific product and/or vendor endorsement, sponsorship or association. This document is provided for informational purposes only and is not a warranty or a specification. For product specifications, please see the data sheets available at www.erp-power.com. For warranty information, please contact ERP Sales at SaveEnergy@erp-power.com. U.S.A. Headquarters Tel: +1-805-517-1300 893 Patriot Drive, Suite E Moorpark, CA 93021 CHINA Operations Tel: +86-756-6266298 No. 8 Pingdong Road 2 Zhuhai, Guangdong, China 519060 SaveEnergy@erp-power.com - 5 - erp-power.com