File E3456 Project 08NK10151 November 24,09 REPORT ON TRANSIENT VOLTAGE SURGE SUPPRESSORS (VZCA/VZCA7) *********************************************************** Complementary Product Category ELECTROMAGNETIC INTERFERENCE FILTERS (FOKY/FOKY7) GE Zenith Controls Bonham, TX Copyright 09 Underwriters Laboratories Inc. Underwriters Laboratories Inc. authorizes the above named company to reproduce this Report provided it is reproduced in its entirety.
File E3456 Vol. 1 Sec. 2 Page 1 Issued: 09-11-24 DESCRIPTION PRODUCTS COVERED: USL, CNL - Surge Protective - Type 2 SPD Devices/Electromagnetic Interference Filters, Models TME or TR7 followed by 1S, 1Y, 2Y, 240Y, 240H, 240D, 277Y, 347Y, 480D, or 600D, followed by 065 or 080, followed by WM, followed by N1, N1D, N4, N4F, N4S, N4X, N12F, or N12S. Type 2 SPD Devices/Electromagnetic Interference Filters, Models THE or TR7 followed by 1S, 1Y, 2Y, 240Y, 240H, 240D, 277Y, 347Y, 480D, or 600D, followed by 100, 125,, 0, 250 or, followed by N1, N1D, N4, N4F, N4S, N4X, N12F, or N12S. USL indicates investigation to the following UL Standards: Surge Protective Devices: ANSI/UL 1449, Third Edition, dated September 29, 06, revised September 4, 09; and Electromagnetic Interference Filters UL 1449, Fifth Edition, dated November 30, 05. CNL indicates investigation to the applicable requirements of Canadian National Standard C22.2 No. 8-M1986, Electromagnetic Interference (EMI) Filters; CSA Electrical Certification Notice No. 516, dated September 2, 1986, Technical Information Letter A-24, dated October 31, 1995, and Technical Information Letter I-11B, dated May 13, 1986. These surge protective devices (SPDs) are designed for repeated limiting of transient voltage surges as specified in the standard on 50 or 60 Hz power circuits not exceeding 1000 V and designated as follows: Type 2 SPD Permanently connected SPDs intended for installation on the load side of the service equipment overcurrent device, including SPDs located at the branch panel. Type 3 SPD Point-of-utilization SPDs, when marked accordingly are intended to be installed at a minimum conductor length of 10 m (30 ft) from the electrical service panel to the point of utilization, e.g., cord-connected, direct plug-in, receptacle type and SPDs installed at the utilization equipment being protected. The distance (10 m) is exclusive of conductors provided with or used to attach SPDs. SPDs have been investigated to verify that the average of the transient voltage surges is limited to the Voltage Protection Rating (VPR) marked on the product. The effect of the SPD on connected loads, the effect of the SPD on harmonic distortion of the supply voltage, and the adequacy of the voltage suppression level to protect connected equipment from damage due to transient voltage surges has not been investigated.
File E3456 Vol. 1 Sec. 2 Page 2 Issued: 09-11-24 Types 1 and 2 SPD will be marked with at least one of the following enclosure type markings: only. When marked Type 1 Enclosure, these SPDs are intended for indoor use When marked "Type 4X Enclosure" these products are suitable for outdoor use and provide a degree of protection with respect to splashing water, windblown dust, hose-directed water, and the formation of ice on the enclosure plus resists corrosion. When marked "Type 12 Enclosure" these SPDs are suitable for indoor use and provide a degree of protection against dust and dripping noncorrosive liquids
File E3456 Vol. 1 Sec. 2 Page 3 Issued: 09-11-24 ELECTRICAL RATINGS: Model V (ac) Hz Phase Mode VPR (Vpk) L-N 1000 THE/TME or TR71S N1, N1D or L-G 1000 1/240 60 1S N4 THE/TME or TR71Y N1, N1D or N4 THE/TME or TR72Y N1, N1D or N4 THE/TME or TR7240Y N1, N1D or N4 THE/TME or TR7240H N1, N1D or N4 THE/TME or TR7240D N1, N1D or N4 THE/TME or TR7277Y N1, N1D or N4 THE/TME or TR7347Y N1, N1D or N4 THE/TME or TR7480D N1, N1D or N4 THE/TME or TR7600D N1, N1D or N4 1/8 60 3Y 2/380 60 3Y 240/415 60 3Y 240 HL 60 3H 240 60 3D 277/480 60 3Y 347/600 60 3Y 480 60 3D 600 60 3D L-L 10 L-N 1000 L-G 1000 L-L 10 L-N 0 L-G 0 N-G 1000 L-L 00 L-N 0 L-G 0 N-G 1000 L-L 00 L-N 1000 L-G 1000 In (ka) MCOV (V) 270 540 270 540 L-L 10 H-N 0 3 H-G 0 3 H-L 2500 470 L-G 0 270 L-L 1800 540 L-N 0 L-G 0 3 N-G 1000 L-L 00 L-N 1800 L-G 0 N-G 0 640 4 SCCR (A) L-L 2500 840 L-G 00 550 L-L 4000 1100 L-G 00 625 L-L 4000 1250
File E3456 Vol. 1 Sec. 2 Page 4 Issued: 09-11-24 ELECTRICAL RATINGS: (cont d) Model V (ac) Hz Phase THE/TME or TR71S THE/TME or TR71Y THE/TME or TR72Y THE/TME or TR7240Y THE/TME or TR7277Y THE/TME or TR7240D THE/TME or TR7240H THE/TME or TR7347Y THE/TME or TR7480D THE/TME or TR7600D 1/240 60 1S 1/8 60 3Y 2/380 60 3Y 240/415 60 3Y 277/480 60 3Y 240 60 3D 240 HL 60 3H 347/600 60 3Y 480 60 3D 600 60 3D Mode VPR In MCOV (Vpk) (ka) (V) L-N 900 L-G 800 L-L 10 L-N 900 L-G 800 L-L 10 L-N 0 L-G 10 N-G 10 L-L 00 L-N 0 L-G 10 N-G 10 L-L 00 L-N 0 L-G 10 N-G 10 L-L 00 L-G 10 270 L-L 1800 540 L-N 900 L-G 800 L-L 10 H-N 10 270 H-G 10 270 H-L 2100 4 L-N 0 L-G 0 4 N-G 0 L-L 2500 840 L-G 1800 550 L-L 0 1100 L-G 00 625 L-L 4000 1250 SCCR (A) All units are rated for use in an ambient operating temperature range of min. 0 C, max. 40 C.
File E3456 Vol. 1 Sec. 2 Page 5 Issued: 09-11-24 Additional Details Regarding Electrical Ratings: PHASE: Y Wye, H Hi-Leg Delta, D Delta, S Split AMPERAGE: NA - Not Applicable for One Port SPDs not intended to carry load current. Mode(s) - Refers to the pair of electrical connections where the VPR applies. The term "ALL" indicates that the VPR applies to all combinations of pairs of electrical connections. In: Nominal Discharge Current Rating in amps or ka. Voltage Protection Rating (VPR) - A rating (VPR) has been assigned to each mode of protection. The value of the VPR is determined as the nearest highest value taken from Table 63.1 in UL 1449 to the measured limiting voltage determined during the transient-voltage surge suppression test using the combination wave generator at a setting of 6 kv, 3 ka. MCOV: Maximum Continuous Operating Voltage Rating in volts - for Type 1 and 2 SPDs. NA - Not Applicable. SCCR: Short-Circuit Current Rating in amps or ka.
File E3456 Vol. 1 Sec. 2 Page 6 Issued: 09-11-24 CONSTRUCTION DETAILS: General - For details of construction, reference should be made to the Section General, the following paragraphs and accompanying descriptive indices. All dimensions are approx. unless specified as "max" or "min". Internal Wiring - Unless otherwise noted, all wiring is min 10 AWG. Markings - In accordance with Section General and as follows: "Suitable For Use on a Circuit Capable of Delivering Not More Than rms symmetrical Amperes, when Protected by a 60 Amp Max. Circuit Breaker Having an Interrupting Rating Not Less Than rms Symmetrical Amperes, (a) Volts Minimum (a) is the rated voltage of the SPD Installation Instructions - In accordance with Section General. Includes the following: Supply Wiring Connection Minimum 10AWG, Maximum 6AWG. Form C contacts rated rated 2.0 A resistive at 30 Vdc, 1.0 A resistive at 1 Vac. The instructions to cover installation of a facility filter shall include prominent mention of all four of the following conditions of installation: a) An insulated grounding conductor that is identical in size and insulation material and thickness to the grounded and ungrounded circuit supply conductors, except that it is green with or without one or more yellow stripes, is to be installed as part of the circuit that supplies the filter. Reference should be made to Table 250-122 of the National Electrical Code regarding the appropriate size of the grounding conductor. b) The grounding conductor mentioned in item a is to be grounded to earth at the service equipment or other acceptable building earth ground such as the building frame in the case of a high-rise steel-frame structure. c) Any attachment-plug receptacles in the vicinity of the filter are to be of a grounding type, and the grounding conductors serving these receptacles are to be connected to earth ground at the service equipment or other acceptable building earth ground such as the building frame in the case of a high-rise steel-frame structure. d) Pressure terminal or pressure splicing connectors and soldering lugs used in the installation of the filter shall be identified as being suitable for the material of the conductors. Conductors of dissimilar metals shall not be intermixed in a terminal or splicing connector where physical contact occurs between dissimilar conductors unless the device is identified for the purpose and conditions of use.
File E3456 Vol. 1 Sec. 2 Page 7 Issued: 09-11-24 NOMENCLATURE: Example: THE 1Y 0 WM N1 I II III IV V I. Prefix Designation a. TME, THE or TR7 - Tranquell High Exposure II. Voltage Code a. 1S - 1/240 Split Phase b. 1Y - 1/8 Three Phase Wye c. 2Y 2/380 Three Phase Wye d. 240Y 240/415 Three Phase Wye e. 240H 240 Delta High Leg f. 240D - 240 Delta g. 277Y - 277/480 Three Phase Wye h. 347Y 347/600 Three Phase Wye i. 480D - 480 Delta j. 600D 600 Delta III. Manufacturer Designation a. 065 b. 080 c. 100 d. 125 e. f. 0 g. 250 e. IV. Wall Mount Suffix a. WM V. Features a. N1 - Painted Steel, Gray, Enclosure b. N1D - Same as N1, except color Black c. N4 - Type 4X, Fiberglas Enclosure d. N4D - Same as N4 e. N4S - Type 4 Surface Mount Painted Steel, No Disconnect Switch e. N4X - Type 4X Surface Mount Stainless Steel, No Disconnect Switch f. N12F Type 12 Flush Mount Painted Steel, No Disconnect Switch h. N12S Type 12 Surface Mount Painted Steel, No Disconnect Switch