Digital Fan Controller Unit Troubleshooting

Similar documents
Wagner Smart Screen Service/Troubleshooting Screens

SS2200 Remote Controller

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

Installation Manual. 1.Included Accessories. System Controller SC-201-6M INT. Requests to Installers *SHA8754 C*

Manual Control Unit GFC 32

Manual Simatek Control Unit GFC 32

FANCOIL CONTROLLER UNIT TC17B01KNX. Product Handbook

G540 User Manual. Date Modified: March 5, 2012 Page 1 of 10

Flomatic Smart Card TM Model FDHC-100 (Digital High-Resolution Controller) Configuration and Operation Manual

Series B9 and C9 Electronic Metering Pumps. Instruction Manual. Manual No : 1796 Rev. : D Rev. Date : 11/2015

G540 4-AXIS DRIVE REV 4: MAY 28, 2010

Service Bulletin SB685. Date: 8/18/2017 TriPac EVOLUTION Communications Update Bulletin Location: TSA Info Central\Service Bulletins

G540 MANUAL MULTIAXIS STEP MOTOR DRIVE

INSTALLATION AND OPERATING INSTRUCTIONS DSST SYSTEM

M1000 INTELLIGENT ZONE CONTROL SYSTEM

February Instruction Manual. TURBO V80 controller. Model Model I. )

Hydraulic Fan Controller User Manual

Description. Monitoring functions Evaluation of brush length monitoring, digital, non-floating A00

External level devices for conductive point level switch

Installation, Operation and Maintenance Manual

P216. Condenser fan speed controller. Product bulletin. Features

MAXIMA+ Series Rotary Level Indicator

WARNING!!!!!!!!! IMPORTANT INFORMATION: READ BEFORE INSTALLATION!

Dip Switch settings.

SITOP power supply. Selectivity modules. Overview. Safety notes. Description, device design, dimension drawing. Mounting/removal 3

SAMPLE HEAT PUMP WIRING DIAGRAMS

PEAKTRONICS DHC-100 FEATURES. Digital High-Resolution Controller

Manual Control Unit GFC 16

Replacement and Calibration of Electronic Spare (PCB) Cassettes - Rosemount 2120 Vibrating Fork Liquid Level Switch

Operator s Manual. Morbark Integrated Control System Woodhog Series Model 2600

GRASSO SYSTEM CONTROL

User s Manual Pulse Encoder Interface Module OTAC-01

UNIT CONTROLLER 7 (UC7) Operation & Installation. Hydronic Units

Operating instructions. Speed monitor D / / 2014

ATS22D17Q soft starter-ats22-control 220V-power 230V (4kW)/ V(7.5kW)

GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC

Operating instructions. Switching amplifier DN0210 DN / / 2015

********SERVICE MANUAL******** MODELS:

IV-30 Operating Manual for Pulse Distributor Cassette with potential separation

FCU-4 FAN COIL CONTROLLER

GV3000/SE 230 VAC 1-20 HP General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.04

4-step Chiller and Heat Pump Controller

MAXIMA + Series ROTARY LEVEL CONTROL

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Tachometer Panel, PE3

LiquiFlo AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 6.4

Non-communicating room controllers

VLT 2800 DRIVE SPECIFICATIONS

Power Amplifiers for PVH-EDC Pumps

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

Application program: description and examples

MAXDTC-BT Family User Manual

Operating instructions AS-i SmartLine module AC3200 AC /00 06/2016

SmartVFD Disconnect Panel Assemblies

Hardware Installation Manual MX Axis Stepper Drive with Breakout Board & I/O s

isma-b-fcu FCU Hardware User Manual Global Control 5 Sp. z o.o. Warsaw, Poland

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

List of contents. 7-2 CE (ENC EN55022) declaration of conformity CE (LVD EN60950) declaration of conformity. 15 發行章

LF3-400 Three Phase Frequency Converter, Operation and Maintenance.

ETM-2050/ETM-2051 Service Manual

P216 Series Condenser Fan Speed Controller

ATS22D17Q soft starter-ats22-control 220V-power 230V(4kW)/ V(7.5kW)

SA-150, SA-300 Series Pure Sine Wave Inverter User s Manual

Display and Diagnostic Module Gauge Operation

Smart Grid Tie Microinverter User Manual

ADVANCED MICRO SYSTEMS

SmartFan Fusion-4. Speed Control and Alarm for DC Fans CONTROL RESOURCES INCORPORATED. The driving force of motor control & electronics cooling.

SmartFan Cirrus-9. Speed Control and Alarm for 4-Wire Fans CONTROL RESOURCES INCORPORATED. The driving force of motor control & electronics cooling.

INSTALLATION MANUAL. MEC-HL COMPACT Electromechanical proportional actuators for Hydraulic Applications

Sierra Dual 24 Volt Brushless DC Motor Controller Product Specification. Assembly 025F0348

Control system for rotary heat exchanger EQRB, L=3,4

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

Overview Included in the Box: Pinout Installation Power Supply Stepping Motors DIP Switch (JP1) Location...

Proportional Control Unit (PCU)

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

Control. Part B, Section 2. This section covers the following unit configurations. 3400V 3500V Voltage 1, 2, 3 Pump Piston (D, E, F, G)

Thermoelectric Cooler Controller TED1000

Quick Start Guide. DVC Family

VR2 R-NET LED R-NET LCD. Controller System Operation

Manual Control Unit GFCD 16

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE TC-20 TEMPERATURE CONTROL SYSTEM

Field module for cold locations for installation in refrigerators for direct control of a pulsed expansion valve

This is an inspection failure, not meeting the requirement of >10k Ohm between either PD battery post and chassis.

ATS22D75S6U. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

Supplementary operating instructions for your air curtain system Controller TMC 500

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

ATS22C17Q. Main. Range of product Altistart 22. Component name. Factory setting current. Utilisation category. IP degree of protection

INSTALLATION INSTRUCTIONS 07/2018

INDOOR UNIT CONTROLLER (IUC) Operation Manual

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

User Guide CPSMP VAC Power Supply Module: PointSystem CPSMC Accessory CPSMC Accessory. Contents.

Installation Instructions

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

Wiring Diagrams DIAGRAM INDEX. POWER SCHEMATICS Unit 30GXN,R Voltage Figure Number

PEM Faults and Blower Failures

TECHNICAL REFERENCE BSD V-3A Bipolar Stepper Driver

ATS22D62Q soft starter-ats22-control 220V-power 230V(15kW)/ V(30kW)

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Genset Controller Unit Model EMS - GC10. Installation Manual Section

J3C-H20DPS 25Nm Smart Electric Actuator Type: J3C Model: H20DPS

Transcription:

Section 2-6 Digital Fan Controller Unit Troubleshooting heck the supply voltage to the controller, making sure that it is correctly wired and fused. nsure that you are aware of the limits, location, & available adjustments in the software. now the Hydraulic circuit you are working on and the anticipated performance expected. ake sure you have the correct tools to do the intended job ( i.e. PC, D.V.M. ) e.t.c. this unit from all other equipment any form of welding takes place. heck connections to and from this unit to ensure ground faults / Open circuits. perate the units within specified operating temperature for best & most reliable performance. nsure that any unused wires / terminals are isolated/insulated and ttempt to use this unit if you are unsure of connections or expected operation. ttempt to use this unit in Areas where AC or DC coils been fully suppressed. se a power supply that is not rated for the correct required O/P current under full load. llow wires TO or FROM the unit to short circuit ( to each other or chassis / cabinet e.t.c. ). ttempt to use this unit in areas of intense RF interference without adequate screening measures. isconnect or connect wires to or from this unit until it is isolated from the power supply. eep High Voltage AC cables separate from Low Voltage DC signal and supply cables. se this unit in temperatures that exceed those specified as operation may be effected. Allied Systems Co. reserves the right to make changes to new equipment without incurring the obligation to make such changes to equipment previously manufactured. 80-806, REV. 5-06 1

2 Torque Convertor Fan Drive Manifold Assy Pump Vane Motors Radiator Assy Figure 1 - System Component Locations (Note: Part of chassis shown removed for clarity.) Filter Assy's Controllers (Under Dash) Vane Motor Transmission Cooler

General Your machine is equiped with a hydraulically driven, digitally controlled cooling system. This cooling system includes both the transmission cooler circuit and the radiator/charge air cooler circuit, and allows for proportional control of the fan speeds based on system temperatures. This on-demand cooling can increase fuel economy by up to 9% by reducing both overheating and overcooling conditions. System Description Refer to Figures 1 and 2 for component locations on a typical Wagner Lumberjack Logstacker. Your system component locations may vary from those shown here. The two Digital Fan Controller Units, mounted in the cab on the terminal panel assembly, receive signals from thermistors mounted on the machine. The transmission cooling fan controller receives a signal from a thermistor mounted on the converter regulator valve. The radiator/charge air cooler fan controller receives signals from two thermistors; one is mounted on the engine thermostat housing port, and one is mounted on a charge air cooler tube located after the charge air cooler. These thermistors signal the temperature of their respective systems to the controllers. The controller will attempt to maintain the temperature of the system, as read from the thermistor, at or near a pre-determined Setpoint. It will alter the fan speed as necessary to regulate the system temperature. If the system temperature reaches the pre-determined Overtemp setting, the controller will output an alarm signal, visible on the controller itself, and on the instrument panel. Refer to the section on troubleshooting for more information on this and other error conditions, and troubleshooting guidelines. The controller outputs a proportional pulse-width modulated (PWM) signal to the valve coil on the fan drive manifold assembly, which regulates the fl ow of hydraulic oil to the vane fan motors mounted directly to the radiator or transmission cooler. Hydraulic pressure is supplied by a tandem vane pump mounted directly to the torque converter. The system is designed so that at maximum PWM voltage, the fan speed is at its lowest, while at 0 PWM voltage, the fan is at full speed. This fail-safe ensures that maximum cooling continues in the event of catastrophic controller failure. See Table 1 for the correlation between system temperature, voltage, fan speed, vane motor hydraulic pressure, and the proportional valve output LED color. Fan Purge Transmission Fan Controller Error Light (Red) Rad/CAC Fan Controller Error Light (Red) Rad/CAC Fan Controller Transmission Fan Controller Both cooling systems have the option to reverse the fan rotation (purge) to clear the cooler tubes of debris. This is a temporary condition, and is not intended to be a permanent running option. This purge condition will cancel automatically anytime the affected system reaches its Overtemp setting, and the fan rotation will return to normal. The purge condition is initiated when the operator depresses either the Purge Trans Fan intermittent switch or the Purge Rad/CAC Fan button on the instrument panel. Once initiated, the fan speed will slow to 0 RPM, pause, reverse direction for a pre-determined time, slow to 0 RPM, pause, then return to normal forward RPM as required. Figure 2 - Controller & Error Light Locations 3

Proportional Valve Output Voltage Proportional Valve Output LED Color System Temperature Motor Pressure Fan RPM 27 Green Cool 270 574 19 Orange 212 270 574 13 Red-Orange 221 1015 1650 8 Red 229 1025 1700 0 Red 237 1010 1700 Table 1 - Conditions for a Properly Operating Transmission Cooling System Error Indications Typically, the operator s fi rst indication of a problem with the cooling system will be the illumination of either the Transmission Fan Controller Error light or the Rad/CAC Fan Controller light on the left side of the instrument panel (see Figure 2). The severity of the error will be indicated by either the light showing a Steady ON state, or a Pulsed ON/OFF state. Steady ON: Non-Critical Errors. These errors should be corrected as soon as possible, but do not immediately endanger the machine or personnel. Pulsed ON/OFF: Critical Errors. These errors indicate that the operator MUST immediately move the machine to level ground, lower the bucket/boom to the ground, and shut off the engine. The problem must be fi xed before the machine is returned to service. Warning: Failure to immediately attend to a critical error of the cooling system may result in damage to the machine and the risk of serious personal injury or death to personnel. The digital controller is able to indicate a variety of errors. Service personnel must note the condition of several LED s on the controller unit during an error to begin the troubleshooting process. Use the table in the troubleshooting section to determine specifi c error conditions. Some errors may require you to use the information in Table 1 for baseline system readings. The relationship between system temperature, proportional valve output LED color, proportional valve output voltage, vane motor pressure, and fan RPM are indicated for a system that is working correctly. Deviations from these readings may help determine the root cause of the error. The readings in Table 1 were taken on the transmission cooling system, with the transmission in a stall condition. The voltage was read at the junction box, the LED color was read on the controller unit, the transmission temperature was read on the Powerview display module, the motor pressure was read at the fan control manifold, and the fan RPM was read at the transmission cooler. 4

Controller Unit LEDs The controller units are able to convey both system operating conditions and diagnostic information by the use of the LEDs on the front face of the controller. Refer to Figure 3. Thermistor Input Status LEDs: The RED LED for the thermistor that is controlling the fans comes on steadily while the other thermistor LEDs are off, if no more than one thermistor is above setpoint. If multiple thermistors are above setpoint, the thermistor that is controlling the PI process has a blinking LED and the others above setpoint are on steady. Power LED: The RED LED indicates power supply status with the LED OFF for less than 8 VDC, ON for 8-40 VDC, and fl ashes ON/OFF for more than 40 VDC. Proportional Valve Output LED: This variable LED is GREEN at the lowest fan speed, and RED at full fan speed, with shades of green, yellow, orange, and red to indicate intermediate values. See Table 1. Reverse (Purge) Output LED: The RED LED is ON with the output to the reversing coil during a Purge cycle. The LED blinks on for about 0.1 seconds then off for about 0.1 seconds to indicate shorts in the circuit, and blinks on for about 0.5 seconds and then off for about 0.5 seconds to indicate opens in the circuit. In either case, the Error LED on the instument panel comes on steady to indicate an error. Error LED (Controller): The RED LED is used to indicate an error condition. Refer to the section on Troubleshooting for details of how to read the error blink codes. The blink rate will be 0.5 seconds on, 0.5 seconds off, with a 2 second delay before it repeats. Reverse (Purge) Input LED: The RED LED is used to indicate an input signal from the instrument panel to initiate a Purge cycle. Power LED Thermistor Input Status LEDs Proportional Valve Output LED Reverse (Purge) Output LED Error LED (Controller) Reverse (Purge) Input LED Figure 3 - Controller Unit LED Locations 5

Troubleshooting 6 Indications Error Condition Correction One Blink One Blink One Blink Green/Blink with Error LED One Blink Red/Blink with Error LED Three Blinks Three Blinks (Shorted Therm.) Four Blinks Four Blinks (Open Therm.) Five Blinks Six Blinks Six Blinks (Overtemp Therm.) Memory Checksum Failure Controller Unit Exceeds 75 C Controller Unit Exceeds 80 C Thermistor Input Shorted Thermistor Input Open Alarm Output (To Instrument Panel Error LED) Shorted Thermistor Input Over Temperature Move the machine to level ground, lower the bucket/boom to the ground, and shut off the engine. Reload Flash or Data File. Move the machine to level ground, lower the bucket/boom to the ground, and shut off the engine until unit <70 C. Move the machine to level ground, lower the bucket/boom to the ground, and shut off the engine until unit <70 C. affected thermistor to controller). affected thermistor to controller). controller to instrument panel error LED). Shut down the machine and allow to cool. Troubleshoot affected system.

Indications Error Condition Correction Flashing Red/ Flashing Green/ Flashing Quickly Flashing Slowly Blinking PWM Output Shorted PWM Output Open Reverse Output Shorted Reverse Output Open Power Supply To Controller Is Less Than 8VDC Power Supply to Controller is Greater Than 40VDC controller to fan drive manifold assembly). controller to fan drive manifold assembly). controller to fan drive manifold assembly). controller to fan drive manifold assembly). troubleshoot circuit supplying power to controller. troubleshoot circuit supplying power to controller. 7

Cooling System Hydraulic Schematic 8

Electrical Schematic, Digital Fan Controller Units 80-806, REV. 5-06 9