Technical Data Sheet. Hilti Firestop Collar CFS-C P. European Technical Approval ETA N o 10/0404. Issue 07 / Hilti Firestop Collar CFS-C P

Similar documents
Technical Data Sheet. Hilti Firestop Collar CFS-C P. European Technical Approval ETA N o 10/0404. Issue 02 / Hilti Firestop Collar CFS-C P

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Firestop Composite Sheet CFS-COS. for Firestop Composite Sheet. Hilti. Outperform. Outlast.

Tremco FX 130 Heavy Duty Chemical Anchor

CERTIFICATE OF APPROVAL No CF 694 3M UK LTD

Water Supply and Sewerage Approved Products Manual - February 2006

Combi-System. Composition pipe Copipe

The ABC of the BCA 2010 Bradford solutions to Section J.

Classification of fire resistance according to EN : A1:2009 of a METACON RGS EW 360 ECO Twindoor rolling shutter

FIRE RESISTANCE EXPERT JUDGEMENT REPORT WITH CLASSIFICATION FIRES-JR NURE

VALLOX BLUESKY AIR DISTRIBUTION SYSTEM

Temperature sensors and accessories for heat and cooling measurement points

Contact Dial Thermometers

11. Wall and Floor Mounted Clips

Han PCB termination. Han-Fast Lock PCB adapter for Han DD PCB adapter for Han DDD module

Heradesign micro Product Data & Certificates

P.O. Box NL-2665 ZN Bleiswijk Brandpuntlaan Zuid 16 - NL-2665 NZ Bleiswijk The Netherlands

CLASSIFICATION OF FIRE RESISTANCE PERFORMANCE ACCORDING TO EN :2007+A1:2009 OF A ROLLING SHUTTER TYPE METACON RGS EI (1) 120 MOUNTED ON A WALL

Ideal protection for your electrics: häwa cable ducts

GALVANIZED-COATED SHELFING SYSTEM SHELVING FOR FOOD

Gas-actuated thermometer Stainless steel version Model 73

IT infrastructure Efficiency-boosting solutions. nextlevel. for data centre

Acoustic baffle system

BS up.v.c SOIL, WASTE, VENT PIPES AND FITTINGS

resistance for high requirement

Minimum < 0.2 ms, maximum 2 ms, typical 1 ms; On request: Delays or holding times for bubble events % relative humidity (not condensing)

DUKE UNIVERSITY CONSTRUCTION STANDARDS

Temperature Measurement SITRANS TS300

Specialist Drainage. Durapipe Vulcathene Mechanical Piping System Vulcathene - Laboratory chemical drainage system. Specialist Drainage

Vario XtraSafe. Installation Guide. Installation Guide

ODU MINI-SNAP PC Product Description. ODU MINI-SNAP PC: The Connector with Push-Pull-Locking in Plastic

Dial Thermometer. Particularities. Brief description. Technical data. Page 1/6. Data Sheet

SADDLES & SNAP-ON SADDLES

Level sensor Stainless steel version Model RLT-1000, for industrial applications

Roller Shutter Door Kits. Diversity in profiles

Declaration of Performance (DOP)

Anchor Systems ANCHOR SYSTEMS

Temperature probes 468 Hans Turck GmbH & Co. KG Tel Fax Edition I/

JUMO PINOS L01. Calorimetric flow sensor. Brief description. Special features. Customer benefits. Data Sheet

SharkBite 25 W ARRANTY Sh YEAR arkbite

Accessories.

Push-Pull and E-Stop Switches. Datasheet

Specification. Radiamatic Detectors and Accessories

Compact Medium SOLARLOK Junction Box. Application Specification

Anchor Systems. Anchoring Systems. Leading-edge Technology. Outstanding Service.

US 5,634,357 D 385,7683 Bulletin: A28S4

BPL SERIES INSTALLATION INSTRUCTIONS THIS SHEET CONTAINS IMPORTANT SAFETY INSTRUCTIONS. SAVE THESE INSTRUCTIONS.

A.A.G. Stucchi TRACK LIGHTING SYSTEM

GSW Office ALU ETA VSG ESG KAT IV A,B,C, D,E PATENT

Data sheet. Server Rack ( heavy duty rack cabinet ) W:600 = D:1000

Free-Stand Stainless Steel Preferred-Cutout Disconnects Stainless Steel Heavy Duty Disconnects US 5,634,357 D 385,7683 BULLETIN: A28S4

IP degrees of protection. Degrees of mechanical shock protection IK conforming to the CEI EN Standard

Motorised butterfly valve DMK Nominal Diameters DN 40 to DN 125

DAIKIN GAS TIGHT JOINT (DGT)

Catalogue 2016 HOSE TECHNOLOGY. Fittings, Valves and Accessories. Schauenburg Hose Technology Group

DN40 (1 1/2") - DN200 (8") Hot Tappings

PSI COMPAKT SEAL PRESSURE TIGHT UP TO 5 BAR SPECIAL VERSIONS FOR DIFFERENT PIPE SYSTEMS STAINLESS STEEL PRESSURE PLATES AS STANDARD

Motorised Butterfly Valve DMK Nominal Diameter Rp 3/4 - Rp 2

Motorised Butterfly Valve DMK

Technical Data Sheet Excel 741

Power supply module, bus connection module

Hercules GENII Screw mount 2in1 450MHz and 868MHz (Separate cable and connectors)

ALPHA Small Distribution Boards SIMBOX 63/SIMBOX WP

Assembly and Setup Manual

Screw-in resistance thermometers with terminal head Form B

Easy Flow Indicator Magnetisch-Induktiver Durchflussmesser. Type 8024 For Insertion Fittings. Analog Flow Rate Indicator, 1/2"-16"; P=87 PSI

C04. S09. P02 P14 GypWall audio

Electromotoric actuators

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

WHOLESALE PRICE LIST EFFECTIVE

14 Pressure Measurement. Measuring Devices Description Pressure range Connection Device Page

Description of parts Panel mounting Insert mounting without/with Carrier element Plastic housings

Declaration of performance (DOP)

Declaration of performance (DOP)

Instructions for Use. Advantix Vario base unit, for Advantix Vario shower channel, can be cut to length continuously

Safety switches with separate actuator

Instructions for Use. Viega Eco Plus Universal shower WC element. for wall-hung WCs, wall-hung shower WCs, wall-hung WCs with shower WC top

IKA Crushing 76 Dispersers (batch operation)

Safety switches with separate actuator

Specification. Hercules G21.B

Data sheet: Wilo-Stratos 40/1-8

Anchor Systems. Hilti. Outperform. Outlast.

TECHNICAL DOCUMENTATION

Technical data: Pin Spacing

5. Operating instructions: Octagon 200CL

Data sheet: Wilo-Stratos 50/1-9

Data sheet: Wilo-Stratos 50/1-10

Furnace Camera System Operator s Manual. Version

ME PLC Multifunctional housing for complex electronics. Data sheet _en_01. 1 Description

Limanda. Technical data

FILTER NAME CONSTRUCTION FEATURES APPLICATIONS ORDER CODE MEMBRANE Body: polycarbonate Filter: PTFE membrane

Han R 23. Circular Connector. Certified acc. to DIN EN ISO 9001 in design/ development, production, installation and servicing.

KM-4800w. Installation Guide

Blue e+ chillers with the principle

CERTIFICATE OF APPROVAL No CF 188 LEADERFLUSH SHAPLAND

DISTRIBUTION OF QUANTITIES

Approx. 4 s, measured in oil, with a probe Ø of 10 mm made of stainless steel. Influential effect of the ambient temperature

Cleanroom Panel System

KM6-II Subracks. APW Electronic Solutions. 152 APW Electronic Solutions Toll Free (800) Fax: (858)

AIR TERMINALS: COPPER

Transcription:

Technical Data Sheet Hilti Firestop Collar CFS-C P Hilti Firestop Collar CFS-C P European Technical Approval ETA N o 10/0404 Issue 07 / 2013 Hilti Firestop Collar CFS-C P Issue 04/2013 page 1

General information end configurations Page 03 end configurations according to intended use Page 04 configurations Page 05 Hilti Firestop Collar CFS-C P Page 06 Product data sheet Page 06 Installation instructions Page 07 Overview table Page 08 Fire classification detail tables for walls Walls Construction and minimum distances Page 08 Flexible and rigid walls minimum wall 100 mm Page 08 Pre-insulated pipes Page 10 Plastic pipes Page 11 Plastic pipes with combustible insulation Page 11 Composite pipes with combustible insulation Page 16 Rigid walls minimum wall 150 mm Page 17 Plastic pipes Page 18 Fire classification detail tables for floors Floors Construction and minimum distances Page 19 Rigid floors minimum density of 2400 kg/m 3 Page 19 Pre-insulated pipes Page 21 Plastic pipes Page 22 Plastic pipes with combustible insulation Page 27 Composite pipes Page 28 Composite pipes with combustible insulation Page 29 Rigid floors minimum density of 550 kg/m 3 Page 30 Pre-insulated pipes Page 30 Plastic pipes Page 30 Plastic pipes with combustible insulation Page 33 Composite pipes Page 34 Composite pipes with combustible insulation Page 34 Hilti Firestop Acrylic Sealant CFS-S ACR Product data sheet Page 36 Installation instructions Page 37 Specification Specification Page 39 Additional attributes Page 39 Ancillary products Page 39 page 2 Hilti Firestop Collar CFS-C P Issue 04/2013

end configurations All pipes tested according to EN 1366-3 have been tested with a specific pipe end configuration. In the fire classification, the first letter of the end configuration refers to the end conditions within the furnace (fire-side), the second letter to the end conditions outside the furnace (non-fire-side). EI 90 U / U Configuration outside furnace Configuration inside furnace Fire resistance classification in minutes, Test condition end configuration Inside furnace Outside furnace U / U Uncapped Uncapped C / U Capped Uncapped U / C Uncapped Capped C / C Capped Capped As the EN test standard EN 1366-3 states, it is important to ensure that sealing systems have been tested with appropriate pipe end conditions. The conditions the pipe and sealing system must endure in a fire situation depend on whether one or both ends of the pipe are sealed in practice, as pressures and the flow of hot gases will vary depending on whether the pipe is ventilated or not. There are rules that determine which tested end configurations are valid for additional pipe end situations. For metal pipes: Tested U / C C / U C / C Covered U / C Y N N C / U Y Y N C / C Y Y Y Y = acceptable, N = not acceptable For plastic pipes: Tested U / U C / U U / C C / C U / U Y N N N Covered C / U Y Y N N U / C Y Y Y N C / C Y Y Y Y Y = acceptable, N = not acceptable So, for example, a plastic pipe tested with the end configuration U / U will cover all possible end conditions. But a plastic pipe tested U / C will only cover the conditions U / C or C / C. Hilti Firestop Collar CFS-C P Issue 04/2013 page 3

end configurations according to intended use As previously stated, it is important to ensure that the tested pipe configuration corresponds to the intended use of the pipe. The table below outlines recommended end configurations for various intended pipe uses as per suggestions laid out in EN 1366-3 2009 H.4.2.2. In the event that a national regulation conflicts with this table, the national regulation takes precedence. Intended use of penetrations (list not exhaustive, other pipes uses possible) Application Penetration material Manufacturer, product (examples) Heating Al-Composite Geberit Mepla U / C CS Recommended pipe end classification KeKelit KELOX KM 110 CS Rehau Rautitan stabil PE-X Rehau Rautitan flex CS CS Potable water Al-Composite Geberit Mepla U / C KeKelit KELOX KM 110 Rehau Rautitan stabil PE EN 12201-2 PE-HD 100 RC Wavin TS CS/LS PE-X Rehau Rautitan flex CS PP EN ISO 15874, DIN 8077/8078 (e.g. fusiotherm, Faserverbundrohr) CS/LS PCV-C Friatherm starr CS/LS Refrigeration ABS +GF+ COOL-FIT CS U/C Ventilated PE EN 1519, EN 12666-1 U / U Waste water Roof CI/CS Drainage PE-HD 1000 RC Wavin TS CS/LS PE-S2 Geberit Silent db20 PP EN 1451-1 climatherm Faserverbundrohr Magnaplast Skolan db life Master 3 Poloplast Polo Kal NG Poloplast Polo Kal 3S Rehau Raupiano Plus Wavin AS/KeKelit Phonex AS Wavin SiTech PVC-C EN 1566-1 PVC-U EN ISO 1452, EN 1329-1, EN 1453-1 Pneumatic Al-composite Geberit Mepla C/C PP DIN 8077/8078 Sprinkler PP-R firestop U/C Industry Al-Composite Varies depending upon application, PE EN ISO 15494, DIN 8074/8075 i.e. consider whether pipe is pressurized (U/C), PP DIN 8077/8078 ventilated (U/U) or unventilated climatherm Faserverbundrohr (U/C) PVC-U EN ISO 15493, DIN 8061/8062 CS CS CS page 4 Hilti Firestop Collar CFS-C P Issue 04/2013

end configurations When sealing pipes, the insulation configuration must be considered. The following configurations are possible: over the entire length of the pipe (i.e. thermal insulation) Continued sustained Continued interrupted only required in the area of the penetration seal Local insulation, sustained Local insulation, sustained See page 35 for specification of suitable insulation products. Hilti Firestop Collar CFS-C P Issue 04/2013 page 5

Hilti Firestop collar CFS-C P Firestopping for flammable pipes up to 250 mm in diameter with European Technical Approval. Applications n Sealing flammable pipes from 50 mm to 250 mm in diameter in penetrations through fire compartment walls and floors n materials: PVC, PVC-U, PE, PE-HD, PE-X, PP, ABS, Al-composite n Suitable for use in openings in concrete, aerated concrete, masonry, drywall, shaft wall and coated board. n Different backfilling and sealing materials are covered Advantages n Quick and easy closure without use of a tool n Adjustable position tabs for simple fastening n Sound decoupling strip based on PE (foam) can be used n Low profile for tight installations Technical data Minimal wall Minimal ceiling Storage and transportation temperature - range Close aperture with CFS-C P 100mm 150mm -5 C - 50 C Gypsum plaster, cementitious mortar, Hilti Firestop Acrylic Sealant CFS-S ACR Expansion temperature 180 C The European Technical Approval (ETA) and the technical data sheet can be obtained via your local Hilti contact. Nominal pipe diameter Number of hooks and fasteners Order designation Sales Quantity Item Number 50 mm 2 Firestop collar CFS-C P 50/1.5 1 pc 00435406 63 mm 2 Firestop collar CFS-C P 63/2 1 pc 00435407 75 mm 3 Firestop collar CFS-C P 75/2.5 1 pc 00435408 90 mm 3 Firestop collar CFS-C P 90/3 1 pc 00435409 110 mm 4 Firestop collar CFS-C P 110/4 1 pc 00435410 125 mm 4 Firestop collar CFS-C P 125/5 1 pc 00435411 160 mm 6 Firestop collar CFS-C P 160/6 1 pc 00435412 180 mm 8 Firestop collar CFS-C P 180/7 1 pc 00435413 200 mm 8 Firestop collar CFS-C P 200/8 1 pc 00435414 225 mm 10 Firestop collar CFS-C P 225/9 1 pc 00435415 250 mm 12 Firestop collar CFS-C P 250/10 1 pc 00435416 page 6 Hilti Firestop Collar CFS-C P Issue 04/2013

Installation instructions Seal the opening: The aperture around the pipe is filled with gypsum plaster (flexible walls) or cementitious mortar (concrete walls/floors) over the full of the wall/floor or alternatively sealed with minimum 25 mm thick Hilti Firestop Acrylic Sealant CFS-S ACR on both sides. Backfilling with stone wool may be omitted in case of small annular gaps and classifications EI 120. In case of missing sound decoupling means around the pipe it is recommended to use Hilti Firestop Acrylic Sealant CFS-S ACR as annular gap seal. If gypsum plaster or cementitious mortar is intended to be used it is recommended to install a PE foam strip around the pipe over the entire wall or floor for sound de coupling of the pipe. Clean the plastic pipe. Remove all plaster/mortar or dust from the pipe in the area where the Firestop collar is to be installed. Close the Hilti Firestop Collar: Place the Hilti Firestop Collar around the plastic pipe and apply firm pressure by hand until it latches with a "click" sound. No tools, pins or screws are necessary. The Hilti Firestop Collar can be re-opened by pushing down the engaged "tongue" with a screwdriver while pulling the Hilti Firestop Collar apart. Attach fastening hooks/tabs: The fastening hooks can be attached to various points of the metal housing. The hooks must be positioned as symmetrically as possible. The required number of fastening hooks is indicated below and on the packaging. Fasten the Hilti Firestop Collar: a) Attach fastening hooks/tabs on the metal housing. b) Mark the fastening points on the wall/floor. c) Fasten the Hilti Firestop Collar, using recommended metal anchors/fasteners, e.g. Hilti DBZ, Hilti HUS, Hilti HSA for rigid walls and floors or threaded rod, nuts, washers in flexible walls. These are defined in the respective test reports and approvals. d) If required by national prescriptions mark the penetration seal with an identification plate containing the required information. In such a case fasten the identification plate in a visible position next to the seal. For wall applications: Repeat installation on the other side of the wall. Collar sizes and number of hooks for suitable pipe diameters FS Collar P 50/1,5" 2 FS Collar P 63/2" 2 FS Collar P 160/6" 6 FS Collar P 250/10" 12 FS Collar P 75/2,5" 3 FS Collar P 90/3" 3 FS Collar P 180/7" 8 FS Collar P 200/8" 8 FS Collar P 110/4" 4 FS Collar P 125/5" 4 FS Collar P 225/9" 10 Hilti Firestop Collar CFS-C P Issue 04/2013 page 7

1. Flexible and rigid walls, minimum wall 100 mm The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Flexible walls / drywalls (E) with a minimum of 100 mm (t E ), with timber or steel studs lined on both faces with a minimum of two layers of 12.5 mm thick boards. For timber stud walls there must be a minimum distance of 100 mm between the seal and any stud, and the cavity must be filled with a minimum of 100 mm insulation of Class A1 or A2 in accordance with EN 13501-1. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) over the entire of the wall or Hilti Firestop Acrylic CFS-S ACR Sealant (A2) on both sides with a depth of minimum 25 mm from the surface of the wall. Rigid walls (E) consisting of comprise concrete, aerated concrete or masonry, minimum density of 450 kg/m 3, minimum 100 mm. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) or cementitious mortar over the entire of the wall or Hilti Firestop Acrylic Sealant CFS-S ACR (A2) on both sides with a depth of minimum 15 mm from the surface of the wall. The sealant may be backfilled with mineral wool. Maximum opening diameter: the opening should not be larger than the collar outside diameter to allow safe fixing of the collar to the wall. Minimum distance between collars (s1): 0 mm. Firestop collar (A1) fastened by hooks (F) (minimum number of hooks: see installation instructions) in flexible wall / drywall and low density rigid wall with M8 threaded rods through the wall secured with nuts on both sides. In high density rigid walls, metal anchors may be used as an alternative (e.g. Hilti HUS, DBZ, HSA). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the wall. For maximum see tables below. page 8 Hilti Firestop Collar CFS-C P Issue 04/2013

Annular gap seal (drawings show non-insulated pipes as example) Gypsum plaster (A 3 ) Gypsum plaster (A 3 ) together with sound decoupling (C 1 ) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) Gypsum plaster or cementitious mortar (A 3 ) Gypsum plaster or cementitious mortar (A 3 ) together with sound decoupling (C 1 ) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) insulation (drawings show mortar as an example for the annular gap seal) Local/Sustained pipe insulation (LS) Continued/Sustained pipe insulation (CS) Hilti Firestop Collar CFS-C P Issue 04/2013 page 9

Flexible and rigid walls 100 mm 1.1. Pre-insulated pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Branded pipes material manufacturer diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 120-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 60-U/C page 10 Hilti Firestop Collar CFS-C P Issue 04/2013

Flexible and rigid walls 100 mm 1.2. Plastic s Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Normed pipes end configuration U/U material manufacturer diameter Inner pipe diameter Collar size Classification PVC-U EN ISO 1452-2, 50 mm 2.4 5.6 mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, 63 mm 3.0 4.7 mm CFS-C P 63/2 EN 1329-1, 75 mm 2.2 3.6 mm CFS-C P 75/2.5 EN 1453-1 90 mm 2.7 4.3 mm CFS-C P 90/3 110 mm 2.2 8.1 mm CFS-C P 110/4 125 mm 3.7 6.0 mm CFS-C P 125/5 160 mm 2.5 11.8 mm CFS-C P 160/6 PE EN 1519, 50 mm 3.0 mm CFS-C P 50/1.5 EI 120-U/U EN 12201-2, EN 12666-1 63 mm 3.0 mm CFS-C P 63/2 75 mm 3.0 mm CFS-C P 75/2.5 90 mm 3.5 mm CFS-C P 90/3 110 mm 4.2 mm CFS-C P 110/4 125 mm 4.8 mm CFS-C P 125/5 160 mm 6.2 mm CFS-C P 160/6 EN ISO 15494, 50 mm 2.9 4.6 mm CFS-C P 50/1.5 EI 120-U/U DIN 8074/5 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 90-U/U 63 mm 3.6 5.8 mm CFS-C P 63/2 EI 120-U/U 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 2.2 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 2.7 10.0 mm CFS-C P 110/4 EI 120-U/U 125 mm 3.1 7.1 mm CFS-C P 125/5 EI 120-U/U 160 mm 4.0 9.1 mm CFS-C P 160/6 EI 120-U/U PP EN ISO 15874 50 mm 1.8 2.9 mm CFS-C P 50/1.5 EI 90-U/U DIN 8077/8078 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 60-U/U 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 60-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 15.0 mm CFS-C P 90/3 EI 120-U/U Normed pipes end configuration U/C material norm diameter wall Collar size Classification PP EN ISO 15874 50 mm 4.6 8.3 mm CFS-C P 50/1.5 EI 90-U/C DIN 8077/8078 63 mm 5.8 10.5 mm CFS-C P 63/2 EI 60-U/C 63 mm 10.5 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 12.5 mm CFS-C P 75/2.5 EI 60-U/C 90 mm 8.2 15.0 mm CFS-C P 90/3 EI 120-U/C 75 mm 12.5 mm CFS-C P 75/2.5 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 04/2013 page 11

Branded pipes end configuration U/U designation manufacturer diameter wall Collar size Classification Geberit Silent-db20 Geberit 56* mm 3.2 mm CFS-C P 63/2 EI 90-U/U (PE-S2) 75 mm 3.6 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 5.6 mm CFS-C P 90/3 El 120-U/U 110* mm 6.0 mm CFS-C P 110/4 EI 90-U/U Wavin TS (PE-HD Wavin 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/U 100 RC) 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/U Skolan-dB (Mineral Magnaplast 58* mm 4.0 mm CFS-C P 63/2 EI 120-U/U wool reinforced-pp) 90 mm 4.5 mm CFS-C P 90/3 EI 120-U/U 110 mm 5.3 mm CFS-C P 110/4 EI 120-U/U Master 3 life 32 mm 1.8 mm CFS-C P 50/1.5 EI 120-U/U (PP-CO/PP-MV/PP- CO) 40 mm 1.8 mm CFS-C P 50/1.5 50 mm 1.8 mm CFS-C P 50/1.5 75 mm 2.1 mm CFS-C P 75/2.5 110 mm 3.0 mm CFS-C P 110/4 Polo Kal NG (PP-CO/ POLOPLAST 32 mm 1.8 mm CFS-C P 50/1.5 EI 120-U/U PP-MV/PP-CO) 40 mm 1.8 mm CFS-C P 50/1.5 50 mm 2.0 mm CFS-C P 50/1.5 75 mm 2.6 mm CFS-C P 75/2.5 90 mm 3 mm CFS-C P 90/3 110 mm 3.4 mm CFS-C P 110/4 Polo Kal 3S (PP/PP- POLOPLAST 75 mm 3.8 mm CFS-C P 75/2.5 EI 120-U/U MV/PP) 90 mm 4.5 mm CFS-C P 90/3 110 mm 4.8 mm CFS-C P 110/4 Raupiano Plus (PP- Rehau 40 mm 1.8 mm CFS-C P 50/1.5 EI 120-U/U PP-MV/PP) 50 mm 1.8 mm CFS-C P 50/1.5 75 mm 1.9 mm CFS-C P 75/2.5 110 mm 2.7 mm CFS-C P 110/4 Wavin AS (PP) Wavin 58* mm 4.0 mm CFS-C P 63/2 EI 90-U/U 110 mm 5.3 mm CFS-C P 110/4 EI 120-U/U Phonex AS (PP) KeKelit 58* mm 4.0 mm CFS-C P 63/2 EI 90-U/U 110 mm 5.3 mm CFS-C P 110/4 EI 120-U/U Wavin SiTech (PP) Wavin 32 mm 1.8 mm CFS-C P 50/1.5 EI 120-U/U 40 mm 1.8 mm CFS-C P 50/1.5 50 mm 1.8 mm CFS-C P 50/1.5 75 mm 2.3 mm CFS-C P 75/2.5 90 mm 2.8 mm CFS-C P 90/3 110 mm 3.4 mm CFS-C P 110/4 63 mm 5.8 mm CFS-C P 63/2 EI 60-U/U climatherm (PP) 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 63 mm 5.8 mm CFS-C P 63/2 EI 60-U/U Climatherm Faserverbundrohr (PP) 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U Fusiotherm (PP) PROGEF Standard pipe (PP) Dekaprop Industry pipe (PP) 63 mm 5.8 mm CFS-C P 63/2 EI 60-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U +GF+ 63 mm 5.8 mm CFS-C P 63/2 EI 60-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U +GF+ 63 mm 3 mm CFS-C P 63/2 EI 60-U/U 75 mm 3 mm CFS-C P 75/2.5 EI 60-U/U 75 mm 3 mm CFS-C P 75/2.5 EI 120-U/U page 12 Hilti Firestop Collar CFS-C P Issue 04/2013

Branded pipes end configuration U/C designation manufacturer diameter wall Collar size Classification 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/C climatherm (PP) 63 mm 5.8 mm CFS-C P 63/2 EI 60-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/C 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/C Climatherm Faserverbundrohr (PP) 63 mm 5.8 mm CFS-C P 63/2 EI 60-U/C 63 mm 10.5 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/C Firestop 50 mm 6.9 mm CFS-C P 50/1.5 EI 90-U/C (PP) 63 mm 8.6 mm CFS-C P 63/2 EI 60-U/C 75 mm 10.3 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 12.3 mm CFS-C P 90/3 EI 120-U/C 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/C Fusiotherm (PP) 63 mm 5.8 mm CFS-C P 63/2 EI 60-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/C 50 mm 5.6 mm CFS-C P 50/1.5 EI 90-U/C Fusiotherm Faserverbundrohr (PP) 63 mm 7.1 mm CFS-C P 63/2 EI 60-U/C 75 mm 8.4 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 10.1 mm CFS-C P 90/3 EI 120-U/C PROGEF Standard +GF+ 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/C pipe (PP) 63 mm 5. mm CFS-C P 63/2 EI 60-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/C * Values not yet included in the ETA 10/0404. Magnaplast, Skolan-dB DN 58 in accordance to Classification Report 283513/3313FR. Geberit db 20, Kekelit Phonex AS DN 58 and Wavin AS DN 58 in accordance to Classification Report 270040/3200FR. Hilti Firestop Collar CFS-C P Issue 04/2013 page 13

Flexible and rigid walls 100 mm 1.3. Plastic s with Armaflex AF insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Normed pipes material norm diameter PE EN 1519, EN 12201-2, EN 12666-1 PE EN 1519, EN 12201-2, EN 12666-1 PP EN ISO 15874 DIN 8077/8078 Branded s designation Fusiotherm SDR 11 (PP) Fusiotherm Faser SDR 7.4/ S3.2 (PP) Wavin TS (PE-HD 100 RC) Friatherm starr (PVC-C) manufacturer wall Collar size Classification configuration 110 mm 4.2 mm 10 mm CFS-C P 125/5 EI 90-U/U Continued Interrupted 110 mm 4.2 mm 25 mm CFS-C P 160/6 EI 90-U/U Continued sustained 40 mm 3.7 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C diameter wall Collar size Classification configuration 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C 40 mm 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C Wavin 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C Continued 63 mm 5.8 mm 10 mm CFS-C P 75/2.5 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 90 mm 8.2 mm 10 mm CFS-C P 110/4 EI 120-U/C 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Friatec 32 mm 3.6 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 40 mm 4.5 mm 9 mm CFS-C P 63/2 EI 120-U/C 50 mm 5.6 mm 9 mm CFS-C P 75/2.5 EI 120-U/C length 200 mm 63 mm 7.1 mm 10 mm CFS-C P 90/3 EI 120-U/C page 14 Hilti Firestop Collar CFS-C P Issue 04/2013

Branded s designation Rautitan flex (PE-Xa) Climatherm Faserverbundrohr (PP) Firestop (PP) PROGEF Standard pipe (PP) manufacturer diameter wall Collar size Classification configuration Rehau 40 mm 5.5 mm 9 mm CFS-C P 63/2 EI 120-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 63 mm 8.6 mm 10 mm CFS-C P 75/2.5 EI 120-U/C length 250 mm 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C 40 mm 5.5 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 10.3 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C +GF+ 40 mm 3.7 mm 9 mm CFS-C P 50/1.5 EI 120-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 120-U/C 75 mm 6.8 mm 10 mm CFS-C P 90/3 EI 120-U/C length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 04/2013 page 15

Flexible and rigid walls 100 mm 1.4. Composite pipes with Armaflex AF insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Branded pipes designation and material Geberit Mepla (PE-Xb/Al/ PE-HD) Rautitan stabil (PE-Xa/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE) manufacturer diameter wall Collar size Classification configuration Geberit 16 mm 2.0 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 3.0 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 40 mm 3.5 mm 9 mm CFS-C P 63/2 EI 120-U/C 50 mm 4.0 mm 9 mm CFS-C P 63/2 EI 120-U/C 63 mm 4.5 mm 10 mm CFS-C P 75/2.5 EI 60-U/C 75 mm 4.7 mm 10 mm CFS-C P 90/3 EI 90-U/C Rehau 16 mm 2.6 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 4.7 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 120-U/C Ke Kelit 16 mm 2.0 mm 11.5 mm CFS-C P 50/1.5 EI 120-U/C Continued 32 mm 3.0 mm 13 mm CFS-C P 63/2 EI 120-U/C sustained 32 mm 3.0 mm 9 mm CFS-C P 50/1.5 EI 90-U/C 40 mm 4.0 mm 9 mm CFS-C P 50/1.5 EI 90-U/C 50 mm 4.5 mm 9 mm CFS-C P 63/2 EI 90-U/C 63 mm 6.0 mm 10 mm CFS-C P 75/2.5 EI 90-U/C page 16 Hilti Firestop Collar CFS-C P Issue 04/2013

2. Rigid walls The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Rigid walls (E) consisting of comprise concrete, aerated concrete or masonry, minimum density of 650 kg/m 3, minimum 150 mm. Penetration seal consists of a single penetration in the wall with Hilti Firestop Collar CFS-C P (A1) on both sides. Annular gap filled with Gypsum plaster (A3) or cementitious mortar over the entire of the wall or Hilti Firestop Acrylic Sealant CFS-S ACR (A2) with a depth of minimum 15 mm from the surface of the wall. The sealant may be backfilled with mineral wool. Maximum opening diameter: the opening should not be larger than the collar outside diameter to allow safe fixing of the collar to the wall. Minimum distance between collars (s1): 0 mm. Firestop collar (A1) fastened by hooks (F) (minimum number of hooks: see installation instructions) in flexible wall / drywall and low density rigid wall with M8 threaded rods through the wall secured with nuts on both sides. In high density rigid walls, metal anchors may be used as an alternative (e.g. Hilti HUS, DBZ, HSA). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the wall. For maximum see tables below. Hilti Firestop Collar CFS-C P Issue 04/2013 page 17

Rigid walls 150 mm 2.1. Plastic s Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on each side of the seal and fixed together with M8 threaded rods, washers and nuts. Normed pipes end configuration U/U material norm diameter wall Collar size Classification PVC-U EN ISO 1452-2, 180 mm 3.6 8.6 mm CFS-C P 180/7 EI 180-U/U EN ISO 15493, DIN 8061/2, EN 1329-1, EN 200 mm 4.0 9.6 mm CFS-C P 200/8 EI 180-U/U 1453-1 225 mm 4.5 10.8 mm CFS-C P 225/9 EI 180-U/U 250 mm 4.9 11.9 mm CFS-C P 250/10 EI 180-U/U PE EN 1519, EN 12201-2, 200 mm 6.2 mm CFS-C P 200/8 EI 120-U/U EN 12666-1 250 mm 7.8 mm CFS-C P 250/10 EI 120-U/U EN ISO 15494, DIN 180 mm 4.4 16.4 mm CFS-C P 180/7 EI 120-U/U 8074/5 200 mm 4.9 11.4 mm CFS-C P 200/8 EI 120-U/U 200 mm 11.4 mm CFS-C P 200/8 EI 180-U/U 225 mm 5.5 12.8 mm CFS-C P 225/9 EI 180-U/U 250 mm 6.2 14.2 mm CFS-C P 250/10 EI 180-U/U EN ISO 15494, DIN 50 mm 2.9 mm CFS-C P 50/1.5 EI 180-U/C 8074/5 250 mm 7.8 mm CFS-C P 250/10 EI 180-U/C 250 mm 7.8 22.7 mm CFS-C P 250/10 EI 120-U/C Normed pipes end configuration U/C material norm diameter wall Collar size Classification PVC-U EN ISO 1452-2, 50 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/C EN ISO 15493, DIN 8061/2, EN 1329-1, 250 mm 4.9 11.9mm CFS-C P 250/10 EI 180-U/C EN 1453-1 PE EN ISO 15494, 50 mm 2.9 mm CFS-C P 50/1.5 EI 180-U/C DIN 8074/5 250 mm 7.8 mm CFS-C P 250/10 EI 180-U/C 250 mm 7.8 22.7 mm CFS-C P 250/10 EI 120-U/C page 18 Hilti Firestop Collar CFS-C P Issue 04/2013

3. Rigid floors, minimum density of 2400 kg/m 3 The intended use of the Hilti Firestop Collar CFS-C is to reinstate the fire resistance of: Rigid floors (E) consisting of concrete with a minimum density of 2400 kg/m 3, minimum 150 mm. Penetration seal consists of a single penetration in the floor with Hilti Firestop Collar CFS-C P (A1) on the underside of the floor. Annular gap filled either with gypsum plaster or cementitious mortar (A3) over the entire of the floor or with mineral wool of minimum density 60 kg/m 3 covered by Hilti Firestop Acrylic Sealant CFS-S ACR (A2) on top side (or on both sides) with a depth of minimum 10 mm. Classifications EI 120 and lower (opening diameter up to 300 mm), classification EI 180 (opening diameter up to 260 mm): The opening diameter should not be larger than the collar outside diameter to allow a safe fixing of the collar to the floor. Classification EI 180 (opening diameter > 260 mm): see in tables below. Minimum distance between collars/annular gap edge (s1): 0 mm. Firestop collar (A1) fastened by hooks (minimum number of hooks: see instructions for use) with metal anchors (e.g. Hilti HUS, DBZ, HSA) on the underside of the floor (minimum 6 mm up to collar size 110/4" and 10 mm for higher collar sizes). Sound decoupling strips (C1) based on PE foam, used in combination with gypsum plaster or mortar as gap filler. Sound decoupling installed around the pipe within the floor. For maximum see tables below. Hilti Firestop Collar CFS-C P Issue 04/2013 page 19

Annular gap seal (drawings show non-insulated pipes as example) Gypsum plaster or cementitious mortar (A 3 ) Cementitious mortar (A 3 ) together with sound decoupling (C 1 ) A3 C1 Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) insulation (drawings show mortar as an example for the annular gap seal) Local/Sustained pipe insulation (LS) Continued/Sustained pipe insulation (CS) Gypsum plaster or cementitious mortar (A 3 ) Hilti Firestop Acrylic Sealant CFS-S ACR (A 2 ) page 20 Hilti Firestop Collar CFS-C P Issue 04/2013

Rigid Floors 2400 kg/m 3 3.1. Pre-insulated s Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Branded s material manufacturer diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 60-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 04/2013 page 21

Rigid Floors 2400 kg/m 3 3.2. Plastic s Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Normed pipes end configuration U/U material norm diameter wall Collar size Classification PVC-U EN ISO 1452-2, 20 mm 1.5 2.2 mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, 50 mm 2.4 5.6 mm CFS-C P 50/1.5 EN 1329-1, 63 mm 3.0 4.7 mm CFS-C P 63/2 EN 1453-1 75 mm 2.2 3.6 mm CFS-C P 75/2.5 90 mm 2.7 4.3 mm CFS-C P 90/3 110 mm 1.8 8.1 mm CFS-C P 110/4 125 mm 3.7 6.0 mm CFS-C P 125/5 160 mm 2.5 11.8 mm CFS-C P 160/6 180 mm 3.6 8.6 mm CFS-C P 180/7 200 mm 4.0 9.6 mm CFS-C P 200/8 225 mm 4.5 10.8 mm CFS-C P 225/9 250 mm 4.9 11.9 mm CFS-C P 250/10 PE EN 1519, 50 mm 3.0 mm CFS-C P 50/1.5 EI 120-U/U EN 12201-2, EN 12666-1 63 mm 3.0 mm CFS-C P 63/2 75 mm 3.0 mm CFS-C P 75/2.5 90 mm 3.5 mm CFS-C P 90/3 110 mm 4.2 mm CFS-C P 110/4 125 mm 4.8 mm CFS-C P 125/5 160 mm 6.2 mm CFS-C P 160/6 200 mm 6.2 mm CFS-C P 200/8 250 mm 7.7 mm CFS-C P 250/10 EN ISO 15494, 20 mm 1.9 2.8 mm CFS-C P 50/1.5 EI 90-U/U DIN 8074/5 50 mm 2.9 4.6 mm CFS-C P 50/1.5 EI 120-U/U 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 120-U/U 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 2.2 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 2.7 10.0 mm CFS-C P 110/4 EI 120-U/U 125 mm 3.1 7.1 mm CFS-C P 125/5 EI 120-U/U 160 mm 4.0 9.1 mm CFS-C P 160/6 EI 120-U/U EN ISO 15494, 20+20 mm 1.9 mm CFS-C P 50/1.5 EI 90-U/U DIN 8074/5 2 s in 1 Collar 20+20 mm 2.8 mm CFS-C P 50/1.5 PP EN ISO 15874 20 mm 1.9 3.4 mm CFS-C P 50/1.5 EI 120-U/U DIN 8077/8078 50 mm 1.8 2.9 mm CFS-C P 50/1.5 EI 120-U/U 63 mm 1.8 5.8 mm CFS-C P 63/2 EI 180-U/U 75 mm 1.9 6.8 mm CFS-C P 75/2.5 EI 180-U/U 90 mm 2.2 8.2 mm CFS-C P 90/3 EI 180-U/U 110 mm 2.7 mm CFS-C P 110/4 EI 180-U/U 125 mm 3.1 mm CFS-C P 125/5 EI 180-U/U page 22 Hilti Firestop Collar CFS-C P Issue 04/2013

Normed pipes end configuration U/C material norm diameter wall Collar size Classification PVC-U EN ISO 1452-2, 50 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/C EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1 250 mm 4.0 11.9 mm CFS-C P 250/10 PE EN ISO 15494, DIN 8074/5 End Configuration U/C PP EN ISO 15874 DIN 8077/8078 50 mm 2.9 mm CFS-C P 50/1.5 EI 180-U/C 180 mm 4.4 16.4 mm CFS-C P 180/7 EI 120-U/C 200 mm 4.9 11.4 mm CFS-C P 200/8 EI 120-U/C 225 m 5.5 12.8 mm CFS-C P 225/9 EI 120-U/C 250 mm 6.2 22.7 mm CFS-C P 250/10 EI 120-U/C 250 mm 7.8 mm CFS-C P 250/10 EI 180-U/C 40 mm 3.7 5.5 mm CFS-C P 50/1.5 EI 120-U/C 50 mm 4.6 8.3 mm CFS-C P 50/1.5 EI 180-U/C 63 mm 5.8 10.5 mm CFS-C P 63/2 EI 180-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/C 75 mm 6.8 12.5 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/C 90 mm 8.2 15.0 mm CFS-C P 90/3 EI 120-U/C 110 mm 10.0 15.1 mm CFS-C P 110/4 EI 120-U/C Hilti Firestop Collar CFS-C P Issue 04/2013 page 23

Branded pipes end configuration U/U designation manufacturer diameter wall Collar size Classification Geberit Silent-db20 Geberit 75 mm 3.6 mm CFS-C P 75/2.5 EI 180-U/U (PE-S2) 90 mm 5.6 mm CFS-C P 90/3 EI 180-U/U 135 mm 6.0 mm CFS-C P 160/6 EI 120-U/U 160 mm 7.0 mm CFS-C P 160/6 EI 180-U/U Wavin TS Wavin 50 mm 4.6 mm CFS-C P 50/1.5 EI 90-U/U (PE-HD 100 RC) 63 mm 5.8 mm CFS-C P 63/2 EI 120-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 120-U/U 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/U Skolan-dB Magnaplast 58 mm 4.0 mm CFS-C P 63/2 EI 180-U/U 78 mm 4.5 mm CFS-C P 75/2.5 90 mm 4.5 mm CFS-C P 90/3 110 mm 5.3 mm CFS-C P 110/4 135 mm 5.3 mm CFS-C P 160/6 160 mm 5.3 mm CFS-C P 160/6 Raupiano Plus Rehau 40 mm 1.8 mm CFS-C P 50/1.5 EI 90-U/U (PP-PP-MV/PP) 50 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/U 75 mm 1.9 mm CFS-C P 75/2.5 EI 180-U/U 110 mm 2.7 mm CFS-C P 110/4 EI 180-U/U Wavin AS / Wavin 58 mm 4.0 mm CFS-C P 63/2 EI 90-U/U 78 mm 4.5 mm CFS-C P 75/2.5 EI 180-U/U 90 mm 4.5 mm CFS-C P 90/3 EI 180-U/U 110 mm 5.3 mm CFS-C P 110/4 EI 90-U/U 135 mm 5.3 mm CFS-C P 160/6 EI 180-U/U 160 mm 5.3 mm CFS-C P 160/6 EI 180-U/U KeKelit Phonex AS KeKelit 58 mm 4.0 mm CFS-C P 63/2 EI 90-U/U 78 mm 4.5 mm CFS-C P 75/2.5 EI 180-U/U 90 mm 4.5 mm CFS-C P 90/3 EI 180-U/U 110 mm 5.3 mm CFS-C P 110/4 EI 90-U/U 135 mm 5.3 mm CFS-C P 160/6 EI 180-U/U 160 mm 5.3 mm CFS-C P 160/6 EI 180-U/U Wavin SiTech Wavin 32 mm 1.8 mm CFS-C P 50/1.5 EI 90-U/U 40 mm 1.8 mm CFS-C P 50/1.5 EI 90-U/U 50 mm 1.8 mm CFS-C P 50/1.5 EI 90-U/U 75 mm 2.3 mm CFS-C P 75/2.5 EI 180-U/U 90 mm 2.8 mm CFS-C P 90/3 EI 180-U/U 110 mm 3.4 mm CFS-C P 110/4 EI 90-U/U 125 mm 3.9 mm CFS-C P 125/5 EI 180-U/U 160 mm 4.9 mm CFS-C P 160/6 EI 180-U/U page 24 Hilti Firestop Collar CFS-C P Issue 04/2013

Branded pipes end configuration U/U designation manufacturer diameter wall Collar size Classification Master 3 life 32 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/U 40 mm 1.8 mm CFS-C P 50/1.5 EI 180-U/U 50 mm 1.8 mm CFS-C P 50/1.5 EI 120-U/U 75 mm 2.1 mm CFS-C P 75/2.5 EI 180-U/U 110 mm 3.0 mm CFS-C P 110/4 EI 90-U/U Polo Kal NG POLOPLAST 32 mm 1.8 mm CFS-C P 50/1.5 EI 120-U/U 40 mm 1.8 mm CFS-C P 50/1.5 EI 120-U/U 50 mm 2.0 mm CFS-C P 50/1.5 EI 120-U/U 75 mm 2.6 mm CFS-C P 75/2.5 EI 120-U/U 90 mm 3 mm CFS-C P 90/3 EI 180-U/U 110 mm 3.4 mm CFS-C P 110/4 125 mm 3.9 mm CFS-C P 125/5 160 mm 4.9 mm CFS-C P 160/6 Polo Kal 3S POLOPLAST 75 mm 3.8 mm CFS-C P 75/2.5 90 mm 4.5 mm CFS-C P 90/3 110 mm 4.8 mm CFS-C P 110/4 EI 90-U/U 125 mm 5.3 mm CFS-C P 125/5 EI 180-U/U 20 mm 1.9 mm CFS-C P 50/1.5 EI 180-U/U climatherm 63 mm 5.8 mm CFS-C P 63/2 EI 180-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 90-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/U 20 mm 2.8 mm CFS-C P 50/1.5 EI 180-U/U Climatherm Faserverbundrohr 63 mm 5.8 mm CFS-C P 63/2 EI 90-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/U Firestop 20 mm 2.8 mm CFS-C P 50/1.5 EI 90-U/U 20 mm 1.9 mm CFS-C P 50/1.5 EI 180-U/U Fusiotherm 63 mm 5.8 mm CFS-C P 63/2 EI 180-U/U 75 mm 6.8 mm CFS-C P 75/2.5 EI 90-U/U 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/U 20 mm 2.8 mm CFS-C P 50/1.5 EI 180-U/U Fusiotherm Faserverbundrohr Dekaprop Industry +GF+ 63 mm 3.0 mm CFS-C P 63/2 EI 90-U/U pipe 75 mm 3.0 mm CFS-C P 75/2.5 EI 90-U/U 90 mm 3.0 mm CFS-C P 90/3 EI 90-U/U Hilti Firestop Collar CFS-C P Issue 04/2013 page 25

Branded pipes end configuration U/C designation manufacturer diameter wall Collar size Classification climatherm 40 mm 3.7 mm CFS-C P 50/1.5 EI 120-U/C End Configuration 50 mm 4.6 mm CFS-C P 50/1.5 EI 180-U/C U/C 63 mm 5.8 mm CFS-C P 63/2 EI 180-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/C 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/C 40 mm 3.7 mm CFS-C P 50/1.5 EI 120-U/C Climatherm Faserverbundrohr End Configuration 50 mm 4.6 mm CFS-C P 50/1.5 EI 180-U/C U/C 63 mm 5.8 mm CFS-C P 63/2 EI 180-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/C 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/C Firestop 40 mm 5.5 mm CFS-C P 50/1.5 EI 120-U/C End Configuration 50 mm 6.9 mm CFS-C P 50/1.5 EI 180-U/C U/C 63 mm 8.6 mm CFS-C P 63/2 EI 180-U/C 75 mm 10.3 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 12.3 mm CFS-C P 90/3 EI 120-U/C 110 mm 15.1 mm CFS-C P 110/4 EI 120-U/C 40 mm 3.7 mm CFS-C P 50/1.5 EI 120-U/C Fusiotherm End Configuration 50 mm 4.6 mm CFS-C P 50/1.5 EI 180-U/C U/C 63 mm 5.8 mm CFS-C P 63/2 EI 180-U/C 75 mm 6.8 mm CFS-C P 75/2.5 EI 180-U/C 90 mm 8.2 mm CFS-C P 90/3 EI 180-U/C 110 mm 10.0 mm CFS-C P 110/4 EI 120-U/C 40 mm 5.5 mm CFS-C P 50/1.5 EI 120-U/C Fusiotherm Faserverbundrohr End Configuration 50 mm 6.9 mm CFS-C P 50/1.5 EI 180-U/C U/C 63 mm 8.6 mm CFS-C P 63/2 EI 180-U/C 75 mm 10.3 mm CFS-C P 75/2.5 EI 120-U/C 90 mm 12.3 mm CFS-C P 90/3 EI 120-U/C 110 mm 15.1 mm CFS-C P 110/4 EI 120-U/C page 26 Hilti Firestop Collar CFS-C P Issue 04/2013

Rigid Floors 2400 kg/m 3 3.3. Plastic s with Armaflex AF insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Normed pipes material norm diameter PP EN ISO 15874 DIN 8077/8078 Branded pipes designation Wavin TS (PE- HD-100 RC) Friatherm starr (PVC-C) Rautitan flex (PE-Xa) climatherm manufacturer wall Collar size Classification configuration 40 mm 3.7 5.5 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 4.6 6.9 mm 9 mm CFS-C P 75/2.5 EI 180-U/C 75 mm 6.8 10.3 mm 10 mm CFS-C P 90/3 EI 180-U/C length 250 mm 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 10.0 15.1 mm 10 mm CFS-C P 125/5 EI 180-U/C diameter wall Collar size Classification configuration Wavin 50 mm 4.6 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued Supllier 63 mm 5.8 mm 10 mm CFS-C P 75/2.5 75 mm 6.8 mm 10 mm CFS-C P 90/3 length 250 mm 90 mm 8.2 mm 9.5 mm CFS-C P 110/4 110 mm 10.0 mm 9.5 mm CFS-C P 125/5 Friatec 32 mm 3.6 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Continued 40 mm 4.5 mm 9 mm CFS-C P 63/2 50 mm 5.6 mm 9 mm CFS-C P 75/2.5 length 200 mm 63 mm 7.1 mm 10 mm CFS-C P 90/3 Rehau 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 6.9 mm 9 mm CFS-C P 75/2.5 EI 180-U/C 63 mm 8.6 mm 9 mm CFS-C P 90/3 EI 180-U/C length 250 mm 40 mm 6.0 mm 9 20.5 mm CFS-C P 63/2 EI 120-U/C 75/2.5 50 mm 6.9 mm 9 21 mm CFS-C P 75/2.5 EI 120-U/C 90/3 63 mm 8.6 mm 9 21.5 mm CFS-C P 90/3 EI 120-U/C 110/4 40 mm 3.7 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 75/2.5 75 mm 6.8 mm 10 mm CFS-C P 90/3 length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 Hilti Firestop Collar CFS-C P Issue 04/2013 page 27

Branded pipes designation climatherm Faserverbundrohr firestop fusiotherm fusiotherm Faserverbundrohr +GF+ PROGEF Standard pipe manufacturer diameter wall Collar size Classification configuration 40 mm 3.7 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 4.6 mm 9 mm CFS-C P 75/2.5 75 mm 6.8 mm 10 mm CFS-C P 90/3 length 250 mm 110 mm 10.0 mm 10 mm CFS-C P 125/5 40 mm 5.5 mm 9 mm CFS-C P 63/2 EI 180-U/C 50 mm 6.9 mm 9 mm CFS-C P 75/2.5 EI 180-U/C 75 mm 10.3 mm 10 mm CFS-C P 90/3 EI 180-U/C 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 15.1 mm 10 mm CFS-C P 125/5 EI 180-U/C 40 mm 3.7 mm 9 mm CFS-C P 63/2 50 mm 4.6 mm 9 mm CFS-C P 75/2.5 75 mm 6.8 mm 10 mm CFS-C P 90/3 110 10.0 mm 10 mm CFS-C P 125/5 40 mm 4.5 mm 9 mm CFS-C P 63/2 EI 180-U/C 50 mm 6.9 mm 9 mm CFS-C P 75/2.5 EI 180-U/C 75 mm 10.3 mm 10 mm CFS-C P 90/3 EI 180-U/C 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 15.1 mm 10 mm CFS-C P 125/5 EI 180-U/C +GF+ 40 mm 3.7 mm 9 mm CFS-C P 63/2 50 mm 4.6 mm 9 mm CFS-C P 75/2.5 75 mm 6.8 mm 10 mm CFS-C P 90/3 110 mm 10.0 mm 10 mm CFS-C P 125/5 Rigid Floors 2400 kg/m 3 3.4. Composite pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Branded pipes designation manufacturer diameter wall Collar size Classification Geberit Mepla Geberit 40 mm 3.5 mm CFS-C P 50/1.5 EI 90-U/C (PE-Xb/Al/PE-HD) 50 mm 4.0 mm CFS-C P 50/1.5 EI 120-U/C 63 mm 4.5 mm CFS-C P 63/2 EI 60-U/C 75 mm 4.7 mm CFS-C P 75/2.5 EI 30-U/C page 28 Hilti Firestop Collar CFS-C P Issue 04/2013

Rigid floors 2400 kg/m 3 3.5. Composite pipes with Armaflex AF insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Branded s designation Geberit Mepla (PE-Xb/Al/ PE-HD) Geberit Mepla (PE-Xb/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE-X) KELOX KM 110 (PE-X/Al/ PE-X) KELOX KM 110 (PE-X/Al/ PE-X) Rautitan stabil (PE-Xa//Al/ PE-HD) manufacturer diameter wall Collar size Classification configuration Geberit 40 mm 3.5 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 50 mm 4.0 mm 9 mm CFS-C P 63/2 63 mm 4.5 mm 9 mm CFS-C P 75/2.5 length 250 mm 75 mm 4.7 mm 10 mm CFS-C P 90/3 Geberit 40 mm 3.5 mm 9 20.5 mm CFS-C P 63/2 EI 120-U/C 75/2.5 50 mm 4.0 mm 9 21 mm CFS-C P 63/2 90/3 63 mm 4.5 mm 9 21.5 mm CFS-C P 75/2.5 110/4 75 mm 4.7 mm 10 22 mm CFS-C P 90/3 125/5 KeKelit 32 mm 3.0 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Continuated 40 mm 4.0 mm 9 mm CFS-C P 50/1.5 EI 180-U/C Sustained 50 mm 4.5 mm 9 mm CFS-C P 63/1.5 EI 180-U/C 63 mm 6.0 mm 10 mm CFS-C P 75/2.5 EI 120-U/C KeKelit 32 mm 3.0 mm 9 19.5 mm CFS-C P 50/1.5 EI 120-U/C Continuated 75/2.5 Sustained 40 mm 4.0 mm 9 20.5 mm CFS-C P 50/1.5 75/2.5 50 mm 4.5 mm 9 21 mm CFS-C P 63/2 90/3 63 mm 6.0 mm 10 21.5 mm CFS-C P 75/2.5 110/4 KeKelit 32 mm 3.0 mm 19.5 mm CFS-C P 75/2.5 EI 120-U/C Continued 40 mm 4.0 mm 20.5 mm CFS-C P 75/2.5 50 mm 4.5 mm 21 mm CFS-C P 90/3 length 250 mm 63 mm 6.0 mm 21.5 mm CFS-C P 110/4 Rehau 40 mm 6.0 mm 9 mm CFS-C P 63/2 EI 180-U/C Continued 40 mm 6.0 mm 9-20.5 mm CFS-C P 63/2 EI 120-U/C 75/2.5 length 250 mm Hilti Firestop Collar CFS-C P Issue 04/2013 page 29

4. Rigid floors, minimum density of 550 kg/m 3 The floor must have a minimum of 150 mm and comprise concrete or aerated concrete with a minimum density of 550 kg/m 3. For details of the penetration seal design see 3. s shall be supported at maximum 200 mm at maximum 250 mm away from the upper face of the floor construction. Rigid Floors 550 kg/m 3 4.1. Pre-insulated s Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Branded pipes material manufacturer diameter Inner pipe diameter Collar size Classification ABS/PUR insulation/ +GF+ COOL-FIT 90 mm 32 mm CFS-C P 90/3 EI 120-U/C PE-HD 110 mm 40 mm CFS-C P 110/4 EI 120-U/C 110 mm 50 mm CFS-C P 110/4 EI 120-U/C 160 mm 90 mm CFS-C P 160/6 EI 120-U/C 180 mm 110 mm CFS-C P 180/7 EI 60-U/C 225 mm 140 mm CFS-C P 225/9 EI 120-U/C 250 mm 160 mm CFS-C P 250/10 EI 120-U/C Rigid Floors 550 kg/m 3 4.2. Plastic s Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts Normed pipes end configuration U/U material norm diameter wall Collar size Classification PVC-U EN ISO 1452-2, 20 mm 1.5 2.2 mm CFS-C P 50/1.5 EI 120-U/U EN ISO 15493, DIN 8061/2, EN 1329-1, EN 1453-1 End Configuration U/U 50 mm 2.4 5.6 mm CFS-C P 50/1.5 EI 120-U/U PE EN ISO 15494, DIN 8074/5 End Configuration U/U EN ISO 15494, DIN 8074/5 2 s in 1 Collar PP EN ISO 15874 DIN 8077/8078 20 mm 1.9 2.8 mm CFS-C P 50/1.5 EI 90-U/U 50 mm 2.9 4.6 mm CFS-C P 50/1.5 EI 90-U/U 20+20 mm 1.9 mm CFS-C P 50/1.5 EI 90-U/U 20+20 mm 2.8 mm CFS-C P 50/1.5 EI 90-U/U 20 mm 1.9 3.4 mm CFS-C P 50/1.5 EI 120-U/U page 30 Hilti Firestop Collar CFS-C P Issue 04/2013

Normed pipes end configuration U/C material norm diameter wall Collar size Classification PP EN ISO 15874 40 mm 3.7 5.5 mm CFS-C P 50/1.5 EI 120-U/C DIN 8077/8078 50 mm 4.6 6.9 mm CFS-C P 50/1.5 75 mm 6.8 mm CFS-C P 75/2.5 90 mm 12.3 mm CFS-C P 90/3 110 mm 10.0 15.1 mm CFS-C P 110/4 Branded pipes end configuration U/U designation manufacturer diameter wall Collar size Classification Master 3 (PP-CO/ life 32 mm 1.2 mm CFS-C P 50/1.5 EI 90-U/U PP-MV/PP-CO) 40 mm 1.8 mm CFS-C P 50/1.5 50 mm 1.8 mm CFS-C P 50/1.5 75 mm 1.8 mm CFS-C P 75/2.5 110 mm 1.8 mm CFS-C P 110/4 Polo Kal 3S (PP/ POLOPLAST 75 mm 3.8 mm CFS-C P 75/2.5 EI 90-U/U PP-MV/PP) 90 mm 4.5 mm CFS-C P 90/3 110 mm 4.8 mm CFS-C P 110/4 Polo Kal NG (PP-CO/ POLOPLAST 32 mm 1.8 mm CFS-C P 50/1.5 EI 90-U/U PP-MV/PP-CO) 40 mm 1.8 mm CFS-C P 50/1.5 50 mm 2.0 mm CFS-C P 50/1.5 75 mm 2.6 mm CFS-C P 75/2.5 90 mm 3.0 mm CFS-C P 90/3 110 mm 3.6 mm CFS-C P 110/4 20 mm 1.9 mm CFS-C P 50/1.5 EI 120-U/U climatherm 20 mm 2.8 mm CFS-C P 50/1.5 EI 120-U/U climatherm Faserverbundrohr firestop 20 mm 2.8 mm CFS-C P 50/1.5 EI 120-U/U fusiotherm 20 mm 1.9 mm CFS-C P 50/1.5 EI 120-U/U fusiotherm 20 mm 2.8 mm CFS-C P 50/1.5 EI 120-U/U Faserverbundrohr +GF+ PROGEF +GF+ 20 mm 1.9 mm CFS-C P 50/1.5 EI 120-U/U Standard pipe, +GF+ Dekaprop Industry pipe +GF+ 20 mm 3.0 mm CFS-C P 50/1.5 EI 120-U/U Hilti Firestop Collar CFS-C P Issue 04/2013 page 31

Branded pipes end configuration U/C designation manufacturer diameter wall Collar size Classification 40 mm 3.7 mm CFS-C P 63/2 EI 120-U/C climatherm 50 mm 4.6 mm CFS-C P 75/2.5 75 mm 6.8 mm CFS-C P 90/3 110 mm 10.0 mm CFS-C P 125/5 40 mm 3.7 mm CFS-C P 63/2 EI 120-U/C climatherm Faserverbundrohr 50 mm 4.6 mm CFS-C P 75/2.5 75 mm 6.8 mm CFS-C P 90/3 110 mm 10.0 mm CFS-C P 125/5 firestop 40 mm 5.5 mm CFS-C P 63/2 EI 120-U/C 50 mm 6.9 mm CFS-C P 75/2.5 90 mm 12.3 mm CFS-C P 160/6 110 15.1 mm CFS-C P 125/5 fusiotherm 40 mm 3.7 mm CFS-C P 63/2 EI 120-U/C 50 mm 4.6 mm CFS-C P 75/2.5 75 mm 6.8 mm CFS-C P 90/3 110 10.0 mm CFS-C P 125/5 fusiotherm 40 mm.5 mm CFS-C P 63/2 EI 120-U/C Faserverbundrohr 50 mm 6.9 mm CFS-C P 75/2.5 90 mm 12.3 mm CFS-C P 160/6 110 15.1 mm CFS-C P 125/5 +GF+ PROGEF +GF+ 40 mm 3.7 mm CFS-C P 63/2 EI 120-U/C Standard pipe 50 mm 4.6 mm CFS-C P 75/2.5 75 mm 6.8 mm CFS-C P 90/3 110 10.0 mm CFS-C P 125/5 page 32 Hilti Firestop Collar CFS-C P Issue 04/2013

Rigid Floors 550 kg/m 3 4.3. Plastic s with Armaflex AF insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Normed pipes end configuration U/C material norm diameter PP EN ISO 15874 DIN 8077/8078 Branded pipes end configuration U/C designation Rautitan flex (PE-Xa) Climatherm Faserverbundrohr Fusiotherm Faserverbundrohr Firestop manufacturer wall Collar size Classification configuration 90 mm 110 mm 12.3 mm 15.1 mm 22.5 mm 10 mm CFS-C P 160/6 CFS-C P 125/5 EI 120-U/C EI 120-U/C Continued length 250 mm diameter wall Collar size Rehau 40 mm 6.0 mm 20.5 mm CFS-C P 63/2 75/2.5 50 mm 6.9 mm 21 mm CFS-C P 75/2.5 90/3 Classification EI 120-U/C EI 120-U/C 63 mm 8.6 mm 21.5 mm CFS-C P 110/4 EI 120-U/C 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C 90 mm 12.3 mm 22.5 mm CFS-C P 160/6 EI 120-U/C 110 mm 15.1 mm 10 mm CFS-C P 125/5 EI 120-U/C configuration Continued length 250 mm Hilti Firestop Collar CFS-C P Issue 04/2013 page 33

Rigid Floors 550 kg/m 3 4.4. Composite pipes Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Branded pipes end configuration U/C designation manufacturer diameter wall Collar size Classification Geberit Mepla Geberit 40 mm 3.5 mm CFS-C P 50/1.5 EI 90-U/C (PE-Xb/Al/PE-HD) 50 mm 4.0 mm CFS-C P 50/1.5 EI 120-U/C 63 mm 4.5 mm CFS-C P 63/2 EI 60-U/C 75 mm 4.7 mm CFS-C P 75/2.5 EI 30-U/C Rigid Floors 550 kg/m 3 4.5. Composite pipes with Armaflex AF insulation Minimum distance between pipe closure devices: 0 mm. Hilti Firestop Collar CFS-C P (A 3 ) installed on bottom side of seal and fixed with M8 threaded rods, washers and nuts. Branded pipes end configuration U/C designation Geberit Mepla (PE-Xb/Al/ PE-HD) KELOX KM 110 (PE-X/Al/ PE-X) Rautitan stabil (PE-Xa/Al/ PE-HD) manufacturer diameter wall Collar size Geberit 40 mm 3.5 mm 20.5 mm CFS-C P 63/2 75/2.5 50 mm 4.0 mm 21 mm CFS-C P 63/2 90/3 63 mm 4.5 mm 21.5 mm CFS-C P 75/2.5 110/4 75 mm 4.7 mm 22 mm CFS-C P 90/3 125/5 Classification EI 120-U/C EI 120-U/C EI 120-U/C EI 120-U/C configuration Continued length 250 mm KeKelit 32 mm 3.0 mm 19.5 mm CFS-C P 75/2.5 EI 120-U/C Continued 40 mm 4.0 mm 20.5 mm CFS-C P 75/2.5 EI 120-U/C 50 mm 4.5 mm 21 mm CFS-C P 90/3 EI 120-U/C length 250 mm 63 mm 6.0 mm 21.5 mm CFS-C P 110/4 EI 120-U/C Rehau 40 mm 6.0 mm 20.5 mm CFS-C P 63/2 EI 120-U/C Continued 75/2.5 length 250 mm page 34 Hilti Firestop Collar CFS-C P Issue 04/2013

Loose mineral wool products suitable for being used as backfilling material of CFS-S ACR Firestop Acrylic Sealant: Product Heralan LS Isover loose wool SL Isover Universal-Stopfwolle Rockwool RL Paroc Pro Loose Wool Manufacturer Knauf Saint-Gobain Isover Saint-Gobain Isover Rockwool Paroc OY AB Specification of flexible elastomeric foam products suitable for being used as pipe insulation: Armacell International GmbH: Armaflex AF (CE marked acc. to EN 14304). Hilti Firestop Collar CFS-C P Issue 04/2013 page 35

Hilti Firestop acrylic sealant CFS-S ACR An acrylic based firestop sealant that provides movement capability in fire rated linear joint seals and penetration seals Applications n Within or between flexible wall constructions n Vertical joints in / between wall constructions n Horizontal joints in a wall abutting a floor, ceiling or roof n Joints in floor construction n Penetration seals (steel and copper pipes) Advantages n Easy to dispense, apply and tool n Strong adhesion to various base materials n Low shrinkage after curing n Excellent airborne sound insulation property n Broad application temperature range Technical data CFS-S ACR Chemical basis Water-based acrylic dispersion Volume shrinkage < 20 % Movement 12.5 % (ISO 11600) Cure Time (at 23 C / 50 % r.h.) ~ 3 mm / 72 h Application temperature range 5 C 40 C Storage and transportation 5 C 25 C temperature - range Shelf life (@73 F / 23 C and 24 month(s) 50 % relative humidity) Reaction to fire class D-s1d0 (EN13501-1) Approvals* ETA 10 / 0292, ETA 10 / 0389 * The European Technical Approval (ETA) can be obtained via your local Hilti contact or www.hilti.com Packaging Volume Color Order designation Sales Quantity Item Number Cartridge 310 ml White Firestop acrylic sealant CFS-S ACR 1 pc 00435859 Cartridge 310 ml White Firestop acrylic sealant CFS-S ACR 1 pc 00435860 Cartridge 310 ml Grey Firestop acrylic sealant CFS-S ACR 1 pc 00435862 Foil pack 580 ml White Firestop acrylic sealant CFS-S ACR 20 pc 00435863 Pail 5 l White Firestop acrylic sealant CFS-S ACR 1 pc 00435864 Pail 10 l White Firestop acrylic sealant CFS-S ACR 1 pc 02046766 page 36 Hilti Firestop Collar CFS-C P Issue 04/2013