ALP UPS FEATURES & ADVANTAGES

Similar documents
Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

USER S MANUAL. 10KSS360400/ nd Edition

HANDOUT Electrical Safety How do we make sure that humans and computer equipment are safe from electrical hazards?

Common Mode Noise The Often Neglected Tenth Power Problem

AIR COOLED MODULAR RECTIFIER

Tel: AC Power for Business-Critical Continuity TM

Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System

MUST900 Modular UPS. Datacenter & servers. Internet centers. Local Area Networks (LAN) Telecommunication devices. Emergency application

VOR. VOR-3P200x5-S400-4CT-MTP MODULAR VOLTAGE REGULATOR

Model HM-535 Power Supply Installation and Service Instructions

Wise HP33 THREE PHASE HIGH PRECISION AVR SURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER

POWERVAR SECURITY PLUS SERIES DETAILED UPS SPECIFICATION (8kVA 10kVA)

LPI SST Surge Filters

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

PowerMust Office Uninterruptible Power System

3- and 4-pole switching in UPS installation

ALL PSU Ltd ROTATION+ 6kVA - 10kVA PARALLEL ON LINE DOUBLE CONVERSION

Cirprotec Technical Article No. 5

MC 11 EB-2 Power supply cabinet with external bus, AC version

PREVENTING DOWNTIME OF E911 CENTERS

1PH RACK 19 SINGLE PHASE UPS Rev. 11 SR 6kVA 10kVA

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA. GE Critical Power

ZP120N Online UPS. High Power Intensity. Flexibility. High efficiency with low heat dissipation. Smart Energy Solutions

********SERVICE MANUAL******** MODELS:

2. Control Pin Functions and Applications

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

TETRIS 2500 High Impedance Active Probe. Instruction Manual

Modular UPS S KVA

Model 7705 Control Module

CUS150M1 Instruction Manual

10 kva 3/1 15 kva 3/1 20 kva 3/1 10 kva 3/3 15 kva 3/3 20 kva 3/3 30 kva 3/3 40 kva 3/3 UOUS SERV WARRANTY

QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE

5 to100 Amperes Linear Power Supply/Charger (120 Volt 60Hz) (220 Volt 50Hz)

Torque Series LCD Remote Panel Installation/Operation Manual Model: TQ-DSP-12/24

Setpoint Isolators. Technical Manual. HA Issue Parker SSD Drives, a division of Parker Hannifin Ltd. WARRANTY

ELV12 Series. Instruction Manual

SmartOnline 40kVA Modular 3-Phase UPS System, On-line Double-Conversion UPS for North America

APC Matrix-UPS 3kVA 208V/240V In 120/208/240V Out

True Sinewave Power Inverter 1000W & 2000W 230V , Owner s Manual

UPS READY POWER DISTRIBUTION ASSEMBLY

Modified Sinewave Series. Power Inverter 1000/1500 MW 1210, MW1215. True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220.

GCI-5K INSTALLATION AND OPERATOR S MANUAL

CA-A480-A Elevator Controller. Reference & Installation Manual

PDS8u POWER DISTRIBUTION SYSTEM USER'S MANUAL

PFC Mini TM Power Factor Corrected AC-DC Switchers

Circuit Protection Application Note TBU Electronic Current Limiter GR-1089 Port Type 2 and 4 Ethernet Protection

AIC1520. Ferrite Bead GND. *33µF, 16V Tantalum, or 100µF, 10V Electrolytic Bold line indicate high-current traces. USB High-Side Power Switch

A0750 AC-DC POWER MODULE

SmartOnline 277/480V 3-Phase Wye 80kVA Modular 3-Phase UPS System, On-line Double- Conversion UPS for North America

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Liebert NXr Series 30kVA to 160kVA. AC Power for Business-Critical Continuity TM

Smart Grid Tie Microinverter User Manual

Quick Guide. Extra Communication Card

Ignitron Driver Manual (N = cable length in meters -example IG5F2-10 = unit with a 10 meter cable length)

OFFICE UPS MULTI-DEVICE PROTECTION UPS 500S/600S/750S

TVAC25100 TVAC25110 User manual

INSTALLATION INSTRUCTIONS

AOZ8900. Ultra-Low Capacitance TVS Diode Array PRELIMINARY. Features. General Description. Applications. Typical Application

Nature Power Inverters. Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w. Owner s Manual

LPI SG + SST Spark Gap Surge Filter

Isobar 12-Outlet Network Server Surge Protector, 15 ft. Cord, 3840 Joules, Diagnostic LEDs, 1U Rack-Mount, Metal Housing

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

LIGHTNING AND SURGE PROTECTION

Technical Data Sheet Medium Current Power Surge Filters

T SERIES UPS kva PF Vac with Internal Battery 7.0 Touch Screen. User Guide

Removal of Hardware ESD, Independent of Safety Logic Solver

BOP QUICK START GUIDE 100W, 200W, 400W. KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY I INTRODUCTION

SMARTONLINE E3 UPS SYSTEMS

FutureNow FNIP-6x2AD

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA

SmartOnline 40kVA Modular 3-Phase UPS System, On-line Double-Conversion UPS for North America

APPLICATION NOTE. Controlling Inrush Current in DC-DC Power Converters. Inrush Current Waveform

Symmetra LX APC Symmetra LX 8kVA Scalable to 8kVA N+1 Rack-mount, 208/240V Input, 208/240V and 120V Output

JUPITER Plus CHUPHOTIC. Performance Power Solutions. JUPITER Plus From 10 kva to 600 kva

Model: Pro93 TRUE RMS LEAKAGE CURRENT TESTER

Symmetra LX APC Symmetra LX 8kVA Scalable to 16kVA N+1, Tower 208/240V Input, 208/240V and 120V Output

Kohler EW 6000TX. Transformer-based. (UPS kVA)

UPS Series. features: uninterruptible power supply. what great systems are built on.

Quantum Chargers Enhanced AC Line Transient Immunity

MA5 active monitor. user manual

Why Optically Isolate Your Data Communication Lines?

GSI three-phases series off-grid Inverter User s Manual

Liebert NX Series. 30kVA to 200kVA. AC Power for Business-Critical Continuity TM

EFE300 / EFE400 EFE300M / EFE400M

Isobar 4-Outlet Surge Protector, 6 ft. Cord with Right-Angle Plug, 3330 Joules, Diagnostic LEDs, Metal Housing

ESS20 Electronic Circuit Breaker

R E C T I F I E R I N V E R T E R C O N V E R T E R MP7

FAQ about Drives Technology

BOP QUICK START GUIDE 100W, 200W, 400W. KEPCO An ISO 9001 Company. BIPOLAR OPERATIONAL POWER SUPPLY WARNINGS I INTRODUCTION II SAFETY.

ELG4125: System Protection

Voltage Dip-Proofing Inverter

24/48V Battery Bank Ah High Cycling Long Life

ME3 Mobile Cabinet Three Phase Frequency Converter, Operation and Maintenence.

THOR Modular. Modular UPS system. Online double-conversion Scalable Decentralized Parallel. Modular. 10, 20, 30, 40kVA modules kVA systems

INSTALLATION, OPERATION AND CONFIGURATION MANUAL September/2016 VRP10-O PROFIBUS-PA OPTICAL REPEATER

PS8 - II. Professional Power Sequencer. User s Manual

VS-P Series. TDK-Lambda INSTRUCTION MANUAL

Symmetra LX APC Symmetra LX 8kVA Scalable to 16kVA N+1 Rack-mount, 208/240V Input, 208/240V and 120V Output

Transcription:

ALP UPS FEATURES & ADVANTAGES 1. True Galvanic Isolation Usually, Y-caps are installed in UPS s input & output to eliminate the electro-magnetic interference, but Y-caps will increase the ground leakage current. Together, with the parasitic capacitance of the unit itself the impedance between power lines and ground becomes very low. Therefore, the grounding quality will be affected, resulting in voltage differences between different systems, and problems will arise, such as the connection terminal sparks when plug in the communication port, or the data transmission seriously interfered. The whole LAN system will be contaminated or even computers (equipments) will be destroyed. The best way to prevent and solve this problem is to completely isolate the UPS output from the input power system. In that case, the UPS output can be tied to any ground at any potential. Not only the noise inside the UPS is stopped, and the output neutral can adapt to any voltage induced by complicated connection of the load system, but also can stop the electro-magnetic interference, surge, and spikes caused by lightning or heavy/inductive load impact/detach nearby, comes through the UPS to the load. Beside, output can remain safe even when neutral is disconnected. Now, protections against over-shoot voltage are explained below. a. Comparative System Diagram Fig 1: ALP True Galvanic Isolation Fig 2: Non-true Galvanic Isolation 1

b. Benefit Explanation (1) In case there are two or more UPSs installed in one building. When Non-isolated UPSs are installed as Fig.3 below, while Vs is the floating voltage and noise voltage between N1 & N2, there will be a considerable large voltage between the communication ports of computer1 and computer2. Therefore, there will be sparks when the two computers are being connected via communication cable. And, the two computers will interfere each other, or even when the voltage difference is strong enough the computers will be damaged. If Galvanic isolated UPSs are installed as Fig.4 below. The Vs between N1 & N2 will not exist (completely isolated) in the output of the UPSs. The phenomenon and accidents mentioned above will never happen. Fig 3:Non-true Galvanic Isolated UPS 2

Fig 4:ALP True Galvanic Isolated UPS (2) Lightning During lightning, power transmission cables are subject to attacks of lightning while very high surge voltage will exist between input L and Ground as Fig.5 below. If common UPS is installed, the input N (neutral) and output N are tied together. Therefore, the surge voltage existing at the output is exactly the size existing in the input. And the voltage is detrimental and dangerous to most of the load, or even if the load has surge protector, it leads to damaging of the load because sometimes the surge energy is larger than the internal surge absorber can endure,. But if true Galvanic isolated UPS is installed as Fig.6, since the input and output ground can be different, thus being connected to different grounds and the impedance between them is very high, the voltage between output L and ground is still zero. That is, absolutely invisible or undectable at the output, surge voltage never reaches the loads. Fig 5:Non-true Galvanic Isolated UPS 3

Fig 6:ALP True Galvanic Isolated UPS (3) Attenuation The noise attenuation of the non-isolated UPS completely relies on the filtering capability of the EMI filters (usually around 40dB to 80dB). But, with the isolation transformer of the Galvanic isolated UPS alone can contribute 120dB (or above). Together with the EMI filter inside, the noise attenuation of the UPS can achieve 200dB, that mean you can get a clean power source as well as without polluting the input. (4) Leakage current In normal power systems, the leakage current of the transmission cables, the leakage current of the UPS, and the leakage current of the load add up to a considerable large amount. If the input NFB is earth leakage current sensing type (for protection of load's faulty current to chassis), that current may force the NFB to trip. But, if Galvanic isolated UPS is used, there is no high frequency components between output neutral and load ground. Therefore, very small leakage current flows out the UPS, and the leakage current flowing into the load is very small too. As a result, the unwanted or annoying tripping of NFB can be prevented, and the load can be connected to the UPS through a long distance. Fig 7:Non-true Galvanic Isolated UPS 4

Fig 8:True Galvanic Isolated UPS (5) Faulty neutral As the figure shown above, the input neutral of the UPS is mistakenly disconnected in reserve or bypass mode, the phase with the lightest load connected will have a voltage rise up to 1.732 X line to neutral voltage (that is, the phase to phase voltage), while the phase with heaviest load will drop to a small voltage (that is, the phase to phase voltage now feed across the input line and neutral). When this condition happens, not only the surge absorber of the UPS will blow (risk of fire), but also the load will be damaged. But, in the same case, if Galvanic isolated UPS is used, the inter-core coupling characteristic of the output transformer will force the input/output neutral to the center point of the 3-phase. Even in the extreme condition of 100% unbalance load and neutral disconnected, the input/output phase to neutral voltage can be kept stably within 5%. In case the UPS output is short circuited, it will be detected and the inverter will limit the current to a safe level until the short circuited time exceed the safe margin, the inverter will automatically shut off, but differing from others, without bypassing the short circuit to mains (preventing the tripping of NFB streams up to top of power distribution, that will shutdown other critical loads!). 5

2. Software and Hardware Redundant Design The UPS employs both hardware and software redundant design, especially in protection circuitry, as the figure above, to ensure safety. The characteristic of CPU control is step by step execution of each program lines. But if one or more lines are jumped over during execution, the following execution may run out of order due to incorrect value inherit from the previous steps. It is very dangerous if short circuit happens when the CPU is not working correctly. Therefore, we add extra hardware circuitry to ensure protection action is taken so as to improve the UPS's reliability and load safety. 3. Component Reliability There are approximately 5,000 components used in one mid-power UPS. The average failure rate of electronic components is 2 PPM. Therefore, excluding the factor of design fault, the failure rate of a UPS caused by components is around (5,000X2/1,000,000)X100%=1%. But our ALP series UPSs employ the quality scheme by a research bureau, for example, sorting the components by 1.5 X rated value, the failure rate of components will drop to 0.2 PPM. Then, the failure rate caused by components is (5000X0.2/1,000,000)X100%=0.1%. That is, only one out of one thousand our UPSs may break down because of component defects. 4. No Harms If Incorrect Operation Different from other UPSs (must follow the specified operation procedures, or else the operator is responsible to the destruction of UPS and loss of user due to power failure), our UPS will not be damaged by any incorrect operation. For example, turning on the bypass breaker of a UPS under inverter operating mode is hazardous to UPS (the inverter is directly shorted to the mains, and unlimited energy will flow either from inverter to mains or from mains to inverter, battery & loads, causing damage of the inverter or high DC voltage damage the connected capacitors or battery. 6

But, our ALP UPSs continuously detect the switches, when the above condition happens, the inverter will shutdown immediately, and transfer the load to the mains. Once the bypass breaker is turned off again, the UPS will perceive and automatically restart and run in inverter mode again. For other breakers and switches, no priority is critical or strictly specified. According to the field statistics, 15% of the UPS failure is caused by incorrect operation; therefore this feature should put in the consideration of UPS design. Non-true Galvanic Isolation ALP True Galvanic Isolation 7

5. Battery Start Usually battery is directly connected to the DC bus, so the inverter cannot be switched on without AC mains because if you close the battery NFB/switch, either someone want to start the UPS with battery only or mistakenly, the current flowing from battery to the empty capacitor is unlimited, the DC capacitor may blow due to very large surge current. But, we put a magnetic switch to limit the current. Therefore, the battery can connect to the DC bus smoothly without AC mains. 6. Input Protection A frequently happen field problem of power system is that (refer to the figure below) the power cable is too long that the inductance is not negligible, when the load change abruptly (switch on/off of adjacent load) the energy stored in the cable (1/2xIxIxL) can not be released, will induced a high voltage between phase and neutral (where V=Lxdi/dt), the UPS (surge absorber or inner semi-conductor) or even all the connected load will be damaged. Therefore, we put a dedicated protection device at the input to release the energy of transmission cable induced by abrupt change of load, preventing any high voltage that threat to all the connected devices. 8

7. Intelligent Charger and Battery Tester There is a big capacity, programmable (as the following LCD Menu), temperature compensated charger inside the UPS. The period and amount of the periodic boost charge is programmable, therefore the life expectancy of battery is prolonged, and can quickly charge up large battery bank. < B O O S T C H A R G E S E T T I N G > A U T O - B O O S T ( M O N T H ) = 0 4 0 8 1 2 1 6 2 0 2 4 A U T O - B O O S T ( B A T T L OW ) = 0 4 0 8 1 2 1 6 2 0 2 4 C H A R G E C U R R E N T = L O M E H I E X I T Beside, there is a safe, intelligent battery tester to periodically, safely test the battery without the risk of affecting the UPS output. Other battery bank problem, such as battery fluid leakage and battery cabinet improper grounded, can also be detected and sent warning message to user. 8. Plug & Play Modular Design The power section of our UPS are divided in several detachable heat-sink modules, (plug & play modules), so as to enable quick debug and repair, in return save cost and minimize the loss of the user. That is, if the users keep one set of the spare part, the MTTR will be shortened to 30 min. 9

9. Features of Parallel Operation a. Can parallel several units together. b. Employ most advanced technology. c. Use high-speed digital signal processors (DSP) to calculate the control signal. Some of the superior features are listed below: (1) No adjustments to be done on the site (all adjustments are done in factory), while most of the products in the market need complicated or difficult adjustments on the site. (2) The difference of power sharing between each unit is smaller than 0.5% under any kind of load. (3) Completely no circulation current between each unit. (4) No extra parallel cabinet needed. (5) Switch on/off procedures are not critical, incorrect operation has no harm to the units. (6) Can endure wide dynamic variations of the input voltage and frequency, no other products in the market can compare. (7) The safety and reliability of the power system is highly increased. 10

10. Variety of Accessories / Options a. UPSCAN TM - Remote Control Penal A hand held display module with LCD and LED can monitor 1 99 UPSs with RS-485 connected in series from distance < 1000M. Size: W*H*D=22*12.3*4.5cm, 0.45kg b. Emergency Stop Switch Be installed outside or nearby the UPS for stopping the UPS output in case of emergency. c. UPSCOM TM - PC Monitoring Software Can provide real-time three phases information of UPS connected on the line and monitor several UPSs with one PC. 11

(a) UPSCOM monitoring 1UPS. RS232 PC CNR21 in 3R PCB (b) UPSCOM monitoring multiple UPS (up to 31 units) RS485 CNR10 in 3R PCB Adapter RS485 RS232 PC RS485 CNR10 in 3R PCB RS485 CNR10 in 3R PCB 12

d. SNMP/HTTP agent Can monitor and manage the UPS through Web browser and Java applet, providing simultaneously three phases data acquisition. 13

10. Low UPS Maintenance Cost Being high reliability and support of quick maintenance, In addition to guaranty period the maintenance charge of ALP series will be assured less than 5% of the UPS sale price in the second year usage and less than 10% in the third year. 14