MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS

Similar documents
SW6000 SEISMIC VIBRATION SWITCH Installation Manual

Electronic Vibration Switch PMC/BETA 440 & 450

Vibration Switches viib

Velomitor* CT Velocity Transducer

Vibration Switches. kmo turbo GmbH Friedrichstr Friedrichshafen Germany

60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application

Level-Lance Model 5400A

Conveyor Belt Alignment Switches from IDEM

Description. Specifications and Ordering Information 9200, 74712, Seismoprobe Velocity Transducer System

Vibration Switches. For 24/7 Protection of Cooling Towers, Fin Fans, HVAC Systems, Blowers, Motors and Other Critical Machinery

Environdata FA ma Converter Guide

MODEL 8000MP LEVEL SENSOR

NETRONICS HS3500 CONTROLLER

9200, Seismoprobe

Table of Contents. Introduction... 2 Description...2 Specifications...3 Installation.. 5 Calibration.. 6 General Maintenance...7

Velomitor * Piezo-velocity Sensor

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

General-Purpose Photoelectric Sensor

Magnetic and Hydraulic-Magnetic Circuit Breaker

onlinecomponents.com

MT400 MOTION CONTROLLER

Electronic, Digital and Mechanical Vibration Switches

FLEX Ex Spring Clamp Terminal Base

Portable vibration calibrator Model 28959G

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

VMS Co., Ltd. VMS Reliability Systems - Korea

MAXIMA+ Series Rotary Level Indicator

Micro Motion. Series 3000

955 ebrik INSTALLATION MANUAL. Series ebrik ABSOLUTE PROCESS CONTROL KNOW WHERE YOU ARE... REGARDLESS LINEAR DISPLACEMENT TRANSDUCERS

SYSTEMS ELECTRONICS GROUP

GF92 Installation, Operation and Troubleshooting Guide

PERFORMANCE SPECIFICATION

Zenith DS9000 Dispensing System

5.1. Motor Protection and Monitoring. Contents. Product Overview. Monitoring Relays. D64R Series Digital Ground Fault Relays...

9200, Seismoprobe * Bently Nevada* Asset Condition Monitoring

Capacitive Proximity Sensor E2K-X

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

Installation & Operation Guide

VM2800 & VM3800 VIBRACHECK METERS Installation Manual

TPE 1464 Series Pressure Transducer

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

Page Housing Plastic Metal Mounting DIN Rail or surface mount Panel or bracket mount Wattage Range 10W to 240W 7.5W to 240W 10W to 300W

Absolute Encoders Multiturn

Screw. Nut Guide. Features

MAXIMA + Series ROTARY LEVEL CONTROL

PI-EX-ME-2NAM/COC-24VDC

EXPRESS SETUP. PanelMate 1700 Series PanelMate Power Pro. Cutler-Hammer

QSB (Q-Star) Electronics for QSE Electromagnetic Meter. Owner s Manual TABLE OF CONTENTS

VM-11 SERIES MODEL VM-11B ACCELERATION INPUT VIBRATION SIGNAL CONDITIONER INSTRUCTION MANUAL. MANUAL No E1.8. Revised in Mar.

TCNM-ACBB1 Installation Manual

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

9200, Seismoprobe* Velocity Transducers

Metrix Probe Mounting System PM Oil-tight, with Insulating Connection Head and Gap Adjustment

PI-EX-ME-2NAM/COC-120VAC

Expansion Unit Catalog Nos , - 152, - 153, - 154, - 156, -E157

Installing Sentor. Hardware Installation

Models 120LS, 200LS, 300LS, 400LS, 560LS Installation Instructions

Table of Contents 1. Overview Installation...6

Autoranging True RMS Multimeter User Manual

Allen-Bradley PLCs. 100 Programmable Controller Processor Unit -Catalog Nos LPI01, -LP102, -LP103, -LP104 SLC TM. The Unit

Installation Instructions

VibraLINK switchable junction boxes Installation and operating guide VLL series

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

S Reclosers Kyle Type VXE Electronic Control SCADA Input/Output Board Installation and Operation Instructions

Your Global Flow Control Partner. Series 50 Valve Status Monitor Operation and Maintenance Manual

24 Input/8 Output AC Block I/O Module

991 Thrust Transmitter Bently Nevada* Asset Condition Monitoring

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

DM200 Dual-Channel A/V/D Vibration Monitor

DTM Distributed Transmitter Monitor

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter

Magnetically Actuated Safety Interlock Switches

Instruction Sheet Board Style Low Water Cutoff

Earth Continuity Monitor

DD1590 Series Proximity Driver. Connection Technology Center, Inc. Vibration Analysis Hardware. DD1590 Series. Proximity Probe Driver.

PHOENIX CONTACT - 12/2007

BNI EIP Z016. IP67 Modules, 8 Outputs BNI EIP Z016 BNI EIP Z016 IP67 Modules, 16 Outputs User s Guide

and High Temperature Velomitor * System

RAYMAPB. Power Supply and Terminal Box for Marathon MM/MR/FA/FR Sensors. Manual Addendum. Rev. A 06/

DS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation /

Analog Voltage Combination Module

SITRANS F Coriolis Flowmeters SITRANS FCT030 transmitter Quick Start

MAXIMA + Series ROTARY LEVEL CONTROL

Product Information SIMATIC S Digital Output Module SM 322; DO 16 UC24/48 V

SKF Machine Condition Transmitters (MCT) Series

IO-DI8-TO8 I/O Expansion Module 8 Inputs, 8 Outputs

CDD4 Duct Carbon Dioxide Transmitter

ADVANCED MICRO SYSTEMS

EXPRESS SETUP. PanelMate 1700 Series PanelMate Power Pro. Cutler-Hammer

MLS7A Series. Photoelectric Sensors. Heavy-Duty Retro-Reflective Sensors. Photoelectric MLS7A Series Heavy Duty PEPPERL+FUCHS 529

25 m 5 m 1 m. Part Number Mounting bracket. E39-LU1 Mounting bracket for E39-R1 reflector

Inductive sensor with analog output BI15-M30-LI-EXI

GF90 Installation, Operation and Troubleshooting Guide

RoHS. High shaft load capacity. Shock / vibration resistant

Capacitive Prox E2K-X

INSTALLATION INSTRUCTIONS FOR THE BV10-100/1000

Transcription:

MODEL SW6000 & SM6100 CENELEC INSTRUCTIONS Installation Manual 1180 METRIX Experience Value 8824 Fallbrook Dr. Houston, TX 77064, USA Tel: 1-281-940-1802 After Hours Technical Assistance: 1-713-702-8805 Fax: 1-713-559-9421 E-mail: info@metrixvibration.com www.metrixvibration.com M9091 REV G

SW6000 SECTION A - MECHANICAL INSTALLATION 1.0 Switch Installation The sensitive axis of the switch can be mounted on any radial axis, although the horizontal axis is preferred so the unit sees maximum vibration. The horizontal axis also reduces the temperature exposure vs a vertical axis. If a bracket is required, it should be rigidly constructed to prevent spurious mechanical resonances in the SW6000 frequency range. Stud Mount Unit: Requires a tapped hole, see Product Identification F or use a model 7084 flange mount adapter. If an NPT mounting stud is selected the stud will tighten before the switch casing touches the machine case. The SW6000 should be hand tightened and then wrench tightened to bring the conduit connections to the appropriate location. Studs with straight threads are provided with a locking nut. The optional display can be rotated in 90 degree increments to bring it to a readable position. Refer to Section B 1.0 for further information. MOUNTING LOCATIONS Figure 1 HOUSING Figure 2 WIRING DIAGRAM Figure 3 NOTE: 1) Diagrams show all available options, see Product Identification to verify options on your particular unit. 2) On Single Limit Models, use Load Limit Two (2). M9091 REV G Page 2

SECTION B - WIRING NOTE: On CENELEC approved units, a locking set screw must be loosened prior to lid removal. 1.0 Terminal Wiring If you have selected the optional display, the display circuit board must be removed (two screws) to expose the terminal strips. The display board cable should not be disconnected. Simply place the display board out of the way to allow wiring to the terminal strips. The display may be reinstalled in any of the four possible orientations. Connection to the unit is through one or two conduit entries (See Sheet 3 of drawing 9030). The cable gland or conduit entries shall be in accordance with 13.1 of EN60079-1 and IEC 60079-1. The user must provide appropriate seal and sealing materials for the rates installation. Unused conduit entries must be plugged with a plug that conforms to Clause 13.2 of EN60079-1 and IEC 60079-1. The internal ground connector allows for the connection of a 14 AWG wire. This has a cross section of 2 mm 2. The external ground terminal can accommodate a 10 AWG wire that has an area of 5 mm 2. It is comprised of an M5 bolt with two flat washers and one lock washer. Refer to figure 3 for wiring information. For incoming power and switch output(s) use approved wire of 14 AWG (1.5 sq. mm) or smaller. NOTE: On CENELEC installations, a means for disconnecting power to the switch must be provided. Also, the symbol signifies a protective earth terminal. For reset and startup delay functions, use a twisted pair to reduce electrical noise pickup. For the current and dynamic signal outputs a shielded, twisted pair is recommended. By convention, the shield should be tied to common only at the receiver end. A cable consisting of separate shielded twisted pairs can also be used. For the dynamic signal output the capacitance of the cable run must not exceed.03 uf (typically 1000 feet). CAUTION: Conduit seals are highly recommended to prevent the entry of moisture into the switch. Moisture will damage the switch and void the warranty. Internal and external protective earth connections must be connected to the installation protective earth circuits. 1.1 Power Wiring It is highly recommended that all power and triac/fet wiring be routed separately from the dynamic signal and 4-20mA wiring in order to reduce a.c./transient noise pickup. The power required is indicated on the nameplate. The voltage supply must be within the following limits: 24 VDC: 20 to 28 VDC 115 VAC: 95 to 125 VAC, 50/60 Hz 230VAC: 190 to 250 VAC, 50/60 Hz Polarity does not need to be observed when wiring for DC power. The preferred method of operation is to continuously apply power to the SW6000. If power is to be applied as a part of the machine startup sequence it is advisable to apply power to the SW6000 30 seconds prior to starting the machine in order to allow the electronics circuits to stabilize. This is particularly important if the adjustable startup delay option is utilized and the delay is set to less than 20 seconds. 1.2 Alarm Limit Triac Output Wiring The triac output(s) are electro-optically isolated from each other, power, and the internal circuit. These are medium power devices with high immunity to electrical transients. If desired, each triac can be supplied from an AC voltage source different from the main supply. The triacs can be connected in series with the triacs of other units. See Fig. 4. Parallel connection of two switches doubles the triac holding (minimum load) current requirements. The maximum triac supply voltage is 250 VAC. The worst case triac leakage (off) current is 2 ma. The maximum triac holding current is 35 ma at 25 C (60mA at -40 C) which requires that the relay pull-in current have a greater value. Do not use a DC supply. The triacs can be set for NC or NO operation by positioning the Limit 1/Limit 2 switches accordingly. TYPICAL CONTROL CIRCUITS SW6000 w/ac Power Wired to Interrupt Motor Starter (series connection) a. Set each SW6000 for N.C. (normally closed) operation. (See Figure 3) b. M2, M3 and remote reset contacts must each be isolated. FIGURE 4 M9091 REV G Page 3

SECTION B - WIRING (con t) 1.3 Alarm Limit FET Output Wiring (optional) The optional FET limit output(s) provide a low leakage switch for DC inputs to PLC s or other devices. Do not use on an AC supply. Observe proper polarity when wiring the FET(s) (See figure 3). Damage to the FET(s) will result from improper wiring. As with the triacs, the FET(s) can be set for N.C. or N.O. operation by positioning the Limit 1/Limit 2 switches accordingly. 1.4 Limit Trip Delay The base unit has an adjustable (1-15 sec.) limit trip delay. The vibration level must be continuously above the limit setting for the duration of the time delay before the output devices switch. The 4-20 ma output is not affected by this time delay. To reset the limit output devices, the internal reset push-button or the optional external reset push-button must be pressed. Remote reset by a N.O. push-button or momentary contacts may be made by wiring to the remote reset terminals. Note that the vibration level must be below the trip level for the reset to function. 1.5 Startup Trip Delay Some machines generate vibration levels during startup which are higher than normal running levels. These high vibration levels can exceed the Alarm Trip Limits which are set above the normal running vibration level. The standard SW6000 has a fixed time delay which inhibits alarm trips for 30 seconds from the closing of the startup contacts. An optional adjustable startup trip delay (1-30 sec.) permits the Alarm Trip Limits to become operative in less than 30 seconds. Protection of machines with short startup times can be improved by utilizing the adjustable Startup Trip delay. The Startup Trip Delay is triggered by closing a set of contacts (momentary or continuous) connected to the startup terminals. The contacts must be opened before the internal startup delay timer can be initiated again. Connecting these terminals to a set of isolated auxiliary N.O. contacts in a motor starter is a method commonly used to initiate the startup trip delay. The 4-20 ma current output is inhibited (set to 4.0 ma) during the startup trip delay. 1.6 Remote Reset Wiring (optional) If remote reset capability is desired, connect Reset terminals (see Figure 3) to a remotely located, momentary N.O. pushbutton switch. Observe hazardous area requirements if applicable. 1.7 4-20 ma Current Source Output (optional) If the optional 4-20 ma output is installed it may be connected to a remote receiver, as shown on the wiring diagram (see Figure 3). This output is a current source (at 15VDC) and requires no external loop power supply. Full scale current (20 ma) corresponds to the full scale vibration response marked on the face plate. A current of 4.0 ma represents a zero vibration condition. The maximum load resistance is 600 ohms. In high electrical noise locations a shielded, twisted pair cable is recommended. FORMULA: Measured ma - 4mA 20mA - 4mA X Full scale vibration = Actual vibration EXAMPLE: Measured ma Full Scale Vibration Actual Vibration 4.0 1.0 ips, peak 0.0 ips, peak 12.0 1.0 ips, peak 0.5 ips, peak 20.0 1.0 ips, peak 1.0 ips, peak 1.8 Dynamic Outputs The sensor (acceleration) signal is available at the terminal block and is capable of driving a cable with a capacitance of up to.03 uf (typically 300m/1000 feet). Longer runs with greater than.03 uf of capacitance can be used without the buffer becoming unstable. However, the frequency response will be reduced due to the increased capacitance. M9091 REV G Page 4

IDENTIFICATION A B C D E F SW6000-r-rr-r-r-r-r Example Part Number: SW6000-1-01-1-2-0-0 *NOTE: add 30 to part no. for RMS calibration EX: SW6000-1-31-1-2-0-0, similar to example, now with RMS calibration. A r Limits and Delay 1 = one limit, triac 2 = two limits, triacs 3 = one limit, FET 4 = two limits, FETs 5 = one limit, triac, with display 6 = two limits, triacs, with display 7 = one limit, FET, with display 8 = two limits, FETs, with display B rr Full Scale Range Velocity Response 0 1 = 1 ips, pk* 3 1 = 1 ips, RMS 0 2 = 2 ips, pk* 3 2 = 2 ips, RMS 0 3 = 20 mm/sec, pk* 3 3 = 20 mm/sec, RMS 0 4 = 50 mm/sec, pk* 3 4 = 50 mm/sec, RMS Displacement Response 5 1 = 20 mils, pk-pk 5 2 = 50 mils, pk-pk 5 3 = 200 microns, pk 5 4 = 500 microns, pk C r Input Power 1 = 115 VAC, 50/60 Hz, 5 watts, max. 2 = 230 VAC, 50/60 Hz, 5 watts, max. 3 = 24 VDC, 7 watts, max. D r Hazard Area Rating/External Reset Options 2 = Class I (B, C & D), Div 1 3 = Class I (B, C & D), Div 1 with external reset 4 = CENELEC EEx d IIB + H2 T4 5 = CENELEC EEx d IIB + H2 T4 with external reset 8 = Non-Agency Approved Locations 9 = Non-Agency Approved Locations with external reset E r Input/Output Options 0 = Standard 1 = 4-20 ma proportional to full-scale range 2 = BNC for external access to dynamic signal 3 = Adjustable startup trip delay 4 = Options 1 & 2 5 = Options 1 & 3 6 = Options 2 & 3 7 = Options 1, 2, & 3 NOTE: Options 2, 4, 6, and 7 not available on hazardous area (D = 2, 3, 4, 5) versions F r Mounting/Conduit Entry 0 = 1/2 NPT stud mount / 3/4 NPT conduit entry (standard) 1 = M20 x 1.5 straight thread / stud mount with jam nut / M20 x 1.5 conduit entry 2 = 1/2-20 UNF straight thread stud mount with jam nut / 3/4 NPT conduit entry M9091 REV G Page 5

SM6100 SECTION A - MECHANICAL INSTALLATION 1.0 Monitor Installation The Model SM6100 Monitor can be mounted in any convenient location where the display can be viewed. Unit requires a tapped hole, see Product Identification F or use a model 7084 flange mount adapter. If an NPT mounting stud is selected the stud will tighten before the switch casing touches the machine case. The SM6100 should be hand tightened and then wrench tightened to bring the conduit connections to the appropriate location. Studs with straight threads are provided with a locking nut. HOUSING Figure 5 WIRING DIAGRAM Figure 6 M9091 REV G Page 6

SECTION B - WIRING NOTE: On CENELEC approved units, a locking set screw must be loosened prior to lid removal. 1.0 Terminal Wiring If you have selected the optional display, the display circuit board must be removed (two screws) to expose the terminal strips. The display board cable should not be disconnected. Simply place the display board out of the way to allow wiring to the terminal strips. The display may be reinstalled in any of the four possible orientations. Refer to figure 3 for wiring information. For incoming power and switch output(s) use approved wire of 14 AWG (1.5 sq. mm) or smaller. NOTE: On CENELEC installations, a means for disconnecting power to the switch must be provided. Also, the symbol signifies a protective earth terminal. For reset and startup delay functions, use a twisted pair to reduce electrical noise pickup. For the current and dynamic signal outputs a shielded, twisted pair is recommended. By convention, the shield should be tied to common only at the receiver end. A cable consisting of separate shielded twisted pairs can also be used. For the dynamic signal output the capacitance of the cable run must not exceed.03 uf (typically 1000 feet). CAUTION: Conduit seals are highly recommended to prevent the entry of moisture into the switch. Moisture will damage the switch and void the warranty. 1.1 Power Wiring It is highly recommended that all power and triac/fet wiring be routed separately from the dynamic signal and 4-20mA wiring in order to reduce AC/transient noise pickup. The power required is indicated on the nameplate. The voltage supply must be within the following limits: 24 VDC: 20 to 28 VDC 115 VAC: 95 to 125 VAC, 50/60 Hz 230VAC: 190 to 250 VAC, 50/60 Hz Polarity does not need to be observed when wiring for DC power. The preferred method of operation is to continuously apply power to the SW6000. If power is to be applied as a part of the machine startup sequence it is advisable to apply power to the SW6000 30 seconds prior to starting the machine in order to allow the electronics circuits to stabilize. This is particularly important if the adjustable startup delay option is utilized and the delay is set to less than 20 seconds. 1.2 Alarm Limit Triac Output Wiring The triac output(s) are electro-optically isolated from each other, power, and the internal circuit. These are medium power devices with high immunity to electrical transients. If desired, each triac can be supplied from an AC voltage source different from the main supply. The triacs can be connected in series with the triacs of other units. See Fig. 6. Parallel connection of two switches doubles the triac holding (minimum load) current requirements. The maximum triac supply voltage is 250 VAC. The worst case triac leakage (off) current is 2mA. The maximum triac holding current is 35mA at 25 C (60mA at -40 C) which requires that the relay pull-in current have a greater value. Do not use a DC supply. The triacs can be set for NC or NO operation by positioning the Limit 1/Limit 2 switches accordingly. TYPICAL CONTROL CIRCUITS SW6000 w/ac Power Wired to Interrupt Motor Starter (series connection) a. Set each SW6000 for N.C. (normally closed) operation. (See Figure 3) b. M2, M3 and remote reset contacts must each be isolated. Figure 6 M9091 REV G Page 7

1.3 Alarm Limit FET Output Wiring (optional) The optional FET limit output(s) provide a low leakage switch for DC inputs to PLC s or other devices. Do not use on an AC supply. Observe proper polarity when wiring the FET(s) (See figure 3). Damage to the FET(s) will result from improper wiring. As with the triacs, the FET(s) can be set for N.C. or N.O. operation by positioning the Limit 1/Limit 2 switches accordingly. 1.4 Limit Trip Delay The base unit has an adjustable (1-15 sec.) limit trip delay. The vibration level must be continuously above the limit setting for the duration of the time delay before the output devices switch. The 4-20 ma output is not affected by this time delay. To reset the limit output devices, the internal reset push-button or the optional external reset push-button must be pressed. Remote reset by a N.O. push-button or momentary contacts may be made by wiring to the remote reset terminals. Note that the vibration level must be below the trip level for the reset to function. 1.5 Startup Trip Delay Some machines generate vibration levels during startup which are higher than normal running levels. These high vibration levels can exceed the Alarm Trip Limits which are set above the normal running vibration level. The standard SM6100 has a fixed time delay which inhibits alarm trips for 30 seconds from the closing of the startup contacts. An optional adjustable startup trip delay (1-30 sec.) permits the Alarm Trip Limits to become operative in less than 30 seconds. Protection of machines with short startup times can be improved by utilizing the adjustable Startup Trip delay. The Startup Trip Delay is triggered by closing a set of contacts (momentary or continuous) connected to the startup terminals. The contacts must be opened before the internal startup delay timer can be initiated again. Connecting these terminals to a set of isolated auxiliary N.O. contacts in a motor starter is a method commonly used to initiate the startup trip delay. The 4-20 ma current output is inhibited (set to 4.0 ma) during the startup trip delay. 1.6 Remote Reset Wiring (optional) If remote reset capability is desired, connect Reset terminals (see Figure 3) to a remotely located, momentary N.O. pushbutton switch. Observe hazardous area requirements if applicable. 1.7 External Sensor The Model SM6100 requires the use of an external sensor. Refer to Product Identification, option G to determine the type of sensor required. Mount and connect the sensor per the manufacturer s instructions and Figure 2. 1.8 4-20 ma Current Source Output (optional) If the optional 4-20 ma output is installed it may be connected to a remote receiver, as shown on the wiring diagram (see Figure 3). This output is a current source (at 15VDC) and requires no external loop power supply. Full scale current (20 ma) corresponds to the full scale vibration response marked on the face plate. A current of 4.0 ma represents a zero vibration condition. The maximum load resistance is 600 ohms. In high electrical noise locations a shielded, twisted pair cable is recommended. Measured ma - 4mA FORMULA: X Full scale vibration = Actual vibration 20mA - 4mA EXAMPLE: Measured ma Full Scale Vibration Actual Vibration 4.0 1.0 ips, peak 0.0 ips, peak 12.0 1.0 ips, peak 0.5 ips, peak 20.0 1.0 ips, peak 1.0 ips, peak 1.9 Dynamic Outputs The sensor (transducer) signal is available at the terminal block and is capable of driving a cable with a capacitance of up to.03 uf (typically 300m/1000 feet). Longer runs with greater than.03 uf of capacitance can be used without the buffer becoming unstable. However, the frequency response will be reduced due to the increased capacitance. M9091 REV G Page 8

IDENTIFICATION A B C D E F G H SM6100-r-rr-r-r-r-r-r-rrr Example Part Number: SM6100-1-01-1-2-0-0-1-100 *NOTE: add 30 to part no. for RMS calibration EX: SM6100-1-31-1-2-0-0-1-100, similar to example, now with RMS calibration. A r Limits and Delay 1 = one limit, triac 2 = two limits, triacs 3 = one limit, FET 4 = two limits, FETs 5 = one limit, triac, with display 6 = two limits, triacs, with display 7 = one limit, FET, with display 8 = two limits, FETs, with display B rr Full Scale Range Velocity Response 0 1 = 1 ips, pk* 0 2 = 2 ips, pk* 0 3 = 20 mm/sec, pk* 0 4 = 50 mm/sec, pk* 0 5 = 5 ips, pk* 0 6 = 100 mm/sec, pk* Displacement Response 5 1 = 20 mils, pk-pk 5 2 = 50 mils, pk-pk 5 3 = 100 mils, pk 6 1 = 200 microns, pk 6 2 = 500 microns, pk 6 3 = 1.00 mm, pk C r Input Power 1 = 115 VAC, 50/60 Hz, 5 watts, max. 2 = 230 VAC, 50/60 Hz, 5 watts, max. 3 = 20-28 VDC D r Hazard Area Rating/External Reset Options 2 = Class I (B, C & D), Div 1 3 = Class I (B, C & D), Div 1 with external reset 4 = CENELEC EEx d IIB + H2 T4 5 = CENELEC EEx d IIB + H2 T4 with external reset 8 = Non-Agency Approved Locations 9 = Non-Agency Approved Locations with external reset E r Input/Output Options 0 = Standard 1 = 4-20 ma proportional to full-scale range 2 = BNC for external access to dynamic signal 3 = Adjustable startup trip delay 4 = Options 1 & 2 5 = Options 1 & 3 6 = Options 2 & 3 7 = Options 1, 2, & 3 NOTE: Options 2, 4, 6, and 7 not available on hazardous area (D = 2, 3, 4, 5) versions F r Mounting/Conduit Entry 0 = 1/2 NPT stud mount / 3/4 NPT conduit entry (standard) 1 = M20 x 1.5 straight thread / stud mount with jam nut / M20 x 1.5 conduit entry 2 = 1/2-20 UNF straight thread stud mount with jam nut / 3/4 NPT conduit entry G r Remote Sensor Type 1 = Remote accelerometer constant current drive, 10-100 mv/g 2 = Remote velocity transducer 100-500 mv/ips 3 = Remote piezo-velocity transducer constant current drive, 100-500 mv/ips H r rr Input Sensitivity Specify input sensitivity with 3 digit number M9091 REV G Page 9