Table of contents. Use of the application program. GAMMA instabus Application program description. July B CO IP Gateway KNX-BACnet

Size: px
Start display at page:

Download "Table of contents. Use of the application program. GAMMA instabus Application program description. July B CO IP Gateway KNX-BACnet"

Transcription

1 Table of contents Use of the application program Functional description... 2 Behavior at bus voltage failure / recovery... 4 Factory default state... 4 Behavior on unloading the application program... 4 Resetting the device to factory default settings Communication objects Functions (Objects, s)... 6 General settings... 6 for the Objects Switching / Status On/Off (1 bit) bit Value (Percent value) bit Value (Unsigned integer) bit Value (Signed integer) bit value (Unsigned integer) bit Value (Signed integer) bit Value (Float) bit Value (Unsigned integer) bit Value (Signed integer) bit Value (Float) Device status BACnet Product Description Protocol Implementation Conformance Statement (PICS) BACnet Stack BACnet Objects Use of the application program Product family: Product type: Manufacturer: Name: Order no.: Communication Interfaces Siemens IP Gateway KNX-BACnet N 143 5WG AB01 P. O. Box , D Regensburg Subject to change without further notice 1/39

2 1. Functional description The application program 07 B0 CO IP Gateway KNX-BACnet can be used for the KNX device listed above. This device is briefly described in the next section. The IP Gateway KNX/BACnet N 143 is a DIN rail mounted device connecting a KNX installation with a system using BACnet communication. The Gateway provides up to 250 communication objects. Via these objects KNX functions (group addresses) are transposed to BACnet objects. The communication objects can be configured optionally as: switching/status on/off (1 bit) 8-bit value (percent value) 8-bit value (unsigned integer) 8-bit value (signed integer) 16-bit value (unsigned integer) 16-bit value (signed integer) 16-bit value (float) 32-bit value (unsigned integer) 32-bit value (signed integer) 32-bit value (float) The device is configured entirely with ETS. The configuration of the KNX communication objects automatically generates the corresponding BACnet objects. The following BACnet objects are being used: Binary Input Binary Output Binary Value Analog Input Analog Output Analog Value No special knowledge about BACnet is required for the commissioning. The KNX objects configured with ETS are automatically translated by the device into BACnet objects according to the following process: The BACnet object instance number is identical to the object number of the ETS. Objects with a 1 bit data type are translated into binary objects. All others become analog objects. The parameter Object Mode (INPUT, OUTPUT, VALUE) completes the transformation to a BACnet object. On BACnet the IP Gateway KNX/BACnet N 143 appears as an Application Specific Controller (B-ASC) with up to 250 BACnet objects. BACnet clients may set up to 455 BACnet change-of-value (COV) subscriptions for these 250 BACnet objects. A common memory space is available for the administration of the COV subscriptions and priority arrays. This resource optimization is based on the fact that subscriptions are required for objects which send from KNX to BACnet whilst priority arrays are for objects sending from BACnet to KNX. The maximum number of possible subscriptions is 455 if no priority arrays are used. As each priority array has a size of 64 Byte (16 priority levels of 4 Byte each), the number of possible subscriptions decreases accordingly. The maximum possible number of subscriptions is displayed on the device website once the configuration is complete. When a subscription is registered the BACnet object sends its current value, if a value is available for this object. The validity of a value can be verified via the status property (Failure flag). Initially, the status failure flag for the object types Binary Input, Binary Value, Analog Input and Analog Value is set to TRUE. Once a value is transmitted from the KNX bus or from BACnet (for Binary Value or Analog Value) this status flag is set to FALSE. Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 2/39 Subject to change without further notice P. O. Box , D Regensburg

3 When using a Priority Array with all Priority Array positions released then the last received KNX value is sent as relinquish default, if the value is valid. All Analog and Binary BACnet objects supported by the device support the writeable Out-Of-Service property. When this property is set to TRUE, the communication of the respective object with KNX is inhibited. Values of Input objects can then be changed from the BACnet side, which otherwise would not be possible. Value changes of objects with set Out-Of- Service property are also indicated via the object status flag Overridden. The Out-Of-Service flag handling is especially important for finding errors in complex systems. When the description of an object is requested from the BACnet side (ReadProperty Description ), the description text is automatically generated and assembled from the object name, BACnet identifier and KNX group address data separated by a colon ( : ). The device is equipped with a web server presenting the configuration and current values in an overview page. This presentation is helpful for testing purposes and for documentation of the interface between KNX and BACnet. The web page contains a header section showing general device specific information: Device name Device description Installation location Device status BACnet instance number of the device Firmware version Revision number Physical KNX address IP address Netmask Gateway address MAC address Number of configured objects Maximum number of possible COV subscriptions Current number of COV subscriptions Priority: This displays the priority array, which is used to transmit events from KNX to BACnet Number of binary input objects Number of binary output objects Number of binary value objects Number of analog input objects Number of analog output objects Number of analog value objects Beneath the header is a table listing all configured objects. The table is divided into the following columns: Object number Object name P. O. Box , D Regensburg Subject to change without further notice 3/39

4 BACnet object ID KNX group address Data type Transmission mode Reading during initialisation Unit Object value Object values are not dynamically up-dated on the website. To up-date the objects, please re-load the website. An EDE (Engineering Data Exchange) list can be exported via the button Export EDE on the right side of the web page. Note In general, the webpage is coded for the UTF-8 character set. A selection field on the web page allows switching between UTF-8 and ISO encoding. Thus the presentation can be adapted to the encoding downloaded by ETS. When ETS4 / ETS5 is used for configuration then texts (including special characters) are coded dependent on the settings in ETS4 / ETS5. The encoding is set in ETS4 / ETS5 for the project under General - Codepage. The UTF-8 character set should be selected. When ETS3 is used for configuration then special characters inserted with ETS3 are encoded with the ISO character set. Texts to be communicated via BACnet are transmitted as entered in ETS. Besides the function as IP Gateway KNX-BACnet the device also provides an IP Interface for ETS configuration of the device itself as well as other KNX devices of the attached KNX line. Behavior at bus voltage failure / recovery Failure of the auxiliary power (DC 24V) results in a functional failure of the device. A bus voltage failure results in a functional failure of the device. On bus voltage recovery the configured actions are executed and, if applicable, new status values are reported. The device sends I am onto BACnet. Factory default state In the default factory state the device has no Gateway function. The IP address is preset to Behavior on unloading the application program When the application program is unloaded with ETS the device does not function. All BACnet objects are still visible but are set to out of service. The property data base revision in the BACnet Device is incremented by one. The web server stays in operation. Resetting the device to factory default settings The device cannot be reset to the factory default settings. Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 4/39 Subject to change without further notice P. O. Box , D Regensburg

5 2. Communication objects Maximum number of group addresses: 255 Maximum number of assignments: 511 Note The number and names of communication objects visible can vary depending on the parameter settings. The application program already has been loaded in the factory. The device is configured and commissioned with the ETS (Engineering Tool Software) version ETS5 v5.5.2 or later. With the ETS (Engineering Tool Software) the specific parameters and addresses are assigned appropriately, and downloaded into the device. The following list shows all objects of the device. Which objects are visible and linkable to group addresses is defined via the functions assigned to the inputs. The objects and associated parameter settings are described with the functions. No. Object name Function Number of Flags bits 1 Object Object name, Switching On / Off 1 Bit CWTU Object Object name, 8-bit percent value [ %] 1 Byte CWTU Object Object name, 8-bit value [ ] 1 Byte CWTU Object Object name, 8-bit value [ ] 1 Byte CWTU Object Object name, 16-bit value [ ] 2 Byte CWTU Object Object name, 16-bit value [ ] 2 Byte CWTU Object Object name, 16-bit value [16-bit float] 2 Byte CWTU Object Object name, 32-bit value [ ] 4 Byte CWTU Object Object name, 32-bit value [-2147 Mio Mio] 4 Byte CWTU Object Object name, 32-bit value [32-bit float] 4 Byte CWTU Object Object name, Switching On / Off 1 Bit CWTU Object Object name, 8-bit percent value [ %] 1 Byte CWTU Object Object name, 8-bit value [ ] 1 Byte CWTU Object Object name, 8-bit value [ ] 1 Byte CWTU Object Object name, 16-bit value [ ] 2 Byte CWTU Object Object name, 16-bit value [ ] 2 Byte CWTU Object Object name, 16-bit value [16-bit float] 2 Byte CWTU Object Object name, 32-bit value [ ] 4 Byte CWTU Object Object name, 32-bit value [-2147 Mio Mio] 4 Byte CWTU Object Object name, 32-bit value [32-bit float] 4 Byte CWTU 251 Device Status Status 1 Bit CRT P. O. Box , D Regensburg Subject to change without further notice 5/39

6 3. Functions (Objects, s) For the functions of the IP Gateway KNX/BACnet first general configuration settings and then the configuration of the 250 Objects have to be done. Note The number and names of the parameter windows in the ETS menus may vary as they are controlled via parameter settings. Another parameter window may appear if due to dynamically added parameters the space in the first parameter window is exhausted. General settings General settings This parameter window is used to set - a device name for identification of the device via KNXnet/IP, - the type of IP address assignment, - the start and cycle time for Read Requests from status objects, and - the base parameters for communication via BAcnet. Device name N143_IP_Gateway_BACnet_KNX (max. 30 char) This parameter assigns a name with up to 30 characters to the IP Gateway KNX/BACnet N 143. This name is used for easy recognition of the device when searched by a KNXnet/IP visualization or the ETS. IP address assignment manual input by DHCP Server This parameter determines the type of IP address assignment. By default DHCP is preset for automatic address assignment by a DHCP server. When manual input is selected, an additional tab for manual input of IP address, subnet mask and the default gateway appears. Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 6/39 Subject to change without further notice P. O. Box , D Regensburg

7 Start delay for ReadOnInit 10 seconds 20 seconds 30 seconds 1 minute 2 minutes 3 minutes 4 minutes 5 minutes This parameter determines the time delay after bus voltage recovery before read requests of status objects are started. Delay between ReadRequests 100 milliseconds 200 milliseconds 500 milliseconds 1 second 2 seconds This parameter determines the time delay between Read Requests of the individual status objects. Device Instance (must be unique) This parameter defines the unique device ID. The ID is an integer value. Value range ( ) BACnet communication port Use this parameter to change the port number of the BACnet server. The pre-set port is DCC Password This parameter defines the password to control the device on the BACnet side (up to 8 characters). By using the BACnet Service DeviceCommunicationControl the device can be temporarily muted for diagnostic purposes. This means all BACnet services apart from DCC are de-activated in order to re-set the device to its normal status. BACnet communication timeout 100 ms 200 ms ms 1 s This parameter determines the time to wait for the BACnet acknowledgement. BACnet communication retries 1 retry 2 retries 3 retries Use this parameter to determine how many times you would like to repeat a request in case of wrong acknowledgement. P. O. Box , D Regensburg Subject to change without further notice 7/39

8 Optional settings This parameter window is used - to store the installation location as information in the device, - to store a brief description of the device as information in the device itself, - to determine the use of priority arrays, and - to register as foreign device at BBMD. Device Location This parameter can be used to enter an installation location of the device for easier localization in the building. Up to 30 characters can be used. Device Description This parameter can be used to enter a brief device description for the device. Up to 30 characters can be used. Usage of priority arrays This parameter generally determines if priority arrays are available for use. The BACnet standard assumes the usage of priority arrays for the BACnet object types Binary Output, Binary Value, Analog Output and Analog Value supported by the device. According to the standard the device supports 16 priority levels for each priority supporting BACnet object. The output value of the highest priority (this is the lowest priority number) is active. All other values with lower priority are stored (one value per priority level and object). In most cases this functionality is not required. By default priority arrays are disabled to have the highest possible memory space for COV subscriptions no yes Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 8/39 Subject to change without further notice P. O. Box , D Regensburg

9 Internet GAMMA instabus Registration as foreign device at BBMD (valid from firmware V1.2 upwards) no yes From firmware V1.2 upwards: Firmware update see column SW If this parameter is set to Yes then the gateway can register as a 3 rd party device with a BBMD (BACnet Broadcast Management Device). In this case all telegrams are sent to the BBMD. IP Subnet 1 IP Subnet 2 IP Subnet 3 LAN Segment BACnet Device Internet Router BBMD Foreign BACnet Device See: BBMD IP address (byte 1) 0 BBMD IP address (byte 2) 0 BBMD IP address (byte 3) 0 BBMD IP address (byte 4) 0 This parameter determines the BBMD IP address. The four bytes of the BBMD IP address must be entered individually. The value range for each byte is BBMD Port Number Use this parameter to change the port number of the BBMD server. The pre-set port is Re-registration time (Time to live) 60 [min] The BBMD registration has to be regularly updated. The update period can be set with this parameter. Note: If the first registration is not successful, then the registration is repeated every 30 seconds. After a successful registration the update period set by this parameter is applied. P. O. Box , D Regensburg Subject to change without further notice 9/39

10 IP This parameter window is visible when the parameter IP address assignment has been set to manual input. IP address byte 1, byte 2, byte 3, byte 4 This parameter determines the IP address if the IP settings are manually assigned. The factory default value for the IP address is This preset value must be replaced with a valid IP address for the target network. The four bytes of the IP address must be entered individually. The value range for each byte is Subnet mask byte 1, byte 2, byte 3, byte 4 This parameter determines the IP subnet mask if the IP settings are manually assigned. The factory default value for the IP subnet mask is This preset value must be replaced with a valid IP subnet mask for the target network. Valid subnet mask may be e.g or The four bytes of the IP subnet mask must be entered individually. The value range for each byte is Gateway address byte 1, byte 2, byte 3, byte 4 This parameter determines the standard gateway address if the IP settings are manually assigned. The factory default value for the standard gateway address is This preset value must be replaced with a valid standard gateway address for the target network. The four bytes of the IP subnet mask must be entered individually. The value range for each byte is The standard gateway forwards IP datagrams to e.g. a computer with an address outside of the local network. If the device shall be configured without a standard gateway then the address shall be used. Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 10/39 Subject to change without further notice P. O. Box , D Regensburg

11 for the Objects Up to 250 objects can be individually configured for transposition of information from KNX to BACnet and vice versa. The communication objects can be configured as either: switching/status on/off (1 bit) 8-bit value (percent value) 8-bit value (unsigned integer) 8-bit value (signed integer) 16-bit value (unsigned integer) 16-bit value (signed integer) 16-bit value (float) 32-bit value (unsigned integer) 32-bit value (signed integer) 32-bit value (float) There is a parameter window for each communication object. The configuration includes - a short description of the object with up to 18 characters, - setting the data type from this list: no object 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float - additional settings dependent on the selected data type, - the type of BACnet object (Input, Output, Value), - selection of the transmission to BACnet (always, on change of value), - whether the status of the object shall be interrogated when the device starts up. Note Representative for all 250 objects only the configuration options for object 1 are described. P. O. Box , D Regensburg Subject to change without further notice 11/39

12 Switching / Status On/Off (1 bit) Objects Obj Object name Function Type Flags 1 Object Object name, Switching On / Off 1 Bit CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 12/39 Subject to change without further notice P. O. Box , D Regensburg

13 Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 13/39

14 8-bit Value (Percent value) Objects Obj Object name Function Type Flags 1 Object Object name, 8-bit percent value [ %] 1 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 14/39 Subject to change without further notice P. O. Box , D Regensburg

15 Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 15/39

16 8-bit Value (Unsigned integer) Objects Obj Object name Function Type Flags 1 Object Object name, 8-bit value [ ] 1 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 16/39 Subject to change without further notice P. O. Box , D Regensburg

17 Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 17/39

18 8-bit Value (Signed integer) Objects Obj Object name Function Type Flags 1 Object Object name, 8-bit value [ ] 1 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 18/39 Subject to change without further notice P. O. Box , D Regensburg

19 Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 19/39

20 16-bit value (Unsigned integer) Objects Obj Object name Function Type Flags 1 Object Object name, 16-bit value [ ] 2 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 20/39 Subject to change without further notice P. O. Box , D Regensburg

21 Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 21/39

22 16-bit Value (Signed integer) Objects Obj Object name Function Type Flags 1 Object Object name, 16-bit value [ ] 2 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Datentyp 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 22/39 Subject to change without further notice P. O. Box , D Regensburg

23 Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 23/39

24 16-bit Value (Float) Objects Obj Object name Function Type Flags 1 Object Object name, 16-bit value [16-bit float] 2 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 24/39 Subject to change without further notice P. O. Box , D Regensburg

25 Unit type no unit (float value) C (DPT9.001) F (Input value by C - DPT9.001) hpa (Input value by Pa - DPT9.006) Pa (DPT9.006) kw (Input value by W - DPT9.024) W (DPT9.024) kw (DPT9.024) W/m2 (DPT9.022) m/s (DPT9.005) km/h (Input value by m/s - DPT9.005) lx (DPT9.004) % Humidity (DPT9.007) s (DPT9.010) A (Input value by ma - DPT9.021) ma (DPT9.021) V (Input value by mv - DPT9.020) mv (DPT9.020) Use this parameter to select the unit for a 2 Byte float data type. Implicit conversions are also possible. The entry for the KNX data input type is important. It means that, for example, the data type (KNX unit m/s) can be converted into km/h and transmitted to BACnet. Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 25/39

26 32-bit Value (Unsigned integer) Objects Obj Object name Function Type Flags 1 Object Object name, 32-bit value [ ] 4 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. The inserted text is concatenated to the object description Object In default setting the object dscription is Object Object name. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Note: KNX 32-bit integer values are transposed on BACnet to analog values, i.e. they are transmitted on BACnet as floating point values. Hence, integer values larger than are transposed with a rounding error into a BACnet analog value. A rounding error also occurs in the opposite transmission direction from BACNet to KNX values larger than Unit type No unit (counter value) Wh (DPT13.010) kwh (DPT13.013) This parameter determines the unit of an unsigned 4 byte data type. Selection of implicit calculations is possible. Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 26/39 Subject to change without further notice P. O. Box , D Regensburg

27 Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 27/39

28 32-bit Value (Signed integer) Objects Obj Object name Function Type Flags 1 Object Object name, 32-bit value [-2147 Mio Mio] 4 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Note: KNX 32-bit integer values are transposed on BACnet to analog values, i.e. they are transmitted on BACnet as floating point values. Hence, integer values larger than are transposed with a rounding error into a BACnet analog value. A rounding error also occurs in the opposite transmission direction from BACNet to KNX values larger than Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 28/39 Subject to change without further notice P. O. Box , D Regensburg

29 Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 29/39

30 32-bit Value (Float) Objects Obj Object name Function Type Flags 1 Object Object name, 32-bit float [32-bit float] 4 Byte CWTU Via this object, dependent on the configuration, the bus telegrams are received from KNX and then sent onto BACnet or data is received from BACnet and then sent to KNX. Object 1 Object description Object name This parameter is used to enter a text, which is displayed in the web server as name of the object. The length of the text is limited to 18 characters. Data type 1 bit 1 Byte ( %) 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte float no object This parameter determines the data type of the communication object and at the same time the data type of the corresponding BACnet object. Additionally, the data transposition from KNX to BACnet and vice versa is determined by this parameter. Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 30/39 Subject to change without further notice P. O. Box , D Regensburg

31 Unit type No unit (float value) C (DPT14.068) F (Input value by C - DPT14.068) hpa (Input value by Pa - DPT14.058) Pa (DPT14.058) kw (Input value by W - DPT14.056) W (DPT14.056) J (DPT14.031) kwh (Input value by J - DPT14.031) Hz (DPT14.033) m3 (DPT14.010) This parameter determines the unit of a 4 byte float data type. Implicit conversions are also possible. The entry for the KNX data input type is important. It means that, for example, the data type (KNX unit W) can be converted into kw and transmitted to BACnet. Transmission direction This parameter determines the transmission direction, which corresponds with the BACnet object type (Input, Output, Value). Transmission direction corresponds with BACnet object type Input Output Value Transmission to BACnet This parameter determines when information is sent to BACnet. on change: Send on change of the object value. on change on all events on all events: Send when any value is received for the object. Enable Read on Init no yes This parameter determines if on startup of the device a Read Request for the object value is sent onto the KNX bus. P. O. Box , D Regensburg Subject to change without further notice 31/39

32 Device status Objects Obj Object name Function Type Flags 251 Device status Status 1 bit CRT Via this object the device status is transmitted. The device status indicates if the device is in a not active BACnet communication status (DCC Disabled). This state can be configured via the Device Communication Control Service. The status of the communication object is also displayed by a flashing ERR LED on the device. Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 32/39 Subject to change without further notice P. O. Box , D Regensburg

33 4. BACnet Product Description B-ASC: BACnet Application Specific Controller Conformance Class: Class 3 Data Link Layer Option: BACnet IP, (Annex J) Protocol Implementation Conformance Statement (PICS) Vendor Name: Siemens Vendor Id: 7 Product Name: IP Gateway KNX-BACnet Product Model Number: 1.0 PICS Data Link Layer BACnet / IP PICS Character Sets Supported ISO PICS Special Functionality Segmented Requests Supported: Segmented Responses Supported: Routing capabilities: no no no P. O. Box , D Regensburg Subject to change without further notice 33/39

34 BACnet Stack Application Services Application Service Initiate Execute AcknowledgeAlarm ConfirmedCOVNotification X ConfirmedEventNotification GetAlarmSummary GetEnrollmentSummary Subscribe COV X UnconfirmedCOVNotification X UnconfirmedEventNotification AtomicReadFile AtomicWriteFile AddListElement RemoveListElement CreateObject DeleteObject ReadProperty X ReadPropertyConditional ReadPropertyMultiple X WriteProperty X WritePropertyMultiple DeviceCommunicationControl X ConfirmedPrivateTransfer UnconfirmedPrivateTransfer ReinitializeDevice X ConfirmedTextMessage UnconfirmedTextMessage TimeSynchronization Who-Has X I-Have X Who-Is X I-Am X VT-Open VT-Close VT-Data Authenticate Request Key Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 34/39 Subject to change without further notice P. O. Box , D Regensburg

35 BACnet Objects BACnet Device Object The obligatory BACnet device object administers central device features. Some of these can be configured via ETS whilst others are implemented statically and cannot be changed. They can only be read as information. Object-Type Properties Access Description Device object-identifier R For example: device(0) object-name R Name as configured in ETS object-type R Device system-status R always STATUS_OPERATIONAL vendor-name R Siemens vendor-identifier R 7 model-name R IP Gateway KNX-BACnet firmware-revision R 1.0 application-software-version R current version 1.0 protocol-version R Implemented BACnet Protocol version 1 protocol-revision R 10 protocol-services-supported R Services (see above) that are supported by the device protocol-object-types-supported R List of supported object types object-list R List of configured objects max-apdu-length-accepted R 1476 Byte segmentation-supported R NO_SEGMENTATION active cov-subscriptions R List of active subscirptions apdu-timeout R Configurable via ETS number-of-apdu-retries R Configurable via ETS device-address-binding R List is empty. Database-revision R 1.0 (Value is incremented with each change of configuration) location R Configurable via ETS description R Configurable via ETS Priority position W Priority Array configuration: (property ID 598): This custom property can be set via BACnet to determine, via which Priority Array Position events shall be transmitted from KNX to BACnet. P. O. Box , D Regensburg Subject to change without further notice 35/39

36 Supported Object Types Object-Type Properties Access Description Analog Input object-identifier R For example: analog input(1) object-name R Name as configured in ETS object-type R Analog input present-value R Present value status-flags R Always FALSE; in case of KNX fault, out of service is set to TRUE. event-state R Always NORMAL out-of-service RW Identical to status flag out-of-service units R According to ETS configuration description R Description text = <object-name>:<object-identifier>:<knx-groupaddress> Example: Temperatur1:analog-input(9):10/0/5 Analog Output object-identifier R For example: analog-output(2) object-name R Name as configured in ETS object-type R Analog-output present-value RW Present value status-flags R Always FALSE; in case of KNX fault out of service is set to TRUE. out-of-service RW Identical to status flag out-of-service units R According to ETS configuration priority-array RW Priority array relinquish-default R Pre-set 0 if no valid KNX value is present. description R Description text = <object-name>:<object-identifier>:<knx-groupadress> Example: Temperatur2:analog-output(2):10/0/6 Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 36/39 Subject to change without further notice P. O. Box , D Regensburg

37 Object-Type Properties Access Description Analog Value object-identifier R For example: analog-value(3) object-name R Name as configured in ETS object-type R Analog-input present-value R Present value status-flags R Always FALSE; in case of KNX fault, out of service is set to TRUE. out-of-service RW Identical to status flag out-of-service units R According to ETS configuration priority-array RW Priority array relinquish-default R Pre-set 0 if no valid KNX value is present. description R Description text= <object-name>:<object-identifier>:<knx-groupaddress> Example: Temperatur2:analog-value(3):10/0/6 Binary Input object-identifier R For example: binary-input(4) object-name R Name as configured in ETS object-type R Binary-input present-value R Present value status-flags R Always FALSE; in case of KNX fault, out of service is set to TRUE. out-of-service RW Identical to status flag out-of-service polarity R Always NORMAL description R Description text = <object-name>:<object-identifier>:<knx-groupaddress> Example: Switch1:binary-input(4):10/1/8 P. O. Box , D Regensburg Subject to change without further notice 37/39

38 Object-Type Properties Access Description Binary Output object-identifier R For example: binary-output(5) object-name R Name as configured in ETS object-type R binary-output present-value R Present value status-flags R Always FALSE; in case of KNX fault. out of service is set to TRUE. out-of-service RW Identical to status flag out-of-service polarity R Always NORMAL priority-array RW Priority array relinquish-default R Pre-set inactive if no valid KNX value is present. description R Description text= <object-name>:<object-identifier>:<knx-groupaddress> Example: Switch1:binary-output(5):10/1/9 Binary Value object-identifier R For example: binary-value(6) object-name R Name as configured in ETS object-type R binary-value present-value R Present value status-flags R Always FALSE; in case of KNX fault, out of service is set to TRUE. out-of-service RW Identical to status flag out-of-service polarity R Always NORMAL priority-array RW Priority array relinquish-default R Pre-set inactive if no valid KNX value is present. description R Description text = <object-name>:<object-identifier>:<knx-groupaddress> Example: Switch3:binary-value(6):10/1/10 Update: DS02 Siemens AG Siemens AG 2017 Control Products and Systems 38/39 Subject to change without further notice P. O. Box , D Regensburg

39 Space for notes P. O. Box , D Regensburg Subject to change without further notice 39/39

Use of the application program

Use of the application program Use of the application program Product family: Product type: Manufacturer: Name: Order no.: Table of contents Communication Interface Siemens IP Gateway KN-BACnet N 143 5WG1 143-1AB01 1. Functional description...

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Vendor Name: McQuay International Product Name: MicroTech Communications Gateway for BACnet Product Model Number: BACdrop Product Description The MicroTech

More information

WT-BAC-IP Gateway Protocol Implementation Conformance Statement

WT-BAC-IP Gateway Protocol Implementation Conformance Statement WT-BAC-IP Gateway Protocol Implementation Conformance Statement Technical Bulletin WT-BAC-IP Code No. LIT-12011936 Issued June 2017 Refer to the QuickLIT Web site for the most up-to-date version of this

More information

NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement

NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement NS Series CO 2 Network Zone Sensors Protocol Implementation Conformance Statement NS-BCN7004-0, NS-BCN7004-2 Code No. LIT-12011581 Issued November 9, 2011 Supersedes April 12, 2011 Refer to the QuickLIT

More information

DIN EN ISO : (E)

DIN EN ISO : (E) DIN EN ISO 16484-5:2014-09 (E) Building automation and control systems (BACS) - Part 5: Data communication protocol (ISO 16484-5:2014); English version EN ISO 16484-5:2014, only on CD-ROM Contents Page

More information

PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE) (This annex is part of this Standard and is required for its use.)

PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIVE) (This annex is part of this Standard and is required for its use.) PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (NORMATIE) (This annex is part of this Standard and is required for its use.) BACnet Protocol Implementation Conformance Statement Date: 2013 endor Name: Abies

More information

S4 Open: BACnet N2 Router

S4 Open: BACnet N2 Router BACnet Date: 10/21/2014 Vendor Name: The S4 Group, Inc. Product Name: S4 Open: BACnet-N2 Router Product Model Number: -16, -32, -64, -128, or -256 Application Software Version: 1.21 Firmware Revision:

More information

ETC Reference Guide BACnet PICS for P-CCS

ETC Reference Guide BACnet PICS for P-CCS BACnet PICS for P-CCS Overview This reference guide defines the BACnet (PICS) for use with ETC s Unison Paradigm Central Control Server. BACnet Vendor Name: Electronic Theatre Controls, Inc. (ETC) BACnet

More information

Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement

Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement Zoning System TEC2647Z-2 and TEC2647Z-2+PIR Zone Controllers Protocol Implementation Conformance Statement Technical Bulletin TEC2647Z-2 and TEC2647Z-2+PIR Code No. LIT-12011399 Issued March 9, 2009 Supersedes

More information

Use of the application program. 1. Functional description. instabus EIB Application Program Description. August 2016.

Use of the application program. 1. Functional description. instabus EIB Application Program Description. August 2016. IP- 001031 Table of contents Use of the application program 1 1. Functional description 1 2. Communication objects 4 3. s 4 General 4 Routing (Bus > IP) 4 Routing (IP > Bus) 5 IP 5 Setting the additional

More information

Product and Application Description

Product and Application Description Technical Product-Information Product and Application Description The IP Gateway KNX-BACnet N 143 is is a DIN rail mounted device connecting a KNX installation with a system using BACnet/IP communication.

More information

NS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement

NS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement NS Series Temperature and Humidity Network Zone and Discharge Air Sensors Protocol Implementation Conformance Statement Technical Bulletin NS-AHx7x0x-x, NS-APx7x0x-0, NS-ATx700x-x, NS-BHx7x0x-0, NS-BPx700x-0,

More information

Use of the application program

Use of the application program Table of contents Use of the application program 1 1. Functional description 1 2. Communication objects 3 3. Parameters 3 IP Settings 3 Setting the additional individual address of the IP Interface with

More information

QC BAC-BOX PIC STATEMENT

QC BAC-BOX PIC STATEMENT QC BAC-BO PIC STATEMENT BACnet Protocol Implementation (PIC) Statement QUATROSENSE ENVIRONMENTAL LTD. 5935 OTTAWA STREET, PO BO 749 (RICHMOND) OTTAWA, ONTARIO CANADA K0A 2Z0 PHONE: (613) 838-4005 FA: (613)

More information

Use of the application program. Contents overview. Gamma instabus Application program description. November 2016

Use of the application program. Contents overview. Gamma instabus Application program description. November 2016 Use of the application program Product family: Product type: Manufacturer: Application: Name: Description: Order no: Application: Name: Description: Order no: Lighting Dimmer Siemens Switch-/Dimming Actuator

More information

Test report. on the conformance of the tested functionality of BACnet implementations according to ANSI/ASHRAE No SAG.001.

Test report. on the conformance of the tested functionality of BACnet implementations according to ANSI/ASHRAE No SAG.001. Test report on the conformance of the tested functionality of BACnet implementations according to ANSI/ASHRAE 135-2001 No. 04.61.SAG.001.1 Initial test This PDF document is verbatim to the original report

More information

Product Implementation Conformance Statement bcx1-r

Product Implementation Conformance Statement bcx1-r PICS bc1-r Product Implementation Conformance Statement bc1-r Date: October 4, 2005 Vendor Name: TAC Product Name: bc1 Product Model Number: bc1-r Applications Software Version: 4.4 Firmware Revision:

More information

Application program usage. Functional description. instabus EIB Application Program Description. December IP-Router

Application program usage. Functional description. instabus EIB Application Program Description. December IP-Router Application program usage Product family: Product type: Manufacturer: Name: Order-No.: System devices IP- Siemens Functional description IP N146 5WG1 146-1AB01 The IP N146 is a DIN rail mounted device.

More information

Delta Control Unit (DCU) 3.30 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

Delta Control Unit (DCU) 3.30 BACNET PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT Date: August 14, 2003 Vendor Name: Delta Controls Inc. Product Name: Delta Control Unit Product Model Number: DSC-1616EX, DCU-050, DSM-050 Product Version: 3.30 BACnet Protocol Revision: 3 Product Description:

More information

entelibus CPU Engine (eb-eng) Firmware

entelibus CPU Engine (eb-eng) Firmware Date: March 27 th, 2017 Vendor Name: Delta Controls Inc. Product Name: entelibus CPU Engine Product Model Number: eb-eng Product Version: 3.40 Firmware BACnet Protocol Revision: 6 Product Description The

More information

Procon BAC-A/50. Installation Instructions MITSUBISHI ELECTRIC

Procon BAC-A/50. Installation Instructions MITSUBISHI ELECTRIC Installation Instructions Procon BAC-A/50 MITSUBISHI ELECTRIC BACnet TM is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc.) 1. Product

More information

Delta Controller Engine (DCE) Firmware

Delta Controller Engine (DCE) Firmware Date: August 22, 2011 Vendor Name: Delta Controls Inc. Product Name: Delta Controller Engine Product Model Number: DCE Product Version: 3.40 Firmware BACnet Protocol Revision: 6 Product Description The

More information

MULTICAL 403 MULTICAL 603

MULTICAL 403 MULTICAL 603 Protocol Implementation Conformance Statement (PICS) MULTICAL 403 MULTICAL 603 Kamstrup A/S Industrivej 28, Stilling DK-8660 Skanderborg T: +45 89 93 10 00 info@kamstrup.com kamstrup.com Contents BACnet

More information

Application program usage. Functional description. instabus EIB Application Program Description. March IP-Router

Application program usage. Functional description. instabus EIB Application Program Description. March IP-Router IP- 001002 Application program usage Product family: Product type: Manufacturer: Name: Order-No.: System devices IP- Siemens Functional description IP N146 5WG1 146-1AB01 The IP N146 is a DIN rail mounted

More information

Application description for the KNXnet/IP Interface Web

Application description for the KNXnet/IP Interface Web Contents 1. General 1. General... 1 1.1 Basic information about the KNX/EIB BUS... 1 1.2 Application versions......1 1.3 Symbols...1 1.4 Function description... 2 1.5 Short description of the function

More information

Delta ORCAview Date: August 5, 2009 Vendor Name: Delta Controls Inc. Product Name:

Delta ORCAview Date: August 5, 2009 Vendor Name: Delta Controls Inc. Product Name: Date: August 5, 2009 Vendor Name: Delta Controls Inc. Product Name: ORCAview Product Model Number: DOW-340 Product Version: 3.40 BACnet Protocol Revision: 6 Product Description: ORCAview is an industry

More information

Functional Specifications Gateway

Functional Specifications Gateway Functional Specifications Gateway IntesisBox-BACnet-ModBusRTU V4 1. BACnet Protocol Implementation Conformance Statement (PICS)... 2 1.1 BACnet Standardized Device Profile (Annex L):... 2 1.2 Segmentation

More information

MXB-50 BACnet Interface for Mitsubishi Air-Conditioning

MXB-50 BACnet Interface for Mitsubishi Air-Conditioning MXB-50 BACnet Interface for Mitsubishi Air-Conditioning Installation and User Guide www.microtrol.co.uk BACnet TM is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air-

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Date: December 1 st, 2015 Vendor Name: Danfoss A/S Product Name: VLT HVAC Drive FC-102 Product Model Number: FC-102 Applications Software Version: 1.6

More information

BACnet Protocol Implementation Conformance Statement (PICS) MULTICAL 62/601/602/6L2/6M2/801

BACnet Protocol Implementation Conformance Statement (PICS) MULTICAL 62/601/602/6L2/6M2/801 BACnet Protocol Implementation Conformance Statement (PICS) MULTICAL 62/601/602/6L2/6M2/801 Contents Product Description... 3 BACnet Standardized Device Profile (Annex L)... 3 List all BACnet Interoperability

More information

D-100 FLOW DISPLAY BACnet Network Interface Installation Guide

D-100 FLOW DISPLAY BACnet Network Interface Installation Guide BACnet D-100 FLOW DISPLAY BACnet Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0635-11 / 18341 www.onicon.com sales@onicon.com

More information

NB-ASC Family Protocol Implementation Conformance Statement (PICS)

NB-ASC Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-ASC Family Product l Number: NB-ASC, NB-ASCe, NB-Rooftop, NB-Heat Pump, NB-Fancoil Firmware Revision: 6.03 BACnet Protocol Revision: 4 Product Description:

More information

ESAC ebacgw SNMP. Date: Mar 08,2009. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description:

ESAC ebacgw SNMP. Date: Mar 08,2009. Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3. Product Description: Date: Mar 08,2009 Vendor Name: ESAC srl Product Name: ebacgw-snmp Product Model Number: Product Version: 1.0 BACnet Protocol Revision: 3 Product Description: ebacgw is a BACnet gateway to SNMP (simple

More information

BACnet IP for Quantum

BACnet IP for Quantum for 1 07.10.08 Description: License for lighting hub to enable integration which allows control of EcoSystem ballasts and modules in Lutron s lighting control system. BACNet IP is embedded in the Lighting

More information

Application program usage. Functional description

Application program usage. Functional description Application program usage Product family: Product type: Manufacturer: Name: Order-No.: Controller Controller Siemens Functional description IP Controller N350E 5WG1 350-1EB01 The IP Controller N350E is

More information

Use of the application program

Use of the application program Use of the application program Product family: Product type: Manufacturer: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order no.: Name: Order

More information

NXAC-120 Area Controller

NXAC-120 Area Controller Date: 5/25/2017 Vendor Name: Hubbell Lighting, Inc. Product Name: NXAC-120 Area Controller Product Model Number: NXAC-120 Area Controller BACnet/IP Application Software Version: 1.0.0 Firmware Revision:

More information

BACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC)

BACnet Protocol Implementation Conformance Statement Unitary Protocol Converter (UPC) Date: 10/05/2016 Vendor Name: OEMCtrl Product Name: Unitary Protocol Converter Product Model Number: UPC Applications Software Version: Firmware Revision: 6.00a BACnet Protocol

More information

BACnet MS/TP-module. Data sheet. for MULTICAL 403 and 603

BACnet MS/TP-module. Data sheet. for MULTICAL 403 and 603 Data sheet BACnet MS/TP-module for MULTICAL 403 and 603 BTL certified and listed Compatible with ANSI/ASHRAE 135/ISO 16484-5 Complies with BACnet Application Specific Controller Profile Communication speed

More information

CAS BACnet Stack Product Data Sheet

CAS BACnet Stack Product Data Sheet Introduction The CAS BACnet stack is a protocol implementation library and methodology which allows a user to develop an application which can act as a BACnet client or server device. The stack is transport

More information

Building Product CCM08 Series BACnet Central Control Module User Manual

Building Product CCM08 Series BACnet Central Control Module User Manual Building Product CCM08 Series BACnet Central Control Module User Manual 2007.10 1 1. connect diagrammatic sketch (1)CCM08 interfaces diagrammatic sketch An Ethernet interface connected to BACnet/IP network.

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15119-3 Daikin Chiller Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE 135-2004, BACnet Model WME Magnetic Bearing Centrifugal Chiller

More information

1. BACnet Protocol Implementation Conformance Statement

1. BACnet Protocol Implementation Conformance Statement Information Sheet BACnet PICS 1. BACnet Protocol Implementation Conformance Statement Date: 29-Jul-2016 Vendor Name: Trend Control Systems Ltd. Product Name: Product Model Number: 11/BAC/230, 11/LAN/BAC/230,

More information

Field Equipment Controllers Protocol Implementation Conformance Statement

Field Equipment Controllers Protocol Implementation Conformance Statement Field Equipment Controllers Protocol Implementation Conformance Statement Technical Bulletin MS-FECx6xx-xxx, MS-VMAx6xx-xxx, MS-IOMx7xx-xxx Code No. LIT-12011100 Software Release 6.0 Issued April 3, 2013

More information

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) July 2017 Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: 13 st September 2017

More information

Functional description. Use of the application program. GAMMA instabus Application program description. June C0 Sensor Switch

Functional description. Use of the application program. GAMMA instabus Application program description. June C0 Sensor Switch Use of the application program Functional description Product family: Product type: Manufacturer: Push button Push button, 1 4 fold Siemens The touch sensors have one, two or four vertically arranged pairs

More information

Titan Products NetMaster TP-NM-R/2000

Titan Products NetMaster TP-NM-R/2000 Titan Products NetMaster TP-NM-R/2000 BACnet MS/TP to IP Router Remote Access C-047 08/16 Description The TITAN Products TP-NM-R/2000 NetMaster Router is a high performance, intelligent and secure communications

More information

1. BACnet Protocol Implementation Conformance Statement

1. BACnet Protocol Implementation Conformance Statement Information Sheet BACnet PICS 1. BACnet Protocol Implementation Conformance Statement Date: 25-Feb-2014 Vendor Name: Trend Control Systems Ltd. Product Name: Product Model Number: 11/BAC/230, 11/LAN/BAC/230,

More information

PXC Compact Series on BACnet/IP

PXC Compact Series on BACnet/IP Technical Specification Sheet Rev. 1, August 2006 PXC Compact Series on BACnet/IP Figure 1. PXC24 Compact Controller Document No. 149-454 Page 1 of 6 BACnet Protocol Implementation Conformance Statement

More information

IQ4NC/.../ BACnet PICS

IQ4NC/.../ BACnet PICS Information Sheet BACnet PICS 1. BACnet Protocol Implementation Conformance Statement Date: 25-Feb-2014 Vendor Name: Trend Control Systems Ltd. Product Name: Product Model Number: IQ4NC/12/230, IQ4NC/12/24VAC,

More information

BTL Listed March 2013

BTL Listed March 2013 BTL Listed March 2013 STRATO Automation BACnet Protocol Implementation Conformance Statement Date: March 8 th, 2013 Product name : BACzone 424 Applications Software Version : 0.1 Firmware Revision: 2.139

More information

BACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000

BACnet Protocol Implementation Conformance Statement Automated Logic Corporation LGR25, LGR250, LGR1000 Date: 9/18/2008 Vendor Name: Automated Logic Corporation Product Name: LGR Product Model Number: LGR25, LGR250, LGR1000 Applications Software Version: ExecB ME-LGR-melgr Firmware Revision: 2.18 BACnet

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Products Product Model Number Protocol Revision Software Version Firmware Version SCADA Engine BACnet Operator Workstation SE-BOW 135-1995b (1) 1.0.0.1

More information

NB-VAV Family Protocol Implementation Conformance Statement (PICS)

NB-VAV Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-VAV Family Product Model Number: NB-VAVta, NB-VAVtf, NB-VAVra, NB-VAVrf, NB-VAVr, NB-VAVta-IAQ, NB-VAVtf-IAQ Firmware Revision: 6.03 BACnet Protocol Revision:

More information

Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet

Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet Engineering Data ED 15126 Group: Controls Part Number: ED 15126 Date: April 2010 Supersedes: New Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement

More information

NB-V3Tb Protocol Implementation Conformance Statement (PICS)

NB-V3Tb Protocol Implementation Conformance Statement (PICS) NB-V3Tb Vendor Name: American Auto-Matrix Product Name: NB-V3Tb Product Model Number: NB-V3Tb Firmware Revision: 6.03 BACnet Protocol Revision: 4 Product Description: NB-V3Tb is a full-featured VVT system

More information

BACnet Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement (PICS) BACnet Protocol Implementation Conformance Statement (PICS) Date: May 2, 2017 Vendor Name: Lutron Electronics Co., Inc. Product Name: Quantum BACnet Integration Applications Version: 2.0 Firmware Revision:

More information

BACnet Protocol Implementation Conformance Statement (PICS) der Automationsstation miles-as29/b

BACnet Protocol Implementation Conformance Statement (PICS) der Automationsstation miles-as29/b + BACnet Protocol Implementation Conformance Statement (PICS) der Automationsstation miles-as29/b Version V.40-04.12 Stand: 01.12.2004 miles-as29/b: BACnet-PICS V.40-04.12 Stand: 12/04 Seite 1 von 8 BACnet-PICS

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement WSC 5xx PICS - POTOCOL IMPLEMENTATION CONFOMANCE STATEMENT 29 September 2014 Date: 29 September 2014 Vendor Name: WindowMaster A/S Product Name: BACnet FlexiSmoke Product Model Number: WSA 5MC BACnet-IP

More information

BACnet Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement (PICS) BACnet Protocol Implementation Conformance Statement (PICS) Date: May 24, 2016 Vendor Name: Lutron Electronics Co., Inc. Product Name: Quantum BACnet Integration Applications Version: 2.0 Firmware Revision:

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Date: 01.09.2013 Vendor Name: NETxAutomation Product Name: NETx BMS Server 2.0 Product Model Number: 2.0 Application Software Version: 20 Firmware Revision:

More information

BACnet Protocol Implementation Conformance Statement Automated Logic G5RE

BACnet Protocol Implementation Conformance Statement Automated Logic G5RE Date: 6/1/2017 Vendor Name: Automated Logic Product Name: G5RE Product Model Number: G5RE Applications Software Version: N/A Firmware Revision: 100.02.2018 BACnet Protocol Revision: 9 Product Description:

More information

IntesisBox BACnet IP Server - M-Bus

IntesisBox BACnet IP Server - M-Bus IntesisBox Server - M-Bus Gateway for integration of M-Bus meters into BACnet/IP based control systems Integrate M-Bus meters into your BACnet/IP control system BACnet/IP Ethernet RS232 RS232 / RS485 to

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Date: Sept 19, 2017 Vendor Name: ABB, Vendor ID 127 Product Name: HVAC Drive Product Model Number: ACH580 Applications Software Version: Drive F: 2.x.x.x

More information

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS)

Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) August 2012 Honeywell ComfortPoint TM Open Plant Controller Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: 27 th August 2012

More information

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX Gamma instabus Technical Product nformation Switching Actuators N53, 6AX Switching Actuators N532, 1AX Switching Actuators N534, 16/2AX 4x AC 23V 5WG1 53-1DB31 5WG1 532-1DB31 5WG1 534-1DB31 8x AC 23V 5WG1

More information

Use of the application program

Use of the application program Use of the application program Product family: Product type: Manufacturer: Output Binary Siemens Name: Switching Actuator N 53/ Order no.: 5WG 53-AB Name: Switching Actuator N 52/ Order no.: 5WG 52-AB

More information

Operation and installation manual KNX IP LineMaster 762 (Art. # 5212) KNX Power supply with integrated KNX IP Router and diagnosis functions

Operation and installation manual KNX IP LineMaster 762 (Art. # 5212) KNX Power supply with integrated KNX IP Router and diagnosis functions EN Operation and installation manual IP (Art. # 5212) Power supply with integrated IP Router and diagnosis functions Switch LAN IP 1.1.0 IP 2.1.0 1.1.1 1.1.7 2.1.1 2.1.7 1.1.2 1.1.8 2.1.2 2.1.8 1.1.3 1.1.9

More information

TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS)

TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS) TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: November 2006

More information

PG AB Hochiki FireNet to BACnet IP Protocol Converter

PG AB Hochiki FireNet to BACnet IP Protocol Converter PG-133-103-AB Hochiki FireNet to BACnet IP Protocol Converter PG-133-103-AB is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators

More information

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS)

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS) ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS) Date: February 7, 2018 Vendor Name: Lutron Electronics Co., Inc. Product Name: myroom BACnet Integration Applications Version: 2.0 Firmware

More information

FOREWORD. In addition, changes to BTL Specified Tests might also contain a yellow highlight to indicate the changes made by this addendum.

FOREWORD. In addition, changes to BTL Specified Tests might also contain a yellow highlight to indicate the changes made by this addendum. [This foreword and the Overview on the following pages are not part of this Test Package. They are merely informative and do not contain requirements necessary for conformance to the Test Package.] FOREWORD

More information

NB-GPC Family Protocol Implementation Conformance Statement (PICS)

NB-GPC Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-GPC Family Product Model Number: NB-GPC1, NB-GPC2, NB-GPC3, NB-GPC4 Firmware Revision: 2.00 BACnet Protocol Revision: 4 Product Description: NB-GPC controllers

More information

Gateway for integration of Modbus RTU slave devices into BACnet IP based systems.

Gateway for integration of Modbus RTU slave devices into BACnet IP based systems. IntesisBox BACnet/IP Server - RTU master Gateway for integration of RTU devices into based systems Integrate any RTU device into your BACnet control system Ethernet RS485 (can be also RS232 for single

More information

BrightCore BACnet Lookout V2.2 Product Family

BrightCore BACnet Lookout V2.2 Product Family Page 1 BrightCore BACnet Lookout User Guide Essential, Standard and Extended v.2.2 Page 2 Copyright 2013 by ELMA Kurtalj ltd. All rights reserved. The contents of this documentation are taken in part from

More information

IntesisBox MAPS. Configuration & monitoring software of IntesisBox KNX series. User's manual Issue Date: 06/17 r1.0 eng

IntesisBox MAPS. Configuration & monitoring software of IntesisBox KNX series. User's manual Issue Date: 06/17 r1.0 eng IntesisBox MAPS Configuration & monitoring software of IntesisBox KNX series User's manual Issue Date: 06/17 r1.0 eng Intesis Software S.L.U. 2017 All Rights Reserved. Information in this document is subject

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Network Communication The device parameters must be set before connection to the network and will ensure each device will have a unique MAC address and Device Instance for startup. On startup, the MAC

More information

Product and Applications Description

Product and Applications Description IP N146/02 Product and Applications Description The IP N146/02 is a DIN rail mounted device. The device implements the KNXnet/IP standard and connects KNX/EIB lines via data networks using the Internet

More information

Installation Manual. DZK BACnet

Installation Manual. DZK BACnet Installation Manual DZK BACnet InterfacepbilCodarPageNumber TABLE OF CONTENTS Page Overview... 5 Outline and Features... 5 System outline... 5 Specifications and device elements... 6 Functional specifications...

More information

ASHRAE STANDARDS COMMITTEE

ASHRAE STANDARDS COMMITTEE ASHRAE STANDARDS COMMITTEE 2010 2011 H. Michael Newman, Chair Krishnan Gowri Janice C. Peterson Carol E. Marriott, Vice-Chair Maureen Grasso Douglas T. Reindl Douglass S. Abramson Cecily M. Grzywacz Boggarm

More information

ETH-1000 Version Info

ETH-1000 Version Info ETH-1000 Version Info 01.05.2018 Main CPU Firmware V5.600 Metasys, FLN release Added ability to release an object s value to Metasys N2 Master. Added ability to release a point s value to Siemens FLN Master.

More information

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS)

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS) ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS) Date: February 7, 2018 Vendor Name: Lutron Electronics Co., Inc. Product Name: myroom BACnet Integration Applications Version: 2.0 Firmware

More information

PG AA BACnet IP to Modbus RTU Protocol Converter

PG AA BACnet IP to Modbus RTU Protocol Converter PG-103-100-AA BACnet IP to Modbus RTU Protocol Converter PG-103-100-AA is highly powerful, superior, completely configurable and productive Building & Industrial Automation gateway for integrators to effortlessly

More information

BACnet Protocol Implementation Conformance Statement

BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement Date: July 17, 2013 Vendor Name: Product Name: Product Model Number: Delta Controls Inc. enteliweb eweb Application Software Version: 2.1 Firmware Revision:

More information

BACnet Protocol Implementation Conformance (PIC) Statement

BACnet Protocol Implementation Conformance (PIC) Statement BACnet Protocol Implementation Conformance (PIC) Statement 149-1033 Building Technologies Table of Contents BACnet Protocol Implementation Conformance Statement... 4 3 BACnet Protocol Implementation Conformance

More information

Table of Contents. NBC User's Manual

Table of Contents. NBC User's Manual User's Manual User's Manual Table of Contents 1. Connections and Power... 3 1.1. Connections and Power for WSXXXX_BR products... 3 2. Initial Configuration... 4 2.1. NBC Network Configuration... 4 2.2.

More information

Heatronic Introduction. BAS Integration Manual. Table of Contents

Heatronic Introduction. BAS Integration Manual. Table of Contents Heatronic 4000 BAS Integration Manual Introduction The Heatronic 4000 can communicate with a Building Automation System (BAS) using either BACnet IP or Modbus. This manual provides information about boiler

More information

Contents 1. Summary

Contents 1. Summary Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R KNX IP Router User manual-ver.1 BNIPR-00/00.1 KNX/EIB Intelligent Installation Systems Contents 1. Summary------------------------------------------------------------------------------------------------------------------------------

More information

NovoCon S Digital/Hybrid - High Accuracy Actuator

NovoCon S Digital/Hybrid - High Accuracy Actuator Description NovoCon S Digital/Hybrid is a high accuracy multi-function actuator, specifically designed for use in combination with Pressure Independent Balancing Control Valve type AB-QM in sizes from

More information

PICS EE160D & EE210D BACnet Protocol Implementation Conformance Statement

PICS EE160D & EE210D BACnet Protocol Implementation Conformance Statement PICS EE160D & EE210D BACnet Protocol Implementation Conformance Statement PICS_EE160D_EE210D // v1.0 / Technical data subject to change Content 1. General Information... 3 2. BACnet Standardized Device

More information

BACnet Protocol Implementation Conformance Statement (PICS)

BACnet Protocol Implementation Conformance Statement (PICS) BACnet Protocol Implementation Conformance Statement (PICS) Date: November 4, 2014 Vendor Name: Lutron Electronics Co., Inc. Product Name: Quantum BACnet Integration Applications Version: 2.0 Firmware

More information

Operation and installation manual KNX IP BAOS 774. KNX IP BAOS 774 as application specific Gateway BAOS SDK. Application. Installation and Connection

Operation and installation manual KNX IP BAOS 774. KNX IP BAOS 774 as application specific Gateway BAOS SDK. Application. Installation and Connection EN Operation and installation manual KNX IP BAOS 774 (Art. # 5263) Compact bus powered Interface and ObjectServer between LAN and KNX bus Protocol descriptions can be downloaded at the KNX IP BAOS 774

More information

System-10 BTU Meter BACnet Network Interface Installation Guide

System-10 BTU Meter BACnet Network Interface Installation Guide BACnet ONICON Flow and Energy Measurement System-10 BTU Meter BACnet Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0652-12

More information

BACnet Protocol Implementation Conformance Statement OEMPrtl Pro

BACnet Protocol Implementation Conformance Statement OEMPrtl Pro Date: 12/13/2011 Vendor Name: OEMCtrl Product Name: Product Model Number: Applications Software Version: Firmware Revision: 4.02 BACnet Protocol Revision: 9 Product Description: The is

More information

Operation and installation manual KNX IP BAOS 773. KNX IP BAOS 773 as application specific Gateway BAOS SDK. Application. Installation and Connection

Operation and installation manual KNX IP BAOS 773. KNX IP BAOS 773 as application specific Gateway BAOS SDK. Application. Installation and Connection EN Operation and installation manual KNX IP BAOS 773 (Art. # 5262) Compact bus powered Interface and ObjectServer between LAN and KNX bus KNX IP BAOS 773 as application specific Gateway To connect to non-knx

More information

Operation and installation manual KNX IP Multi IO 580 (48I/O) Application. 2. Factory default settings. 1. Installation and connection ❹ ❼ ❻ ❷

Operation and installation manual KNX IP Multi IO 580 (48I/O) Application. 2. Factory default settings. 1. Installation and connection ❹ ❼ ❻ ❷ EN ❶ Operation and installation manual KNX IP Multi IO 580 (48I/O) (Art. # 5238) KNX IP Multi IO with 48 configurable In- and Outputs ❸ ❹ ❼ ❺ ❽ ❻ ❷ ❶ ❶ ❶ Inputs and Outputs 1-48 ❷ LAN Connector ❸ OLED

More information

Use of the application program

Use of the application program Use of the application program Product family: Product type: Manufacturer: Name: Order no.: Output Controller Siemens UP 255/11 brightness controller or AP 255/12 brightness controller 5WG1 255-4AB11 or

More information

SAUTER BACnet PICS EY-modulo 5 ecos504/505 BACnet Protocol Implementation Conformance Statement

SAUTER BACnet PICS EY-modulo 5 ecos504/505 BACnet Protocol Implementation Conformance Statement BACnet Protocol Implementation Conformance Statement D100275255-05 Content Note: This statement corresponds to the ANSI/ASHRAE 135-2012 release. Changes are taking place constantly, without prior notification.

More information

BASrouterLX Versatile Routing Between IP Network Support Flexible Communications Convenient Installation

BASrouterLX Versatile Routing Between IP Network Support Flexible Communications Convenient Installation BASrouterLX d a t a SHEET BASrouterLX High-Performance BACnet Router with Diagnostic Capabilities The BASrouterLX is a high-performance BACnet storage for use with Wireshark. As a BBMD, up to router providing

More information

BACnet Today and the Smart Grid

BACnet Today and the Smart Grid BACnet Today and the Smart Grid This article was published in ASHRAE Journal, November 2013. Copyright 2013 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically

More information