Configuration/ Alarm EPS

Size: px
Start display at page:

Download "Configuration/ Alarm EPS"

Transcription

1 Equipment Alarm Description Configuration/ Alarm EPS Most Probable Cause Action Tx Regeneration section trace identifier mismatch (J0) Tx Multiplex section alarm indication signal (MS-AIS) Tx Multiplex section remote defect indication (MS-RDI) Tx Excessive BER (HBER) Major Minor RS-TIM (regeneration section trace identifier mismatch) detected on each STM-1 channel from external line which is known as J0 byte in regeneration section overhead Major Minor Multiplex Section AIS (MS- AIS) specified as all "1"s in the entire STM-1 from external line, excluding the STM-1 RSOH Major Minor From external line. The Multiplex Section Remote Defect Indication (MS-RDI) is used to return an indication to the transmit end that the received end has detected an incoming section defect or is receiving MS-AIS Major Minor In the direction from external line, when the line BER exceeds 5*10-5 Check STM-1 source Check STM-1 source Check STM-1 source Check STM-1 source Sync Fail Major Minor Managed only if the addressed STM-1 has been configured as primary/secondary synchronization source Check STM-1 source Sync Degraded signal High Order Path alarm indication signal (AU4-AIS) Major Minor Managed only if the addressed STM-1 has been configured as primary or secondary synchronization source Major Minor The AU4-AIS is specified as all "1"s in the entire high order path Administrative Unit. The alarm becomes significant and must be reported if STM- 1 LOS, STM-1 LOF, STM-1 TIM, or MS-AIS alarm is not present. As consequent action, any E1 extracted from STM-1 will be replaced with AIS (and then circuit emulated according the provisioned settings). Check STM-1 source Check STM-1 source 898/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

2 Equipment Alarm Description Configuration/ Alarm EPS Most Probable Cause Action Loss of Administrative Unit Pointer (AU4-LOP) High OrderSignal Label Mismatch (VC4 -SLM) Loss of Multiframe of Tributary Unit (VC4-LOM) Major Minor This alarm is raised when 8 to 10 consecutive invalid pointers is received or 8 to 10 consecutive NDF is received. The alarm becomes significant and must be reported if STM-1 LOS, STM-1 LOF, STM-1 TIM, MS-AIS, or AU4- AIS alarms are not present. As consequent action, any E1 extracted from STM-1 will be replaced with AIS (and then circuit emulated according the provisioned settings). Major Minor This alarm is raised when the value of C2 byte in VC-4 POH is different between received VC-4 and Tx VC-4. The vale of C2 byte should be 0x02 for E1 mapping for channelized SDH. The alarm becomes significant and must be reported if STM-1 LOS, STM- 1 LOF, STM-1 TIM, MS-AIS, AU4-AIS or AU4-LOP alarms are not present. As consequent action, any E1 extracted from STM-1 will be replaced with AIS (and then circuit emulated according the provisioned settings). Major Minor The value of H4 byte in VC-4 POH is not in the range (01H- 04H) or H4 multiframe is not recovered within 'm' VC-4 frames, a LOM defect shall be declared; 'm' shall be in the range of 8 to 40 and is not configurable. The alarm becomes significant and must be reported if STM-1 LOS, STM-1 LOF, STM-1 TIM, MS-AIS, AU4-AIS, AU4-LOP or VC4-SLM alarms are not present. As consequent action, any E1 extracted from STM-1 will be replaced with AIS (and then circuit emulated according the provisioned settings). Check STM-1 source Check STM-1 source Check STM-1 source Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 899/980

3 Equipment Alarm Description Configuration/ Alarm EPS Most Probable Cause Action Low Order Path alarm indication signal (TU12-AIS) Loss of Tributary Unit Pointer (TU12-LOP) Low Order Path Signal Label Mismatch (VC12-SLM) Major Minor The TU12-AIS is specified as all "1"s in the entire low order pathtributary Unit. The alarm becomes significant and must be reported if STM- 1 LOS, STM-1 LOF, STM-1 TIM, MS-AIS or AU4-AIS, AU4-LOP, VC4-SLM or VC4- LOM alarms are not present. As consequent action, the relevant E1 will be replaced with AIS (and then circuit emulated according the provisioned settings). Major Minor This alarm is raised when 8 to 10 consecutive invalid pointers is received or 8 to 10 consecutive NDF is received. The alarm becomes significant and must be reported if STM-1 LOS, STM-1 LOF, STM-1 TIM,or MS-AIS, AU4- AIS, AU4-LOP, VC4-LOM VC4-SLM or TU12-AIS alarms are not present. As consequent action the relevant E1 will be replaced with AIS (and then circuit emulated according the provisioned settings). Major Minor This alarm is raised when the value of V5 [bit5-7] in VC-12 POH is different from the expected value (010: asyncronous mapping). The alarm becomes significant and must be reported if STM- 1 LOS, STM-1 LOF, STM-1 TIM, MS-AIS, AU4-AIS, AU4-LOP, VC4-SLM, VC4- LOM, TU12-AIS or TU12- LOP alarms are not present. As consequent action the relevant E1 will be replaced with AIS (and then circuit emulated according the provisioned settings) Check STM-1 source Check STM-1 source Check STM-1 source 900/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

4 Equipment Alarm Description Configuration/ Alarm EPS Most Probable Cause Action E1 in STM-1 Tx Alarm Indication Signal (E1-tx AIS) E1 in STM-1 Loss of CESoETH Frames E1 in STM-1 Rx Alarm Indication Signal (E1-rx AIS) Major Minor It reports the Alarm Indication Signal detected on E1 in STM-1 on ingressing (Tx side) and it is detected according to G.775-sect.4. The alarm becomes significant and must be reported if STM-1 LOS, STM-1 LOF, STM-1 TIM, MS-AIS, HP- AIS or LP-AIS alarm is not present. Major Minor Due to Loss-of-CESoETH alarm detection an AIS is inserted as consequent action. AIS insertion: set all '1' on data. Major Minor It reports the Alarm Indication Signal detected on each E1 in STM-1 on egressing (Rx side) and it is detected according to G.775-sect.4. The alarm becomes significant and must be reported if a Loss of CESoETH Frame alarm is not present. Check STM-1 source Check STM-1 source Check STM-1 source E1 in STM-1 Rx Loss Of Frame (E1-rx LOF) Firmware Download In Progress Underlying Resource Unavailable (URU) Major Minor It reports the loss of frame detected on each E1 in STM- 1 on egressing (Rx side) and it is detected according ITU-T G.706-sect.4, and G.706- Annex_B. The alarm becomes significant and must be reported if the E1 is configured as framed and a Loss of CESoETH Frames or E1-rx AIS alarms are not present. Due to LOF alarm detection an AIS must be inserted as consequent action. AIS insertion: set all '1' on data. Check STM-1 source Minor Minor Status of download Wait for downloading to complete Major Major On detection of card failure the STM-1 port objects emit a communication Alarm notification showing the transmission resources are affected by the equipment failure Replace STM-1 Access card Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 901/980

5 Equipment Alarm Description Configuration/ Alarm EPS Most Probable Cause Action 16E1DS1 ASAP Card Card Fail Major - Failure of ASAP Card Replace ASAP Card Equipment Mismatch Major - Card in slot does not match Card configured in Core-E memory Install correct configured card Card Missing Major - ASAP Card is missing from slot Install ASAP Card in slot Unconfigured Equipment Major - Card is not Enabled on the Settings screen Enable card Firmware Download In Progress Minor - Status of download Wait for downloading to complete Loss Of Signal (LOS) Major - Loss of signal on each incoming E1 signal (detected according to ITU-T G.775-sect.4) Check E1 source and/or cable Tx Alarm Indication Signal (Tx AIS) Major - Alarm Indication Signal detected on each incoming E1 signal (Tx side) (detected according to ITU-T G.775- sect.4) Check E1 source Loss Of Frame (LOF) Major - Loss of frame on each incoming E1 signal (detected according to ITU-T G.706- sect.4) Check to CRC4 multiframe alignment of the Far End equipment Loss of Cell Delineation (LCD) Loss of IMA Frame (LIF) Link Out of Delay Synchronisation (LODS) Major - Loss of ATM cell delineation on each incoming E1 signal, when the E1 port is used as physical layer for ATM (detected according to ITU-T I.432) Major - Loss of IMA Frame on each incoming E1 signal, when the E1 port is used as IMA link (detected according to IMA Standard AF-PHY ) Major - It reports the event that, when the E1 port is used as IMA link, it is not synchronized with the other links within the IMA group (detected according to IMA Standard AF- PHY ) Check the ATM scrambling of the Far End equipment Check the IMA configuration of the Far End equipment Check the synchronization of the Far End equipment 902/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

6 Equipment Alarm Description Configuration/ Alarm EPS Most Probable Cause Action RDI/Link Failure Major - It reports, when the E1 port is used as IMA link, the OR of other alarms that are foreseen by IMA Standard AF- PHY : RFI-IMA Tx-Mis-Connected Rx-Mis-Connected Tx-Unusable-FE Link Rx-Unusable-FE Check the Far End equipment IMA Group Trail Signal Fail (TSF) Underlying Resource Unavailable (URU) Major - It reports, for a configured IMA Group, the event that its Group Traffic State Machine is 'down', that is NE and FE Group State Machine are both NOT in "operational" state (IMA Standard AF- PHY ) IMA Group TSFAlarm is also generated by OR of the following alarms (IMA Standard AF-PHY ): Tx-Unusable-FE Link Rx-Unusable-FE Group Start-up-FE Group Config-Aborted Group Config-Aborted- FE Group Insufficient- Links Group Insufficient- Links-FE Group Blocked-FE Group GR-Timing-Mismatch Major Major On detection of card failure the E1 port objects emit a communication Alarm notification showing the transmission resources are affected by the equipment failure Check the Far End equipment Replace 16E1DS1 ASAP Card EAS Card Card Fail Major - EAS card failed Replace EAS Card Equipment Mismatch Major - Card in slot does not match card configured in Core-E memory Install correct configured card Card Missing Major - EAS card is missing from slot Install EAS Card in slot SFP missing alarm Major - The SFP optional plug-in is provisioned, but not present Install the plug-in in the SFP slot Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 903/980

7 Equipment Alarm Description Configuration/ Alarm EPS Most Probable Cause Action Unconfigured Equipment N/A - Card in slot is not provisioned (enabled) Provision card LOS on Gigabit ETH Interface Firmware Download In Progress Underlying Resource Unavailable (URU) Major - Loss of Ethernet is detected Check link partner and cable between link partner and Ethernet connector Minor - Status of download Wait for downloading to complete Major - On detection of card failure the Ethernet port objects emit a communication Alarm notification showing the transmission resources are affected by the equipment failure Replace EAS card Fans Unit Card Fail Major - Fan failed Replace fan unit Card Missing Major - Fan unit is missing from slot Install fan unit Unconfigured Equipment Minor Minor Unit is not Enabled on the Settings screen Enable fan unit 904/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

8 Table 57. Modem Card and ODU300 Alarm Matrix Configuration/Alarm Equipment Alarm Description HS 1+1 FD Most Probable Cause Action Modem Card Card Fail Major Minor Minor Modem Card failed Replace Modem Card Equipment Mismatch Minor Minor Minor Card in slot does not match card configured in Core-E memory Card Missing Major Minor Minor Modem Card is missing from slot Install correct configured card Install Modem Card in slot Unconfigured Equipment Minor Minor Minor Card is not Enabled on the Settings screen Enable card PNU Cable Loss Major Minor Minor Bad cable connection at IF in/out connector on Modem Card Check/repair IF cable connection on alarmed Modem Card Loss of Radio Frame Minor Minor Minor Far end problems, RF path problems, or local circuit failures have caused BER to increase to the point that frames are being lost 1. Switch far end equipment (in a protected system). If alarm clears, replace far end off- line Modem Card. 2. Check/troubleshoot far end alarms 3. Replace alarmed Modem Card Loss of Alignment N/A Minor Minor Delay between main and protect RF paths detected Demod Function Fail Major Minor Minor Internal receive circuit failure 1. Replace main Radio Modem Card 2. Replace protect Modem Card 3. Replace main ODU 4. Replace protect ODU Replace Modem Card High BER Major Minor Minor Bit Error Rate threshold (10E-4) exceeded on RCVR input circuits on modem 1. Verify RF path is clear, antenna is aligned, and no existing weather- related problems 2. Verify RSL is above RCV threshold. If not check upstream transmitter output/troubleshoot transmitter Early Warning N/A Minor Minor 10E-9 BER detected No action is required at this time. Monitor receive signal for increased degrading Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 905/980

9 Configuration/Alarm Equipment Alarm Description HS 1+1 FD Most Probable Cause Action Link Identifier Mismatch Major Major Major Link identifier number provisioned on Modem Card settings screen is different from link identifier number provisioned at other end of hop Set numbers at both ends of hop to match TCA on Radio Link N/A N/A Major Alarm threshold exceeded on standby Modem Card Switch far end equipment (in a protected system). If alarm clears, replace far end off-line Modem Card TCA on Radio Hop Major N/A Minor Alarm threshold exceeded on standby Modem Card after switching from main to standby UAT on Radio Link N/A N/A Major 10 consecutive SES (unavailable time period) detected on main Modem Card Switch far end equipment (in a protected system). If alarm clears, replace far end off-line Modem Card UAT on Radio Hop Major N/A Minor 10 consecutive SES (unavailable time period) detected on standby Modem Card after switching from admin to standby Firmware Download In Progress Minor Minor Minor Download status Wait for downloading to complete Degraded Signal Minor Minor Minor Low quality sync signal from Modem Card Replace Modem Card License Mismatch for Equipment Provisioned Major Major Major Modem card type does not match card type stored in memory on the Core-E Card flash card Replace Modem Card with correct card type Underlying Resource Unavailable (URU) Major Major Major On detection of card failure the Radio port objects emit a communication Alarm notification showing the transmission resources are affected by the equipment failure Replace Modem Card 906/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

10 Configuration/Alarm Equipment Alarm Description HS 1+1 FD Most Probable Cause Action ODU300 Card Fail Major Minor Minor ODU failed Replace ODU Equipment Mismatch Major Minor Minor ODU does not match ODU configured in Core-E memory RCV Function Fail Major Minor Minor ODU receiver circuit failed Replace ODU Replace ODU RF Frequency Mismatch Major Minor Minor Frequency out-ofrange of configured Tx frequency Re-configure frequency Shifter Frequency Mismatch Major Minor Minor Configured shifter value not supported by ODU Re-configure shifter value TX Power Mismatch Minor Minor Minor Configured TX power value not supported by ODU Re-configure Tx power value Software Mismatch Minor Minor Minor Software version on ODU does not match software version on Core ODU Not Responding Minor Minor Minor Loss of communication with ODU Download correct software version 1. Replace ODU 2. Replace alarmed Modem Card Firmware Download In Progress Minor Minor Minor Download status Wait for downloading to complete Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 907/980

11 Table 58. MPT Access Peripheral Card and MPT-HC/MPT-HC V2 Alarm Matrix Configuration/Alarm Equipment Alarm Description HS 1+1 FD Most Probable Cause Action MPT Access Card Card Fail Major - - MPT Access Card failed Equipment Mismatch Major - - Card in slot does not match card configured in Core-E memory Card Missing Major - - MPT Access Card is missing from slot Replace MPT Access Card Install correct configured card Install MPT Access Card in slot Unconfigured Equipment Minor - - Card is not Enabled on the Settings screen Enable card MPT Power Supply Failure Loss Of Ethernet Signal Major - - Power Supply Failure Check/repair the cable connection. If ok, replace MPT-HC Major - - Loss of the incoming Ethernet signal (the signal is missing) or a communication problem with the remote peer (i.e. the communication has not been established for physical problem on cable or interface -> link down) Check the cable connection. If ok, replace the MPT Accerss unit Ethernet Link Error Minor - - Partial failure of electrical or optical cable for the GbEth port Check the cable connection. If ok, replace the MPT Accerss unit Degraded Signal of the MPT Ethernet Interface Minor - - This alarm is active only when the interface is selected as Primary or Secondary synchronization source Check the cable Firmware Download In Progress Minor - - Download status Wait for downloading to complete 908/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

12 Configuration/Alarm Equipment Alarm Description HS 1+1 FD Most Probable Cause Action MPT-HC/ MPT-HC V2 Card Fail Major Minor Minor MPT-HC failed Replace MPT-HC Equipment Mismatch Major Minor Minor MPT-HC does not match MPT-HC configured in Core-E memory Replace MPT-HC RCV Function Fail Major Minor Minor MPT-HC receiver circuit failed Replace MPT-HC RF Frequency Mismatch Major Minor Minor Frequency out-ofrange of configured Tx frequency Re-configure frequency Shifter Frequency Mismatch Major Minor Minor Configured shifter value not supported by MPT-HC Re-configure shifter value TX Power Mismatch Minor Minor Minor Configured TX power value not supported by MPT-HC Re-configure TX power value Modulation parameters Mismatch Major Minor Minor The modulation parameters already configured and stored in the MPR DB are not actually supported by MPT Change the modulation parameters Software Mismatch Minor Minor Minor Software version on MPT-HC does not match software version on Core Download correct software version MPT-HC Not Responding Minor Minor Minor Loss of communication with MPT-HC 1. Replace MPT-HC 2. Replace alarmed MPT Access Card Firmware Download In Progress Minor Minor Minor Download status Wait for downloading to complete Loss of Radio Frame Major Minor Minor Far end problems, RF path problems, or local circuit failures have caused BER to increase to the point that frames are being lost 1. Switch far end equipment (in a protected system). If alarm clears, replace far end off- line MPT-HC. 2. Check/troubleshoot far end alarms 3. Replace alarmed MPT-HC Loss of Alignment N/A Minor Minor Delay between main and protect RF paths detected 1. Replace main MPT- HC 2. Replace protect MPT- HC Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 909/980

13 Configuration/Alarm Equipment Alarm Description HS 1+1 FD Most Probable Cause Action Demod Function Fail Major Minor Minor Internal receive circuit failure High BER Major Minor Minor Bit Error Rate threshold (10E-4) exceeded Replace MPT-HC 1. Verify RF path is clear, antenna is aligned, and no existing weather- related problems 2. Verify RSL is above RCV threshold. If not check upstream transmitter output/troubleshoot transmitter Early Warning N/A Minor Minor 10E-9 BER detected No action is required at this time. Monitor receive signal for increased degrading Link Identifier Mismatch Major Major Major Link identifier number provisioned is different from link identifier number provisioned at other end of hop Set numbers at both ends of hop to match MPT Loop Communication alarm Minor Minor Minor Communication problem between the local MPT and the remote MPT for all the functionalities requiring a communication loop (ATPC, ACM, Pre-distorsion) Check the radio hop Sync Degraded signal Minor Minor Minor This alarm can raise if the addressed Radio interface has been configured as primary/secondary synchronization source. It is active if the frequency of the clock recovered from radio Rx signal is mistuned Check the radio hop 910/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

14 Configuration/Alarm Equipment Alarm Description HS 1+1 FD Most Probable Cause Action Coupling port Loss of Ethernet Signal N/A Minor Minor For the MPT Coupling optical port: - the loss of incoming Ethernet signal (the signal is missing); - a communication problem with the alternate MPT (i.e. the communication has not been established for physical problem on cable or interface -> link down). When this alarm is raised, RPS is not working Check the cable Coupling port Link Error N/A Minor Minor For the MPT Coupling optical port, the ratio between the number of received errored packets and the total number of received packets is above a given threshold. When this alarm is raised, RPS is not working Check the cable Traffic port Link Error Minor Minor Minor For the MPT Traffic optical port, the ratio between the number of received errored packets and the total number of received packets is above a given threshold MPT Tx Clock Failure Minor Minor Minor The MPT is not able to lock the air Tx symbol rate to the NE Clock TCA on Radio Link N/A N/A Major Alarm threshold exceeded on standby MPT-HC Check the cable Check the radio hop Switch far end equipment (in a protected system). If alarm clears, replace far end off-line MPT-HC TCA on Radio Hop Major N/A Minor Alarm threshold exceeded on standby MPT-HC after switching from main to standby Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 911/980

15 Configuration/Alarm Equipment Alarm Description HS 1+1 FD Most Probable Cause Action UAT on Radio Link N/A N/A Major 10 consecutive SES (unavailable time period) detected on main MPT-HC Switch far end equipment (in a protected system). If alarm clears, replace far end off-line MPT-HC UAT on Radio Hop Major N/A Minor 10 consecutive SES (unavailable time period) detected on standby MPT-HC after switching from admin to standby Degraded Signal Minor Minor Minor Low quality sync signal from MPT-HC Replace MPT-HC PPP IP Fail Minor Minor Minor Point to point IP failure Check the settings Incompatible protection N/A Major Major 1+1 configuration has been provisioned between the two MPT- HC or the two MPT-HC V2, but the RPS or the XPIC module have not been deployed. When this alarm is active, the Transmitter is muted Remove the protection configuration or modify the hardware XPIC cable loss (only for MPT-HC V2 with the RPS+XPIC external module installed N/A Major N/A Loss of signal on the XPIC interface Chec the cable 912/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

16 Table 59. MPT Access Peripheral Card and MPT-MC Alarm Matrix Equipment Alarm Description Configuration/Alarm HS Most Probable Cause Action MPT-MC Card Fail Major Minor MPT-MC failed Replace MPT-MC Equipment Mismatch Major Minor MPT-MC does not match MPT-MC configured in Core-E memory Replace MPT-MC RCV Function Fail Major Minor MPT-MC receiver circuit failed Replace MPT-MC RF Frequency Mismatch Major Minor Frequency out-ofrange of configured Tx frequency Re-configure frequency Shifter Frequency Mismatch Major Minor Configured shifter value not supported by MPT-MC Re-configure shifter value TX Power Mismatch Minor Minor Configured TX power value not supported by MPT-MC Re-configure TX power value Modulation parameters Mismatch Major Minor The modulation parameters already configured and stored in the MPR DB are not actually supported by MPT Change the modulation parameters Software Mismatch Minor Minor Software version on MPT-MC does not match software version on Core Download correct software version MPT-MC Not Responding Minor Minor Loss of communication with MPT-MC 1. Replace MPT-MC 2. Replace alarmed MPT Access Card Firmware Download In Progress Minor Minor Download status Wait for downloading to complete Loss of Radio Frame Major Minor Far end problems, RF path problems, or local circuit failures have caused BER to increase to the point that frames are being lost 1. Switch far end equipment (in a protected system). If alarm clears, replace far end off- line MPT-MC. 2. Check/troubleshoot far end alarms 3. Replace alarmed MPT-MC Loss of Alignment Minor Minor Delay between main and protect RF paths detected Demod Function Fail Major Minor Internal receive circuit failure 1. Replace main MPT- HC 2. Replace protect MPT- HC Replace MPT-MC Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 913/980

17 Equipment Alarm Description Configuration/Alarm HS Most Probable Cause Action High BER Major Minor Bit Error Rate threshold (10E-4) exceeded 1. Verify RF path is clear, antenna is aligned, and no existing weather- related problems 2. Verify RSL is above RCV threshold. If not check upstream transmitter output/troubleshoot transmitter Early Warning N/A Minor 10E-9 BER detected No action is required at this time. Monitor receive signal for increased degrading Link Identifier Mismatch Major Major Link identifier number provisioned is different from link identifier number provisioned at other end of hop Set numbers at both ends of hop to match MPT Loop Communication alarm Minor Minor Communication problem between the local MPT and the remote MPT for all the functionalities requiring a communication loop (ATPC, ACM, Pre-distorsion) Check the radio hop Sync Degraded signal Minor Minor This alarm can raise if the addressed Radio interface has been configured as primary/secondary synchronization source. It is active if the frequency of the clock recovered from radio Rx signal is mistuned Check the radio hop MPT Tx Clock Failure Minor Minor The MPT is not able to lock the air Tx symbol rate to the NE Clock TCA on Radio Link N/A N/A Alarm threshold exceeded on standby MPT-MC Check the radio hop Switch far end equipment (in a protected system). If alarm clears, replace far end off-line MPT-MC 914/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

18 Equipment Alarm Description Configuration/Alarm HS Most Probable Cause Action TCA on Radio Hop Major N/A Alarm threshold exceeded on standby MPT-MC after switching from main to standby UAT on Radio Link N/A N/A 10 consecutive SES (unavailable time period) detected on main MPT-MC Switch far end equipment (in a protected system). If alarm clears, replace far end off-line MPT-MC UAT on Radio Hop Major N/A 10 consecutive SES (unavailable time period) detected on standby MPT-MC after switching from admin to standby Degraded Signal Minor Minor Low quality sync signal from MPT-MC Replace MPT-MC PPP IP Fail Minor Minor Point to point IP failure Check the settings EPS LOS RPS RCV TCA UAT Equipment Protection Switching Loss of Signal Radio Protection Switching Receiver Threshold Crossing Alarm Un-Available Time Check the basics first. For example, if multiple alarms are present, and these include power supply voltage or hardware alarms, always check their cause before looking at resultant down-stream path failure or path warning (signal) alarms. Similarly, if a path-related failure is indicated (no hardware or software alarms), investigate the path. Go to the WebEML History screen (15 minute view) to check supporting data, such as low RSL and incidence of intermittent pre-failure BER alarms, which if present are evidence of a path-related failure. Check if symptoms match the alarm. Alarms reflect the alarm state, but in exceptional circumstances an alarm may be raised because of a failure to communicate correctly with the alarm source, or a failure in alarm management processing. Always check to see if symptoms match the alarm, using LED indications and the WebEML. Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 915/980

19 Check if recent work may be a cause. Recent work at the site may be a cause or contributing factor. Check for a configuration change, software upgrade, power recycling (reboot), or other site work: Many hardware alarms are only initiated as a loss-of-communications alarm during a reboot, software upgrade, or reconfiguration. By not being able to communicate with the Core-E, their settings cannot be loaded. The fault may be at the hardware device (most likely), communications to it, or the Core-E. Hardware/software compatibility alarms will be raised when a new plug-in is installed that needs a later version of 9500 MPR-E software. Hardware incompatible alarms will be raised when a plug-in is installed in a slot that has been configured for a different plug-in. MSS before an ODU. If there is doubt about whether a fault is in the MSS or ODU, always replace the MSS first; it is quicker and easier. Hot-pluggable. MSS cards are hot-pluggable. There is no need to power-down before replacing, but traffic will be lost unless the plug-in is protected. Plug-in restoration time. Ensure adequate time is allowed for services to resume when a plug-in is replaced Troubleshooting Path Problems A path-related problem, with the exception of interference, is characterized by traffic being similarly affected in both directions. Generally, if you are experiencing only a one-way problem, it is not a path problem. Note A path extends from ODU antenna port to ODU antenna port. Normally a path problem is signalled by a reduced RSL, and depending on its severity, a high BER. Only in worst case situations, such as an antenna knocked out of alignment, will a path fail completely, and stay that way. For weather-related problems, such as rain or ducting, the path problem will disappear as the weather returns to normal Path Problems on a Commissioned Link A path problem on an existing link, one that has been operating satisfactorily may be caused by: Weather-related path degradation If BER alarms are fleeting/not permanent and RSL returns to its normal, commissioned level after the alarm is cleared, rain, diffraction, or multipath fading is indicated. Rain fade is the likely cause of fade for links 13 GHz and higher. Diffraction and multipath/ducting for links 11 GHz and lower. If these alarms are persistent, there could be a problem with the link design or original installation. 916/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

20 Changed antenna alignment or antenna feed problem If RSLs do not return to commissioned levels after a period of exceptionally strong winds, suspect antenna alignment. Also, check the antenna for physical damage, such as may occur with ice-fall. For a remote-mounted ODU, check its antenna feeder. New path obstruction Where all other parameters check as normal, and the path has potential for it to be obstructed by construction works, view/survey the path for possible new obstructions. Interference from other signal sources Interference usually affects traffic in just one direction. Unlike other path problems, RSL is not affected. If suspected, check for new link installations at, or in the same geographical area, as the affected site. Ultimately, a spectrum analyzer may have to be used to confirm interference, which is not an easy task given the need to connect directly to the antenna port, after removing the ODU Path Problems on a New Link For a new link, potential problems can extend to also include: Incorrect antenna alignment One or both antennas incorrectly aligned. Refer to Installation alignment procedure on CD. Mismatching antenna polarizations Given a typical polarization discrimination of 30 db, for most links it is not possible to capture a signal to begin the antenna alignment process. Incorrect path calculations If the RSLs are too low or too high, antenna alignment is correct, and Tx power settings are correct, check the path calculations used to determine the link performance. A good calculation match is +/ - 2 db. Disagreements in excess of 3 db should be investigated. Reflections Reflection (path cancellation) problems may not have been picked up at the path planning stage, particularly if the survey was a simple line-of-sight. If suspected, resurvey the path. Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 917/980

21 6.4.4 Troubleshooting Configuration Problems Configuration problems should only occur during the setup of a new link, or reconfiguration of an existing link. The more common problems may be broadly categorized as: Compatibility Problems The two alarms that may activate are Configuration Not Supported and SW/HW Incompatible: Configuration Not Supported: The plug-in installed is not enabled or is incorrect for the configuration. SW/HW Incompatible: Typically raised when new hardware is plugged into an existing MSS that has software from an earlier release. To remove the alarm, compatible 9500 MPR-E software is required; install the latest software. Incorrect circuit connections No alarms are activated for incorrect circuit connections. An incorrect assignment means the expected end-to-end circuit connectivity will not happen. Re-check circuit assignments for all nodes carrying the lost circuit(s). Take extra care when configuring ring circuits. Incorrect ID naming and commissioning All traffic-carrying circuits must have a unique flow ID for the cross-connect capability to operate. Incorrect/incompatible trib settings Trib line interface settings incorrect, or line levels incompatible. While no alarm activates for an incorrect setting, its effect may result in line levels being too low (LOS alarm), or too high, resulting in a high BER Troubleshooting Ethernet Problems This section gives general guidance on troubleshooting problems related to the four Ethernet ports on the Core-E Card. The most common Ethernet problems are network and connectivity related and therefore always check the following first: for User and NMS ports, verify link partner capability, provisioning, and connection for Radio ports, verify the cabling between ODU and MSS. In order for the green Link LED to light: 1) Cable must be connected to Ethernet port 2) Ethernet port must be enabled (provisioned Enabled). Applicable for User and NMS ports 3) Speed and mode must be provisioned the same as the link partner. The yellow LED opposite the green on the connector indicates activity only. The flashing yellow LED is not an indicator of signal type or quality. 918/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

22 6.4.6 Troubleshooting TMN Problems This section gives general guidance on troubleshooting TMN problems related to Ethernet port 4 on the Core-E Card. Ethernet port 4 on the Core-E Card can be used to transport SNMP IP data. Troubleshoot port 4 connectivity alarms the same as Ethernet ports 1-3. The most common TMN problems are network related and first alert is normally observed by improper operation at the SNMP master. Always check the following first: Verify master is properly registered in NE to receive traps. Verify SNMP version matches system requirements Verify correct community string and privileges Verify proper network routing. Refer to Table 60. for detail TMN network troubleshooting. Table 60. TMN Network Troubleshooting Problem Possible Cause Possible Solution Unusually slow communication in radio network Unable to operate controls using SNMP Can Read SNMP objects but cannot Write to SNMP objects No traps being received from NE Unable to communicate with the NE through the radio network (unable to ping the NE). Can ping the TMN Interface but cannot communicate with the NE using SNMP, or can only see a few SNMP objects in the NE. 1. Normal network management traffic is saturating the communications channel. 2. Polling radios for PM data or missed alarms too rapidly 3. Multiple remote software downloads in process 4. IP traffic other than network management traffic being routed through radio network To perform control operations, the Manager must be registered as a craft device. 1. There may be too many radios being managed within a single region. Split the radio network management into different regions and backhaul the traffic for each region through separate channels. 2. Poll the radios more slowly. 3. Download to fewer radios at a time. 4. Configure external routers to allow only network management related traffic through the Management network of the radios. Dynamic route updates (OSPF, RIP) may attempt to reroute high speed traffic through the TMN network if a high speed ink fails. Register the Manager as a craft device. Manager registration type can be changed as needed to type ct to allow control operation and then be changed back to nml for normal operation. 1. Incorrect community string 1. Use the correct community string. 2. If the TMN Interface is configured for SNMPv2, the write community string is probably wrong. 1. Manager not registered in NE to receive traps 2. Communication failure in network Possible communication path failure or routing failure within the radio network. If using SNMPv2, using the wrong community string. 2. Use the correct write community string. 1. Register Manager with NE. 2. Check network connectivity. Check redundant network paths and routing. Traceroute (tracert) is useful for locating path or routing faults. Use traceroute (tracert) to help locate for communication path or routing problems. Verify community string or username/ passphrase. Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 919/980

23 6.5 Card Removal and REPLACEMENT The basic rules for installing plug-in cards are as follows: Never install, change or remove a card without first connecting to the shelf with an ESD grounding cable. Failure to do so may cause ESD damage to the cards. Plug-ins must be withdrawn and inserted using their finger-grip fastener/pulls. Never withdraw or insert using attached cable(s). Pulling on the cables may damage the cable, plug-in connector, and/or plug-in card connector attachment. When installing a plug-in, ensure its backplane connector is correctly engaged before applying sufficient pressure to bring the plug-in panel flush with the front panel. Improper alignment can result in damaged pins on the backplane connector and/or damage to the plug-in connector. All slots must be filled with either a peripheral plug-in card or a blank panel. Failure to do so will compromise EMC integrity and cooling air from the fan. 920/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

24 Use extreme caution when connecting or disconnecting the ODU cable on the Modem Card. The shelf battery voltage is present on the center conductor of the connector. When removing or replacing a Modem Card, withdraw the card from the shelf before disconnecting the cable to the ODU. Failure to follow these cautions may cause arcing and/or possible power spikes that could affect traffic on other links installed at the node. Removing an in-service card in an unprotected link will cause loss of traffic. Removing an in-service card in a protected link requires switching the traffic onto the standby (protection) channel. All plug-ins can be removed and installed with power applied. a) Turn off NE power. If the main Core-E Card fails, traffic and platform data will switch to the spare Core-E Card automatically. Do not remove power from the NE during the removal and replacement of the failed main Core-E Card without first reviewing/performing the following procedure: b) Remove failed main Core-E Card. c) Turn on NE power. d) Wait two (2) minutes. e) Install replacement Core-E Card. Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 921/980

25 6.5.1 Core-E Card Removal and Replacement Core-E Protected Radio If the Main Core-E Card in slot 1 fails, traffic/services protection and control platform protection switches to the spare Core-E Card in slot 2. Loopbacks and all other manual operations, such as manual switch, tx mute, will be lost (deactivated). Alarms previously active will be newly detected and reported via notification, with a new time stamp. After the removal of a faulty card, when you re-insert the new card, before re-connecting the Ethernet cables between the Core-E card and other systems, wait that the Core-E card LED STATUS (S) ends its flashing activity. Verify the replacement Core-E Card meets the following compatibility rules: Main Core-E Card (in slot 1) and Spare Core-E Card (in slot 2) must be the same type. Local and far end Core-E Cards must use the same software version, but do not have to be the same type Flash card replacement procedure First case: Core-E Protected 1) Get a spare FLASH CARD with the same sw-package release and license of the Main flash. 2) Remove the faulty FLASH CARD from the main Core-E and insert the spare one. 3) Insert the Core-E with the new FLASH CARD 4) The MIB (MAIN FLASH) will be automatically aligned with the MIB (SPARE FLASH). Second case: Core-E Not Protected (NB) 1) Get a spare FLASH CARD with the same sw-package release and license. 2) Remove the faulty FLASH CARD from the main Core-E and insert the spare one. 3) Insert the Core-E with the new FLASH CARD 4) Carry-out the RESTORE procedure. ATTENTION (caution to avoid complete traffic loss) Do not insert in the system a Flash Card the content of which is unknow. You must be aware that, if a Flash Card with SW information different from that running in the system is inserted as it is, the software download will be automatically carried out from the Flash Card toward the System, thus causing a complete system crash. 922/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

26 Note The license of the Spare Flash card can be different from the license of the Main Flash card. Only the license of the Main Flash card manages the NE. By changing the Main Flash card, also the MAC address changes: in this case the cross-connection must be reviewed ODU300 or MPT-HC V2 or MPT-MC removal and replacement Disconnect the cables from the Outdoor Unit to be replaced and connect them to the spare ODU MPT-HC removal and replacement Disconnect the cables and the co-box from the MPT-HC to be replaced and connect them to the spare MPT-HC. Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 923/980

27 6.6 Upgrade from Not Protected to a Protected Radio (with ODU300) Adaptive Modulation to 1+1 HSB Adaptive Modulation and 1+1 EPS Starting from a 1+0 configuration (see an example in the graphics below) perform the following procedure to upgrade to a 1+1 HSB radio with Adaptive Modulation and 1+1 EPS. This is an in-service but not a hitless procedure. 1) Plug-in the Access card (E1 or STM-1) in slot 4 (spare). An Unconfigured Equipment alarm displays. Note: in the figure is shown the 32E1 Access card. 2) Plug-in Modem card in slot 8 (spare). An Unconfigured Equipment alarm displays. 3) On WebEML Settings screen enable the Access card (E1 or STM-1) in slot 4. 4) On WebEML Settings screen enable the Modem card in slot 8. 5) On WebEML Settings screen provision the Access card (E1 or STM-1) (slots 3 and 4) for 1+1 EPS Protection Type. 6) On WebEML Settings screen provision the Modem cards (slots 7 and 8) for HSB Protection Type. Local station and remote station will observe 2 seconds sync loss. 7) Connect the signal cables to the spare the Access card (E1 or STM-1) in slot 4. 8) Connect the new IDU/ODU cable to the spare Modem card in slot 8. Note After the changes a modification must be done in the TDM2Eth cross-connections of the remote NE: the MAC address must be changed from Unicast to Multicast as explained in Figure 126., Figure 127. and Figure /980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

28 Static Modulation to 1+1 HSB Static Modulation and 1+1 EPS Refer to the 1+0 Adaptive Modulation to 1+1 HSB Adaptive Modulation procedure above to 1+1 Frequency Diversity and 1+1 EPS This is an in-service but not a hitless procedure. Starting from a 1+0 configuration (see an example in the graphics below) perform the following procedure to upgrade to a 1+1 Frequency Diversity and 1+1 EPS. 1) Plug-in the Access card (E1 or STM-1) in slot 4 (spare). An Unconfigured Equipment alarm displays. Note: in the figure is shown the 32E1 Access card. 2) Plug-in Modem card in slot 8 (spare). An Unconfigured Equipment alarm displays. 3) On WebEML Settings screen enable the Access card (E1 or STM-1) in slot 4. 4) On WebEML Settings screen enable the Modem card in slot 8. 5) On WebEML Settings screen provision the Access card (E1 or STM-1) (slots 3 and 4) for 1+1 EPS Protection Type. 6) On WebEML Settings screen provision the Modem cards (slots 7 and 8) for 1+1 FD Protection Type. Local station and remote station will observe 2 seconds sync loss. 7) Connect the signal cables to the spare the Access card (E1 or STM-1) in slot 4. 8) Connect the new IDU/ODU cable to the spare Modem card in slot 8. 9) Properly configure the protection ODU. Note After the changes a modification must be done in the TDM2Eth cross-connections of the remote NE: the MAC address must be changed from Unicast to Multicast as explained in Figure 126., Figure 127. and Figure Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 925/980

29 6.7 Upgrade from Not Protected to a Protected Radio (with MPT-HC/ MPT-HC V2 or MPT-MC) Note With MPT-MC only the 1+1 HSB configuration is available Adaptive Modulation to 1+1 HSB/FD Adaptive Modulation and 1+1 EPS Starting from a 1+0 configuration (see an example in the graphics below) perform the following procedure to upgrade to a 1+1 HSB radio with Adaptive Modulation and 1+1 EPS. This is an in-service but not a hitless procedure. 1) Plug-in the Access card (E1 or STM-1) in slot 4 (spare). An Unconfigured Equipment alarm displays. Note: in the figure is shown the 32E1 Access card. 2) Plug-in MPT Access card in slot 8 (spare). An Unconfigured Equipment alarm displays. 3) On WebEML Settings screen enable the Access card (E1 or STM-1) in slot 4. 4) On WebEML Settings screen enable the MPT Access card in slot 8. 5) On WebEML Settings screen provision the Access card (E1 or STM-1) (slots 3 and 4) for 1+1 EPS Protection Type. 6) On WebEML Settings screen provision the MPT Access cards (slots 7 and 8) for HSB or FD Protection Type. The Local station and the Remote station will observe a short traffic impact. 7) Connect the signal cables to the spare the Access card (E1 or STM-1) in slot /980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

30 8) Connect the new Power Supply cable and new Ethernet cable to the spare MPT Access card in slot 8. 9) In case of 1+1 FD properly configure the protection MPT-HC. Note After the changes a modification must be done in the TDM2Eth cross-connections of the remote NE: the MAC address must be changed from Multicast to Unicast as explained in Figure 126., Figure 127. and Figure Static Modulation to 1+1 HSB/FD Static Modulation and 1+1 EPS Refer to the 1+0 Adaptive Modulation to 1+1 HSB/FD Adaptive Modulation procedure above. Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 927/980

31 6.8 Downgrade from Protected to a Not Protected Radio (with ODU300) HSB Adaptive Modulation and 1+1 EPS to 1+0 Adaptive Modulation Downgrading from 1+1 HSB and 1+1 EPS to 1+0 configuration is an out-of-service procedure. The main channel must be in service including sync source before starting procedure. 1) Disconnect signal cables from the spare the Access card (E1 or STM-1) in slot 4. Note: in the figure is shown the 32E1 Access card. 2) Disconnect IDU/ODU cable on the spare Modem card in slot 8. 3) On WebEML Settings screen for Modem cards (slots 7 and 8) enable Local Tx Mute for Channel #1 and Channel #0. 4) On WebEML Settings screen for Modem cards (slots 7 and 8) set Protection Type to no Protection. 5) On WebEML Settings screen provision the MPT Access cards (slots 7 and 8) for HSB or FD Protection Type. The Local station will observe a short traffic impact. 6) On WebEML Settings screen for Modem cards (slots 7 and 8) disable Local Tx Mute for Channel #1 and Channel #0. 7) On WebEML Settings screen for the Access card (E1 or STM-1) (slots 3 and 4) set Protection Type to no Protection. 8) On WebEML Settings screen for spare the Access card (E1 or STM-1) (slot 4) set Equipment Type to EMPTY. 9) On WebEML Settings screen for spare Modem card (slot 8) set Equipment Type to EMPTY. 10) Remove spare Modem card (slot 8). 928/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

32 11) Remove spare the Access card (E1 or STM-1) (slot 4). 12) Power off and power on the NE. Note After the changes a modification must be done in the TDM2Eth cross-connections of the remote NE: the MAC address must be changed from Multicast to Unicast as explained in Figure 126., Figure 127. and Figure HSB Static Modulation and 1+1 EPS to 1+0 Static Modulation Refer to the 1+1 HSB Adaptive Modulation and 1+1 EPS to 1+0 Adaptive Modulation procedure above FD to 1+0 Downgrading from 1+1 FD to 1+0 configuration is an out-of-service procedure. The main channel must be in service including sync source before starting procedure. 1) Disconnect E1 signal cables from the spare the Access card (E1 or STM-1) in slot 4. Note: in the figure is shown the 32E1 Access card. 2) Disconnect IDU/ODU cable on the spare Modem card in slot 8. Note Local AIS will remain active throughout remainder of procedure. Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 929/980

33 3) On WebEML Settings screen for Modem cards (slots 7 and 8) set Protection Type to no Protection. 4) On WebEML Settings screen provision the MPT Access cards (slots 7 and 8) for HSB or FD Protection Type. The Local station will observe a short traffic impact. 5) On WebEML Settings screen for the Access card (E1 or STM-1) (slots 3 and 4) set Protection Type to no Protection. 6) On WebEML Settings screen for Modem cards (slots 7 and 8) set Protection Type to no Protection. 7) On WebEML Settings screen for spare the Access card (E1 or STM-1) (slot 4) set Equipment Type to EMPTY. 8) On WebEML Settings screen for spare Modem card (slot 8) set Equipment Type to EMPTY. 9) Remove spare Modem card (slot 8). 10) Remove spare the Access card (E1 or STM-1) (slot 4). 11) Power off and power on the NE. Note After the changes a modification must be done in the TDM2Eth cross-connections of the remote NE: the MAC address must be changed from Multicast to Unicast as explained in Figure 126., Figure 127. and Figure /980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

34 6.9 Downgrade from Protected to a Not Protected Radio (with MPT-HC/ MPT-HC V2 or MPT-MC) Note With MPT-MC only the 1+1 HSB configuration is available HSB/FD Adaptive Modulation and 1+1 EPS to 1+0 Adaptive Modulation Downgrading from 1+1 HSB/FD and 1+1 EPS to 1+0 configuration is an out-of-service procedure. The main channel must be in service including sync source before starting procedure. 1) Disconnect the signal cables from the spare the Access card (E1 or STM-1) in slot 4. Note: in the figure is shown the 32E1 Access card. 2) Disconnect IDU/ODU cables on the spare MPT Access card in slot 8. Note In case of 1+1 FD local AIS will remain active throughout remainder of procedure. 3) On WebEML Settings screen for MPT Access cards (slots 7 and 8) enable Local Tx Mute for Channel #1 and Channel #0. 4) On WebEML Settings screen for MPT Access cards (slots 7 and 8) set Protection Type to no Protection. 5) On WebEML Settings screen provision the MPT Access cards (slots 7 and 8) for HSB or FD Protection Type. The Local station will observe a short traffic impact. Maintenance and Trouble-clearing 3DB18809AAAA Issue 1 931/980

35 6) On WebEML Settings screen for MPT Access cards (slots 7 and 8) disable Local Tx Mute for Channel #1 and Channel #0. 7) On WebEML Settings screen for the Access card (E1 or STM-1) (slots 3 and 4) set Protection Type to no Protection. 8) On WebEML Settings screen for spare the Access card (E1 or STM-1) (slot 4) set Equipment Type to EMPTY. 9) On WebEML Settings screen for spare MPT Access card (slot 8) set Equipment Type to EMPTY. 10) Remove spare MPT Access card (slot 8). 11) Remove spare the Access card (E1 or STM-1) (slot 4). 12) Power off and power on the NE. Note After the changes a modification must be done in the TDM2Eth cross-connections of the remote NE: the MAC address must be changed from Multicast to Unicast as explained in Figure 126., Figure 127. and Figure HSB/FD Static Modulation and 1+1 EPS to 1+0 Static Modulation Refer to the 1+1 HSB/FD Adaptive Modulation and 1+1 EPS to 1+0 Adaptive Modulation procedure above Cleaning Do not use acid, alcohol, or brushes to clean cards because damage to the silkscreen labeling and antistatic coating can result. Cleaning should be confined to the removal of dust and dirt using a damp cloth. Cleaning should normally be confined to the removal of dust and dirt using a soft bristled (natural fiber) brush and a low velocity blower (such as a vacuum cleaner with a plastic blower nozzle). Do not use acid or synthetic bristled brushes to clean cards that contain electrostatic-sensitive components. 932/980 3DB18809AAAA Issue 1 Maintenance and Trouble-clearing

36 7 Line up and Commissioning This chapter details all phases necessary for the equipment line up and commissioning. Subject On page Introduction 934 General 934 Safety EMC EMF ESD norms and Cautions to avoid equipment damage 935 Conventions 935 Summary of the commissioning phases 936 General information about test bench drawings 937 Commissioning of STATION A phase 1 (Turn up) 938 Commissioning of STATION B phase 1 (Turn up) 940 Fine antenna alignment and preliminary checks Stations A & B 940 End of commissioning phase 1 (Turn up) in STATION A 944 Commissioning station A phase 2 (acceptance test) 945 Commissioning station B Phase 2 (acceptance Test) 971 Final operations 971 Annex A: fine antenna alignment 971 Line up and Commissioning 3DB18809AAAA Issue 1 933/980

37 7.1 Introduction General This chapter details all phases necessary for the equipment line up, commissioning, and acceptance, providing the user with the information needed to connect, power on, and perform a minimum turn up of a radio link comprising two 9500 MPR-E Rel Network Elements. It is assumed that, at both premises (Station A and Station B), the mechanical installation and cabling of the INDOOR and OUTDOOR units is completed, the antennas are installed and pre positioned, and the MSS ODU cable(s) has/have been connected to the MSS. Any information needed to complete the above mentioned operations are out of the scope of this chapter. For this purpose refer to the Installation section. All the cables and measurement kits as described in Table 61. below are supposed to be available. Table 61. Test and commissioning instruments INSTRUMENT QTY CHARACTERISTICS Laptop computer running the supervisory software 1 SWP 9500 MPR-E V PDH Analyzer Pattern Generator 1 E1 traffic SDH Analyzer Pattern Generator 1 STM-1 traffic ATM Analyzer 1 V.11 Analyzer 1 Link Service kit cable (for MPT antenna alignment) 1 In alternative, for Ethernet Data channel functionality tests: Optional 1 PC + 1 Ethernet cable (for ping function) or 2 PCs (for ping function) or 2 Ethernet Data Analyzers Multi meter 1 Voltmeter AC and DC Loop tester Cable Tester 1 For RJ45, Ethernet, Optical fiber etc. TRS 1 Test Result Sheet, available as separate document The Alcatel Lucent Software package SWP 9500 MPR-E V3.1.0 must have already been installed in the PC used as the WebEML (WebEML) and the same software V3.1.0 must be already present as commit version in the Flash Card of both two Network Elements. Before proceeding with line up and commissioning, ensure that you have the equipment and accessoriesrequired for that purpose. 934/980 3DB18809AAAA Issue 1 Line up and Commissioning

38 7.1.2 Safety EMC EMF ESD norms and cautions to avoid equipment damage Warning: to make sure of the continuity and avoid short circuit, all cables / connectors connections (RJ45, Coaxial, Ethernet, Optical Fiber.. ) made on the field have to be verified and checked with Cable tester. The waterproofness must be also checked. If not yet done, read whole Chapter 1 on page 31: it describes the operations and/or precautions to be observed to safeguard operating personnel during the working phases, and to guarantee equipment safety. Read them with accuracy before to start every action on the equipment Conventions To simplify the description of actions, the following symbols are in use: Symbol used WebEML Meaning Manual action Check/Verify On WebEML Select Select a Menu item Sub Menu item The commissioning operations described in this document are for a radio link between a Station A and a Station B. If the network includes supervision, station A is the one located between the supervisory station and station B (see figure below). Installation and commissioning begin at station A. MSS MSS Figure 654. Relative positions of stations A and B WARNING: at the beginning of this procedure, the local IP address and Ethernet IP address of both the NE 9500 MPR-E stations, are still set to default value (as delivered from Alcatel Lucent factory). For this reason, their physical connection to the TMN network must be done after having changed such addresses to correct values. Line up and Commissioning 3DB18809AAAA Issue 1 935/980

39 7.1.4 Summary of the line up, commissioning, and acceptance phases Note: The following procedure must be used for every Modem unit installed in MSS. The commissioning procedure is summarized as follows: [1] Turn up (phase 1) 1) Visual inspection and NE configuration. a) Station A, roughly point the antenna towards station B (if not done in the Hardware Installation procedure) b) Commission station A (phase 1) c) Commission station B (phase 1) MSS MSS 2) Fine antenna alignment and preliminary checks Stations A & B a) Station B, fine align the antenna towards station A, and preliminary checks b) Station A, fine align the antenna towards station B, and preliminary checks MSS MSS [2] Site acceptance tests (phase 2) 3) Station A, perform all the commissioning checks and tests Report the results in the TRS. MSS MSS 936/980 3DB18809AAAA Issue 1 Line up and Commissioning

40 4) Station B, perform all the commissioning checks and tests Report the results in the TRS. MSS MSS General information about test bench drawings In the test bench drawings depicted in the following paragraphs of this chapter, take always into account the following considerations: [1] Actual station configuration For detailed information on the layout and equipment interconnections refer to the Plant documentation. [2] 1+0 and 1+1 configurations Test bench drawings refer usually to the 1+0 configuration. When necessary, the additional material for 1+1 configurations is drawn in dotted line. [3] Equipment interfaces for test access points, signal meaning and use The standard equipment interfaces for access points are always considered at Station DDF. Station DDF is not detailed in the drawings: refer to your own plant documentation for details. [4] Craft terminal need The WebEML (WebEML) is always required. Line up and Commissioning 3DB18809AAAA Issue 1 937/980

41 7.2 Commissioning of STATION A phase 1 (Turn up) Where necessary, switch OFF the power supply before disconnecting the earth connection. Do not connect instruments directly to the MSS/ODU cable connector since the connector carries DC voltage used to supply the ODU. Do not connect the IDU-ODU cable between MSS and ODU, while the MSS is powered up Turn on preliminary operations ALL THESE OPERATIONS ARE PERFORMED WITH THE POWER OFF The antenna of station A (or B) is pointed towards station B (or A) the best as possible (use compass if necessary). The hardware configuration of the equipment corresponds to the expected one. Make visual inspection for units installation and cabling: The MSS subrack allocation according to the station lay out The MSS subrack and units ground connections The power supply voltage is present with the correct polarity at the MSS power supply input Tributaries are cabled on the station DDF The MSS ODU cables ground kit connections The ODU(s) ground connections (In the case of a non integrated antenna, the antenna and the ODU(s) must be ground connected) The MSS(s) / ODU(s) cables are connected to MSS(s) and ODU(s) The ODU(s) cables connectors waterproofing. 938/980 3DB18809AAAA Issue 1 Line up and Commissioning

42 7.2.2 Powering up the MSS(s) with ODU(s) connected This operation has the following scopes: verify the SWP present both in WebEML and NE make the Central Frequency and Shifter values of ODUs be acquired by MSS (so that they are retained in the NE s data base). Proceed as follows: a) Switch on the MSS by using the circuit breakers b) Connect locally the WebEML to the MSS of the local station and perform the NE login with NEtO. 1) Make a local connection through the Ethernet cable, between the Ethernet port of the PC and the NMS interface on the MSS 2) Power on the PC and wait for its start up 3) Start up the WebEML and wait for the NEtO screen 4) Insert the local IP address of the NE 9500 MPR-E station 5) Start supervision on the local Network Element c) Configure the NE as explained in the Provisioning chapter. Line up and Commissioning 3DB18809AAAA Issue 1 939/980

43 7.3 Commissioning of STATION B phase 1 (Turn up) To commission Station B, perform (at Station B premises) the same operations carried on at Station A Phase 1. For near future tests, establish, on the DDF of Station B, hardware loops on every tributary. 7.4 Fine antenna alignment and preliminary checks Stations A & B Fine antenna alignment When Station A and Station B are fully configured and operational, and assuming that the antenna instation A (or B) has been previously correctly pointed toward the antenna in station B (or A), you should receive some field from station B (or A). Note 1: Verify that the ATPC is disabled. Note 2: In case of 1+1 (with asymmetric coupler) to facilitate the alignment make sure that Channel #1 is active. Now, proceed to a fine tuning of the antenna to improve as much as possible the received level, in both- Station A (at Station A premises) and Station B (at Station B premises). To perform the fine antenna alignment refer to Annex A: fine antenna alignment on page Preliminary checks At first on Station A (at Station A premises), then on Station B (at Station B premises), log in the NE andperform following checks by WebEML: Subject On page Verify ODU(s) alarm status 940 Transmitter power output check 941 Received power measurement Verify ODU300/MPT-HC alarm status Purpose: Required Instruments: Procedure: Verify no abnormal communication alarm between MSS(s) and ODU(s) PC with WebEML software Connect WebEML to MSS. WebEML Views Equipment In the left window, select ODU ch#1n 940/980 3DB18809AAAA Issue 1 Line up and Commissioning

44 In the lower right window, verify in the alarms list for that there is no internal communication failure In the lower right window, verify in the alarms list that there is no TX failure Repeat for Ch#0 if any (1+1) Transmitter power output check Purpose: Required Instruments: Procedure: Verify via WebEML the ODU(s) transmitted power output. PC with WebEML software Connect WebEML to MSS. WebEML Double click on the front panel of the Modem unit (Channel #1) (for ODU300) or on the front panel of the MPT Access peripheral unit or MPT-HC (for MPT-HC) Verify that ATPC is Disabled (If required, change the ATPC status to disable in the ATPC field then Apply) Verify that Tx Power value complies with the suitable value already set (If required, change the Tx Power in the RTPC field then Apply) Repeat for Ch#0 if any (1+1) Received power measurement Purpose: Required Instruments: Procedure: Verify via WebEML the received power to detect any interference PC with WebEML software Connect WebEML to MSS. WebEML Double click on the front panel of the Modem unit (Channel #1) (for ODU300) or on the front panel of the MPT Access peripheral unit or MPT-HC (for MPT-HC) Select Measurements tab panel In the Sample time (sec), write the suitable measurement poling time then press Start Line up and Commissioning 3DB18809AAAA Issue 1 941/980

45 Figure 655. Received power check Pressing Start will prompt a graphic monitoring view of the transmitted and received levels: Figure 656. Power measurements Ticking the box Show Details in the lower left corner will call a summary view of the TX an Rx levels: 942/980 3DB18809AAAA Issue 1 Line up and Commissioning

46 Figure 657. Received power details Verify in the hop calculation (plant documentation) that the calculated received level has been reached. Verify that there are no interferences. Repeat for Ch#0 if any (1+1) WARNING: If in the Tx end field the indication in dbm is +99, the Transmitter is off (or in HSB Configuration thetransmitter is in standby). If in the Tx end field the indication in dbm is +99 and, at the same time, in the relevant Rx end field the information in dbm is 99, probably the supervision has been lost. Line up and Commissioning 3DB18809AAAA Issue 1 943/980

47 7.5 End of commissioning phase 1 (Turn up) in STATION A In Station A, proceed to a final fine alignment of the antenna toward the antenna of Station B. To perform the fine antenna alignment, refer to Annex A: fine antenna alignment on page 971. In Station A, proceed to the remote NE (station B) acquisition (by opening a second NEtO session) in order to verify in both the stations: Received level complies with hop calculation No alarm showing (except unloaded tributaries) 944/980 3DB18809AAAA Issue 1 Line up and Commissioning

48 7.6 Commissioning station A phase 2 (acceptance test) Commissioning phase 2 is a site acceptance test procedure made up of the required tests to ensure that the equipment is fully operational. This phase describes first of all the way to check and to change (if necessary) via the WebEML menu the different configuration parameters already set, for most of them, during the Provisioning followed by various tests. Most of the tests and checks results have to be recorded in the TRS (Test Results Sheet). Operator will be invited to do so each time it is required by the following sentence: Report in the TRS. N.B. The lettered titles in following table [ a ), b ), etc.] correspond to the page s heading titles of the TRS document. Test On page Report in TRS a) Installation and cabling visual inspection 947 Indoor System installation and cabling visual inspection Outdoor System installation and cabling visual inspection b) System configuration 947 Check Software Release Check/set Mode (Presettings or Adaptive modulation), Channel spacing, Modulation Check/set Link Identifier configuration (optional) Check/set the QoS criteria to be used Check/set the Automatic Restoration Criteria (only 1+1) HSB Transmission Protection (1+1 HSB configurations only) Radio Protection (RPS) EPS Protection Check/set Tx/Rx Spacing, Transmission and Reception frequencies Check/set Tx power (ATPC Off) or Tx range and Rx threshold (ATPC On) Check/set the XPIC configuration (if required) Check/set the synchronization Tx and Rx power measurement (with WebEML) IF Loopback functionality (ODU300) Core-facing loopback functionality (MPT-HC/MPT-MC) Line up and Commissioning 3DB18809AAAA Issue 1 945/980

49 Test On page Report in TRS c) P32E1 unit 952 Balanced or Unbalanced impedance Check/set E1 tributaries configuration Protection functionality (1+1 only) E1 point to point loop test d) STM-1 unit 955 Check/set STM-1 configuration Protection functionality (1+1 only) STM-1 point to point loop test e) 16E1/DS1 ASAP unit 958 Check/set E1 layer configuration Check/set IMA layer configuration Check/set ATM layer configuration Check/set ATM PW layer configuration f) EAS unit 959 Check/set EAS unit configuration g) AUX unit 958 Check/set AUX unit configuration Check/set the Housekeeping configuration h) Core-E unit 959 Check the Software Licence Code Check/set Traffic Ethernet port parameters i) NE configuration 959 Check/set the local NE IP address Check/set OSPF Area Configuration Check/set the Ethernet access (OS) configuration Check/set IP static routing configuration j) Data/Time settings 960 k) E1 Hop stability test 960 l) STM-1 Hop stability test 962 m) Ethernet Traffic stability test 964 n) ATM Traffic stability test 968 o) 64 kbit/s Service Channel functionality test (optional) /980 3DB18809AAAA Issue 1 Line up and Commissioning

50 7.6.1 Installation and cabling visual inspection Indoor System installation and cabling visual inspection See and fill the indoor inspection check list in the TRS Outdoor System installation and cabling visual inspection See and fill the indoor inspection check list in the TRS System configuration Purpose: Required Instruments: Procedure: Verify via WebEML the configuration of the Local Station. PC with WebEML software Connect WebEML to MSS Check Software Release WebEML Menu bar Menu SW Download SW Status Check the Software release. Report in the TRS Check/set Mode (Presettings or Adaptive modulation), Channel spacing, Modulation WebEML Double click on the front panel of the Modem unit for ODU300 or of the MPT Access unit or on the MPT-HC/MPT-MC for MPT-HC/MPT-MC Settings tab panel In the left window Mode (Presettings or Adaptive modulation), Channel spacing, Modulation (Supported Modulation Schemes and Switching Threshold, if the Adaptive Modulation has been enabled) If required, change any paramater. Report the parameters in the TRS Check/set Link Identifier configuration (optional) Double click on the front panel of the Modem unit for ODU300 or of the MPT Access unit or on the MPT- HC/MPT-MC for MPT-HC/MPT-MC Link Identifier If it is necessary, change any parameter. Report the Link Identifier status (Enabled or Disabled), and, if Enabled, the Expected and Sent values Check/set the QoS criteria to be used WebEML Menu bar Configuration System Settings Select the suitable QoS criteria to be used: Disabled/802.1p/DiffServ. Report in the TRS. Line up and Commissioning 3DB18809AAAA Issue 1 947/980

51 Check/set the Automatic Restoration Criteria (only 1+1) HSB Transmission Protection (1+1 HSB configurations only) WebEML Views Protection Schemes In the left window HSB Protection In the lower right window Protection Scheme Parameters Tab panel Protection Type 1+1 If required, change Operation type (Revertive or Not Revertive) then Apply Report the Operation Type in the TRS Radio Protection (RPS) WebEML Views Protection Schemes In the left window Rx Radio Protection (RPS) In the lower right window Protection Scheme Parameters Tab panel Protection Type 1+1 If required, change Operation type (Revertive or Not Revertive) then Apply Report the Operation Type in the TRS EPS Protection WebEML Views Protection Schemes In the left window Equipment Protection In the lower right window Protection Scheme Parameters Tab panel Protection Type 1+1 If required, change Operation type (Revertive or Not Revertive) then Apply Report the Operation Type in the TRS Check/set Tx/Rx Spacing, Transmission and Reception frequencies WebEML Double click on the front panel of the Modem unit for ODU300 or of the MPT Access unit or on the MPT-HC/MPT-MC for MPT-HC/MPT-MC In the central window Channel #1 Shifter, Tx frequency Repeat for Channel 0 (only in 1+1) Report the Shifter, Tx and the Rx frequencies in the TRS. If required, change the Tx frequency then Apply. Rx Freq. will be automatically adjusted Check/set Tx power (ATPC Off) or Tx range and Rx threshold (ATPC On) ATPC Disabled: WebEML Double click on the front panel of the Modem unit for ODU300 or of the MPT Access unit or on the MPT-HC/MPT-MC for MPT-HC/MPT-MC Setting tab panel 948/980 3DB18809AAAA Issue 1 Line up and Commissioning

52 RTPC&ATPC field ATPC Disabled Repeat for Channel 0 (only in 1+1) Report the ATPC Disabled status, Tx nominal Power and Tx Power setting into thetrs. ATPC Enabled: WebEML Double click on the front panel of the Modem unit for ODU300 or of the MPT Access unit or on the MPT-HC/MPT-MC for MPT-HC/MPT-MC Setting tab panel RTPC&ATPC field ATPC Enabled Repeat for Channel 0 (only in 1+1) Report the ATPC Enabled status, ATPC Range and ATPC RX Threshold setting in the TRS. If required, change ATPC Mode or ATPC Range or ATPC Rx Threshold then Apply Check/set the XPIC configuration (if required) WebEML Menu Configuration XPIC Configuration Check/set all the parameters regarding the XPIC (refer to paragraph 3.16 on page 441). Report in the TRS Check/set the synchronization WebEML Tab panel Synchronization Check/set all the parameters regarding the synchronization. Report in the TRS Tx and Rx power measurement (with WebEML) Purpose: Required Instruments: Procedure: Verify via WebEML the Transmitted (PTx) and Received (PRx) power. PC with WebEML software Connect WebEML to MSS WebEML Double click on the front panel of the Modem unit for ODU300 or of the MPT Access unit or on the MPT-HC/MPT-MC for MPT-HC/MPT-MC From the left window select Channel #1 select Measurements tab panel In the Sample time (sec), write the suitable measurement poling time then press Start Pressing Start will prompt a graphic monitoring view of the transmitted and received levels. Ticking the box Show details in the lower left corner will call a summary view of the TX an Rx levels. Report the Current Tx Local End (PTx) and the current Rx Local End (PRx) in the TRS. Line up and Commissioning 3DB18809AAAA Issue 1 949/980

53 Loopback functionality IF Loopback functionality (ODU300) Purpose: Required Instruments: Procedure: Verify via WebEML the IF cable loopback functionality (only in the local NE) PC with WebEML software and E1 Data Analyzer Connect WebEML to MSS Connect Pattern Generator/Error Detector analyzer on one Tributary Access (At the Station DDF) A delay up to 10 seconds may be observed for each activation/deactivation. Ensure that the local tributary access is active (unframed and configured). Ensure that the local transmitter is muted (double click on the front panel of the Modem unit Settings tab panel). IF cable loopback Figure 658. IF Cable loopback WebEML Double click on the front panel of the Modem unit Loopback tab panel In the left window IF cable In the lower right window Active Apply Error Detector showing no errors. Loopback showing in the Summary Block Diagram view. To remove the loopback: in the lower right window Not Active Apply Report about the Loopback functionality in the TRS. 950/980 3DB18809AAAA Issue 1 Line up and Commissioning

54 Core-facing loopback functionality (MPT-HC/MPT-MC) Purpose: Required Instruments: Procedure: Verify via WebEML the Core-facing loopback functionality (only in the local NE) PC with WebEML software and E1 Data Analyzer Connect WebEML to MSS Connect Pattern Generator/Error Detector analyzer on one Tributary Access (At the Station DDF) A delay up to 10 seconds may be observed for each activation/deactivation. Ensure that the local tributary access is active (unframed and configured). Figure 659. Core-facing loopback WebEML Double click on the front panel of the MPT-Access unit or on the MPT-HC/MPT-MC Loopback tab panel In the left window Core-facing In the lower right window Active Apply Error Detector showing no errors. Loopback showing in the Summary Block Diagram view. To remove the loopback: in the lower right window Not Active Apply Report about the Loopback functionality in the TRS. Line up and Commissioning 3DB18809AAAA Issue 1 951/980

55 Protection functionality (1+1 only) Purpose: Required Instruments: Procedure: Force command (if the active channel is the Main) and Lockout command (if the active channel is the Spare) PC with WebEML software Connect WebEML to MSS WebEML View Protection Schemes In the left window Rx Radio Protection Main #1 or Spare #0 In the Commands tab panel window Commands scroll list Forced or Lockout Apply Repeat for HSB Tx Protection (for 1+1 HSB configurations only) Repeat for Equipment Protection Check in the Summary block diagram that the full channel (Tx and Rx) path is in service. Report about the Channel protection switching functionality in the TRS P32E1 unit Balanced or Unbalanced impedance WebEML Menu bar Configuration System Settings Set the impedance for the E1 streams. Report the Impedance in the TRS Check/set E1 tributaries configuration WebEML Double click on the front panel of the P32E1DS1 unit In the left window E1 port# 1 In the lower right window Settings Tab panel If it is necessary, change the E1 parameters. Report in the TRS. Repeat for each E1 port# Protection functionality (1+1 only) Purpose: Required Instruments: Procedure: Force command (if the active channel is the Main) and Lockout command (if the active channel is the Spare) PC with WebEML software Connect WebEML to MSS WebEML View Protection Schemes 952/980 3DB18809AAAA Issue 1 Line up and Commissioning

56 In the left window Equipment Protection Main #1 or Spare #0 In the Commands tab panel Forced or Lockout Apply Check in the Summary block diagram that the full channel (TX and RX) path is in service. Report about the Channel protection switching functionality in the TRS E1 point to point loop test Purpose: Required Instruments: Procedure: Verify the point to point Tributaries quality Verify the tributaries alarm status monitoring functionality PC with WebEML software and E1 Data Analyzer Connect WebEML to MSS Connect Pattern Generator/Error Detector on Tributary Access (At the Station DDF) WebEML Diagnosis Summary Block Diagram View Report the result in the TRS. Figure 660. Test bench for tributary functionality check with ODU300 Line up and Commissioning 3DB18809AAAA Issue 1 953/980

57 Figure 661. Test bench for tributary functionality check with MPT-HC/MPT-HC V2/MPT-MC [1] Point to point Tributaries quality test Assuming that all the tributaries have been enabled and configured (Unframed status and configuration) via WebEML in both stations and that every tributary is looped at the DDF in the remote station: Perform one minute of BER test on each E1 tributary Verify that the analyzer detects no error. Verify the tributary alarm status: WebEML Double click on the front panel of the P32E1DS1 unit In the lower right Alarms tab panel, verify that while the data analyzer is connected, the AlarmLossSignal on the relevant tributary is off. Leave the Alarms screen open, to perform following check [2] Check of the tributaries alarm status monitoring functionality To create an alarmed condition, remove the Tributary loopback at the Remote station. In the lower right Alarms, verify that while the data analyzer is connected, the AlarmLossSignal on the relevant tributary goes on. Restore the Tributary loopback at the Remote station, and verify that the AlarmLossSignal on therelevant tributary goes off. 954/980 3DB18809AAAA Issue 1 Line up and Commissioning

58 Figure 662. Tributary alarm status monitoring Report about the Tributary BER test and alarm WebEML monitoring in the TRS STM-1 unit Check/set STM-1 configuration WebEML Double click on the front panel of the SDHACC unit In the left window STM-1 port# 1 In the lower right window Settings Tab panel If it is necessary, change the STM-1 parameters. Report in the TRS. Repeat for each STM-1 port#2 (if any) Protection functionality (1+1 only) Purpose: Required Instruments: Procedure: Force command (if the active channel is the Main) and Lockout command (if the active channel is the Spare) PC with WebEML software Connect WebEML to MSS Line up and Commissioning 3DB18809AAAA Issue 1 955/980

59 WebEML View Protection Schemes In the left window Equipment Protection Main #1 or Spare #0 In the Commands tab panel Forced or Lockout Apply Check in the Summary block diagram that the full channel (TX and RX) path is in service. Report about the Channel protection switching functionality in the TRS STM-1 point to point loop test Purpose: Required Instruments: Procedure: Verify the point to point STM-1 quality Verify the tributaries alarm status monitoring functionality PC with WebEML software and SDH Data Analyzer Connect WebEML to MSS Connect Pattern Generator/Error Detector on STM-1 Access (At the Station DDF) WebEML Diagnosis Summary Block Diagram View Report the result in the TRS. Figure 663. Test bench for tributary functionality check with ODU /980 3DB18809AAAA Issue 1 Line up and Commissioning

60 Figure 664. Test bench for tributary functionality check with MPT-HC/MPT-HC V2/MPT-MC [1] Point to point quality test Assuming that the STM-1 has been enabled and configured via WebEML in both stations and that every STM-1 is looped at the DDF in the remote station: Perform one minute of BER test the STM-1 Verify that the analyzer detects no error. Verify the STM-1 alarm status: WebEML Double click on the front panel of the SDHACC unit In the lower right Alarms tab panel, verify that while the data analyzer is connected, the AlarmLossSignal on the relevant STM-1 is off. Leave the Alarms screen open, to perform following check [2] Check of the alarm status monitoring functionality To create an alarmed condition, remove the Loopback at the Remote station. In the lower right Alarms, verify that while the data analyzer is connected, the AlarmLossSignal on the relevant signal goes on. Restore the Loopback at the Remote station, and verify that the AlarmLossSignal on therelevant STM- 1 goes off. Report about the BER test and alarm WebEML monitoring in the TRS. Line up and Commissioning 3DB18809AAAA Issue 1 957/980

61 E1/DS1 ASAP unit Check/set E1 layer configuration WebEML Double click on the front panel of the 16E1/DS1 ASAP unit To configure refer to par on page 476. Report in the TRS Check/set IMA layer configuration WebEML Double click on the front panel of the 16E1/DS1 ASAP unit To configure refer to par on page 477. Report in the TRS Check/set ATM layer configuration WebEML Double click on the front panel of the 16E1/DS1 ASAP unit To configure refer to par on page 479. Report in the TRS Check/set ATM PW layer configuration WebEML Double click on the front panel of the 16E1/DS1 ASAP unit To configure refer to par on page 485. Report in the TRS AUX unit Check/set AUX unit configuration WebEML Double click on the front panel of the AUX unit To configure refer to par on page 498. Report in the TRS Check/set the Housekeeping configuration WebEML Double click on the front panel of the AUX unit To configure refer to par on page 499. Report in the TRS. 958/980 3DB18809AAAA Issue 1 Line up and Commissioning

62 7.6.7 EAS unit Check/set EAS unit configuration WebEML Double click on the front panel of the EAS unit To configure refer to par on page 424. Report in the TRS Core-E unit Check the Software Licence Code WebEML Menu bar Supervision SW licence Report the Licence string and code in the TRS Check/set Traffic Ethernet port parameters WebEML Double click on the front panel of the Core-E unit In the left window Ethernet Port#1 or Ethernet Port#2 or Ethernet Port#3 or Ethernet Port#4 or Optical SFP Ethernet Port #5. In the lower right window Settings Tab panel If it is necessary, change the parameters. Report in the TRS NE configuration Check/set the local NE IP address WebEML Configuration Network Configuration Local Configuration Report the local IP Address in the TRS Check/set OSPF Area Configuration WebEML Configuration Network Configuration IP Configuration OSPF Area Configuration Report the Id, IP Address, IP Mask and Stub flag in the TRS Check/set the Ethernet access (OS) configuration WebEML Double click on the front panel fo the Core-E unit TMN Interface tab panel Report the IP Address, IP Mask, IP Routing protocol and OSPF Area in the TRS. Line up and Commissioning 3DB18809AAAA Issue 1 959/980

63 Check/set IP static routing configuration WebEML Configuration Network Configuration IP Configuration IP Static Routing Configuration Report the IP Address, IP Mask and Default gateway IP Address or interface type into thetrs Data/Time settings WebEML Menu bar Configuration NE Time Enter the time settings. Report in the TRS. WebEML Menu bar Configuration Network Configuration NTP Server Configuration Enter the IP address of the NTP Server, if any E1 Hop stability test N.B.: this test is in alternative to that described in point d) (performed on one Ethernet port) Purpose: Required Instruments: Procedure: Verify the Hop stability PC with WebEML software and E1 Data Analyzer Connect WebEML to MSS Connect Data analyzer on one Tributary Access (At the Station DDF) The Hop stability test is performed during two consecutive hours, one time, on one Tributary, in realworking condition whatever the protection configuration (1+ 0 or 1+1). The two-hour stability test must be free of error in normal propagation conditions (out of fading period) Via the WebEML, let only one active tributary in both station In the remote Station, place a hardware loop on the relevant tributary access (at the station DDF). In the local station, connect the E1 Data Analyzer on the relevant tributary. Check that the Tributary Alarm Loss disappears. Verify in both stations that there are no active software loopbacks or switching requests. Verify in both stations that none alarm is showing. Report the two-hour error-free of error Hop Stability Test result in the TRS. 960/980 3DB18809AAAA Issue 1 Line up and Commissioning

64 Figure 665. Test bench for hop stability test with ODU300 Figure 666. Test bench for tributary functionality check with MPT-HC/MPT-HC V2/MPT-MC Line up and Commissioning 3DB18809AAAA Issue 1 961/980

65 STM-1 Hop stability test N.B.: this test is in alternative to that described in point d) (performed on one Ethernet port) Purpose: Required Instruments: Procedure: Verify the Hop stability PC with WebEML software and E1 Data Analyzer Connect WebEML to MSS Connect Data analyzer on one Tributary Access (At the Station DDF) The Hop stability test is performed during two consecutive hours, one time, on one STM-1, in realworking condition whatever the protection configuration (1+ 0 or 1+1). The two-hour stability test must be free of error in normal propagation conditions (out of fading period) Via the WebEML, let only one active STM-1 in both station In the remote Station, place a hardware loop on the relevant STM-1 access (at the station DDF). In the local station, connect the SDH Data Analyzer on the relevant tributary. Check that the STM-1 Alarm Loss disappears. Verify in both stations that there are no active software loopbacks or switching requests. Verify in both stations that none alarm is showing. Report the two-hour error-free of error Hop Stability Test result in the TRS. Figure 667. Test bench for hop stability test with ODU /980 3DB18809AAAA Issue 1 Line up and Commissioning

66 Figure 668. Test bench for tributary functionality check with MPT-HC/MPT-HC V2/MPT-MC Line up and Commissioning 3DB18809AAAA Issue 1 963/980

67 Ethernet Traffic stability test Purpose: Required Instruments: Verify the quality of point to point Ethernet Data Channels PC with WebEML software and, in alternative: 1 additional PC and 1 Ethernet cable 2 additional PCs 2 Ethernet Data Analyzers Procedure: a) Connect WebEML to MSS of local station b) Perform the connectivity test on port #1, according to the chosen test bench: Test bench with 1 additional PC and 1 Ethernet cable: see point [1] Test bench with 2 additional PCs: see point [2] Test bench with 2 Ethernet Data Analyzers: see point [3] c) Perform the connectivity test on ports #2, #3, #4 and #5 (if enabled) If required in plant documentation, repeat the connectivity test [step b) above] for the other threeports, with obvious test bench changes on remote station. Report about the connectivity test of Ethernet Data Channels in the TRS. d) Perform the hop stability test 1) Set up the test bench with 2 Ethernet Data Analyzers (point [3]). On both stations, connect the Data analyzer on Ethernet port #1 on the Core-E unit. 2) Start this test after the learning of the MAC address. 3) Configure the pattern A generator, in order to generate continuos traffic, and set the data ratehalf to the radio capacity and with packet size of 1518 bytes. 4) Perform the stability test for 2 hours. 5) Compare the number of TX and Rx Frames on the Pattern A: the number of frames must be equal in normal propagation conditions (out of fading period). Report the two-hour error-free Ethernet Stability Test result in the TRS. 964/980 3DB18809AAAA Issue 1 Line up and Commissioning

68 [1] Test bench with 1 additional PC and 1 Ethernet cable a) Connections On local station, connect the additional PC on Ethernet port #1 (testing port). On remote station, through the Ethernet cable, connect the NMS Ethernet port to the Ethernet port #1 (port to be tested) b) Set Enable, Flow Control disable, and Capability Advertised for ports to test WebEML perform the following operations on each data port (Ethernet ports #1 to #4) of both stations: Enabled Apply Auto Negotiation Status Disabled Apply Flow Control Disabled Apply Capability Advertised 1000 Mb/s Full Apply c) Perform the connectivity test on port #1 1) at local station, on PC connected to Ethernet port #1 (N.B.), ping the remote station (using) the NE s Ethernet Configuration IP address ) with 50 packets with 1000 byte length. N.B.: the PC s IP address and the NE s Ethernet Configuration IP address must belong to the same subnetwork. Windows OS details, if necessary: Start Programs Accessories Command Prompt ping <space> l <space> 1000 <space> n <space> 50 <space> IP Address <enter> 2) the RIGHT LED on the corresponding front panel blinks with cable inserted and traffic running At least 45 packets must pass without any packet loss from the 5th packet Figure 669. Test bench for optional Ethernet Data Channel functionality with 1 additional PC and 1 Ethernet cable Line up and Commissioning 3DB18809AAAA Issue 1 965/980

69 [2] Test bench with 2 additional PCs a) Connections On local station, connect the additional PC on Ethernet port #1 (testing port) On remote station, connect the additional PC on Ethernet port #1 (port to be tested) b) Set Enable, Flow Control disable, and Capability Advertised for ports to test WebEML perform the following operations on each data port (Ethernet ports #1 to #4) of both stations: Enabled Apply Auto Negotiation Status Disabled Apply Flow Control Disabled Apply Capability Advertised 1000 Mb/s Full Apply c) Perform the connectivity test on port #1 1) at local station, on PC connected to Ethernet port #1, ping the far end PC with 50 packets with 1000 byte length. Windows OS details, if necessary: Start Programs Accessories Command Prompt ping <space> l <space> 1000 <space> n <space> 50 <space> IP Address <enter> 2) the RIGHT LED on the corresponding front panel blinks with cable inserted and traffic running. At least 45 packets must pass without any packet loss from the 5th packet. Figure 670. Test bench for optional Ethernet Data Channel functionality with 2 additional PCs 966/980 3DB18809AAAA Issue 1 Line up and Commissioning

70 [3] Test bench with 2 Ethernet Data Analyzers a) Connections On local station, connect the Data analyzer on Ethernet port #1 (testing port) On remote station, connect the Data analyzer on Ethernet port #1 (port to be tested) b) Set Enable, Flow Control disable, and Capability Advertised for ports to test WebEML perform the following operations on each data port (Ethernet ports #1 to #4) of both stations: Enabled Apply Auto Negotiation Status Disabled Apply Flow Control Disabled Apply Capability Advertised 1000 Mb/s Full Apply c) Perform the connectivity test on port #1 1) Start this test after the learning of the MAC address. 2) Configure Pattern Generator A in order to generate 50 packets with 1000 byte length, and set the data rate half of the radio capacity. 3) the RIGHT LED on the corresponding front panel blinks with cable inserted and traffic running. At least 45 packets must pass without any packet loss from the 5th packet. Figure 671. Test bench for optional Ethernet Data Channel functionality with 2 Ethernet Data Analyzers Line up and Commissioning 3DB18809AAAA Issue 1 967/980

71 ATM Traffic stability test Purpose: Required Instruments: Verify the quality of point to point ATM Data Channels (where 16E1/DS1 ASAP unit has been installed) PC with WebEML software and 1 4xE1 ATM/IMA Generator/Analizer Procedure: The Hop stability test is performed during two consecutive hours, one time, on one IMA Group configured on 16E1DS ASAP peripheral, in realworking condition whatever the radio peripheral protection configuration (1+ 0 or 1+1). The two-hour stability test must be free of error (no ATM Cell Loss) in normal propagation conditions (out of fading period) a) Connect WebEML to MSS of local station b) Check IMA connectivity in the local Station: "configure on ATM/IMA instrument a 4xE1 IMA Group with MPR default configuration values "activate the IMA Group of ATM/IMA instrument: it will result in "Not Operational" state since no connection to MSS and IMA configuration has been yet performed "connect E1 ports of ATM/IMA instrument to DDF connection points corresponding to E1 ports #1,#2,#3,#4 of relevant ASAP peripheral on MSS, enable E1 ports #1,#2,#3,#4 of relevant 16E1DS1 ASAP peripheral by configuring as Framed their Signal Mode without change to default configuration values, activate ATM interface #1 associated to IMA Group #1 of relevant ASAP peripheral associate to IMA Group #1 of relevant ASAP peripheral and make active as IMA Links the E1 ports #1,#2,#3,#4 activate ATM interface #1,associated to IMA Group #1 of relevant ASAP peripheral the IMA Group #1 of relevant ASAP peripheral and the one in the ATM/IMA instrument shall become "Operational" ("TSF" alarm should be cleared, if previously raised) c) Perform the IMA connectivity test for all E1 ports of relevant ASAP peripheral(s) Repeat the IMA connectivity test [step b) above] for the other E1 ports, with the below association associate to IMA Group #2 of relevant ASAP peripheral the E1 ports #5,#6,#7,#8 associate to IMA Group #3 of relevant ASAP peripheral the E1 ports #9,#10,#11,#12 associate to IMA Group #4 of relevant ASAP peripheral the E1 ports #13,#14,#15,#16 Report about the IMA connectivity test of ATM Data Channels in the TRS. d) Configure ATM traffic in the local Station On ATM interface #1 (associated to IMA Group #1) of relevant ASAP peripheral create and configure: 968/980 3DB18809AAAA Issue 1 Line up and Commissioning

72 "one ATM Traffic Descriptor for an ATM Circuit of type CBR, PCR=17960 cell/s, CDVT=1000 microsecond, ATM Policing Enabled "one VP of "Not Logical" type, with VPI=1 and associate the above ATM TD (both for Ingress/Egress) On PW Layer of relevant ASAP peripheral create one ATM PW flow associated to the above VP, with PW Label = 100, 1 cell max per frame and 1 millisecond timeout (no VPI translation) On PW Layer of relevant ASAP peripheral create one ATM PW flow associated to the above VP, with PW Label = 100, 1 cell max per frame and 1 millisecond timeout (no VPI translation) Configure the cross-connection of the above ATM PW flow towards the relevant radio peripheral, with associated VLAN ID = 4000 e) Configure in the remote Station a Loopback at DDF level, as shown in Figure 672. f) Configure and start in the local Station the ATM Generator/Analizer Configure, ATM Generator of ATM/IMA instrument for one ATM Cell stream, with rate cell/s, VPI=1, VCI=1 (if the ATM Generator has this capability, use test pattern inside ATM Cells to detect Cell Loss), without starting traffic Start ATM Analyzer Start ATM Generator Check the same rate of ATM Cell of configured ATM Circuit is transmitted by ATM Generator is also received by the ATM Analyzer (since ATM Traffic is looped-back by the remote Station); if random pattern is available on ATM/IMA instrument, directly check on ATM Analyzer that no cell is actually lost Report the two-hour error-free ATM Stability Test result in the TRS. Figure 672. Test bench for ATM traffic Line up and Commissioning 3DB18809AAAA Issue 1 969/980

73 kbit/s Service Channel functionality test (optional) Purpose: Required Instruments: Procedure: Verify the point to point Service Data Channel quality PC with WebEML software and RS422 / V11 64 Kbit/s Data Analyzer Connect WebEML to MSS Define the operational ESC ports (Enable/Disable) (local and remote NE). Cross-connect the configured ports to the appropriate radio channel (local and remote). Connect Data analyzer on the service channel Access Figure 673. Test bench for 64 kbit/s Service Channel functionality check Assuming that the User service Channel is looped in the remote station: Perform 10 minutes of BER test. Verify that the Data analyzer detects no error. Report about the 64 Kbit/s Data channel BER test into the TRS. 970/980 3DB18809AAAA Issue 1 Line up and Commissioning

74 7.7 Commissioning station B Phase 2 (acceptance Test) Repeat in Station B all the tests performed in Station A except the Hop Stability Test that has to be run only one time for the full hop. Fill a second Test Result Sheet for Station B END OF COMMISSIONING ACCEPTANCE TEST 7.8 Final operations Complete the commissioning of each NE, creating the NE operator profiles and saving its data. 7.9 Annex A: fine antenna alignment Safety requirements for workers on antenna pole, and microwave radiations (EMF norms) SAFETY RULES When operating on the antenna pole, strictly follow cautions. In particular, if ODU is powered on from MSS, do not stand on the antenna axis and beaware of the compliance boundaries. Antenna pre pointing should have been done during equipment hardware installation. This annex explains how to carry out the antenna fine alignment. To monitor the received level during alignment in the local station: use the ODU Rx power monitoring in addition to a voltmeter, or, after having logged in the NE, use the WebEML received power measurement facility Alignment procedure using the ODU Rx power monitoring a) the radio link must be up and the ATPC disabled b) in general, fine alignment should be done only on one station of the radio link c) connect a voltmeter to the ODU (by using the Light Serfice kit cable for the MPT) d) proceed with Vertical alignment, then with Horizontal alignment e) in configurations with two antennas, repeat the procedure for the second antenna. Note Procedures for Vertical and Horizontal alignment depend on the type of integrated polemounting employed. Line up and Commissioning 3DB18809AAAA Issue 1 971/980

Configuration/Alarm HS 1+1 FD. ODU Card Fail Major Minor Minor ODU failed Replace ODU

Configuration/Alarm HS 1+1 FD. ODU Card Fail Major Minor Minor ODU failed Replace ODU Configuration/Alarm Equipment Alarm Description 1+0 1+1 HS 1+1 FD Most Probable Cause Action ODU Card Fail Major Minor Minor ODU failed Replace ODU Equipment Mismatch Major Minor Minor ODU does not match

More information

Software Status Detail. [6] Click the Yes button to begin the download process.

Software Status Detail. [6] Click the Yes button to begin the download process. [6] Click the Yes button to begin the download process. Note: The complete SWP of 3.1.0 is made up of two packages: SWP 3.1.0 to upgrade from Rel. 2.1ICS2 to Rel. 3.1.0 SWP 3.1.0 to upgrade from Rel. 3.0.0

More information

9500 MPR. Indoor: MSS-8/MSS-4 + Outdoor: ODU300 / MPT-HC / MPT- HC V2 / MPT-MC. User Manual. Rel. 3.1

9500 MPR. Indoor: MSS-8/MSS-4 + Outdoor: ODU300 / MPT-HC / MPT- HC V2 / MPT-MC. User Manual. Rel. 3.1 9500 MPR Indoor: MSS-8/MSS-4 + Outdoor: ODU300 / MPT-HC / MPT- HC V2 / MPT-MC Rel. 3.1 3DB18809AAAA Issue 1 May 2011 Alcatel, Lucent, Alcatel-Lucent and the Alcatel-Lucent logo are trademarks of Alcatel-Lucent.

More information

CE Ethernet Operation

CE Ethernet Operation 25 CHAPTER Note The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms do not refer to using Cisco ONS 15xxx products in a unidirectional path switched ring

More information

Network Topologies & Error Performance Monitoring in SDH Technology

Network Topologies & Error Performance Monitoring in SDH Technology Network Topologies & Error Performance Monitoring in SDH Technology Shiva Sharma Electronics and Communications Department Dronacharya College of Engineering Gurgaon, Haryana Shiva.92@hotmail.com Abstract

More information

Manage Circuits. Before You Begin CHAPTER. This chapter explains how to manage Cisco ONS SDH electrical, optical and Ethernet circuits.

Manage Circuits. Before You Begin CHAPTER. This chapter explains how to manage Cisco ONS SDH electrical, optical and Ethernet circuits. CHAPTER 9 This chapter explains how to manage Cisco ONS 15454 SDH electrical, optical and Ethernet circuits. Before You Begin To create circuits, see Chapter 6, Create Circuits and Low-Order Tunnels. To

More information

Troubleshooting Physical Layer Alarms on SONET and SDH Links

Troubleshooting Physical Layer Alarms on SONET and SDH Links Troubleshooting Physical Layer Alarms on SONET and SDH Links Document ID: 16154 Introduction Prerequisites Requirements Components Used Conventions Alarms at SONET's Layers Alarm Indicators Troubleshooting

More information

SDH Principle. Copyright 2012 Huawei Technologies Co., Ltd. All rights reserved.

SDH Principle.   Copyright 2012 Huawei Technologies Co., Ltd. All rights reserved. SDH Principle www.huawei.com Objectives Upon completion of this course, you will be able to: Understand the basic of SDH multiplexing standard Know the features, applications and advantages of SDH based

More information

Table of Contents 1 E-CPOS Interface Configuration 1-1

Table of Contents 1 E-CPOS Interface Configuration 1-1 Table of Contents 1 E-CPOS Interface Configuration 1-1 Overview 1-1 SONET 1-1 SDH 1-1 E-CPOS 1-5 Configuring an E-CPOS Interface 1-6 Configuring an E-CPOS Interface 1-6 Configuring the Operating Mode of

More information

CMA 3000, all-in-one field tester SDH test options

CMA 3000, all-in-one field tester SDH test options CMA 3000, all-in-one field tester SDH test options KEY FEATURES Simultaneous bidirectional monitoring of SDH lines Powerful testing of SDH systems and embedded PDH systems Mapping and demapping Comprehensive

More information

General information on the radio performance monitoring process

General information on the radio performance monitoring process 3.21.9 RADIO PMs 3.21.9.1 General information on the radio performance monitoring process The performance monitoring (PM) gives indication on the quality of the service and the levels of the Tx power and

More information

Create Circuits. Before You Begin CHAPTER

Create Circuits. Before You Begin CHAPTER 6 CHAPTER Create Circuits This chapter explains how to create Cisco ONS 15600 SDH circuits and tunnels. For additional information, refer to the Circuits and Tunnels chapter in the Cisco ONS 15600 SDH

More information

LIM Configuration Menu

LIM Configuration Menu CHAPTER 7 This chapter deals with configura tion of LIM devices. It is organized as follows:, page 7-1 LIM Maintenance, page 7-4 LIM Alarms, page 7-7 SONET/SDH, page 7-7 SONET Maintenance, page 7-13 DSX1,

More information

Monitoring DWDM Properties

Monitoring DWDM Properties 15 CHAPTER The Cisco IP over dense wavelength division multiplexing (IPoDWDM) solution enables the convergence of the IP and DWDM core networks of the service providers. It increases service flexibility,

More information

Circuits and Tunnels CHAPTER

Circuits and Tunnels CHAPTER CHAPTER 7 Circuits and Tunnels This chapter explains Cisco ONS 15600 SDH high-order circuits, data communications channel (DCC), and IP-encapsulated tunnels. To provision circuits and tunnels, refer to

More information

Configuring Performance Monitoring, RMON, OTN, and Port Provisioning

Configuring Performance Monitoring, RMON, OTN, and Port Provisioning Configuring Performance Monitoring, RMON, OTN, and Port Provisioning This chapter describes performance monitoring, RMON, and OTN, port provisioning and the configuration procedures. Understanding Performance

More information

Alcatel-Lucent MICROWAVE PACKET RADIO for ANSI and ETSI RELEASE MPR-e and MSS-1c User Manual 3DB19901EFAA Edition 01

Alcatel-Lucent MICROWAVE PACKET RADIO for ANSI and ETSI RELEASE MPR-e and MSS-1c User Manual 3DB19901EFAA Edition 01 MPR-e and MSS-1c User Manual3DB19901EFAA Edition 01 Alcatel-Lucent 9500 MICROWAVE PACKET RADIO for ANSI and ETSI RELEASE 5.2.0 MPR-e and MSS-1c User Manual 3DB19901EFAA Edition 01 Alcatel-Lucent Proprietary

More information

ALCATEL-LUCENT 9500 MICROWAVE PACKET RADIO RELEASE 3 ANSI

ALCATEL-LUCENT 9500 MICROWAVE PACKET RADIO RELEASE 3 ANSI ALCATEL-LUCENT 9500 MICROWAVE PACKET RELEASE 3 ANSI The Alcatel-Lucent 9500 Microwave Packet Radio (MPR) addresses all microwave applications with a single product family for all traffic (TDM/IP/hybrid)

More information

Differences Between SONET and SDH Framing in Optical Networks

Differences Between SONET and SDH Framing in Optical Networks Differences Between SONET and SDH Framing in Optical Networks Document ID: 16180 Contents Introduction Prerequisites Requirements Components Used Conventions SONET and SDH Framing ATM Over SONET Packet

More information

Installing ONS SDH OC3 IR 4/STM1 SH 1310 Cards

Installing ONS SDH OC3 IR 4/STM1 SH 1310 Cards Installing ONS 15454 SDH OC3 IR 4/STM1 SH 1310 Cards Product Name: 15454E-S1.1-4= This document contains a description of OC3 IR 4/STM1 SH 1310 card features, installation procedures, removal instructions,

More information

Giga Orion DATASHEET. DS-1025-E 1 of 5

Giga Orion DATASHEET. DS-1025-E 1 of 5 DS-1025-E 1 of 5 Giga Orion Overview The Giga Orion is an ultra-high performance split architecture point-to-point wireless microwave system designed for carrier, enterprise, service provider, and government

More information

OPCOM STM-1 High Capacity Terminal Multiplexer USER MANUAL. Raisecom Technology Co., Ltd (4/2005)

OPCOM STM-1 High Capacity Terminal Multiplexer USER MANUAL. Raisecom Technology Co., Ltd (4/2005) OPCOM3100-155 STM-1 High Capacity Terminal Multiplexer USER MANUAL Raisecom Technology Co., Ltd (4/2005) 1. Cautions Please read the following notices carefully before installing and using the device,

More information

Configuring SDH on 1-Port OC-192/STM-64 or 8-Port OC-3/12/48/STM-1/-4/-16 Module

Configuring SDH on 1-Port OC-192/STM-64 or 8-Port OC-3/12/48/STM-1/-4/-16 Module Configuring SDH on 1-Port OC-192/STM-64 or 8-Port OC-3/12/48/STM-1/-4/-16 Module SDH is a standard that defines optical signals as well as a synchronous frame structure for multiplexed digital traffic.

More information

Cisco Series Router Alarms and Error Messages

Cisco Series Router Alarms and Error Messages CHAPTER 5 Cisco 10000 Series Router Alarms and Error Messages This chapter describes the alarms and error messages that can be raised on the Cisco 10000 series router. The Cisco 10000 series router interface,

More information

NSP Network Services Platform Network Functions Manager - Packet (NFM-P) 9500 MPTBWA Version Guide

NSP Network Services Platform Network Functions Manager - Packet (NFM-P) 9500 MPTBWA Version Guide NSP Network Services Platform Network Functions Manager - Packet () 9500 MPTBWA Version 3.1.0 Guide 3HE-13301-AAAA-TQZZA Legal notice Nokia is a registered trademark of Nokia Corporation. Other products

More information

Performance Monitoring

Performance Monitoring CHAPTER 15 The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms do not refer to using Cisco ONS 15xxx products in a unidirectional path switched ring configuration.

More information

Future Orient High Capacity Nodal Equipment

Future Orient High Capacity Nodal Equipment F Future Orient High Capacity Nodal Equipment ZTE Microwave NR8250 Equipment Introduction 1. Based on the SDR Platform ZTE s unified SDR-based hybrid microwave radio system NR8250 can be deployed for 2G/3G/LTE

More information

General Troubleshooting

General Troubleshooting CHAPTER 1 The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms do not refer to using Cisco ONS 15xxx products in a unidirectional path switched ring configuration.

More information

STI 25 Edition 1/May 2002

STI 25 Edition 1/May 2002 STI 25 Edition 1/May 2002 Interface technical specifications for France Telecom s network As required by Directive 1999/5/EC Numeris Multisite Service (NMS) access interface characteristics Summary: This

More information

Telecom Point to Point Radio

Telecom Point to Point Radio RADTR-P2P-6-38-IP170MB-a9 Telecom Point to Point Radio PDH 4-16E1s/E3 and/or Ethernet up to 170Mbps 6-38GHz Applications Ethernet IP Cellular Backhaul TDM/PDH/IP Radio Networks Trunking or Access Networks

More information

Alcatel-Lucent 5620 SERVICE AWARE MANAGER MPR USER GUIDE R7 December HE AAAG TQZZA Edition 01

Alcatel-Lucent 5620 SERVICE AWARE MANAGER MPR USER GUIDE R7 December HE AAAG TQZZA Edition 01 MPR USER GUIDE 12.0 R7 December 2014 3HE 08850 AAAG TQZZA Edition 01 Alcatel-Lucent 5620 SERVICE AWARE MANAGER MPR USER GUIDE Alcatel-Lucent Proprietary This document contains proprietary information of

More information

DLPs A100 to A199. DLP-A111 Changing the Maximum Number of Session Entries for Alarm History CHAPTER

DLPs A100 to A199. DLP-A111 Changing the Maximum Number of Session Entries for Alarm History CHAPTER 18 CHAPTER DLPs A100 to A199 DLP-A111 Changing the Maximum Number of Session Entries for Alarm History This task changes the maximum number of session entries included in the alarm history. Use this task

More information

Displaying Overhead Bytes

Displaying Overhead Bytes Victoria Combo enables you to view Overhead Bytes of STM-16/OC-48 and STM-64/OC-192 traffic. This is particularly useful in fault-finding on a network. This Application Note describes how to display overhead

More information

RADview-EMS/NGN Element Management System for NGN Applications ACE-3100, ACE-3200

RADview-EMS/NGN Element Management System for NGN Applications ACE-3100, ACE-3200 RADview-EMS/NGN Element Management System for NGN Applications ACE-3100, ACE-3200 1994 2008 RAD Data Communications Publication 05/08 Contents Chapter 1. Introduction 1.1 ACE-3100, ACE-3200 Overview...

More information

Ethernet Operation Any Service Any Port Card Application CHAPTER

Ethernet Operation Any Service Any Port Card Application CHAPTER 10 CHAPTER Operation This chapter describes the operation of the Cisco ONS 15600 SDH ASAP card. For card specifications, refer to Appendix A, Hardware Specifications. For step-by-step card circuit configuration

More information

Technical Committee. M4 Interface Requirments and Logical MIB. af-nm

Technical Committee. M4 Interface Requirments and Logical MIB. af-nm Technical Committee M4 Interface Requirments and Logical MIB October 1994 (C) 1994 The ATM Forum. All Rights Reserved. Limited reproduction of this specification is authorized for internal use only by

More information

NSP Network Services Platform Network Functions Manager - Packet (NFM-P) 9500 MPTSUB6 Driver Version Guide

NSP Network Services Platform Network Functions Manager - Packet (NFM-P) 9500 MPTSUB6 Driver Version Guide NSP Network Services Platform Network Functions Manager - Packet (NFM-P) 9500 MPTSUB6 Driver Version 3.2.0 Guide 3HE-13356-AAAB-TQZZA NFM-P Legal notice Nokia is a registered trademark of Nokia Corporation.

More information

Configuring Dense Wavelength Division Multiplexing Controllers

Configuring Dense Wavelength Division Multiplexing Controllers Configuring Dense Wavelength Division Multiplexing Controllers This module describes the configuration of dense wavelength division multiplexing (DWDM) controllers. DWDM is an optical technology that is

More information

Performance Monitoring

Performance Monitoring CHAPTER 15 Performance monitoring (PM) parameters are used by service providers to gather, store, set thresholds, and report performance data for early detection of problems. In this chapter, PM parameters

More information

Interface Configuration

Interface Configuration CHAPTER 7 You can configure or set up any interface through interface configuration windows, which are associated with each particular line card. This chapter contains the following information: Generic

More information

DRS/FI. Digital Radio System/Full Indoor (Hybrid) Frequency Range from 4 to 11GHz HIGH CAPACITY MW SYSTEMS. System Features

DRS/FI. Digital Radio System/Full Indoor (Hybrid) Frequency Range from 4 to 11GHz HIGH CAPACITY MW SYSTEMS. System Features HIGH CAPACITY MW SYSTEMS DRS/FI Digital Radio System/Full Indoor (Hybrid) Frequency Range from 4 to 11GHz System Features > SDIDU In 1+0 Configuration > SDIDU In 1+1 Configuration > VHP 1+0 Configurations

More information

ANT-20SE Advanced Network Tester ANT-20 NEXT Network Expert Test Software

ANT-20SE Advanced Network Tester ANT-20 NEXT Network Expert Test Software ANT-20SE Advanced Network Tester ANT-20 NEXT Network Expert Test Software BN 3035/95.40 Software Version 2.00 Operating Manual 9 BN 3060/98.38 Please direct all enquiries to your local Wavetek Wandel Goltermann

More information

Single-router APS for the Cisco Series Router

Single-router APS for the Cisco Series Router Single-router APS for the Cisco 12000 Series Router This feature provides 1+1 single-router automatic protection switching (SR-APS) for the Cisco 12000 series ISE ATM line cards (Engine 3) installed in

More information

OmniBER OTN 10 Gb/s communications performance analyzer. Product note. The key to (10G) line card testing G.709

OmniBER OTN 10 Gb/s communications performance analyzer. Product note. The key to (10G) line card testing G.709 OmniBER OTN 10 Gb/s communications performance analyzer Product note The key to (10G) line card testing G.709 The growing demand for bandwidth in the network has encouraged service providers to install

More information

Tandem connection monitoring

Tandem connection monitoring Tandem connection monitoring Product note For point-to-point SDH transmission, user data may be routed and carried by a number of network operators working in tandem to its final destination. In such situations,

More information

5620 SAM SERVICE AWARE MANAGER 14.0 R3. MPR User Guide

5620 SAM SERVICE AWARE MANAGER 14.0 R3. MPR User Guide 5620 SAM SERVICE AWARE MANAGER 14.0 R3 MPR User Guide 3HE-10693-AAAB-TQZZA June 2016 5620 SAM Legal notice Nokia is a registered trademark of Nokia Corporation. Other products and company names mentioned

More information

TrangoLINK GigaPlus. Software v1.3.3 Release Notes & Upgrade Instructions. 16 December 2011

TrangoLINK GigaPlus. Software v1.3.3 Release Notes & Upgrade Instructions. 16 December 2011 Software v1.3.3 Release Notes & Upgrade Instructions 16 December 2011 2010-2011 Trango Systems, Inc. All rights reserved. Page 1 of 13 v1.3.3 Release The release consists of the following software images

More information

RADview. Element Management System Optimux-4E1, Optimux-4T1 Optimux-4E1L, Optimux-4T1L RAD Data Communications Publication 07/05

RADview. Element Management System Optimux-4E1, Optimux-4T1 Optimux-4E1L, Optimux-4T1L RAD Data Communications Publication 07/05 RADview Element Management System Optimux-4E1, Optimux-4T1 Optimux-4E1L, Optimux-4T1L 1994 2005 RAD Data Communications Publication 07/05 Contents Chapter 1. Introduction 1.1 Overview... 1-1 General...1-1

More information

CCIE SP Operations Written Exam v1.0

CCIE SP Operations Written Exam v1.0 Cisco 350-060 CCIE SP Operations Written Exam v1.0 Version: 5.0 QUESTION NO: 1 DRAG DROP Cisco 350-060 Exam Answer: Critical Section Loss of Signal (SLOS) Critical Section Loss of Frame (SLOF) Major Alarm

More information

Alcatel-Lucent 9500 Microwave Packet Radio (ETSI Markets)

Alcatel-Lucent 9500 Microwave Packet Radio (ETSI Markets) Alcatel-Lucent 9500 Microwave Packet Radio (ETSI Markets) The Alcatel-Lucent 9500 Microwave Packet Radio (MPR) provides cost-effective IP transformation for seamless microwave transport of TDM, ATM, IP

More information

learntelecoms interactive e-learning suite of courses: SyncNet v6 SDH-based broadband networks SyncNet

learntelecoms interactive e-learning suite of courses: SyncNet v6 SDH-based broadband networks SyncNet Tel: 0845 0949 120 Email: info@ptt.co.uk Web site: www.ptt.co.uk SyncNet SyncNet v6 SDH-based broadband networks SyncNet is a suite of interactive, multimedia e-learning courses. provides training in the

More information

Alcatel-Lucent 5620 SERVICE AWARE MANAGER. Release 13.0 R2 May HE AAAB TQZZA Edition 01 MPR USER GUIDE

Alcatel-Lucent 5620 SERVICE AWARE MANAGER. Release 13.0 R2 May HE AAAB TQZZA Edition 01 MPR USER GUIDE MPR USER GUIDE Release 13.0 R2 May 2015 3HE 09803 AAAB TQZZA Edition 01 Alcatel-Lucent 5620 SERVICE AWARE MANAGER MPR USER GUIDE Alcatel-Lucent Proprietary This document contains proprietary information

More information

ITU-T G.774. Synchronous digital hierarchy (SDH) Management information model for the network element view

ITU-T G.774. Synchronous digital hierarchy (SDH) Management information model for the network element view INTERNATIONAL TELECOMMUNICATION UNION ITU-T G.774 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (02/2001) SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Digital terminal equipments

More information

RC702-FX Ethernet over SDH User Manual

RC702-FX Ethernet over SDH User Manual RC702-FX Ethernet over SDH User Manual Raisecom Technology Co., Ltd 1. Caution Please carefully read the following precautions before installing and deploying RC702-FX equipment, and operate strictly according

More information

HP 6600/HSR6600 Routers

HP 6600/HSR6600 Routers HP 6600/HSR6600 Routers Interface Configuration Guide Part number: 5998-1499 Software version: A6602-CMW520-R3103 A6600-CMW520-R3102-RPE A6600-CMW520-R3102-RSE HSR6602_MCP-CMW520-R3102 Document version:

More information

Create Circuits. Before You Begin CHAPTER

Create Circuits. Before You Begin CHAPTER CHAPTER 6 Create Circuits The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms do not refer to using Cisco ONS 15xxx products in a unidirectional path switched

More information

Create Circuits and Low-Order Tunnels

Create Circuits and Low-Order Tunnels CHAPTER 6 Create Circuits and Low-Order Tunnels The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms do not refer to using Cisco ONS 15xxx products in a

More information

Practical NewGen Measurements with ONT-503/ONT-506/ONT-512

Practical NewGen Measurements with ONT-503/ONT-506/ONT-512 Application Note Practical NewGen Measurements with ONT-503/ONT-506/ONT-512 Practical NewGen measurements To evaluate NewGen network elements it is essential to test all particular technologies, which

More information

RADview-EMS/NGN. Element Management System for NGN Applications ACE-201/ RAD Data Communications Publication 06/07

RADview-EMS/NGN. Element Management System for NGN Applications ACE-201/ RAD Data Communications Publication 06/07 RADview-EMS/NGN Element Management System for NGN Applications ACE-201/622 1994 2007 RAD Data Communications Publication 06/07 Contents Chapter 1. Introduction 1.1 ACE-201/622 Overview...1-1 1.2 RADview-EMS/NGN

More information

This specification this document to get an official version of this User Network Interface Specification

This specification this document to get an official version of this User Network Interface Specification This specification describes the situation of the Proximus network and services. It will be subject to modifications for corrections or when the network or the services will be modified. Please take into

More information

Product Overview. Switch Models CHAPTER

Product Overview. Switch Models CHAPTER CHAPTER 1 The Cisco CGS 2520 switches, also referred to as the switch, are Ethernet switches that you can connect devices such as Intelligent Electronic Devices (IEDs), distributed controllers, substation

More information

SONET Testing and Maintenance

SONET Testing and Maintenance a step ahead Application Series SONET Testing and Maintenance 302 Enzo Drive San Jose CA 95138 USA ph 1 408 363 8000 fax 1 408 363 8313 info@sunrisetelecom.com www.sunrisetelecom.com Publication Number

More information

MANUAL. Monitoring & Control. Antenna Deicing Controller HDCU

MANUAL. Monitoring & Control. Antenna Deicing Controller HDCU MANUAL_HDCU_en.doc Page 1 of 25 MANUAL for Monitoring & Control Antenna Deicing Controller HDCU MANUAL_HDCU_en.doc Page 2 of 25 CE Declaration of Conformity MANUFACTURER MODEL NUMBER DESCRIPTION Hiltron

More information

NGN - SYNCHRONOUS DIGITAL HIERARCHY

NGN - SYNCHRONOUS DIGITAL HIERARCHY NGN - SYNCHRONOUS DIGITAL HIERARCHY http://www.tutorialspoint.com/ngn/ngn_synchronous_digital_hierarchy.htm Copyright tutorialspoint.com SDH Networks replaced PDH and had several key advantages. G.707,

More information

Create Circuits and Low-Order Tunnels

Create Circuits and Low-Order Tunnels 6 CHAPTER Note The terms "Unidirectional Path Switched Ring" and "UPSR" may appear in Cisco literature. These terms do not refer to using Cisco ONS 15xxx products in a unidirectional path switched ring

More information

This is an inspection failure, not meeting the requirement of >10k Ohm between either PD battery post and chassis.

This is an inspection failure, not meeting the requirement of >10k Ohm between either PD battery post and chassis. Troubleshooting This is a document put together by CSA Laura Rhodes that contains a lot of information about troubleshooting steps for a lot of common control system problems encountered at events. No

More information

Catalyst 2960-X and 2960-XR Switch Hardware Guide

Catalyst 2960-X and 2960-XR Switch Hardware Guide 2960-X and 2960-XR Switch Hardware Guide The 2960-X and 2960-XRfamily of switches are Ethernet switches to which you can connect devices such as Cisco IP Phones, Cisco Wireless Access Points, workstations,

More information

Troubleshooting. Diagnosing Problems

Troubleshooting. Diagnosing Problems Troubleshooting 8 This chapter explains how you can troubleshoot a specific problem at system power-up, such as abnormal LED activity or no system power. Topic Page Diagnosing Problems 8-1 Troubleshooting

More information

Smart IDU. Digital Microwave Radio SM Sygnus SHC. User s Manual

Smart IDU. Digital Microwave Radio SM Sygnus SHC. User s Manual Smart IDU Digital Microwave Radio SM Sygnus SHC User s Manual 1 CONTENTS Section Page 1 CONTENTS... 2 2 INTRODUCTION... 3 3 INSTALLATION... 4 3.1 PACKING LIST... 4 4 CONFIGURATION... 10 4.1 FUNCTIONAL

More information

SMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015)

SMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015) SMM Series 3G and GSM Modems Quick Start Guide Document Number: 0013-001-000272 () Documentation Control Generation Date: October 20, 2015 Cybertec Pty Limited All rights Reserved. No part of this publication

More information

Using Operator Interfaces to Optimize Performance of Industrial Wireless Networks

Using Operator Interfaces to Optimize Performance of Industrial Wireless Networks Using Operator Interfaces to Optimize Performance of Industrial Wireless Networks Jim Ralston, Wireless Sales Engineer ProSoft Technology, August 2007 Abstract The performance of wireless networks can

More information

Hitless Failover and Hitless Upgrade User Guide

Hitless Failover and Hitless Upgrade User Guide Hitless Failover and Hitless Upgrade User Guide This guide describes hitless failover and hitless upgrade, including: Causes and Behaviors of MSM Failover on page 1 Summary of Supported Features on page

More information

Managing Switch Stacks

Managing Switch Stacks Finding Feature Information, page 1 Prerequisites for Switch Stacks, page 1 Restrictions for Switch Stacks, page 2 Information About Switch Stacks, page 2 How to Configure a Switch Stack, page 14 Troubleshooting

More information

PEM Faults and Blower Failures

PEM Faults and Blower Failures CHAPTER 2 The following sections provide methods for troubleshooting faults involving the Cisco 10000 series router Power Entry Modules (PEMs) and blower modules. This chapter contains the following major

More information

Cisco 2-Port, 4-Port, and 8-Port OC-12c/STM-4 Packet over SONET Shared Port Adapters

Cisco 2-Port, 4-Port, and 8-Port OC-12c/STM-4 Packet over SONET Shared Port Adapters Cisco 2-Port, 4-Port, and 8-Port OC-12c/STM-4 Packet over SONET Shared Port Adapters The Cisco I-Flex design combines shared port adapters (SPAs) and SPA interface processors (SIPs), using an extensible

More information

Cisco 2-Port and 4-Port OC-3c/STM-1c POS Shared Port Adapters

Cisco 2-Port and 4-Port OC-3c/STM-1c POS Shared Port Adapters Cisco 2-Port and 4-Port OC-3c/STM-1c POS Shared Port Adapters The Cisco I-Flex approach combines shared port adapters (SPAs) and SPA interface processors (SIPs), providing an extensible design that enables

More information

Administrative and Service States

Administrative and Service States APPENDIXB Administrative and Service States This appendix describes the administrative and service states for Cisco ONS 15454 SDH cards, ports, and cross-connects. For circuit state information, see Chapter

More information

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS

MAINTENANCE MANUAL. EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS MAINTENANCE MANUAL EDACS REDUNDANT POWER SUPPLY SYSTEM 350A1441P1 and P2 POWER MODULE CHASSIS 350A1441P3, P4, AND P5 POWER MODULES TABLE OF CONTENTS SPECIFICATIONS*... 2 INTRODUCTION... 3 DESCRIPTION...

More information

Access Circuit Redundancy Support for IMA

Access Circuit Redundancy Support for IMA The Access Circuit Redundancy Support (ACR) for Inverse Multiplexing over ATM (IMA) feature provides a converged IP or Multiprotocol Label Switching (MPLS) access network for its mobile users that use

More information

Synchronous Ethernet (SyncE) ESMC and SSM

Synchronous Ethernet (SyncE) ESMC and SSM This module describes Synchronization Status Message (SSM), Ethernet Synchronization Message Channel (ESMC), and generating the Simple Network Management Protocol (SNMP) traps on the SyncE feature. With

More information

Software Update C.09.xx Release Notes for the HP Procurve Switches 1600M, 2400M, 2424M, 4000M, and 8000M

Software Update C.09.xx Release Notes for the HP Procurve Switches 1600M, 2400M, 2424M, 4000M, and 8000M Software Update C.09.xx Release Notes for the HP Procurve Switches 1600M, 2400M, 2424M, 4000M, and 8000M Topics: TACACS+ Authentication for Centralized Control of Switch Access Security (page 7) CDP (page

More information

Turn Up a Node. Before You Begin CHAPTER

Turn Up a Node. Before You Begin CHAPTER CHAPTER 4 Turn Up a Node This chapter explains how to provision a single Cisco ONS 15600 node and turn it up for service, including node name, date and time, timing references, network attributes such

More information

ERX System Overview. The ERX System. This chapter provides information about the system.

ERX System Overview. The ERX System. This chapter provides information about the system. ERX System Overview 1 This chapter provides information about the system. Topic Page The ERX System 1-1 Where the ERX System Fits In 1-6 ERX System Modules 1-7 Network Management Tools 1-11 Redundancy

More information

Monitoring Policies Reference

Monitoring Policies Reference The following topics describe the monitoring policies used by Cisco EPN Manager. For information on the supported MIBs and MIB objects, see Cisco Evolved Programmable Network Manager Supported Devices.

More information

SM Cirius LM 175/200+ Mbps Ethernet + 16 T1/E1

SM Cirius LM 175/200+ Mbps Ethernet + 16 T1/E1 SM Cirius LM 175/200+ Mbps Ethernet + 16 T1/E1 Split Mount TDM + Ethernet Radio The Cirius LM is a low-cost point-to-point PDH digital microwave radio system for T1/E1 payloads plus Ethernet and meets

More information

Optical Network Control

Optical Network Control Optical Network Control Jorge M. Finochietto Córdoba 2014 LCD EFN UNC Laboratorio de Comunicaciones Digitales Facultad de Ciencias Exactas, Físicas y Naturales Universidad Nacional de Córdoba, Argentina

More information

NSP Network Services Platform Network Functions Manager - Packet (NFM-P) Release MPR User Guide

NSP Network Services Platform Network Functions Manager - Packet (NFM-P) Release MPR User Guide NSP Network Services Platform Network Functions Manager - Packet (NFM-P) MPR User Guide 3HE-11997-AAAA-TQZZA Legal notice Nokia is a registered trademark of Nokia Corporation. Other products and company

More information

User Manual & Modem Installation Guide

User Manual & Modem Installation Guide ..... digital July 2005 Draft Version 07012005 whirlwind 99 Ling Road Rochester, NY 14612 Telephone: 888.733.4396 Fax: 585.865.8930 Email: sales@whirlwindusa.com Technical Support: techsupport@whirlwindusa.com

More information

EUROPEAN ETS TELECOMMUNICATION April 1997 STANDARD

EUROPEAN ETS TELECOMMUNICATION April 1997 STANDARD EUROPEAN ETS 300 147 TELECOMMUNICATION April 1997 STANDARD Third Edition Source: ETSI TC-TM Reference: RE/TM-03045 ICS: 33.020 Key words: Transmission, mux, SDH Transmission and Multiplexing (TM); Synchronous

More information

Initial Configuration

Initial Configuration 3 CHAPTER This chapter describes the initial configuration of the ML-Series card and contains the following major sections: Hardware Installation, page 3-1 Cisco IOS on the ML-Series Card, page 3-2 Startup

More information

TrangoLINK GigaPlus. Software v1.3.2 Release Notes & Upgrade Instructions. 3 October 2011

TrangoLINK GigaPlus. Software v1.3.2 Release Notes & Upgrade Instructions. 3 October 2011 Software v1.3.2 Release Notes & Upgrade Instructions 3 October 2011 2010-2011 Trango Systems, Inc. All rights reserved. Page 1 of 15 Table of Contents Image Updates Supported Modulation/Symbol rate combination

More information

)454 ' 3YNCHRONOUS $IGITAL (IERARCHY 3$( UNIDIRECTIONAL PERFORMANCE MONITORING FOR THE NETWORK ELEMENT VIEW

)454 ' 3YNCHRONOUS $IGITAL (IERARCHY 3$( UNIDIRECTIONAL PERFORMANCE MONITORING FOR THE NETWORK ELEMENT VIEW INTERNATIONAL TELECOMMUNICATION UNION )454 ' TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (04/97) SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Digital transmission systems

More information

Cisco Prisma II Platform

Cisco Prisma II Platform Cisco Prisma II Platform In optical transmission systems, the network platform forms the foundation of the product family. The Cisco Prisma II platform provides network operators with the unique features

More information

Final draft ETSI EN V1.4.1 ( )

Final draft ETSI EN V1.4.1 ( ) Final draft EN 300 147 V1.4.1 (2001-05) European Standard (Telecommunications series) Transmission and Multiplexing (TM); Synchronous Digital Hierarchy (SDH); Multiplexing structure 2 Final draft EN 300

More information

Troubleshooting. Diagnosing Problems CHAPTER

Troubleshooting. Diagnosing Problems CHAPTER CHAPTER 5 Troubleshooting There are several ways to troubleshoot installation and performance problems. For instance, the front-panel LEDs provide the quickest way to evaluate switch operation. The statistics

More information

ITU-T G.832. Transport of SDH elements on PDH networks Frame and multiplexing structures

ITU-T G.832. Transport of SDH elements on PDH networks Frame and multiplexing structures INTERNATIONAL TELECOMMUNICATION UNION ITU-T G.832 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (10/98) SERIES G: TRANSMISSION SYSTEMS AND MEDIA, DIGITAL SYSTEMS AND NETWORKS Digital transmission systems

More information

Interface Management API Implementation Agreement (SONET/SDH Interfaces)

Interface Management API Implementation Agreement (SONET/SDH Interfaces) Interface Management API Implementation Agreement (SONET/SDH Interfaces) Revision 3.0 Editor: Tim Shanley, TranSwitch, tim.shanley@txc.com Copyright 2004 The Network Processing Forum (NPF). All Rights

More information

JJ TTC STANDARDS. Physical Layer Specifications of kbit/s Optical. Subscriber Line. Version 1. Nov

JJ TTC STANDARDS. Physical Layer Specifications of kbit/s Optical. Subscriber Line. Version 1. Nov TTC STANDARDS JJ-50.30 Physical Layer Specifications of 155520kbit/s Optical Subscriber Line Version 1 Nov 25 1999 THE TELECOMMUNICATION TECHNOLOGY COMMITTEE Introduction This document provides the TTC

More information

Think Smart Get Connected. Professional. Microwave Radio Solutions for Data and Voice Communication

Think Smart Get Connected. Professional. Microwave Radio Solutions for Data and Voice Communication Think Smart Get Connected Professional Microwave Radio Solutions for Data and Voice Communication SAF Tehnika SAF Tehnika is a Latvian (Europe) designer, producer and distributor of digital microwave data

More information

CP30/G30/MC31 Firmware Version 3100 Known Issues

CP30/G30/MC31 Firmware Version 3100 Known Issues CP30/G30/MC31 Firmware Version 3100 Known Issues Introduction This document lists issues that have been identified with firmware version 3100 for the Kingfisher CP30/G30/MC31 modules. Where possible, workarounds

More information