3. Phase Indications. kwh 1. Introduction. Units of measurement. kwh. Volts Amps Hz Kwatts KVAr KVA. Degree Wh VAh

Size: px
Start display at page:

Download "3. Phase Indications. kwh 1. Introduction. Units of measurement. kwh. Volts Amps Hz Kwatts KVAr KVA. Degree Wh VAh"

Transcription

1 EM 349 SS Single Phase Energy Meter 3. Phase Indications Installation & Operating Instructions Section Contents. Introduction 2. Measurement Reading Screen 3. Phase Indications 4. Programming 4. Password Protection 4.2 Menu selection 4.2. System Parameter selection screen Potential transformer Primary value Potential transformer secondary value transformer Primary value Energy Display on modbus Energy Digit Rollover(reset) count Communication Parameter selection screen Setting RS 485 Baud rate RS 485 Parity selection Reset Parameter selection screen Resetting Parameter Relay Output parameter selection screen Pulse Duration (width) selection Pulse rate divisor Quit screen 5. Relay Output (Optional). 5. Pulse Output 6. RS 485 (Modbus) Output 6. User assignable Modbus Register 7. Phaser Diagram TABLE : Measured Parameters Display Parameter Active Energy (8 digit counter) Modbus Parameter System System Frequency Active Power Reactive Power Apparent Power Phase Angle Active Energy Apparent Energy Units of measurement Volts Amps Hz Kwatts KVAr KVA Degree Wh VAh LED Von glowing Phase present LED Von off phase absent LED glowing out of phase w.r.t voltage. LED off in phase w.r.t voltage Installation 8. EMC Installation Requirements 8.2 Case Dimensions and Panel Cut-out 8.3 Wiring 8.4 Auxiliary Supply 8.5 Fusing 8.6 Earth / Ground Connections Network Wiring. Specification 2. Measurement Reading Screen In normal operation the user is presented with active energy measurement screen. Screen : Active Energy () Setup Parameter Screen cd (PassWord) Exit from setup Parameter to Main Display. Connection for Optional Pulse output / RS 485 (Select). Introduction Ultra high brightness LED display. 55_Rev.D -5/3 The instrument is a panel mounted 96 x 96mm DIN Quadratic energy meter. It accumulates Active energy, in single phase network. The instrument also measures AC, AC, Frequency, Power, Power factor, Phase Angle, Apparent Energy which can be accessed via Modbus. All voltage & measurements are True RMS upto 5th harmonic. Meter can be configured & Programmed at site for the following : PT Primary, PT Secondary, CT Primary, Modbus Settings & Pulse output settings. The front panel has two push buttons through which the user can reset the energy & configure the product. The front panel has Impulse red led, flashing at rate proportional to measured power. Its impulse rate is 36impulses/. Active energy is displayed in 8 digit counter with auto ranging feature. Below given table describes auto ranging with minimum resolution of energy measured in perticular range. When LED glows the energy is displayed in mega watt. Display Format X LED Minimum resolution ON ON ON miliwatt miliwatt miliwatt Watt Watt Watt kilowatt kilowatt kilowatt MegaWatt Maximum Active energy count reached is MegaWatt after this counter rollovers to zero and measurement starts from first range. Impulse led on front panel can be used to cross check the energy calibration on site. Its nominal impulse rate is 36 impulses /. A SYS SEriAL (Select System Parameter) Parameter (Sec 4.2.) (Sec 4.2.2) UP (PT Primary) (Sec 4.2..) US (PT Secondary) (Sec ) AP (CT Primary) (Sec ) EnO (Energy Display on ModBUS) (Sec ) Edr (Energy digit reset count) (Sec ) A ( Serial Communication ) Add (Modbus ) (Sec ) br (Baud Rate) (Sec ) Pr (Parity Bits) (Sec ) reset (Reset Parameter) (Sec 4.2.3) non (No Parameter), E (Energy), Down key (Sec ) relay (Select Relay Parameter) (Sec 4.2.4) dur ( Relay Pulse Duration) (Sec ) rat (Pulse Rate Divisor) (Sec ) quit (Exit Menu) (Sec 4.2.5) : UP KEY : DOWN KEY A Down Up 2

2 4. Programming The following sections comprise step by step procedures for configuring the meter for individual user requirements. To access the set-up screens press and hold the Down and Up Key simultaneously for 5 seconds. This will take the User into the Password Protection Entry Stage (Section 4.). 4.. Password Protection Password protection can be enabled to prevent unauthorised access to set-up screens, by default password protection is not enabled. Password protection is enabled by selecting a four digit number other than, setting a password of disables the password protection. Password Incorrect. The unit has not accepted the Password entered. Pressing the " Down" key will return to the Enter Password stage. Up key exits the Password menu and returns operation to the measurement reading mode. New / Change Password (*Decimal point indicates that this will be flashing). first digit from through to 9, the value will wrap from 9 Up key to advance the operation to the next digit and sets the first digit, in this case to 2 New / Change Password, first digit entered, prompting for second digit. (*Decimal point indicates that this will be flashing). second digit from through to 9, the value will wrap from 9 Up key to advance the operation to the next digit and sets the second digit, in this case to 4.2 Menu selection System Parameter selection screen. This menu screen is used to select the different system Parameter like system type, CT Ratio, PT Ratio, Up key allows the user to set Different system parameters. (see section to ) down key will advance to Communication selection screen (see section 4.2.2) Communication Parameter selection screen Reset Parameter selection screen. This menu screen is used to select the different communication parameters like selection, RS485 Parity selection, RS485 baud rate Up key allows the user to set different Communication parameters (see section to ) down key will advance to Reset parameter Screen. (see section 4.2.3) This menu screen is used to Reset the energy parameter. Up key allows the user to Reset energy system parameter (see section ) 4.2. System parameters Selection Potential Transformer Primary Value This screen enables the user to set primary transformer voltage In terms of kilovolts (note the enunciator). Up key accepts the present value and advances to the potential Transformer secondary Value edit menu. (See Section ) Down key will enter the Potential Transformer Primary Value Edit mode. Initially the multiplier must be selected, pressing the Down key will move the decimal point position to the right until it reaches # # #.# after which it will return to #. # # #. Up key accepts the present multiplier (decimal point position) and advances to the potential Transformer primary Digit Edit mode. Potential Transformer primary Digit Edit Down key will scroll the value of the most significant digit from through to 9 unless the presently displayed Potential Transformer Primary Value together with the Transformer Primary Value, previously set, would result in a maximum power of greater than MVA per phase in which case the digit range will be restricted. Up key accepts the present value at the cursor position and advances the cursor to the next less significant digit. Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present to identify the scaling of the number until the cursor position coincides with the steady decimal point position. At this stage the decimal point will flash. Enter Password, second digit entered, prompt for third digit. Use the Down key to scroll the value of the third digit from through to 9, the value will wrap from 9 Up key to advance to next digit. New / Change Password, second digit entered, prompting for third digit. (*decimal point indicates that this will be flashing). third digit from through to 9, the value will wrap from 9 Up key to advance the operation to the next digit and sets the third digit, in this case to 5 down key will advance to Output Option selection screen (see section 4.2.4) Relay Output Parameter selection screen. This menu screen will allow the user to select different Parameter related to Relay Output. When the least significant digit has been set pressing the Potential Transformer Primary Value Confirmation stage. Up key will advance to the Screen showing display of.239 kv i.e. 239 Volts indicating steady decimal point and cursor flashing at the hundreds of volts position. Potential Transformer Primary Value Confirmation Potential Transformer Primary Value. If the scaling is not correct, pressing the Down key will return to the Potential Transformer Primary Value Edit stage. Enter Password, third digit entered, prompt for fourth digit. Use the Down key to scroll the value of the fourth digit from through to 9, the value will wrap from 9 Up key to advance to verification of the password. Enter Password, fourth digit entered, awaiting verification of the password. Password confirmed. Pressing Down key will advance to the New / change Password entry stage. New / Change Password, third digit entered, prompting for fourth digit. (* denotes that decimal point will be flashing). fourth digit from through to 9, the value will wrap from 9 Up key to advance the operation to the New Password Confirmed and sets the fourth digit, in this case to 3. New Password confirmed. Down key will return to the New/Change Password. Up key will advances to the Menu selection screen.(see section 4.2) Quit screen. Up key allows the user to select & Configuare the relay output option (see section ) down key will advance to Quit screen. (see section 4.2.5) This screen allows user to Quit from Menu. Up key will allow the user to Quit from menu & return to measurement screen. 4.2.) Up key sets the displayed value and will advance to the Potential Transformer secondary Value (See Section ) Potential Transformer secondary Value The value must be set to the nominal full scale secondary voltage which will be obtained from the Transformer when the potential transformer(pt)primary is supplied with the voltage defined in potential transformer primary voltage. The ratio of full scale primary to full scale secondary is defined as the transformer ratio. Up key accepts the present value and advances to the Transformer Primary Value edit menu. (See Section ) Note that the range of instrument is from 4 to 277V for 239 VL-N. Please refer the table below for different ranges. Down key will enter the Potential Transformer Secondary Value Edit mode. Pressing the Down key will scroll the value of the most significant digit From available range of PT secondary value Up key accepts the present value at the cursor position and advances the cursor to the next less significant digit. Potential Transformer secondary ranges for various Input s Up key will advance to the Menu selection screen. (See section 4.2). 63.5V L-N 57V - 69V L-N 33.V L-N 7V - 39V L-N 239.6V L-N 4V - 277V L-N 3 4

3 Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present to identify the scaling of the number until the cursor position coincides with the steady decimal point position. At this stage the decimal point will flash. When the least significant digit has been set pressing the Up key will advance to the Potential Transformer secondary Value Confirmation stage Transformer Primary Value The nominal Full Scale that will be displayed as the Line currents. This screen enables the user to display the Line currents inclusive of any transformer ratios, the values displayed represent the in Amps. Up key accepts the present value and rollbacks to menu selection screen (See Section 4.2) Down key will enter the Transformer Primary Value Edit mode. This will scroll the value of the most significant digit from through to 9, unless the presently displayed Transformer Primary Value together with the Potential Transformer Primary Value results in a maximum power of greater than MVA in which case the digit range will be restricted, the value will wrap. Example: If primary value of PT is set as 4kV (max value) then primary value of is restricted to 736A. Up key will advance to the next less significant digit. (* Denotes that decimal point will be flashing). The Maximum Power restriction of MVA refers to 2% of nominal current and 2% of nominal voltage, i.e, MVA nominal power per phase. When the least significant digit had been set, pressing the Transformer Primary Value Confirmation stage. Potential Transformer Secondary Value Confirmation Potential Transformer Secondary Value. If the scaling is not correct, pressing the Down key will return to the Potential Transformer Secondary Value Edit Up key sets the displayed value and will advance to the current Transformer Primary Value (See Section ) Up key will advance to the The minimum value allowed is, the value will be forced to if the display contains zero when the Up key is pressed Energy Display on modbus Transformer Primary Value Confirmation. Transformer Primary Value. If the scaling is not correct, Down key will return to the Transformer Primary Value Edit stage with the most significant digit highlighted (associated decimal point flashing). This screen enable user to set energy in terms of Wh / KWh / MWh on RS 485 Output depending as per the requirement. Up key sets the displayed value and will advance to the Energy Display on Modbus menu. (See section ) Pressing Up key accepts the presents value and advances to the Energy digit Rollover(reset) count menu (See section ). Down key will enter the Energy Display On Modbus Edit mode and scroll the value through the values,2 & 3 wrapping back to : Energy In Wh 2 : Energy in KWh 3: Energy in MWh. Up key advances to the Energy Display Energy Display On Modbus Confirmation. Energy Display On Modbus. Down key will enter the Energy Display On Modbus Edit. Pressing Up key sets the displayed value and will advance to the Energy digit reset count menu. (See section ) Note : Default value is set to i.e. Energy on Modbus will be in terms of Wh resp Energy Digit Rollover(reset) count : Communication Parameter Selection : Setting : This screen applies to the RS 485 output only. This screen allows the user to set RS485 parameter for instruments This screen enables user for setting maximum energy count after which energy will rollback to zero depends upon setting of Wh,KWh, & MWh. Up key sets the displayed value and will jump back to the system parameter selection (See Section 4.2.) Down key will enter the Energy digit reset count edit mode. This will scroll the value of reset count from 7 to 4 for Wh,from 7 to 2 for KWh & from 7 to 9 for MWh. Ex. If energy display on modbus is set Wh & It will set Energy digit count to then energy will reset after 9,999,999,999 & then will rollback to zero. Pressing Up key will advance to Energy digit reset count confirmation screen. Down key will re-enter Energy digit Rollover(reset) count edit mode. Up key sets the displayed value and will rollbacks to menu selection screen (see section 4.2). Note : ) Default value is set to 4 i.e if energy count crosses4 digit it will rollback to zero. 2) Energy displays on modbus is set to (2) & energy digit reset count is set to 2.Energy screen on display will show i.e Energy overflow.when energy crosses the digit count. 3) Energy displays on modbus is set to (3) & energy digit reset count is set to 9.Energy screen on display will show i.e Energy overflow. when energy crosses the 8 digit count. The range of allowable address is to 247. Enter, prompt for first digit. Enter, first digit entered, prompt for second digit Use the Down key to scroll the value of the second digit Up key to advance to next digit. Enter, second digit entered, prompt for third digit Use the Down key to scroll the value of the third digit Enter for third digit. Screen. Down key to scroll the value of the first digit Up key to advance to next digit. Up key to advance to confirmation confirmation Screen. This Screen confirms the set by user. Up key to advance to next Screen Rs485 Baud Rate (See Section ) Edit mode. Down key will reenter the RS 485 Baud Rate : This screen allows the user to set Baud Rate of RS 485 port. The values displayed on screen are in kbaud.. Pressing Up key accepts the present value and advance to the Parity Selection (See Section ) Down key will enter the Baud Rate Edit mode and scroll the value through 2.4, 4.8, 9.6, 9.2 and back to 2.4 RS 485 Baud Rate confirmation : Pressing Down key will be re-enter into the. Baud Rate Edit mode Up key will select the value and advances to the Parity Selection (See Section ) RS 485 Parity Selection : This screen allows the user to set Parity & number of stop bits of RS 485 port. Pressing Up key accepts the present value and advance to Menu selection (see section 4.2). Down key will enter the Parity & stop bit Edit mode and scroll the value through odd : odd parity with one stop bit no : no parity with one stop bit no 2 : no parity with two stop bit E : even parity with one stop bit RS 485 Parity confirmation : Pressing Down key will be re-enter into Parity Edit mode Reset Parameter Selection : Resetting Parameter The following screens allow the users to reset the all Energy. Reset (None) Up key will set the value. Up key again will jump back to the menu selection screen (see section 4.2). Pressing Up key advances to menu selection screen (see section 4.2) Down key will enter the Reset option mode and scroll through Parameter and wrapping back to None. Reset option select, The user has scrolled through to the E Energy value. Pressing Up key will select the value and advance to the Reset Energy Confirmation Mode. & resets energy. Integrated Energy at the moment of resetting energy will become zero. Reset Energy Confirmation. option mode. Down key will re-enter the Reset Pressing Up key will jump back to the menu selection screen (see section 4.2) Relay output menu Pulse Duration Selection: This screen applies only to the Pulsed output mode of the relay This screen allows the user to set Relay energisation time in milliseconds Pulse Rate Pulse Duration Edit. Pressing Up key accepts the present value and advance to pulse rate selection menu (see section ). Down key will enter the Pulse Duration Edit mode and scroll the value through 6,, 2 and wrapping back to 6. Up key will select the value and advances to Pulse Duration Confirmation. Pulse Duration Confirmation. Pulse duration. pressing the Down key will re-enter the Pulse Duration Edit mode. Pressing Up key set displayed value and Will advance to pulse rate selection menu (See section ) This screen applies to the Relay Output option only. The screen allows user to set the energy pulse rate divisor. Divisor values can be selected through,,,. 5. Relay output (Optional) : 5. Pulse Output : TABLE 3 : Energy Pulse Rate Divisor Pulse rate Divisor Pulse System Power* per Whr per r per MWhr per Whr per r per MWhr per Whr per r per MWhr per Whr per r per MWhr Pulse Duration 6 ms, ms or 2 ms * System power = CT(Primary) x PT(Primary)L-N Pressing Up key accepts the presents value and advances to the Menu Selection Screen (See section ). Down key will enter the Pulse rate divisor Edit mode and scroll the value through the values,,, wrapping back to. Up key advances to the Pulse rate Divisor Confirmation menu. Pulse Rate Divisor Confirmation. Pulse rate divisor. If the Pulse rate shown is not correct, pressing the Down key will return to the Pulse rate divisor Edit stage by blanking the bottom line of the display. Pressing Up key sets the displayed value and will advance to the Relay output Option Menu. (See section 4.2.4) Pulse output is the potential free, very fast acting relay contact which can be used to drive an external mechanical counter for energy measurement. Rish EM 349 SS has one pulse output. Relay Contact One normally open & one normally closed Pulse Duration 6ms, ms or 2ms. For Energy Output in Wh 2. For Energy Output in KWh Divisor Divisor Pulse rate Pulse System Power* per KWhr per KWhr per MWhr 3. For Energy Output in MWh Pulse rate Pulse System Power* per MWhr per MWhr per GWhr 5 6

4 6. RS 485 ( ModBus ) Output : Meter supports MODBUS (RS485) RTU protocol( 2-wire ). Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained together. The screens should also be connected to the Gnd terminal. To avoid the possibility of loop currents, an Earth connection should be made at one point on the network.loop (ring) topology does not require any termination load. Line topology may or may not require terminating loads depending on the type and length of cable used. The impedance of the termination load should match the impedance of the cable and be at both ends of the line. The cable should be terminated at each end with a 2 ohm (/4 Watt min.) resistor. RS 485 network supports maximum length of.2km. Including the meter, a maximum of 32 instruments can be connected in RS485 network.the permissible address range for meter s between and 247 for 32 instruments. Broadcast Mode (address ) is not allowed. The maximum latency time of an meter is 2ms i.e. this is the amount of time that can pass before the first response character is output. After sending any query through software ( of the Master), it must allow 2ms of time to elapse before assuming that the meter is not going to respond. If slave does not respond within 2 ms, Master can ignore the previous query and can issue fresh query to the slave. The each byte in RTU mode has following format: Format of Data Bytes Error Checking Bytes Byte format 8-bit binary, hexadecimal -9, A-F 2 hexadecimal characters contained in each 8-bit field of the message 4 bytes (32 bits) per parameter. Floating point format ( to IEEE 754) Most significant byte first (Alternative least significant byte first) 2 byte Cyclical Redundancy Check () start bit, 8 data bits, least significant bit sent first bit for even/odd parity stop bit if parity is used; or 2 bits if no parity Communication Baud Rate is user selectable from the front panel between 24, 48, 96, 92 bps. Function code : 3 Read Holding Registers Read content of read /write location ( 4X ) 4 Read input Registers Read content of read only location ( 3X ) 6 Presets Multiple Registers Set the content of read / write locations ( 4X ) Response: Volt (239.6V) (Hex) 43 (Hex) 6E (Hex) E9 (Hex) 7B (Hex) 8D (Hex) Device Function Code Byte Count Data Register High Byte Data Register Low Byte Data Register2 High Byte Byte Count : Total number of data bytes received. Data register High Byte : Most significant 8 bits of Data register of the parameter requested. Data register Low Byte : Least significant 8 bits of Data register of the parameter requested. Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested. (Note : Two consecutive 6 bit register represent one parameter.) Table 4 : 3 X register addresses (measured parameters) Data Register2 Low Byte Parameter Parameter Modbus Start Hex (Register) No. 3 Volts W C 39 VA VAR PF E Phase Angle Freq Wh Vah 5 Note : Active Energy reading received will be in Watt Hours. Note : Apparent Energy reading received will be in VA Hours. Accessing 4 X register for Reading & Writing : Low Each setting is held in the 4X registers.modbus code 3 is used to read the current setting and code 6 is used to write/change the setting. Refer Table 5 for 4 X Register addresses. AE (Hex) High Response: PT Secondary 239.6V Device Byte Count Data Register High Byte Data RegisterLow Byte Data Register2 High Byte Data Register2 Low Byte Low High Byte Count : Total number of data bytes received. Data register High Byte : Most significant 8 bits of Data register of the parameter requested. Data register Low Byte : Least significant 8 bits of Data register of the parameter requested. Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested. (Note : Two consecutive 6 bit register represent one parameter.) (Hex) 3 (Hex) 43 (Hex) 6F (Hex) 99 (Hex) 9A (Hex) 35 (Hex) 9 (Hex) Byte Count : Total number of data bytes to be transmitted. Data register High Byte : Most significant 8 bits of Data register of the parameter requested. Data register Low Byte : Least significant 8 bits of Data register of the parameter requested. Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested. Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested. (Note : Two consecutive 6 bit register represent one parameter.) Response: Device Start High Start Low Low High (Hex) (Hex) 2C (Hex) (Hex) 8 (Hex) (Hex) Start High : Most significant 8 bits of starting address of the parameter requested. Start low :Least significant 8 bits of starting address of the parameter requested. (Note : Two consecutive 6 bit register represent one parameter.) Exception Cases : An exception code will be generated when meter receives ModBus query with valid parity & error check but which contains some other error ( e.g. Attempt to set floating point variable to an invalid value ) The response generated will be Function code ORed with HEX (8H ). The exception codes are listed below Illegal function The function code is not supported by meter. Example : Reading PT Secondary System type : Start address= 2C (Hex) Number of registers = Note :Number of registers = Number of Parameters x 2 Query : Example : Writing PT Secondary System type : Start address= 2C(Hex) Number of registers = Illegal Data 3 Illegal Data Value Attempt to access an invalid address or an attempt to read or write part of a floating point value Attempt to set a floating point variable to an invalid value Accessing 3 X register for reading measured values: Two consecutive 6 bit registers represent one parameter. Refer table 4 for the addresses of 3X registers (Parameters measured by the instruments). Each parameter is held in the 3X registers. Modbus Code 4 is used to access all parameters. Example : To read parameter, Volts : Start address= (Hex) Number of registers = Note : Number of registers = Number of parameters x 2 Each Query for reading the data must be restricted to 2 parameters or less. Exceeding the 2 parameter limit will cause a ModBus exception code to be returned. Query : (Hex) (Hex) (Hex) 7 (Hex) CB (Hex) Device Function Code Start High Start Low Number of Registers Hi Number of Registers Lo Low High Device Start High Start Low Low High (Hex) 3 (Hex) 2C (Hex) 5 (Hex) C2 (Hex) Start High : Most significant 8 bits of starting address of the parameter requested. Start low :Least significant 8 bits of starting address of the parameter requested. (Note : Two consecutive 6 bit register represent one parameter.) Query:( Set PT Secondary = 239.6V). Device Starting Hi Starting Lo Byte Count Data Register-High Byte Data Register- Low Byte Data Register-2 High Byte Data Register-2 Low Byte Low High (Hex) (Hex) 2C (Hex) (Hex) 43 (Hex) 6F (Hex) 99 (Hex) 9A (Hex) 3E (Hex) 4 (Hex) Table 5 : 4 X register addresses Parameter Parameter Read / Write Modbus Start Hex (Register) No Energy Display on Modbus Sys R Sys R Pulse Width C 45 6 Energy Reset Wp E RS 485 Set-up Code Node Pulse Divisor PT Primary CT Primary System Power R Energy Digit Rollover(reset) count Register Order/Word Order PT Secondary 2C 47 7 Password R/W 46 Start High : Most significant 8 bits of starting address of the parameter requested. Start low :Least significant 8 bits of starting address of the parameter requested. (Note : Two consecutive 6 bit register represent one parameter.) 7 8

5 Explanation for 4 X register : Parameter Description System 49 System 4-43 Pulse Width of Relay 45 Reset Energy Counter Rs485 Set-up Code This address is read only and displays System This address is read only and displays System - This address is used to set pulse width of the Pulse output. Write one of the following values to this address: 6 : 6 ms : ms 2 : 2 ms Writing any other value will return error. This address is used to reset the Energy Counter. Write zero value to this register to reset the energy counter. Writing any other value will return an error. This address is used to set the baud rate, Parity, Number of stop bits. Refer to Table 6 for details. 42 Node This register address is used to set Device address between to Pulse Divisor This address is used to set pulse divisor of the Pulse output. Write one of the following values to this address: : Divisor : Divisor : Divisor : Divisor & in KWh and MWh divisor will be by default. Writing any other value will return an error. 433 PT Primary This address allows the user to set PT Primary value. The maximum settable value is 4kV & also depends on the per phase MVA Restriction of power combined with CT primary. PT primary value should be in terms of voltage for example to set 2kV send 2V. 435 CT Pimary This address allows the user to set CT Primary value. The maximum settable value is 9999 & also depends on the per phase MVA Restriction of power combined with PT primary 437 Sys Power System Power (Read Only) is the Nominal system power based on the values of Nominal system volts and Nominal system current Energy display on Modbus Energy digit Rollover(Reset) Count Word Order PT secondary This address is used to set energy display on modbus in Wh,KWh & MWh. Write one of the following value to this address. = Energy in Wh. 2 = Energy in KWh. 3 = Energy in MWh. This address is used to setting maximum energy count after which energy will rollback to zero depends upon setting of Wh,KWh, & MWh. If Energy display on modbus in Wh count will be set in between 7 to 4 or In KWh set in between 7 to 2 & In MWh set in Word Order controls the order in which meter receives or sends floating - point numbers:- normal or reversed register order. In normal mode, the two registers that make up a floating point numbers are sent most significant bytes first. In reversed register mode, the two registers that make up a floating point numbers are sent least significant bytes first. To set the mode, write the value 24. into this registerthe instrument will detect the order used to send this value and set that order for all ModBus transaction involving floating point numbers. This address is used to read and write the PT secondary value. Ref Table for the range of PT secondary settable values in Section Password This address is used to set & reset the password. Valid Range of Password can be set is ) If password lock is present & if this location is read it will return zero. 2) If Password lock is absent & if this location is read it will return One. 3) If password lock is present & to disable this lock first send valid password to this location then write to this location 4) If password lock is present & to modify 4X parameter first send valid password to this location so that 4X parameter will be accessible for modification. 5) If for in any of the above case invalid password is send then meter will return exceptional error 2. Table 6 : RS 485 Set-up Code Baud Rate Parity Stop Bit Decimal value 92 NONE 92 NONE 92 EVEN 92 ODD 96 NONE 96 NONE 96 EVEN 96 ODD 48 NONE 48 NONE 48 EVEN 48 ODD 24 NONE 24 NONE 24 EVEN 24 ODD NOTE : Codes not listed in the table above may give rise to unpredictable results including loss of communication. Excise caution when attempting to change mode via direct Modbus writes. 6. User Assignable Modbus Registers: The meter contains the 2 user assignable registers in the address range of x2 (353) to x226 (355) (see Table 9). Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the instrument can be mapped to these 2 user assignable registers. Parameters (3X registers addresses ) that resides in different locations may be accessed by the single request by re-mapping them to adjacent address in the user assignable registers area. The actual address of the parameters ( 3X registers addresses) which are to be assessed via address x2 to x226 are specified in 4x Register x2 to x23 (see Table ). Table 9 : User Assignable 3X Data Registers Parameter Modbus Start (Hex) (Register) Number. Assignable Register Assignable Reg Assignable Reg Assignable Reg Assignable Reg Assignable Reg Assignable Reg 6 A Assignable Reg 7 C Assignable Reg 8 E Assignable Reg Assignable Reg Assignable Reg Assignable Reg Assignable Reg Assignable Reg 4 A Assignable Reg 5 C Assignable Reg 6 E Assignable Reg Assignable Reg Assignable Reg Assignable Reg 2 26 Table : User Assignable mapping register ( 4X registers) Parameter Modbus Start (Hex) (Register) Number. Mapping Register Mapped Add for register #x Mapped Add for register #x Mapped Add for register #x Mapped Add for register #x Mapped Add for register #x Mapped Add for register #xa Mapped Add for register #xc Mapped Add for register #xe Mapped Add for register #x Mapped Add for register #x Mapped Add for register #x4 A Mapped Add for register #x6 B Mapped Add for register #x8 C Mapped Add for register #xa D Mapped Add for register #xc E Mapped Add for register #xe F Mapped Add for register #x Mapped Add for register #x Mapped Add for register #x Mapped Add for register #x26 3 Example : Assigning parameter to user assignable registers To access the voltage (3X address x) and (3X address xe) through user assignable register assign these addresses to 4x register (Table ) x and x respectively. Assigning Query: Device Starting Hi Starting Lo Byte Count Data Register-High Byte Data Register- Low Byte Data Register-2 High Byte Data Register-2 Low Byte Low High (Hex) (Hex) * (Hex)* E (Hex) 6A (Hex) C7 (Hex) } } * (3X x) * (3X xe) * Note : Parameters should be assigned in Multiple of two i.e. 2,4,6, Response : Device Start High Start Low Low (Hex) (Hex) 4 (Hex) Reading Parameter data through User Assignable Registers: In assigning query and parameters were assigned to x 2 and x2(table) which will point to user assignable 3xregisters x2 and x2 (table9). So to read and PowerFactor data reading query should be as below. Query: Device Start High Start Low Low High (Hex) ** F (Hex) 7 (Hex) Start High : Most significant 8 bits of starting address of User assignable register. Start low :Least significant 8 bits of starting address of User assignable register. (Starting ) **Note : Two consecutive 6 bit register represent one parameter. Since two parameters are requested four registers are required Response : (Volt2 = 29.3 / =.) x2 x2 x2 x23 x22 x23 Device Byte count Data Register-High Byte Data Register- Low Byte Data Register-2 High Byte Data Register-2 Low Byte Data Register-3 High Byte Data Register-3 Low Byte Data Register-4 High Byte Data Register-4 Low Byte Low High User Assignable mapping Registers ( 4X Registers Table ) (x) (xe) Wh Import (x48) Frequency (x46) (x6) VAh (x5) (Hex) 8 (Hex) 43 (Hex) 5B (Hex) 4E (Hex) 3F (Hex) 8 (Hex) 79 (Hex) 3F (Hex) (Starting ) x2 x2 x24 x26 x224 x226 } Data } Data User Assignable Data Registers ( 3X Registers Table 9 ) x2 (6 bit) x2 (6 bit) x24 (6 bit) x26 (6 bit) x224 (6 bit) x226 (6 bit) x2 (6 bit) x23 (6 bit) x25 (6 bit) x27 (6 bit) x225 (6 bit) x227 (6 bit) High 7 (Hex) To get the data through User assignable Register use following steps: ) Assign starting addresses(table3) of parameters of interest to a User assignable mapping registers in a sequence in which they are to be accessed (see section Assigning parameter to user assignable registers ) 9 2) Once the parameters are mapped data can be acquired by using User assignable data register Starting address. i.e to access data of, Power factor,wh import, Frequency send query with starting address x2 with number of register 8 or individually parameters can be accessed for example if current to be accessed use starting address x22. (See section Reading Parameter data through User Assignable Registers)

6 7. Phaser Diagram : Capacitive Inductive 8. EMC Installation Requirements This product has been designed to meet the certification of the EU directives when installed to a good code of practice for EMC in industrial environments, e.g.. Screened output and low signal input leads or have provision for fitting RF suppression components, such as ferrite absorbers, line filters etc., in the event that RF fields cause problems.. Specification : System Phase 2 Wire (Single Phase) Inputs Nominal input voltage 57.7 V L-N to 277VL-N Nominal range of use of influence quantities for measurands Input frequency Temperature Auxiliary supply voltage % of Rated Value.. 2 % of Rated Value Rated Value + % to 5 C Rated Value + % Inductive Connections Quadrant Sign of Active Power ( P ) Sign of Sign of Reactive Power Power ( Q ) Factor ( PF ) Inductive / Capacitive Import + P + Q + L Import 4 + P - Q + C Export 2 - P + Q - C Export 3 - P - Q - L Inductive means lags Capacitive means leads Note : Though meter displays Active power ( P )with + ( Positive sign ) or - ( negative sign ) depending on External CT Connection, Energy ( ) integration will be in done same register irrespective of Import or Export connection Capacitive Note: It is good practice to install sensitive electronic instruments that are performing critical functions, in EMC enclosures that protect against electrical interference which could cause a disturbance in function. 2. Avoid routing leads alongside cables and products that are, or could be, a source of interference. 3. To protect the product against permanent damage, surge transients must be limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source. The unit has been designed to automatically recover in the event of a high level of transients. In extreme circumstances it may be necessary to temporarily disconnect the auxiliary supply for a period of greater than 5 seconds to restore correct operation. The inputs of these products are designed for connection in to systems via Transformers only, where one side is grounded. 4. ESD precautions must be taken at all times when handling this product. 8.2 Case Dimension and Panel Cut Out mm mm FRONT DISPLAY AREA 3.5 8mm mm PANEL CUTOUT mm Max continuous input voltage Max short duration input voltage Nominal input voltage burden Nominal input current Starting Max continuous input current Nominal input current burden System CT primary values 2% of Rated Value 2 x Rated Value (s application repeated times at s intervals).2va approx. per phase A OR 5A AC rms 2% of Rated Value.6VA approx. per phase Max short duration current input 2 x Rated Value (s application repeated 5 times at 5 min. intervals) Auxiliary Standard nominal Auxillary supply voltages & Frequency a.c. supply voltage tolerance a.c. supply frequency range a.c. supply burden.4% of Nominal Input Std. Values upto 4kA ( or 5 Amp secondaries) V AC/5 Hz, 23V AC/5 Hz,38V AC/5 Hz, - 25V AC- DC, 2-48V DC +2 % / -5 % of Rated Value 45 to 66 Hz 4.5VA Auxiliary supply frequency Temperature Coefficient (For Rated value range of use... 5 C ) Error change due to variation of an influence quantity Display LED Update Impulse LED Controls User Interface Standards EMC Immunity Safety IP for water & dust Rated Value + %.5% / C for (5..2% of Rated Value).5% / C for (..2% of Rated Value ) 2 * Error allowed for the reference condition applied in the test. digits. Approx. seconds Impulse Rate 36 impulses/ Two push buttons IEC 6326 V/m min-level 3 industrial low level electromagnetic radiation environment IEC IEC 6-, Year 2 IEC Installation Mounting is by four side clamps, slide the side clamps through side slot till side clamp gets firmly locked in a groove (Refer fig.) Consideration should be given to the space required behind the instrument to allow for bends in the connection cables. PANEL SLIDE IN THIS DIRECTION AND LOCK MAX PANEL THICKNESS.8,5mm 8.3 Wiring Input connections are made directly to screw-type terminals with indirect wire pressure. Numbering is clearly marked in the plastic moulding. Choice of cable should meet local regulations. Terminal for both and 2 inputs will accept upto 3mm x 2 diameter cables. Note : It is recommended to use wire with lug for connection with meter. d.c. supply burden Operating Measuring Ranges Frequency 3W % of Rated Value % of Rated Value Hz.5 Lag Lead Isolation Dielectric voltage withstand test between circuits and accessible surfaces Environmental Operating temperature Storage temperature Relative humidity Warm up time 2.2 kv RMS 5 Hz for minute between all electrical circuits - to 55 C -2 to +65 C.. 9 % RH 3 minute (minimum) Shock 5g in 3 planes Front As the front of the enclosure conforms to IP54 it is protected from water spray from all directions, additional protection to the panel may be obtained by the use of an optional panel gasket. The terminals at the rear of the product should be protected from liquids. The meter should be mounted in a reasonably stable ambient temperature and where the operating temperature is within the range - to 55 C. Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight. Caution. In the interest of safety and functionality this product must be installed by a qualified engineer, abiding by any local regulations. 2. s dangerous to human life are present at some of the terminal connections of this unit. Ensure that all supplies are de-energised before attempting any connection or disconnection. 3. These products do not have internal fuses therefore external fuses must be used to ensure safety under fault conditions. 8.4 Auxiliary Supply Meter should ideally be powered from a dedicated supply, however it may be powered from the signal source, provided the source remains within the limits of the chosen auxiliary voltage. 8.5 Fusing It is recommended that all voltage lines are fitted with amp HRC fuses. 8.6 Earth/Ground Connections For safety reasons, CT secondary connections should be grounded in accordance with local regulations. 9. Connection Diagram 9. Network Wiring L Single Phase DIGITAL METERING SYSTEM P S + - L N AUX SUPPLY L O AD Accuracy Frequency Active Power Re- Active Power Apparent Power Angle Class. : +.5 % of range ( 5... % of Rated Value ) +.5 % of range (... % of Rated Value ).5% of mid frequency +.5 % of range (... % of Rated Value ) +.5 % of range (... % of Rated Value ) +.5 % of range (... % of Rated Value ) + % of Unity + % of range Active Energy + % as per IEC Active P.F. (.5 lag lead) Apparant Energy + % Class.5 (optional) : Active Energy +.5 % as per IEC Active P.F. (.5 lag lead) Apparant Energy +.5 % Reference conditions for Accuracy : Reference temperature Input frequency 23 C + 2 C 5 or 6Hz + 2% Input waveform Sinusoidal (distortion factor.5) Auxiliary supply voltage Rated Value + % Auxiliary supply frequency Rated Value + %.5 lag lead Vibration Enclosure ( front only ) Enclosure Style Material Terminals Depth Weight ModBus ( RS 485 ) Option : Protocol Baud Rate Parity.. 55 Hz,.5mm amplitude IP 54 as per IEC mm x 96mm DIN Quadratic Polycarbonate Housing, Self extinguish & non dripping as per UL 94 V- Screw-type terminals < 8 mm.62 kg Approx. ModBus ( RS 485 ) 92, 96, 48 or 24 ( Programmable ) Odd or Even, with stop bit, Or None with or 2 stop bits N 2

7 . Connection for Optional Pulse Output / RS 485 Notes :. One Pulse Output & RS Pulse out NO NC COM RS 485 B A G RS 485 Output RS 485 B A G One Pulse Output Pulse out NO NC COM The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method of installation for this product. However, organization has no control over the field conditions which influence product installation. It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Organization only obligations are those in organization standard Conditions of Sale for this product and in no case will organization be liable for any other incidental, indirect or consequential damages arising from the use or misuse of the products. 3

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016 Interface Definition RISH EM 2340/1320/30/40 1 2-60-006-00-00494_Rev. D - 8/2016 2 Section DIGITAL MULTIFUNCTION INSTRUMENT Contents 1. Introduction Programmable Multi-function Energy Meter Installation

More information

Operating Manual RISH DPM Hz

Operating Manual RISH DPM Hz Operating Manual RISH DPM 72mm x 144mm 96mm x 96mm 48mm x 96mm 2-60-006-00-00512_Rev. B - 7/2016 DIGITAL MULTIFUNCTION INSTRUMENT Programmable Digital Panel Meter Installation & Operating Instructions

More information

Energy Division

Energy Division Energy Division http://energy.tycoelectronics.com Installation and Operating Instructions QUADRATIC INTEGRA 1000 Tyco Electronics UK Limited Crompton Instruments Freebournes Road, Witham, Essex, CM8 3AH,

More information

USER MANUAL 2012 V1.1

USER MANUAL 2012 V1.1 SMART MINI POWER SDM630 USER MANUAL 2012 V1.1-1 - Installation and Operation Instructions Important Safety Information is contained in the Maintenance section. Familiarise yourself with this information

More information

Digital Multifunction Meters. Digital Multifunction Meters

Digital Multifunction Meters. Digital Multifunction Meters Digital Multifunction Meters Digital Multifunction Meters DIGITAL MULTIFUNCTIOL METERS SECTION INDEX 1. MFM 3410 3420 3430 3440 6100 & 2000 - Multifunctional Instrument Series 2. EM 3490, 3490SS, 3490DS

More information

SDM630M CT USER MANUAL 2016 V4.7. DIN Rail Energy Meter for Single and Three Phase Electrical Systems

SDM630M CT USER MANUAL 2016 V4.7. DIN Rail Energy Meter for Single and Three Phase Electrical Systems SDM630M CT DIN Rail Energy Meter for Single and Three Phase Electrical Systems Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, THD,etc. Bi-directional measurement IMP & EXP Two pulse outputs

More information

B+G E-Tech User Manual for SDM630 SDM630. Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2013 V1.

B+G E-Tech User Manual for SDM630 SDM630. Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2013 V1. SDM630 Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 203 V. Important Safety Information is contained in the Maintenance section. Familiarize yourself with this

More information

EngyVolt RV12 and RV15

EngyVolt RV12 and RV15 Technical Information EngyVolt RV12 and RV15 Multifunctional electrical energy meters for top-hat rail installation or panel mounting Application For measuring voltage, frequency, current, power, as well

More information

SDM530CT-Modbus USER MANUAL 2015 V1.6. Three Phase Multi-function DIN rail meter. Eastron SDM530CT-Modbus User Manual

SDM530CT-Modbus USER MANUAL 2015 V1.6. Three Phase Multi-function DIN rail meter. Eastron SDM530CT-Modbus User Manual SDM530CT-Modbus Three Phase Multi-function DIN rail meter Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, etc. Bi-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting

More information

SDM530-Modbus USER MANUAL 2015 V1.5. Three Phase Multi-function DIN rail meter. Eastron SDM530-Modbus User Manual

SDM530-Modbus USER MANUAL 2015 V1.5. Three Phase Multi-function DIN rail meter. Eastron SDM530-Modbus User Manual SDM530-Modbus Three Phase Multi-function DIN rail meter Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, etc. Bi-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting

More information

INTEGRA DIGITAL METERING SYSTEMS

INTEGRA DIGITAL METERING SYSTEMS CROMPTON INSTRUMENTS INTEGRA DIGITAL METERING SYSTEMS INTEGRA DIGITAL METERING SYSTEMS The Integra digital metering product portfolio offers an extensive range of systems designed to suit any power monitoring

More information

User Manual V1.1. SDM120-Modbus(mV) Single-Phase Multifunction DIN rail Meter

User Manual V1.1. SDM120-Modbus(mV) Single-Phase Multifunction DIN rail Meter SDM120-Modbus(mV) Single-Phase Multifunction DIN rail Meter Measures kwh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc. Di-directional measurement IMP & EXP Two pulse outputs RS485 Modbus Din rail mounting

More information

Energy Division. Installation and Operating Instructions. Integra Ci1

Energy Division. Installation and Operating Instructions. Integra Ci1 Energy Division Installation and Operating Instructions Integra Ci1 Crompton Instruments The following symbols may appear in this user guide, and may also be affixed to the products discussed in this guide:

More information

MID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID

MID PRELIMINARY DATA SHEET. RI-D Series. Single Phase Multifunction Energy Meter (MID Certified) MID PRELIMINARY DATA SHEET RI-D35-100 Series Single Phase Multifunction Energy Meter (MID Certified) MID direct connected Two pulse outputs LED pulse indication High definition LCD display with white backlight

More information

RISH Master 3440i/3440iDL 0.2S

RISH Master 3440i/3440iDL 0.2S Interface Definition RISH Master 344i/344iDL.2S as per IEC6253-22 DIGITAL MULTIFUNCTION INSTRUMENT Installation & Operating Instructions Section 1. 2. 3. 4. 5. Contents Introduction Communication selection

More information

MultiCube Single Phase Multi-Function Electricity Meter. Installation and Operation

MultiCube Single Phase Multi-Function Electricity Meter. Installation and Operation MultiCube Single Phase Multi-Function Electricity Meter Installation and Operation PREFACE MultiCube Single Phase Meter Operating Guide Revision 5.01 August 2002 This manual represents your meter as manufactured

More information

PowerLogic power-monitoring units. PM1000 series power meter. Technical data sheet

PowerLogic power-monitoring units. PM1000 series power meter. Technical data sheet PowerLogic power-monitoring units power meter Technical data sheet 2011 Basic energy meters Functions and characteristics PE86261 PE86260 PowerLogic PM1000 power meter. The PowerLogic power meters are

More information

DIN Rail Smart Meter for Single and Three Phase Electrical Systems

DIN Rail Smart Meter for Single and Three Phase Electrical Systems SDM630-Modbus V2 DIN Rail Smart Meter for Single and Three Phase Electrical Systems Measures kwh Kvarh, KW, Kvar, KVA, P, F, PF, Hz, dmd, V, A, etc. Bi-directional measurement IMP & EXP Two pulse outputs

More information

MIC-2 MKII, Multi-instrument DATA SHEET

MIC-2 MKII, Multi-instrument DATA SHEET MIC-2 MKII, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

Energy Division. Crompton Instruments Integra 1630 Low Profile Digital Metering System

Energy Division. Crompton Instruments Integra 1630 Low Profile Digital Metering System Energy Division Crompton Instruments Integra 1630 Low Profile Digital Metering System DIN Integra 1630 Series Multifunction Integra 1630 digital metering system provides high accuracy 0.2% measurement,

More information

AP25-1DO METER (MID CERTIFIED) User Manual - Issue 1.0

AP25-1DO METER (MID CERTIFIED) User Manual - Issue 1.0 (MID CERTIFIED) AP25-1DO www.sifamtinsley.co.uk NEW PRODUCT Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue

More information

PowerLogic power-monitoring units. EM1000 series power meter. Technical data sheet

PowerLogic power-monitoring units. EM1000 series power meter. Technical data sheet PowerLogic power-monitoring units power meter Technical data sheet Distributed By: MetersUSA www.metersusa.com Meters@MetersUSA.com 1 224 365 5935 Basic energy meters Functions and characteristics PB105460

More information

SUBJECT TO CHANGE WITHOUT NOTICE

SUBJECT TO CHANGE WITHOUT NOTICE 100A DIRECT CONNECTED (MID CERTIFIED) AP25-3DO www.sifamtinsley.co.uk NEW PRODUCT Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current

More information

DKM-407 DIN RAIL TYPE NETWORK ANALYZER

DKM-407 DIN RAIL TYPE NETWORK ANALYZER DKM-407 User Manual DKM-407 DIN RAIL TYPE NETWORK ANALYZER DESCRIPTION The DKM-407 is a DIN rail mounted precision and low cost unit allowing measurement and remote monitoring of AC parameters of a distribution

More information

MIC-2 Multi-instrument DATA SHEET

MIC-2 Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional) Profibus DP (optional) I/O modules

More information

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D

Data Sheet. Digital Multifunctional Power Meter with LCD Display and Optional Modules WPM D WPM 770 Data Sheet 679.D.141.02 Digital Multifunctional Power Meter with LCD Display and Application The digital Weigel Power Meters WPM 770 have been designed to display the electrical parameters in low

More information

1.Eastron SDM230Modbus Smart Meter Modbus Protocol Implementation V1.2

1.Eastron SDM230Modbus Smart Meter Modbus Protocol Implementation V1.2 1.Eastron SDM230Modbus Smart Meter Modbus Protocol Implementation V1.2 1.1 Modbus Protocol Overview This section provides basic information for interfacing the Eastron Smart meter to a Modbus Protocol

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET

MIC-2 MKII & MIC-2 MKII DIN, Multi-instrument DATA SHEET & DIN, Multi-instrument DATA SHEET Measurements All 3-phase AC measurements True RMS 4-Quadrant energy Power Quality Analysis Replaces analogue meters RS-485 Modbus RTU protocol TCP/IP Modbus (optional)

More information

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation: DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated

More information

1.Eastron SDM530-Modbus Smart Meter Modbus Protocol Implementation V1.1

1.Eastron SDM530-Modbus Smart Meter Modbus Protocol Implementation V1.1 1.Eastron SDM530-Modbus Smart Meter Modbus Protocol Implementation V1.1 1.1 Modbus Protocol Overview This section provides basic information for interfacing the Eastron Smart meter to a Modbus Protocol

More information

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006

PowerLogic power-monitoring units. Power Meter PM500. Technical data sheet 2006 PowerLogic power-monitoring units Technical data sheet 2006 Functions and characteristics E90463 The PowerLogic PM500 Power Meter provides all measurement capabilities required to monitor an electrical

More information

INTEGRA Ri3 digital metering system DIN Rail Digital Energy Meter for Single- and Three-phase Electrical Systems

INTEGRA Ri3 digital metering system DIN Rail Digital Energy Meter for Single- and Three-phase Electrical Systems INTEGRA Ri3 digital metering system DIN Rail Digital Energy Meter for Single- and Three-phase Electrical Systems Installation and Operating Instructions Important safety information is contained in the

More information

EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters

EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters Power and Energy Meters Code No. LIT-1900845 Issued December 4, 2013 EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters EM-1000 Series Meter Description The EM-1000 Series monitor is

More information

Multifunction Transducer MT440

Multifunction Transducer MT440 Multifunction Transducer MT440 Voltage and current auto range measurements up to 600V, 12.5A Universal wide auxiliary power supply range 24 300 Vdc, 40 276 Vac Power accuracy class 0.5 (EN 60 688), Up

More information

EM6400 series Multi-Function meters

EM6400 series Multi-Function meters 6400 series Multi-Function meters 1 Digital display & Analog load bar indicators 2 Bright Red LED display 3 Global: CE, UL marks 4 Universal Demand Monitoring Quick and easy installation Turbo Key 6400

More information

Voltage Transducer UMT516 / MT516

Voltage Transducer UMT516 / MT516 Voltage Transducer UMT516 / MT516 True RMS AC voltage measurements Voltage auto range measurements up to 600V # Wide frequency measurement range 16 400 Hz High accuracy class 0.2 (IEC-688), 0.1 on communication

More information

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET

APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET APU 200 Automatic DATA SHEET Gen-set Controller DATA SHEET Measurement input, auto range Up to 1000 V AC L-L Up to 12.5 A (sinusoidal) 16 400 Hz Output Up to four analogue outputs Relay output RS 485 Modbus

More information

PowerLogic power-monitoring units. DM6000 series digital panel meters. Technical data sheet

PowerLogic power-monitoring units. DM6000 series digital panel meters. Technical data sheet PowerLogic power-monitoring units digital panel meters Technical data sheet 2011 Authorized Distributor: WESCHLER INSTRUMENTS phone: 800-903-9870 440-378-6580 fax: 800-903-9590 440-238-0660 www.weschler.com

More information

Energy Management Energy Transducer Type ET112

Energy Management Energy Transducer Type ET112 Energy Management Energy Transducer Type Single phase energy transducer Class 1 (kwh according to EN62053-21 Class B (kwh according to EN50470-3 Accuracy ±0.5% RDG (current/voltage Direct current measurement

More information

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L

OHIO SEMITRONICS, INC. AC MULTIFUNCTION PROGRAMMABLE TRANSDUCERS & -1000L AC PROGRAMMABLE TRANSDUCERS MODBUS OR LONWORKS DESCRIPTION The DMT-1000 is a programmable transducer with an RS-485 bus interface (MODBUS ). It supervises several variables of a poly-phase electrical power

More information

A2000 Multifunctional Power Meter

A2000 Multifunctional Power Meter 3-348-980-03 3/12.99 Capable of communications via Profibus-DP, LONWORKS interface or RS 485 interface (depending upon model) Measurement of current, voltage, active, reactive and apparent power, power

More information

EM210 COMMUNICATION PROTOCOL. Version 3 Revision 1

EM210 COMMUNICATION PROTOCOL. Version 3 Revision 1 EM210 COMMUNICATION PROTOCOL Version 3 Revision 1 June 4 th, 2014 Index 1.1 Introduction...3 1.2 MODBUS functions...3 Function 03h (Read Holding Registers)...3 Function 04h (Read Input Registers)...4 Function

More information

EM300 Series. ET300 Series

EM300 Series. ET300 Series EM300 Series and ET300 Series COMMUNICATION PROTOCOL Version 2 Revision 11 Index 1.1 Introduction... 3 1.2 MODBUS functions... 3 1.2.1 Function 03h (Read Holding Registers)... 3 1.2.2 Function 04h (Read

More information

Type MVTT 14 and MVTT 15: Static Digital Time delay relays

Type MVTT 14 and MVTT 15: Static Digital Time delay relays Type MVTT 4 and MVTT 5: Static Digital Time delay relays Features 000/ setting range Time settings easily selected by means of thumbwheel switches Provide time delayed pick-up, or drop-off Compact construction

More information

IPD163C. Single-Phase Multifunction Meter User Manual Version: V1. August 20, 2017

IPD163C. Single-Phase Multifunction Meter User Manual Version: V1. August 20, 2017 163C Single-Phase Multifunction Meter User Manual Version: V1 August 20, 2017 This manual may not be reproduced in whole or in part by any means without the express written permission from IPD. The information

More information

Modbus Communications October Programming Meters fitted with the Modbus option have two additional stages in the front panel programming menu.

Modbus Communications October Programming Meters fitted with the Modbus option have two additional stages in the front panel programming menu. Modbus Communications October 2005 1 Programming Meters fitted with the Modbus option have two additional stages in the front panel programming menu. br 9600 Baud Rate Addr 25 Unique Modbus Address In

More information

EM21 COMMUNICATION PROTOCOL. Version 1 Revision 0

EM21 COMMUNICATION PROTOCOL. Version 1 Revision 0 EM21 COMMUNICATION PROTOCOL Version 1 Revision 0 April 7 th, 2008 Index 1.1 Introduction...3 1.2 MODBUS functions...3 1.2.1 Function 03h (Read Holding Registers)...3 1.2.2 Function 04h (Read Input Registers)...4

More information

8 data bits, least significant bit sent first 1 bit for even/odd parity (or no parity) 1 stop bit if parity is used; 1 or 2 bits if no parity

8 data bits, least significant bit sent first 1 bit for even/odd parity (or no parity) 1 stop bit if parity is used; 1 or 2 bits if no parity 1 Eastron SDM630 Smart Meter Modbus Protocol Implementation V1.2 1.1 Modbus Protocol Overview This section provides basic information for interfacing the Eastron Smart meter to a Modbus Protocol network.

More information

ASTAT XB/XBm Remote Operator

ASTAT XB/XBm Remote Operator ASTAT XB/XBm Remote Operator User Manual 1 Introduction 1.1 Important User Information Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery

More information

EM24-DIN PFA, PFB & X models

EM24-DIN PFA, PFB & X models EM24-DIN PFA, PFB & X models COMMUNICATION PROTOCOL Version 4 Revision 0 December 03 th, 2012 Index 1.1 Introduction...3 1.2 MODBUS functions...3 1.2.1 Function 03h (Read Holding Registers)...3 1.2.2 Function

More information

Technical Specifications. Multi Function Meter

Technical Specifications. Multi Function Meter Technical Specifications of Multi Function Meter (SPM300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email : info@spowerz.com

More information

GNM3D Series COMMUNICATION PROTOCOL. Version 1 Revision 0

GNM3D Series COMMUNICATION PROTOCOL. Version 1 Revision 0 GNM3D Series COMMUNICATION PROTOCOL Version 1 Revision 0 Index 1.1 1.2 Introduction... 3 MODBUS functions... 3 1.2.1 Function 03h (Read Holding Registers)... 3 1.2.2 Function 04h (Read Input Registers)...

More information

EPM g Energy. Multilin BUILDING AUTOMATION POWER METER. BACnet /IP Communications and Energy Measurement KEY BENEFITS APPLICATIONS FEATURES

EPM g Energy. Multilin BUILDING AUTOMATION POWER METER. BACnet /IP Communications and Energy Measurement KEY BENEFITS APPLICATIONS FEATURES Multilin EPM 6010 BUILDING AUTOMATION POWER METER BACnet /IP Communications and Energy Measurement KEY BENEFITS Rapid integration into BACnet management systems High accuracy multifunction power meter,

More information

Number. Number. Error Address. Check (Hi) Points. Points. (Hi)

Number. Number. Error Address. Check (Hi) Points. Points. (Hi) 1 MODBUS Protocol Message Format The MODBUS Protocol defines the format for the master s query and the slave s response. The query contains the device (or broadcast) address, a function code defining the

More information

RTU560. CT/VT Interface 560CVT10. Meter Operation. Application. Characteristics. Data Sheet CT/VT Interface 560CVT10. Instantaneous Meter Values

RTU560. CT/VT Interface 560CVT10. Meter Operation. Application. Characteristics. Data Sheet CT/VT Interface 560CVT10. Instantaneous Meter Values CT/VT Interface 560CVT10 The fault current is measured up to 20 times nominal current. Therefore the current inputs withstand 50 times nominal current for 1 s. The CT/VT interface is equipped with one

More information

EM210 COMMUNICATION PROTOCOL. Version 3 Revision 3

EM210 COMMUNICATION PROTOCOL. Version 3 Revision 3 EM210 COMMUNICATION PROTOCOL Version 3 Revision 3 November 13 th, 2015 Index 1.1 Introduction... 3 1.2 MODBUS functions... 3 Function 03h (Read Holding Registers)... 3 Function 04h (Read Input Registers)...

More information

C192PF8-RPR. Power Factor Manager & Reactive Power Regulator Reference Guide. Modbus. Communications Protocol. BG0348 Rev. A1

C192PF8-RPR. Power Factor Manager & Reactive Power Regulator Reference Guide. Modbus. Communications Protocol. BG0348 Rev. A1 C192PF8-RPR Power Factor Manager & Reactive Power Regulator Reference Guide Modbus Communications Protocol BG0348 Rev. A1 C192PF8-RPR POWER FACTOR MANAGER AND REACTIVE POWER REGULATOR COMMUNICATIONS Modbus

More information

SMARTRAIL X100 Protocol

SMARTRAIL X100 Protocol Smart Process & Control Ltd 11 Totman Close Brook Road Industrial Estate Rayleigh, Essex SS6 7UZ Customer Service: 01268 773422 www.smartprocess.co.uk SMARTRAIL X100 Protocol 1. SMARTRAIL X100 Protocol

More information

SKD-005-M Protocol. 2 RS485 General Information 2.1 Half Duplex 2.2 Connecting the Instruments 2.3 A and B terminals 2.

SKD-005-M Protocol. 2 RS485 General Information 2.1 Half Duplex 2.2 Connecting the Instruments 2.3 A and B terminals 2. Controlin BV Glasblazerstraat 1 2984 BL Ridderkerk Customer Service: +31 (0)180 330 522 www.controlin.nl SKD-005-M Protocol 1. SKD-005-M Protocol Implementation 1.1 Modbus Protocol Overview 1.2 Input register

More information

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S

DEIF A/S. MIC Multi-instrument G. Data sheet. Features. Accuracy. Measurements. Installation. Intelligent. Display. Communication DEIF A/S Multi-instrument 4921210107G Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Intelligent Suitable for all 3-phase network topologies Replaces transducers Accuracy U,

More information

SICAM P35 SICAM P36 3-phase Multi-Function Power Meter

SICAM P35 SICAM P36 3-phase Multi-Function Power Meter Preface SICAM P35 SICAM P36 3-phase Multi-Function Power Meter V1.30 Manual Content Overview 1 Technical Data 2 Functions 3 Operation and Display 4 Installation and Wiring 5 Communication 6 Maintenance

More information

DRS-100-3P MID Energy Meter Direct Connect, 100A, Three phase Communications Guide

DRS-100-3P MID Energy Meter Direct Connect, 100A, Three phase Communications Guide DRS-100-3P MID Energy Meter Direct Connect, 100A, Three phase Communications Guide Contents 1 DRS-100-3P - Modbus Protocol Implementation 3 1.1 Modbus Protocol Overview 3 1.2 Modbus Protocol Input Registers

More information

INTEGRA DL1 DUAL LOAD DIGITAL METER COMMUNICATIONS GUIDE DIGITAL ENERGY METER FOR MULTIPLE LOADS IN AN ELECTRICAL SYSTEM

INTEGRA DL1 DUAL LOAD DIGITAL METER COMMUNICATIONS GUIDE DIGITAL ENERGY METER FOR MULTIPLE LOADS IN AN ELECTRICAL SYSTEM DL1 INTEGRA DL1 DUAL LOAD DIGITAL METER COMMUNICATIONS GUIDE DIGITAL ENERGY METER FOR MULTIPLE LOADS IN AN ELECTRICAL SYSTEM Contents 1 Dual Load Digital meters Modbus Protocol implementation 3 1.1 Modbus

More information

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE

installation Operation ADDRESS product diagram H8030/8031 INSTALLATION GUIDE POWER MONITORING INSTALLATION GUIDE H8030/8031 H8030/8031 Modbus Energy Meter Networked kw/kwh Transducer Product Identification Model Max Amps CT Size Enhanced Data Stream Meters H8030-0100- 100 H8030-0300-

More information

EM24-DIN COMMUNICATION PROTOCOL. Version 3 Revision 1

EM24-DIN COMMUNICATION PROTOCOL. Version 3 Revision 1 EM24-DIN COMMUNICATION PROTOCOL Version 3 Revision 1 July 15 th, 2008 Index 1.1 Introduction... 3 1.2 MODBUS functions... 3 1.2.1 Function 03h (Read Holding Registers)...3 1.2.2 Function 04h (Read Input

More information

Smart Energy Meter. Benefits and Main Features. User Manual Revision English OB (100)A

Smart Energy Meter. Benefits and Main Features. User Manual Revision English OB (100)A User Manual Revision 2.001 English Smart Energy Meter OB737 0.5-10(100)A Benefits and Main Features Three phase metering Standard DIN rail Format (DIN43880) EN50470-3 Class B. IEC62053-21 Import & Export

More information

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2. Section 1.0 Introduction 1.1 Important user information... 2 1.2 General... 2 1.3 Manual description...2 Contents Section 2.0 Specification 2.1 General technical data...3 2.2 Dimensions...3 Section 3.0

More information

Multifuncion Measuring Device 96x96 mm, connection via CT

Multifuncion Measuring Device 96x96 mm, connection via CT Viale Borri 231, 21100 Varese Italy Multifuncion Measuring Device Contents Pages 1. Description Use... 2 2. Range... 2 3. Overall dimensions... 2 4. Preparation Connection... 2 5. General characteristics...

More information

AP25-3DO PROTOCOL. Modbus Guide - Issue 1.0 SUBJECT TO CHANGE WITHOUT NOTICE

AP25-3DO PROTOCOL. Modbus Guide - Issue 1.0 SUBJECT TO CHANGE WITHOUT NOTICE MODBUS PROTOCOL IMPLEMENTATION AP25-3DO www.sifamtinsley.co.uk NEW PRODUCT Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers

More information

Pulse concentrator, 12 inputs, 4 mod. DIN, with RS485 port

Pulse concentrator, 12 inputs, 4 mod. DIN, with RS485 port Viale Borri 231, 21100 Varese - Italy Pulse concentrator, 12 inputs, Contents Pages 1. Description - Use... 2 2. Range... 2 3. Overall dimensions... 2 4. Preparation - Connection... 2 5. General characteristics...

More information

EM132 EM132. Main Features. Multi-functional 3-Phase Transducer. Energy Meter

EM132 EM132. Main Features. Multi-functional 3-Phase Transducer. Energy Meter EM132 MULTI-FUNCTION TRANSDUCER SATEC EM132 is a Smart DIN Rail Multi-Function Transducer with a local display. It is based on SATEC s best seller PM130 PLUS with an off-the-shelf LCD display (similar

More information

PFC-10 Power Factor Controller

PFC-10 Power Factor Controller PFC-10 Power Factor Controller Instruction Manual Ver. 6.0 / 2002 (2-2005 update) Table of Contents Page Subject 3 Starter ion 4-5 Installation Notes 6-7 Terminals Review & Control Wiring 8 Front-panel

More information

4 Is this model available for special primary current and special primary voltage?

4 Is this model available for special primary current and special primary voltage? Category: Sales 1 Is it possible to exchange the backlights? The backlights are LED, no need to exchange. Fukuyama Works, Mitsubishi Electric Corporation March, 2018 2 Which standards does this model support?

More information

TNY Series-Multifunction Panel Meter

TNY Series-Multifunction Panel Meter PROCOM TNY Series-Multifunction Panel Meter Rev.-01 TNY Series-Multifunction Panel Meter 1. Introduction : INDEX 2. Features : 3. Model Selection : 4. Specification : 5. Integer Flow : 6. Auxiliary Supply

More information

PM130 Powermeters Reference Guide Modbus Communications Protocol

PM130 Powermeters Reference Guide Modbus Communications Protocol PM130 Powermeters Reference Guide Modbus Communications Protocol BG0310 Rev. A1 SERIES PM130 POWERMETERS COMMUNICATIONS Modbus Communications Protocol REFERENCE GUIDE Every effort has been made to ensure

More information

SERIES PM130EH POWERMETERS COMMUNICATIONS REFERENCE GUIDE

SERIES PM130EH POWERMETERS COMMUNICATIONS REFERENCE GUIDE SERIES PM130EH POWERMETERS COMMUNICATIONS ASCII Communications Protocol REFERENCE GUIDE Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer

More information

Carbon Monoxide Sensor - ModBus

Carbon Monoxide Sensor - ModBus Introduction The CO Sensor uses an electrochemical sensor to monitor CO level in a range of 0 to 500 ppm and communicates via an RS-485 network configured for ModBus protocol. Before Installation Read

More information

DATA SHEET. Advanced Power Meter, APM 380 & APM 305

DATA SHEET. Advanced Power Meter, APM 380 & APM 305 DATA SHEET Advanced Power Meter, APM 380 & APM 305 Easy installation Monitors all 3 phases 5 optional communication interfaces Phase error detection Low power consumption Two-pulse output DEIF A/S Frisenborgvej

More information

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS

ENERCEPT H8035/H8036 DANGER NOTICE CAUTION. Networked Power Transducer (Modbus RTU) INSTALLATION GUIDE QUICK INSTALL TABLE OF CONTENTS POWER MONITORING ENERCEPT Networked Power Transducer (Modbus RTU) DANGER US Patent No. 6,373,238 HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in

More information

EM24-DIN COMMUNICATION PROTOCOL. Version 3 Revision 0

EM24-DIN COMMUNICATION PROTOCOL. Version 3 Revision 0 EM24-DIN COMMUNICATION PROTOCOL Version 3 Revision 0 March 25 th, 2008 Index 1.1 Introduction...3 1.2 MODBUS functions...3 1.2.1 Function 03h (Read Holding Registers)...3 1.2.2 Function 04h (Read Input

More information

Energy Management BUS Adapter Type VMU-B 01

Energy Management BUS Adapter Type VMU-B 01 Energy Management BUS Adapter Type VMU-B 01 RS485 (Modbus) to M-Bus communication adapter EM21-72D, EM24-DIN and EM33-DIN self recognition Front diagnostic LED s Universal 18 to 260 VAC/DC power supply

More information

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description

ILBPB24DO32. Inline Block IO Module for PROFIBUS With 32 Digital Outputs. AUTOMATIONWORX Data Sheet 6889_en_04. Description Inline Block IO Module for PROFIBUS With 32 Digital Outputs AUTOMATIONWORX Data Sheet 6889_en_04 Description PHOENIX CONTACT - 03/2007 & & ' ) The ILB PB 24 DO32 module is designed for use within a PROFIBUS

More information

DNP3 Communications Protocol

DNP3 Communications Protocol Powermeter and Power Quality Analyzer PM174 DNP3 Communications Protocol Reference Guide BG0413 Rev. A3 Every effort has been made to ensure that the material herein is complete and accurate. However,

More information

DPT300 transducer range. Technical reference manual BGX R01

DPT300 transducer range. Technical reference manual BGX R01 DPT300 transducer range Technical reference manual BGX701-015-R01 Copyright 2016, SIHPL Page 2 of 40 BGX701-015-R01, User manual for DPT300 transducers Public Table of Contents 1 Preface... 5 1.1 Purpose

More information

Electronic timer CT-AHD.22

Electronic timer CT-AHD.22 2CDC 251 093 F0t06 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied

More information

Electronic Submeter with Advanced WiFi Ethernet Capability

Electronic Submeter with Advanced WiFi Ethernet Capability SH RK 100S Electronic Submeter with Advanced WiFi Ethernet Capability AGGRESSIVE TECHNOLOGY W NEIndustry Leading Technology High Performance Metering Technology 0.2% Accuracy Class Revenue Certifiable

More information

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature

More information

Technical Specifications. Dual Source Energy Meter (EB / DG)

Technical Specifications. Dual Source Energy Meter (EB / DG) Technical Specifications of Dual Source Energy Meter (EB / DG) (SPMG300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com

More information

Power Meter PowerMonitor 500

Power Meter PowerMonitor 500 ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION PowerMonitor 500 NOTICE: The specification guidelines in this document are intended to aid in the specification of products. Specific

More information

Jewell DPM PGDA/PGDV/PGD3A/PGD3V BEST IN CLASS

Jewell DPM PGDA/PGDV/PGD3A/PGD3V BEST IN CLASS Application: Salient Features: The digital panel meters have been Fast and easy installation on panel without designed for industrial applications, any need of external swivel screws (clip-in which frequently

More information

Metering Devices IQ 300

Metering Devices IQ 300 Effective: May 2001 Page 1 New Information Contents Description Page General Description......... 2 Specifications.............. 3 Field Wiring Connections.... 4 Page 2 Effective: May 2001 Applications

More information

EM270. Multi-channel power analyzer. Benefits. Description

EM270. Multi-channel power analyzer. Benefits. Description Multi-channel power analyzer Description Multi-circuit power analyzer for single or threephase systems installable on panels or DIN rails. Manages current input via two current transformer blocks connected

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/ O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/ O Main Range of product Product or component type Discrete output type Device short name Nominal output current Zelio Time Modular timing

More information

Copyright: December 2017 Nidec Issue: E

Copyright: December 2017 Nidec Issue: E General Information The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent or incorrect installation or adjustment of the optional parameters of the equipment

More information

EM26-96 COMMUNICATION PROTOCOL. Version 1 Revision 0

EM26-96 COMMUNICATION PROTOCOL. Version 1 Revision 0 EM26-96 COMMUNICATION PROTOCOL Version 1 Revision 0 February 5 th, 2007 Index 1.1 Introduction...3 1.2 MODBUS functions...3 1.2.1 Function 03h (Read Holding Registers)... 3 1.2.2 Function 04h (Read Input

More information

Universal Power Supplies

Universal Power Supplies , Features Universal input: 90 264 VAC or 120 30 VDC Active power factor correction (>0.95) High efficiency up to 93% Load share function for up to 3 units in parallel Adjustable output voltage EMI/EMC

More information

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

CEM M-RS485 INSTRUCTION MANUAL (M014B A) Communications interface CEM M-RS485 INSTRUCTION MANUAL (M014B01-03-14A) 2 SAFETY PRECAUTIONS Follow the warnings described in this manual with the symbols shown below. DANGER Warns of a risk, which could

More information

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O

RE22R1QMQ star-delta timing relay - 230VAC/440VAC - 1 C/O Characteristics star-delta timing relay - 230VAC/440VAC - 1 C/O Main Range of product Product or component type Discrete output type Device short name Nominal output current Complementary Contacts type

More information

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information