houle electric limited # Devonshire Road, Victoria V9A 4T5 TEL: (250) FAX (250) TRANSMITTAL

Size: px
Start display at page:

Download "houle electric limited # Devonshire Road, Victoria V9A 4T5 TEL: (250) FAX (250) TRANSMITTAL"

Transcription

1 houle electric limited # Devonshire Road, Victoria V9A 4T5 TEL: (250) FAX (250) TRANSMITTAL To: Windly Contracting Ltd. Date: March 29, 2006 Attn: Cliff Thompson Page(s): 1 Address: 3711 Shenton Road Nanaimo, BC V9T 2H1 Project: SCHOOL OF MGT CENTRE, MALASPINA Job No.: We transmit: Action Required: Via Courier Drawings For Your Information Via Mail Shop Drawings Review & Comment Via Fax Correspondence Returned As Requested Via Hand Other As Noted Copies: Description: 1 Control shop drawings in hard and soft format Joe LeRoy, P.Eng. Controls Project Manager/Estimator HOULE ELECTRIC LIMITED THE POWER IN ELECTRICAL CONTRACTING Building Strength Through Successful Partnerships OPERATING THROUGHOUT WESTERN CANADA SINCE 1944 CORPORATE HEAD OFFICE VANCOUVER BRANCH OFFICES IN NANAIMO PRINCE GEORGE VICTORIA

2 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: &2.8 Description: Valve Schedule Model: Supplier info: Address: Manufacturer info: Address: Website

3 Level 1 VAV Valve L/s GPM PD Type Return Fail Design CV 3/29/2006 Actual CV Size Model Actuator 1 VAV m non-spring b210 tr24-sr-t us 2 VAV m non-spring b211 tr24-sr-t us 3 VAV m non-spring b210 tr24-sr-t us 4 VAV m non-spring b215 tr24-sr-t us 5 VAV m non-spring b311 tr24-sr-t us 6 VAV m non-spring b209 tr24-sr-t us 7 VAV m non-spring b310 tr24-sr-t us 8 VAV m non-spring b210 tr24-sr-t us 9 VAV m non-spring b209 tr24-sr-t us Level 2 VAV Valve L/s GPM PD Type Return Fail Design CV Actual CV Size Model Actuator 10 VAV m non-spring b210 tr24-sr-t us 11 VAV m non-spring b210 tr24-sr-t us 12 VAV m non-spring b211 tr24-sr-t us 13 VAV m non-spring b310 tr24-sr-t us 14 VAV m non-spring b310 tr24-sr-t us 15 VAV m non-spring b209 tr24-sr-t us 16 VAV m non-spring b210 tr24-sr-t us 17 VAV m non-spring b210 tr24-sr-t us 18 VAV m non-spring b211 tr24-sr-t us Level 3 VAV Valve L/s GPM PD Type Return Fail Design CV Actual CV Size Model Actuator 19 VAV m non-spring b311 tr24-sr-t us 20 VAV m non-spring b209 tr24-sr-t us 21 VAV m non-spring b209 tr24-sr-t us 22 VAV m non-spring b209 tr24-sr-t us 23 VAV m non-spring b209 tr24-sr-t us 24 VAV m non-spring b207 tr24-sr-t us 25 VAV m non-spring b209 tr24-sr-t us 26 VAV m non-spring b209 tr24-sr-t us 27 VAV m non-spring b309 tr24-sr-t us 28 VAV m non-spring b207 tr24-sr-t us 29 VAV m non-spring b207 tr24-sr-t us 30 VAV m non-spring b208 tr24-sr-t us Level 4 VAV Valve L/s GPM PD Type Return Fail Design CV Actual CV Size Model Actuator 31 VAV m non-spring b208 tr24-sr-t us 32 VAV m non-spring b209 tr24-sr-t us 33 VAV m non-spring b209 tr24-sr-t us 34 VAV m non-spring b210 tr24-sr-t us 35 VAV m non-spring b207 tr24-sr-t us 36 VAV m non-spring b209 tr24-sr-t us 37 VAV m non-spring b209 tr24-sr-t us 38 VAV m non-spring b309 tr24-sr-t us 39 VAV m non-spring b310 tr24-sr-t us 40 VAV m non-spring b207 tr24-sr-t us 41 VAV m non-spring b209 tr24-sr-t us 42 VAV m non-spring b215 tr24-sr-t us 43 VAV m non-spring b209 tr24-sr-t us 44 VAV m non-spring b209 tr24-sr-t us Convectors Valve L/s GPM PD Type Return Fail Design CV Actual CV Size Model Actuator 45 CNVT m non-spring b207 tr24-sr-t us 46 CNVT m non-spring b207 tr24-sr-t us 47 CNVT m non-spring b207 tr24-sr-t us 48 CNVT m non-spring b207 tr24-sr-t us 49 CNVT m non-spring b207 tr24-sr-t us 50 CNVT m non-spring b207 tr24-sr-t us 51 CNVT m non-spring b207 tr24-sr-t us 52 CUH m spring open b210 tr24-sr-t us MISC Valve L/s GPM PD Type Return Fail Design CV Actual CV Size Model Actuator 53 2ndry mix m spring atoab g765 af24-mft us 54 trap p spring close ZONE215N-35 ZONE24NC 55 trap p spring close ZONE215N-36 ZONE24NC 56 trap p spring close ZONE215N-37 ZONE24NC 57 trap p spring close ZONE215N-38 ZONE24NC 58 trap p spring close ZONE215N-39 ZONE24NC Malaspina School of Mgt Pts List 29Mar06.xls Control Valve Schedule 1 of 1

4 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: &2.8 Description: 65mm 3-way mod spring return characterized control valve Model: G765 c/w AF24-MFT US Supplier info: Address: Manufacturer info: Address: Website Belimo Aircontrols (CAN), Inc Yeomans Cres., Langley, BC V1M 2P8 Belimo Aircontrols (CAN), Inc Yeomans Cres., Langley, BC V1M 2P8

5 G7 Series Flanged Globe Valve, Spring Return Actuator Three-way Valve with Bronze Trim ANSI 125 Flanged, Mixing and Diverting AF 2x AF G7 Three-way Mixing Flanged Globe Valve with Spring Return Actuator Valve Spring Return Actuator Model C v Valve On/Off Proportional / MFT # Nominal Size Close- Flanged Off AF24 US AF24-MFT US Valve Inches Type psi 2x AF24 US 2x AF24-MFT US G /2 ANSI Pg 68 Pg 68 G ANSI Pg 68 Pg 68 G ANSI Pg 68 Pg 68 G /2 ANSI Pg 68 Pg 68 G ANSI Pg 68 Pg 68 G ANSI Pg 68 Pg 68 G ANSI Pg 68 Pg 68 G ANSI Pg 68 Pg 68 Specify when ordering proportional (P-10001) 2-10 VDC, floating point (P-30001), on/off (P-40002) for AF actuators. AF24 US 2x AF24 US AF24-MFT US 2x AF24-MFT US G /05 - Subject to change. Belimo Aircontrols (USA), Inc. G7 D Three-way Diverting Flanged Globe Valve with Spring Return Actuator Valve Spring Return Actuator Model C v Valve On/Off Proportional / MFT # Nominal Size Close- Flanged Off AF24 US AF24-MFT US Valve Inches Type psi 2x AF24 US 2x AF24-MFT US G765D /2 ANSI Pg 80 Pg 80 G780D 85 3 ANSI Pg 80 Pg 80 G7100D ANSI Pg 80 Pg 80 G7125D ANSI Pg 80 Pg 80 G7150D ANSI Pg 80 Pg 80 For fail safe operation where AF actuator is not available or close-off is too low, use GM actuator with NSV battery backup. Specify when ordering proportional (P-10001) 2-10 VDC, floating point (P-30001), on/off (P-40002) for AF actuators. AF24 US 2x AF24-MFT US 2x Options (add to list price) AF24 US AF24-MFT US 2x AF24 US 2x AF24-MFT US built-in aux. switch* AF -S US 120 VAC power supply AF Ω control AF24-MFT95 US * For tandem actuators only one of the two actuators is provided with switch. Add to -MFT price. 19

6 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: &2.8 Description: 12mm 2-way mod non-spring return characterized control valve Model: B207 to B215 c/w TR24-SR-T US Supplier info: Address: Manufacturer info: Address: Website Belimo Aircontrols (CAN), Inc Yeomans Cres., Langley, BC V1M 2P8 Belimo Aircontrols (CAN), Inc Yeomans Cres., Langley, BC V1M 2P8

7 B2 Series Characterized Control Valve, Non-Spring Return Actuator Two-way Valve with Stainless Steel Ball and Stem, NPT female ends TR LR NM AM B2 Two-way Characterized Control Valve, Stainless Steel Ball and Stem Valve NM24 US Non-Spring Return Actuator On/Off, Floating On/Off, Floating Proportional Proportional Proportional / MFT Model Cv Valve Close- # Rating Nominal Size Off LR24-3 US LR24-SR US LR24-MFT US CCV DN psi TR24-3-T US NM24 US TR24-SR-T US NM24-SR US NM24-MFT US Valve Inches mm AM24 US AM24-MFT US B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B215* 10 1/ Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B / Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B220* 24 3/ Pg 40 Pg 44 Pg 42 Pg 46 Pg 48 B Pg 44 Pg 46 Pg 48 B Pg 44 Pg 46 Pg 48 B Pg 44 Pg 46 Pg 48 B225* Pg 44 Pg 46 Pg 48 B / Pg 44 Pg 46 Pg 48 B230* / Pg 44 Pg 46 Pg 48 B / Pg 50 Pg 52 Pg 54 B232* / Pg 50 Pg 52 Pg 54 B / Pg 50 Pg 52 Pg 54 B / Pg 50 Pg 52 Pg 54 B240* / Pg 50 Pg 52 Pg 54 B Pg 50 Pg 52 Pg 54 B Pg 50 Pg 52 Pg 54 B250* Pg 50 Pg 52 Pg 54 B Pg 56 Pg 58 B Pg 56 Pg 58 B Pg 56 Pg 58 B254* Pg 56 Pg 58 B Pg 56 Pg 58 B Pg 56 Pg 58 B Pg 56 Pg 58 B Pg 56 Pg 58 B265* Pg 56 Pg 58 B Pg 56 Pg 58 B Pg 56 Pg 58 B280* Pg 56 Pg 58 Electrical Covered 3 ft cable, Covered Terminal 3 ft cable, 3 ft cable, Connection Terminal Strip 1/2 conduit Strip 1/2 conduit 1/2 conduit fitting fitting fitting * Models without characterizing discs. See pg 11 for corrected C v s with piping reduction factor. See pg 132 for MFT Configuration. TR24-3-T US LR24-3 US AM24 US TR24-SR-T US LR24-SR US NM24-SR US LR24-MFT US NM24-MFT US AM24-MFT US G /05 - IG-Subject to change. Belimo Aircontrols (USA), Inc. TR24-3-T US Options (add to list price) TR24-SR-T US LR24-3 US built-in aux. switch LR -S US Pg 44 3-foot cable TR24-3 US, TR24-SR US Pg 40/42 6-foot cable TR /200 US, LR /200 US Pg 40/42 Pg foot cable TR /300 US, LR /300 US Pg 40/42 Pg 44 14

8 B2 Two-way Characterized Control Valve, Stainless Steel Ball and Stem TR Actuators, Proportional Technical Data/Submittal Application This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV Box reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable flow. This valve is designed for modulating control using VDC or mA. (for mA control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 24 VAC/VDC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic A port equal percentage Action Max 95 rotation Sizes 1/2, 3/4 Type of end fitting female, NPT Materials: Body forged brass, nickel plated Ball stainless steel Stem stainless steel Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing 2 EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to 212 F [-18 C to 100 C] Close off pressure 200 psi Maximum differential: For Characterized A-port pressure ( P) 20 psi for typical applications 30 psi max for quiet service For full flow versions only (no A-disc) On/Off control 150 psi Leakage 0% Cv rating A port: see product chart for values Tefzel is a registered trademark of DuPont Actuator Specifications TR24-SR-T US Reversing switch under cover Control Proportional Input Impedance 100 kω Nominal voltage 24 VAC 50/60 Hz, 24VDC Nominal voltage range VAC, VDC Power Consumption 0.5 W Transformer Sizing 1VA (Class 2 power source) Electrical Connection Screw Terminals accessible after removal of small cover (3 ft, 6 ft, 10 ft cables optional) Angle of Rotation 90 Torque 18 in-lbs (2Nm) Position Indication Integrated into handle Manual override: Push down handle Running Time 90 seconds Humidity 5 to 95% non-condensing Ambient Temperature 19 F to 122 F (-7 C to +50 C) Storage Temperature -40 F to 176 F (-40 C to +80 C) Housing NEMA 1 Housing Rating UL94-5V(B) Agency Listing CE, UL EMC CE according to 89/336/EEC Mode of Operation Type 1 to UL Noise Level max. 35 db (A) Quality Standard ISO 9001 Additional Models TR24-SR US TR24-SR-T US with 3 ft plenum rated cable TR24-SR/200 US TR24-SR-T US with 6 ft plenum rated cable TR24-SR/300 US TR24-SR-T US with 10 ft plenum rated cable G /05 - IG-Subject to change. Belimo Aircontrols (USA), Inc. 42 See Selection Chart Pg 14 for Control Valve No., C v and Close-off

9 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: &2.8 Description: 12mm 3-way mod non-spring return characterized control valve Model: B309 to B311 c/w TR24-SR-T US Supplier info: Address: Manufacturer info: Address: Website Belimo Aircontrols (CAN), Inc Yeomans Cres., Langley, BC V1M 2P8 Belimo Aircontrols (CAN), Inc Yeomans Cres., Langley, BC V1M 2P8

10 B3 Series Characterized Control Valve, Non-Spring Return Actuator Three-way Valve with Stainless Steel Ball and Stem, NPT female ends TR LR NM G /05 - IG-Subject to change. Belimo Aircontrols (USA), Inc. B3 Three-way Characterized Control Valve, Stainless Steel Ball and Stem Valve Non-Spring Return Actuator Model Cv Valve On/Off, Floating On/Off, Floating Proportional Proportional Proportional / MFT # Rating Nominal Size Close- CCV DN Off TR24-3-T US LR24-3 US TR24-SR-T US LR24-SR US LR24-MFT US Valve Inches mm psi NM24 US NM24-SR US NM24-MFT US B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B315* 10 1/ Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B / Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B320* 24 3/ Pg 60 Pg 64 Pg 62 Pg 66 Pg 68 B Pg 64 Pg 66 Pg 68 B Pg 64 Pg 66 Pg 68 B325* Pg 64 Pg 66 Pg 68 B / Pg 64 Pg 66 Pg 68 B330* / Pg 64 Pg 66 Pg 68 B / Pg 70 Pg 72 Pg 74 B332* / Pg 70 Pg 72 Pg 74 B / Pg 70 Pg 72 Pg 74 B / Pg 70 Pg 72 Pg 74 B340* / Pg 70 Pg 72 Pg 74 B Pg 70 Pg 72 Pg 74 B Pg 70 Pg 72 Pg 74 B350* Pg 70 Pg 72 Pg 74 Electrical Covered 3 ft cable, Covered Terminal 3 ft cable, 3 ft cable, Connection Terminal Strip 1/2 conduit Strip 1/2 conduit 1/2 conduit fitting fitting fitting * Models without characterizing discs. See pg 132 for MFT Configuration. TR24-3-T US LR24-3 US NM24 US TR24-SR-T US LR24-SR US NM24-SR US LR24-MFT US NM24-MFT US TR24-3-T US Options (add to list price) TR24-SR-T US LR24-3 US built-in aux. switch LR -S US Pg 64 3-foot cable TR24-3 US, TR24-SR US Pg 60/62 6-foot cable TR /200 US, LR /200 US Pg 60/62 Pg foot cable TR /300 US, LR /300 US Pg 60/62 Pg 64 15

11 B3 Three-way Characterized Control Valve, Stainless Steel Ball and Stem TR Actuators, Proportional Technical Data/Submittal Application This valve is typically used in air handling units on heating or cooling coils, and fan coil unit heating or cooling coils. Some other common applications include Unit Ventilators, VAV Box reheat coils and bypass loops. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed for modulating control using VDC or mA. (for mA control input a 500 ohm resistor is required). The valve is designed to fit in compact areas where proportional control is required using 24 VAC/VDC. Valve Specifications Service chilled or hot water, 60% glycol Flow characteristic A port equal percentage B port modified linear for constant AB flow Action Max 95 rotation Sizes 1/2, 3/4 Type of end fitting female, NPT Materials: Body forged brass, nickel plated Ball stainless steel Stem stainless steel Seats fiberglass reinforced teflon PTFE Characterizing disc TEFZEL Packing 2 EPDM O-rings, lubricated Pressure rating 600 psi Media temp. range 0 F to 212 F [-18 C to 100 C] Close off pressure 200 psi Maximum differential: For Characterized A-port pressure ( P) 20 psi for typical applications 30 psi max for quiet service For full flow versions only (no A-disc) On/Off control 150 psi Leakage A port: 0% B port: 0.5% - 2% of full rated CV AB port: 0% Cv rating A port: see product chart for values B port: 70% of A port flow Tefzel is a registered trademark of DuPont Actuator Specifications TR24-SR-T US Reversing switch under cover Control Proportional Input Impedance 100 kω Nominal voltage 24 VAC 50/60 Hz, 24VDC Nominal voltage range VAC, VDC Power Consumption 0.5 W Transformer Sizing 1VA (Class 2 power source) Electrical Connection Screw Terminals accessible after removal of small cover (3 ft, 6 ft, 10 ft cables optional) Angle of Rotation 90 Torque 18 in-lbs (2Nm) Position Indication Integrated into Handle Manual override: Push down handle Running Time 90 seconds Humidity 5 to 95% non-condensing Ambient Temperature 19 F to 122 F (-7 C to +50 C) Storage Temperature -40 F to 176 F (-40 C to +80 C) Housing NEMA 1 Housing Rating UL94-5V(B) Agency Listing CE, UL EMC CE according to 89/336/EEC Mode of Operation Type 1 to UL Noise Level max. 35 db (A) Quality Standard ISO 9001 Additional Models TR24-SR US TR24-SR-T US with 3 ft plenum rated cable TR24-SR/200 US TR24-SR-T US with 6 ft plenum rated cable TR24-SR/300 US TR24-SR-T US with 10 ft plenum rated cable G /05 - IG-Subject to change. Belimo Aircontrols (USA), Inc. 62 See Selection Chart Pg 15 for Control Valve No., C v and Close-off

12 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: &2.8 Description: 12mm 2-way 2 pos'n spring return zone valve Model: ZONE215N-35 Supplier info: Address: Manufacturer info: Address: Website Belimo Aircontrols (CAN), Inc Yeomans Cres., Langley, BC V1M 2P8 Belimo Aircontrols (CAN), Inc Yeomans Cres., Langley, BC V1M 2P8

13 Electronic Zone Valves, Spring Return Actuator Two-way and Three-way valves with NPT or sweat ends Valve Actuator Nominal Close- 24 V 24 V 120 V 120 V Model # C v Size off Normally Closed Normally Open Normally Closed Normally Open Valve Rating Inches mm (psi) ZONE24NC ZONE24NO ZONE120NC ZONE120NO Two-way with NPT Female Connection ZONE215N / Pg 10 Pg 10 Pg 10 Pg 10 ZONE215N / Pg 10 Pg 10 Pg 10 Pg 10 ZONE215N / Pg 10 Pg 10 Pg 10 Pg 10 ZONE220N / Pg 10 Pg 10 Pg 10 Pg 10 ZONE220N / Pg 10 Pg 10 Pg 10 Pg 10 ZONE225N Pg 10 Pg 10 Pg 10 Pg 10 ZONE24NC ZONE24NO ZONE120NC ZONE120NO Three-way with NPT Female Connection ZONE315N / Pg 10 Pg 10 ZONE315N / Pg 10 Pg 10 ZONE24NC ZONE315N / Pg 10 Pg 10 ZONE320N / Pg 10 Pg 10 ZONE320N / Pg 10 Pg 10 ZONE325N Pg 10 Pg 10 Two-way with Sweat Connection ZONE215S / Pg 10 Pg 10 Pg 10 Pg 10 ZONE215S / Pg 10 Pg 10 Pg 10 Pg 10 ZONE24NC ZONE215S / Pg 10 Pg 10 Pg 10 Pg 10 ZONE220S / Pg 10 Pg 10 Pg 10 Pg 10 ZONE220S / Pg 10 Pg 10 Pg 10 Pg 10 ZONE225S Pg 10 Pg 10 Pg 10 Pg 10 Three-way with Sweat Connection ZONE315S / Pg 10 Pg 10 ZONE315S / Pg 10 Pg 10 ZONE24NC ZONE315S / Pg 10 Pg 10 ZONE320S / Pg 10 Pg 10 ZONE320S / Pg 10 Pg 10 ZONE325S Pg 10 Pg 10 Built-in auxiliary switch ZONE215N-10+ZONE24NC-S Pg 10 Pg 10 Pg 10 Pg 10 (add -S to model number) ZONE24NO ZONE120NC ZONE120NC ZONE120NC ZONE120NO H /05 - Subject to change. Belimo Aircontrols (USA), Inc. Three-way valve can be NC or NO depending on installation always using the NC actuator. See technical literature for details. 8

14 Electronic Zone Valves ZONE Series Technical Data/Submittal Application This valve is typically used on fan coil units, baseboards or other hydronic applications where fail safe operation or 2-wire control is required. This valve is suitable for use in a hydronic system with variable or constant flow. This valve is designed to fit in compact areas where on/off or control is required using 24 VAC or 120 VAC. Valve Specifications Service chilled or hot water, 50% glycol Flow characteristic Two-way on/off Three-way on/off, diverting Sizes 1/2, 3/4 and 1 Type of end fitting female, NPT or Sweat Materials: Body forged brass Stem stainless steel Seals EPDM Pressure rating 300 psi Media temp. range 32 F to 212 F [0 C to 100 C] Close off pressure psi Leakage Class III 0.1% Cv rating U.S. & Foreign Patent Pending Actuator Specifications Control On/off Nominal voltage 24 VAC 50/60 Hz ± 10% or 120 VAC 50/60 Hz ± 10% Power Consumption 6.5 W Transformer Sizing 7VA (Class 2 power source) Electrical Connection Wire lead length, 120V 6 24V 18 Position Indication Integrated into lever (NC only) Running Time Motor: seconds Spring: 5 seconds Humidity 5 to 95% non-condensing Ambient Temperature 32 F to 104 F (0 C to + 40 C) Storage Temperature -40 F to 176 F (-40 C to +80 C) Housing Rating UL94-5V(B) Agency Listing CE, culus Noise Level max. 35 db (A) Quality Standard ISO 9001 Built-in Auxiliary Switch 1 x SPDT, 5A resistive (5A inductive) 24 VAC 1 x SPDT, 5A resistive (5A 120 VAC H /05 - Subject to change. Belimo Aircontrols (USA), Inc. 10

15 Electronic Zone Valves Installation Installation The valve can be installed vertically or horizontally, but not turned upside down. 360 A 3-way valve cannot be transformed into a 2-way valve and visa versa. The flow is from A to B (see diagram below) and must be installed so the paddle closes against the direction of flow as indicated in the following diagrams. The 2-way valves can be installed on the supply or on the return; for correct installation it is necessary to respect the direction of flow indicated from the arrow on the body valve. (NO) B A (NC) AB 3-way valve normally closed actuator (Note: 3-way uses only normally closed actuator) A B B A AB Load H /05 - Subject to change. Belimo Aircontrols (USA), Inc. 2-way valve normally closed actuator A B B A Load 2-way installed on the supply Load 2-way installed on the return 3-way installed on the supply in diverting configuration B AB 3-way installed on the return A 2-way Load 3-way Port A closed N.C. without power Port A closed Port B open Port AB open N.C. open with power Port A open Port A open Port B closed Port AB open N.C. manually open Port A open Port A open Port B open Port AB open 9

16 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Room temperature sensor Model: TE200AD7 Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

17 ISO 9002 Q M I SPACE/WALL MOUNT FEATURES: The TE Series Space Temperature sensors are available in four different enclosure styles. They are available with a choice of precision RTD s, IC s, or thermistors. A number of options, such as momentary override and setpoint adjustment are also available for various configurations. A transmitter option is also available to be used with the 1000 ohm platinum sensor which provides either 4-20mA, 0 5 VDC or 0 10 VDC output proportional to a selected temperature span. A 100 ohm platinum sensor transmitter is optional. TRANSMITTER: stability, low hysteresis, fast response and a wide operating temperature range. Every transmitter offers accuracy of 0.1% of span or better and are highly stable due to excellent RFI rejection and are also virtually immune to power supply noise and input voltage fluctuations. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 20mA, 0 5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0 C 70 C (32 F 158 F) Calibration In compliance with ANSI/NCSL The transmitters provide high accuracy, long-term Display Type LCD Display LED Display Power Supply VAC/DC at 2mA max VAC/DC at 30mA max Display Units C or F (factory set) C or F (jumper selectable) Display Range C ( F) C ( F) Display Resolution 0.1 C (0.1 F) 0.5 C (1.0 F) Display Size 23 mm W x 11 mm H (0.9 W x 0.45 H) 3 digit x 30 mm W x 7.6 mm H (1.18 W x 0.3 H) Available Options Various sensors, set points, push buttons, external jacks, and logos. A) Micro Includes a compact snap-mounted cover for ease of installation, available with various temperature sensors. AD) Designer Features include a three-piece enclosure that mounts directly to a wall box or on any wall. Available with various options. Including set point adjustments, push button overrides, etc. AS) Surface - A stainless steel plate which can be mounted to a wall box used where tamper-proof or protection is required. Available with various options, including push button overrides, etc. GREYSTONE ENERGY SYSTEMS INC.

18 ISO 9002 Q M I SPACE TEMPERATURE SENSORS/TRANSMITTERS: PRODUCT ORDERING INFORMATION MODEL TE200 TE500 Product Description Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard) CODE A AD AS Enclosure Micro (not available with transmitter or options) Designer S/S plate CODE Sensor PT ohm Platinum, IEC 751, 385 Alpha, thin film 1801 ohm, NTC Thermistor, ±0.2 C 3,000 ohm, NTC Thermistor, ±0.2 C 10,000 ohm, type 3, NTC Thermistor, ±0.2 C K ohm NTC Thermistor, ±0.2 C 100,000 ohm, NTC Thermistor, ±0.2 C LM334 IC, 1.0uA/ C PT ohm Platinum, IEC 751, Alpha, thin film 1000 ohm nickel 10,000 ohm type 3, NTC Thermistor, ±0.2 C c/w 11k shunt resistor 20,000 ohm, NTC Thermistor, ±0.2 C LM335 IC, 10mv/ C 10,000 ohm, type 2, NTC Thermistor, ±0.2 C CODE AP AS BS AM BC BF AC AF LY LR LG CJ AE AI Options (TE200AD assembly only) 20-30K linear slide pot for set point control Concealed push button momentary switch (NO) Exposed push button momentary switch (NO) Alcohol thermometer C & F Bi-metal thermometer C Bi-metal thermometer F 3-digit LCD temperature indicator C 3-digit LCD temperature indicator F Yellow LED Red LED Green LED External jack for remote system access (phono jack) External jack for remote system access (4-pin header) Internal jack (RJ-45) CODE TE500 Transmitter Power Supply 1 24 VAC/DC CODE A D E TE500 Transmitter Output Option Current 4 20mA Voltage 0 5 VDC Voltage 0 10 VDC CODE TE500 Transmitter Range Option C 35 C (32 F 95 F) 0 C 50 C (32 F 122 F) TE500 AD 12-1 A 2 Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. NOTE: Due to the many possible configurations, special part numbers may be required, please contact Greystone for more information. GREYSTONE ENERGY SYSTEMS INC. EXAMPLE: Designer space, c/w PT1000Ω RTD, 4 20mA transmitter with a 0 C 50 C (32 F 122 F) range.

19 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Room temperature sensor c/w two button adjust Model: RT Supplier info: Address: Manufacturer info: Address: Website Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R11 Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R11

20

21

22 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Room temperature sensor S/S plate Model: TE200AS7 Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

23 ISO 9002 Q M I SPACE/WALL MOUNT FEATURES: The TE Series Space Temperature sensors are available in four different enclosure styles. They are available with a choice of precision RTD s, IC s, or thermistors. A number of options, such as momentary override and setpoint adjustment are also available for various configurations. A transmitter option is also available to be used with the 1000 ohm platinum sensor which provides either 4-20mA, 0 5 VDC or 0 10 VDC output proportional to a selected temperature span. A 100 ohm platinum sensor transmitter is optional. TRANSMITTER: stability, low hysteresis, fast response and a wide operating temperature range. Every transmitter offers accuracy of 0.1% of span or better and are highly stable due to excellent RFI rejection and are also virtually immune to power supply noise and input voltage fluctuations. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 20mA, 0 5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0 C 70 C (32 F 158 F) Calibration In compliance with ANSI/NCSL The transmitters provide high accuracy, long-term Display Type LCD Display LED Display Power Supply VAC/DC at 2mA max VAC/DC at 30mA max Display Units C or F (factory set) C or F (jumper selectable) Display Range C ( F) C ( F) Display Resolution 0.1 C (0.1 F) 0.5 C (1.0 F) Display Size 23 mm W x 11 mm H (0.9 W x 0.45 H) 3 digit x 30 mm W x 7.6 mm H (1.18 W x 0.3 H) Available Options Various sensors, set points, push buttons, external jacks, and logos. A) Micro Includes a compact snap-mounted cover for ease of installation, available with various temperature sensors. AD) Designer Features include a three-piece enclosure that mounts directly to a wall box or on any wall. Available with various options. Including set point adjustments, push button overrides, etc. AS) Surface - A stainless steel plate which can be mounted to a wall box used where tamper-proof or protection is required. Available with various options, including push button overrides, etc. GREYSTONE ENERGY SYSTEMS INC.

24 ISO 9002 Q M I SPACE TEMPERATURE SENSORS/TRANSMITTERS: PRODUCT ORDERING INFORMATION MODEL TE200 TE500 Product Description Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard) CODE A AD AS Enclosure Micro (not available with transmitter or options) Designer S/S plate CODE Sensor PT ohm Platinum, IEC 751, 385 Alpha, thin film 1801 ohm, NTC Thermistor, ±0.2 C 3,000 ohm, NTC Thermistor, ±0.2 C 10,000 ohm, type 3, NTC Thermistor, ±0.2 C K ohm NTC Thermistor, ±0.2 C 100,000 ohm, NTC Thermistor, ±0.2 C LM334 IC, 1.0uA/ C PT ohm Platinum, IEC 751, Alpha, thin film 1000 ohm nickel 10,000 ohm type 3, NTC Thermistor, ±0.2 C c/w 11k shunt resistor 20,000 ohm, NTC Thermistor, ±0.2 C LM335 IC, 10mv/ C 10,000 ohm, type 2, NTC Thermistor, ±0.2 C CODE AP AS BS AM BC BF AC AF LY LR LG CJ AE AI Options (TE200AD assembly only) 20-30K linear slide pot for set point control Concealed push button momentary switch (NO) Exposed push button momentary switch (NO) Alcohol thermometer C & F Bi-metal thermometer C Bi-metal thermometer F 3-digit LCD temperature indicator C 3-digit LCD temperature indicator F Yellow LED Red LED Green LED External jack for remote system access (phono jack) External jack for remote system access (4-pin header) Internal jack (RJ-45) CODE TE500 Transmitter Power Supply 1 24 VAC/DC CODE A D E TE500 Transmitter Output Option Current 4 20mA Voltage 0 5 VDC Voltage 0 10 VDC CODE TE500 Transmitter Range Option C 35 C (32 F 95 F) 0 C 50 C (32 F 122 F) TE500 AD 12-1 A 2 Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. NOTE: Due to the many possible configurations, special part numbers may be required, please contact Greystone for more information. GREYSTONE ENERGY SYSTEMS INC. EXAMPLE: Designer space, c/w PT1000Ω RTD, 4 20mA transmitter with a 0 C 50 C (32 F 122 F) range.

25 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Room temperature sensor with pushbutton override Model: TE200AD7BS Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

26 ISO 9002 Q M I SPACE/WALL MOUNT FEATURES: The TE Series Space Temperature sensors are available in four different enclosure styles. They are available with a choice of precision RTD s, IC s, or thermistors. A number of options, such as momentary override and setpoint adjustment are also available for various configurations. A transmitter option is also available to be used with the 1000 ohm platinum sensor which provides either 4-20mA, 0 5 VDC or 0 10 VDC output proportional to a selected temperature span. A 100 ohm platinum sensor transmitter is optional. TRANSMITTER: stability, low hysteresis, fast response and a wide operating temperature range. Every transmitter offers accuracy of 0.1% of span or better and are highly stable due to excellent RFI rejection and are also virtually immune to power supply noise and input voltage fluctuations. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 20mA, 0 5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0 C 70 C (32 F 158 F) Calibration In compliance with ANSI/NCSL The transmitters provide high accuracy, long-term Display Type LCD Display LED Display Power Supply VAC/DC at 2mA max VAC/DC at 30mA max Display Units C or F (factory set) C or F (jumper selectable) Display Range C ( F) C ( F) Display Resolution 0.1 C (0.1 F) 0.5 C (1.0 F) Display Size 23 mm W x 11 mm H (0.9 W x 0.45 H) 3 digit x 30 mm W x 7.6 mm H (1.18 W x 0.3 H) Available Options Various sensors, set points, push buttons, external jacks, and logos. A) Micro Includes a compact snap-mounted cover for ease of installation, available with various temperature sensors. AD) Designer Features include a three-piece enclosure that mounts directly to a wall box or on any wall. Available with various options. Including set point adjustments, push button overrides, etc. AS) Surface - A stainless steel plate which can be mounted to a wall box used where tamper-proof or protection is required. Available with various options, including push button overrides, etc. GREYSTONE ENERGY SYSTEMS INC.

27 ISO 9002 Q M I SPACE TEMPERATURE SENSORS/TRANSMITTERS: PRODUCT ORDERING INFORMATION MODEL TE200 TE500 Product Description Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard) CODE A AD AS Enclosure Micro (not available with transmitter or options) Designer S/S plate CODE Sensor PT ohm Platinum, IEC 751, 385 Alpha, thin film 1801 ohm, NTC Thermistor, ±0.2 C 3,000 ohm, NTC Thermistor, ±0.2 C 10,000 ohm, type 3, NTC Thermistor, ±0.2 C K ohm NTC Thermistor, ±0.2 C 100,000 ohm, NTC Thermistor, ±0.2 C LM334 IC, 1.0uA/ C PT ohm Platinum, IEC 751, Alpha, thin film 1000 ohm nickel 10,000 ohm type 3, NTC Thermistor, ±0.2 C c/w 11k shunt resistor 20,000 ohm, NTC Thermistor, ±0.2 C LM335 IC, 10mv/ C 10,000 ohm, type 2, NTC Thermistor, ±0.2 C CODE AP AS BS AM BC BF AC AF LY LR LG CJ AE AI Options (TE200AD assembly only) 20-30K linear slide pot for set point control Concealed push button momentary switch (NO) Exposed push button momentary switch (NO) Alcohol thermometer C & F Bi-metal thermometer C Bi-metal thermometer F 3-digit LCD temperature indicator C 3-digit LCD temperature indicator F Yellow LED Red LED Green LED External jack for remote system access (phono jack) External jack for remote system access (4-pin header) Internal jack (RJ-45) CODE TE500 Transmitter Power Supply 1 24 VAC/DC CODE A D E TE500 Transmitter Output Option Current 4 20mA Voltage 0 5 VDC Voltage 0 10 VDC CODE TE500 Transmitter Range Option C 35 C (32 F 95 F) 0 C 50 C (32 F 122 F) TE500 AD 12-1 A 2 Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. NOTE: Due to the many possible configurations, special part numbers may be required, please contact Greystone for more information. GREYSTONE ENERGY SYSTEMS INC. EXAMPLE: Designer space, c/w PT1000Ω RTD, 4 20mA transmitter with a 0 C 50 C (32 F 122 F) range.

28 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Duct temperature sensor Model: TE200B7D2 Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

29 ISO 9002 Q M I PROBE SENSORS FEATURES: The TE Series Temperature sensors offer a choice of precision platinum RTD s, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system. The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications. The single point sensors are encapsulated in a 6.35 mm (0.25 ) OD 304 stainless steel probe. All probes are constructed to provide good heat transfer and fast response. The averaging sensors are available in both plenum rated cable or with a copper probe. TRANSMITTER: The TE500 transmitter option is standard with the 1000Ω platinum sensor and provides either 4 20mA, 0 5 VDC or 0 10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100Ω platinum sensor transmitter is optional. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 20mA, 0 5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0ºC 70ºC (32ºF 158ºF) OSA operating temp: -40 C 85 C (-40 F 185 F) Calibration: In compliance with ANSI/NCSL B) Duct Sensor For single point monitoring. It is available with various probe lengths and enclosures to fit any application. C) Immersion Sensor Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a ½ NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles. E) Strap-on Sensor Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed. F) OSA Sensor Comes in an aluminum LB c/w ½ NPT fitting for connection to conduit. It incorporates a sun/wind shield to protect the sensor FD) Flex-Duct Sensor Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors. D) Duct Average Sensor Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors. NOTE: Standard probe assemblies are rated at -40 C 105 C (-40 F F). For higher or lower temperature applications, please contact Greystone. GREYSTONE ENERGY SYSTEMS INC.

30 ISO 9002 Q M I PROBE TEMPERATURE SENSORS/TRANSDUCERS: PRODUCT ORDERING INFORMATION MODEL TE200 TE500 Product Description Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard) CODE AP B BB C D E F FD G H HC Style All purpose Duct mount Duct probe w/ mounting bracket only Immersion Duct average (copper) Strap-on Outside Air Duct average (flexible plenum rated cable) Glass Stack Clip CODE Enclosure (GES ABS enclosure is standard) CODE Flex Duct Only - M R W ABS enclosure, standard (no code required, leave blank) Metal utility box No box Aluminum weatherproof box A B C D Lead only, no box ABS enclosure Aluminum weatherpoof box Metal utility box CODE Sensor PT Ω Platinum,IEC 751, 385 Alpha, thin film PT Ω Platinum, IEC 751, 385 Alpha, wire wound-ceramic* (see below) 1801Ω, NTC Thermistor, ±0.2 C 3000Ω, NTC Thermistor, ±0.2 C 10,000Ω, type 3, NTC Thermistor, ±0.2 C 2.252KΩ, NTC Thermistor, ±0.2 C 100,000Ω, NTC Thermistor, ±0.2 C LM334 IC, 1.0uA/ C PT1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel 20,000Ω, NTC Thermsitor, ±0.2 C LM335 IC, 10mv/ C 10,000Ω, type 2, NTC Thermistor, ±0.2 C *must use for high temp. applications over 400 C (752 F) CODE Probe Length CODE Copper Avg. (D) CODE Flex Avg. (FD) A B C D E F 50 mm (2 ) 100 mm (4 ) 150 mm (6 ) 200 mm (8 ) 300 mm (12 ) 450 mm (18 ) CODE 2 3 G H I J 1800 mm (6 ) 3600 mm (12 ) 6100 mm (20 ) 7300 mm (24 ) Probe Material (not required for F, FD, G, HC) Stainless steel Copper (rigid duct average only) CODE A E Fitting (only required for immersion) Spring loaded 1/2 NPT Non-spring loaded 1/2 NPT CODE A B C D TE500 Transmitter Power Supply 1 24 VAC/VDC TE200 D - 7 I Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. CODE TE500 Transmitter Output Option A D E 4 20mA 0 5 VDC 0 10 VDC CODE mm (6 ) 3600 mm (12 ) 6100 mm (20 ) 7300 mm (24 ) TE500 Transmitter Range Option 0 C 35 C (32 F 95 F) 0 C 50 C (32 F 122 F) 0 C 100 C (32 F 212 F) 50 C 150 C (122 F 302 F) 50 C 250 C (122 F 482 F) -50 C +50 C (-58 F 122 F) Custom ranges available upon request. GREYSTONE ENERGY SYSTEMS INC.

31 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: 4" immersion temperature sensor Model: TE200C7B2E Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

32 ISO 9002 Q M I PROBE SENSORS FEATURES: The TE Series Temperature sensors offer a choice of precision platinum RTD s, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system. The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications. The single point sensors are encapsulated in a 6.35 mm (0.25 ) OD 304 stainless steel probe. All probes are constructed to provide good heat transfer and fast response. The averaging sensors are available in both plenum rated cable or with a copper probe. TRANSMITTER: The TE500 transmitter option is standard with the 1000Ω platinum sensor and provides either 4 20mA, 0 5 VDC or 0 10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100Ω platinum sensor transmitter is optional. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 20mA, 0 5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0ºC 70ºC (32ºF 158ºF) OSA operating temp: -40 C 85 C (-40 F 185 F) Calibration: In compliance with ANSI/NCSL B) Duct Sensor For single point monitoring. It is available with various probe lengths and enclosures to fit any application. C) Immersion Sensor Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a ½ NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles. E) Strap-on Sensor Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed. F) OSA Sensor Comes in an aluminum LB c/w ½ NPT fitting for connection to conduit. It incorporates a sun/wind shield to protect the sensor FD) Flex-Duct Sensor Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors. D) Duct Average Sensor Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors. NOTE: Standard probe assemblies are rated at -40 C 105 C (-40 F F). For higher or lower temperature applications, please contact Greystone. GREYSTONE ENERGY SYSTEMS INC.

33 ISO 9002 Q M I PROBE TEMPERATURE SENSORS/TRANSDUCERS: PRODUCT ORDERING INFORMATION MODEL TE200 TE500 Product Description Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard) CODE AP B BB C D E F FD G H HC Style All purpose Duct mount Duct probe w/ mounting bracket only Immersion Duct average (copper) Strap-on Outside Air Duct average (flexible plenum rated cable) Glass Stack Clip CODE Enclosure (GES ABS enclosure is standard) CODE Flex Duct Only - M R W ABS enclosure, standard (no code required, leave blank) Metal utility box No box Aluminum weatherproof box A B C D Lead only, no box ABS enclosure Aluminum weatherpoof box Metal utility box CODE Sensor PT Ω Platinum,IEC 751, 385 Alpha, thin film PT Ω Platinum, IEC 751, 385 Alpha, wire wound-ceramic* (see below) 1801Ω, NTC Thermistor, ±0.2 C 3000Ω, NTC Thermistor, ±0.2 C 10,000Ω, type 3, NTC Thermistor, ±0.2 C 2.252KΩ, NTC Thermistor, ±0.2 C 100,000Ω, NTC Thermistor, ±0.2 C LM334 IC, 1.0uA/ C PT1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel 20,000Ω, NTC Thermsitor, ±0.2 C LM335 IC, 10mv/ C 10,000Ω, type 2, NTC Thermistor, ±0.2 C *must use for high temp. applications over 400 C (752 F) CODE Probe Length CODE Copper Avg. (D) CODE Flex Avg. (FD) A B C D E F 50 mm (2 ) 100 mm (4 ) 150 mm (6 ) 200 mm (8 ) 300 mm (12 ) 450 mm (18 ) CODE 2 3 G H I J 1800 mm (6 ) 3600 mm (12 ) 6100 mm (20 ) 7300 mm (24 ) Probe Material (not required for F, FD, G, HC) Stainless steel Copper (rigid duct average only) CODE A E Fitting (only required for immersion) Spring loaded 1/2 NPT Non-spring loaded 1/2 NPT CODE A B C D TE500 Transmitter Power Supply 1 24 VAC/VDC TE200 D - 7 I Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. CODE TE500 Transmitter Output Option A D E 4 20mA 0 5 VDC 0 10 VDC CODE mm (6 ) 3600 mm (12 ) 6100 mm (20 ) 7300 mm (24 ) TE500 Transmitter Range Option 0 C 35 C (32 F 95 F) 0 C 50 C (32 F 122 F) 0 C 100 C (32 F 212 F) 50 C 150 C (122 F 302 F) 50 C 250 C (122 F 482 F) -50 C +50 C (-58 F 122 F) Custom ranges available upon request. GREYSTONE ENERGY SYSTEMS INC.

34 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: 4" Brass thermowell Model: T1-1/2BR4 Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

35 Q M I OPTIONS: Immersion Wells ASSEMBLIES: BB) Duct probe c/w mounting bracket ENCLOSURES: GES ABS Enclosure H) Stack M) Stamped Metal Utility Box G) Glass W) Aluminum Weatherproof Box AP) All Purpose ISO 9002 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB Canada E1E 4G7 (506) Fax: (506) mail@greystoneenergy.com Greystone Energy Systems Inc., established in 1983, is Canada s largest manufacturer of HVAC sensors and transducers for Building Automation Management Systems. We have conscientiously established a worldwide reputation as an industry leader by maintaining leading-edge design technology, prompt technical support, and a commitment to on-time deliveries. We take pride in our Quality Management System which is ISO 9002 certified, assuring our customers of consistent product reliability. GREYSTONE IS AN ISO 9002 REGISTERED COMPANY

36 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Outdoor air temperature sensor Model: TE200F7 Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

37 ISO 9002 Q M I PROBE SENSORS FEATURES: The TE Series Temperature sensors offer a choice of precision platinum RTD s, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system. The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications. The single point sensors are encapsulated in a 6.35 mm (0.25 ) OD 304 stainless steel probe. All probes are constructed to provide good heat transfer and fast response. The averaging sensors are available in both plenum rated cable or with a copper probe. TRANSMITTER: The TE500 transmitter option is standard with the 1000Ω platinum sensor and provides either 4 20mA, 0 5 VDC or 0 10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100Ω platinum sensor transmitter is optional. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 20mA, 0 5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0ºC 70ºC (32ºF 158ºF) OSA operating temp: -40 C 85 C (-40 F 185 F) Calibration: In compliance with ANSI/NCSL B) Duct Sensor For single point monitoring. It is available with various probe lengths and enclosures to fit any application. C) Immersion Sensor Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a ½ NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles. E) Strap-on Sensor Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed. F) OSA Sensor Comes in an aluminum LB c/w ½ NPT fitting for connection to conduit. It incorporates a sun/wind shield to protect the sensor FD) Flex-Duct Sensor Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors. D) Duct Average Sensor Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors. NOTE: Standard probe assemblies are rated at -40 C 105 C (-40 F F). For higher or lower temperature applications, please contact Greystone. GREYSTONE ENERGY SYSTEMS INC.

38 ISO 9002 Q M I PROBE TEMPERATURE SENSORS/TRANSDUCERS: PRODUCT ORDERING INFORMATION MODEL TE200 TE500 Product Description Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard) CODE AP B BB C D E F FD G H HC Style All purpose Duct mount Duct probe w/ mounting bracket only Immersion Duct average (copper) Strap-on Outside Air Duct average (flexible plenum rated cable) Glass Stack Clip CODE Enclosure (GES ABS enclosure is standard) CODE Flex Duct Only - M R W ABS enclosure, standard (no code required, leave blank) Metal utility box No box Aluminum weatherproof box A B C D Lead only, no box ABS enclosure Aluminum weatherpoof box Metal utility box CODE Sensor PT Ω Platinum,IEC 751, 385 Alpha, thin film PT Ω Platinum, IEC 751, 385 Alpha, wire wound-ceramic* (see below) 1801Ω, NTC Thermistor, ±0.2 C 3000Ω, NTC Thermistor, ±0.2 C 10,000Ω, type 3, NTC Thermistor, ±0.2 C 2.252KΩ, NTC Thermistor, ±0.2 C 100,000Ω, NTC Thermistor, ±0.2 C LM334 IC, 1.0uA/ C PT1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel 20,000Ω, NTC Thermsitor, ±0.2 C LM335 IC, 10mv/ C 10,000Ω, type 2, NTC Thermistor, ±0.2 C *must use for high temp. applications over 400 C (752 F) CODE Probe Length CODE Copper Avg. (D) CODE Flex Avg. (FD) A B C D E F 50 mm (2 ) 100 mm (4 ) 150 mm (6 ) 200 mm (8 ) 300 mm (12 ) 450 mm (18 ) CODE 2 3 G H I J 1800 mm (6 ) 3600 mm (12 ) 6100 mm (20 ) 7300 mm (24 ) Probe Material (not required for F, FD, G, HC) Stainless steel Copper (rigid duct average only) CODE A E Fitting (only required for immersion) Spring loaded 1/2 NPT Non-spring loaded 1/2 NPT CODE A B C D TE500 Transmitter Power Supply 1 24 VAC/VDC TE200 D - 7 I Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. CODE TE500 Transmitter Output Option A D E 4 20mA 0 5 VDC 0 10 VDC CODE mm (6 ) 3600 mm (12 ) 6100 mm (20 ) 7300 mm (24 ) TE500 Transmitter Range Option 0 C 35 C (32 F 95 F) 0 C 50 C (32 F 122 F) 0 C 100 C (32 F 212 F) 50 C 150 C (122 F 302 F) 50 C 250 C (122 F 482 F) -50 C +50 C (-58 F 122 F) Custom ranges available upon request. GREYSTONE ENERGY SYSTEMS INC.

39 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Average duct temperature sensor 20' Model: TE200FDB7C Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

40 ISO 9002 Q M I PROBE SENSORS FEATURES: The TE Series Temperature sensors offer a choice of precision platinum RTD s, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system. The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications. The single point sensors are encapsulated in a 6.35 mm (0.25 ) OD 304 stainless steel probe. All probes are constructed to provide good heat transfer and fast response. The averaging sensors are available in both plenum rated cable or with a copper probe. TRANSMITTER: The TE500 transmitter option is standard with the 1000Ω platinum sensor and provides either 4 20mA, 0 5 VDC or 0 10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100Ω platinum sensor transmitter is optional. Transmitter General Specifications: Supply Voltage: 24 VDC/VAC Output: 4 20mA, 0 5 VDC or 0-10 VDC Accuracy: ±0.1% of span Operating temp: 0ºC 70ºC (32ºF 158ºF) OSA operating temp: -40 C 85 C (-40 F 185 F) Calibration: In compliance with ANSI/NCSL B) Duct Sensor For single point monitoring. It is available with various probe lengths and enclosures to fit any application. C) Immersion Sensor Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a ½ NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles. E) Strap-on Sensor Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed. F) OSA Sensor Comes in an aluminum LB c/w ½ NPT fitting for connection to conduit. It incorporates a sun/wind shield to protect the sensor FD) Flex-Duct Sensor Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors. D) Duct Average Sensor Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors. NOTE: Standard probe assemblies are rated at -40 C 105 C (-40 F F). For higher or lower temperature applications, please contact Greystone. GREYSTONE ENERGY SYSTEMS INC.

41 ISO 9002 Q M I PROBE TEMPERATURE SENSORS/TRANSDUCERS: PRODUCT ORDERING INFORMATION MODEL TE200 TE500 Product Description Sensor assembly Sensor assembly c/w transmitter (sensor type 12 is standard) CODE AP B BB C D E F FD G H HC Style All purpose Duct mount Duct probe w/ mounting bracket only Immersion Duct average (copper) Strap-on Outside Air Duct average (flexible plenum rated cable) Glass Stack Clip CODE Enclosure (GES ABS enclosure is standard) CODE Flex Duct Only - M R W ABS enclosure, standard (no code required, leave blank) Metal utility box No box Aluminum weatherproof box A B C D Lead only, no box ABS enclosure Aluminum weatherpoof box Metal utility box CODE Sensor PT Ω Platinum,IEC 751, 385 Alpha, thin film PT Ω Platinum, IEC 751, 385 Alpha, wire wound-ceramic* (see below) 1801Ω, NTC Thermistor, ±0.2 C 3000Ω, NTC Thermistor, ±0.2 C 10,000Ω, type 3, NTC Thermistor, ±0.2 C 2.252KΩ, NTC Thermistor, ±0.2 C 100,000Ω, NTC Thermistor, ±0.2 C LM334 IC, 1.0uA/ C PT1000Ω Platinum, IEC 751, 385 Alpha, thin film 1000Ω Nickel 20,000Ω, NTC Thermsitor, ±0.2 C LM335 IC, 10mv/ C 10,000Ω, type 2, NTC Thermistor, ±0.2 C *must use for high temp. applications over 400 C (752 F) CODE Probe Length CODE Copper Avg. (D) CODE Flex Avg. (FD) A B C D E F 50 mm (2 ) 100 mm (4 ) 150 mm (6 ) 200 mm (8 ) 300 mm (12 ) 450 mm (18 ) CODE 2 3 G H I J 1800 mm (6 ) 3600 mm (12 ) 6100 mm (20 ) 7300 mm (24 ) Probe Material (not required for F, FD, G, HC) Stainless steel Copper (rigid duct average only) CODE A E Fitting (only required for immersion) Spring loaded 1/2 NPT Non-spring loaded 1/2 NPT CODE A B C D TE500 Transmitter Power Supply 1 24 VAC/VDC TE200 D - 7 I Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. CODE TE500 Transmitter Output Option A D E 4 20mA 0 5 VDC 0 10 VDC CODE mm (6 ) 3600 mm (12 ) 6100 mm (20 ) 7300 mm (24 ) TE500 Transmitter Range Option 0 C 35 C (32 F 95 F) 0 C 50 C (32 F 122 F) 0 C 100 C (32 F 212 F) 50 C 150 C (122 F 302 F) 50 C 250 C (122 F 482 F) -50 C +50 C (-58 F 122 F) Custom ranges available upon request. GREYSTONE ENERGY SYSTEMS INC.

42 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: CO2 detector Duct Mounted Model: CCD1A6000 Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

43 ISO 9002 Q M I CO 2 DETECTOR Environmental, industrial and commercial indoor Carbon Dioxide (CO 2 ) gas detector. Available in both a space and duct mount version. APPLICATION: To sense and transmit to any compatible electronic analog control, DDC/PLC controller or automation system for the control of ventilation equipment. Designed to meet ventilation requirements specified in ASHRAE Standard FEATURES: Setup/calibration fully menu driven (requires LCD option) Monitors CO2 over range PPM (factory default) Field adjustable range from PPM up to 10,000 PPM without re-calibration! NDIR single beam with patented ACLP selfcalibration algorithm Guaranteed 5 year calibration interval Optional on board relay with field adjustable trip point Optional LCD for displaying PPM level and menu options Powered by either AC or DC source with no change to circuit required Choice of two field adjustable analog output signals, linearized over full range Easy to calibrate in the field Duct Mount ABS Enclosure with Sampling Tube SPECIFICATIONS CO 2 DETECTOR Product # CDD Gas Detected Carbon Dioxide (CO 2 ) Range Standard Accuracy Extended Accuracy Sensing Element Operation Conditions Repeatability Stability Manufacturing Process Output Signal Output Drive Capability Output Resolution LCD Display (optional) Field Calibration ppm standard, programmable from 1500 up to 10,000 ppm in 500 ppm increments ±75 PPM or3% of reading (whichever is greater) C (59-90 F) for ppm range ±5% of reading for ,000 ppm ±150 ppm or 5% of reading (whichever is greater) 0-50 C ( F) for ppm range ±7% of reading for ,000 ppm Non-Dispersive Infrared (NDIR) 0-50C(32-122F), 0-95% RH non-condensing ±20 PPM ±20 PPM typical, 5 year calibration interval ISO 9002 certified 4-20 ma active (sourcing), 0-5Vdc and 0-10Vdc, jumper selectable (Note correct part number) 550 ohm max for current output, 10 Kohm min for voltage output 10 bit PWM LCD for displaying PPM level (required for field programming) 1 ppm resolution, 1.1 w x 0.5 h (28 x 13 mm) alpha-numeric 2 line x 8 characters Calibration, applying calibration gas standards (Contact Greystone for Calibration kit) External Dimensions Corporate Space 91mm W x 127mm H x 43 mm D (3.6 x 5 x 1.7 ) Duct ABS 124 mm W x 183 mm H x 43 mm D (4.9 x 7.22 x 1.69 ) GREYSTONE ENERGY SYSTEMS INC.

44 ISO 9002 Q M I SPECIFICATIONS (Con t) Pressure Dependence Altitude Correction Response Time Warm-up Time Power Supply Consumption Input Voltage Effect Protection Circuitry CO 2 DETECTOR Product # CDD 0.13% of reading per mm Hg Programmable from ft in 500 ft increments < 60 seconds for 90% step change < two (2) minutes Vac/dc (non-isolated half-wave rectified) 80 ma 24 Vdc, 36 ma Vdc Negligible over specified operating range Reverse voltage protected and output limited Optional Relay Output One Form C contact (N.O. and N.C.), status LED, Vac, 5 30Vdc, p.f. = 1 Relay Trip Point Programmable ppm in 50 ppm increments Relay Hysteresis Programmable ppm in 25 ppm increments Programming and Selection Wiring Connections Via internal push-buttons and jumper Screw terminal block (14 to 22 AWG) CARBON DIOXIDE (CO2): PRODUCT ORDERING INFORMATION MODEL Description CDD Carbon Dioxide Detector (CO 2 ) CODE Sensing Element 1 Non-Dispersive Infrared (NDIR) CODE Gas Type Range A CO 2 Carbon Dioxide Detector (CDD) PPM Standard User programmable up to 10,000 PPM CODE Enclosure and Outputs Corporate Space c/w 4-20 ma and 0-5 Vdc outputs Corporate Space c/w 4-20 ma and 0-10 Vdc outputs Duct ABS c/w Sampling Tube, 4-20 ma, 0-5 Vdc and 0-10 Vdc outputs CODE Circuit Board Relay No Relay One Relay (DPDT, N.O. or N.C., 24 VDC) CODE Options No options LCD RS-485 Communication (Please contact Greystone) CDD 1 A Typical Model Number Example: NDIR CO2 Corporate No Relay No Options Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice. GREYSTONE ENERGY SYSTEMS INC.

45 Q M I DIMENSIONS nts mm (4.90 ) 43.8 mm (1.69 ) mm (7.22 ) 127 mm (5.00 ) 92.7 mm (3.65 ) 42.9 mm (1.69 ) ACLP SOFTWARE AND 5 YEAR CALIBRATION GUARANTEE ACLP SOFTWARE ACLP (Automatic Calibration Logic Program) software utilizes the computing power in the sensor s on-board microprocessor to remember the lowest CO2 concentration that takes place every 24 hours. The sensor assumes this low point is at outside levels. The sensor is also smart enough to discount periodic elevated readings that might occur if for example a space was used 24 hours per day over a few days. Once the sensor has collected 14 days worth of low concentration points it performs a statistical analysis to see if there has been any small changes in the sensor reading over background levels that could be attributable to sensor drift. If the analysis concludes there is drift, a small correction factor is made to the sensor calibration to adjust for this change. 5 YEAR CALIBRATION GUARANTEE Based on the results of years of testing of ACLP software, Greystone now offers a 5 year calibration guarantee on all its CDD series wall and duct mount sensors used for CO2 based ventilation control when operated in an environment that can utilize ACLP software. If the sensor is found to be out of calibration more than 150 ppm as compared to a calibration gas or recently calibrated reference, Greystone will provide a free factory calibration of the sensor if returned to Greystone. This guarantee only applies if the sensor is operated in an environment where inside levels periodically drop to outside concentrations (i.e. during evenings or weekends when there is no occupancy) as is required by ACLP software. If a space does not experience a periodic drop to outside levels (e.g. where occupancy is 24 hours, 7 days/week), ACLP software should be deactivated off. With ACLP deactivated (via menu buttons) calibration may be required every 2 to 3 years. ISO 9002 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB Canada E1E 4G7 (506) Fax: (506) mail@greystoneenergy.com Greystone Energy Systems Inc., established in 1983, is Canada s largest manufacturer of HVAC sensors and transducers for Building Automation Management Systems. We have conscientiously established a worldwide reputation as an industry leader by maintaining leadingedge design technology, prompt technical support, and a commitment to on-time deliveries. We take pride in our Quality Management System which is ISO 9002 certified, assuring our customers of consistent product reliability. GREYSTONE IS AN ISO 9002 REGISTERED COMPANY

46 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: CO2 detector Wall Mounted Model: Ventostat 8001-L Supplier info: Address: Tinsmith Mechanical Manufacturer info: Telaire Address: 6860 Cortona Drive - Suite B, Golete, CA Website

47 Ventostat 8001/8002 Single Beam CO2 Ventilation Controllers The Ventostat 8001 and 8002 carbon dioxide (CO2) sensors and controllers are designed for Demand Controlled Ventilation DCV in buildings This approach, using CO2 as an indicator of occupancy, allows ventilation based on actual occupancy while still maintaining ASHRAE recommended per-person ventilation rates Over-ventilation of buildings can be reduced, energy can be saved and air quality can be optimized The optional black case (8001B Commercial Grade and 8002B) is UL94-V5 rated making these models suitable for mounting directly inside the ductwork Typical applications for the 8001 and 8002 include office buildings, conference rooms, schools, retail stores, restaurants, gymnasiums, and movie theaters B B

48 Features/Benefits Telaire s Patented Absorption Infrared TM gas sensing engine provides high accuracy in a compact low cost package Patented ABC Logic self-calibration system eliminates the need for manual calibration in most applications (see ABC Logic section) 10 years of Telaire experience and reliability built in Gold-plated optical sensor increases sensor life and durability Attractive low profile case in either white or black to suit you building décor Mounting plate with terminal block provides quick, easy wiring Compatible with standard US and European junction boxes Gas permeable, water resistant diffusion filter prevents particulate and water contamination of the sensor Locking screw secures cover and sensor to the mounting plate for tamper resistance Dual simultaneous analog output (V & ma) On-board relay (normally open or closed) with adjustable setpoint and dead-band Choice of 9 pre-programmed standard settings Adjustable settings allow for simple configuration with economizers to deliver specific target cfm/person ventilation rates Simple plug-in PC based user interface program allows for configuring and calibrating the sensor On-board push-button interface and 2 line by 8 character display allows for quick, easy customizing (8002 models only) Optional enclosures available for wet and cold temperature environments One-step calibration process (if necessary) can be completed in 5 minutes The 8001B/8002B (Black Case) includes conformal coated PCB with a UL94-5V rated enclosure for direct in duct mounting or increased environmental durability ABC Logic Provides Automatic Calibration Telaire s 8001 and 8002 commercial CO2 controllers use the patented ABC Logic (Automatic Background Calibration) self- Calibration system that virtually eliminates the need for manual calibration in applications where the indoor CO2 level drops to outside levels during unoccupied periods (e g during evening hours) ABC Logic is a special software routine in the sensor that CO PPM Reading Using 980 PPM Calibration Gas Days Fast One Step Calibration All 8000 Series CO2 Sensors feature a fast one step calibration process should it ever be required A zero calibration can be performed in 5 minutes by flowing gas to the calibration port and activating the calibration routine If drift occurs in the sensor it usually affects the zero setting of the sensor only If a two point calibration is desired, it can be performed using the UIP Program User Interface Program (UIP) All Ventostat 8000 series controllers can be connected to a PC using the UIP 2072 easyto-use Windows program Simply connect to the sensor using the on-board RJ45 jack and you can adjust the output scaling, elevation adjustment, relay setpoint, relay remembers the background readings for 14 consecutive evenings and calculates if there is sensor drift and then corrects for it ABC Logic will not work properly in applications where the space is unoccupied for less than four hours a day or where there are industrial sources of CO2 in the building such as breweries or wineries Year Calibration Guarantee Telaire is serious about calibration stability and backs Ventostat 8001 and 8002 models with a 5 year calibration guarantee If a Telaire 8000 sensor drifts out of calibration range in the first five years of use it can be sent back to Telaire for a free factory calibration Further information on the guarantee is provided with every product dead-band, select linear or proportional or exponential output, perform single-point or two-point calibration, and check ppm levels Display units can also be adjusted using the keypad ABC Logic

49 CO2 Engineering Specification The CO2 sensor for demand control ventilation shall be the 8001 or 8002 nondispersive infrared sensor made by Telaire ( ) The diffusion gas chamber in the sensor should incorporate a reflective, gold plated light pipe or waveguide surrounded by a gas permeable teflon based hydrophobic diffusion filter that prevents particulate and water contamination of the sensor The sensor shall provide simultaneous analog outputs in volts and miliamps and shall have a gold bifurcated relay that can be operated as normally open or closed The sensor shall incorporate elevation correction adjustment and ABC Logic (Automatic Background Calibration) software for self-correction of drift to better than ±10ppm per year The sensor shall have an accuracy of ±75 ppm or 7% of the reading (whichever is greater) All adjustments to the sensor including output scaling, elevation adjustment, relay setpoint, relay dead-band, proportional or exponential output, and single-point calibration shall be made via computer connection to an onboard RJ45 jack The 8002 product shall also be adjusted using the on-board push buttons and display For ease of installation, the sensor shall have a detachable base with all field wiring terminals on the base This product meets or exceeds specifications for the Ventostat Model 2001V Accessories 1505 Water Resistant Enclosure for Harsh Environments UIP 2072 UIP For Customizing Settings and Calibration Models / Features 1551 Outside Air Enclosure for Temperatures to -20 F (-29 C) 1508 Aspiration Box For In Duct Mounting 2075 Calibration Kit Replacement Bottles For Performing Zero For Replacing 2075 and Span Calibration Gas Bottles Factory calibration available - Call for details Ventostat 8001 Ventostat 8001B Ventostat 8002 Ventostat 8002B No Display Wall Mount 0-10,000 PPM No Display Wall or In-Duct Mount 0-10,000 PPM Display Wall Mount 0-10,000 PPM Display Wall or In-Duct Mount 0-10,000 PPM All units are compatible with Accessory Enclosures, 2072 UIP and Calibration Kit All units can be zero calibrated using a zero gas and on-board keypad Black enclosures are UL94-5V Rated and electronics are conformally coated for direct in-duct mounting Display units are provided with locking covers for hidden or visible display Cross-Reference Dimensions The Ventostat 8001 and 8002 controllers meets or exceeds the performance specifications and functionality for the Model Ventostat 2001V and may be used as a direct substitute 3 1/4" 1 1/8" 2 7/8" 2 3/8" 2 3/8" 5 5/8" 3 1/4" 4 1/4" 5 1/16" Front View of Sensor Side View with Mounting Bracket Mounting Bracket

50 How The Commercial Grade Sensor Works Telaire s CO2 sensor can detect gases based on the fact that gases will absorb light at very specific wavelengths in the infrared spectrum In the Telaire sensor, gas diffuses through a gas permeable membrane and into the sample chamber The gas permeable membrane allows gas molecules to pass freely but prevents the entry of particulates A light source at one end of the chamber generates a broad band of infrared energy that is directed through the sample chamber Because much of the light bounces off the gold plated walls of the sensor, a longer effective sample path can be achieved in a small distance At the other end of the sensor is a special optical filter installed on top of a light detector The optical filter is designed to only admit light at the wavelength where CO2 is known to absorb light The small change in light intensity caused by a change in CO2 concentrations is then measured by the detector and converted into a CO2 measurement by a microprocessor The microprocessor also automatically calibrates and corrects the sensor for long term drift using Telaire s patented ABC Logic self calibration software Gas Permeable Membrane CO2 Microprocessor Corrects Drift Using ABC Logic Signal to Microprocessor COP 87L88GGV-XE Light Source Single Channel Detector Sends CO2 Signal to Equipment Specifications Method Single Beam Absorption Infrared Diffusion sample method Performance Measurement Range ppm factory default Adjustable to 10,000 ppm Accuracy ±75ppm or 7% whichever is greater Elevation (Pressure) Correction Add 0 13% of reading per mm Hg decrease from 760 mm Hg (On-board correction, user set with UIP software), preset at sea level Response Time 0-90% <1 minute Warm-Up 25 o C <2 minutes Operating Conditions o C (60-90 o F) 0 95% RH, non-condensing Storage Temperature o C Agency Certification FCC Part 15 Class B / CE Black Case - UL94-5V Rated Input/Output Power VAC RMS, 50/60 Hz -half-wave rectified VDC polarity protected 1 75 VA maximum average power 2 75 VA peak power Analog Output (Simultaneous) 0-10 VDC (100 Ohms output impedance) 4-20 ma (RLmax = 500 Ohms) Relay Output Normally Open and Normally Closed (wire either way), gold bifurcated, 2A 24VAC Adjustable setpoint (with UIP software kit), factory set at 1000 ppm, 50 ppm hysteresis Wiring AWG stranded copper wire only 2 wires each for power, analog output, relay Digital I/O RS-232 interface for use with optional PC software and cable in UIP kit 2072 Warranty/Other Warranty 18 months parts and labor Calibration 5-year calibration guarantee 6489 Calle Real Goleta, CA FAX www telaire com It is our intention to keep the product information current and accurate We can not cover specific applications or anticipate all requirements All specifications are subject to change without notice For more information or questions relative to this Specification Sheet, contact Telaire Copyright Telaire Covered by United States Patents: 5,060,508 and 5,163,332 F F0124-1

51 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Web Access Software Model: RC Webview Supplier info: Address: Manufacturer info: Address: Website Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R6 Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R6

52 The Reliable Controls RC-WebView Web based system access software gives building operators yet another Reliable Controls MACH-System server based Web access Distributed system access and manipulation through IE 5.5 or higher Real-time, dynamic display of System Group screens Configuration utility for ease-of-setup Unlimited number of simultaneous user connections Password protection for system integrity simple, flexible, and economical solution to access, monitor, and control building environments The Reliable Controls RC-WebView Web server software is part of the software suite for the Reliable Controls MACH-System Reliable Controls Corporation Reliable Controls Corporation, Whittier Ave., Victoria BC, V8Z 3R1 Toll Free: 1 (877) Tel: (250) Fax: (250)

53 RC-WebView Software Rc-WebView enhances the Reliable Controls suite of building automation software by providing a Web-based access solution that uses Microsoft Internet Explorer 5.5 in place of client side software. RC-WebView resides on a dedicated server connected anywhere in the World Wide Web. The software configuration is easy and the number of users connected to RC-WebView is only limited by the capability of the server hosting the application. RC-WebView is designed to user the same file structure as RC-Studio, enabling the two applications to present system group data in the same manner. A common file structure allows the two applications to dynamically synchronize data so that the display is the same in either application. RC-WebView allows the operator to user a browser to view and manually override points, adjust weekly schedules and annual schedules, view graph and print trend and runtime logs, and view and print current alarms. F E A T U R E S Easy Setup Configuration utility provides easy setup Password security protection Tree view feature provides intuitive navigation Mulltiple systems supported Easy Operator Use Dynamic system data displayed in intuitive graphical screens Right click access to edit and manually override points Single click access to view and adjust weekly schedules, annual schedules, trend and runtime logs, and current system alarms Custom functionality achieved through the inclusion of system keywords Dynamic Data Data synchronization between RC-WebView and the systems connected to RC-Studio Automatic translation of graphics. No need to perform custom exports Easy Connectivity Use any copy of Microsoft Internet Explorer 5.5 or higher to display Web sites created in RC-WebView Unlimited number of users can access site simultaneously O R D E R I N G RC-WEB-SRV RC-WebView Server configured with single system license of RC-WebView Software RC-WEB-A RC-WebView Software - additional system license PC Requirements Intel Pentium IV 1.8 Ghz Processor Gigabyte GA-8INXP Server Motherboard 2 x Maxtor 40.0 GB, 7,200 RPM ATA/133 Hard Drive 1.44 MB Floppy Drive, LG 52x CDROM Drive 2 x 256 MB DDR RAM Nvidia GeForce Video Card Windows 2000 Server License, IIS Service 19 4U Rackmount Chassis, 300W Power Supply Keyboard Logitech Wheel Mouse Configuration Utility Current Alarms Operator Workstation Off-Site Office Tower School System In Browser INTERNET Router/Firewall Ethernet Hub Hospital Router/Firewall Operator Workstation RC-WebView SERVER Administration Web Site RC-WebView Web Site # 01 RC-WebView Web Site # xx WAN Network Architecture Trend Log in Browser RCW-09/ Reliable Controls Corporation Designed and Manufactured in Canada

54 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Building Controller Model: Mach Global (MG) Supplier info: Address: Manufacturer info: Address: Website Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R10 Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R10

55 The Reliable Controls MACH-Global building controller gives operators yet another Ultimate, intelligent, networkable complete building controller Completely programmable DDC controller Modular Input, Output cards provide up to 128 points of measurement Trend logs with historical tracking Ideal for high-point applications requiring unrestricted programming Support provided for two subnetworks Multiple, simultaneous communication channels simple, flexible, and economical solution to access, monitor, and control building environments The Reliable Controls MACH-Global building controller is a super solution to any new or replacement equipment application, and ships with the Reliable Controls industry best 5 year warranty. Dimensions: 31.4 cm L x 19.9 cm W x 3.8 cm H (12.4 L x 7.9 W x 1.25 H) 2003 Reliable Controls Corporation Reliable Controls Corporation, Whittier Ave., Victoria BC, V8Z 3R1 Toll Free: 1 (877) Tel: (250) Fax: (250)

56 MACH-Global Controller The Reliable Controls MACH-Global building controller is a powerful, central-point DDC controller designed to support multiple BACnet LAN communication technologies simultaneously through nine ports; 1-IEEE802.3 (Ethernet), 3- EIA-232 (PC/Modem), 2-EIA-485 (token passing), 2-EIA-422/ 485 and 1-MSP (SMART-Net ). This flexible and powerful controller also supports up to 128 universal input/output hard points directly onboard using a combination of eight modular 16-point expansion cards. The MACH-Global controller is a dual-protocol device, supporting BACnet and Reliable Controls protocols. A fully configured Reliable-Controls MACH-System supports over 2,000,000 points of measurement. Processor 16-bit embedded microcontroller Memory 2 MB of NV RAM user database 1 MB Flash EEPROM for operating system firmware Supply Voltages 24 VAC Class 2, 75 VA 3.15 A slow blow fuse Communications 1-IEEE Ethernet 10BaseT 115 kbps 115 kbps 115 kbps 1 -SMART-Net (16 SMART-Sensors max) Inputs/Outputs 8 ports, each addressing 16 Input points or Output points Converters 12 bit A-D for inputs 12 bit D-A for outputs Real-Time Clock +/-1 second per day Memory/RTC Backup 48 hours by zero maintenance capacitor Dimensions 31.4 cm L x 19.9 cm W x 3.8 cm H (12.4 L x 7.9 W x 1.25 H) Mounting #6 clearance holes on 30.0 cm L x 18.5 cm W (11.8 L x 7.25 W) centers Weight 1.0 kg (2.5 lb.) Ambient Limits Operating: 0 C to 40 C (32 F to 104 F) Shipping: -40 C to 60 C (-40 F to 140 F) Humidity: 10% to 90% RH non-condensing F E A T U R E S Protocol BACnet - PTP (EIA-232) - MS/TP (EIA-485) - B/IP (Ethernet) - ISO Reliable Controls - Ethernet (IP) - PC & Modem (EIA-232) - Network (EIA-485/Token Bus) 128 Control-BASIC Programs User programmable control strategy in a readable, BASIC-like language 2500 bytes per program 128 Inputs/Outputs Universal ranges 256 Variables Selectable standard and custom ranges, as well as fixed or program-driven values 64 PID Loops Standard P, PI, or PID controllers for closed loop control 96 Trend Logs Each trend log stores 512 samples of 6 points at programmable time intervals 128 Runtime Logs Totals the on time and records the on/off times of a digital point 64 System Groups Allows related points to be grouped on one display 160 points per group 32 Weekly Schedules 4 on/off times for each weekday and 2 override days MACH1 MACH2 MACH-Air Sub network A Sub network B MACH-Zone MACH-Air MACH2 8 Annual Schedules Days of the year designated as holidays 48 Variable Arrays Up to 128 elements in a one-dimensional array 128 User Passwords Protects access to system Each user is assigned a user name and an access level 20 Custom Tables For creating custom input ranges 16 Custom Units 8 analogue engineering units 8 digital engineering units SMART-Net Port Networks up to 16 SMART-Sensors 127 Network In Points 127 Network Out Points Warranty 5 years O R D E R I N G MG MACH-Global controller Ethernet 24 VAC/VDC Power switch Modem Operator Work Station Main network to other controllers MACH-Global SMART-Sensor Printer MACH-Global Input Expansion Cards MACH-Global Output Expansion Cards MG-11/04-RAR 2003 Reliable Controls Corporation Designed and Manufactured in Canada

57 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Input Card for Building Controller Model: Mach Global Input Card (MGX-I) Supplier info: Address: Manufacturer info: Address: Website Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R11 Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R11

58 The Reliable Controls MACH-Global Input expansion cards give operators yet another simple, flexible, and Ultimate modularity for MACH-Global building controller Universal inputs, 16 per card Expansion cards provide up to 128 Inputs Pulse 40 HZ provides support for flow meters Status LEDs glow proportionally Powered by MACH-Global building controller economical solution to access, monitor, and control building environments The Reliable Controls MACH-Global Input expansion cards offer a super solution to any new or expanding equipment application, and ship with the Reliable Controls industry best 5 year warranty. Dimensions: 22.3 cm L x 11.4 cm W x 4.5 cm H (8.75 L x 4.5 W x 1.75 H) 2003 Reliable Controls Corporation Reliable Controls Corporation, Whittier Ave., Victoria BC, V8Z 3R1 Toll Free: 1 (877) Tel: (250) Fax: (250)

59 MACH-Global Input Expansion Card The Reliable Controls MACH-Global input card is a general purpose universal input expansion card that is designed for use with the MACH-Global controller. The expansion card accepts analogue, digital or pulsed signals at each of its 16 inputs. Each input has two dip switch poles for configuring the input to be a 0-5 Volt, 4-20 ma, or themistor/dry contact. A maximum of eight input cards can be connected to one MACH-Global controller. Each input has an LED that glows proportionally to the input value. F E A T U R E S 16 Universal Inputs 0-5 VDC pulse, thermistor/dry contact, or 4-20 ma Software configured as analogue or digital Folded Metal Enclosure Strong powder coated steel metal enclosure protects circuitry and adds to the ease of installation Removable Connectors Two 16-pole removable connectors for easy change out Warranty 5 years O R D E R I N G MGX-I MACH-Global input expansion card MGX-RC-B MACH-Global expansion card ribbon cable - base MGX-RC-C MACH-Global expansion card ribbon cable - cable per 30 cm/1 ft. up to a max. of 120 cm/4 ft. Supply Voltage Supplied by MACH-Global controller Inputs 16 universal inputs 12 bit A-D converter Analogue: 0-5 VDC, 4-20 ma, thermistor Digital: dry contact Impedance: 15k Ω on 0-5 VDC range, 250 Ω on 4-20 ma range, 10k Ω on thermistor range 40 Hz pulse counting (supports flow meters) 24 VAC over voltage protection Connectors Two 16-pole removable connectors for inputs One 20-pole ribbon cable header Status LEDs One LED per input, intensity proportional to input value Dimensions 22.3 cm L x 11.4 cm W x 4.5 cm H (8.75 L x 4.5 W x 1.75 H) Mounting #6 clearance holes on 20.5 cm L x 10.0 cm W (8.12 L x 4 W) Weight 0.7 kg (1.2 lb.) Ambient Limits Operating: 0 C to 40 C (32 F to 104 F) Shipping: -20 C to 60 C (-40 F to 140 F) Humidity: 10% to 90% RH non-condensing Ribbon Cable to Expansion Cards MACH-Global Input Expansion Cards MACH-Global Controller Expansion Ports MGI-11/04-RAR 2003 Reliable Controls Corporation Designed and Manufactured in Canada

60 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Output Card for Building Controller Model: Mach Global Output Card (MGX-O) Supplier info: Address: Manufacturer info: Address: Website Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R12 Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R12

61 The Reliable Controls MACH-Global Output expansion cards give operators yet another simple, flexible, and Ultimate modularity for MACH-Global building controller Universal outputs, 16 per card, HOA switches standard Expansion cards provide up to 128 outputs Output signal configured in RC-Studio software Status LEDs glow proportionally Separate power supply for maximum efficiency economical solution to access, monitor, and control building environments The Reliable Controls MACH-Global Output expansion cards offer a super solution to any new or expanding equipment application, and ship with the Reliable Controls industry best 5 year warranty. Dimensions: 22.3 cm L x 11.4 cm W x 4.5 cm H (8.75 L x 4.5 W x 1.75 H) 2003 Reliable Controls Corporation Reliable Controls Corporation, Whittier Ave., Victoria BC, V8Z 3R1 Toll Free: 1 (877) Tel: (250) Fax: (250)

62 MACH-Global Output Expansion Card The Reliable Controls MACH-Global output card is a general purpose universal output expansion card that is designed for use with the MACH-Global controller. Each of the expansion cards 16 outputs can be independently configured to deliver an analogue or digital signal. Every output comes standard with a Hand/Off/Auto switch for convenient override in the field, and position feedback to RC-Studio software. A maximum of eight output cards can be connected to one MACH-Global controller. Each MACH-Global output card requires its own 24 VAC power source. F E A T U R E S 16 Universal Outputs 0-12 VDC, analogue 0-12 VDC, digital Software configured as analogue or digital HOA Switches Standard for each output Convenient override in the field Switch position feedback to RC-Studio software Proportional LEDs LED brilliance is proportional to output signal Metal Enclosure Strong powder coated steel metal enclosure protects circuitry and adds to the ease of installation Removable Connectors Two 16-pole and one 2-pole removable connectors for easy change out Warranty 5 years O R D E R I N G MGX-O MACH-Global output expansion card MGX-RC-B MACH-Global expansion card ribbon cable - base MGX-RC-C MACH-Global expansion card ribbon cable - cable per 30 cm/ 1 ft. up to a max. of 120 cm/4 ft. Supply Voltage 24 VAC 50 VA Class 2 Outputs 16 universal outputs 12 bit D-A converter Analogue: 0-12 VDC Digital: 0-12 VDC Manual ON provides 15 VDC LED indicator Output power: VDC 24 VAC over voltage and short protection Switches HOA toggle switch Switch position feedback to RC-Studio software Connectors Two 16-pole removable connectors for output One 20-pole ribbon cable header One 2-pole power connector Status LEDs One LED per output, intensity proportional to output value Dimensions 22.3 cm L x 11.4 cm W x 4.5 cm H (8.75 L x 4.5 W x 1.75 H) Mounting #6 clearance holes on 20.5 cm L x 10.0 cm W (8.12 L x 4 W) Weight 0.7 kg (1.2 lb.) Ambient Limits Operating: 0 C to 40 C (32 F to 104 F) Shipping: -20 C to 60 C (-40 F to 140 F) Humidity: 10% to 90% RH non-condensing Fuse 3.15 A slow blow 5 A ground protection fuse MACH-Global Controller Expansion Ports Ribbon Cable to Expansion Cards MACH-Global Output Expansion Cards MGO-11/04-RAR 2003 Reliable Controls Corporation Designed and Manufactured in Canada

63 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: VAV Controller Model: Mach Air (MAH-T) Supplier info: Address: Manufacturer info: Address: Website Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R13 Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R13

64 The Reliable Controls MACH-Air VAV controller gives operators yet another Ultimate, intelligent, networkable VAV box controller Completely programmable DDC controller simple, flexible, and economical solution to Relocatable Belimo damper actuator Mounted directly to your VAV equipment Trend logs with historical tracking Accessible environmental building controls Onboard velocity sensors for flow measurement BACnet MS/TP communications (BTL Listed) access, monitor, and control building environments The Reliable Controls MACH-Air VAV controller is a super solution to any new or replacement air handling application, and ships with the Reliable Controls industry best 5 year warranty. Dimensions: 22.9 cm L x 13.4 cm W x 6.3 cm H (9.0 L x 4.8 W x 2.5 H) 2003 Reliable Controls Corporation Reliable Controls Corporation, Whittier Ave., Victoria BC, V8Z 3R1 Toll Free: 1 (877) Tel: (250) Fax: (250)

65 MACH-Air VAV Controller F E A T U R E S The Reliable Controls MACH-Air controller is a programmable, 6 input, 5 output, DDC controller and shaft-mount damper actuator, combined together into one device to meet the needs of variable air volume (VAV) control. The MACH-Air controller features onboard velocity measurement, a 35 in-lb Belimo actuator, three user specified universal inputs/outputs, and optional triac outputs. Removable connectors are standard on the MACH-Air controller. 50 points/group 1 We e k l y S ch e d u l e Protocols BACnet - MS/TP (EIA-485) Reliable - Network (EIA-485/Token Bus) 8 Control-BASIC Programs 25 MHz, high-performance 16-bit embedded microcontroller Mem ory 32k RAM 128k Flash EEPROM operating system firmware and controller configurations S u p p l y Vo l ta ge s 24 VAC/VDC, 25 VA max. C o m m u n ic a t io n s 76.8 kbps max. SMART-Net (4 SMART-Sensors max.) Digital: 0-12 VDC Output power: VDC 24 VAC over voltage and short protection S i n g l e S ta ge Tri a c Outputs 24 1 A Dual Stage Tr ia c O u tputs 24 1 A Common return Vel o c it y Sen s o rs Flow-through thermistor 0-1 W.C. SET U P-To ol Ac t u at or SETUP-Tool used for configuration Torque: 35 in-lb. Enclosure Inputs NEMA type 1 UL94-5V 3 universal inputs 10 bit A-D converter Analogue: 0-5 VDC, 4-20 ma, thermistor Digital: dry contact Impedance: 15k Ω on 0-5 VDC range 40 Hz pulse counting (supports flow meters) 24 VAC over voltage protection Outputs 3 universal outputs 8 bit D-A converter Analogue: 0-12 VDC Days of the year designated as holidays For creating custom input ranges and Control-BASIC lookup tables SM ART- Ne t Port 6 Inputs 3 Inputs with universal ranges Jumper selectable 0-5 VDC, 4-20 ma, thermistor/dry contact Input #4 dedicated to the flow sensor Input #5 dedicated to the damper position feedkback Input #6 dedicated to indicate damper at end of position 3 Outputs with universal ranges Scalable 0-12 VDC Output #4 dedicated to damper motor Output #5 dedicated to control direction of rotation to close Single stage triac (T model only) Dual stage triac (T model only) 4 8 Var i a b l e s Selectable standard and custom ranges, as well as fixed or program-driven values Variable #1 dedicated to flow calibration 4 C on t r o l l e r s Standard P, PI, or PID controllers for closed loop control 2 Tr e n d L o g s Each trend log stores 150 samples of 6 points at programmable time intervals Networks up to 4 SMART-Sensors SMART-Sensor #5 is dedicated to SETUP-Tool 32 Ne tw ork In Poi n ts 3 2 N e tw ork Ou t Poi n ts Wa rr an ty 5 years C e rt i fi c a t io n UL listed 916 OPEN ENERGY MANAGEMENT EQUIPMENT O R D E R I N G MA MACH-Air controller with 3 universal inputs and 3 universal outputs M A -T MACH-Air controller with 3 universal inputs and 1 universal output, 1 single stage triac output, 1 dual stage triac output. M A -P MACH-Air controller with potentiometer position feedback M A -TP MACH-Air-T controller with potentiometer position feedback M A -WA MACH-Air without actuator M A -W F MACH-Air without flow sensor 4 R u nt i m e L o g s M A -C Totals the on time and records the on/off times of a digital point MACH-Air connector cover D im en s io n s 2 S y s t e m G r o up s 22.9 cm L x 13.4 cm W x 6.3 cm H (9 L x 4.8 W x 2.5 H) Allows related points to be grouped on to one display SETUP-Tool (required for configuration) M A Z- ST Wei gh t 24 VAC 60Hz Power EIA-485 Network Output-1 Output-2 Output-3 Input-1 Input-2 Input kg (1.8 lb.) Am b ie n t L im it s Operating: 0 C to 40 C (32 F to 104 F) Shipping: -20 C to 60 C) (-40 F to 140 F) Humidity: 10% to 90% RH non-condensing SMART-Sensor 24VAC 24VAC GND GND A- A- B+ B+ OUT 1 + A OUT + A OUT TRIAC 1 RTN-T 1 DS 1 -T 1 DS 1 -T 2 RTN-DS 1 IN 1 + 1OUT 2 + OUT 2 OUT 3 + OUT 3 IN 1 + IN 1 IN 2 + IN 2 IN 3 + IN 3 OUT BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve or test products for compliance with ASHRAE standards. Compliance of listed products to requirements of ASHRAE Standard 135 is the responsibility of the BACnet Manufactures Association (BMA). BTL is a registered trademark of the BMA MA-11/04-RAR 1 Annual schedule 5 C u s to m Tab l e s User programmable control strategy in a readable, BASIC-like language 2000 bytes per program 5 O u tp u t s Pro ce ssor 4 on/off times for each weekday and 2 override days 2003 Reliable Controls Corporation MACH-Air Connector Wiring MACH-Air -T Connector Wiring GND IN IN GND Designed and Manufactured in Canada

66 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Line Filter/Surge Suppressor Model: PLF-2 Supplier info: Address: Reliable Controls Corporation Whittier Avenue, Victoria, BC V8Z 3R3 Manufacturer info: Corcom Address: 844 E. Rockland Road Libertyville, IL Website

67 CORCOM Product Guide RFI Power Line Filters for Switching Power Supply Noise Suppression EP/VP Series UL Recognized CSA Certified VDE Approved EP1/VP1 EP7/VP7 EP/VP Series The EP/VP series of RFI filters has been developed to reduce conducted noise to acceptable limits for equipment that must comply with the requirements of CISPR in Europe and the FCC specifications in the USA. These filters provide high insertion loss for both lineto-ground and line-to-line emissions throughout the frequency range. They are particularly well suited for equipment to better meet both stringent emissions specifications (such as CISPR 22, A-level and FCC Part 15J, Class B) and the EP models meet very low leakage current requirements. Electrical Schematic LINE Resistor location for reference only. Line Cord Line Cord No. GA400: 71/2 foot, 3-conductor line cord. LOAD Specifications Maximum leakage current,each line-to-ground VP Models EP 120 VAC VAC 50 Hz: 1.27mA.36mA Hipot rating (one minute): line-to-ground 2250 VDC line-to-line 1450 VDC Operating frequency: 50/60 Hz Rated voltage (max.): Rated current: 03EP 06EP 10EP 20EP/VP Minimum insertion loss in db: Line-to-ground in 50 ohm circuit EP3/VP3 250 VAC 03A 06A 10A 20A Current Frequency MHz Rating EP 3A A,10A A VP 20A Line-to-line in 50 ohm circuit Current Frequency MHz Rating EP1, EP3 3A A,10A A VP 20A Catalog Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: Revised millimeters unless otherwise reference purposes only. CORCOM Prods: specified. Values in italics Specifications subject are metric equivalents. to change. Germany:

68 CORCOM Product Guide RFI Power Line Filters for Switching Power Supply Noise Suppression (Continued) EP/VP Series Case Styles EP1/VP1 B 20EP/VP6 B RFI Power Line Filters D E A Typical dimensions: Terminals:.250 [6.35] (5) Holes:.07 [1.8] Dia.(4) Mounting Holes:.188 [4.78] Dia. (2) Slot:.07 x.16 [1.8 x 4.1] C D E A Terminals: No (5) C Torque: 18 ± 2 in.lb EP3 Brown Blue A D E Typical dimensions: Wire leads: 4.0 [101.6] Min. Brown Blue EP7 & EP7M (with metric insert) A Green/ Yellow C Mounting Holes:.188 [4.78] Dia.(2) No x 1/4 (2)-EP7 Tapped insert: No. M-3 x.5 (2)-EP7M.235 R 5.96 C E D B B.157 Dia. (2) 3.98 Case Dimensions A B C D E Part No. (max) (max) (max) ±.015 (max) ±.38 3EP EP EP EP7M EP EP EP EP EP1, 20VP EP6, 20VP ±.02 [±.5] Typical dimensions: Terminals:.250 [6.35] (3) Slot:.07 x.16 [1.8 x 4.1] Panel Cutout (back mount) Tolerance ±.005 [0.13] Holes:.07 [1.8] Dia.(2) Part Numbers 3EP1 3EP3 3EP7 3EP7M 6EP1 6EP3 Line Cord No. 10EP1 10EP3 20EP1 20EP6 20VP1 20VP6 GA400 Catalog Dimensions are in inches and Dimensions are shown for USA Cust. Svc.: Revised millimeters unless otherwise reference purposes only. CORCOM Prods: specified. Values in italics Specifications subject are metric equivalents. to change. Germany:

69 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Low voltage relay Model: M15MAH001812VDC c/w ZD35 base Supplier info: Address: Manufacturer info: Address: Website Carlo Gavazzi (Canada) Inc 2660 Meadowvale Boulevard, Mississauga, ON L5N 6M6 Carlo Gavazzi (Canada) Inc 2660 Meadowvale Boulevard, Mississauga, ON L5N 6M6

70 Miniature Relays Types MZ MZ M15 - M15 R1/R2 M25 (1 Pole) (2 Poles) (1 Pole) (1or 2 Poles) Dimensions (mm) H x W x D Terminal types No. of Contacts Contact rating 25.2/26.5 x 29.4 x 12.5 PCB 1 Normally open 1 Change-over 5 A - 10 A - 16 A 25.2/26.5 x 29.4 x 12.5 PCB 2 Normally open 2 Change-over 5 A - 10 A 15 x 29 x 10 PCB 1 Normally open 1 Change-over 8 A 15.7 x 29 x 12.7 PCB 1 Change-over (1 pole) 2 Change-over (2 poles) 12 A - 16 A (1 pole) 8 A (2 poles) Output Specifications Max. load AC1 Min. load Electrical life Switching power 6 A - 12 A - 20 A 100 ma at 24 mvdc 3.5 x 10 5 cycles (5/10A) 1.5 x 10 5 cycles (16A) 1250/2500/4000 VA 6 A - 12 A 100 ma at 24 mvdc 2.5 x 10 5 cycles (5 A) 8 x 10 4 cycles (10 A) 1250/2500 VA 10 A 100 ma at 24 mvdc cycles 2000 VA 9 A - 13 A - 18 A 100 ma at 24 mvdc 1x10 5 cycles 4000/3000/2000 VA General Specifications Voltage ranges VDC Voltage ranges VAC Insulation Coil/Contact Consumption Approvals/Conformity VAC See PCB General Cat. UL - CSA - VDE - IMQ S - N - D - F - SEV VAC See PCB General Cat. UL - CSA - VDE - IMQ S - N - D - F - SEV (M15) (M15R) 4000 VAC 220 mw UL - CSA - VDE - IMQ S - N - D - F - SEV VAC 5 00 mw cul - VDE References Consult your Carlo Gavazzi Partner or Distributor From 1.8 to 160 VDC From 6 to 264 VAC From 2.5 to 260 VDC From 6 to 260 VAC 3 to 110 VDC (M15) 3 to 48 VDC (M15R) From 5 to 110 VDC Types ZD 25 - ZD 32 - ZD 35 - ZD 50 ES 50/3 General Specifications Rated volt. / Rated curr. Insulation voltage Socket material Mounting Protection degree Approvals 300 VAC / 12 A 5 / 8 pole socket. > 5 kv Screw terminal Self-ext. PA 6 + GF (V1) connection. DIN-rail Standardized markings. IP 20 UL, CSA (12 A 300 VCA) 300 VAC / 12 A 5 / 8 pole socket. > 5 kv Screw terminal Self-ext. PA 6 + GF (V1) connection. DIN-rail Standardized markings. IP 20 UL, CSA (12 A 300 VCA) References For detailed informations consult your Carlo Gavazzi Partner or Distributor ZD 25 For relay: M15 F 8 A ZD 32 For relay: M15 E 8 A ZD 35 For relay: MZ 1P 5/10 A M15 M 8A M25 1P 12 A ZD 50 For relay: MZ B 1P 5/10 A MZ 2P 5/10 A MZ 1P 16 A M15 M 8 A M25 1P 16 A M25 2P 8 A ES 50/3 For relay: MZ B 1P 5/10 A MZ 2P 5/10 A MZ 1P 16 A M15 B 8 A

71 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Current transducer Model: CS Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

72 CURRENT SENSORS Detect current fluctuation remotely and reliably Solid Core CS-450 & CS-475 Series Current Sensors Split Core SC-550 & SC-575 Series Current Sensors CT/PT Input transducer Peace of mind through reliable current sensors GREYSTONE IS AN ISO 9002 REGISTERED COMPANY

73 AC CURRENT SENSORS CS-450 / 475 and SC-550 / 575 DESCRIPTION: The CS-450 / 475 and SC-550 / 575 series of AC current sensors are solid-state transducers that convert a primary circuit current to a proportional output signal. The sensors can monitor up to 200 Amps continuous and feature three jumper selectable current ranges for the highest accuracy. All sensors are factory calibrated to ensure better than SPECIFICATIONS: FEATURES: CS-45X / SC-55X Power Supply 0-5/0-10 Vdc models are self-powered, 4-20 ma model requires Vdc at sensor SOLID-STATE SENSORS FOR MONITORING AC CIRCUITS. Three ranges per unit reduces inventory No field adjustment necessary, factory calibrated Average measurement is equivalent to True RMS for pure sine waves for the CS-450 / SC-550 series True RMS measurement for sine waves or variable frequency drives for the CS-475 / SC-575 series Input / Output isolation via current transformer Solid-state reliability Small compact size 1% accuracy. The CS-450 and the SC-550 are available with 0-5, 0-10 Vdc or 4-20 ma output signal types. The CS-475 and the SC-575 feature a true RMS 4-20 ma loop-powered output signal. All models are CSA certified, UL Approved and CE compliant. CS-475 / SC Vdc at sensor (loop powered) Input Current Ranges Three field selectable ranges (see below) Maximum Input Current 10/20/50 Amp ranges-80/120/180 Amps continuous 50/100/200 Amp ranges-120/200/325 Amps continuous Three field selectable ranges (see below) 2/5/10 Amp ranges 35/60/90 Amps continuous 10/20/50 Amp ranges 80/120/200 Amps continuous 50/100/200 Amp ranges 175/300/400 Amps continuous Response Time 100 ms (0-90%) 250 ms (0-90%) AC Conductor Hole Solid Core 20mm (0.8 ) diameter Split Core 24 x 19 mm (0.95 x 0.75 ) Output Loading Error (0-5/0-10) Calibrated with 1 M ohm load, add 1.2% error with 100k ohm load Enclosure Size (H x W x D) Solid Core 49 x 87 x 25 mm (1.95 x 3.45 x 1.0 ) Split Core 70 x 87 x 30 mm (2.75 x 3.45 x 1.2 ) Operating Temperature -30 to 70 C (-22 to 158 F) Operating Humidity 0 to 95% RH, non-condensing Protection Circuitry Reverse voltage protected and output limited Wiring Connections Solid Core Barrier strip Split Core Screw terminals (14 to 22 AWG) Enclosure Material UL 94 V-0 flammability rated ABS, Insulation class 600V Manufacturing ISO 9002 Certified Output Signal & Accuracy 0-5 Vdc, 0-10 Vdc or 4-20 ma Better than ±1% FS on all three ranges Solid Core 20mm (0.8 ) diameter Split Core 24 x 19 mm (0.95 x 0.75 ) N/A Solid Core 49 x 87 x 25 mm (1.95 x 3.45 x 1.0 ) Split Core 70 x 87 x 30 mm (2.75 x 3.45 x 1.2 ) 0 to 70 C (32 to 158 F) 0 to 95% RH, non-condensing Reverse voltage protected and output limited Solid Core Barrier strip Split Core Screw terminals (14 to 22 AWG) UL 94 V-0 flammability rated ABS, Insulation class 600V ISO 9002 Certified 4 to 20 ma represents 0 to 100% of current span Better than ±1% FS on all three ranges CURRENT SENSOR: PRODUCT ORDERING INFORMATION Solid Core (CS) Split Core (SC) Model Output Accuracy Frequency Amp Ranges Model Output Accuracy Frequency Amp Ranges CS Vdc ±1% FSO Hz 0-10/0-20/0-50 SC Vdc ±1% FSO Hz 0-10/0-20/0-50 CS Vdc ±1% FSO Hz 0-50/0-100/0-200 SC Vdc ±1% FSO Hz 0-50/0-100/0-200 CS Vdc ±1% FSO Hz 0-10/0-20/0-50 SC Vdc ±1% FSO Hz 0-10/0-20/0-50 CS Vdc ±1% FSO Hz 0-50/0-100/0-200 SC Vdc ±1% FSO Hz 0-50/0-100/0-200 CS ma ±1% FSO Hz 0-10/0-20/0-50 SC ma ±1% FSO Hz 0-10/0-20/0-50 CS ma ±1% FSO Hz 0-50/0-100/0-200 SC ma ±1% FSO Hz 0-50/0-100/0-200 CS ma ±1% FSO Hz 0-2/0-5/0-10 SC ma ±1% FSO Hz 0-2/0-5/0-10 CS ma ±1% FSO Hz 0-10/0-20/0-50 SC ma ±1% FSO Hz 0-10/0-20/0-50 CS ma ±1% FSO Hz 0-50/0-100/0-200 SC ma ±1% FSO Hz 0-50/0-100/0-200 GREYSTONE ENERGY SYSTEMS INC.

74 Solid Core CS-450 & CS-475 Series Current Sensor Split Core SC-550 & SC-575 Series Current Sensor 20 mm (0.8 ) diam. 49 mm (1.95 ) 19 mm (0.75 ) 24 mm (0.95 ) 70 mm (2.75 ) 87 mm (3.45 ) 25 mm (1.0 ) 87 mm (3.45 ) 30 mm (1.2 ) Options Relay Mounting Base CR-112 / CR-124 DESCRIPTION: The CR-112 and CR-124 Command Relays are line voltage relays for use with the CS and SC current sensors and switches or as SPECIFICATIONS: (NOTE: COMMAND RELAY DOES NOT ACCEPT A VARIABLE ANALOG SIGNAL Relay Coil CR-112 CR-124 Relay Contacts 12 Vac/dc ± 18 ma 24 Vac/dc ± 10 ma SPDT Form C (normally open, common, normally closed) 10 Amp 250 Vac (UL508) 8 Amp 250 Vac 5 30 Vdc Greystone Energy Systems Inc. 150 English Drive, Moncton, NB Canada E1E 4G7 (506) Fax: (506) mail@greystoneenergy.com Enclosure Size (L x W x D) Mounting Holes Dimension 102 x 44 x 25 mm (4 x 1.75 x 1 ) 125 mm (4.9 ) length with mounting tabs 114 mm (4.5 ) spacing, 4.8 mm (0.19 ) diameter Contact Resistance 100 mω maximum Enclosure Material UL 94V-0 flammability rated ABS Oper. Temperature -40 to 85 C (-40 to 185 F) Operating Humidity 20 to 85% RH, non-condensing Wiring Connections Screw terminal block (12 to 28 AWG) FEATURES: Can be easily mounted to any CS or SC product for easier installation Can be used as a stand-alone relay Convenient Relay Status LED Can be factory assembled with any CS or SC product Push-rivets supplied for fast and reliable field assembly SPDT Form C relay contacts Environmentally-friendly cadmium-free contacts Ideal for switching contactors, solenoids and motors Small compact size stand-alone devices. All models are CSA certified, UL approved and CE compliant. Manufacturing Process ISO 9002 Certified Greystone Energy Systems Inc. is one of North America s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation Management Systems. We have conscientiously established a worldwide reputation as an industry leader by maintaining leading-edge design technology, prompt technical support, and a commitment to on-time deliveries. We take pride in our Quality Management System which is ISO 9002 certified, assuring our customers of consistent product reliability. GREYSTONE IS AN ISO 9002 REGISTERED COMPANY Copyright Greystone Energy Systems Inc. All Rights Reserved

75 Malaspina University-College School of Management Centre 900 Fifth Street, Nanaimo BC DDC Controls Shop Drawing Submittal Submitted To: Windley Contracting Ltd Shenton Road Nanaimo, British Columbia V9T 2H1 Submitted By: houle controls (a div. of houle electric ltd.) Joe LeRoy, P.Eng Devonshire Rd. Victoria, BC V9A 4T Submittal Details: Date Submitted: 3/30/2006 Date Resubmitted: Specification Section: Description: Differential pressure sensor Model: LP1B00 Supplier info: Address: Manufacturer info: Address: Website Pacific Controls Ltd. 440 Garbally Road, Victoria, BC V8T 2S9 Greystone Energy Systems Inc. 150 English Drive, Moncton, NB E1E 4G7

76 LOW PRESSURE TRANSDUCERS LP1 Series Shown above c/w LCD and mounted static probe options Each series of Greystone low pressure transducers comes standard with an ABS enclosure. These transducers feature high level outputs, environmental protection, and temperature compensation. FEATURES: Jumper selectable 2 wire current and 3 wire voltage outputs standard 24 Vac/dc power supply standard Eight variable jumper selectable pressure range s, WC and PA Functional weather resistant ABS Enclosure Available options include LCD display and mounted static probe Two available accuracy's Peace of mind through reliable pressure transducers GREYSTONE HAS AN ISO 9001 REGISTERED QUALITY SYSTEM

77 APPLICATIONS: HVAC/VAV Process Control Air Flow Monitoring Drop Across Air Filters Hydraulic Pressures Pneumatic Pressures SPECIFICATIONS: LP1 Series Pressure Ranges See ordering information Calibration Accuracy Measurement Type Response Time Stability Thermal Effects Compensated Range Over Pressure Operating Conditions Media Compatibility Power Supply (at transmitter) Supply Current Input Voltage Effect Protection Circuitry Output Signal Current Output Drive Capability Voltage Output Drive Capability Zero Adjustment Wiring Connections Pressure Connections Conduit Connection Optional LCD Enclosure ± 1% F.S.O. (LP1A/B Series) Differential (two port) 1 ms maximum <±1% F.S.O. per year <±3% over compensated range C ( F) 20 psi or 2 x range (whichever is greater) 0 60 C ( F), 10 90% RH non-condensing Limited only to those that will not attack polyetherimide, silicon, fluorosilicone, silicone, EPDM, and neoprene seals. Typically dry air or inert gas but liquid is allowed Vac, Vdc (non-isolated half-wave rectified) <4 ma Negligible over specified operating range Reverse voltage protected and output limited 4 20 ma (2-wire), 0 5 Vdc or 0 10 Vdc (3-wire) 400 ohms 24 Vdc 2 Kohms minimum for 0-5 Vdc signal 10 Kohms minimum for 0-10 Vdc signal Pushbutton auto-zero Screw terminal block (14 to 22 AWG) Barbed ports for ID flexible tubing Access hole for 1/2 NPT conduit or cable gland 3½ digit, 0.4 digit height ± 1.25% F.S.O. (LP1C Series) High Impact Black ABS, plenum rated with optional gasket 116 mm W x 84 mm H x 53 mm D (4.55 x 3.3 x 2.1 ) LP1 c/w LCD LP1 c/w LCD & Mounted static probe GREYSTONE ENERGY SYSTEMS INC.

78 DESCRIPTION: The LP1 Low Pressure Transmitter can be used to measure positive, negative or differential pressure in the ranges of 0.25 wc to 12 wc (50 TO 2000Pa). The piezoresistive sensor is ideal for monitoring the pressure for air or other clean inert gas and is limited only to those media which will not attack polyetherimide, silicon, fluorosilicone, silicone, EPDM and neoprene seals. The LP1 features field selectable pressure ranges and output signal types for the most flexible application. Typical HVAC applications include monitoring of filter differential pressure or clean room pressure. The output signal is factory calibrated and temperature compensated for highest startup accuracy and trouble-free operation. Available options include accuracy s, LCD, mounted static pressure probes and access options for room pressure monitoring. Please read the installation instructions carefully before commissioning the pressure transmitter. Failure to follow the instructions may result in product damage. A qualified technician must install this device. The LP1 Pressure Transmitter mounts on any surface using the two holes provided on the base of the unit. Make sure there is enough space around the unit to connect the pressure tubing without kinking and avoid locations where severe vibrations or excessive moisture are present. Mount the enclosure with two user-supplied screws but do not over-tighten. The unit may be mounted in any position but typically is installed on a vertical surface with the pressure ports on the right and the cable entrance on the left. The enclosure has a standard ½ conduit opening and may be installed with either conduit and a conduit coupler or a cable gland type fitting. Do not use in an explosive or hazardous environment, with combustible or flammable gasses, as safety or emergency stop devices or in any other application where failure of the product could result in personal injury. Use electrostatic discharge precautions during installation and do not exceed the device ratings. JUMPER SELECTABLE LP1 SERIES: PRODUCT ORDERING INFORMATION Model LP1 Description Jumper Selectable Low Pressure Transducer CODE A B C Optional accuracy's ± 1% F.S.O. LCD Display (Only available in ± 1% configuration) ± 1.25 % F.S.O. CODE Jumper Selectable Pressure Ranges ±0.25, ±0.5, ±1, ±2, 0-0.5, 0-1, 0-2, 0-4 wc ±0.75, ±1.5, ±3, ±6, 0-1.5, 0-3, 0-6, 0-12 wc ±50, ±100, ±200, ±400, 100, 200, 400, 800 Pa ±125, ±250, ±500, ±1000, 250, 500, 1000, 2000 Pa CODE S R Options Mounted Static Pressure Probe (N/A with LP1C series) Room Pressure Model, all electrical and pressure connections on back LP1 B 00 S Typical Model Number Example: LCD, ±0.25 to 0-4 wc, Static Pressure Probe GREYSTONE ENERGY SYSTEMS INC.

79 DIMENSIONS: 116 mm (4.55") 53 mm (2.1") 84 mm (3.3") ABS enclosure dimensions OPTIONS: Pitot Tube HFO & HSO Series The HFO and HSO series are used to sense velocity pressure or static pressure respectively. Available in 6 length. Kits are available for differential and static that are complete with pneumatic tubing. Static Probe Option The S option is a high accuracy static tube. It is available as an option on the LP1A / B Series low pressure transducer. Differential Pressure Probe SSS Series The SS series DP probe is used for sensing velocity pressure in the duct. Available in 4, 6, 8 & 10 lengths. Kits are available that come complete with pneumatic tubing. 150 English Drive, Moncton, NB, Canada E1E 4G7 mail@greystoneenergy.com Tel.: (506) Fax: (506) web site: Greystone Energy Systems Inc. is one of North America s largest ISO registered manufacturers of HVAC sensors and transducers for Building Automation Management Systems. We have conscientiously established a worldwide reputation as an industry leader by maintaining leadingedge design technology, prompt technical support, and a commitment to on-time deliveries. We take pride in our Quality Management System which is ISO 9001 certified, assuring our customers of consistent product reliability.

A C C U R A C Y B Y D E S I G N

A C C U R A C Y B Y D E S I G N A C C U R A C Y B Y D E S I G N Precision temperature control/sensing TEMPERATURE SENSORS TE200 Series FEATURES: Thermistor, Precision RTD or I.C. sensing element Various configurations available, i.e.:

More information

Precision temperature control/sensing

Precision temperature control/sensing PROBE TEMPERATURE SENSORS TE200 Series Precision temperature control/sensing FEATURES: Thermistor or Precision RTD Various configurations available Selection of enclosures Custom laser etching available

More information

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 NPT

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 NPT 1/4 to 2 NPT Features Direct mount ISO5211 Full Port 316 stainless steel ball valve 1000 PSI working pressure at 100 F (38 C) Highly visual dome style valve position indicator Rugged aluminum Type 4X weatherproof

More information

Precision humidity/temperature control/sensing

Precision humidity/temperature control/sensing HIGH ACCURACY HUMIDITY/TEMPERATURE TRANSMITTER HAHT Series Precision humidity/temperature control/sensing FEATURES: Highly stable RH sensor element Humidity range: 0-100% Accuracy available 1% & 2% High

More information

SECTION THERMAL UTILITY METERING INTERFACE

SECTION THERMAL UTILITY METERING INTERFACE SECTION 25 33 13 THERMAL UTILITY METERING INTERFACE GENERAL 1.1 SUMMARY A. Section includes metering and monitoring for interface points for utility chilled water, hot water, and steam fed to each building,

More information

AF24-MFT (-S) US Proportional damper actuator, Spring Return Fail-Safe, Multi-Function Technology

AF24-MFT (-S) US Proportional damper actuator, Spring Return Fail-Safe, Multi-Function Technology AF4-MFT (-S) US Proportional damper actuator, Spring Return Fail-Safe, Multi-Function Technology Torque min. in-lb Control to 0 VDC (DEFAULT) Feedback to 0 VDC (DEFAULT) Application For proportional modulation

More information

BA/BS4S Temperature Sensor Installation & Operating Instructions

BA/BS4S Temperature Sensor Installation & Operating Instructions Product Overview and Identification The BAPI-Stat 4 room temperature sensor features a large format LCD and slider setpoint adjustment. Additional options include button override and communication jack.

More information

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN 1 2 8 4 AI6 R R Installation Bulletin UNT1100 Issue Date 0309 UNT1100 Series Introduction The Unitary (UNT) controller (UNT1100 Series) is a digital controller with applications for air handling units,

More information

NKQB24-1, NKQX24-1 On/Off, Fail-Safe, Operation, Direct Coupled, 24V

NKQB24-1, NKQX24-1 On/Off, Fail-Safe, Operation, Direct Coupled, 24V NKQB24-1, NKQX24-1 On/Off, Fail-Safe, Operation, Direct Coupled, 24V orque min. 54 in-lb for control damper surfaces up to 12 sq ft. Application For proportional modulation of dampers in HVAC systems.

More information

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90 Cloud capable and communicating failsafe valve actuator for adjusting flow in commercial HVAC applications. Failsafe Power Supply AC/DC 24 V Used for CCV and LGCCV assemblies. Ethernet 10/100 Mbit/s, TCP/IP,

More information

VAV Modular Assembly (VMA) 1410/1420

VAV Modular Assembly (VMA) 1410/1420 Installation Instructions Issue Date June 9, 2004 VAV Modular Assembly (VMA) 1410/1420 Application The Variable Air Volume (VAV) Modular Assembly (VMA) 1400 Series consists of configurable digital controllers.

More information

Easy Flow Indicator Magnetisch-Induktiver Durchflussmesser. Type 8024 For Insertion Fittings. Analog Flow Rate Indicator, 1/2"-16"; P=87 PSI

Easy Flow Indicator Magnetisch-Induktiver Durchflussmesser. Type 8024 For Insertion Fittings. Analog Flow Rate Indicator, 1/2-16; P=87 PSI Analog Flow Rate Indicator, 1/2"-16"; P=87 PSI Advantages / Benefits Reduced costs of ownership up to 6% Economic integration in pipe systems without any additional piping Shows flow rate with a clear,

More information

Industrial Electric Actuators AC and DC Voltages Nm/ inch lbs

Industrial Electric Actuators AC and DC Voltages Nm/ inch lbs Industrial Electric Actuators AC and DC Voltages 30-200Nm/265-1770 inch lbs Features Quarter turn (90 ) operation with mechanical travel stops Type 4X/IP67 weatherproof aluminum alloy enclosure Highly

More information

Functional data Position indication reflective visual indicator (snap on) Communicative control Cloud: (call for clientapi )

Functional data Position indication reflective visual indicator (snap on) Communicative control Cloud: (call for clientapi ) Technical data sheet AKRB24 IP Cloud capable and communicating valve actuator for adjusting flow in commercial HVAC applications. Failsafe Power Supply AC/DC 24 V Used for CCV and LGCCV assemblies. Ethernet

More information

Precision humidity/temperature sensing/control

Precision humidity/temperature sensing/control HUMIDITY/TEMPERATURE SENSOR BACnet or Modbus Communication NT Series Precision humidity/temperature sensing/control FEATURES: BACnet or Modbus communication Temperature and RH monitoring Room, Duct or

More information

Functional data Nominal torque min. 180 in lb [20 NM] Communicative control Cloud: (call for clientapi )

Functional data Nominal torque min. 180 in lb [20 NM] Communicative control Cloud: (call for clientapi ) Cloud capable and communicating failsafe damper actuator for adjusting dampers in commercial HVAC applications. Failsafe Air Damper Size Up to approx. 45 sq. ft. Nominal Torque 180 in lb [20 NM] Power

More information

Siemens BACnet Programmable TEC Unit Conditioner Controller

Siemens BACnet Programmable TEC Unit Conditioner Controller Technical Specification Sheet Document No. 149-831 September 24, 2014 Siemens BACnet Programmable TEC Unit Conditioner Controller Returns from power failure without operator intervention. No calibration

More information

Siemens BACnet Programmable TEC Constant Volume

Siemens BACnet Programmable TEC Constant Volume Technical Specification Sheet Document No. 149-852 September 24, 2014 Siemens BACnet Programmable TEC Constant Volume Returns from power failure without operator intervention. No calibration required,

More information

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90

Functional data Communicative control Cloud: (call for clientapi ) Angle of rotation 90 Cloud capable and communicating valve actuator for adjusting flow in commercial HVAC applications. Non-Failsafe Power Supply AC/DC 24 V Used for CCV and LGCCV assemblies Ethernet 10/100 Mbit/s, TCP/IP,

More information

RWD68U Universal Controller

RWD68U Universal Controller Document No. 155-738 RWD68U Universal Controller Description Features Product Number The Universal Controller is intended for heating, air conditioning, ventilation and refrigeration in comfort control

More information

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W Differential Pressure Sensor (Air) Differential pressure transmitter with 8 selectable ranges 0 to 5/10 V, 4 to 20 ma outputs and Modbus functionality. NEMA 4X / IP65 rated enclosure. For monitoring the

More information

PS-AULDP Series. Overview. Applications. Features & Benefits. Datasheet. Ultra Low Air Differential Pressure Transmitters

PS-AULDP Series. Overview. Applications. Features & Benefits. Datasheet. Ultra Low Air Differential Pressure Transmitters PS-AULDP Series Datasheet Ultra Low Air Differential Pressure Transmitters Overview The PS-AULDP Series are ultra-low-pressure transmitters. These devices can be used to measure differential pressure between

More information

Signet 2552 Metal Magmeter Flow Sensors

Signet 2552 Metal Magmeter Flow Sensors Signet 2552 Metal Magmeter Flow s Features Test certificate included Award winning hot-tap magnetic flow sensor up to DN2550 (102 in.) Patented Magmeter technology* Operating range 0.05 to 10 m/s (0.15

More information

NKQB24-1, NKQX24-1 On/Off, Electronic Fail-Safe, Direct Coupled, 24V

NKQB24-1, NKQX24-1 On/Off, Electronic Fail-Safe, Direct Coupled, 24V NKQB24-1, NKQX24-1 On/Off, Electronic Fail-Safe, Direct Coupled, 24V orque min. 54 in-lb for control damper surfaces up to 12 sq ft. Application For on/off, fail-safe control of dampers in HVAC systems.

More information

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller Technical Specification Sheet Document No. 149-831 August 12, 2011 Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller No calibration required, thereby reducing maintenance costs. PID

More information

Control IT Booster Pump Controller

Control IT Booster Pump Controller Data Sheet SS/_4 Control IT Booster Pump Controller Protection for the pasteurization process ensuring a high quality, safe product for your customers High visibility LED displays continuous indication

More information

Zone Pressure Touch Sensor - Standard Range

Zone Pressure Touch Sensor - Standard Range Overview The Zone Pressure Touch (ZPT) Sensor is an accurate, rugged and economical solution for measuring and reporting duct/ building static pressure, room-to-room differential pressure or air velocities/volumes.

More information

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control Technical Specification Sheet Document No. 149-844 August 12, 2011 Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control Returns from power failure without operator intervention.

More information

Bulletin 871D Cylinder Position Inductive Style

Bulletin 871D Cylinder Position Inductive Style Bulletin 871D Cylinder Position Inductive Style Description Bulletin 871D cylinder position inductive proximity sensors are self-contained solid state devices. These devices are designed for sensing metal

More information

M6410A, M7410F Small Individual Room Controller (IRC) Electric Linear Valve Actuators

M6410A, M7410F Small Individual Room Controller (IRC) Electric Linear Valve Actuators M60A, M70F Small Individual Room Controller (IRC) Electric Linear Valve Actuators FEATURES PRODUCT DATA M60A and M70F Underwriters Laboratories Inc. rated for plenum use (UL9-5V). Especially suitable for

More information

PP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions

PP-8516 & PP Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions PP-8516 & PP-8616 Electronic Static Pressure Controllers and Transmitters for Cental Air Supply Systems General Instructions Part Number PP-8516 Static Pressure Controller/Transmitter PP-8616 Static Pressure

More information

TC-9102 Terminal Controller

TC-9102 Terminal Controller Metasys Network Sales Resource Manual 635 Application Specific Controllers Section Product Bulletin Issue Date 1095 TC-9102 Terminal Controller The TC-9102 Terminal Controller, the latest addition to the

More information

ECON-ZIP-BASE. ZIP Economizer Base Module

ECON-ZIP-BASE. ZIP Economizer Base Module ECON-ZIP-BASE ZIP Economizer Base Module You can mount the ZIP Economizer in any orientation; it is recommended that you mount it in a position that will allow full utilization of the LCD and key pad and

More information

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control

Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control Powermite 599 MT Series SAS Electronic Valve Actuator 24 Vac or 24 Vdc, Proportional Control Description Features Application The Powermite 599 MT Series SAS Electronic Valve Actuator requires a 24 Vac

More information

MRC 7000 Proven Recording Reliability that Became the Industry Standard!

MRC 7000 Proven Recording Reliability that Became the Industry Standard! Data Sheet Recorder//Profiler DESCRIPTION The MRC7000 Recorder/ is a microprocessor based circular chart instrument capable of measuring, displaying, recording and controlling up to two process variables

More information

Conductivity Transmitters

Conductivity Transmitters Conductivity Transmitters CDTX-90 Series Starts at $ 576 Electronics Only Display in µs, ms, kω, MΩ, ppm (TDS) Simulate Function Programmable Temperature Compensation Relay Options Dual Output Option Allows

More information

VA-7700 Series. Electric Valve Actuators. Product Bulletin

VA-7700 Series. Electric Valve Actuators. Product Bulletin VA-7700 Series Electric Valve Actuators Product Bulletin The VA-77xx Series synchronous motor driven actuator, for valves in heating, ventilation and air conditioning applications, is available for floating

More information

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller Technical Specification Sheet Document No. 149-851 September 24, 2014 Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller The Siemens BACnet PTEC Dual Duct Controller provides

More information

HTZ. Description. Features. Smart HART Humidity and Temperature Transmitter

HTZ. Description. Features. Smart HART Humidity and Temperature Transmitter March 2018 Description The HTZ Smart HART Transmitter simultaneously measures humidity and temperature in industrial, commercial, manufacturing, and HVAC applications. Based on the humidity and temperature

More information

Zone Pressure Touch (ZPT) Sensor - Standard Range

Zone Pressure Touch (ZPT) Sensor - Standard Range Product Identification BAPI s Touch Pressure Sensor is an accurate, rugged and economical solution for measuring and reporting duct/ building static pressure, room-to-room differential pressure or air

More information

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval.

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on

More information

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN

ECON-ZIP-BASE. ZIP Economizer Base Unit. Wiring Diagram USA CANADA LATIN AMERICA / CARIBBEAN ECON-ZIP-BASE ZIP Economizer Base Unit 24 VAC ± 20%, 50/60 Hz; Class 2 power source 4 VA Base Control (ECON-ZIP-BASE) 5.5 VA Base Control with Energy Module (ECON-ZIP-BASE + ECON-ZIP-EM) Power Consumption

More information

TPE 1464 Series Pressure Transducer

TPE 1464 Series Pressure Transducer TPE 1464 Series Pressure Transducer Description The KMC TPE 1464 series of pressure transducers incorporate a gauge pressure transmitter featuring low hysteresis, excellent repeatability, and longterm

More information

HMT330 Series Humidity and Temperature Transmitters for Industrial Applications

HMT330 Series Humidity and Temperature Transmitters for Industrial Applications HMT330 Series Humidity and Temperature Transmitters for Industrial Applications The HMT330 transmitter family has the solution for demanding industrial humidity measurements. Six models for demanding industrial

More information

INSTRUCTION MANUAL MODEL RTI-EC RESISTANCE TEMPERATURE INDICATOR TABLE OF CONTENTS 1. GENERAL DESCRIPTION PAGE 1

INSTRUCTION MANUAL MODEL RTI-EC RESISTANCE TEMPERATURE INDICATOR TABLE OF CONTENTS 1. GENERAL DESCRIPTION PAGE 1 DEVAR Inc. 706 Bostwick Avenue, Bridgeport, CT 06605 TEL: 203-368-6751 FAX: 203-368-3747 1-800-566-6822 www.devarinc.com INSTRUCTION MANUAL MODEL RTI-EC RESISTANCE TEMPERATURE INDICATOR TABLE OF CONTENTS

More information

Type Electrically Actuated 3-way Ball Valves

Type Electrically Actuated 3-way Ball Valves GF Piping Systems Electrically Actuated 3-way Ball Valves Type 167-17 General Size: ⅜ 2 aterial: PVC, CPVC, PROGEF Standard PP, ABS, SYGEF Standard PVDF Seat: PTFE Seals: EPD, FP End Connection: Solvent

More information

Humidity goes Digital

Humidity goes Digital Humidity goes Digital Networkable Industrial Transmitter Humidity, Temperature and Dew Point or other Computed Parameter Optional metal enclosure Unique HygroClip technology for superior performance Durable,

More information

FXVMA Variable Air Volume (VAV) Box Controller

FXVMA Variable Air Volume (VAV) Box Controller FXVMA Product Bulletin FXVMA Issue Date November 21, 2008 FXVMA Variable Air Volume (VAV) Box Controller The FXVMA is an integrated assembly used to control Variable Air Volume (VAV) boxes. The FXVMA consists

More information

ECP-VAV Series. ECP-VAV Series. 10-Point Single Duct VAV / VVT Free Programmable Controller. Applications. Features

ECP-VAV Series. ECP-VAV Series. 10-Point Single Duct VAV / VVT Free Programmable Controller. Applications. Features ECP-VAV Series 10-Point Single Duct VAV / VVT Free Programmable Controller Applications Designed to meet the requirements of single duct variable air volume (VAV) or variable volume according to temperature

More information

Wall-/Pipe Mounted Universal Process Indicator

Wall-/Pipe Mounted Universal Process Indicator Data Sheet SS/_8 Wall-/Pipe Mounted Universal Process Indicator High visibility LED display the clearest view of your process status 0.1% measurement accuracy precise indication of process measurement

More information

Temperature Switches

Temperature Switches ETS 00 Series Temperature Switch for Inline and Tank Mounting Applications Description The ETS 00 is a compact electronic temperature switch with 4-digit digital display. Pressure resistant to 8700 psi,

More information

! Ranges from -45º to 650ºC. ! Rapid heating, cooling and settling. ! Switch test, ramp, step and preset functions

! Ranges from -45º to 650ºC. ! Rapid heating, cooling and settling. ! Switch test, ramp, step and preset functions DBC SERIES DBC 150/650 Series Dry Block Temperature Calibrators 99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com! s from -45º to 650ºC! Rapid heating, cooling and settling!

More information

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010

STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 STT 3000 Series STT250 Smart Temperature Transmitters Specifications Models STT25H, STT25S, STT25M, STT25D EN0I-6031 March 2010 Introduction Honeywell s STT 3000 family of microprocessor based smart temperature

More information

SRQ24A. Technical data. Safety notes. Rotary actuator for ball valves Torque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s

SRQ24A. Technical data. Safety notes. Rotary actuator for ball valves Torque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s SRQ24A Rotary actuator for ball valves orque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s echnical data Electrical data Nominal voltage AC 24V, 50/60Hz / DC 24V Nominal voltage range

More information

Compact Electric Actuators AC and DC Voltages 18 Nm/160 inch lbs

Compact Electric Actuators AC and DC Voltages 18 Nm/160 inch lbs Compact Electric Actuators AC and DC Voltages 18 Nm/160 inch lbs Features Miniature industrial quality quarter turn (90 ) rotation Excellent power to size ratio only 4.6 H x 3 D Type 4X and IP67 weatherproof

More information

A CLOSER LOOK. Electronic Fail-Safe Series Direct Coupled Actuators. The Belimo Difference. Brushless DC Motor for Added Accuracy and Controllability

A CLOSER LOOK. Electronic Fail-Safe Series Direct Coupled Actuators. The Belimo Difference. Brushless DC Motor for Added Accuracy and Controllability Electronic Fail-Safe Series Direct Coupled Actuators A CLOSER LOOK Brushless DC Motor for Added Accuracy and Controllability Cut Labor Costs with Simple Direct Coupling Self-Centers on 1.05" or 3/4" with

More information

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications LAUREL ELECTRONICS, INC. Laureate RTD Temperature Panel Meter / Controller Features Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs 2, 3 or 4-wire connection with lead resistance compensation

More information

Fast Route to Reliable Energy Savings ZIP Economizer

Fast Route to Reliable Energy Savings ZIP Economizer Fast Route to Reliable Energy Savings ZIP Economizer LCD Display Automotive quality, easy-to-read display allows easy verifi cation of set values and real time operating information Alarm Notification

More information

TEC Terminal Box (VAV) Controller

TEC Terminal Box (VAV) Controller Document No. 540-1025 TEC Terminal Box (VAV) Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2020 through 2027 Product Description These

More information

DMT345 and DMT346 Dewpoint Transmitters

DMT345 and DMT346 Dewpoint Transmitters DMT345 and DMT346 Dewpoint Transmitters for High Temperature Applications Features DMT345 measures humidity at temperatures up to 180 C (356 F) DMT346 measures humidity at temperatures up to 350 C (+662

More information

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency echnical data sheet LR24A-MOD Communicative rotary actuator for ball valves orque motor 5 Nm Nominal voltage AC/DC 24 V Control modulating,, hybrid mode Conversion of sensor signals Communication via BACnet

More information

Technical data sheet

Technical data sheet ZoneEase VAV Cloud VAV Controller set with Room Unit of Choice and Integrated pressure sensor, controller and damper actuator for pressure-independent temperature control VAV, Simple VAV and Demand Control

More information

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions Product Identification BAPI s Touch Low Range Pressure Sensor with Attached Static Pressure Probe is an accurate, rugged and economical solution for measuring and reporting duct/building static pressure,

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate RTD Temperature Panel Meter / Controller Features Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs 2, 3 or 4-wire connection with lead resistance compensation

More information

A 101 A B C. Variable flow-control valve, series DXC. Dynamic Flow Networking. Description. Content

A 101 A B C. Variable flow-control valve, series DXC. Dynamic Flow Networking. Description. Content 101 DX Variable flow-control valve, series DX Pressure independent variable flow-control Dynamic hydronic balancing in full load and part load Integrated flow and temperature measurement Power supply U

More information

DMP 333 DMP 333. Industrial Pressure Transmitter For High Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial

DMP 333 DMP 333. Industrial Pressure Transmitter For High Pressure. Stainless Steel Sensor. Pressure Transmitter. Industrial DMP Industrial Pressure Transmitter For High Pressure Stainless Steel Sensor accuracy according to IEC 60770: standard: 0.5 % FSO option: 0.5 / 0. % FSO Industrial Pressure Transmitter DMP Nominal pressure

More information

CDD4 Series Room CO2 Transmitter Installation Instructions

CDD4 Series Room CO2 Transmitter Installation Instructions CDD4 Series Room CO2 Transmitter Installation Instructions Introduction The CO2 transmitter uses Infrared Technology to monitor CO2 levels and outputs a linear 4-20 ma or 0-5/0-10 Vdc signal. Options include

More information

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities

MiG2 CONTROLLERS. 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities MiG2 CONTROLLERS 2 & 4 Stage General Purpose Controllers, with Air-conditioning Facilities The MiG2 controllers incorporate: 2 Inputs (Configurable as Resistive, 0 10V, 0 20mA or 4 20mA) 2 or 4 Relay Outputs

More information

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller Technical Specification Sheet Document No. 149-851 August 12, 2011 Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller The Siemens BACnet PTEC Dual Duct Controller provides high

More information

Level-Lance Model 5400A

Level-Lance Model 5400A Sales Manual Section 100 PRODUCT SPECIFICATION 5400A GENERAL DESCRIPTION The ROBERTSHAW Level-Lance Model 5400A is a microprocessor based, multi-point On-Off capacitance type level detection system. Utilizing

More information

T EN TROVIS Electropneumatic Positioner

T EN TROVIS Electropneumatic Positioner T 8484-1 EN TROVIS 3730-1 Electropneumatic Positioner Application Single-acting positioner for attachment to pneumatic globe and rotary valves. Self-calibrating, automatic adaptation to valve and actuator.

More information

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 12/99 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC 1000 and UDC 1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers

More information

Inductive Cylinder Position Sensors

Inductive Cylinder Position Sensors Inductive Cylinder Position Sensors 4-Wire DC (NPN and PNP) 2-Wire AC/DC Weld immune 250, 000, and 3000 psi designs C-Series F-Series Rating (psi) Probe Diameter Inductive Cylinder Position Sensors Pepperl+Fuchs

More information

Output signal active note. Output signal. temperature DC V, DC V DC V, DC V DC V

Output signal active note. Output signal. temperature DC V, DC V DC V, DC V DC V Duct Air Quality Sensor Duct air quality sensor for detection of CO₂ with 0 to10 V output. Optional integrated, humidity, VOC sensors and LCD display. Type Overview Type active CO₂ 22DC-11 22DC-110L 22DCK-11

More information

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position) echnical data sheet EF24A- Communicative spring return actuator with emergency function for adjusting air dampers in ventilation and air conditioning systems in buildings For air dampers up to approx.

More information

Siemens BACnet Programmable TEC Unit Vent Controller

Siemens BACnet Programmable TEC Unit Vent Controller Technical Specification Sheet Document No. 149-833 August 12, 2011 Siemens BACnet Programmable TEC Unit Vent Controller The Siemens BACnet PTEC Unit Vent Controller provides high performance Direct Digital

More information

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter

Standard Options. Model 4100 Position Indicating Meter. Three Phase Motor Control. Positran Transmitter Standard Options Model 4100 Position Indicating Meter A percent-of-full-travel meter is supplied with a trim potentiometer resistor, terminal block and connectors. A potentiometer is required in the actuator

More information

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller

Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller Technical Specification Sheet Document No. 149-834 August 23, 2010 Siemens BACnet Programmable TEC VAV with Series Fan and 3-Stage Electric Heat Controller The Siemens BACnet PTEC VAV with Series Fan and

More information

VALVE ACCESSORIES & CONTROLS V100 POSITIONER VAC V100 SERIES POSITIONER SIMPLE DURABLE RELIABLE

VALVE ACCESSORIES & CONTROLS V100 POSITIONER VAC V100 SERIES POSITIONER SIMPLE DURABLE RELIABLE VALVE ACCESSORIES & CONTROLS V100 POSITIONER VAC V100 SERIES POSITIONER SIMPLE DURABLE RELIABLE WWW.VACACCESSORIES.COM 205-678-0507 The V100 Positioner V100-EX The V100E (0/10V) Nema 4x I/P or V100-IS

More information

B. AVM321S/AVM322S: 1000N Actuator with analog SUT positioner

B. AVM321S/AVM322S: 1000N Actuator with analog SUT positioner GB Product Data Sheet 99.70.06-B AVM321S/AVM322S: 1000N Actuator with analog SUT positioner Areas of use For actuation of 2- and 3-way valves. For controllers with constant output (0...10 V / 4...20 ma)

More information

BACnet Terminal Box (VAV) Controller

BACnet Terminal Box (VAV) Controller Technical Specification Sheet May 30, 2012 BACnet Terminal Box (VAV) Controller Figure 1. BACnet Terminal Box Controller. The BACnet Terminal Box Controller (Figure 1) provides high performance Direct

More information

InBin-P Pressure switches from 5 Pa Pa

InBin-P Pressure switches from 5 Pa Pa InBin-P Pressure switches from 5 Pa...100 Pa Electrical, binary pressure or differential pressure switches with adjustable switch activation delay 24 VAC/DC supply voltage, potential free switching contact

More information

DM28 - Economical Digital Process and Strain Gauge Panel Meters

DM28 - Economical Digital Process and Strain Gauge Panel Meters DM28 - Economical Digital Process and Strain Gauge Panel Meters TRANSDUCERS Easily scaled in any engineering units from -19999 to 99999 Large 18mm (.71 ) high red or green display Front panel MIN, MAX

More information

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat Features Modern Appearance Stylish rotary dial and buttons Large LCD with backlight Support Modbus RTU protocol Support standalone operation

More information

14 Pressure Measurement. Measuring Devices Description Pressure range Connection Device Page

14 Pressure Measurement. Measuring Devices Description Pressure range Connection Device Page Measuring Devices Pressure range Connection Device Page Digital display mounting, für niedrige Drücke 0 2. mbar / 2. bar 4 mm tube MPV, MPA.02 portable, hand-operated 0 1 mbar / 10 bar 4 mm tube MHA.03

More information

The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box

The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box Infinity TCX 865,866 VAV Controller with Built-in Actuator The Infinity TCX 865 programmable Infinet terminal controller is a unique, low-cost VAV box controller that comes equipped with a built-in damper

More information

Siemens BACnet VAV Actuator

Siemens BACnet VAV Actuator Technical Specification Sheet Document No. 149-481 May 30, 2012 Siemens BACnet VAV Actuator Setpoints and control parameters assigned and changed locally or remotely. Setpoints and control parameters stored

More information

TEC Unit Conditioner Controller

TEC Unit Conditioner Controller Document No. 540-1026 TEC Unit Conditioner Controller Generic Controller I/O Layout. See Wiring Diagram for application specific details. Control Applications 2040 and 2041 2050 through 2054 Product Description

More information

Flow Measurement SITRANS F M

Flow Measurement SITRANS F M Overview Mode of operation The flow measuring principle is based on araday s law of electromagnetic induction according to which the sensor converts the flow into an electrical voltage proportional to

More information

VZ7000 Series. BACnet Commercial Zoning System

VZ7000 Series. BACnet Commercial Zoning System VZ7000 Series BACnet Commercial Zoning System A cost-effective, scalable zoning system for the commercial market that delivers unparalleled flexibility via the open BACnet communication protocol. VZ7000

More information

HIT/HIX HART Isolator

HIT/HIX HART Isolator / Isolator December 2017 Description Moore Industries Isolators provide highly economical solutions to common and costly problems that plague many of today s smart process loops. Protect and enhance your

More information

AIR QUALITY/ GAS DETECTION

AIR QUALITY/ GAS DETECTION AIR QUALITY/ GAS DETECTION Veris offers an extensive line of CO, and NO 2 sensors. Whether your application requires ventilation of a parking garage or an indoor venue, we have the perfect product for

More information

FX06 Field Controller

FX06 Field Controller Code No. LIT-1900406 Issued October 19, 2012 Facility Explorer FX06 Field Controller The FX06 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

C160 Wall-/Pipe Mounted Universal Process Indicator

C160 Wall-/Pipe Mounted Universal Process Indicator Data sheet DS/ EN Rev. I Wall-/Pipe Mounted Universal Process Indicator reliable process indicator, wherever it s needed High visibility LED display the clearest view of your process status 0.1% measurement

More information

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units

RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units NT10 Series Revision Date April 16, 2014 RS-485 FClink Networking Room Thermostats with LCD for Fan Coil Units Features Ultra slim wall-mount unit to match any decor Supports standalone operation on RS

More information

Digital Indicating Controllers. JC Series. High performance controllers...at the lowest prices anywhere! Toll Free

Digital Indicating Controllers. JC Series. High performance controllers...at the lowest prices anywhere!   Toll Free Digital Indicating Controllers JC Series High performance controllers...at the lowest prices anywhere! www.mod-tronic.com Toll Free 1-800 794-5883 Standard Features Structure Units available in standard

More information

VVP10-H HART VALVE POSITIONER. Great Performance, Compact, Robust in Severe Conditions* HART 7 Communication Protocol. Electronic Coil Technology

VVP10-H HART VALVE POSITIONER. Great Performance, Compact, Robust in Severe Conditions* HART 7 Communication Protocol. Electronic Coil Technology VVP10-H HART VALVE POSITIONER Great Performance, Compact, Robust in Severe Conditions* HART 7 Communication Protocol Electronic Coil Technology Non-Contact Position Sensor (Hall Sensor) 4-20 ma NAMUR NE

More information

Variable Air Volume Modular Assembly (VMA) 1400 Series

Variable Air Volume Modular Assembly (VMA) 1400 Series Product Bulletin Issue Date March 27, 2009 Variable Air Volume Modular Assembly (VMA) 1400 Series The Variable Air Volume Modular Assembly (VMA) Series is a family of configurable digital controllers.

More information

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator

Andover ContinuumTM b3865/866 VAV Controllers with Built-in Actuator Andover ContinuumTM b3865/866 VAV Controllers The Andover Continuum TM b3865 and b3866 are native BACnet controllers that communicate on an RS-485 field bus as Master devices using the MS/TP BACnet protocol.

More information

Family of Water Cut Analyzers

Family of Water Cut Analyzers Phase Dynamics Technology for Precision Measurements Phase Dynamics, Inc. 1251 Columbia Drive Richardson, TX 75081 USA E-Mail sales@phasedynamics.com Tel: 972-680-1550 Fax: 972-680-3262 Family of Water

More information