M1500-UPS-PFP Programmable Home Cinema UPS Owner s Manual

Size: px
Start display at page:

Download "M1500-UPS-PFP Programmable Home Cinema UPS Owner s Manual"

Transcription

1 M1500-UPS-PFP Programmable Home Cinema UPS Owner s Manual M1500-UPS-PFP The M1500-UPS-PFP is a Programmable Uninterruptible Power Supply, Voltage Regulator & Power Conditioner. Patent Pending 1690 Corporate Circle, Petaluma, CA INS00836 REV. A 8/07

2 Table of Contents Important Safety Instructions...pg. 1 Battery Features...pgs. 10, 11 Installing Your UPS...pg. 2 Diagnostics...pg. 11 Basic Operation...pgs. 2, 3 Troubleshooting...pg. 12 Advanced Operation...pgs. 4, 5 Technical Specifications...pg. 12 Home Cinema Power Control Software Installation Instructions...pgs. 5, 6 RS232 Communications Protocol & Command Set...pgs. 13, 14, 15, 16 Home Cinema Power Control Software Instructions...pgs. 7, 8, 9, 10 FCC Notice and Warranties...Pg. 17 Before You Begin UNPACKING Inspect the UPS upon receipt. In addition to this manual the box should contain the following: 1. UPS Unit 2. Power Cord 3. Phone Cord 4. DB 9 Serial Cable 5. Rack Mounting Kit 6. Home Cinema Power Control Software.

3 Important Safety Instructions This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate. CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection. DO NOT plug the machine into an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the UPS. CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIP- MENT! PF Power does not sell products for life support or medical applications. DO NOT use in any circumstance that would affect operation or safety of any life support equipment, with any medical applications, or patient care. CAUTION! To reduce the risk of electric shock, do not remove the cover, except to service the battery. No user serviceable parts inside, except for the battery. CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a component. CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from the aquarium can come in contact with metal current contacts and cause the machine to short out. CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected. CAUTION! To prevent the risk of fire or electric shock install in a temperature and humidity controlled indoor area, free of conductive contaminants. (Please see specifications for acceptable temperature and humidity range). MODEL # M1500-UPS-PFP CAUTION! The 2 silver handles on the battery access panel are for removing the panel only. NOT FOR LIFTING PRODUCT. USA & Canada (800) (707) Fax (707)

4 Installing Your UPS HARDWARE INSTALLATION GUIDE 1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least four hours is recommended to insure that the battery s maximum charge capacity is achieved. Charge loss may occur during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet. The unit will charge in both the ON as well as the OFF position. If you wish to use the software, connect the enclosed serial interface cable to the serial port on the UPS and an open serial port on the computer. 2. With the UPS unit OFF and unplugged, plug your home theater equipment into the unit s rear panel AC outlets. DO NOT plug a laser printer, copier, space heater, vacuum cleaner, paper shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage the unit. 3. To protect a telephone modem line (DVR or Satellite TV receiver) or network cable, connect a telephone cable or network cable from the wall jack outlet to the IN jack of the UPS. Then connect a telephone cable or network cable from the OUT jack on the UPS to the equipment s telephone jack or network device. Note: This unit provides both telephone and LAN protection on one set of RJ-11/45 jacks. The telephone circuit uses pins 4 & 5 while the LAN circuit uses pins 1, 2, 3 & 6. Adapters or custom cables (not included) must be used when utilizing both protection circuits at the same time. 4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e. g. refrigerator, copier, etc.) Avoid using extension cords. If used, the extension cord must be rated for 15 Amps. 5. Press the power switch to turn the UPS on. The Power ON indicator light will illuminate. 6. The rear panel circuit breakers will open and power to the connected equipment will be turned OFF if an overload is detected. To correct this, turn the UPS off, unplug at least one piece of equipment, wait 10 seconds, check to make sure that the circuit breakers are reset, and turn the unit on. 7. The UPS will automatically charge the battery whenever it is plugged into an AC outlet, 8. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 9. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to insure battery life. Basic Operation FRONT PANEL DESCRIPTION Power Switch Press the power button to turn the UPS ON or OFF. Test Switch This UPS performs a self-test automatically when powered on. The test switch allows you to test the system at any time. When the UPS passes the test, it returns to online operation. If the UPS fails the self-test, please recharge the battery for 4 hours and perform another self-test. If it fails after recharging the battery, please replace the battery. In battery mode, you can press this button to silence an audible alarm. Removable Access Panel Easy to remove for battery access and replacement. DO NOT lift product with handles. They are for panel removal only. 2 USA & Canada (800) (707) Fax (707)

5 Basic Operation (continued) FRONT PANEL DISPLAY LED DESCRIPTIONS Power On Indicator This LED is illuminated when the utility condition is normal and the UPS outlets are providing clean, protected power. Line Fault Indicator This LED will illuminate to warn the user that a wiring problem such as a bad/missing ground or reversed wiring exists within the AC receptacle. If illuminated, disconnect all equipment and contact an electrician to insure outlet is properly wired. Unsafe Voltage Indicator This LED will illuminate to inform the user that an unsafe line voltage is present and that the UPS has switched to battery power. This could be either an over-voltage or under-voltage. Battery Level Indicator This is a visual indication of the battery charge. If battery capacity is under 25%, no indicator LED will illuminate and UPS starts beeping (if the audible alarm is enabled) Load Level Indicator This is a visual indication of the UPS load. The 1st arrow will illuminate when the load is above 25%, the 2nd above 50% and the 3rd above 75%. The 4th arrow will flash when the load is between 85% and 100%. Battery Mode Indicator This illuminates during utility failure or an unsafe voltage condition, indicating that the battery is supplying power to the connected equipment. AVR Indicator This indicates that the UPS is operating in automatic voltage regulation mode. When the led is illuminated continuously, it indicates an input over-voltage and the UPS unit reduces (bucks) the voltage to the normal operating range. When the led is flashing, it indicates that the input line voltage is low and that the UPS is increasing (boosts) input voltage to the normal range. REAR PANEL DESCRIPTION Non-Critical-Load Outlets Four battery powered, surge protected and AVR outlets for connected equipment insures temporary uninterrupted operation of connected equipment during a power failure. Critical Load Outlets Two battery powered, surge protected and AVR outlets for critical-load equipment insures temporary uninterrupted operation of connected equipment during a power failure. AC Power Cord Input Receptacle IR Control Section Learning Control Switches Push to program or test the IR function IR Detector Window Receives the IR signal to be learned Indicator LED s Indicates learning status Output Delay Switches Set the desired time delay between a power failure and when the IR signals are sent to the connected equipment IR Output Jacks Standard 1/8 (3.5mm) mono jack for connection to an IR flasher (IR flashers not included) Circuit Breakers for Overload Protection Resettable circuit breakers provide optimal overload protection. RS232 Serial Communication Port The serial port allows connection and communication between the UPS and a HTPC (home theater personal computer) or home automation system. If used temporarily during setup (with the included software), it allows the installer to program a number of variables including the Critical Load Battery Threshold. See the software documentation for more information. RJ11/RJ45 Jacks Ports protect standard telephone line, modem, or network cable. USA & Canada (800) (707) Fax (707)

6 Advanced Operation Audio/Video components such as Digital Video Recorders, DLP projectors and any component with volatile memory can benefit from connection to a UPS. The M1500-UPS-PFP takes this to the next level with a number of features designed specifically for the home theater. Critical Load Function One of the user programmable settings in the Home Cinema Power Control software is the Low Battery NCL Shutoff threshold. This sets the battery capacity level at the point where the non-critical load outlets are turned off and all remaining battery power is reserved for equipment plugged into the 2 critical load outlets. This value is stored internally by the UPS and is not dependent on having the software running on a computer. Learning IR Control *Patent Pending The learning IR function lets you program the UPS to send standby or shut-down commands to components such as DLP ceiling projectors. If the power fails, the projector s lamps are turned off while the UPS continues providing battery power to the projector s cooling fan. Proper shutdown is ensured and expensive lamps are protected from damage. Note: This function should only be used with discrete IR codes. Programming an On/ toggle command could result in the equipment being turned ON during a power failure! IR Power Failure Operation The UPS can learn two IR commands. The learned commands will be transmitted on both output jacks so you have the ability to control 2 different pieces of equipment or use a 2-step macro for one component. The IR Output Delay switches provide the ability to ridethrough brief power outages without sending a shut-down signal to the connected device. You have a choice of a 30 second or 5 minute delay. 1. After a power failure and the selected delay, the IR codes will be sent to both outputs. The IR LED s will flash once per second during the delay time and will stop flashing after the IR code is sent. 2. If the delay settings are the same for both IR1 and IR2, the IR2 code will be sent to both outputs 2 seconds after IR1. 3. The IR commands will also be transmitted immediately after the battery charge falls below the critical load battery threshold. This ensures that equipment will be shutdown properly if the UPS s load level is extremely high and the backup time would be less than the 5 minute ride-through delay. 4. There is no IR output after the power is restored to the system. IR LED Color & Status LED COLOR Green, solid Green, flashing Red, flashing To program IR output: 1. Press and hold the IR1 button for approximately 2 seconds. 2. When the IR1 LED turns solid GREEN, release the button (after approx. 2 seconds) 3. Point the remote control at the detector window and quickly press and release the appropriate button on the remote control. If no signal is received within 10 seconds, the programming mode is cancelled, the IR1 LED turns off and you will have to start over. 4. The IR1 LED flashes GREEN if the IR signal is sampled and stored in memory. 5. The IR1 LED will flash RED if the IR signal was not learned. Start over at Step Repeat steps 1-5 for IR2. To clear IR programming: 1. Press and hold the appropriate IR button, release after 2 sec. 2. The IR LED turns solid Green STATUS Idle Waiting to receive IR signal IR signal sampled Failed to learn IR signal 3. Press the button again. The IR code will be erased from memory and the LED will turn off. IR Output Test 1. An IR flasher must be connected to the UPS and in line-ofsight to the IR receiver window of the equipment to be controlled in order to verify that the code was learned correctly. 2. Make sure that the component to be controlled is turned ON. 3. Press and release the IRx button. The code for IRx will be transmitted on both IR1 and IR2 outputs. 4. If you are testing a 2-step macro, be sure to press the second IR button to transmit that code. 4 USA & Canada (800) (707) Fax (707)

7 Advanced Operation (continued) 5. If the learning process was successful, the controlled equipment should accept the IR command and turn off or go into standby mode. 6. Reprogram the IR command if the controlled equipment does not respond. a. Be sure that the batteries in the teaching remote are fresh and do not need to be replaced. b. If press & release (Step 3 in Programming) doesn t work, try press & hold on the remote control button being taught to the UPS. RS232 Control with Open Protocol The RS232 serial interface can be used in the following ways: 1. Initial system setup. An installer can use a notebook computer to set the variables within the Home Cinema Power Control software. Once the setup is completed, the notebook computer can be disconnected. All settings are stored in the UPS. 2. Connection to a Home Theater Personal Computer (HTPC). Functionality is very similar to a standard UPS with a PC. The UPS can provide continued power to the HTPC to maintain recording capabilities if it is being used as a digital video recorder. It is also capable of saving open documents and shutting down the HTPC during extended power failures. This requires a permanent RS232 connection to the HTPC and having the Home Cinema Power Control software running in the background on the HTPC. 3. Integration with home automation systems like AMX and Crestron. The serial communications command set and protocol is open and is published later in this manual. This information can be used by the automation system programmer for both UPS control by the automation system and reporting of power events by the UPS to the automation system. Home Cinema Power Control Software The M1500-UPS-PFP has one rear-panel serial port that provides the ability to program special functions, safely shutdown a home theater PC (HTPC) or integrate the UPS with home automation systems. Use of the software is optional. The communications protocol is open ; a programmer can write their own control program or integrate the UPS s programming/control functions into home automation software if desired. The UPS will provide surge suppression, automatic voltage regulation and battery backup without the software. Automatic shutdown of an HTPC requires the use of the software. Software Installation For Windows XP (Home and Professional) 1. Click on Start and then click on Control Panel. 2. Double-click on Power Options then click on the UPS tab. 3. Set the manufacturer to none. 4. Exit to the desktop and shutdown your computer. 5. Turn the UPS off and unplug it. 6. Connect the serial interface cable to the UPS and an open serial port on the back of the computer. (Note: You must use the serial cable that was supplied with the unit). 7. Plug the UPS into an AC outlet, turn the UPS on and start your computer. 8. Windows will recognize your UPS as New Hardware. 9. Insert the software disk into the computer s drive. The installation program should start automatically. If the installation program does not start automatically, open it manually with the Window s Run command. 10. Follow the on-screen instructions. 11. Once the software has finished installing, remove the disk and restart your computer. For Windows 95/98/Me 1. Turn off your UPS. 2. Connect the Serial Cable to your UPS and the open serial port on the rear panel of the computer. (Note: You must use the serial cable that was supplied with the unit). 3. Plug the UPS into an AC outlet, turn the UPS on and then start your computer. 4. Follow the instructions below for your PC s operating system. USA & Canada (800) (707) Fax (707)

8 Home Cinema Power Control Software (continued) 5. Windows will recognize your UPS as New Hardware. 6. Insert the software disk into the computer s drive. The installation program should start automatically. If the installation program does not start automatically, open it manually with the Window s Run command. 7. Follow the on-screen instructions. 8. Once the software is installed, remove the disk and restart your computer. For Windows Click on Start, point to Settings then click Control Panel. 2. Double-click on Power Options. 3. On the UPS Tab, click Select. 4. In the UPS Selection Dialog Box, under Manufacturers, click None. 5. Exit to the desktop. 6. Shutdown the computer. 7. Turn the UPS off and unplug it. 8. Connect the serial interface cable to the UPS and an open serial port on the back of the computer. (Note: You must use the serial cable that was supplied with the unit). 9. Plug the UPS into an AC outlet, turn the UPS on and start your computer. 10. Windows will recognize your UPS as New Hardware. 11. Insert the software disk into the computer s drive. The installation program should start automatically. If the installation program does not start automatically, open it manually with the Window s Run command. 12. Follow the on-screen instructions. 13. Once the software has finished installing, remove the disk and restart your computer. For Windows NT Click on Start, point to Settings then click Control Panel. 2. Double-click on the UPS Icon. 3.. Remove the check mark from the box labeled UPS is installed on. 4. Click OK. 5. Acknowledge the message that the UPS is in an unknown state. 6. Exit to the desktop. 7. Shutdown your computer. 8. Turn the UPS off and unplug it. 9. Connect the serial interface cable to the UPS and an open serial port on the back of the computer. (Note: You must use the serial cable that was supplied with the unit). 10. Plug the UPS into an AC outlet, turn the UPS on and then start your computer. 11. Click on Start, point to Settings then click Control Panel. 12. Double-click on Add/Remove Programs. 13. Insert the software disk into the computer s drive. The installation program should start automatically. If the installation program does not start automatically, open it manually with the Window s Run command. 14. Click Install. 15. Follow the on-screen instructions. 16. Once the software is installed, remove the disk and restart your computer. When your computer restarts, the Home Cinema Power Control software will appear on your screen for a few seconds, and then minimize. It will appear as a blue and white battery icon located in the system tray, near the clock. 6 USA & Canada (800) (707) Fax (707)

9 Home Cinema Power Control Software Instructions Overview The Home Cinema Power Control software is designed for use with Windows 95, Windows 98, Windows Me, Windows NT, Windows 2000 and Windows XP. It works in conjunction with the UPS to provide full protection of home theater equipment including digital video recorders, home theater PC s (HTPC) and video projectors/lamps. This program may be used temporarily during the Initial system setup. An installer can use a notebook computer to set the variables within the Home Cinema Power Control software. Once the setup is completed, the notebook computer can be disconnected. All settings are stored in the UPS. The software can also be used to manage a Home Theater Personal Computer (HTPC). Functionality is very similar to a standard UPS with a PC. The UPS can provide continued power to the HTPC to maintain recording capabilities if it is being used as a digital video recorder. It is also capable of saving open documents and shutting down the HTPC during extended power failures. This requires a permanent RS232 connection to the HTPC and having the Home Cinema Power Control software running in the background on the HTPC. When a power failure occurs, open files are saved under auto-assigned file names or existing file names and the files closed. The computer and UPS are automatically shutdown to conserve battery power. Files with auto-assigned names will be saved under C:\PCTemp, where C is the name of your main hard drive. Files that have previously been saved will be saved in their original location. There is also a Schedule feature that can automatically save and close open files and then shutdown the computer and UPS at a user specified date and time as well as re-start the computer at a user specified date and time. Use of this feature is optional and is not required for the power failure shutdown to occur. MAIN MENU 1. Log Button: Opens the Event Log Window. 2. Power Button: Closes the program window. 3. Minimize Button: Minimize the program window. 4. Setup Button: Opens the Setup Window. 5. Model: Shows the model of UPS that is being used. 6. Schedule Button: Click this button to access the Schedule Window. 7. Status Bar: Displays messages about the status of the software. USA & Canada (800) (707) Fax (707)

10 Home Cinema Power Control Software Instructions (continued) MAIN WINDOW DESCRIPTIONS 1. Battery Level: Displays the current charge on the battery. The indicator will display a red color when a power failure occurs. 2. Input Voltage: Shows the current input voltage. The input normally appears in green, but will turn red if the input voltage is lower than 85v or higher than 150v. 3. Output Voltage: Shows the output voltage of the UPS. 4. Load Level: Shows the % of capacity that is currently being used. If the load level exceeds 90%, the indicator will change to a red color. 10. Frequency: This indicator displays the frequency of the utility power. 9. Scheduled On: The Home Cinema Power Control software can be scheduled to turn your connected equipment on. It can only be set when a Scheduled is also set. Scheduled On settings that are set to occur within seven days will be displayed. 8. Countdown: For use with a Home Theater PC. When the program detects that the utility voltage is below 88 volts or above 147 volts, the countdown will begin. When the countdown reaches zero, the program will save and close any open applications, and then shut down the operating system in an intelligent and orderly manner. 7. Approximate Backup Time: Indicates the approximate amount of backup time that is available, based upon the battery capacity and the load on the system. This indicator can appear in red, yellow, or green, depending upon the number of minutes available. 5. Temperature: Displays the internal operating temperature of the unit. If the temperature exceeds 158 F (70 C), the indicator will change from green to red. 6. Scheduled : The program can be set to automatically shutdown the system at a user specified time. Scheduled settings that are set to occur within seven days will be displayed. When combined with the Scheduled On function, connected equipment can automatically be rebooted. SETUP MENU 12. Time between power failure and shutdown: For use with an HTPC. This is the user controllable delay between when the power fails and the software starts the shutdown process. If unchecked and plugged into one of the critical load outlets the HTPC will run on battery until the low battery signal is received (2 minutes of backup time remaining) and then start the shutdown process. 11. Time between power failure and initial warning: Sets the time delay between a power failure and the first audible alarm. 1. Play voice: Enables audible voice messages through your computer speakers. A sound card and speakers are required. 2. Alarm On: Toggles the audible alarm on and off. 3. UPS Communication Media: Leave this on Auto for automatic detection or select the correct communications port from the dropdown list. The port assigned to the UPS needs to be used exclusively for the UPS software. 4. OK: Closes the window and saves changes. 5. Cancel: Closes the window without saving changes. 6. Default: Returns the software to original factory settings. 7. Advanced: Opens the Advanced Setup Window. 10. Delay between warning messages: Sets the delay between the audible alarms (during a power failure). 9. UPS Self-Test: Allows the user to test the UPS without having to unplug the unit from the wall. When Run is clicked, the UPS will switch to battery power and the unit will beep. 8. About: This button will display information about the software, as well as contact information. 8 USA & Canada (800) (707) Fax (707)

11 Home Cinema Power Control Software Instructions (continued) ADVANCED SETUP MENU 1. Low Battery HTPC Shutoff: For use with a Home Theater PC. Sets the low battery cutoff level. The user can slightly extend the UPS run time by adjusting this setting. This setting must be higher than the Critical Load Threshold if the HTPC is plugged into a non-critical load outlet. 9. High-Voltage Failure: Sets the upper level where the UPS will cycle to battery. This level can be adjusted from 137V to 147V. 8. Low-Voltage Failure: Sets the lower level where the UPS will cycle to battery. This level can be adjusted from 88V to 97V. 2. Low Battery NCL Shutoff: NCL stands for Non- Critical Load. Sets the % of battery capacity at which all remaining battery power is reserved for the equipment plugged into the critical load outlet bank. Power to the 4 NCL outlets will be turned off at this point. 3. Cold Start: When this is enabled, the UPS can start in the absence of AC power. To maximize battery life, it is recommended to keep this disabled. 4. OK: Closes the windows and saves changes. 5. Cancel: Closes the window without saving changes. 6. Default: Restores the settings to the factory defaults. 7. Battery-mode Output Voltage: Sets the voltage that the unit will output. This level can be adjusted from 110V to 130V when running on battery. SCHEDULE MENU - SPECIAL 1. Special Setting: Allows you to schedule a one-time shutdown/startup. 9. Turn On: Select the day/date and time that you want the computer system to restart. Can only be used in conjunction with a scheduled shutdown. 2. Weekly Setting: Allows you to schedule a shutdown and start up based upon the day of the week. 3. Turn : Select the day/date and time that you want the computer system to shutdown. This is optional and has no effect on whether your computer will shut down during a power failure. 4. OK: Closes the window. Please note: You must click Add to add the item to the schedule. 5. Cancel: Closes the window without saving any schedules even if one was added to the Schedule Display Window. Does not cancel previously applied schedules. 8. Schedule Display: Window display of the days/dates and times of any scheduled startups and shutdowns. 6. Add: Adds an item to the schedule. 7. Delete: Clears the selected item from the schedule. USA & Canada (800) (707) Fax (707)

12 Home Cinema Power Control Software Instructions (continued) LOG MENU 1. Log Display: This window displays the information as selected by the Event, Closed Application Information, or Data Record option buttons. 2. Event: When this option is selected, the log will display a list of events such as power failure, program start, and program end. 3. Closed Application Information: When this option is selected, the log will display the names and location of any files that were auto-saved by the software. 4. Data Record: When this option is selected, the log will display a record of the items that are shown in the main window. 5. OK: Closes the window and saves any changes. 6. Cancel: Closes the window without saving any changes. 7. Clear: Clears the selected log. Battery Features Testing The Battery Backup Function Once you have set up your UPS system, you may wish to test it. Make sure that the UPS has been charged for at least 4 hours before testing. To test the UPS, simply depress the test button located on the front of the unit. The unit will cycle to battery and emit an audible beep. The unit will stop beeping when the test is complete. You may also use the self-test function in the software. To use the software self-test, open the main window, and then click mode on Setup. Click the red run button. The unit will cycle to battery mode and emit an audible beep. With the software self-test, the unit will switch back to AC power automatically. Battery Replacement Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. M1500-UPS-PFP Battery Replacement Policy Batteries are included under the M1500-UPS-PFP 3 year warranty. PF Power will replace M1500-UPS-PFP batteries if the fail within the 3 year product warranty period. For battery replacement information and instructions please contact Panamax Customer Service at or call If batteries fail after the M1500-UPS-PFP 3 year product warranty then the customer is responsible for battery replacement. For detailed battery replacement information and instructions please contact Panamax Customer Service at or call Service the battery under the supervision of personnel knowledgable of batteries and their precautions. Sevicing the battery should only be performed by qualified personnel. CAUTION! USE ONLY THE SPECIFIED TYPE OF BATTERY. Contact Panamax Customer Service at or call for battery replacement information. CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire as they may explode. Follow all local ordinances regarding proper disposal of batteries. CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes and may be toxic CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before replacing the battery: 1. Remove all watches, rings or other metal objects. 2. Only use tools with insulated handles. 3. Do not lay tools or metal parts on top of battery or any terminals. 4. Wear rubber gloves and boots. 5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit). 10 USA & Canada (800) (707) Fax (707)

13 Battery Features (continued) Battery Replacement Procedure 1. Remove the right side front panel using pull-out handles. 2. Remove the two retaining screws of the cable protection cover then remove the cover. 3. Disconnect the black and red cable. 6. Slide a new battery pack into the unit. Assemble the screws, cover, cable and front panel in the reverse sequence of above steps. 4. Remove the four retaining screws. Diagnostics Battery pullout tab handle 5. Pull the battery pack out from the unit. 7. Recharge the unit for 4-8 hours to ensure the UPS performs expected runtime. Power On LED Wiring Fault LED AVR LED Using Battery LED Circuit Breaker Audible Alarm Condition On Set Normal On Slow Flash Set AVR- Max. boost 13% of input voltage for output regulation while input voltage is from 8% to 15% under nominal. On Rapid Flash Set AVR- Max. boost 26% of input voltage for output regulation while input voltage is from 15% to 26% under nominal. On On Set AVR- Max. buck 15% of input voltage for output regulation while input voltage is from 8% to 26% over nominal. On Set Two Beeps Utility Failure- The UPS is providing battery power to the connected equipment. On Set Rapid Beeps Utility Failure- The UPS is providing battery power. Rapid beeps indicate the battery will run out of charge within a few minutes. On/ On//Flash On/ Set Long Beep Overload- Turn the UPS off and unplug at least one piece of equipment from the UPS. Wait 5 seconds, reset the circuit breaker and restart the UPS. On Up Long Beep Overload- Turn the UPS off and unplug at least one piece of equipment from the UPS. Wait 5 seconds, reset the circuit breaker and restart the UPS. On On//Flash Set None Weak Battery- Recharge the battery for at least 8 hours. If Check Battery is illuminated, contact Panamax for battery replacement information. Set Surge Protection Malfunction- Power surge has damaged the unit. Please contact Panamax. On/ On On//Flash On/ Set/Up None Electrical Wiring Fault- Indicates wiring problems such as a bad ground, missed ground or reversed wiring within the AC outlet. User is advised to disconnect all electrical equipment from the outlet and have the outlet checked by an electrician. USA & Canada (800) (707) Fax (707)

14 Troubleshooting Problem Outlets do not provide power to equipment. The UPS does not perform expected runtime. The UPS will not turn on. Software is inactive. Possible Cause Circuit breaker is tripped due to overload Batteries are discharged. Unit has been damaged by a surge or spike. Battery is not fully charged. Battery is slightly worn out. The on/off switch is designed to prevent damage by rapidly turning it off and on. The unit is not connected to an AC outlet. The battery is worn out. Mechanical problem. The serial cable is not connected. The serial cable is connected to the wrong port. The unit is not providing battery power The serial cable is not the cable that was provided with the unit. Solution Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit breaker and then turn the UPS on. Recharge the unit for at least 4 hours. Recharge the battery by leaving the UPS plugged in. Recharge the battery by leaving the UPS plugged in. Contact Panamax about replacement batteries. Turn the UPS off. Wait 10 seconds and then turn the UPS on. The unit must be connected to a 110/120v 60Hz outlet. Contact Panamax about replacement batteries. Contact Panamax. Connect the serial cable to the UPS unit and an open serial port of your computer. You must use the cable included with the unit. Try another serial port on your computer. Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the UPS on. This should reset the unit. You must use the cable included with the unit for the software. Technical Specifications AC SPECIFICATIONS CAPACITY ( VA ) VA ( Wa t t s ) W INPUT Voltage Range 88Vac - 147Vac Frequency Range Hz OUTPUT On Battery Output Voltage Pure Sine Wave at 120VAC +/- 5% On Battery Output Frequency 60 Hz +/- 1% Transfer Time 4ms PROTECTION & FILTRATION On Utility Over/Under voltage protection On Battery Internal Current Limiting Patented Power Management Circuit Yes Overvoltage Shutoff 144V ±8V Undervoltage Shutoff 90V ±6V Thermal Fusing Ye s Initial Clamping Level 200V Peak, 141V RMS UL 1449 Suppression Rating 330V Protection Modes L-N, L-G, N-G Response Time < 1 n Single Pulse Energy Dissipation 1650 Joules Peak Impulse Current 52,000 A EMI/RFI Noise Filtration 50dB (100kHz 1 MHz) TELCO PROTECTION F u s e l e s s / A u t o - R e s e t t a b l e _ Ye s Clamping Level 260V Capacitance 30 pf (approx.) Suppression Modes Metallic & Longitudinal Wires Protected 2 wire, 1 pair (4 & 5) Connectors RJ-11/45 Shared with LAN LAN PROTECTION Compatibility 10/100bT Clamping Level 7V Suppression Modes Differential & Common Ground Wires Protected Pins 1, 2, 3, & 6 Connectors RJ/11-45 Shared with Telco BATTERY S e a l e d Yes M a i n t e n a n c e - f r e e Ye s Lead acid Yes User replaceable Yes Typical recharge time 8 hrs. COMMUNICATION Software Included (Windows95/98/ME/NT/2000/XP) Hardware RS232 (open command set) Programmable IR (learning) sends IR signals to equipment after power failure PHYSICAL Rack Mountable Yes (rack mount kit included) Maximum Dimensions 17" x 3.5 x 15.3" Weight (lbs.) 59 Outlets 6 Total (2 assigned critical load) GENERAL Lightning protection Yes Product Warranty 3 Years Design and specifications subject to change without notice due to product improvement. 12 USA & Canada (800) (707) Fax (707)

15 RS232 Communications Protocol & Command Set Communications Protocol Baud rate: 2400 bps Start bit: 1 bit Data length: 8 bits Stop bit: 1 bit P a r i t y : N o n e Flow control: one Controller Commands Commands and responses are in the form of ASCII character strings terminated with a carriage return <CR> ASCII character 13 (hex). It is important to understand how the UPS circuitry switches power to the outlets in order to use the outlet switching commands effectively. The following diagram provides a basic illustration: Figure 2.1 UPS Power Switching The UPS provides one bank of switched outlets (Outlet Bank 1) that can be controlled independently. These are referred to as Non-Critical Load (NCL) Outlets. The other outlet bank (Outlet Bank 2) will be referred to as Critical Load (CL) Outlets. Note that NCL outlets cannot be energized unless the critical load outlets are on. NCL outlets are designated for equipment that is considered non-critical. Power will be turned off if the battery charge falls below a set threshold (refer 2.5). It is desirable to have the ability to switch the power to the outlets on and off to force a hard reboot of equipment. Devices such as satellite receivers often crash and must be reset. The following are commands made by the controller to the UPS: Main Power On Main Power MAIN_ON<CR> MAIN_OFF<CR> If power is not switched off due to low battery conditions: Action: AC power is switched ON to the CL out lets by closing the AC input relay or turn ing on the inverter. CL_OUTLETS_ON<CR> NCL_OUTLETS_ON<CR> (if NCL relay is closed) If power is already switched off due to low battery conditions: Action: None Action: All outlets are de-energized by disconnecting the AC input relay and turning off the Inverter. NCL_OUTLETS_OFF<CR> CL_OUTLETS_OFF<CR> LOWBATT<CR> USA & Canada (800) (707) Fax (707)

16 RS232 Communications Protocol & Command Set (continued) Non Critical Load Outlets On This command controls the relay that feeds power to the NCL Outlets. Note that if the MAIN relay is off, the outlets will still be un-energized. Action: NCL_ON<CR> NCL relay closes. NCL_OUTLETS_ON<CR> (if MAIN relay is ON) NCL_OUTLETS_OFF<CR> (if MAIN relay is OFF) Enable Audible Alarm It is important that the UPS be as quiet as possible as it will be located in a home theater environment. It is desirable to control the warning beeper. The default setting for the alarm is OFF. Action: Disable Warning Beeper BEEPON<CR> The beeper will sound when running from battery. BEEPISON<CR> Non Critical Outlets Action: NCL_OFF<CR> NCL relay opens. Action: BEEPOFF<CR> The beeper will not sound when running from battery. NCL_OUTLETS_OFF<CR> BEEPISOFF<CR> Set Low Battery NCL (Non-Critical Load) Shutoff It is desirable to allow the user to set the battery storage threshold in which the non-critical load outlets will shut off therefore reserving the remaining battery charge for the critical equipment. If the battery charge falls below the threshold, Non Critical Load Outlets are turned OFF. A common example of critical equipment would be a projector. It is critical that power be maintained to a projector to allow its fan to run and cool the bulb. If the bulb is allowed to overheat, it will be damaged and is very expensive to replace. BATTHRESH<SP>XX<CR> <SP> represents a space: 20 Hex Restore Default Settings RESTORE<CR> Action: Set Non-critical load threshold (2.5) to 66% Disable the warning beeper (2.7) Set High Voltage Failure Threshold to 147V (2.8) Set Low Voltage Failure Threshold to 88V (2.9) XX is a number between 25 and 60 represented in ASCII. Set Battery Mode Voltage to 120V (2.10) DEFAULTSRESTORED<CR> If XX is a valid number, between 25 and 60: Action: Assigns the battery threshold variable with the value XX QUERIES Request Outlet Status Transmit the ON/OFF status of the outlet banks. BTHRESH<SP>XX<CR>?OUTLETSTAT<CR> If XX is not valid: Action: None INVALIDCMD<CR> If NCL Outlets are ON: If NCL Outlets are OFF: NCL_OUTLETS_ON<CR> NCL_OUTLETS_OFF<CR> If CL Outlets are ON: CL_OUTLETS_ON<CR> If CL Outlets are OFF: CL_OUTLETS_OFF<CR> 14 USA & Canada (800) (707) Fax (707)

17 RS232 Communications Protocol & Command Set (continued) Request Input Voltage Level Transmit the input AC voltage status Identify Equipment Transmit the model number, firmware number and revision.?inputvolts<cr>?id<cr> XXX<SP>VAC<SP>IN<CR> PANAMAX<CR> Request Output Voltage Status Transmit the output voltage state XXX is the input AC voltage represented in ASCII. M1500-UPS<CR> FW<SP>PARTNUMBER<CR> REV<SP>REVISION<CR>?OUTPUTSTAT XXX<SP>VAC<SP>OUT<CR> XXX is the output voltage represented in ASCII. List all Commands and Queries HELP<CR> MAIN_ON<CR> If the UPS is not in AVR or BATTERY mode: NORMAL<CR> If the UPS is in AVR mode and boosting voltage by 13% AVRBOOST1<CR> If the UPS is in AVR mode and boosting voltage by 26% AVRBOOST2<CR> If the UPS is in AVR mode and bucking voltage by 11% AVRBUCK1<CR> If the UPS is in BATTERY mode BATTERY<CR> Request Load Level Status Transmit the load level percentage.?loadstat<cr> XX<SP>%LOAD<CR> XX is the load percentage represented in ASCII. Request Battery Charge Level Status Transmit the remaining battery charge percentage. MAIN_OFF<CR> NCL_ON<CR> NCL_OFF<CR> BATTHRESH<CR> BEEPON<CR> BEEPOFF<CR> RESTORE<CR>?OUTLETSTAT<CR>?INPUTVOLTS<CR>?OUTPUTSTAT?LOADSTAT<CR>?BATTERYSTAT<CR>?ID<CR> HELP<CR>?BATTERYSTAT<CR> XX<SP>%BATTERY<CR> XX is the battery charge percentage represented in ASCII. USA & Canada (800) (707) Fax (707)

18 RS232 Communications Protocol & Command Set (continued) Responses and Warning Messages A warning message is to be transmitted whenever the status of the following systems changes: Power Status Messages Whenever the power changes state the UPS sends a message to the controller: Outlet Bank Status Messages Whenever an outlet bank switches state (ON or OFF) the UPS sends a message to the controller: Condition CL Outlet Bank switches ON CL Outlet Bank switches OFF NCL Outlet Bank switches ON NCL Outlet Bank switches OFF Response from UPS CL_OUTLETS_ON<CR> CL_OUTLETS_OFF<CR> NCL_OUTLETS_ON<CR> NCL_OUTLETS _OFF<CR> Condition UPS is not in AVR or BATTERY mode UPS is in AVR boosting 13% UPS is in AVR boosting 26% UPS is in AVR bucking 15% UPS is in BATTERY mode Battery charge falls below critical load threshold Input voltage exceeds high voltage failure t hold Input voltage falls below low voltage failure t hold Battery charge falls below critical load threshold Response from UPS NORMAL<CR> AVRBOOST1<CR> AVRBOOST2<CR> AVRBUCK1<CR> BATTERY<CR> LOWBATT<CR> OVERVOLTAGE<CR> UNDERVOLTAGE<CR> LOWBATT<CR> Invalid Command or Query If the UPS receives a command or query ASCII string that it does not understand, an error message is transmitted. Condition: Command or query not recognized or properly formatted INVALIDCMD<CR> 16 USA & Canada (800) (707) Fax (707)

19 FCC Notice and Warranties FCC Notice This equipment has been tested and found to comply with the limits for a Class B Digital Device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: (1) Reorient or relocate the receiving antenna. (2) Increase the separation between the equipment and receiver. (3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. (4) Consult the dealer or an experienced radio/tv technician for help. Any special accessories needed for compliance must be specified in the instruction. CAUTION: A shielded-type power cord is required in order to meet FCC emission limits and also to prevent interference to the nearby radio and television reception. It is essential that only the supplied power cord be used. Use only shielded cables to connect I/O devices to this equipment. CAUTION: Any changes or modifications not expressly approved by the guarantee of this device could void the user's authority to operate the equipment. PF Power 1500-UPS-PFP LIMITED PRODUCT WARRANTY Panamax warrants to the purchaser of this Panamax audio/video component style uninterruptible power supply, for a period of three (3) years from the date of purchase, that the unit shall be free of defects in design, material, or workmanship, and Panamax will repair or replace any defective unit. Upgrade Policy Valid only in the United states and Canada If your Panamax UPS sacrifices itself while protecting your connected equipment, you have an option to upgrade to the latest technology. Please go to our web site or contact Panamax Customer Relations at for details. Warning Notice WARRANTY LIMITATION FOR INTERNET PUR- CHASERS Panamax products purchased through the Internet do not carry a valid Connected Equipment Protection Policy unless purchased from an Authorized Panamax Internet Dealer! Authorized Panamax Internet Dealers have sufficient expertise to insure warranty compliant installations. For a list of Authorized Panamax Internet Dealers go to CAUTION Audio/Video, computer and/or telephone system installations can be very complex systems, which consist of many interconnected components. Due to the nature of electricity and surges, a single protector may not be able to completely protect complex installations. In those cases, a systematic approach using multiple protectors must be employed. Systematic protection requires professional design. AC power, satellite cables, CATV cables, A/V signal line cables or telephone/network lines entering the system that do not pass through a Panamax surge protector will render the Panamax connected equipment protection policy null and void. For additional information on how to protect your system, please contact Panamax before connecting your equipment to the surge protector. More detailed information is available at If you have any questions regarding these requirements, please contact Panamax Customer Relations. Effective Date 8/07 Q01L0047 REV. A 1690 Corporate Circle, Petaluma, CA Tel: (707) Fax: (707)

20 1690 Corporate Circle, Petaluma, CA Tel: (707) Fax: (707)

Model: VA/230W UPS Backup System

Model: VA/230W UPS Backup System IMPORTANT SAFETY INSTRUCTIONS (SAVE THESE INSTRUCTIONS) This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of unit.

More information

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during installation

More information

User s Manual Legend SB425 K

User s Manual Legend SB425 K User s Manual Legend SB425 K01-1120007-00 TABLE OF CONTENTS IMPORTANT SAFETY WARNINGS.. 1 INSTALLING YOUR UPS SYSTEM.. 2 - UNPACKING..2 - HARDWARE INSTALLATION GUIDE. 2 BASIC OPERATION...2 - FRONT PANEL

More information

User s Manual Legend SB500R UPS K

User s Manual Legend SB500R UPS K User s Manual Legend SB500R UPS K01-1120008-00 Legend SB500R Uninterruptible Power System TABLE OF CONTENTS IMPORTANT SAFETY WARNINGS. 2 INSTALLING YOUR UPS SYSTEM.. 3 - UNPACKING.3 - HARDWARE INSTALLATION

More information

U P S USER S MANUAL IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Uninterruptible Power System. Line Interactive (Network) UPS

U P S USER S MANUAL IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. Uninterruptible Power System. Line Interactive (Network) UPS Important Safety Instructions IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS U P S Uninterruptible Power System Line Interactive (Network) UPS 400VA/ 500VA/ 600VA/ 800VA USER S MANUAL WARNING (SAVE

More information

OFFICE UPS MULTI-DEVICE PROTECTION UPS 500S/600S/750S

OFFICE UPS MULTI-DEVICE PROTECTION UPS 500S/600S/750S OFFICE UPS MULTI-DEVICE PROTECTION UPS 500S/600S/750S USER S MANUAL 1.Safety instructions Thank you for selecting this uninterrupted power source. It provides you with better protection for connected equipment.

More information

Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System

Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System USER MANUAL Line Interactive 1000VA/1400VA/2000VA Uninterruptible Power System 614-06762-00 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for Line Interactive

More information

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA. GE Critical Power

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA. GE Critical Power Critical Power USER MANUAL Uninterruptible Power Supply Line-interactive VCL Series UPS 400 600 800 1000 1500 VA GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland

More information

INSTALLATION TIPS CAN BE FOUND AT:

INSTALLATION TIPS CAN BE FOUND AT: User Manual for and PowerPanel Plus Software User Manual ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT: www.cyberpowersystems.com/faqs.htm TABLE OF CONTENTS Description...1 Determining Power Requirements...1

More information

User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA

User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA User Manual Back-UPS Pro BN 1100/1350/1375/1400/1500 M2 BN 1100/1350/1500 M2-CA Safety and General Information Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.

More information

INSTALLATION TIPS CAN BE FOUND AT:

INSTALLATION TIPS CAN BE FOUND AT: User Manual for CPS1250AVR and PowerPanel Plus Software User Manual ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT: http://www.cyberpowersystems.com/faqs.htm TABLE OF CONTENTS Description.1 Determining Power

More information

CPS1000AVR Guaranteed Uninterruptible Power System

CPS1000AVR Guaranteed Uninterruptible Power System CPS1000AVR HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 1. Make sure that the total Volt-Amp (VA) requirements of your computer, monitor and peripheral equipment does not exceed 1440VA. 2.

More information

User Manual Back-UPS BE650MC

User Manual Back-UPS BE650MC User Manual Back-UPS BE650MC Inventory Back-UPS ES 650 bu075b This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with fluids, or where there is excessive

More information

Back-UPS RS APC Back-UPS RS 800VA 120V Black

Back-UPS RS APC Back-UPS RS 800VA 120V Black Back-UPS RS APC Back-UPS RS 800VA 120V Black APC Back-UPS RS, 540 Watts / 800 VA,Input 120V / Output 120V Includes: CD with software, Cord management straps, Free trial of anti-virus : firewall : email

More information

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to install, operate, service

More information

Installation and Operation Manual Back-UPS BR900G-RS

Installation and Operation Manual Back-UPS BR900G-RS Installation and Operation Manual Back-UPS BR900G-RS Inventory Safety bu001a This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with fluids, or where there

More information

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Liebert PSA iton User Manual Version: V2.8 Revision date: November 14, 2005 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or

More information

ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT:

ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT: User Manual for CPS625AVR with USB Interface and PowerPanel Software ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT: www.cyberpowersystems.com TABLE OF CONTENTS Description..1 Hardware Installation Guide

More information

ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT:

ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT: User Manual for CPS1100AVR with USB / Serial Interface and PowerPanel Plus Software ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT: www.cyberpowersystems.com/faqs.htm TABLE OF CONTENTS Determining Power

More information

OFFICE UPS MULTI-DEVICE PROTECTION UPS 500S/600S/750S USER S MANUAL

OFFICE UPS MULTI-DEVICE PROTECTION UPS 500S/600S/750S USER S MANUAL OFFICE UPS MULTI-DEVICE PROTECTION UPS 500S/600S/750S USER S MANUAL 1.Safety instructions Thank you for selecting this uninterrupted power source. It provides you with better protection for connected equipment.

More information

Powerware 3105 UPS User s manual

Powerware 3105 UPS User s manual Powerware 3105 UPS 2005 Eaton Corporation All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care

More information

Powerware 3105 UPS User s manual

Powerware 3105 UPS User s manual Powerware 3105 UPS 2005 Eaton Corporation All Rights Reserved The contents of this manual are the copyright of the publisher and may not be reproduced (even extracts) unless permission granted. Every care

More information

User Manual for: CPS320SL / CPS375SL / CPS500SL / CPS575SL / CPS650SL and PowerPanel Software

User Manual for: CPS320SL / CPS375SL / CPS500SL / CPS575SL / CPS650SL and PowerPanel Software User Manual for: CPS320SL / CPS375SL / CPS500SL / CPS575SL / CPS650SL and PowerPanel Software ADDITIONAL INSTALLATION TIPS CAN BE FOUND AT: http://www.cyberpowersystems.com/faq_sl.htm TABLE OF CONTENTS

More information

POWERWALKER. Uninterruptible Power Supply. Line Interactive VI 1000/1400/2000. Thank you for purchasing PowerWalker UPS.

POWERWALKER. Uninterruptible Power Supply. Line Interactive VI 1000/1400/2000. Thank you for purchasing PowerWalker UPS. POWERWALKER Uninterruptible Power Supply Line Interactive VI 1000/1400/2000 Thank you for purchasing PowerWalker UPS. User s Manual Safety information and operating instructions are included in this manual.

More information

PowerMust Office Uninterruptible Power System

PowerMust Office Uninterruptible Power System USER MANUAL E PowerMust Office Uninterruptible Power System 614-05737-05 28-2PRO000001 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for Models PowerMust

More information

SmartPro LCD 120V 1500VA 900W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets

SmartPro LCD 120V 1500VA 900W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets SmartPro LCD 120V 1500VA 900W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets MODEL NUMBER: SMART1500LCD Highlights Supports a half-load (450W) up to 11.8 min. during power outage

More information

Owner s Manual. Models: ECO650LCD, ECO850LCD. Not suitable for mobile applications

Owner s Manual. Models: ECO650LCD, ECO850LCD. Not suitable for mobile applications Warranty Registration Register online today for a chance to win a FREE Tripp Lite product! www.tripplite.com/warranty Owner s Manual ECO-UPS Systems with LCD Models: ECO650LCD, ECO850LCD Not suitable for

More information

1. IMPORTANT SAFETY INSTRUCTIONS WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during install

1. IMPORTANT SAFETY INSTRUCTIONS WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during install DIN RAIL UPS Off Line 500 VA / 850 VA User Manual 1 1. IMPORTANT SAFETY INSTRUCTIONS WARNING (SAVE THESE INSTRUCTIONS): This manual contains important instructions that should be followed during installation

More information

Installation and Operation Back-UPS Pro BR700G-TW

Installation and Operation Back-UPS Pro BR700G-TW Installation and Operation Back-UPS Pro BR700G-TW Inventory Safety Do not install the UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Do not connect a laser printer or hair

More information

Xtreme Value Rack Tower Series (XVRT) User s & Installation Manual

Xtreme Value Rack Tower Series (XVRT) User s & Installation Manual Xtreme Value Rack Tower Series (XVRT) User s & Installation Manual Xtreme Power Conversion Corporation TABLE OF CONTENTS INTRODUCTION...2 SAFETY INSTRUCTIONS...3 PRODUCT DESCRIPTION...5 DETERMINING THE

More information

Back-UPS RS 550 Installation & Operation

Back-UPS RS 550 Installation & Operation Back-UPS RS 550 Installation & Operation Inventory Safety Do not install the UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. bu001a Do not connect a laser printer or hair

More information

User s Manual. Professional Rack Mount LCD XL Series PR1000ELCDRTXL2U/PR1500ELCDRTXL2U/ PR2200ELCDRTXL2U K

User s Manual. Professional Rack Mount LCD XL Series PR1000ELCDRTXL2U/PR1500ELCDRTXL2U/ PR2200ELCDRTXL2U K EN User s Manual Professional Rack Mount LCD XL Series PR1000ELCDRTXL2U/PR1500ELCDRTXL2U/ PR2200ELCDRTXL2U K01-0000125-01 IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS This manual contains

More information

LevelOne BLH-1000 Bluetooth Headset User s Manual

LevelOne BLH-1000 Bluetooth Headset User s Manual LevelOne BLH-1000 Bluetooth Headset User s Manual - 1 - Introduction Introduction to Bluetooth Wireless Technology Bluetooth is a short- range wireless communication technology. It allows wireless connections

More information

User Manual. C Type Power Filter. Model C3 and C3BLK

User Manual. C Type Power Filter. Model C3 and C3BLK User Manual C Type Power Filter Model C3 and C3BLK Entire contents copyright 2010 American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited.

More information

powerware 5105 User s Guide VA

powerware 5105 User s Guide VA powerware 5105 User s Guide 450-1500 VA www.powerware.com Requesting a Declaration of Conformity The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the

More information

Owner s Instruction Manual

Owner s Instruction Manual Owner s Instruction Manual Advanced Healthcare Telephone Model 5150 Contents IMPORTANT SAFETY INSTRUCTIONS...3 BOX CONTENTS...4 FEATURES...4 ON/OFF SWITCH...4 DIAL BUTTONS...4 RECEIVER VOLUME CONTROL...4

More information

Innovative Circuit Technology Ltd.

Innovative Circuit Technology Ltd. Innovative Circuit Technology Ltd. Pro Series DC Power Supply INSTRUCTION MANUAL 855-343-001 Models: ICT690-12S/ICT690-12SB ICT690-24S/ICT690-24SB ICT690-48S/ICT690-48SB ICT1190-12S/ICT1190-12SB ICT1190-24S/ICT1190-24SB

More information

XBDM. 1015LV, 1020LV, 1030LV, 1020HV Models USER & INSTALLATION MANUAL BYPASS DISTRIBUTION MODULE

XBDM. 1015LV, 1020LV, 1030LV, 1020HV Models USER & INSTALLATION MANUAL BYPASS DISTRIBUTION MODULE XBDM 1015LV, 1020LV, 1030LV, 1020HV Models USER & INSTALLATION MANUAL www.xpcc.com 2013 Xtreme Power Conversion Corporation. All rights reserved. Table of Contents IMPORTANT SAFETY INSTRUCTIONS:... 4 INTRODUCTION...

More information

SmartPro LCD 120V 1300VA 720W Line- Interactive UPS, AVR, Tower, LCD, USB, 8 Outlets

SmartPro LCD 120V 1300VA 720W Line- Interactive UPS, AVR, Tower, LCD, USB, 8 Outlets SmartPro LCD 120V 1300VA 720W Line- Interactive UPS, AVR, Tower, LCD, USB, 8 Outlets MODEL NUMBER: SMART1300LCDT Highlights Supports a basic desktop PC up to 64 min. during power outage Features 8 protected

More information

PWRguard PLUS Spring City Drive Waukesha, WI

PWRguard PLUS Spring City Drive Waukesha, WI PWRguard PLUS www.westmountainradio.com 1020 Spring City Drive Waukesha, WI 53186 262-522-6503 sales@westmountainradio.com 2016, All rights reserved. All trademarks are the property of their respective

More information

SmartPro LCD 120V 1500VA 900W Line-Interactive UPS, AVR, Tower, LCD, USB, 10 Outlets

SmartPro LCD 120V 1500VA 900W Line-Interactive UPS, AVR, Tower, LCD, USB, 10 Outlets SmartPro LCD 120V 1500VA 900W Line-Interactive UPS, AVR, Tower, LCD, USB, 10 Outlets MODEL NUMBER: SMART1500LCDT Highlights Supports a basic desktop PC up to 90 min. during power outage Features 10 protected

More information

Modified Sinewave Series. Power Inverter 1000/1500 MW 1210, MW1215. True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220.

Modified Sinewave Series. Power Inverter 1000/1500 MW 1210, MW1215. True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220. Modified Sinewave Power Inverter 1000/1500 MW 1210, MW1215 True Sinewave Power Inverter 1000/2000 SW 1210, SW 1220 Owner s Manual Modified Sinewave Series True Sinewave Series 1. INTRODUCTION Thank you

More information

SuperBus 2000 Phone Interface/Voice Module Installation Instructions

SuperBus 2000 Phone Interface/Voice Module Installation Instructions SuperBus 2000 Module Installation Instructions Product summary The SuperBus 2000 (PIV) Module provides phone and voice functions for the Concord, Concord 4, and Concord Express (v4) panels. The PIV module

More information

Nature Power Inverters. Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w. Owner s Manual

Nature Power Inverters. Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w. Owner s Manual Nature Power Inverters Modified Sinewave 1000w/1500w True Sinewave 1000w/2000w Owner s Manual Modified Sinewave Series True Sinewave Series For safe and optimum performance, the Power Inverter must be

More information

DRP16 Series. User Guide. DVR Surge Protector & UPS. DITEK Corporation One DITEK Center 1720 Starkey Road Largo, FL

DRP16 Series. User Guide. DVR Surge Protector & UPS. DITEK Corporation One DITEK Center 1720 Starkey Road Largo, FL DRP16 Series DVR Surge Protector & UPS User Guide INT-100084-001 Rev 7 06/10/08 191004 DITEK Corporation One DITEK Center 1720 Starkey Road Largo, FL 33771 1-800-753-2345 www.ditekcorp.com DITEK CORPORATION

More information

USB Port Hub HO

USB Port Hub HO USB 2.0 7-Port Hub INSTRUCTION MANUAL HO97916 www.jascoproducts.com Table of Contents I. INTRODUCTION 3 II. OVERVIEW 4 III. SAFETY INSTRUCTIONS 5 IV. POWER MODE SETTING 6 V. HUB STAND ASSEMBLY 7 VI. HARDWARE

More information

AX3000 Platine Terminal Ethernet TCP/IP

AX3000 Platine Terminal Ethernet TCP/IP AX3000 Platine Terminal Ethernet TCP/IP Model 80 Installation Guide January 2012 - Ref: I80E0922-2 Model AX3000/M80 Type EA The reproduction of this material, in part or whole, is strictly prohibited.

More information

UPS Series. features: uninterruptible power supply. what great systems are built on.

UPS Series. features: uninterruptible power supply. what great systems are built on. uninterruptible power supply uninterruptible power supply with energy saver design that is optimized to address the needs of A/V systems features: Pure Sine Wave technology with Automatic Voltage Regulation

More information

Installation and Operation Back-UPS Pro 900

Installation and Operation Back-UPS Pro 900 software Us er Documentation Installation and Operation Back-UPS Pro 900 Inventory Connect the Battery bu001a User Documentation (2) Safety and General Information Inspect the package contents upon receipt.

More information

SmartPro LCD 120V 1200VA 700W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets

SmartPro LCD 120V 1200VA 700W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets SmartPro LCD 120V 1200VA 700W Line- Interactive UPS, AVR, 2U Rack/Tower, LCD, USB, DB9 Serial, 8 Outlets MODEL NUMBER: SMART1200LCD Highlights Supports a half-load (350W) up to 14.3 min. during power outage

More information

Installation and Operation Back-UPS Pro 900

Installation and Operation Back-UPS Pro 900 Us er Documentation Installation and Operation Back-UPS Pro 900 Inventory bu001a User Documentation (2) Safety and General Information Inspect the package contents upon receipt. Notify the carrier and

More information

SmartPro LCD 120V 50/60Hz 1500VA 900W Line- Interactive UPS, AVR, Tower, LCD, USB, 10 Outlets

SmartPro LCD 120V 50/60Hz 1500VA 900W Line- Interactive UPS, AVR, Tower, LCD, USB, 10 Outlets SmartPro LCD 120V 50/60Hz 1500VA 900W Line- Interactive UPS, AVR, Tower, LCD, USB, 10 Outlets MODEL NUMBER: SMART1500LCDT Highlights Supports a basic desktop PC up to 90 min. during power outage Features

More information

EATON 5S 850/1200/1600

EATON 5S 850/1200/1600 www.eaton.com EATON 5S 850/1200/1600 Installation and user manual Packaging EATON 5S 1 2 3 5 Caution! l Before installing the Eaton 5S, read the booklet 3 containing the safety instructions to be respected.

More information

SmartPro LCD 120V 1500VA 900W Line-Interactive UPS, Extended Run, 2U Rack/Tower, LCD Display, USB, DB9 Serial

SmartPro LCD 120V 1500VA 900W Line-Interactive UPS, Extended Run, 2U Rack/Tower, LCD Display, USB, DB9 Serial SmartPro LCD 120V 1500VA 900W Line-Interactive UPS, Extended Run, 2U Rack/Tower, LCD Display, USB, DB9 Serial MODEL NUMBER: SMART1500LCDXL Highlights 1500VA / 1.5kVA 2U rack/tower 120V line interactive

More information

User Manual. C Type Wall Mount Power Filter C2, C2-CN

User Manual. C Type Wall Mount Power Filter C2, C2-CN User Manual C Type Wall Mount Power Filter C2, C2-CN 2009 APC by Schneider Electric. APC, the APC logo, and TRADEMARK NAMES are owned by Schneider Electric Industries S.A.S., American Power Conversion

More information

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack, LCD display, USB, DB9 Serial

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack, LCD display, USB, DB9 Serial SmartOnline 100-127V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack, LCD display, USB, DB9 Serial MODEL NUMBER: SU3000RTXLCD2U Description Tripp Lite Smart Online UPS systems

More information

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack, LCD display, USB, DB9 Serial

SmartOnline V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack, LCD display, USB, DB9 Serial SmartOnline 100-127V 3kVA 2.7kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 3U Rack, LCD display, USB, DB9 Serial MODEL NUMBER: SU3000RTXLCD3U Description Tripp Lite Smart Online UPS systems

More information

TAA-Compliant SmartPro LCD 120V 1000VA 500W Line-Interactive UPS, AVR, Tower, USB, TEL/DSL/Coax Protection, 8 Outlets

TAA-Compliant SmartPro LCD 120V 1000VA 500W Line-Interactive UPS, AVR, Tower, USB, TEL/DSL/Coax Protection, 8 Outlets TAA-Compliant SmartPro LCD 120V 1000VA 500W Line-Interactive UPS, AVR, Tower, USB, TEL/DSL/Coax Protection, 8 Outlets MODEL NUMBER: SMART1000LCDTAA Highlights Supports a basic desktop PC up to 60 min.

More information

Safety and Maintenance You can use your Tablet PC under a wide range of environmental conditions. However, to ensure long use and continued high

Safety and Maintenance You can use your Tablet PC under a wide range of environmental conditions. However, to ensure long use and continued high EVG7 DL46 Getting Started Congratulations on your purchase of a Tablet PC. The Tablet PC is a fully functional PC with built-in LAN, and wireless connectivity. With your Tablet PC you will be able to organize

More information

Smart-UPS APC Smart-UPS 750VA USB & Serial RM 1U 120V

Smart-UPS APC Smart-UPS 750VA USB & Serial RM 1U 120V Smart-UPS APC Smart-UPS 750VA USB & Serial RM 1U 120V APC Smart-UPS, 480 Watts / 750 VA,Input 120V / Output 120V, Interface Port DB-9 RS-232, SmartSlot, USB, Rack Height 1 U Includes: CD with software,

More information

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318

ATS-16 HV USER MANUAL. Automatic Transfer Switch 16A / 230Vac V090318 ATS-16 HV Automatic Transfer Switch 16A / 230Vac USER MANUAL V090318 SAFETY Intended use The ATS-16 HV device serves as a power source selector to provide improved power supply for connected loads. ATS-16

More information

Port PCI Quick Installation Guide

Port PCI Quick Installation Guide 1394 3-Port PCI Quick Installation Guide Introducing the 1394 3-Port PCI The 1394 3-Port PCI is designed to connect DV camcorders, hard disk drives, scanners, printers and other 1394 audio/video devices

More information

LED FOLDING WORKLIGHT TM

LED FOLDING WORKLIGHT TM LED FOLDING WORKLIGHT TM LED LIGHT POWERSTRIP USB CHARGING ITM. / ART. 689211 Model: LM55812 CARE & USE INSTRUCTIONS IMPORTANT, RETAIN FOR FUTURE REFERENCE: READ CAREFULLY For assistance with assembly

More information

FCC Regulatory Information

FCC Regulatory Information DVW32C Advanced Wireless Voice Gateway - Safety and Installation Product Insert Federal Communications Commission (FCC) Interference Statement This equipment has been tested and found to comply with the

More information

Wise HP33 THREE PHASE HIGH PRECISION AVR SURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER

Wise HP33 THREE PHASE HIGH PRECISION AVR SURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER Wise HP33 THREE PHASE HIGH PRECISION AVR SURVO-MOTOR AUTOMATIC VOLTAGE STABILIZER LEN.MAN.STA.111 Rev.4.00/2010 CONTENTS 1. SAFETY INSTRUCTIONS 1 2. INTRODUCTION 2 3. FRONT PANEL AND CONNECTION BOARD 3

More information

Smart-UPS XL APC Smart-UPS XL 2200VA RM 3U 120V

Smart-UPS XL APC Smart-UPS XL 2200VA RM 3U 120V Smart-UPS XL APC Smart-UPS XL 2200VA RM 3U 120V APC Smart-UPS XL, 1850 Watts / 1850 VA,Input 120V / Output 120V, Interface Port DB-9 RS-232, USB, SmartSlot, Extended runtime model, Rack Height 3 U Includes:

More information

Owner s Manual. Isolate. Restore. Inspire! Power Conditioners Audio / Video Power Isolation Units Rack Mount / Consumer Series

Owner s Manual. Isolate. Restore. Inspire! Power Conditioners Audio / Video Power Isolation Units Rack Mount / Consumer Series Owner s Manual 19 Pro Series Rack Mount (RK) Faceplate Isolate. 17 Consumer Series (C) Faceplate Available in Black (B) and Silver (S) Colours Restore. Power Conditioners Audio / Video Power Isolation

More information

Installation and Operation

Installation and Operation Installation and Operation G-Type Rack Power Filter G50NETB2 G50NETB-20A2 120 Vac 15 A 20 A General Information Product Features The APC AV G-Type G50NETB2 and G50NETB-20A2 Rack Power Filters protect high-performance

More information

P OCKET POWER 6000 T. Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT

P OCKET POWER 6000 T. Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT P OCKET POWER 6000 T M Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT HALO POCKET POWER 6000 Thank you for choosing HALO. Innovative, fashionable and easy to use, the HALO

More information

SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, SNMPWEBCARD Option, LCD Display, USB, DB9 Serial

SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, SNMPWEBCARD Option, LCD Display, USB, DB9 Serial SmartPro 120V 1.5kVA 1.35kW Line-Interactive Sine Wave UPS, 2U Rack/Tower, SNMPWEBCARD Option, LCD Display, USB, DB9 Serial MODEL NUMBER: SMART1500RM2U Highlights 1500VA / 1.5kVA / 1350W line interactive

More information

SmartPro 120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial

SmartPro 120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial SmartPro 120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART1500SLT Highlights 1.5kVA / 1500VA line interactive tower UPS; Sine wave output 100/110/120V

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS Adaptor Model No. CZ-CFUNC1U For your safety Read the following instructions carefully, and carry out secure installation and electrical work. The precautions given in this manual

More information

AX3000 Platine Terminal Ethernet TCP/IP

AX3000 Platine Terminal Ethernet TCP/IP AX3000 Platine Terminal Ethernet TCP/IP Model 80WMS Installation Guide January 2012 - Ref: I80ME0922-2 Model AX3000/M80M Type EA The reproduction of this material, in part or whole, is strictly prohibited.

More information

Audio/Video Digital UPS Line-Interactive UPS System with LCD Status Screen

Audio/Video Digital UPS Line-Interactive UPS System with LCD Status Screen Audio/Video Digital UPS Line-Interactive UPS System with LCD Status Screen LOCATE A DISTRIBUTOR IN YOUR AREA Model #: HT1000UPS Automatic voltage regulation protects sensitive A/V components from damaging

More information

Allworx 24x Service and Troubleshooting Guide

Allworx 24x Service and Troubleshooting Guide Allworx 24x Service and Troubleshooting Guide -PAGE INTENTIALLY LEFT BLANK- Table of Contents 1 Safety Instructions...1 1.1 Electrical...1 1.2 Electrostatic Discharge...1 2 Chassis Views...2 3 Exterior

More information

SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack, USB, DB9 Serial, LCD

SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack, USB, DB9 Serial, LCD SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack, USB, DB9 Serial, LCD MODEL NUMBER: SMART1000RM2U Highlights 1kVA / 1000VA / 800W line interactive 2U rack/tower UPS, Sine

More information

AUD-340 Installation Guide

AUD-340 Installation Guide F0123456789ABC DE AUD-340 Installation Guide INPUTS CONTROL OUTPUT 24V DC 48V LINE 2 AUDIO IR RS232 COM 70V 100V 1 3 DIGITAL L R AUDIO 2.5A MAX TX RX 1 2 3 INPUT SELECT LINE BASS TREBLE MUTE 1 Safety Precautions

More information

SmartPro UPS System Intelligent line interactive medical-grade battery backup and network power management

SmartPro UPS System Intelligent line interactive medical-grade battery backup and network power management SmartPro UPS System Intelligent line interactive medical-grade battery backup and network power management Model #: SMART700HG UL2601-1 listed. Full isolation 700VA line interactive tower UPS system with

More information

HomePro ZRF113. Z-Wave Radio Frequency (RF) Controlled, 120 VAC, Isolated Contact Fixture Module, Series 200, Release 2.2

HomePro ZRF113. Z-Wave Radio Frequency (RF) Controlled, 120 VAC, Isolated Contact Fixture Module, Series 200, Release 2.2 RF Home Automation ZRF113 Z-Wave Radio Frequency (RF) Controlled, 120 VAC, Isolated Contact Fixture Module, Series 200, Release 2.2 Note: This module must be Included in the Network only where it will

More information

4 Message Paging System

4 Message Paging System 4 Message Paging System Thank you for choosing Pagertec Thank you for choosing Pagertec as your provider for your wireless paging requirements. We greatly appreciate your confidence in our products. At

More information

SmartPro LCD 120V 1000VA 500W Line- Interactive UPS, AVR, Tower, USB, TEL/DSL/Coax Protection, 8 Outlets

SmartPro LCD 120V 1000VA 500W Line- Interactive UPS, AVR, Tower, USB, TEL/DSL/Coax Protection, 8 Outlets SmartPro LCD 120V 1000VA 500W Line- Interactive UPS, AVR, Tower, USB, TEL/DSL/Coax Protection, 8 Outlets MODEL NUMBER: SMART1000LCD Highlights Supports a basic desktop PC up to 60 min. during power outage

More information

SmartPro LCD 120V 1000VA 500W Line-Interactive Desktop UPS, AVR, Tower, USB, TEL/DSL/Coax, 8 Outlets, ENERGY STAR

SmartPro LCD 120V 1000VA 500W Line-Interactive Desktop UPS, AVR, Tower, USB, TEL/DSL/Coax, 8 Outlets, ENERGY STAR SmartPro LCD 120V 1000VA 500W Line-Interactive Desktop UPS, AVR, Tower, USB, TEL/DSL/Coax, 8 Outlets, ENERGY STAR MODEL NUMBER: SMART1000LCDU Highlights Supports a basic desktop PC up to 60 min. during

More information

Model 7705 Control Module

Model 7705 Control Module www.keithley.com Model 7705 Control Module User s Guide PA-696 Rev. D / October 2006 A G R E A T E R M E A S U R E O F C O N F I D E N C E Safety Precautions The following safety precautions should be

More information

P OCKET POWER 9000 T. Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT

P OCKET POWER 9000 T. Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT P OCKET POWER 9000 T M Powerful Universal Portable Charger PLEASE READ BEFORE OPERATING THIS EQUIPMENT HALO POCKET POWER 9000 Thank you for choosing HALO. Innovative, fashionable and easy to use, the HALO

More information

AUD-220 Installation Guide

AUD-220 Installation Guide AUD-220 Installation Guide STEREO MONO BRIDGE IR RS232 TX RX MIC 48V LINE L R MIC 1 2 INPUTS 24V DC 1 x 40W @ 8Ω 2 x 20W @ 4Ω LOOP OUTPUTS The Intelix AUD-220 is a 2x20 watt Class D amplifier with 8Ω speaker

More information

SmartPro 120V 750VA 500W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial

SmartPro 120V 750VA 500W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial SmartPro 120V 750VA 500W Line-Interactive Sine Wave UPS, Tower, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART750SLT Highlights 750VA line interactive tower UPS; Sine wave output 100/110/120V

More information

Smart-UPS APC Smart-UPS 1500VA USB & Serial 120V

Smart-UPS APC Smart-UPS 1500VA USB & Serial 120V Smart-UPS APC Smart-UPS 1500VA USB & Serial 120V APC Smart-UPS, 980 Watts / 1440 VA,Input 120V / Output 120V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling

More information

Alternative B Type Mid-Span Power Sourcing Equipment. User s Guide

Alternative B Type Mid-Span Power Sourcing Equipment. User s Guide Alternative B Type Mid-Span Power Sourcing Equipment User s Guide REGULATORY STATEMENTS FCC Certifications This equipment has been tested and found to comply with the limits for a Class B digital device,

More information

SmartPro 120V 750VA 450W Line-Interactive UPS, AVR (Boost only), Tower, USB

SmartPro 120V 750VA 450W Line-Interactive UPS, AVR (Boost only), Tower, USB SmartPro 120V 750VA 450W Line-Interactive UPS, AVR (Boost only), Tower, USB MODEL NUMBER: SMART750USB Highlights 750VA tower 120V line interactive UPS Corrects brownouts as low as 89V without using battery

More information

WIRESPEED ADSL MODEM (MODEL 2000) User Guide

WIRESPEED ADSL MODEM (MODEL 2000) User Guide WIRESPEED ADSL MODEM (MODEL 2000) User Guide Copyright 2001 Westell, Inc. All rights reserved. 030-300187 Rev. A Printed in the United States of America December 2001 CONTENTS 1. PRODUCT DESCRIPTION...

More information

SmartPro LCD 120V 1.5kVA 900W Line-Interactive UPS, AVR, 2U Rack/Tower, LCD Display, USB, DB9 Serial

SmartPro LCD 120V 1.5kVA 900W Line-Interactive UPS, AVR, 2U Rack/Tower, LCD Display, USB, DB9 Serial SmartPro LCD 120V 1.5kVA 900W Line-Interactive UPS, AVR, 2U Rack/Tower, LCD Display, USB, DB9 Serial MODEL NUMBER: SMART1500LCD Highlights 1500VA / 1.5kVA 2U rack/tower 120V line interactive UPS with LCD

More information

4170 POS System Installation Guide

4170 POS System Installation Guide 4170 POS System 4170 Installation Guide Thank you for selecting UTC RETAIL s innovative Model 4170 Point of Sale solution! This Installation Guide will help you efficiently install the 4170 POS. The document

More information

Wireless Lighting Control. On/Off/Dim. Lamp Module. Z-Wave Certified Wireless Lighting Control

Wireless Lighting Control. On/Off/Dim. Lamp Module. Z-Wave Certified Wireless Lighting Control 45602 Wireless Lighting Control On/Off/Dim Lamp Module Z-Wave Certified Wireless Lighting Control Introduction: Thank you for your purchase of a GE Z-Wave control device. Z-Wave technology is designed

More information

Wa r n i n g-wa r n i n g-wa r n i n g

Wa r n i n g-wa r n i n g-wa r n i n g Installation Instructions of the Power Analyzer Wa r n i n g-wa r n i n g-wa r n i n g Read and understand this manual before connecting device. Death, fire or serious injury can occur from using equipment

More information

MGE Galaxy kva 208V. Operation

MGE Galaxy kva 208V. Operation MGE Galaxy 4000 40 75 kva 208V Operation Table of Contents About This Manual... 1 Companion Manuals... 1 Find Updates to this Manual... 1 Overview... 2 Operator Interface Keys and Indicators... 2 LED

More information

Notebook Expansion USB home dock with audio pass-through USER GUIDE

Notebook Expansion USB home dock with audio pass-through USER GUIDE Notebook Expansion USB home dock with audio pass-through USER GUIDE Table of Contents Introduction... 3 Package Contents... 5 System Requirements... 5 Connecting the Notebook Expansion USB home dock with

More information

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C

Instruction Manual. Electrical Management System (EMS) EMS-HW30C & EMS-HW50C Instruction Manual Electrical Management System (EMS) EMS-HW30C & EMS-HW50C EMS-HW50C EMS-HW30C! CAUTION These instructions are intended to provide assistance with the installation of this product, and

More information

SmartOnline V 1kVA 800W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial

SmartOnline V 1kVA 800W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial SmartOnline 100-120V 1kVA 800W On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU1000RTXL2UA Highlights 1000VA / 1kVA / 800 watt on-line double-conversion

More information

ECO Series 120V 850VA 425W Energy-Saving Standby UPS with USB port, LCD Display and 12 Outlets

ECO Series 120V 850VA 425W Energy-Saving Standby UPS with USB port, LCD Display and 12 Outlets ECO Series 120V 850VA 425W Energy-Saving Standby UPS with USB port, LCD Display and 12 Outlets MODEL NUMBER: ECO850LCD Description The ECO850LCD ultra-compact green UPS offers complete protection from

More information

Isobar 4-Outlet Surge Protector, 6 ft. Cord with Right-Angle Plug, 3300 Joules, Diagnostic LEDs, Tel/Fax/Modem, Metal

Isobar 4-Outlet Surge Protector, 6 ft. Cord with Right-Angle Plug, 3300 Joules, Diagnostic LEDs, Tel/Fax/Modem, Metal Isobar 4-Outlet Surge Protector, 6 ft. Cord with Right-Angle Plug, 3300 Joules, Diagnostic LEDs, Tel/Fax/Modem, Metal MODEL NUMBER: ISOTEL4ULTRA Highlights 4 NEMA 5-15R outlets in exclusive isolated filter

More information