Lightning Protection as Per IEC & Key Factors of Installation, Maintenance
|
|
- Dana Day
- 5 years ago
- Views:
Transcription
1 IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: ,p-ISSN: , Volume 12, Issue 5 Ver. I (Sep. Oct. 2017), PP Lightning Protection as Per IEC & Key Factors of Installation, Maintenance * Dr. K. Janakiraman., Senior Manager Product Development, M/s. OBO Bettermann INDIA PVT LTD., India (The Author is also a Representing Member of National Building Code BIS) Corresponding Author: Dr. K. Janakiraman. Abstract: The basic interest of this paper is to discuss and insist on the importance of protection devices / system and to regulate the overall process including selection, installation and upkeep of the lightning protection system in place for many years down the line of installation. Not limiting to the orientation of the product technicality or specification, the most important thing that is left out off-late is the Good Practices to be maintained in implementing and maintaining the same. Many installations across the world for lightning protection device just confirm to the requirement criterion of merely having a terminal on top and further completion of system are not followed. This paper will help in understanding the issues of various installation procedures and fool proof method of recommending and implementing Lighting Protection System, Earthing and Surge Protection System. This paper also will define about, how a selection of lightning protection device is to be done, the basis of installation and utilization of component. Keywords: Complete Solution against Lightning, Lightning Protection, Maintenance & Installation aspects of Lightning protection system Date of Submission: Date of acceptance: I. Introduction The most important aspect of understanding in lightning protection is that - not only a direct lightning strike act as a potential threat to the structure but also more frequently, electronic equipment are damaged by surges caused by remote lightning discharges (caused because of Lightning Electromagnetic Impulses LEMPs)or switching operations in larger electrical systems. During thunderstorms too, high volume of energy is instantaneously released. These voltage peaks can penetrate a building through Power, Data and Telephone cables causing heavy damage to Electronic Equipment. The international standard for Lightning Protection referred as IEC Protection against Lightning, (which is also accepted by many countries as national standard) especially adopted by Bureau of Indian standard as IS IEC 62305, in one of its part explains the need of planning, erection, testing and maintenance of lightning protection systems for building structures without any height limit. The same is also implemented in new National Building Code 2016, Part -8, Section 2 which also clearly defines the need of the measures to be taken care for planning, erection, testing and maintenance of lightning protection system. The standard IEC in its second part Risk Management categorizes the four sources of Lightning as 1. Flashes to a structure, 2. Flashes near to a structure 3. Flashes to a service line, 4. Flashes near to a service line. Fig 1 : Representation of different sources of lightning (picture courtesy IEC ) DOI: / Page
2 A proper lightning protection system design is very important to ensure increased protection of a building against Lightning and its effects. Systems followed in most of the buildings now are unfortunately not meeting the basic or statutory requirements. Since only a mere vertical air terminal will not solve the purpose for protection of building unless the entire building is sufficiently protected either with 1. Angle of protection method 2. Mesh conductor method or calculated as per rolling sphere method. It is important to remember any best lightning protection implemented in the structure will not protect the personal outside the building (within the premises where the building is located). Since the angle of protection offered by the lightning protection terminal will only protect against direct strike, however induced step and touch potential will not be protected and which will lead to electrocution and causalities thereafter. The standard practice of using external lightning protection system is to handshake with the downward leader of the lightning strike and ensure the lightning does not strike anywhere else in the structure. A proper lightning protection system, should consist of three prime components in principal Air termination (vertical or horizontal mesh), down conductor and earthing system and should also offer a least resistance path for the discharge of lightning current. This measure should not be mis-understood that by providing external lightning protection our entire equipment / devices will get protected from damage. Separate measures as recommended in IEC Protection against Lighting: Electrical and Electronic system within the structure need to be followed and a proper and respective Surge Protection Device (SPDs)need to be employed individually for power line, data line and coaxial line for various application such as electronic appliances, internet modems, television etc. Assume a television has failed due to lightning, the protection measure for that Television should be co-ordinated by employing SPDs at both power and Data inputs (satellite cable - coaxial cable terminated) since both sources are vulnerable of carrying lightning current. If this method is practiced then damages can be avoidedfor such systems even if connection remains plugged. In both external lightning protection system and internal lightning protection system (SPDs) Earthing is an inevitable component, without which in both the cases dissipation of current is possible. Hence properly selected and properly maintained earthing is also needed for maximum safety in consolidation. II. Effective Lightning Protection Measures Proper measures are to be taken care of while designing, procuring and installing of lighting protection components for handling a strike and dissipation of current without any dangerous spark overs. For buildings are surrounded by trees, or a taller metallic tower the protection measures should include not only lightning protection but also required ring earthing around the building and Surge protection for the equipment since the fatality due to lighting could be more disastrous for an equipment than a structural damage. Fig - 2 : Sample representation of Lightning protection, Surge Protection and Earthing for building located near metallic structure. DOI: / Page
3 Moreover the installed protective devices tend to lose their visibility in due course due to various reasons. Periodic maintenance, monitoring and certification should be made mandatory for the effective functioning of the protective devices installed. For protection of Electrical, wiring, Electrical and electronic equipment, installation of Surge Protection Devices should be adopted. Lightning Protection is often a challenge for the building designer when it comes to aesthetics of the building. Routing of down conductors through outer wall generally spoil the aesthetics of the building, due to which the down conductors are often routed through shafts, un-accessible areas, non-visible places etc. These down conductor increases the chance of fire and explosion in case of lightning. As a statutory requirement Lightning Protection is implemented in most of the buildings, but unfortunately in an inefficient way. Lightning flashes to, or nearby, structures (or lines connected to the structures) are hazardous to people, to the structures themselves, their contents and installations need to be considered for protection measures. An effective lightning protection is achieved only if the following points are adhered viz., Type of protection Level of protection based on risk assessment Technically qualified product as per latest and relevant IEC standards Sizes and dimensions of components Location of Air terminal& coverage Conductor routing and connections Sufficient and required Earthing provisions Proper Utilization natural components as down conductor if applicable. III. Design Guidelines The following design guidelines need to be adhered to ensure safer installation of the external LPS. A down-conductor should be installed at each exposed corner of the structure where this is possible. The down-conductors should form a direct continuation of the air-termination conductors Straight and vertical so that they provide the shortest and most direct path to earth The formation of loops in bring the down conductor shall be avoided, but where this is not possible the distance s shall be maintained. Connection of down conductors to gutters or down-spouts even if they are covered by insulating materials. Usage of multiple connection with different materials should not be permitted. Insufficient conductor dimensions (non-complying material as mentioned in IEC Table 5) should be strictly avoided. When the distance from down conductors to combustible materials can not be assured, the cross section of the down conductor shall not be less than 100 mm² The electrical insulation between the air-termination or down-conductors and the structural metal parts, the metal installations and the internal systems can be achieved by providing a distance d between the parts greater then the separation distance s. S = (Ki) x {Kc/Km} x L Where: Ki Kc Km L -depends on the selected class of LPS - depends on the lightning current flowing on the down conductors - depends on the electrical insulation material - length in meters along the air-termination or down-conductor, from the point where the separation distance is to be considered, to the nearest EPB point Selection of Zonal Concepts need to be analyzed (LPZ- Lightning Protection Zones) in the IS / IEC standards. Secondly proper installation is more important than the selection of SPDs. It is strongly the responsibility of the SPD manufacturer to study the site, identify the key areas where protection is mandatory. Depending upon the nature of LPS system and area to be protected the number of air termination will be decided. The maximum distance of any point on the roof from the nearest horizontal protective conductor shall be decided as per nature of LPS system and the level of protection. Horizontal conductors in form of a mesh conductor. The mesh spacing of the horizontal conductor should depend on the class of LPS as per tabulation of IEC Part 3 for mesh spacing. CHECKLIST REQUIREMENTS: Inspections, tests, and maintenance shall be performed in accordance with either of the standards, IEC or NFPA 780 (latest edition). The following list highlights minimum requirements for the essential care of lightning protection systems. Many system components tend to lose their DOI: / Page
4 effectiveness over the years because of corrosion factors, roof repairs, weather related damage, and damage caused by lightning strikes. The physical, as well as the electrical characteristics, of the lightning protection system must be maintained to prevent building damage. The following points are the minimum requirement of design guideline as recommended in various IEC standards: Air terminal should be selected and provided only based on the protection angle or rolling sphere method. Connection to the air terminal and down conductors should be checked properly and the connection need to be done with proper tested clamps as insisted by IEC (Lightning Protection System Components) Wherever incompatible materials to be joined (Ex. Copper with Aluminium), suitable bi-metal connectors should be used. Suitable expansion joints must be provided on the horizontal conductors on top to take care of thermal effects. Special conductor holders of insulating type need to be provided on top of the terrace floor for routing the conductor to ensure electrocution impact does not happen in case of water stagnation. Establishing connection for equipotential bonding with nearby metallic components need to be taken care of. Proper safety distance between the air terminal and any metallic object need to be maintained as per the calculation mentioned earlier to avoid dangerous spark-overs. Down conductor should run as straight as possible thereby providing a low impedance path from the air termination to the earth electrode so that the lightning current can be safely conducted to earth. There should be a test joint arrangement to have separation between down conductor and earth termination for safety and for measurement of earth resistance. At least two down conductors are mandatory immaterial of how small is the installation is. In case of using reinforcement in concrete structures as lightning down conductor details should be decided at the design stage, before building construction begins. Good contact between reinforcing bars to be ensured only by using connection clamps tested as per the requirement of IEC Joints should be mechanically and electrically effective, should be protected against corrosion or erosion from the elements or the environment and should present an adequate contact area. A common earth termination network is recommended for the lightning protective system and all other services. Earth electrodes for each down conductor to be provided for the installation. The termination of down conductor to an earth electrode should be done minimum of 1 meter away from the structure and minimum of 0.5m depth inside the ground. Proper monitoring and value measuring option to be provided for earth pits and should be protected with proper cover and maintained. Selection of Earth electrode should be accordance with the recommendations of IEC & IEC Required measures to ensure shielding, bonding / equipotential bonding techniques are handled properly to avoid LEMPs. Proper SPDs need to be employed at every entry point of a service in to the building. The cable lead length to& from the SPD should be shorter less than 025m as recommended in IEC. Use proper signage boards mentioning lightning protection down conductor, earth pits etc., for people to easily identify. IV. Conclusion The most neglected part in many structures / buildings are protection against lightning. Since the post impact of lightning is too severe and disastrous care should be given at every level to ensure lightning protection is not provided for seeking statutory approvals. The installation should not be a vendor driven and only based on regulations as insisted by National / International standards and code. All maintenance procedures shall be scheduled and carried out meeting the standard requirements in periodic intervals. Last but not the least human safety from lightning will only be possible by creating awareness, use of warning signage boards in required location and not by any protective devices. DOI: / Page
5 About the Author: Dr. K. JANAKIRAMAN is an eminent speaker in many forum on Protection against Lightning, Earthing and Surge Protection Techniques. With his field experience in the area of Lightning Protection for more than 12 years and also based on his practical site visit experience on lightning protection installation in various countries as Germany, Sri Lanka, Spain, Malaysia, Singapore & London he has authored several articles and publications in many conferences and journals. Also have delivered several Guest lectures in many universities on Electrical Systems for budding future Engineers. The author is also a representing member in CED46 committee for Electrical Installations of National Building Code, India. References [1] IEC : International Electro technical Commission standard : Protection against Lightning : Part -2 Risk Assessment. [2] IEC : International Electro technical Commission standard : Protection against Lightning : Part -3Physical Damage to Structure and Life hazard. [3] IEC : International Electro technical Commission standard : Protection against Lightning : Part -2 Electrical & Electronic System within the structure. [4] IEC part 1 7 : Lightning Protection System Components (All parts) [5] NBC 2016 : National Building Code of India: Part 8 Building Services, Section 2 Electrical Installations IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) is UGC approved Journal with Sl. No. 4198, Journal no *Dr. K. Janakiraman. Lightning Protection as Per IEC & Key Factors of Installation, Maintenance. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE), vol. 12, no. 5, 2017, pp DOI: / Page
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62305-4 Edition 2.0 2010-12 Protection against lightning Part 4: Electrical and electronic systems within structures INTERNATIONAL ELECTROTECHNICAL COMMISSION XC ICS 29.020;
More informationFirst Year Operation Events for EgyptSat-1: Ground Control Station Lightening strike and Protection Measures"
First Year Operation Events for EgyptSat-1: Ground Control Station Lightening strike and Protection Measures" By Prof.Fatma Elhefnawi, Eng. Ahmed Yousef, Prof.Amal Zaki fatma.hefnawi@gmail.com Prof.Dr.Fatma
More informationCode for Design Protection of Structures Against Lightning
UDC NATIONAL STANDARD OF THE PEOPLE'S REPUBLIC OF CHINA i:f:t~a~:=jt*100 00%filt p GB 50057-2010 Code for Design Protection of Structures Against Lightning Issued on: November 3, 2010 Implemented on: October
More informationLIGHTNING PROTECTION
The University of New South Wales School of Electrical Engineering and Telecommunications Industrial and Commercial Power Systems Topic 8 LIGHTNING PROTECTION Aim is to protect: People Buildings and Contents
More informationALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD
64 Catalyst Drive Canton, North Carolina, 28716 USA +1.828.646.9290 +1.828.646.9527 (Fax) +1.800.203.2658 (Toll Free) www.alltecglobal.com ALLTEC PROTECTION PYRAMID TM FOR PHOTOVOLTAIC SOLAR FIELD Photovoltaic
More informationLIGHTNING PROTECTION FOR ROOFTOP PV PLANTS LIGHTNING & SURGE PROTECTION SYSTEM
LIGHTNING PROTECTION FOR ROOFTOP PV PLANTS LIGHTNING & SURGE PROTECTION SYSTE PREPARED BY : LIGHTNING PROTECTION CONCEPTS PONTINS REFERENCE : D00-RTPVP-05 ISSUE : B DATE : arch 07 Lightning Protection
More informationLightning and Surge Protection of Photovoltaic Installations. Leutron GmbH 2013 Leinfelden-Echterdingen, Germany
Lightning and Surge Protection of Photovoltaic Installations 1 Lightning and Surge Protection for PV Installations 2 Safeguard from Risks Ups, that was the insurance policy of my house!! 3 Why Lightning
More informationINTERNATIONAL. Protection against lightning Part 4: Electrical and electronic systems within structures
INTERNATIONAL STANDARD IEC 62305-4 First edition 2006-01 Protection against lightning Part 4: Electrical and electronic systems within structures This English-language version is derived from the original
More informationSession Two: Effective Surge Protection Installation
Abstract Session Two: Effective Surge Protection Installation Phillip Tompson Managing Director, Novaris Pty Ltd This paper provides an outline of how to effectively install surge protection to various
More informationLightning and surge protection for wind turbines
Lightning and surge protection for wind turbines Information from DEHN Due to their vast exposed surface and height, wind turbines are vulnerable to direct lightning strikes. Since the risk of lightning
More informationLIGHTNING AND SURGE PROTECTION
White Paper LIGHTNING AND SURGE PROTECTION Lightning and Surge Protection 01/20/17 1 of 7 www.murata.com APPLICATION NOTE: LIGHTNING AND SURGE PROTECTION Because wireless systems are typically located
More informationMaking the Right Choices In Lightning & Surge Arrestors Some Basics:
Making the Right Choices In Lightning & Surge Arrestors Some Basics: It is a fact that the Highveld region of South Africa and Lesotho have amongst the highest lightning strikes per square km per annum
More informationLightning and Surge Protection of Cellular Transmit Sites
IX-19 Lightning and Surge Protection of Cellular Transmit Sites D. Kokkinos, N. Kokkinos, I. Vlaseros, ELEMKO SA, K. Dimas, M. Koulizos, P. Garoufalis, J. Sotiriadis TIM STET HELLAS Abstract-- This paper
More informationOutdoor Risk and Equipment Protection
Outdoor Risk and Equipment Protection The proper use of surge suppressors, lightening arrestors, and weatherproof enclosures are critical protection measures for all outdoor wireless and IP video devices.
More informationRetrofitting sewage plants with lightning and surge protection measures
904 Retrofitting sewage plants with lightning and surge protection measures A more efficient use of drinking water is growing in significance, especially against a backdrop of increasingly scarce drinking
More informationProtection against electric shock
Protection against electric shock BS EN 61140 tells us that hazardous live parts shall not be accessible and that accessible conductive parts shall not be hazardous live, when in use without a fault or
More informationPHOTOVOLTAIC PLANTS Comprehensive lightning protection
PHOTOVOLTAIC PLANTS Comprehensive lightning protection 1. Introduction Photovoltaic (PV) plants are composed of many panels supported on large metal structures, located in open areas and normally highly
More informationdv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2
dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Operating Instructions Safety information 1 General 2 Mechanical installation 3 Electrical
More information17 th Edition (BS 7671:2008) incorporating Amendment No 1
20 17th Edition 17 th Edition (BS 7671:2008) incorporating Amendment No 1 Installations designed from the 1 st January 2012 are to comply with Amendment number 1. Geoff Cronshaw The first amendment to
More informationLightning Protection for a Complex Isolated Renewable and Diesel Power Network Micro Grid
Lightning Protection for a Complex Isolated Renewable and Diesel Power Network Micro Grid D. Kokkinos 1, G. Ladopoulos 2, N. Kokkinos 1 1: Elemko SA, Tatoiou 90, 144 52 GR, Metamorphosis, Hellas 2: Fasma
More informationLXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual
LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp Single phase two wire DIN rail energy meter (One module) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic
More informationSystems which use a conventional POTS subscriber line to dial a compatible system and transfer digital data.
PSTN Protection The demand for voice and data communications has never been greater. Today, virtually everyone in the developed world has access to a land-line telephone, which carries their voice or data
More informationDesign of Lightning Protection Systems. DEHNsupport Toolbox Software.
Design of Lightning Protection Systems DEHNsupport Toolbox Software www.dehn-international.com 2 No more complicated calculations with DEHNsupport Toolbox Software for design and calculation of lightning
More informationBS th Edition wiring regulations Furse overview
BS 7671 18th Edition wiring regulations Furse overview Transient overvoltage protection TRANSIENT OVERVOLTAGE PROTECTION - RISK ASSESSMENT TO BS 7671 Furse electronic systems protection Enhanced solutions
More informationMICHIGAN DEPARTMENT OF TRANSPORTATION
MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13
More informationModel P4017 Single Channel USB Oscilloscope. Quick Start Guide
Model P4017 Single Channel USB Oscilloscope Quick Start Guide General Warranty BNC warrants that the product will be free from defects in materials and workmanship for 3 years from the date of purchase
More informationManual for overvoltage protection for LED luminaires rev 1
Kurtatsch, Italy, February 10, 2017 Manual for overvoltage protection for LED luminaires rev 1 Through the introduction of LED luminaires, substantial improvements have been achieved with respect to conventional
More informationGLOSSARY OF TERMS. Surge and Lightning Protection ERICO Inc.
GLOSSARY OF TERMS Surge and Lightning Protection ERICO Inc. Air Termination - shall mean that part of a lightning protection system designed to capture the lightning strike. Normally is mounted on the
More informationSINAMICS. SINAMICS G120P dv/dt filter plus Voltage Peak Limiter. Safety information 1. General. Mechanical installation. Electrical installation 4
Safety information 1 General 2 SINAMICS SINAMICS G120P dv/dt filter plus Voltage Peak Limiter Operating Instructions Mechanical installation 3 Electrical installation 4 Maintenance and servicing 5 Technical
More informationA Hybrid Lightning Strike Protection System
6687 Arapahoe Road Boulder, Colorado 80303-1453 USA Ph: +1-303-447-2828 Fx: +1-303-447-8122 A Hybrid Lightning Strike Protection System Roy B. Carpenter, Jr. Darwin N. Sletten, PE Revision B, August 2014
More informationSDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)
SDM120 SERIES Single phase two wire DIN rail energy meter (One module) User manual ------------ 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Dimension
More informationProduct safety and quality. Edition 2 of the testing standards IEC/EN (VDE ) for lightning protection system components
Product safety and quality Edition 2 of the testing standards IEC/EN 62561 (VDE 0185-561) for lightning protection system components International overall provider for lightning and surge protection systems
More information2 Principle of lightning protection
2 Principle of lightning protection The system for protecting a building against the effects of lightning must include: bprotection of structures against direct lightning strokes; bprotection of electrical
More informationSurge protection for closed-circuit television systems (CCTV) Guide for support in planning and installation. Building Connections
Surge protection for closed-circuit television systems (CCTV) Guide for support in planning and installation Building Connections Application Camera systems are used to monitor rooms, buildings and outdoor
More informationELPROMA NTSprotect Surge Protection
ELPROMA NTSprotect Surge Protection Rack 19 back panel with NTS-protect As the antenna is roof mounted (to have a clear view of the sky) it is likely to be exposed to lightning strikes. Protection against
More informationDeploying surge protective devices (SPDs) in photovoltaic systems. Technical Information
Deploying surge protective devices (SPDs) in photovoltaic systems Technical Information 2 00/09.08 Preface Preface Damages caused by overvoltage s are not only responsible for expensive repair costs; they
More informationOperating Instructions
Introduction To protect the signal lines of field devices and systems in the cabinet against lightning. Pepperl+Fuchs covers the complete range of Surge Protection Barriers. Housing types Depending on
More informationRisk Assessment of Damages due to Lightning Discharges: A Case Study to a Telecommunication System in Singburi Province of Thailand.
Proceedings of the 2007 WSEAS Int. Conference on Circuits, Systems, Signal and s, Gold Coast, Australia, January 17-19, 2007 216 Risk Assessment of Damages due to Lightning Discharges: A Case Study to
More informationLine reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation
Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.7 04/2014 A5E00331462A Legal
More informationEMC-Compatible Installation of the Electric Cabinet
EMC-Compatible Installation of the Electric Cabinet Introduction Malfunction and failure of an automated system due to electromagnetic influence can cause loss of production with high follow-up costs.
More informationPRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5
PRO1250D CT MID DIN rail three phase four wire energy meter. User manual Version 1.5 1 Safety instructions...3 2 Foreword...4 3 CE certificates...5 4 MID certificate...7 5 Performance criteria...8 6 Specifications...8
More informationLightning Current Equipotential Bonding SPDs
Lightning Current Equipotential Bonding SPDs Introduction Furse is a world leader in the design, manufacture, and supply of earthing and lightning protection systems. Over 100 years of experience makes
More informationPRO-1250D CT MID DIN rail three phase four wire energy meter.
PRO-1250D CT MID DIN rail three phase four wire energy meter. 1.1 Safety instructions 1.2 Foreword 1.3 MID certificate 1.4 Performance criteria 1.5 Specifications 1.6 Basic errors 1.7 Description 1.8 Dimensions
More informationXTM1250SA DIN rail three phase four wire LCD display energy meter
XTM1250SA DIN rail three phase four wire LCD display energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Intrinsic errors 1.6 Description 1.7 Dimensions 1.8
More informationPRO1 V21.xxx series MID DIN rail single phase two wire energy meter
PRO1 V21.xxx series MID DIN rail single phase two wire energy meter PRO1D V21.212 Version 1.1 Note: the picture on the frontpage is a meter from the series of this meter, it might not be exactly the same
More informationPreparing to Install the VG248
CHAPTER 2 To ensure normal system operation, plan your site configuration and prepare your site before installation. Before installing the VG248, review these sections: Preparing the Installation Site,
More informationZener Barriers Bulletin 937Z
Technical Data Zener Barriers Bulletin 937Z Topic Page Introduction 2 Mounting 2 Housing 3 Operating Principle 3 Specifications 6 Introduction Allen-Bradley Zener barriers are a cost-effective solution
More informationThe Solid-State Decoupler (SSD)
The Solid-State Decoupler (SSD) Installation Instructions Introduction The Solid-State Decoupler (SSD) is a solid-state DC isolation/ac grounding (i.e., coupling) device design ed for use in conjunction
More informationETSI EN V1.2.1 ( )
EN 302 999 V1.2.1 (2013-03) European Standard Safety; Remote Power Feeding Installations; Safety requirements for the erection and operation of information technology installations with remote power feeding
More informationHazardous Area Protection
Hazardous Area Protection Global Solutions in Hazardous Area Surge and Lightning Protection Intrinsic Safety When instrumentation is installed in a potentially explosive environment steps must be taken
More informationObtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx
Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining
More informationMICHIGAN DEPARTMENT OF TRANSPORTATION
MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 6 APPR:MDW:JVG:06-08-18
More informationDANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.
Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,
More informationBS EN :2012 Part 2: Risk Management
BS EN 62305-2:2012 Part 2: Risk Management 2 - BS EN 62305 Risk Management 1 Lightning protection standardisation BS EN 62305-2 62305-1 General Principles 62305-2 Risk Management 62305-3 Physical damage
More informationITU-T K.118. Requirements for lightning protection of fibre to the distribution point equipment SERIES K: PROTECTION AGAINST INTERFERENCE
I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T K.118 TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU (12/2016) SERIES K: PROTECTION AGAINST INTERFERENCE Requirements for lightning
More informationSECTION PANELBOARDS
SECTION 16450 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for panelboards providing fault interrupting capability and overcurrent protective devices. 1.02 REFERENCE STANDARDS A.
More informationTel: Web: Lightning and surge protection help pages
Lightning and surge protection help pages Effects of lightning on your home or office Modern Technology has progressed to the point where detecting and preventing surges, has become an exact science -
More informationITU-T K.66. Protection of customer premises from overvoltages SERIES K: PROTECTION AGAINST INTERFERENCE. Recommendation ITU-T K.
International Telecommunication Union ITU-T K.66 TELECOMMUICATIO STADARDIZATIO SECTOR OF ITU (06/2011) SERIES K: PROTECTIO AGAIST ITERFERECE Protection of customer premises from overvoltages Recommendation
More informationInstallation manual plugs and connectors with screw connection (16/32 A)
EN Installation manual plugs and connectors with screw connection (16/32 60003213 Issue 04.2016 2016-04-01 Table of contents 1 About this manual 3 1.1 Structure of the warnings 3 1.2 Symbols used 4 1.3
More informationNational Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 14 FROM: Kimberly Shea,
More informationInstallation Notes TII Model 341 Protector
Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow
More informationTRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 07/16/08 TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA
TSEWG TP-3: SURGE PROTECTOR PERFORMANCE AND EVALUATION CRITERIA SURGE PROTECTION DESIGN. Parallel Versus Series Protection. Surge protectors within the scope of this UFC should normally be of the parallel
More informationLightning and surge protection for maximum safety and security. Protected THINK CONNECTED.
Lightning and surge protection for maximum safety and security Protected THINK CONNECTED. Lightning and voltage surges endanger people and assets. 2 OBO TBS Protected Like four well-trained bodyguards,
More informationModel 2600B-PM V Protection Module with 1 A Clamp. Description / April 2015 *PPA * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2600B-PM-1 200 V Protection Module with 1 A Clamp Description The Model 2600B-PM-1 200 V Protection
More informationUSER MANUAL MODEL 570/ Base-T (CAT-5) Surge Protectors SALES OFFICE (301) TECHNICAL SUPPORT (301)
USER MANUAL MODEL 570/580 100Base-T (CAT-5) Surge Protectors Part# 07M570/580-B Doc# 074091UB Revised 2/16/96 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007 1.0 WARRANTY INFORMATION Patton
More informationDRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria
DRT-301 A/D Three phase four wire DIN rail energy meter (Seven modules) 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Structure Diagram 1.7 Dimensions
More informationElectrical Components and Equipment for General Use Self Inspection Checklist
Name of School: Optional Information Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: Electrical Components and Equipment for General Use Self Inspection Checklist Guidelines:
More informationSIWAREX JB Aluminum Housing. Instruction Manual Edition 03/2006
s SIWAREX JB Aluminum Housing Instruction Manual Edition 03/2006 Table of Contents Table of Contents... 2 Warning and Safety Terms... 3 General... 4 1 Technical Description... 5 1.1 Area of Application...
More informationOPERATING MANUAL FOR THE 30KV A.C. TEST SET P123. Bicotest High Voltage Products Ltd
OPERATING MANUAL FOR THE 30KV A.C. TEST SET P123 Product: High Voltage AC Test Set Type: P123 Bicotest High Voltage Products Ltd Hellesdon Park Road, Drayton High Road, Norwich NR6 5DR United Kingdom Phone
More informationPRO-75 SERIES. User manual
PRO-75 SERIES DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
More informationGE Power Conversion T1930EN INSTRUCTION SHEET REV. 09 MV3000E DELTA MAINS VOLTAGE MONITOR UNIT MVC X 1. DESCRIPTION
GE Power Conversion T1930EN INSTRUCTION SHEET REV. 09 MV3000E DELTA MAINS VOLTAGE MONITOR UNIT 1. DESCRIPTION The Mains Voltage Monitor Unit (MVM Unit) is used to precisely monitor the mains voltage and
More informationModel 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit
More informationPRO1250D CT M-bus MID DIN rail three phase four wire energy meter. User manual Version 1.11
PRO1250D CT M-bus MID DIN rail three phase four wire energy meter. User manual Version 1.11 1 Safety instructions...3 2 Foreword...4 3 MID certificate...5 4 CE certificates...6 6 Performance criteria...8
More informationLIGHTNING DANGEROUS CAUSED BY POTENTIAL DIFFERENCES INSIDE STRUCTURES
10. Щуп Т.Е. Прикладные численные методы в физике и технике. М.: Высшая школа, 1990. С. 168-176. 11. Дьяконов В.П. Справочник по алгоритмам и программам на языке Бейсик для персональных ЭВМ. М.: Наука,
More informationPOCKET MULTIMETER Model No: MM18
INSTRUCTIONS FOR: POCKET MULTIMETER Model No: MM18 Thank you for purchasing a Sealey product. Manufactured to a high standard this product will, if used according to these instructions and properly maintained,
More informationIRANIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 4, NO. 1, WINTER-SPRING 2005
IRANIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING, VOL. 4, NO. 1, WINTERSPRING 2005 57 Study of Overvoltage Protection of a Microwave Repeater Station P. Valsalal, S. Usa, and K. Udayakumar Abstract
More informationLightning Protection of Buildings: Guidance to MS IEC and Updates from Working Group/Research Institute
Lightning Protection of Buildings: Guidance to MS IEC 62305 and Updates from Working Group/Research Institute Professor Mohd Zainal Abidin Ab Kadir, PhD PEng CEng CELP UPM Chair, IEC TC 81: Lightning Protection
More informationYOU NEED A WHOLE- HOUSE PROTECTION SYSTEM
YOU NEED A WHOLE- HOUSE PROTECTION SYSTEM Dr. Richard L. Cohen Panamax San Rafael, CA, 94903 (INTRO/ABSTRACT) Hard-wired AC and telephone protectors at the building entrance can keep major disturbances
More informationLightning PROtECtiOn general PRinCiPLEs theory of the Lightning Flash
Lightning PROTECTION General Principles Theory of the Lightning Flash Lightning is a natural phenomenon which develops when the upper atmosphere becomes unstable due to the convergence of a warm, solar
More informationIM /2016 REV01 LACI Production Monitoring Module
IM3063 03/2016 REV01 LACI Production Monitoring Module OPERATOR S MANUAL Lincoln Electric Bester Sp. z o.o. ul. Jana III Sobieskiego 19A, 58-263 Bielawa, Poland www.lincolnelectric.eu Declaration of conformity
More informationOwner s Manual DMX SPLITTER
Owner s Manual DMX SPLITTER 4 www.thomann.de 1 Thank you for choosing one of our DMX splitters. Please read this user manual carefully and follow the instructions to avoid danger or damage to the unit
More information9040/9040UK. Users Manual. Phase Rotation Indicator
9040/9040UK Phase Rotation Indicator Users Manual PN 2438546 April 2005 2005 Fluke Corporation. All rights reserved. Printed in China All product names are trademarks of their respective companies. LIMITED
More informationSolutions for residential buildings
Solutions for residential buildings THINK CONNECTED. Solutions for residential buildings The place where we feel safest and most secure must surely be within our own four walls. OBO offers a wide range
More informationicore Kiosk system Installation Guide
icore Kiosk system Installation Guide The reproduction, transmission or use of this document or its contents is not permitted without express authority. Offenders will be liable for damages. All rights,
More informationOperating Instructions for Level Switch for Liquids. Model: RFS
Operating Instructions for Level Switch for Liquids Model: RFS 1. Contents 1. Contents... 2 2. Note... 3 3. Instrument Inspection... 3 4. Regulation Use... 3 5. Operating Principle... 4 6. Use in Hazardous
More informationEmerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.
Liebert PSA iton User Manual Version: V2.8 Revision date: November 14, 2005 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or
More information2 Check that Public Safety has been considered (e.g. cabinet secured and locked, trip hazards removed where applicable).
NOTE: SAFETY: Tests must be carried out after the installation, alteration or repair and before putting back to service. At all times maintain suitable clearance to all other electrical equipment and verify
More informationINTRINSICALLY SAFE Ex ia PSU TYPE AC36W
Title INTRINSICALLY SAFE Ex ia PSU TYPE AC36W USER MANUAL Document Number 66-184-12 Issue 10 10 Update new logo and address 2017.10.18 CW CW PC 09 Added Um as 265V, Io up to 3.3A & IIB data 2017.08.21
More informationTelcordia GR-1089-CORE Issue 4 Topics Primary Protection
Telcordia GR-1089-CORE Issue 4 Topics Primary Protection Bourns engages in standards development and produces components that will help customers products comply with published standard requirements. For
More information110.4 Use of Equipment.
110.4 Use of Equipment. (A) Test Instruments and Equipment. 1 Testing. Only qualified persons shall perform tasks such as testing, troubleshooting, and voltage measuring within the limited approach boundary
More informationSINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS
SINAMICS G130 Operating Instructions 03/2013 SINAMICS s Safety information 1 General information 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5
More informationM ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS
M ISCELLANEOUS A CCESSORIES O BSTRUCTIONS LIGHTS MISCELLANEOUS ACCESSORIES OBSTRUCTION LIGHTS G1 Outdoor Surge Protector for AC/Traction network VP range Dimensions (in mm) 19 M8 44 73 diam. 47 6 mm² Electrical
More informationSINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS
SINAMICS G130 Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Voltage Sensing Module 10 (VSM10) Mechanical installation 3 Electrical installation 4 Technical
More informationExternal Assessment Specifications Document Curriculum. NQF Qualification Title Code
External Assessment Specifications Document Curriculum NQF Qualification Title Code Level 671101000 Occupational Certificate: Electrician 4 Name E-mail Phone Logo National Assessment Artisan Quality Moderation
More informationOwner s Manual. Isolate. Restore. Inspire! Power Conditioners Audio / Video Power Isolation Units Rack Mount / Consumer Series
Owner s Manual 19 Pro Series Rack Mount (RK) Faceplate Isolate. 17 Consumer Series (C) Faceplate Available in Black (B) and Silver (S) Colours Restore. Power Conditioners Audio / Video Power Isolation
More informationPoint-of-Use Surge Protection
Point-of-Use Surge Protection Point-of-use surge protection consists of a power strip with surge protection circuitry incorporated. Point-of-use surge protection should be used anywhere expensive and sensitive
More informationDS-1H05 Ethernet-over-Coax Extender. User Manual
DS-1H05 Ethernet-over-Coax Extender User Manual Thank you for purchasing our product. If there is any question or request, please do not hesitate to contact dealer. This manual is applicable to DS-1H05-T,
More informationLightning and surge protection for wind turbines
916 Lightning and surge protection for wind turbines Due to their exposed location and height, wind turbines are vulnerable to the effects of direct lightning strikes. Several studies have shown that at
More informationModel 2657A-LIM-3 LO Interconnect Module
Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 2657A-LIM-3 LO Interconnect Module User's Guide Description The Model 2657A-LIM-3 LO Interconnect
More informationPRO2DM DIN rail single phase two wire energy meter
PRO2DM DIN rail single phase two wire energy meter User manual Version 1.04 1 Safety instructions...3 2 Foreword...4 3 CE Certificate...5 4 Performance criteria...6 5 Specifications...6 6 Basic errors...6
More information