Operating Manual. Micro-Ohmmeter VG-CS200 VG-CS300 VG-CS400 VG-CS600

Size: px
Start display at page:

Download "Operating Manual. Micro-Ohmmeter VG-CS200 VG-CS300 VG-CS400 VG-CS600"

Transcription

1 Operating Manual Micro-Ohmmeter VG-CS200 VG-CS300 VG-CS400 VG-CS600

2 Warranty Mostec AG warrants this product to be free of manufacturing defects for a 2-year period after the original date of purchase. Within this period, defective products will be repaired free of charge provided that the defect occurred during normal operation. This warranty does not cover damage to the product resulting from ordinary usage such as front panel scratches, broken control elements and corrosion, etc. The customer is responsible for shipping and packing charges for products returned under warranty to Mostec AG. Transportation damages are not covered by the warranty and should be referred to the respective delivery service. Technical description The micro-ohmmeters VG-CS200/300/400 and VG-CS600 are used for ohmic measurements of high power switches etc. All instruments are identical, except the maximal measuring current. The strengths of the instruments are the easy handling, rugged design and low weight. The two different kinds of displays, red LED`s and back lighted LCD, enables measurements in darkness, coldness and full sunlight. Designed for continuous measurements, the instrument has no limitation for the numbers of current cycles. An internal thermal printer is standard to enable logging of test results. With the option remote logging all stored measuring values can be downloaded to a personal computer or laptop. A cable remote control is optionally available. The VG-CS200, with a weight of 8kg only, makes it very handy and easy transportable and the rugged case contains all test cables. Typical applications are ohmic tests of: - Circuit breakers - Disconnecting switches - High current busbar joints - Cable splices - Welding joints - Ground connections Page 2

3 Index: Page 1 Safety regulations 4 2 Operating instructions 4 3 Control panel 5 4 Power ON 6 5 Main menu 6 6 System menu 6 7 System menu, description 7 8 System menu, flow chart 8 9 Result window 9 10 Start/Stop the measurement 9 11 LED display 9 12 Printer 9 13 Error messages 9 14 Instrument temperature monitoring Application example - one side grounded Application example - both sides grounded Verify measuring current Technical data Notes Page 3

4 1. Safety Regulations Always comply with local safety regulations when using the Micro-Ohmmeter. Always connect protective earth (ground). Read and comply with the safety regulations in this manual before using Micro-Ohmmeter. Never open a breaker as long as the Micro-Ohmmeter is connected. High voltage/currents can occur at the input/output clamps. The connection joints of the high current cables may become hot during a test. 2. Operating Instructions 1. Keep the Micro-Ohmmeter disconnected from the mains while making connections. 2. Ground one side of the test object. 3. Ground the Micro-Ohmmeter. 4. Connect the current cables to the test object. 5. Connect the two sense cables as close as possible to the test object. 6. Connect the Micro-Ohmmeter to the mains and switch it ON. 7. The Micro-Ohmmeter powers up and shows the startup text on the display and on the printer. 8. Select the desired measuring current with the "ADJUST" keys [+] and [-] or use a preset current with the keys [F1] or [F2]. 9. Start the measurement with [Start/Stop]. To change the instrument settings, see menu flow chart page Page 4

5 3. Control Panel 01. LCD display 02. Keys to control the menu functions 03. LED display indicating the value R and I 04. Increment/decrement keys for menus and values 05. Status LED s indicating the actual measuring status 06. Error LED when the adjusted current could not be reached 07. Start/Stop keys with status LED 08. Temp. Sensor RS232/V24 for PT USB Interface for communication to PC 10. Remote control connector 11. Mains plug 12. Main switch 13. Ground terminal 14. Raw signal shunt voltage terminals 15. Printer 16. DC - current output 17. DC+ current output 18. Clamp sense input 19. Sense terminals 20. Case screws Warning: Opening the instrument case voids the warranty Page 5

6 4. Power ON After power up the display shows the welcome message for 3 seconds. After that, the display shows the main menu. 5. Main Menu Iset = Menu = The previously set measuring current. By using the [+] and [-] keys, located below the red displays, the measuring current can be changed. Pressing [Ent], the user enters the system menu. Further explanations see below. Reslt = Pressing [Esc], the user enters the window with the measuring results. 50A = 100A = 6. System Menu Fast preselected value 1 of the measuring current. By pressing [F1], the measuring current Iset is changed to 50A. This value can be changed in the system menu. Fast preselected value 1 of the measuring current. By pressing [F2], the measuring current Iset is changed to 100A. This value can be changed in the system menu. Pressing [Ent] in the main menu leads to the system menu. In this menu, the user can navigate between the items by [F1] and [F2]. [Ent] selects the actual indicated item. The data of the selected item can be modified using the keys [+] and [-]. To store the modified data and leave the selected menu item, use the [Ent]. Press [Esc] to leave without storing the data Page 6

7 7. System Menu, Description Menu item: Legend: range of values: SM 0 Continuous Mde= On/Off The measuring current flows continuously until it's interrupted by the user. Selection only possible for 200A instruments! Normal = the measuring current only flows for a fixed given time. SM 1 Current= 5A to 200A (600A) Preset current 1. The adjusted value appears in the main menu above [F1]. SM 2 Current= 5A to 200A (600A) Preset current 2. The adjusted value appears in the main menu above [F2]. SM 3 Buzzer= On/Off Key click and audio warning during the measurement and error message. SM 4 24/12h Format= On/Off Time format 12.00am = ON SM 5 Hours= 0 12 / 0 23 Hours adjust of the internal clock. SM 6 Minutes= 0 59 Minutes adjust of the internal clock. SM 7 DDMMYY/MMDDYY Format= On/Off Date format month/day/year = ON SM 8 Year= Year adjust of the internal calendar. SM 9 Month= On/Off Month adjust of the internal calendar. SM 10 Day= 0 31 Day adjust of the internal calendar. SM 11 Erase measurement Y/N Erase all saved measurements. SM 12 Counter Printouts= Incremental counter for the printout. The printouts are incrementally numbered and it starts with the number set by SM11. SM 13 Printout all values= On/Off When On, ramp times will additionally be printed. SM 14 Current Clamp= On/Off The instrument calculates the current which can be bypassed through the grounding connections. This value is subtracted from the measuring current which flows through the equipment under test. When this item is ON, the instrument immediately asks for the external clamp sensitivity in mv/a Page 7

8 Menu item: Legend: range of values: SM 15 Temp. Compensation On/Off When this item is ON, the instrument immediately asks for the temperature coefficient (α). SM 16 Language English The user can switch the language. Deutsch Español Swenska Française 8. System Menu, Flow Chart Main Menu 9:37 Iset= 50A Menu Reslt 150A 200A Press F1 Iset=150A Press F2 Iset=200A Adjust in SM1/SM2 Setup Menu SM 0 Continuos/Normal Setup Menu SM 1 Preset Current 1 Setup Menu SM 2 Preset Current 2 Setup Menu SM 3 Buzzer 13: No: uΩ 150A Setup Menu SM 4 Time Format print exit < > Setup Menu Prints the indicated results on the internal printer Setup Menu SM 5 Hours Setup Menu SM 6 Minutes Setup Menu SM 7 Date Format To modify values in the setup menu press the ENT key and change the value or the state with the ADJUST keys. Then press ENT to save the changes or ESC to disregard it. Setup Menu SM 8 Year Setup Menu SM 9 Month Setup Menu SM10 Day Setup Menu SM16 Language Setup Menu SM11 Erase measurements Setup Menu SM15 Temp. Compensation Setup Menu SM12 Counter Printouts Setup Menu SM14 Current Clamp Setup Menu SM13 Printout all values Page 8

9 9. Result Window The result window can be activated by pressing the key below the text Reslt in the main menu. It will also be activated if a measurement has been completed. During continuous mode, the result window is continuously updated after a completed measuring cycle. The Micro- Ohmmeter stores the last 100 data sets. Line 1 = Time and date of the current test Line 2 = Storing location #16, ohmic value and test current Line 3 = When the external current clamp is activated, the clamp current. [Ent] Printing the data set [Esc] Back to the main menu [F1] Show/print the next result [F2] Show/print the previous result 10. Start/Stop Measurement The measurement is started by [Start/Stop]. This process is announced by the red blinking LED and, if activated, a pulsating audio alarm (Buzzer). The measurement can be aborted by [Start/Stop] or [ESC]. 11. LED Displays The two red LED displays are for better readability in darkness. The instrument indicates the result twice, on the LCD and the LED display. The upper LED display shows the value for resistance "R" and the lower LED the value for actual measuring current "I". During the current adjustment, the red LED display indicates Iset. 12. Printer The printer is maintenance free and the paper can be easily changed. The button above the paper output is for manual paper feed. The green LED lamp indicates "printer ready". 13. Error Messages The Micro-Ohmmeter can detect and display different errors. Fault Cause Remedy Sense line broken Sense line defective or broken Verify the sense line connections Overflow Resistance > 999.9mΩ Bad connection and/or too large resistance Measuring current 1. Instrument overheated 1. Cool down the instrument value not reached 2. Resistance > 999.9mΩ 2. Bad connection or too large resistance Page 9

10 14. Instrument Temperature Monitoring The Mirco-Ohmmeter has a temperature surveillance controller. At >40 C internal temperature, the LCD display shows the inside temperature, right, on the first line. At >50 C it derates the test current. At >70 C the measuring current is set zero. For more cycles, wait until the internal temperature decreases. internal temperature Page 10

11 15. Application Example - one side grounded Comply to the safety regulations and operation instructions when using the Micro- Ohmmeter. See page 4 Important: The sensing cables must be connected inside the current cables. Otherwise the test data may be incorrect Note: If you are measuring resistance in a breaker or disconnecting switch (isola tor), make sure that it is closed before starting. High current must only flow throughout a short interval. 1. Make certain the mains are de-energized on both sides of the breaker. Ground the breaker on one side and make certain it is closed. 2. Keep the Micro-Ohmmeter disconnected from the mains while making connections. 3. Ground the Micro-Ohmmeter. 4. Connect one current cable between one side of the object being tested and the DC+ terminal on Micro-Ohmmeter. Connect the other current cable between the other side of the object being tested and the COM terminal on Micro-Ohmmeter. 5. Connect the two sensing cables (using the same polarities as those used for the current cables) on two sides of the test object and as close to the test object as possible. 6. Connect the Micro-Ohmmeter to the mains. 7. Switch on the Micro-Ohmmeter. 8. Set the test current using the keys <+> and <-> or use one of the preselected currents using the <F1> or <F2> key. Note: If you are using the instrument the first time, make sure that the continuous mode (Setup Menu SM0, see page 7) is not selected. Also verify that the current clamp is switched off (Setup Menu SM14, see page 7). 9. Press the <START/STOP> key. The measurement is announced by a red blinking LED, green Status LED s and if activated a pulsating audio alarm (Buzzer). The result is shown after some seconds. The result is saved, you can make a printout and/or run a new test. 10. You can stop the measurement by pressing <START/STOP> or <ESC> keys. 11. Turn off and disconnect the Micro-Ohmmeter from the mains before doing any disconnection work or moving any cables or wiring Page 11

12 16. Application Example - both sides grounded Comply to the safety regulations and operation instructions when using the Micro- Ohmmeter. See page 4 Important: The sensing cables must be connected inside the current cables. Otherwise the test data may be incorrect Note: If you are measuring resistance in a breaker or disconnecting switch (isola tor), make sure that it is closed before starting. High current must only flow throughout a short interval. 1. Make certain the mains are de-energized on both sides of the breaker. Ground the circuit breaker on both sides and make certain it is closed. 2. Keep Micro-Ohmmeter disconnected from the mains while making connections. 3. Ground Micro-Ohmmeter 4. Connect one current cable between one side of the object being tested and the DC+ terminal on Micro-Ohmmeter. Connect the other current cable between the other side of the object being tested and the COM terminal on Micro-Ohmmeter. 5. Connect the two sensing cables on two sides of the test object and as close to the test object as possible. 6. Connect the external current clamp to one of the ground bars of the breaker and the clamp outputs to the CT INPUT on Micro-Ohmmeter. 7. Connect Micro-Ohmmeter to the mains. 8. Switch on Micro-Ohmmeter. 9. Set the test current using the keys <+> and <-> or use one of the preselected currents using the <F1> or <F2> key. Note: If you are using the instrument the first time, make sure that the continuous mode (Setup Menu SM0, see page 7) is not selected. 10. In the "Setup Menu", "SM14" (see page 7) switch on the current clamp and key in the proper sensitivity of the current clamp you are using. Confirm by pressing <ENT>. 11. Press the <START/STOP> key. 12. You can stop the measurement by pressing <START/STOP> or <ESC> keys. 13. If the current through the ground bar was too high compared to the current through the breaker, adjust the test current and start the measurement again. Repeat this step, until the current through the breaker meets your requirements. 14. Turn off and disconnect the Micro-Ohmmeter from the mains before doing any disconnection work or moving any cables or wiring Page 12

13 17. Verify measuring current Comply to the safety regulations and operation instructions when using the Micro- Ohmmeter. See page 4 1. Connect mv-meter to the shunt output 2. Calculate the measuring current: For Example: VG-CS200 Shunt voltage = 300uV/A For Example: VG-CS600 Shunt voltage = 100uV/A Measuring mv Measuring Current = Shunt voltage uv/a Page 13

14 18. Technical Data Page 14

15 19. Notes Page 15

16 Page 16

Operating Manual. Micro-Ohmmeter VG - CS200 VG - CS300 VG - CS400 VG - CS600

Operating Manual. Micro-Ohmmeter VG - CS200 VG - CS300 VG - CS400 VG - CS600 Operating Manual Micro-Ohmmeter VG - CS200 VG - CS300 VG - CS400 VG - CS600 Warranty Mostec AG warrants this product to be free of manufacturing defects for a 2-year period after the original date of purchase.

More information

VAREG. Micro-Ohmmeter VG-CS Technical description

VAREG. Micro-Ohmmeter VG-CS Technical description Mostec AG Mess- und Regeltechnik Lausenerstrasse 13a CH-4410 Liestal, Switzerland Tel. + 41 61 921 40 90 Fax + 41 61 921 40 83 Internet www.mostec.ch E-Mail info@mostec.ch 200A unlimited continuous mode

More information

VAREG. Micro-Ohmmeter VG-CSx00-II. Technical description

VAREG. Micro-Ohmmeter VG-CSx00-II. Technical description Mostec AG Mess- und Regeltechnik Lausenerstrasse 13a CH-4410 Liestal, Switzerland Tel. + 41 61 921 40 90 Fax + 41 61 921 40 83 Internet www.mostec.ch E-Mail info@mostec.ch Unlimited continuous mode Measures

More information

Micro-Ohmmeter VG-CSx00-II

Micro-Ohmmeter VG-CSx00-II Unlimited continuous mode Measures with both sides grounded Comfort push/pull connections Ext. Pt-100 temperature comp. Remote control Thermal printer USB PC-Interface USB stick (data logger) 4.3" LCD

More information

MJÖLNER 200 Micro-ohmmeter

MJÖLNER 200 Micro-ohmmeter Fully automatic testing Micro processor controlled Safe test DualGround and Remote control True DC ripple free current Lightweight suitcase withstands the impact of water, dust or sand Built in thermal

More information

Micro-Ohmmeter Model 6292

Micro-Ohmmeter Model 6292 Micro-Ohmmeter Model 6292 Quick Start Guide ENGLISH www.aemc.com CHAUVIN ARNOUX GROUP Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated

More information

Micro-Ohmmeter. Digital 200A. Model Measure low resistance with high accuracy

Micro-Ohmmeter. Digital 200A. Model Measure low resistance with high accuracy Digital 200A Micro-Ohmmeter Model 6290 Measure low resistance with high accuracy Accurately measures low contact resistances with test currents up to 200A Measures resistances from 0 to 20mΩ Resolution

More information

Micro Ohmmeter RMO200G

Micro Ohmmeter RMO200G Micro Ohmmeter RMO200G Lightweight only 8 kg Powerful 5 A 200 A DC Measuring range 0 999,9 mω Resolution to 0,1 µω Typical accuracy 0,1 % Remote Control Unit (optional) Both Sides Grounded Unit (optional)

More information

Handheld Micro Ohmmeters RMO-H series

Handheld Micro Ohmmeters RMO-H series Handheld Micro Ohmmeters RMO-H series Handheld only 0,95 kg / 2.1 lbs Powerful regulated current up to 300 A DC Automatic test current ramp Operated by high-capacity battery Measuring range 0,1 μω 2000

More information

200A MICRO-OHMMETER ENGLISH. User Manual

200A MICRO-OHMMETER ENGLISH. User Manual 200A MICRO-OHMMETER 6290 ENGLISH User Manual Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated using standards and instruments traceable

More information

Micro-Ohmmeter. Digital 200A. Model Measure low resistance with high accuracy

Micro-Ohmmeter. Digital 200A. Model Measure low resistance with high accuracy Digital 200A Micro-Ohmmeter Model 6290 Measure low resistance with high accuracy Accurately measures low contact resistances with test currents up to 200A Measures resistances up to 20mΩ Low resolution

More information

Micro-Ohmmeters. Digital 10A. Models 6240 & Measure low resistance with high accuracy. Selectable test current and resistance ranges

Micro-Ohmmeters. Digital 10A. Models 6240 & Measure low resistance with high accuracy. Selectable test current and resistance ranges Digital 10A Micro-Ohmmeters Models 6240 & 6250 Measure low resistance with high accuracy Selectable test current and resistance ranges 0.1µΩ resolution Simple one button press-to-start operation Software

More information

Programmable temperature transducer from Pt1000 sensor to current loop 4-20 ma Instruction Manual

Programmable temperature transducer from Pt1000 sensor to current loop 4-20 ma Instruction Manual T4111 TRANSDUCER Programmable temperature transducer from Pt1000 sensor to current loop 4-20 ma Instruction Manual Instruction manual for use of T4111 transducer Transducer is designed for temperature

More information

MJÖLNER 600 Microhmmeter

MJÖLNER 600 Microhmmeter Microhmmeter A Megger Group Company Microhmmeter The MJÖLNER 600 is designed to measure the resistance of circuit breaker contacts, bus-bar joints, contact elements in bus-bars and other high-current links.

More information

SGT-600 SAFETY GROUND TESTER

SGT-600 SAFETY GROUND TESTER SGT-600 SAFETY GROUND TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 April 2015 Revision 1.0 SAFETY

More information

10A Micro-Ohmmeter Model 6240

10A Micro-Ohmmeter Model 6240 10A Micro-Ohmmeter Model 6240 Selectable test current and resistance ranges 0.25% accuracy and 1µΩ resolution Simple one button press-to-start operation Software temperature correction for accurate measurements

More information

User's Guide. Model High Precision Quad Output DC Power Supply

User's Guide. Model High Precision Quad Output DC Power Supply User's Guide Model 382270 High Precision Quad Output DC Power Supply Introduction Congratulations on your purchase of the Extech 382270 DC Power Supply. The Model 382270 can be used for many applications

More information

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE PTC-20 PELTIER TEMPERATURE CONTROL SYSTEM

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE PTC-20 PELTIER TEMPERATURE CONTROL SYSTEM OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE PTC-20 PELTIER TEMPERATURE CONTROL SYSTEM VERSION 2.11 npi 2002 npi electronic GmbH, Hauptstrasse 96, D-71732 Tamm, Germany Phone +49 (0)7141-601534;

More information

User Manual Digi-Sense 12-Channel Benchtop Data Logging Thermocouple Thermometer

User Manual Digi-Sense 12-Channel Benchtop Data Logging Thermocouple Thermometer User Manual Digi-Sense 12-Channel Benchtop Data Logging Thermocouple Thermometer Model: 92000-01 THE STANDARD IN PRECISION MEASUREMENT Table of Contents Introduction... 3 Unpacking... 3 Initial Setup...3

More information

LCI User Manual mantracourt.com

LCI User Manual mantracourt.com LCI User Manual mantracourt.com LCI Load Cell Junction Box with Fault Monitor Contents Chapter 1 Introduction to the LCI... 2 Chapter 2 Installing the LCI... 3 Chapter 3 Setting up the LCI... 4 Sequence

More information

Micro-Ohmmeters. Digital 10A. Models 6240 & Measure low resistance with high accuracy. Technical Hotline: (800)

Micro-Ohmmeters. Digital 10A. Models 6240 & Measure low resistance with high accuracy. Technical Hotline: (800) Digital 10A Micro-Ohmmeters Models 6240 & 6250 Measure low resistance with high accuracy Selectable test current and resistance ranges 0.1µΩ resolution Simple one button press-to-start operation Software

More information

CT-8000 S3 digital circuit breaker analyzer

CT-8000 S3 digital circuit breaker analyzer CT-8000 S3 digital circuit breaker analyzer Vanguard Instruments Company, Inc. www.vanguard-instruments.com CT-8000 S3 digital circuit breaker analyzer Product Overview The CT-8000 S3 is Vanguard's fourth

More information

IRM-5000P. insulation resistance meter. Vanguard Instruments Company, Inc.

IRM-5000P. insulation resistance meter. Vanguard Instruments Company, Inc. IRM-5000P insulation resistance meter Vanguard Instruments Company, Inc. www.vanguard-instruments.com IRM-5000P insulation resistance meter The IRM-5000P is a microprocessor-based, high-voltage, insulation-test

More information

EZCT-2KA. current transformer test set

EZCT-2KA. current transformer test set EZCT-2KA current transformer test set EZCT-2KA current transformer test set Product Overview The EZCT-2KA is Vanguard s third-generation microprocessor-based current transformer test set. The EZCT-2KA

More information

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN

Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Installation and Operation Back-UPS BR1000G-IN / BR1500G-IN Important Safety Information Read the instructions carefully to become familiar with the equipment before trying to install, operate, service

More information

Tri-Phase. true 3-phase transformer turns ratio tester

Tri-Phase. true 3-phase transformer turns ratio tester Tri-Phase true 3-phase transformer turns ratio tester Tri-Phase true 3-phase transformer turns ratio tester Product Overview The Tri-Phase can be used as a stand-alone unit or can be computer-controlled.

More information

Datalogging Hot Wire CFM Anemometer

Datalogging Hot Wire CFM Anemometer Datalogging Hot Wire CFM Anemometer 840002 Instruction Manual SPER SCIENTIFIC LTD. TABLE OF CONTENTS 1. INTRODUCTION... 3 2. PANEL DESCRIPTION... 4-5 3. MEASURING PROCEDURE... 5 3-A Air Velocity and Ambient

More information

QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE

QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE QUALITY POWER SOLUTIONS BACKED UP BY REAL-WORLD ENGINEERING EXPERIENCE User s Manual SR250HL Power Supply/ Float Charger for Lead Acid Batteries STANDARD FEATURES OPTIONAL FEATURES 3 Relay Alarms-Form

More information

OX 5022-CK OX 5042-CK

OX 5022-CK OX 5042-CK QUICK START USER GUIDE OX 5022-CK OX 5042-CK Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated using standards and instruments traceable

More information

RST INSTRUMENTS LTD.

RST INSTRUMENTS LTD. Carlson/RST MA-7 Readout Instruction Manual 1 RST INSTRUMENTS LTD. Carlson/RST MA-7 Readout Instruction Manual Ltd. 11545 Kingston St Maple Ridge, BC Canada V2X 0Z5 Tel: (604) 540-1100 Fax: (604) 540-1005

More information

CT-8000 S3. digital circuit breaker analyzer

CT-8000 S3. digital circuit breaker analyzer CT-8000 S3 digital circuit breaker analyzer CT-8000 S3 digital circuit breaker analyzer Product Overview The CT-8000 S3 is Vanguard's fourth generation EHV circuit breaker analyzer. The CT-8000 S3 is available

More information

Operation Manual Series W-500

Operation Manual Series W-500 Operation Manual Series W-500 Table of Content 1 Safety information... 2 1.1 Place of application of the unit... 2 1.2 Instructions for installation... 3 2 Start-up and adjustment of controller 4 3 General

More information

INSTRUCTION MANUAL FOR THE MC-01 CONTROL UNIT

INSTRUCTION MANUAL FOR THE MC-01 CONTROL UNIT 1 INSTRUCTION MANUAL FOR THE MC-01 CONTROL UNIT TABLE OF CONTENTS 1 INSTALLATION... 2 1.1 Mounting... 2 1.2 Mains Connection... 2 1.3 Relay Connection... 3 1.4 Pulse Input Connection... 3 1.5 4-20 ma Output

More information

Back-UPS RS 550 Installation & Operation

Back-UPS RS 550 Installation & Operation Back-UPS RS 550 Installation & Operation Inventory Safety Do not install the UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. bu001a Do not connect a laser printer or hair

More information

Auto-Ohm 200 S3 / DMOM-200 S3 / DMOM-600 True DC Digital Micro-Ohmmeters

Auto-Ohm 200 S3 / DMOM-200 S3 / DMOM-600 True DC Digital Micro-Ohmmeters Auto-Ohm 200 S3 / DMOM-200 S3 / DMOM-600 True DC Digital Micro-Ohmmeters USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909)

More information

True RMS AC Voltage/Current Datalogger

True RMS AC Voltage/Current Datalogger User's Guide True RMS AC Voltage/Current Datalogger Model DL150 Introduction Congratulations on your purchase of this Voltage or Current datalogger. With this meter, you can monitor and log data over long

More information

This document set is applicable to the following part number configurations:

This document set is applicable to the following part number configurations: This document set is applicable to the following part number configurations: Part Number Kit Configuration Instrument Sensors VA200 VA200 - VA200K VA200 1 X A200-HAS Voltmeter and ammeter systems VA200X

More information

Integrating Sound Level Datalogger Model

Integrating Sound Level Datalogger Model User's Guide Integrating Sound Level Datalogger Model 407780 Introduction Congratulations on your purchase of the Extech 407780 Integrating Sound Level Meter. The 407780 with programmable integrating time

More information

Datalogging Conductivity/ TDS Meter. Instruction Manual

Datalogging Conductivity/ TDS Meter. Instruction Manual Datalogging Conductivity/ TDS Meter 850039 Instruction Manual 1 TABLE OF CONTENTS 1. INTRODUCTION...3 2. PANEL DESCRIPTION...4 3. MEASURING PROCEDURE...5 3-A General Measurement...5 3-B Auto and Manual

More information

INSTRUCTION MANUAL. Model True RMS AC/DC 30A Mini Clamp-on Meter. Introduction. True RMS AC Current and Voltage

INSTRUCTION MANUAL. Model True RMS AC/DC 30A Mini Clamp-on Meter. Introduction. True RMS AC Current and Voltage INSTRUCTION MANUAL Model 380942 True RMS AC/DC 30A Mini Clamp-on Meter True RMS AC Current and Voltage Measure low current with high resolution to 0.1mA AC and 1mA DC Auto Power Off One touch DCA zero

More information

This document set is applicable to the following part number configurations:

This document set is applicable to the following part number configurations: This document set is applicable to the following part number configurations: Part Number Kit Configuration Instrument Sensors VA200 VA200 - VA200K VA200 1 X A200-HAS Voltmeter and ammeter systems VA200X

More information

TRF-250A. automatic, 3-phase transformer turns ratio finder

TRF-250A. automatic, 3-phase transformer turns ratio finder TRF-250A automatic, 3-phase transformer turns ratio finder TRF-250A 3-phase transformer turns ratio finder Product Overview The TRF-250A is the battery-powered version of the TRF- 250. Its battery offers

More information

Energy Management System. Operation and Installation Manual

Energy Management System. Operation and Installation Manual Energy Management System Operation and Installation Manual AA Portable Power Corp 825 S 19 TH Street, Richmond, CA 94804 www.batteryspace.com Table of Contents 1 Introduction 3 2. Packing List 5 3. Specifications

More information

Pulsar EXtreme 2000/3000 VA

Pulsar EXtreme 2000/3000 VA www.mgeups.com MGE UPS SYSTEMS Pulsar EXtreme 2000/3000 VA Installation and user manual P O W E R P R O V I D E R L E I B E R R U P T N T N I E U T H 51033211EN/AC - Page 1 Introduction Thank you for selecting

More information

Installation and Operation Back-UPS Pro BR700G-TW

Installation and Operation Back-UPS Pro BR700G-TW Installation and Operation Back-UPS Pro BR700G-TW Inventory Safety Do not install the UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Do not connect a laser printer or hair

More information

TRF-250. automatic, 3-phase transformer turns ratio finder

TRF-250. automatic, 3-phase transformer turns ratio finder TRF-250 automatic, 3-phase transformer turns ratio finder TRF-250 3-phase transformer turns ratio finder Product Overview The 250V Test Voltage Advantage The TRF-250 is Vanguard s fourth generation transformer

More information

ATD-5493 Wireless Battery System Tester

ATD-5493 Wireless Battery System Tester ATD-5493 Wireless Battery System Tester For Testing 6V & 12V Vehicle Batteries individually & in Battery Packs. Also for testing 6V, 12V, 24V and 36V Charging & Starter Systems User Manual Remote Battery

More information

TRF-250. automatic, 250V, 3-phase transformer ratio finder. Vanguard Instruments Company, Inc.

TRF-250. automatic, 250V, 3-phase transformer ratio finder. Vanguard Instruments Company, Inc. TRF-250 automatic, 250V, 3-phase transformer ratio finder Vanguard Instruments Company, Inc. www.vanguard-instruments.com TRF-250 automatic, 3-phase transformer ratio finder The TRF-250 is Vanguard's fourth

More information

User's Guide. MiniTec TM Series Model MN25 MultiMeter

User's Guide. MiniTec TM Series Model MN25 MultiMeter User's Guide MiniTec TM Series Model MN25 MultiMeter Warranty EXTECH INSTRUMENTS CORPORATION warrants this instrument to be free of defects in parts and workmanship for one year from date of shipment (a

More information

Installation and Operation Manual Back-UPS BR900G-RS

Installation and Operation Manual Back-UPS BR900G-RS Installation and Operation Manual Back-UPS BR900G-RS Inventory Safety bu001a This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with fluids, or where there

More information

Visit to download the software Digalox Manager. Package contents: Panel meter Digalox DPM72, 5 jumpers, 1 mounting bracket

Visit   to download the software Digalox Manager. Package contents: Panel meter Digalox DPM72, 5 jumpers, 1 mounting bracket Digalox DPM72MPN Instruction manual (Rev201809) Visit www.digalox.com to download the software Digalox Manager. Package contents: Panel meter Digalox DPM72, 5 jumpers, 1 mounting bracket 1. Intended Use

More information

L300 user manual. Programmable DC Electronic Load CONTENTS. Electronic Load Software CAUTION...2 SAFETY NOTES...2

L300 user manual. Programmable DC Electronic Load CONTENTS. Electronic Load Software CAUTION...2 SAFETY NOTES...2 Programmable DC Electronic Load L300 user manual CONTENTS CAUTION......2 SAFETY NOTES......2 Chapter 1 General Introduction...3 1.1 General Introduction......3 1.2 Specification......3 1.3 Features......3

More information

Back-UPS RS APC Back-UPS RS 800VA 120V Black

Back-UPS RS APC Back-UPS RS 800VA 120V Black Back-UPS RS APC Back-UPS RS 800VA 120V Black APC Back-UPS RS, 540 Watts / 800 VA,Input 120V / Output 120V Includes: CD with software, Cord management straps, Free trial of anti-virus : firewall : email

More information

Circuit Breaker Analyzer & Timer CAT66

Circuit Breaker Analyzer & Timer CAT66 Safe and fast testing with BSG (Both Sides Grounded) Timing and motion measurement 6 timing channels (3x2) for main and resistive contacts 6 timing channels for auxiliary inputs 3 transducer input channels

More information

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704, EP GFK-2960B November 2017

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704, EP GFK-2960B November 2017 November 2017 Module Status LED Channel Status LEDs Digital Input Connector Ground 24 V DC FE Analog Input Module RSTI-EP Slice I/O Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3704,

More information

3700 SERIES USER MANUAL

3700 SERIES USER MANUAL SAFETY GUIDE This manual contains the precautions necessary to ensure your personal safety as well as for protection for the products and the connected equipment. These precautions are highlighted with

More information

Users Manual. Phenix Technologies Inc. MICRO-OHMMETER MODEL NUMBER MRM-100. Version 1.1

Users Manual. Phenix Technologies Inc. MICRO-OHMMETER MODEL NUMBER MRM-100. Version 1.1 Users Manual Phenix Technologies Inc. MICRO-OHMMETER MODEL NUMBER MRM-100 Version 1.1 DK/ELL/LEO/slu May, 2004 TABLE OF CONTENTS Section Number GENERAL SAFETY PRECAUTIONS PRODUCT INFORMATION 1 -SAFETY

More information

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter

Operation Manual MODEL 2TX. 2-wire Isolated ph/orp Transmitter Operation Manual MODEL 2TX 2-wire Isolated ph/orp Transmitter 0 2TX CONTENTS INITIAL INSPECTION.....2 INTRODUCTION......2 ASSEMBLY...3 PREPARATION....4 CONNECTING THE ELECTRODE...4 CONNECTING THE TEMPERATURE

More information

User Guide. Model Temperature Datalogger Kit Model Temperature and Humidity Datalogger Kit Model SW276 Datalogging Software SW276

User Guide. Model Temperature Datalogger Kit Model Temperature and Humidity Datalogger Kit Model SW276 Datalogging Software SW276 User Guide Model 42265 Temperature Datalogger Kit Model 42275 Temperature and Humidity Datalogger Kit Model SW276 Datalogging Software SW276 Introduction Congratulations on your purchase of Extech Instrument

More information

Operations Manual EcoSense ph100

Operations Manual EcoSense ph100 Operations Manual EcoSense ph100 Portable ph, mv and Temperature Instrument English Français Español Deutsch Italiano WARRANTY The EcoSense ph100 Instrument is warranted for one year from date of purchase

More information

Innovative Circuit Technology Ltd.

Innovative Circuit Technology Ltd. Innovative Circuit Technology Ltd. DC UPS Series 2 INSTRUCTION MANUAL 855-146-200 Models: ICT24012-15IBD ICT24012-15IBDM ICT24012-30IBDM WARNING Risk of serious personal injury or damage to equipment and

More information

Micro-Ohmmeter. Digital 200A. Model Measure low resistance with high accuracy. Technical Hotline: (800)

Micro-Ohmmeter. Digital 200A. Model Measure low resistance with high accuracy. Technical Hotline: (800) Digital 200A Micro-Ohmmeter Model 6290 Measure low resistance with high accuracy Accurately measures low contact resistances with test currents up to 200A Measures resistances from 0 to 20mΩ Resolution

More information

MICRO-OHMMETER ENGLISH. User Manual

MICRO-OHMMETER ENGLISH. User Manual n MICRO-OHMMETER ENGLISH User Manual 6292 Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated using standards and instruments traceable

More information

CONTENT Warning...1 I.Brief Introduction...3 II.Electrical Symbol...4 III.Series Model...4 IV. Technical Specifications...4 V.

CONTENT Warning...1 I.Brief Introduction...3 II.Electrical Symbol...4 III.Series Model...4 IV. Technical Specifications...4 V. CONTENT Warning...1 I.Brief Introduction...3 II.Electrical Symbol...4 III.Series Model...4 IV. Technical Specifications...4 V. Instrument Structure...6 VI. Instrument Operation...7 1 Turning on and off...7

More information

EZCT S2A current transformer test set

EZCT S2A current transformer test set EZCT S2A current transformer test set Vanguard Instruments Company, Inc. www.vanguard-instruments.com EZCT S2A current transformer test set Product Overview The EZCT S2A is Vanguard s third-generation,

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Simplify phase) and is annotated with the phase angle in degrees. The CT currentratio error and phase displacement is

More information

EZCT-2000C current transformer test set

EZCT-2000C current transformer test set EZCT-2000C current transformer test set Vanguard Instruments Company, Inc. www.vanguard-instruments.com EZCT-2000C current transformer test set Product Overview The EZCT-2000C is Vanguard s third-generation

More information

ATRT-03 S2. automatic, 3-phase transformer turns ratio tester

ATRT-03 S2. automatic, 3-phase transformer turns ratio tester ATRT-03 S2 automatic, 3-phase transformer turns ratio tester ATRT-03 S2 3-phase transformer turns ratio tester Product Overview The ATRT-03 S2 can be used as a standalone unit or can be computer-controlled.

More information

Circuit Breaker Analyzer & Timer CAT126

Circuit Breaker Analyzer & Timer CAT126 Safe and fast testing with BSG (Both Sides Grounded) Timing and motion measurement 12 timing channels (3x4) for main and resistive contacts 6 timing channels for auxiliary inputs 3 transducer input channels

More information

INSTRUCTION MANUAL. Model Dual Input RTD Thermometer. Measures two temperatures simultaneously. Dual RTD probe inputs

INSTRUCTION MANUAL. Model Dual Input RTD Thermometer. Measures two temperatures simultaneously. Dual RTD probe inputs INSTRUCTION MANUAL Model 421504 Dual Input RTD Thermometer Measures two temperatures simultaneously Dual RTD probe inputs Clock and Elapsed Timer functions Special functions include Data Hold, MIN/MAX/AVG,

More information

CT-7500 S2. Advanced Test Equipment Rentals ATEC (2832) digital circuit breaker analyzer

CT-7500 S2. Advanced Test Equipment Rentals ATEC (2832) digital circuit breaker analyzer Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CT-7500 S2 digital circuit breaker analyzer Vanguard Instruments Company, Inc. www.vanguard-instruments.com CT-7500

More information

Circuit Breaker Analyzer & Timer CAT126

Circuit Breaker Analyzer & Timer CAT126 Robust design for field use Timing and motion measurement 12 timing channels (3x4) for main and resistive contacts 6 timing channels for auxiliary inputs 3 transducer input channels 4 additional analog

More information

CT-6500 S2. digital circuit breaker analyzer. Vanguard Instruments Company, Inc.

CT-6500 S2. digital circuit breaker analyzer. Vanguard Instruments Company, Inc. CT-6500 S2 digital circuit breaker analyzer Vanguard Instruments Company, Inc. www.vanguard-instruments.com CT-6500 S2 digital circuit breaker analyzer The CT-6500 S2 is an inexpensive, easy to use, stand-alone,

More information

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10)

PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10) TEC (Peltier) Controller PLC-24V10AL(-PT/-TH) Quick Start Manual (Rev.1.10) Thank you for purchasing the TEC (Peltier) Controller PLC-24V10AL. Read these operating instructions carefully to ensure effective

More information

USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230

USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230 USER MANUAL VIBRATION CONTROL Version 2.2 1 IMPORTANT NOTES Electrical danger within the meaning of this documentation or the warning labels on the product itself respectively means that death, serious

More information

RS Stock No Instruction Manual RS Input Data Logging Thermometer

RS Stock No Instruction Manual RS Input Data Logging Thermometer RS Stock No. 730-0458 Instruction Manual RS-1384 4 Input Data Logging Thermometer EN FR IT DE ES TABLE OF CONTENTS / EN TITLE TABLE OF CONTENTS PAGE 1. INTRODUCTION FEATURE... 1 2. SPECIFICATIONS... 2

More information

High Precision Quad Output DC Power Supply

High Precision Quad Output DC Power Supply User's Guide High Precision Quad Output DC Power Supply Model 382270 Introduction Thank you for selecting the Extech Model 382270. This device is shipped fully tested and calibrated and, with proper use,

More information

PS-5030 (5A) OPERATION MANUAL

PS-5030 (5A) OPERATION MANUAL CIRCUIT-TEST Single Output Power Supplies 0-30 VDC @ 3A PS-3030 (3A) 0-30 VDC @ 5A PS-5030 (5A) OPERATION MANUAL Contents INTRODUCTION... page 2 OPERATING INSTRUCTIONS... 2 OPERATING CAUTIONS... 2 SPECIFICATIONS...

More information

Owner's Manual. True RMS Multimeter. Model No Safety Operation Maintenance Español

Owner's Manual. True RMS Multimeter. Model No Safety Operation Maintenance Español Owner's Manual True RMS Multimeter Model No. 82023 CAUTION: Read, understand and follow Safety Rules and Operating Instructions in this manual before using this product. Safety Operation Maintenance Español

More information

EZCT-2000C Plus. current transformer test set. Vanguard Instruments Company, Inc.

EZCT-2000C Plus. current transformer test set. Vanguard Instruments Company, Inc. EZCT-2000C Plus current transformer test set Vanguard Instruments Company, Inc. www.vanguard-instruments.com EZCT-2000C Plus current transformer test set The EZCT-2000C Plus is Vanguard s third-generation

More information

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description. Practical Instrument Electronics PIECAL 322 Automated Thermocouple Calibrator Operating Instructions Product Description Easy to use With the PIECAL 322-1 you can check & calibrate all your thermocouple instruments and measure thermocouple

More information

Manual. NanoTron Dual Timer. Installation Maintenance Repair Manual

Manual. NanoTron Dual Timer. Installation Maintenance Repair Manual Manual NanoTron Dual Timer Installation Maintenance Repair Manual Advantage Controls P.O. Box 1472 Muskogee, OK 74402 Phone: 800-743-7431 Fax: 888-686-6212 www.advantagecontrols.com email: support@advantagecontrols.com

More information

PS-1030 (30V) OPERATION MANUAL

PS-1030 (30V) OPERATION MANUAL CIRCUIT-TEST Single Output Power Supplies 0-30 VDC @ 10A PS-1030 (30V) OPERATION MANUAL Contents INTRODUCTION...page 2 OPERATING INSTRUCTIONS... 2 OPERATING CAUTIONS... 2 SPECIFICATIONS... 3 FRONT PANEL

More information

Micro-Ohmmeter Model 6290

Micro-Ohmmeter Model 6290 Digital 200A Micro-Ohmmeter Model 6290 Measure low resistance with high accuracy Our products are backed by over 100 years of experience in test and measurement equipment, and encompass the latest international

More information

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER

MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER MCCB-500 MOLDED-CASE CIRCUIT BREAKER TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 January 2015 Revision

More information

Installation and Operation Back-UPS Pro 900

Installation and Operation Back-UPS Pro 900 Us er Documentation Installation and Operation Back-UPS Pro 900 Inventory bu001a User Documentation (2) Safety and General Information Inspect the package contents upon receipt. Notify the carrier and

More information

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664, EP-3704, EP GFK-2960F September 2018

RSTI-EP Slice I/O. Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664, EP-3704, EP GFK-2960F September 2018 September 2018 Module Status LED Channel Status LEDs Digital Input Connector Ground 24 V DC FE Analog Input Module RSTI-EP Slice I/O Analog Input Modules `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468 EP-3664,

More information

7032 Digital-Analog Multimeter

7032 Digital-Analog Multimeter 7032 Digital-Analog Multimeter OPERATOR S MANUAL CONTENTS: 1. Safety precautions and procedures 1 1.1. Preliminary 1 1.2. During Use 2 1.3. After Use.. 2 2. General Description. 3 3. Preparation for Use..

More information

HI ma Simulator

HI ma Simulator Instruction Manual HI 931002 4-20 ma Simulator http://www.hannainst.com These Instruments are in Compliance with the CE Directives Dear Customer, Thank you for choosing a Hanna Instruments Product. Please

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

Installation Instructions

Installation Instructions Lucci Remote Fan Control Non Dimming SKU# 210019 Rated Voltage 240V~ 50Hz Thank you for purchasing this quality Lucci product. To ensure correct function and safety, please read and follow all instructions

More information

SOLARIMMERSION IV Advanced Installation Manual v1.9

SOLARIMMERSION IV Advanced Installation Manual v1.9 SOLARIMMERSION IV Advanced Installation Manual v1.9 1 Contents 1. Overview 2. Technical Specifications 3. Installation Mounting Electrical Installation Clamp Installation Wiring Diagrams 4. Installation

More information

Installation and Operation Back-UPS Pro 900

Installation and Operation Back-UPS Pro 900 software Us er Documentation Installation and Operation Back-UPS Pro 900 Inventory Connect the Battery bu001a User Documentation (2) Safety and General Information Inspect the package contents upon receipt.

More information

QUICK START USER GUIDE. Data Logger Model L452

QUICK START USER GUIDE. Data Logger Model L452 QUICK START USER GUIDE Data Logger Model L452 Statement of Compliance Chauvin Arnoux, Inc. d.b.a. AEMC Instruments certifies that this instrument has been calibrated using standards and instruments traceable

More information

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE TC-20 TEMPERATURE CONTROL SYSTEM

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE TC-20 TEMPERATURE CONTROL SYSTEM OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE TC-20 TEMPERATURE CONTROL SYSTEM VERSION 3.8 npi 2016 npi electronic GmbH, Bauhofring 16, D-71732 Tamm, Germany Phone +49 (0)7141-9730230; Fax: +49

More information

User's Guide. Programmable DC Power Supply 200 Watt (40 Volts / 5 Amps) Model Introduction

User's Guide. Programmable DC Power Supply 200 Watt (40 Volts / 5 Amps) Model Introduction User's Guide Programmable DC Power Supply 200 Watt (40 Volts / 5 Amps) Model 382280 382280 Introduction Congratulations on your purchase of the Extech 382280 Programmable DC Power Supply. This 200 watt

More information

Dual channel temperature logger with two voltage inputs 0-5V Instruction Manual

Dual channel temperature logger with two voltage inputs 0-5V Instruction Manual LOGGER S0541 Dual channel temperature logger with two voltage inputs 0-5V Instruction Manual Instruction Manual for use of S0541 logger Instrument is designed for measurement and record of temperature

More information

INSTRUCTION and OPERATIONS MANUAL. for

INSTRUCTION and OPERATIONS MANUAL. for INSTRUCTION and OPERATIONS MANUAL for CAB SIGNAL MASTER MODEL NUMBER 15100-00 CAUTION Be sure to read and become thoroughly familiar with the entire contents of this manual before attempting to operate

More information

ATRT-03B S2. automatic, 3-phase transformer turns ratio tester. Vanguard Instruments Company, Inc.

ATRT-03B S2. automatic, 3-phase transformer turns ratio tester. Vanguard Instruments Company, Inc. ATRT-03B S2 automatic, 3-phase transformer turns ratio tester Vanguard Instruments Company, Inc. www.vanguard-instruments.com ATRT-03B S2 automatic, 3-phase transformer turns ratio tester The ATRT-03B

More information

Broadband CTSP-EM48 Series. Total System Power Electronics Module. User Manual

Broadband CTSP-EM48 Series. Total System Power Electronics Module. User Manual Broadband CTSP-EM48 Series Total System Power Electronics Module User Manual 990-5500F 05/2005 Chapter 1 General Information The CTSP Electronics Module (CTSP-EM) is compatible with all CTSP Transformer

More information