V117. Instruction Manual. MDU12i. 12 port Intelligent Mains Distribution Unit HG

Size: px
Start display at page:

Download "V117. Instruction Manual. MDU12i. 12 port Intelligent Mains Distribution Unit HG"

Transcription

1 1 MDU12i HG

2 2 This page is inten onally blank

3 3 Contents 1.0 Description 2.0 Installation 3.0 Operation 4.0 Connections 5.0 Indication 6.0 Characteristics Appendix A Web server HTML page description Appendix B SNMP trap setup and register description Appendix C Telnet command line interface description

4 4 This page is intentionally blank

5 5 1.0 Description The Argosy Intelligent Mains Distribution Unit is a meter grade 12 outlet power distribution product housed within a 1U 19 sub-rack. The main function of the product is to distribute a single phase mains power supply to 12 socket outlets while monitoring voltage, current, power and energy usage to a meter grade accuracy of ± 1%. Additionally the product can monitor external environmental conditions, temperature or humidity, contact inputs, 0-5VDC analogue inputs and control voltage free contact outputs. The product is controlled remotely over an Ethernet network using the integrated web server, SNMP registers or Telnet command interface. The product provides the following features: Single phase 16A capable ± 1% accuracy metering. Monitoring of VRMS, IRMS, kw, kwh, Power factor, kva, kgco2, BTU/h, kj/h and frequency measurements. Ethernet port [IEEE with full 10/100Base-T network compatibility]. High-speed MODBUS RS485 port for local daisy-chaining of up to 31 imdu slaves. Temperature sensor bus [8x chained] + Humidity/Temperature sensor port. External GPIO contact monitoring inputs x8. External GPIO 0-5VDC analogue inputs x2. External GPIO voltage free N.O. 48VAC/DC relay output x2. 12 socket outlets with 16A N.O. switching and fuse blown monitoring. USB Type A port with 5VDC power output. Remote monitoring and configuration [HTML webserver, SNMP registers and Telnet command interface]. Physical layout The product is enclosed within a 1U 19 sub-rack with a mains inlet/outlet, illuminated front panel mounted isolator switch, 12x IEC outlets and main interface connectors on the rear panel and USB port, 12x fuses and power/fuse blown LED indication on the front panel. The product is made up of a Control PCB assembly which consists of a front panel removable processor and mains power supply PCB that plugs into (hot swappable) a fixed rear mounted meter and interface PCB.

6 6 This page is intentionally blank

7 7 2.0 Installation Installation should be performed by a suitably competent person. The MDU12i (imdu) is designed to be mounted in a 19 rack. The rear of the unit must be supported within the rack. The unit is supplied with an inlet connector for the user and wiring instructions. The unit has an earth stud at the rear of the unit and must be connected to earth. The unit ratings are shown at the rear of the unit. The unit must be protected by a suitably rated 16A MCB or fuse. The unit is supplied with 5 amp HRC fuses in each outlet fuse holder. The maximum rating for each outlet is 10 amps provided a suitably rated HRC fuse is fitted in the front panel mounted fuse holder. Make all connections before applying power to the unit and switching on. To ensure isolation, the illuminated front panel switch must be in the off position with the green light extinguished. Disconnect from the supply before making or changing connections to the IEC outlets or connected equipment. Control card The control card is designed to be hot swappable from the front panel as a security against system failure or future upgrade. The main parts of the system are located on this card eg. CPU, SMPS. Control card change Ensure the new card has the keep outlet status enabled option set (enquire with the factory if confirmation is required ) Undo the two hex head screws securing the card to the front panel and gently withdraw the card. Warning, at this point the outlets will remain live but the outlet status indication will be lost! The front panel mounted illuminated switch will remain lit at all times power is supplied to the unit. Do not leave the unit with the card removed and do not insert anything other than a control card into the aperture. Insert the new card into the aperture and card guides. Push home until the front plate is against the front panel. Fuse indication and all functions should reappear at this point. Replace the hex head screws and tighten.

8 8 This page is intentionally blank

9 9 3.0 Operation The imdu product is energised when supplied with AC power. On power application, and if configured to do so, the system will sequentially switch each socket outlet ON starting at socket 1 and ending at socket 12 at a pre-defined sequence period (default 0.5 seconds) illuminating the optical power indicator associated with each socket. Should a fuse be ruptured (blown) on any outlet the corresponding optical fuse blown indicator shall also illuminate. The system will continually collect data from the meter and store this for access via the Web server, SNMP registers, Telnet command interface or Modbus requests. MODBUS connection. The imdu product may be configured as a Master and connected to up to thirty-one other imdu s, via a 2 wire RS485 interface, that are configured as Slaves to allow the master imdu to collect measurements from the slaves. Ethernet connection The imdu product may be connected to a PC or laptop using a cross-over CAT5 Ethernet cable or to a router using a straight through CAT5 Ethernet cable. The GREEN LED on the Ethernet connection port indicates that the product is connected to a valid device, the YELLOW LED indicates data traffic to/from the unit.the product, as default, is configured for DHCP [Dynamic Host Configuration Protocol] which allows a connected Ethernet router to assign an IP address to the product for Ethernet communication. DHCP may be configured using the Network Configuration button within the Web server, see Appendix A Web server HTML page description for more information. Web server access The imdu product supports full HTTP access of the internal HTML web pages using any standard internet browser ie. Internet Explorer, Firefox, Google Chrome etc. Please see Appendix A Web server HTML page description for more information on accessing this service. SNMP register access The imdu product can be provided with a MIB [Management Information Base] for use with any SNMP manager. This MIB outlines all the accessible registers, there type and description. The file is called imdu_vxxx.mib. For more information please look at the MIB file. Please see Appendix B SNMP trap setup and register description for more information. Telnet command line access The imdu product supports a selectable Telnet command line interface that allows anexternal user to access system information and control socket status. See Appendix C Telnet command line interface description for more information.

10 10 This page is intentionally blank

11 11 Connections External connections (Rear panel) Ethernet Port - 8way RJ45 right-angle socket. GPIO port - 15way D type right-angle socket. MODBUS port - 2x 4way RJ11 right-angle socket.

12 12 Temperature sensor and humidity sensor port - 4way RJ11 right-angle socket. Mains outlets - 12x C14 IEC outlets. External connections (Front panel) USB port - 1x USB type A socket.

13 Indication External optical indication (rear panel) Ethernet connection indicator - GREEN L.E.D indicator, mounted on Ethernet port. Ethernet data indicator - YELLOW L.E.D indicator, mounted on Ethernet port. External optical indication (front panel) Front panel mounted switch with integral indicator. Green light is lit when switch is on and mains applied. Outlet power indicator - 12x GREEN 3mmD L.E.D indicator, located next to fuse. Fuse blown indicator - 12x RED 3mmD L.E.D indicator, located next to fuse.

14 14 This page is intentionally blank

15 Characteristics AC Characteristics Mains input 115/230VAC 50-60Hz Mains input protection Transient suppression (LIVE - NEUTRAL) Mains power consumption 15W Maximum load 16A DC Characteristics USB Supply output 1A max. USB Supply protection 1A Current limit Ethernet port Compatibility IEEE /100/1000Base-T (Auto-negotiated to 10 or 100Mb) Protocols TCP/IP, HTTP, SNMP, XML, DHCP, SMTP, Telnet MODBUS port Compatibility RS kbps, 8 data bits, no parity, 1 stop bit Protocol MODBUS RTU Digital temperature sensor [x8] Temperature range 0 to +125 C Accuracy (Temperature Error) 0 C to +85 C = ±0.5 C nominal 85 C to +125 C = ±1.0 C nominal Resolution C Sensor supply voltage 3.3VDC Sensor interface I2C 3.3V [TTL/CMOS] logic Humidity sensor [x1] Humidity range 0-100% Relative humidity Response Time 8 Seconds in slow moving 25ºC Stability < 0.5% RH per year Accuracy ± 2.0% RH, 0-100% RH 25ºC Non-linearity < 1% RH Typical Repeatability ± 0.1% RH Resolution 0.04 %RH Temperature range 0 to +125ºC (32 to F) Response Time 5 to 30 seconds Accuracy ±0.4 C nominal Repeatability ± 0.1 C Resolution 0.01 C Sensor supply voltage 3.3VDC Sensor interface I2C 3.3V [TTL/CMOS] logic

16 16 GPIO inputs Contact type Voltage free normally open or closed Contact resistance 2Kohm max. Contact de-bounce time 50mS GPIO analogue inputs Analogue input voltage 0-5V (6V max.) mV per bit Analogue measurement period 100mS GPIO control output 1 Output type Voltage free Solid State Relay (SSR) Output capability 1000mA max. GPIO control output 2 Output type Voltage free Mechanical Relay (SPDT) Output capability 1000mA max. General timings Temperature & humidity measurement rate 1000mS default (software programmable) General parameters Login name & password admin default (HTML programmable)

17 17 Appendix A. Web server HTML page description Web server HTML page description The imdu HTTP web server service provides a set of HTML pages that can be viewed within any HTML compatible web browser [ie. Internet Explorer, Firefox, Google Chrome etc.]. Logging into the web server The HTTP service provides Domain Name Service [DNS] resolution so that the imdu IP address does not need to be known, entering imdusnmp into the browsers URL bar will contact the web server and initiate the authentication process to allow entry into the imdu system. The following authentication screen will be displayed: At this point the operator may enter the system as a User, Administrator or Factory operator. The default User name and Password for the default administrator account is Admin, both are case sensitive. New accounts may be configured under the Configuration tab settings, see later in this appendix. User account A User account prevents access to the all configuration options and most other operations that could compromise imdu SNMP operation. Administrator account An Administrator account allows the operator to re-configure any aspect of the imdu configuration. This configuration includes re-naming of the imdu customer name, location, outlet equipment names and changes to default parameters. The Administrator also has access to buttons that allow the imdu to turn individual outlets ON/OFF and reset currently stored energy levels etc.

18 18 Factory account As the Administrator account but allows access to the config.htm page Overview page After successful authentication the operator is presented with the initial Overview page which provides an overview of all master and slave imdu units. The following screen shot shows a master only unit with an alarm condition: The imdu Information provides an overview of the customer and location to which the imdu belongs, its IP address, the mode of operation (NORMAL, MASTER or SLAVE) and the alarm status. Below this an overview of the master and connected slave units outlet status and meter current. Clicking on the arrow next to the status line takes the user to the Outlets page for this particular unit.

19 19 Environmental page Clicking on the Environmental button the operator is presented with the environmental status page for the currently selected master or slave which contains details of any humidity probe or temperature probes connected to the unit, the eight [8] contact inputs, the two [2] Analogue to Digital Converter (ADC) levels and the two [2] General Purpose Outputs (GPO) contact outputs. The following screen shot shows the top of the page with a humidity probe connected and contacts 1&2 OPEN: The humidity probe status box provides the temperature and humidity output from any connected humidity probe along with location name and check boxes and threshold levels to configure alarms against these parameters. Please see later topic for alarm setup. The temperature probe status box(s) provide the temperature output from up to eight temperature probes along with location name and check boxes and threshold levels to configure alarms against these parameters. Please see later topic for alarm setup. The contact status boxes provide the status (OPEN or CLOSED) of the contact inputs along with location name and check boxes to configure alarms. Please see later topic for alarm setup.

20 20 The following screen shot shows the bottom of the page showing the two ADC channels and the two GPO outputs: The ADC Input status boxes show the input voltage measured from the ADC a name and check boxes and threshold levels to configure alarms against these parameters. Please see later topic for alarm setup. The GPO Output status boxes provide the status (OPEN or CLOSED) of the contact outputs along with name and check boxes to configure alarms. Please see later topic for alarm setup.

21 21 Outlets page Clicking on the Outlets button the operator is presented with the outlets status page for the currently selected master or slave which displays status of the twelve [12] outlets on the system. The following screen shot shows the Master selected with outlet 1 OFF and a fuse blown alert on outlet 10: Each outlet has a status of ON, OFF or FUSE which are depicted as ORANGE, GREEN or RED respectively to allow at a glance determination of status. An outlet can be selected using the drop-down menu and its status box provide the status (ON, OFF or FUSE) of the outlet along with equipment name and check boxes to configure alarms. Please see later topic for alarm setup. A button is provided to switch the outlet ON or OFF, depending on its current status, unless a FUSE indication is shown.

22 22 Metering page Clicking on the Metering button the operator is presented with the metering page for the currently selected master or slave which contains measurements from the on-board meter. The following screen shot shows the unit connected to a 230VAC supply and no load: The imdu RMS volts, amps, kw s, frequency and power factor are shown along with check boxes and threshold levels to configure alarms against these parameters. Please see later topic for alarm setup. The Energy usage box provides the total energy usage on this imdu, including relevant conversions such as kgco2. Buttons on this page allow the alarm thresholds to be saved and the energy consumption to be reset if required.

23 23 Configuration page Clicking on the Configuration button the operator is presented with the Configuration page which contains configuration details for the unit. The following screen shot shows the System Information and Configuration box at the top of the page: The top half of the System Information and Configuration box shows the currently logged in operator level, USER, ADMINISTRATOR or FACTORY, current firmware version, the HTML page version, customer name and location. The bottom half of the System Information and Configuration box shows all the parameters that can be configured within the system. Outlet startup type allows Instant (all outlets turn ON together), Sequential (outlets turn ON from 1 to 12 with an Outlet sequential period between each) or Delay (outlets turn ON from 1 to 12 with an individual delay for each outlet, setup in the Outlet delay configuration box) to be configured. If an LCD panel is connected the LCD functions define its operation.

24 24 The second section of the page contains the imdu Mode Configuration, USER Configuration and Network Configuration boxes: The imdu Mode Configuration box allows the imdu mode to be configured (NORMAL-No MODBUS support, MASTER-MODBUS Slaves are queried and data collected and SLAVE-External master collects data from this imdu using the configured slave address). When configured for MASTER the Timeout (time to wait for a slave to respond) and Retries (Number of times the master retries a query) are configurable. When configured for SLAVE the MODBUS Slave Address must be configured to an exclusive address on the MODBUS network. The MODBUS Status box provides real-time information about MASTER mode queries or SLAVE mode requests being made on the MODBUS network. The User Configuration box allows a maximum of 20 users to be configured with one of 3 different user levels. USER level allows access to all pages, but 'Save Changes' buttons are disabled. ADMINISTRATOR level allows access to all pages and 'Save Changes' are enabled as well as upgrade functions. FACTORY level provides access to all pages and buttons as well as advanced configurations on the config.htm page.

25 25 The third section of the page contains the Network Configuration and Configuration boxes: The Network Configuration box allows the host name and DHCP configuration to be configured. When DHCP is disabled a static IP address, gateway and DNS addresses may be configured. Changes can be made to the fields by de-selecting the 'Enable DHCP' checkbox, updating the fields and clicking the 'Save Changes' button. The Configuration box allows the address and mail server to be configured for alarms. Enter the destination , from and the server information and click 'Save Changes' then 'Send Test ' button to test the configuration. The SSL checkbox allows SSL to be used for when set.

26 26 The fourth section of the page contains the SNMP Configuration, Telnet Configuration and Upgrade, default and reset boxes: The SNMP Configuration box allows the SNMP Read and Write communities to configured. Enter up to 3 communities for read and write or leave blank if unused and update by clicking 'Save Changes'. The Telnet Configuration box allows the Telnet authentication username and password to be configured. Enter username and password and update by clicking 'Save Changes'. Note that the Telnet functionality can only be enabled from the Advanced Configuration page config.htm. The Upgrade, default and reset box contains the followign functions: The imdu firmware can be upgraded by clicking on the Activate button and following the prompts. CAUTION: The imdu may be rendered inoperative if firmware update is unsuccessful. The imdu configuration can be reset to the factory defaults by clicking the Activate button. CAUTION: Current configuration data [name, alarm values etc.] will be lost. The imdu unit can be reset by clicking the Activate button.

27 27 Alarm setup and generation Individual pages allow various low, high and event alarms to be configured. To setup a low threshold alarm click on the Low Alarm checkbox and enter a threshold level at which an alarm should be generated if the reported value drops below i.e. for a temperature alarm enter 5.00 if you want an alarm to be generated if the temperature drops below 5.00C. To setup a high threshold alarm click on the High Alarm checkbox and enter a threshold level at which an alarm should be generated if the reported value rises above i.e. for a temperature alarmenter if you want an alarm to be generated if the temperature rises above 40.00C. Click on the 'Save Changes' button to update the alarm setting. Note: An alarm comparison is immediately undertaken on configuring a new alarm. The normal alarm check period of 1 to 240 minutes can be configured on the Configuration page. On every alarm check period timeout all configured alarm thresholds are compared with the currently report value and if found to be above or below the threshold an SNMP trap generated, see SNMP Trap Host Setup in Appendix B, and if the alarms enabled checkbox is selected on the Configuration page and alarm will also be generated to the configured address.

28 28 Advanced Configuration page (hidden) On entering the IP address followed by /config.htm in the top bar the operator, must be a factory level user, is presented with the Advanced Configuration page which contains advanced configuration details. The following screen shot shows the imdu Advanced Configuration and Meter Calibration boxes: The imdu Advanced Configuration box allows a number of factory configurable settings to be changed, induding: System serial number, page copyright notice and product code and a printable page can also be generated containing this information along with the system MAC address. The Meter Calibration box allows the meter to be calibrated. To calibrate voltage measure the mains voltage [RMS] at the feed input, enter the value in the DMM field and click on Calibrate. To calibrate current a RMS ammeter must be placed in series with an outlet and load device eg. heater. Enter the amps value in the DMM field and click on Calibrate. Logout button Clicking on the Logout button the operator is presented with a blank page.

29 29 Appendix B. SNMP trap setup and register description Overview The imdu supports multiple SNMP registers which can be accessed through its MIB file definition [IMDU_Vxxx.mib] by any SNMP manager. The product supports all standard SNMP operations such as GET, SET, GET NEXT, GET SUBTREE, GET BULK and WALK along with table viewing for some sets of registers and global registers. The product is also capable of generating SNMP traps when previously setup alarm thresholds or alarm conditions are encountered. SNMP trap host setup The imdu supports two SNMP host IP addresses allowing two different host systems to be sent trap alarm information. The host destination enable status, destination IP address and SNMP community string are setup through a table view of the imdu-trapdesttable: Which when viewed as a table will look like this: The destination IP address should be set to the IP of the host that is to receive the trap notifications and the trap destination status set to 1 for ENABLED. The SNMP trap community can also be changed if required. Once configured any alarms generated by the system will be sent as traps every <AlarmPeriod> minutes.

30 30 This page is intentionally blank

31 31 SNMP register definitions The imdu register set can be broken into two [2] functional categories, imdu-snmp and slave-global. Please refer to Appendix A Web server HTML web page description for more information about the individual values available as registers. imdu-snmp Site totals and Server status registers The imdu-sitetotals and imdu-server branches allow the imdu Slave totals to be read and the server status to be read. The following MIB tree shows the registers available: imdu-snmp Master configuration and information registers The remaining imdu-snmp branches contain registers that allow the master imdu status registers to be read (Meter, Outlets and Environmental), allow the Master imdu to be configured and trap thresholds to be setup. The following MIB tree shows the branches available:

32 32 imdu-configuration branch The imdu-configuration branch contains relevant configuration information for the Master imdu as follows: Registers to display Master imdu customer and imdu location name, CO2 conversion factor, MODBUS interface setup, outlet start-up configuration and network settings are accessible with those displaying a pen nib also being configurable. imdu-information branch The imdu-information branch contains relevant information for the Master imdu as follows: imdu-productname and imdu-serialnumber are set at factory. imdu-meter branch The imdu-meter branch contains meter measurements for the Master imdu as follows: imdu-outlets branch The imdu-outlets branch contains outlet status for the Master imdu as follows:

33 33 imdu-environmental branch The imdu-environmental branch contains humidity probe, temperature probe, contact input, ADC input and GPO output measurements and status for the Master imdu as follows:

34 34 imdu-traps - imdu-trapthresholds branch The imdu-trapthresholds branch allows the Master imdu alarm thresholds and conditions to be configured. The first few can be seen as follows: Please refer to Appendix A Web server HTML web page description for more information about the individual values available as registers. imdu-trapsetnotifications branch The imdu-trapsetnotifications branch contains the trap SET (when an alarm is activated) definitions for all Master and Slave traps, a small sample of which are as follows: imdu-trapclearnotifications branch The imdu-trapclearnotifications branch contains the trap CLEAR (when an alarm is deactivated) definitions for all Master and Slave traps, a small sample of which are as follows:

35 35 Slave-Global branch The Slave-Global branch contains tabled registers that allow the Master and all Slave imdu s in the installation to be viewed as follows: Please refer to Appendix A Web server HTML web page description for more information about the individual values available as registers.

36 36 SNMP V3 Setup The imdu also support SNMP V3 which supports authenticated and encrypted SNMP operations such as GET, SET, GET NEXT, GET SUBTREE, GET BULK and WALK along with table viewing for some sets of registers and global registers. The SNMP manager must be pre-configured with username, authentication protocol, authentication password, privacy protocol and privacy password before SNMP V3 operations cantake place. The following branches show the tables that allow these parameters to be configured: Before SNMP V3 operations can be undertaken the SNMP manager must be configured. An example ireasoning setup is as follows: The default credentials for userone are MD5 auth algorithm with password authpass and AESprivacy algorithm with password privpass. Context Name MUST be left blank.

37 37 Appendix C. Telnet command line interface description Telnet server The imdu supports a configuration selectable Telnet command line interface that allows a user to control/monitor system settings and measurements. Logging into the Telnet server The Telnet server can be logged into using any Telnet compatible application. For clarity the following description uses the Putty application ( as the client as it is available as a free download. After starting the application you will be presented with following setup screen: Select the Telnet radio button, enter the imdu IP address into the Host Name box and click Open. If a connection is made you will be presented with the following screen: Enter the default user name username and password password and the following screen will be displayed:

38 38 Telnet server commands The Telnet server supports a number of commands that allow the slave imdu to be selected, outlets read and set and metering/environmental measurements to be read. Set slave command The set slave command allows the slave imdu to be set ready for other read/set commands, the format being : set slave xx Where xx is the slave address 01-31, replies with: Slave xx set Read outlet command The Read outlet command allows the status of an outlet to be returned, the format being: read outlet xx Where xx is the outlet number 01-12, replies with: Outlet xx: ddd Where ddd is ON if the outlet is on, OFF if the outlet is off or FUSE BLOWN if the outlets fuse has opened. Set outlet command The Set outlet command allows an outlet to be switched on/off instantly or with a delay and be cycled off/on with a delay, the format being: set outlet xx dddd Where xx is the outlet number and dddd is as follows: on instant Turns the outlet on instantly. off instant Turns the outlet off instantly. on delay Turns the outlet on after the delay period setup on the configuration page for that particular outlet. off delay Turns the outlet off after the delay period setup on the configuration page for that particular outlet. Cycle Turns the outlet off and then on again using the delay setup on the configuration page for that particular outlet.

39 39 Read meter voltage command The Read meter voltage command returns the current voltage measured by the meter, the format being: read volts Replies with: Meter volts: vvv.vvac Where vvv.v is the current AC voltage. Read meter current command The Read meter current command returns the current amps measured by the meter, the format being: read current Replies with: Meter current: aa.aaa Where aa.aa is the current AC amperage. Read meter power command The Read meter power command returns the current wattage in kws measured by the meter, the format being: read power Replies with: Meter power: ww.wwwwkws Where ww.wwww is the current power in kws. Read meter frequency command The Read meter frequency command returns the current mains frequency measured by the meter, the format being: read freq Replies with: Meter frequency: ff.fhz Where ff.f is the current frequency in Hz. Read meter power factor command The Read meter power factor command returns the current PF measured by the meter, the format being: read pf Replies with: Meter PF: p.ppp Where p.ppp is the current power factor.

40 40 Read meter energy command The Read meter energy command returns the current energy in kwhs measured by the meter, the format being: read energy Replies with: Meter energy: eeeee.ekwh Where eeeee.e is the current power in kwhs. Read humidity command The Read humidity command returns the current humidity and temperature measured by the humidity probe, the format being: read humidity Replies with: Humidity: hh.hh% Temp: tt.ttc Where hh.hh is the humidity in % and tt.tt is the temperature in celsius. Read temperature probe command The Read temperature probe command returns the current temperature measured by the selected temperature probe, the format being: read probe xx Where xx is the probe to read 01-08, replies with: Temperature probe xx: tt.ttc Where tt.tt is the temperature in celsius. Read contact command The Read contact command allows the status of a contact to be returned, the format being: read contact xx Where xx is the contact number 01-08, replies with: Contact xx: ddd Where ddd is OPEN if the contact is open, CLOSED if the contact is closed.

41 41 Read ADC level command The Read ADC level command returns the current voltage measured on the selected ADC channel, the format being: read adc xx Where xx is the probe to read 01-02, replies with: ADC xx: v.vvv Where v.vv is the voltage V. Set gpo command The Set gpo command allows a gpo contact to be opened or closed, the format being: set gpo xx dddd Where xx is the gpo number and dddd is as follows: Close Closes the output contact. open Opens the output contact. Help command The help command provides a summary of the commands, the format being: help And returns the following: set slave XX read outlet XX set outlet XX on/off/cycle instant/delay read volts read current read power read freq read pf read energy read humidity read probe YY read contact YY read adc ZZ set gpo ZZ where XX=01-12, YY=01-07 & ZZ=01-02 Quit command The Quit command exits the Telnet session, the format being: quit

User Manual. Per Port Monitoring Models

User Manual. Per Port Monitoring Models User Manual Per Port Monitoring Models Table of Contents 1. Introduction... 1 2. Package Contents... 2 3. Function... 3 4. Installation... 5 5. Web Interface... 6 1. Introduction The ServerLink Per Port

More information

Switched XPDU. 15A Model. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved.

Switched XPDU. 15A Model. User & Installation Manual Xtreme Power Conversion Corporation. All rights reserved. Switched XPDU 15A Model User & Installation Manual www.xpcc.com 2014. All rights reserved. (Rev 10/02/14) Table of Contents Introduction...4 PDU Package...4 Function...4 Interface...4 Installation...5

More information

1. General Description

1. General Description ipio-2, ipio-8, ipio-16 Monitor and Control of Digital I/O 1. General Description The ipio is a network attached, web enabled digital input and output device. The ipio can be controlled and monitored with

More information

Innovative Electronics for a Changing World INDEX

Innovative Electronics for a Changing World INDEX Innovative Electronics for a Changing World INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION DIAGRAM 4. START UP GUIDE and passwords 5. HOME PAGE 6. STATUS PAGE 7.

More information

Industrial Serial Device Server

Industrial Serial Device Server 1. Quick Start Guide This quick start guide describes how to install and use the Industrial Serial Device Server. Capable of operating at temperature extremes of -10 C to +60 C, this is the Serial Device

More information

ECO PDU Power Distribution Unit

ECO PDU Power Distribution Unit ECO PDU Distribution Unit PE6108/PE6208/PE8108/PE8208 ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage.

More information

Table of Contents. 1. Introduction Package Contents Function Installation Web Interface... 4

Table of Contents. 1. Introduction Package Contents Function Installation Web Interface... 4 User Manual Table of Contents 1. Introduction... 1 2. Package Contents... 2 3. Function... 3 4. Installation... 2 5. Web Interface... 4 1. Introduction The ServerLink PDU is a network ready device designed

More information

Ethernet Interface Module

Ethernet Interface Module Interface Manual 1 Ethernet Interface Module SignalFire Number: ENET-DIN The SignalFire Ethernet Gateway has the following features: - Wide range DC power input. 6 to 36VDC - Power Over Ethernet (POE)

More information

IPDU-A Series User Manual. IPDU-A Series User Manual

IPDU-A Series User Manual. IPDU-A Series User Manual 1 Contents Ⅰ. Introduction... 3 Ⅱ. Main functions... 3 Ⅲ. Monitoring method... 3 Ⅳ. Applications... 3 Ⅴ. Product sketch... 4 Ⅶ. Mounting method... 4 Ⅷ. Hardware introduction... 5 1. Front panel introduction...

More information

Copyright 2016 IPT PDUUM Revision

Copyright 2016 IPT PDUUM Revision PDUUM052016 Revision 1.03.250516 Table of Contents Introduction...3 Warranty...3 Installation...3 Operation...3 View...4 Adding PDU Servers...4 Agent Information...5 Graphs...5 Log Views...5 Tools...5

More information

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT DKG-210 UNIVERSAL INTERNET GATEWAY UNIT AC & DC SUPPLY VERSIONS DESCRIPTION The DKG-210 is designed for internet monitoring and control of industrial devices using different protocols through the RAINBOW

More information

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER! QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

Technical Manual Nova: Cabinet Security Management System (CSMS)

Technical Manual Nova: Cabinet Security Management System (CSMS) Technical Manual Nova: Cabinet Security Management System (CSMS) KP_nova_TM_160501_EN 1 Publication May, 2016, Keyprocessor BV Paasheuvelweg 20 1105BJ Amsterdam, The Netherlands www.keyprocessor.com/nova

More information

Switched Rack Power Distribution Unit

Switched Rack Power Distribution Unit Switched Rack Power Distribution Unit AS-216-520-30A-L530 Installation and Quick Start Contents Product Description and Inventory...................... 1 AS-216-520-30A-L530....................... 1 Additional

More information

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!

QUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER! QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

BCM2 Series Branch Circuit Monitors Quick Setup Guide

BCM2 Series Branch Circuit Monitors Quick Setup Guide BCM2 Series Branch Circuit Monitors Quick Setup Guide Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable

More information

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service. PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA

More information

JNIOR Series 4 A Network I/O Resource Utilizing the JAVA Platform Getting Started Manual Release 2.0 NOTE: JANOS OS 1.1 or greater required

JNIOR Series 4 A Network I/O Resource Utilizing the JAVA Platform Getting Started Manual Release 2.0 NOTE: JANOS OS 1.1 or greater required JNIOR Series 4 A Network I/O Resource Utilizing the JAVA Platform Getting Started Manual Release 2.0 NOTE: JANOS OS 1.1 or greater required INTEG Process Group, Inc. 2919 East Hardies Rd, First Floor Gibsonia,

More information

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V

CRAGG RAILCHARGER Instruction Manual for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V CRAGG RAILCHARGER for 10DTC-12V 20DTC-12V 30DTC-24V 40DTC-12V 60DTC-12V Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 2 3 Features... 2 3.1 STANDARD FEATURES... 2 3.2 CHARGER REGULATION...

More information

IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide

IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide VxI Power Ltd. IPM-01 / IPM-01H MODBUS TCP/RTU Bridge User Guide 01/12/2015 Document Number: 14970-020A Issue Number: 2 Contents 1.0 Device Overview... 2 2.0 Getting Started... 3 2.1 Connecting the Device...

More information

PN5212/PN5320/PN7212/PN7320

PN5212/PN5320/PN7212/PN7320 PN522/PN520/PN722/PN720 Power Over the NET Power Distribution Units ALTUSEN Power Over the NET products are Power Distribution Units that offer outlet level control combined with remote access to give

More information

PM Series Power Meter

PM Series Power Meter PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See

More information

Frequently Asked Questions

Frequently Asked Questions Q. What is the power metering accuracy on CPI econnect PDUs? A. The power metering accuracy on CPI econnect PDUs is ±1% for each breaker. Meters are included in Monitored, Monitored, Switched and Switched

More information

Innovative. Engineering. Power. structure source. Making the complex, simple. Structure Source PDU s

Innovative. Engineering. Power. structure source. Making the complex, simple. Structure Source PDU s Structure Source PDU s Innovative Power Engineering High Quality Power Distribution for the Data Centre structure source Making the complex, simple structure source product range Rack and Server Power

More information

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter

QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960, PMMC-1000 PM Series Power Meter Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices.

More information

Model# ANI SWH. Ver. 1.1

Model# ANI SWH. Ver. 1.1 PDU Per Outlet Control and Total Current Monitoring User Manual Model# ANI-15115-08SWH Ver. 1.1 Table of Contents 1. Introduction... 1 2. PDU Package... 2 3. Function... 3 4. Installation... 5 5. Web Interface...

More information

Hardware Installation

Hardware Installation LOLM366912 The ipio-8 is a network attached, IP addressed digital input and output device. The ipio-8 can be controlled and monitored with a standard web browser. Multiple ipio-8 devices can communicate

More information

EGW1-IA3-MB User s Manual

EGW1-IA3-MB User s Manual www.exemys.com Rev. 0 1 Products are in constant evolution to satisfy our customer needs. For that reason, the specifications and capabilities are subject to change without prior notice. Updated information

More information

ETH044-4 SSR (230VAC) and 4 Digital IO

ETH044-4 SSR (230VAC) and 4 Digital IO ETH044-4 SSR (230VAC) and 4 Digital IO Technical Documentation WARNING Mains Voltages can be Lethal. If you are not confident with using these voltages, please use a qualified electrician to wire this

More information

25.2kW 3-Phase Switched PDU, LX Platform Interface, 240V Outlets (24 C13/6 C19), Touchscreen LCD, IEC A Red 415V, 0U, TAA

25.2kW 3-Phase Switched PDU, LX Platform Interface, 240V Outlets (24 C13/6 C19), Touchscreen LCD, IEC A Red 415V, 0U, TAA 25.2kW 3-Phase Switched PDU, LX Platform Interface, 240V Outlets (24 C13/6 C19), Touchscreen LCD, IEC 309 60A Red 415V, 0U, TAA MODEL NUMBER: PDU3XEVSR6G60B Highlights 25.2kW 240V 3-phase switched 1.8m

More information

INDEX. Network Power Monitor NPM-R10-SNMP. Innovative Electronics for a Changing World. NPM-R10-SNMP Remote Network Power Monitor

INDEX. Network Power Monitor NPM-R10-SNMP. Innovative Electronics for a Changing World. NPM-R10-SNMP Remote Network Power Monitor Innovative Electronics for a Changing World NPM-R10-SNMP Remote Network Power Monitor Optional relay board and GSM module INDEX 1. SYSTEM DESCRIPTION 2. SYSTEM BATTERY CONNECTIONS 3. SERIES CONNECTED BATTERIES

More information

Application. Contents of Package. Inspect the CyberSwitch upon receipt. The package should contain the following items:

Application. Contents of Package. Inspect the CyberSwitch upon receipt. The package should contain the following items: Overview CyberPower power manager CyberSwitch is the ultimate power control center to manage multiple network devices via the Internet. After installing the hardware and setting up an IP address, this

More information

OPERATING MANUAL AC POWER DISTRIBUTION UNITS VIGILANT SERIES

OPERATING MANUAL AC POWER DISTRIBUTION UNITS VIGILANT SERIES OPERATING MANUAL AC POWER DISTRIBUTION UNITS VIGILANT SERIES www.unipowerco.com Manual No. PDUAC1USM-2 pduac1us-man-rev2-0115.indd 2015 UNIPOWER LLC All Rights Reserved NORTH AMERICA 3900 Coral Ridge Drive,

More information

Contents 1 Warnings, Cautions, and Notes Description Features... 1

Contents 1 Warnings, Cautions, and Notes Description Features... 1 EnCell Contents 1 Warnings, Cautions, and Notes... 1 2 Description... 1 3 Features... 1 3.1 STANDARD FEATURES... 1 3.2 FRONT PANEL FEATURES... 2 3.2.1 Display... 2 3.2.2 OK LED... 2 3.2.3 FAULT LED...

More information

Table Of Contents. 1. Introduction... 1

Table Of Contents. 1. Introduction... 1 User Manual Table of Content Table Of Contents 1. Introduction... 1 1.1 Brief Introduction to Web Interfaces... 1 1.2 How to Log In... 1 1.3 General Setting... 2 1.3.1 Date and Time Setting... 2 1.3.2

More information

User s Manual. Management Converter Chassis. Model No.: SP1386 / SP1387. World Wide Web: ;

User s Manual. Management Converter Chassis. Model No.: SP1386 / SP1387. World Wide Web:   ; User s Manual Management Converter Chassis Model No.: SP1386 / SP1387 World Wide Web: www.micronet.com.tw ; www.micronet.info Table of Content 1. INTRODUCTION... 2 1.1 PACKAGE CONTENT... 2 1.2 KEY FEATURES...

More information

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw

isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw isma-b-mg-ip User Manual Global Control 5 Sp. z o.o. Poland, Warsaw www.gc5.pl Table of content 1 Introduction... 4 1.1 Revision history... 5 1.2 Safety rules... 5 1.3 Technical specifications... 6 1.4

More information

Innovative Electronics for a Changing World. NPM-R10 Remote Network Power Monitor. With optional relay board and GSM module INDEX

Innovative Electronics for a Changing World. NPM-R10 Remote Network Power Monitor. With optional relay board and GSM module INDEX Innovative Electronics for a Changing World NPM-R10 Remote Network Power Monitor With optional relay board and GSM module INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION

More information

smartden IP-WatchDog PING Restarter and Auto-Rebooter

smartden IP-WatchDog PING Restarter and Auto-Rebooter smartden IP-WatchDog PING Restarter and Auto-Rebooter User Manual Date: For firmware version: v1.21 / May 2017-1- Content smartden IP-WatchDog User Manual 1. Features... 3 2. Application examples... 4

More information

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2

NET101. RS232 / RS422 / RS485 to Ethernet Converter. User s Manual. Version 1.2 NET101 RS232 / RS422 / RS485 to Ethernet Converter User s Manual Version 1.2 Copyright Information Copyright 2004-2005, Mega System Technologies, Inc. All rights reserved. Reproduction without permission

More information

PE A/16A 8-Outlet 1U Outlet-Metered & Switched eco PDU

PE A/16A 8-Outlet 1U Outlet-Metered & Switched eco PDU PE8208 20A/16A 8-Outlet 1U Outlet-Metered & Switched eco PDU 8 outlets 20A (UL derated 16A) / 16A Outlet Power Measurement The PE8208 eco PDU is intelligent PDUs that contains 8 AC outlets and is available

More information

Poseidon 4002 MANUAL

Poseidon 4002 MANUAL Poseidon 4002 MANUAL Poseidon 4002 MANUAL POWER input 12VDC supply (jack or terminals) INPUTS Binary inputs 1 6 (for contacts) OUTPUTS Two 50V rated switchover relay contacts ETHERNET 10 or 100/10 Mbps

More information

epowerswitch 8M+ R2 User guide Version

epowerswitch 8M+ R2 User guide Version epowerswitch 8M+ R2 User guide Version 03 2011 www.neol.com Copyright by NEOL S.A.S - 4 Rue Nationale, 67800 BISCHHEIM, France Printed in France All rights reserved. No part of this documentation, accompanying

More information

Table of Contents. 1. Introduction Package Contents Function Installation Web Interface... 5

Table of Contents. 1. Introduction Package Contents Function Installation Web Interface... 5 User Manual Table of Contents 1. Introduction... 1 2. Package Contents... 2 3. Function... 3 4. Installation... 4 5. Web Interface... 5 6. Specifications... 8 1. Introduction The ServerLink PDU is a network

More information

AcquiSuite Ally 48 Advanced Branch Circuit Monitor

AcquiSuite Ally 48 Advanced Branch Circuit Monitor AcquiSuite Ally 48 Advanced Branch Circuit Monitor AMC48-MD AMC48-ED Split Core CT Split Core CT Ally Rogowski Rope CT DESCRIPTION The AcquiSuite Ally 48 is the perfect companion to the data acquisition

More information

LAN Interface TCW120B

LAN Interface TCW120B LAN Interface TCW120B 1. Short description TCW120 is a multifunctional device for remote monitoring and management. It is an Ethernet based controller, which is designed to work in IP-based networks and

More information

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer K01-SNMP004-00 TABLE OF CONTENTS INTRODUCTION... 1 INSTALLATION GUIDE...

More information

INDEX. Network Power Monitor R10 SNMP

INDEX. Network Power Monitor R10 SNMP Innovative Electronics for a Changing World NPM-R10 Remote Network Power Monitor With optional relay board and GSM module INDEX Amended 21 March 2017: Add user defined Password see page 13 Add wire Connection

More information

TIME SERVER NETSILON. Quick start.

TIME SERVER NETSILON. Quick start. TIME SERVER NETSILON Quick start This document refers to the following products: 907,900 NETSILON 7 (100-240 VAC) 907,901 NETSILON 7 (18-36 VDC) 907,902 NETSILON 7 (100-240 VAC + 18-36 VDC) www.bodet-time.com

More information

IPDU-Sx Secure Remote Power Reboot Switch Installation and Operation Manual

IPDU-Sx Secure Remote Power Reboot Switch Installation and Operation Manual ENVIROMUX Series IPDU-Sx Secure Remote Power Reboot Switch Installation and Operation Manual Front and Rear View of IPDU-S2 Front and Rear View of IPDU-S8-P15 MAN119 Rev Date 3/26/18 TRADEMARK ENVIROMUX

More information

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer

User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer Version 1.3 TABLE OF CONTENTS INTRODUCTION... 1 INSTALLATION GUIDE... 4

More information

EnerSure Installation Guide

EnerSure Installation Guide EnerSure Installation Guide Danger!!! The electrical components of this system may contain voltage and /or amperage sufficient to injure or kill. Installation is only to be performed by a licensed, bonded

More information

8-Outlet eco PDU PE6208AV

8-Outlet eco PDU PE6208AV 8-Outlet eco PDU Ideal for CI and Pro-AV applications, the ATEN NRGence eco PDU is an intelligent 1U rack PDU that contains 8 AC outlets available in an IEC socket configuration. The unique design with

More information

EnCell Battery Cell Monitor

EnCell Battery Cell Monitor EnCell Battery Cell Monitor Instruction Manual Model RCM15S12 NERC Compliant YO R U H T PA TO Z O R E W O D N M I T E enchargepowersystems.com sales@enchargepowersystems.com (888) 407.5040 Contents 1 Warnings,

More information

Conettix ITS-D6682-INTL

Conettix ITS-D6682-INTL Conettix ITS-D6682-INTL EN Installation Guide Ethernet Network Adapter Conettix ITS-D6682-INTL Installation Guide Contents Contents 1.0 Introduction... 3 1.1 Network Interface... 3 1.2 Serial Interface...

More information

Table of Contents SMARTZONE G5 USER MANUAL

Table of Contents SMARTZONE G5 USER MANUAL G5 PDU User Manual 1 Table of Contents Table of Figures... 5 Section 1 System Overview... 8 Intelligent Network Controller... 8 Connecting the PDU to a LAN Ethernet Port... 8 Connecting the PDU to a Computer

More information

Innovative Circuit Technology Ltd. Digital Series Power Supply Instruction Manual

Innovative Circuit Technology Ltd. Digital Series Power Supply Instruction Manual Innovative Circuit Technology Ltd. Digital Series Power Supply Instruction Manual 855-317-000 Rev 2.0 Feb 2018 Copyright 2018 Innovative Circuit Technology Ltd. All rights reserved. No part of this publication

More information

UPS Series. features: uninterruptible power supply. what great systems are built on.

UPS Series. features: uninterruptible power supply. what great systems are built on. uninterruptible power supply uninterruptible power supply with energy saver design that is optimized to address the needs of A/V systems features: Pure Sine Wave technology with Automatic Voltage Regulation

More information

Chassis Power Supplies

Chassis Power Supplies PDC24 / PAC Chassis Power Supplies (PDC24 / PAC) Issue 3 October 2005 INTRODUCTION PURPOSE Two Power Supply Units (PSUs) provide a dual-redundant source of 5.4Vand 12Vdc onto the backplane for the modules

More information

Three-phase electricity meter with instantaneous reading of electrical variables. Input current measurement: 5 A, 90 A, 150 A, 250 A (span by model).

Three-phase electricity meter with instantaneous reading of electrical variables. Input current measurement: 5 A, 90 A, 150 A, 250 A (span by model). SCEE AR 3 - Smart Analyzer 485/Ethernet with web visualization Three-phase electricity meter with instantaneous reading of electrical variables. System variables: V, A, kw, kva, kvar, PF and Hz. Variables

More information

JNIOR Series 3 A Network I/O Resource Utilizing the JAVA Platform Getting Started Manual Release 3.3 NOTE: JNIOR OS 3.4 or greater required

JNIOR Series 3 A Network I/O Resource Utilizing the JAVA Platform Getting Started Manual Release 3.3 NOTE: JNIOR OS 3.4 or greater required JNIOR Series 3 A Network I/O Resource Utilizing the JAVA Platform Getting Started Manual Release 3.3 NOTE: JNIOR OS 3.4 or greater required INTEG Process Group, Inc. 2919 East Hardies Rd, First Floor Gibsonia,

More information

SNMP Web Management. User s Manual

SNMP Web Management. User s Manual SNMP Web Management User s Manual Suitable Product: SNMP Web Card SNMP Web Box Management Software for Uninterruptible Power Supply Systems Table of Contents 1. Overview... 1 1.1 Introduction... 1 1.2

More information

EC-11 Ethernet Converter

EC-11 Ethernet Converter EC-11 Ethernet Converter PSTN Contact ID to TCP Converter Installation and Operations Manual Version 8.H3.MID 1 Table of Contents About EC-11 Ethernet Converter... 3 Circuit Board Layout and Wiring Diagram...

More information

ACTpro Single Door IP Controller. Operating & Installation Instructions

ACTpro Single Door IP Controller. Operating & Installation Instructions ACTpro 1500 Single Door IP Controller Operating & Installation Instructions 18-00079 Issue 1 This manual refers to the ACTpro 1500 a TCP/IP based control unit supporting up to 32 doors. Access Control

More information

VT805 / Monitoring system

VT805 / Monitoring system Environmental Infrastructure monitoring VT805 / Monitoring system Environmental monitoring of any facilities, control of security breaches, temperatures, smoke, water leakages, voltages and more. Compatible

More information

Conettix ITS-D6686-INTL

Conettix ITS-D6686-INTL Conettix ITS-D6686-INTL EN Installation Guide Ethernet Network Adapter Conettix ITS-D6686-INTL Installation Guide Contents Contents 1.0 Introduction... 3 1.1 Network Interface... 3 1.2 Serial Interface...

More information

MOD-RI Room Interface Modules with Modbus

MOD-RI Room Interface Modules with Modbus Product sheet MOD3.00 Type MOD-RI MOD-RI Room Interface Modules with Modbus The MOD-RI are room interface modules designed to provide room control interface for the building management systems. The MOD-RI

More information

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

MOD-IO9 Modbus Input / Output Modules, Wall Mounted Product sheet MOD3.9 Type MOD-IO9 MOD-IO9 Modbus Input / Output Modules, Wall Mounted MOD-IO9 and MOD-IO9-AI have been designed to be a compact wall mounted Modbus RTU input and output module. The module

More information

Power Switch Cabinet 4-Port New Generation

Power Switch Cabinet 4-Port New Generation May 2011 PSE544-XX Power Switch Cabinet 4-Port New Generation SUPPORT FREE technical support This product carries the CE mark to indicate compliance with the European Directive on Electromagnetic Compatibility

More information

Preface. Managed Media Converter Chassis System

Preface. Managed Media Converter Chassis System Preface The Managed Media Converter Chassis System supports the Media Converter Chassis to monitor the each Media Converter ( CO ) or Chassis Manager status and to configure advanced function of the Managed

More information

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, Pre-installed WEBCARDLX Network Interface, USB, DB9 Serial

SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, Pre-installed WEBCARDLX Network Interface, USB, DB9 Serial SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, Pre-installed WEBCARDLX Network Interface, USB, DB9 Serial MODEL NUMBER: SMART750RM1UN Highlights.75kVA / 750VA / 600W line interactive

More information

RMS-U-RB-8 Relay box 8 User Manual

RMS-U-RB-8 Relay box 8 User Manual RMS-U-RB-8 Relay box 8 User Manual Version 1.1; 28.05.2014 2013 CONTEG, spol. s r.o. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted or stored in any

More information

USB-Cascading Solution

USB-Cascading Solution USB-Cascading Solution Guide Release 3.2.10 Copyright 2016 Raritan, Inc. USBcascade-0E-v3.2.10-E March 2016 255-80-0012-00 RoHS Safety Guidelines WARNING! Read and understand all sections in this guide

More information

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision

Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision Motortronics VirtualSCADA VS2-MT Communication Gateway VS2-MT User Manual Revision 1.03.00 Motortronics / Phasetronics 1600 Sunshine Drive Clearwater, Florida 33765 Tel: 727-573-1819 Fax: 727-573-1803

More information

Safety Precautions Legrand PDU. 0U PDU Overview. Outlets. Circuits. Controller with Connector Ports: See Controller (on page 4).

Safety Precautions Legrand PDU. 0U PDU Overview. Outlets. Circuits. Controller with Connector Ports: See Controller (on page 4). LG_QSG _0A_3.4.11 0A 255-80-0053-00 R oh S Legrand PDU - LG_QSG_0A_3.4.11 Safety Precautions Legrand PDU WARNING! Read and understand all sections in this guide before installing or operating this product.

More information

VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System User Guide V1.0. Innovations BTRM200. Battery Test Remote Monitor User Guide

VENTEV INNOVATIONS BTRM200 Battery Test Remote Monitoring System User Guide V1.0. Innovations BTRM200. Battery Test Remote Monitor User Guide Innovations BTRM200 Battery Test Remote Monitor User Guide Contact : Ventev Innovations 10999 McCormick Road Hunt Valley, MD 21031 Phone Number 800.759.9996 Email Info@ventev.com 1 Contents 1. 2. 3. 4.

More information

Installation A B. Install each bracket using screws provided shown in Figure 1. Fix the KVM into the rack

Installation A B. Install each bracket using screws provided shown in Figure 1. Fix the KVM into the rack Installation screw A: M3.2 x 4.5 mm A B Cy r be Vie w screw B: M4 x 0 mm Install each bracket using screws provided shown in Figure. Fix the KVM into the rack Figure. Installing the bracket to the KVM.

More information

Installation of the PCMeasure Movement Sensor (30114)

Installation of the PCMeasure Movement Sensor (30114) 1. Hardware: Installation of the PCMeasure Movement Sensor (30114) Connect the sensor to a serial or parallel port of the PC using one of the PCMeasure adaptors, or directly to the PCMeasure Ethernet Box.

More information

Conettix ITS-D6682-UL

Conettix ITS-D6682-UL Conettix ITS-D6682-UL EN Installation Guide Ethernet Network Adapter Conettix ITS-D6682-UL Installation Guide Contents Contents 1.0 Introduction...3 1.1 Network Interface... 3 1.2 Serial Interface... 3

More information

ECO PDU. Features. PE5220sA

ECO PDU. Features. PE5220sA ECO PDU PE5220s As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage. The NRGence

More information

Chassis-based Media Converters

Chassis-based Media Converters Media Converters with Individual Metal Case Housing. DMC-615SC DMC-1002 Management Module DMC-1000 Chassis Chassis-based Media Converters System Overview The Chassis-based Media Converters include a number

More information

ECO PDU PE7108/PE7208

ECO PDU PE7108/PE7208 PE7108/PE7208 ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage. The PE7108 / PE7208 eco PDUs are intelligent

More information

PE A/16A 8-Outlet 1U Outlet-Metered & Switched eco PDU. 8 outlets. 20A (UL derated 16A) / 16A. Outlet Power Measurement

PE A/16A 8-Outlet 1U Outlet-Metered & Switched eco PDU. 8 outlets. 20A (UL derated 16A) / 16A. Outlet Power Measurement PE8208 20A/16A 8-Outlet 1U Outlet-Metered & Switched eco PDU 8 outlets 20A (UL derated 16A) / 16A Outlet Power Measurement The PE8208 eco PDU is intelligent PDUs that contains 8 AC outlets and is available

More information

INSTALLATION. Lightning / Surge Protection Static Shock IO. All ports/case Max. Length of Combined Cont. to Cont. Bus Network.

INSTALLATION. Lightning / Surge Protection Static Shock IO. All ports/case Max. Length of Combined Cont. to Cont. Bus Network. INSTALLATION VANTAGECONTROLS.COM VANTAGE INSTALL GUIDES 1061 South 800 East Orem, Utah 84097 Telephone 801 229 2800 Fax 801 224 0355 InFusion Controller II MODEL: IC-36-II & IC-24-II Overview The InFusion

More information

Instruction Manual Environmental Monitoring Unit with Optional POE. Watchdog 15 Series Firmware Version 1

Instruction Manual Environmental Monitoring Unit with Optional POE. Watchdog 15 Series Firmware Version 1 Instruction Manual Environmental Monitoring Unit with Optional POE Watchdog 15 Series Firmware Version 1 Geist 1821 Yolande Ave., Lincoln, NE 68521 800.432.3219 402.474.3400 F: 402.474.4369 www.geistglobal.com

More information

User Manual. PPS-02-S, IP dongle GUI & SNMP. Inspired by Your Data Center. Designed and manufactured by Austin Hughes

User Manual. PPS-02-S, IP dongle GUI & SNMP. Inspired by Your Data Center. Designed and manufactured by Austin Hughes Inspired by Your Data Center User Manual PPS-02-S, IP dongle GUI & SNMP W Monitored Wi Outlet Monitored WS Switched WSi Outlet Switched Single Phase 230V / 208V / 110V Single Phase 63A 230V Three Phase

More information

BTRM200 Battery Test Remote Monitor. User Guide

BTRM200 Battery Test Remote Monitor. User Guide BTRM200 Battery Test Remote Monitor User Guide Contact : Ventev Wireless Infrastructure 11126 McCormick Road Hunt Valley, MD 21031 Phone Number 800.851.4965 Email Sales@ventev.com Ventev Wireless Infrastructure

More information

Polar PDUs POWER MANAGEMENT

Polar PDUs POWER MANAGEMENT Polar Power Distribution Units (PDUs) provide the ultimate solution for combining cabinet level power management, environmental monitoring, and cabinet access control in multi-tenant and enterprise data

More information

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X

Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X Energy Management Modular DC Energy analyzer Type VMU-E and VMU-X Modular solution based on the combination of two units: VMU-E analysis unit and VMU-X universal power supply and RS485 communication unit.

More information

Version 1.0c May 6, 2010 ATK3

Version 1.0c May 6, 2010 ATK3 Version 1.0c May 6, 2010 ATK3 Contents 1 Hardware 2 1.1 Inputs............................... 2 1.2 Outputs.............................. 3 1.3 RS485............................... 3 1.4 Ethernet..............................

More information

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES

D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES 11/17 D7000 SERIES MODBUS TCP/IP ETHERNET INTERFACE MODULES D7000 FEATURES Complete data acquisition systems. Analog and Digital I/O models available. RJ-45 Ethernet 10/100MB interface. Modbus TCP/IP Ethernet

More information

Environmental Manager: Main Module

Environmental Manager: Main Module Contents Introduction--1 Product Description....................................... 1 Features of the 1 Initial setup 2 Access Procedures....................................... 3 Overview 3 Access priority

More information

ROOM GUARD VT335. Environmental Infrastructure monitoring

ROOM GUARD VT335. Environmental Infrastructure monitoring Environmental Infrastructure monitoring ROOM GUARD VT335 Environmental monitoring of any facilities, control of security breaches, temperatures, smoke, water leakages, voltages and more. Compatible with

More information

PE8216/PE8324. Energy Intelligence Solutions

PE8216/PE8324. Energy Intelligence Solutions PE8216/PE8324 As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center power usage. The

More information

Table of Contents SMARTZONE G5 USER MANUAL

Table of Contents SMARTZONE G5 USER MANUAL G5 PDU User Manual 1 Table of Contents Table of Figures... 4 Section 1 System Overview... 7 Intelligent Network Controller... 7 Connecting the PDU to a LAN Ethernet Port... 7 Connecting the PDU to a Computer

More information

ECO PDU PE5108/PE5208

ECO PDU PE5108/PE5208 1 NRGence Energy Intelligence Solutions PE5108/PE5208 ATEN has developed a new generation of green energy power distribution units (PDUs) to effectively increase the efficiency of data center power usage.

More information

Setting Up Your Cisco Unified Videoconferencing 3500 Gateway

Setting Up Your Cisco Unified Videoconferencing 3500 Gateway CHAPTER 2 Setting Up Your Cisco Unified Videoconferencing 3500 Gateway This section describes the following topics: Physical Description, page 2-1 Preparing for Installation of the Cisco Unified Videoconferencing

More information

Any device, including routers and hosts, is running an implementation of IP address Host

Any device, including routers and hosts, is running an implementation of IP address Host INSTRUCTION MANUAL IM471-U v0.1 EMI-10L Introduction EMI-10L converter lets you convert a serial RS485 communications port on a bus Ethernet with TCP / IP. The concepts and terms commonly used in the TCP

More information

PX Serial - Quick Start Guide

PX Serial - Quick Start Guide PX Serial - Quick Start Guide 1. Introduction To take advantage of the full range of features, we recommend you read the softcopy User Guide after performing the Quick Start procedure. It s in PDF format

More information

Sierra Wireless AirLink LS300. Setup Steps

Sierra Wireless AirLink LS300. Setup Steps Sierra Wireless AirLink LS300 Description The target of the Airlink LS300 is the Alarming Module. Its purpose is to Send and Receive SMS messages. Essentially, it is going to be utilized as an SMS gateway.

More information