Start-up of IRI-KHD2-4HB6, IRI-KHA6-4HB6 at S7-300 V1.2. Table of Contents TABLE OF CONTENTS... 1

Size: px
Start display at page:

Download "Start-up of IRI-KHD2-4HB6, IRI-KHA6-4HB6 at S7-300 V1.2. Table of Contents TABLE OF CONTENTS... 1"

Transcription

1 Table of Contents TABLE OF CONTENTS DESCRIPTION OF HARDWARE Modules and devices Set-up and installation HARDWARE CONFIGURATION Installation of the GSE file PROFIBUS DP CONFIGURATION Add users Organization of data/addresses Diagnosis address SOFTWARE Modules and their function Data exchange Diagnosis Program control by means of a variables table Additional information /2000

2 1. Description of Hardware 1.1 Modules and devices Components utilized: Designation Explanation Manufacturer PS 307 Load power supply SIEMENS CPU DP CPU with PROFIBUS DP SIEMENS Master/Slave Interface Programming device PG 740PII Programming software SIEMENS STEP7 V5.0 Programming software SIEMENS IRI-KHA6-4HB6 Analyzer unit (Read ) Pepperl+Fuchs GmbH IRH-18GM-V1 Read head Pepperl+Fuchs GmbH 1.2 Set-up and installation Please see the handbook entitled "Automation System S7-300, Set-up, CPU data" by Siemens for information regarding the connection of the S7 components and their supply. The analyzer unit utilized is to be operated with a voltage of 85 VAC VAC (50 Hz...60 Hz ) (Connection terminal 47 "L",terminal 48 "N"). The read head is connected to terminals 1 to 4 (terminal 1: Supply voltage plus, terminal 2: "Direction", terminal 3: "Data",terminal 4: Supply voltage minus). More detailed information regarding the connection and installation of the device can be found in the handbook of Pepperl+Fuchs GmbH. In the following example, the device address is set to 3 by means of the front side DIP switch (switches 1 and 2 "on"). The analyzer unit is connected to the PROFIBUS DP Master/Slave interface by means of the 9-pole Sub-D connector. If the analyzer unit is the last device on the bus branch, then the bus moving load must be switched on. The bus terminal can either be switched on at the bus plug or at the analyzer unit (rotary switch 9 at the housing side "on ). 2. Hardware configuration 2.1 Installation of the GSE file The standard GSE file must be installed first. To do so, the hardware configuration of your SIMATIC 300-Station must be opened. Under menu item "Extras install new GSE", you can integrate the GSE file in your STEP7 software. After installation of the GSE file, menu item "Extras update catalog" should be called up. 2 7/2000

3 3. PROFIBUS DP Configuration 3.1 Add users The PROFIBUS DP interface must be installed as the DP master. After the PROFIBUS DP bus cable has been set up, the analyzer unit can be placed on it. In the hardware catalog under menu item "PROFIBUS-DP additional field devices general you can now select the IRI- KHxx-4HB6. Click the device with your left mouse button, hold down the button, drag the device to the bus cable of the DP master system, and then release the mouse button. The user address for the PROFIBUS should be entered in the menu which now appears. It must correspond to the address set at the device by the DIP switches (in our example "3" ). At this point the desired analyzing unit should appear as a symbol on your bus cable. 3 7/2000

4 3.2 Organization of data/addresses Click on the symbol for the analyzer unit on the bus cable. In the hardware catalog you can choose from among three sub-items in the listing of the IRI-KHxx-4HB6. First click with the left mouse button on sub-item "20 Bytes Input", hold down the mouse button, drag the mouse arrow to the 0 slot and release the mouse button. Following this and by the same principle, you then put sub-item "2 Bytes Output" in slot /2000

5 The I/O addresses are automatically put on the next free periphery addresses by the STEP7 software. The user can change these addresses. A double click on the respective line opens a window, by means of which the addresses can be transposed. In the example illustrated here the input addresses lie between Since the output data consists of only two bytes, it is possible to assign this address area directly over the output area. This is why the start address was set to /2000

6 3.3 Diagnosis address By double-clicking on the slave symbol at the bus cable, a properties window for the PROFIBUS slave opens. Here the diagnosis address for requesting diagnosis data and the settings of the slave (analyzing unit) are identifiable. The meaning and application of the diagnosis address will be explained later. 4. Software 4.1 Modules and their function With consistent data transfer of from 3 bytes or more than 4 bytes, existing function modules must be used. (!) Modules utilized: Module Designation Description SFC 14 System function Reads in consistent data of a DP norm slave SFC 13 System function Retrieval of diagnosis data of a DP norm slave OB 82 Organization module Called up when a diagnosis alarm of a module appears, so that CPU does not switch into STOP status. OB 86 Organization module Called up upon failure of an expansion device, a DP 6 7/2000

7 master system or a device found at the PROFIBUS DP (e.g. by failure of the supply voltage), so that CPU does not switch into STOP status. OB 100 Organization module Called up upon every new start-up of the CPU, sets all markers to the start position "0. DB 1 Data module Saves read data of the analyzer unit DB 2 Data module Stores diagnosis data OB 1 Organization module Cyclical program flow VAT 1 Variables table Online control of the ID system by means of the PROFIBUS DP 4.2 Data exchange First of all, the IRI-KHA6-4HB6 is initialized. The transmitted command (2 bytes = 1 word ) is compiled in the following way: Word 0 Commands and Parameters Bit No Designation B4 B3 B2 B1 DS K3 K2 K1 T Binary value Hexadecimal value Bit 15 to 12 determines the desired command. The sequence 0011 stands for Buffered Auto Read Fixcode. You will find a detailed explanation of the commands in the handbook for the IRI-KHA6-4HB6. - Bit 11 switches on the "Doubleside-Mode" here set to 0. - Bits 10 to 4 have no significance and are set to /2000

8 - Bits 3 to 1 determine which read head is to be addressed.. The sequence 100 activates all connected read heads. - Bit 0 is the "Toggle flag". To submit a new valid command to the analyzer unit, this bit must be changed ("toggled"). This bit must be set to 1 upon initial sending of a command. More detailed explanations for setting up commands and the meaning of the individual bits can be found in the handbook. For reading in of data from the analyzer unit, the system function SFC14 is called up. The start address of the inputs of the PROFIBUS slave is a required parameter. This address is to be indicated as a hexadecimal indicator (W#16#... ). In our example, the start address is 304. Hexadecimal thus results in the address 130hex. The return value RET-VAL contains an error code. If no error occurred during transfer, the return value contains the sequence You can find a detailed description of the error code in the reference handbook entitled "System Software for the S7-300/400, System and Standard Functions" by Siemens. The goal of the data is to be given as an additional parameter. In our example the term "P#DB1.DBX0.0 byte 20", means that the goal of the data module DB1, beginning with the offset 0.0 and a data field length of 20 bytes, has been selected. Data module DB1 must be laid out ahead of time in a byte structure and at the correct length. The first four bytes are occupied by the command being reported back, the number of the assigned head, the execution counter and the status. The read data of the analyzer unit thus begin with the fourth byte. 8 7/2000

9 Word 0 Command, Parameter and Toggle flag reflected Bit No Designation B4 B3 B2 B1 DS K3 K2 K1 T Word 1 Status, Execution counter, head number Bit No Designation - K3 K2 K1 A4 A3 A2 A S4 S3 S2 S1 Word Read data The image inserted here clarifies the total set up of data module DB1: 4.3 Diagnosis In order to obtain diagnosis data of the slave, the system function SFC13 is called up. The diagnosis address is required here as the start address. In this case, the address is given as Hexadecimal results in the address 3FEhex. 9 7/2000

10 Here, too, the return value contains an error code. In the event that no error occurred during transfer, the return value contains the length of the read data in bytes. You will find a detailed explanation of the error codes in the reference handbook entitled "System Software for S7-300/400, System and Standard Functions" by Siemens. The diagnosis data is stored in the data module DB2. The goal of the data is indicated at the SFC14. In any case, 19 bytes are now transferred. This data module must also be set up ahead of time. The first 6 bytes are occupied by the station status, the master station number and the manufacturer identifier. Starting at the 7th byte, the slave-specific diagnosis data is transmitted. The analyzer unit described here deals with 13 bytes. Contained therein, for example, are the device identifier and the designation of the software of the bus and ID system. You will find more detailed explanations of the meanings of the individual bits in the handbook by Pepperl+Fuchs GmbH. 10 7/2000

11 4.4 Program control by means of a variables table Communication with the ID system can be tested with a variables table set up ahead of time. 11 7/2000

12 By setting the bit 0 in marker byte MB1, the one-time retrieval of diagnosis data is activated. Additional commands can be transmitted to the IRI-KHA6-4HB6 by means of the AW10. For each new command which is to achieve validity, the toggle flag (Bit 0) must be changed. DB1.DBB 0 to DB1.DBB19 contain the PROFIBUS DP input data. -{}-DB2.DBB 6 to DB2.DBB 18 contain the read-in slave-specific PROFIBUS DP diagnosis data. The marker words MW10 and MW20 contain the error codes of the system functions SFC 13 and SFC 14, as already described. 4.5 Additional information In a program designed to take over the evaluation of the extracted data, there are a few basic considerations which are meaningful. If possible, there should always be an inquiry made as to the execution counter. If the revisions to read data are the only information to be considered, then certain errors - the carrying out of a command, for example - are more difficult to recognize. The status indicator, which is transmitted along with the newly read data each time, is also important. The status indicator, for example, could identify a failed reader head, immediately. Pepperl+Fuchs GmbH describes the meaning of the individual status bits in detail in the handbook. 12 7/2000

Table of Contents TABLE OF CONTENTS DESCRIPTION OF HARDWARE Modules and devices Set-up and Installation...

Table of Contents TABLE OF CONTENTS DESCRIPTION OF HARDWARE Modules and devices Set-up and Installation... Table of Contents TABLE OF CONTENTS... 1 1. DESCRIPTION OF HARDWARE... 2 1.1 Modules and devices... 2 1.2 Set-up and Installation... 2 2. SETTING UP PARAMETERS... 2 2.1 Setting up parameters in accordance

More information

Implementation of the Identification System IRI-KHD2-4HB6 to a SIMATIC S PLC

Implementation of the Identification System IRI-KHD2-4HB6 to a SIMATIC S PLC Implementation of the Identification System IRI-KHD2-4HB6 to a SIMATIC S-7 400 PLC Side 1 of 13 Contents 1 Hardware Specification... 3 1.1 Equipment and Devices... 3 1.2 Configuration and Installation...

More information

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D3

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D3 Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D3 PROFIBUS DP with Master CPU 315-2DP / Slave ET 200L T I A Training document Page 1 of 18 Module

More information

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO

Table of Contents 1 ABOUT THIS DOCUMENT GENERAL COPYRIGHT INFORMATION TERMS ABOUT THE GATEWAY PRODUCT FUNCTIO DeviceNet/PROFIBUS-DP Adapter - User Manual REV 4.0 SiboTech Automation Co., Ltd. Technical Support: +86-21-5102 8348 E-mail:gt@sibotech.net Table of Contents 1 ABOUT THIS DOCUMENT...2 1.1 GENERAL... 2

More information

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D5

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D5 Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE D5 PROFIBUS DP with Master CPU 315-2DP / Slave ET 200S T I A Training document Page 1 of 34 Module

More information

FAQ Communication over PROFIBUS

FAQ Communication over PROFIBUS FAQ Communication over PROFIBUS Communication over PROFIBUS FAQ Table of Contents Table of Contents... 2 Question...2 How do I configure a PC station as DP Slave interfacing to a S7 station (as DP Master)

More information

Totally Integrated Automation (T I A) MODULE A3 Startup PLC- Programming with STEP 7

Totally Integrated Automation (T I A) MODULE A3 Startup PLC- Programming with STEP 7 Totally Integrated Automation (T I A) MODULE A3 Startup PLC- Programming with STEP 7 Page 1 of 48 AGE: 1. Forward... 5 2. Notes for the Programming of SIMATIC S7-300 with STEP 7... 7 2.1 Automation system

More information

DVPPF02-SL PROFIBUS DP Slave Communication Module

DVPPF02-SL PROFIBUS DP Slave Communication Module DVPPF02-SL PROFIBUS DP Slave Communication Module Operation Manual DVP-0155320-01 Warning This operation manual provides introduction on the functions, specifications, installation, basic operation, settings

More information

CDN Series Displays with Profibus-DP ELEN UNI-TXT (ND) protocol PARAMETRIZATION OF PROFIBUS-DP COMMUNICATION INTERFACE

CDN Series Displays with Profibus-DP ELEN UNI-TXT (ND) protocol PARAMETRIZATION OF PROFIBUS-DP COMMUNICATION INTERFACE CDN Series Displays with Profibus-DP ELEN UNI-TXT (ND) protocol PARAMETRIZATION OF PROFIBUS-DP COMMUNICATION INTERFACE ELEN, s.r.o. NDI Display Profibus DP UNI TXT(ND) CONTENT Page 2 of 12 1. Introduction...

More information

PROFIBUS DP/CAN Gateway PCA-100. User Manual

PROFIBUS DP/CAN Gateway PCA-100. User Manual PCA-100 REV 4.0 SiboTech Automation Co., Ltd. Technical Support: 021-5102 8348 E-mail: support@sibotech.net Catalog 1 Introduction... 2 1.1 About This Instruction... 2 1.2 Copyright... 2 1.3 Related Products...

More information

Danfoss FCD 300 AS-i and Siemens DP/AS-i Link 20E

Danfoss FCD 300 AS-i and Siemens DP/AS-i Link 20E Introduction This application note describes how to set up an ASi system between a Danfoss FCD 300 frequency converter and Profibus DP/AS-i Link 20E gateway from Siemens. DP/AS-i Link 20E is a gateway

More information

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE E09. PROFINET with 2x CPU 315F-2 PN/DP

Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE E09. PROFINET with 2x CPU 315F-2 PN/DP Training Document for Comprehensive Automation Solutions Totally Integrated Automation (T I A) MODULE PROFINET with 2 x CPU 315F-2 PN/DP T I A Training Document Page 1 of 45 Module This document has been

More information

Additional instructions Memograph M, RSG45 Advanced Data Manager

Additional instructions Memograph M, RSG45 Advanced Data Manager BA01414R/09/EN/01.15 No.: 71302193 Firmware version ENU000A, V2.00.xx Products Solutions Services Additional instructions Memograph M, RSG45 Advanced Data Manager PROFIBUS DP slave Table of contents: 1

More information

Modicon Quantum and Siemens S7-300 PLC as DP slave System User Guide [source code]

Modicon Quantum and Siemens S7-300 PLC as DP slave System User Guide [source code] 33003471.01 Modicon Quantum and Siemens S7-300 PLC as DP slave System User Guide [source code] Table of Content Application Example - Source Code...2 System...3 Architecture...3 Application...4 Hardware

More information

Catalog 1 Product Overview General Important User Information About the Gateway Function Features Tec

Catalog 1 Product Overview General Important User Information About the Gateway Function Features Tec PROFIBUS DP / Modbus TCP Gateway EP-321MP User Manual REV 1.2 Sibotech Automation Co., Ltd Technical Support: 021-5102 8348 E-mail:support@sibotech.net Catalog 1 Product Overview... 4 1.1 General...4 1.2

More information

SIMATIC S7-400, CPU KB WORKING MEMORY (384 KB CODE, 384 KB DATA) 1. INTERFACE MPI/DP 12 MBIT/S 2.IF PROFIBUS DP, 3.

SIMATIC S7-400, CPU KB WORKING MEMORY (384 KB CODE, 384 KB DATA) 1. INTERFACE MPI/DP 12 MBIT/S 2.IF PROFIBUS DP, 3. Product data sheet SIMATIC S7-400, CPU 414-3 768 KB WORKING MEMORY (384 KB CODE, 384 KB DATA) 1. INTERFACE MPI/DP 12 MBIT/S 2.IF PROFIBUS DP, 3.IF FOR IFM CiR - Configuration in RUN CiR synchronization

More information

Supply voltage. Input current. Power loss. Memory. Battery. CPU processing times

Supply voltage. Input current. Power loss. Memory. Battery. CPU processing times Data sheet SIMATIC S7-400H, CPU 417H CENTRAL UNIT FOR S7-400H 4 INTERFACES: 1 MPI/DP, 1 DP A. 2 FOR SYNC MODULES 4MB MEMORY (2MB CODE/2MB DATA) Supply voltage Rated value (DC) 24 V DC Input current from

More information

Cover. Configuration of an IM 308-C as DP Slave to a CP as DP Master PROFIBUS DP. FAQ July Service & Support. Answers for industry.

Cover. Configuration of an IM 308-C as DP Slave to a CP as DP Master PROFIBUS DP. FAQ July Service & Support. Answers for industry. Cover Configuration of an IM 308-C as DP Slave to a CP 342-5 as DP Master PROFIBUS DP FAQ July 2010 Service & Support Answers for industry. Question This entry is from the Service&Support portal of Siemens

More information

General information. Supply voltage

General information. Supply voltage Data sheet SIMATIC S7-300, CPU 313C-2DP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 128 KBYTE WORKING MEMORY, FRONT CONNECTOR (1

More information

While every effort was made to verify the following information, no warranty of accuracy or usability is expressed or implied.

While every effort was made to verify the following information, no warranty of accuracy or usability is expressed or implied. AG090115 How to configure SIMATIC STEP7 V5.5 to read cyclic data from Objective: To use Siemens SIMATC S7300 PLC to read data from MultiRanger/HydroRanger 200 HMI through SmartLinx PROFIBUS communication

More information

Product type designation. General information. Supply voltage. Input current

Product type designation. General information. Supply voltage. Input current Data sheet SIMATIC S7-300, CPU 312C COMPACT CPU WITH MPI, 10 DI/6 DO, 2 FAST COUNTERS (10 KHZ), INTEGRATED 24V DC POWER SUPPLY, 64 KBYTE WORKING MEMORY, FRONT CONNECTOR (1 X 40PIN) AND MICRO MEMORY CARD

More information

STEP 7. Function. Page 1791 Mar 2008 Siemens ITS

STEP 7. Function. Page 1791 Mar 2008 Siemens ITS STEP 7 Function STEP 7 blocks STEP 7 files all user-written programs and all the data required by those programs in blocks. The possibility of calling other blocks within one block, as though they were

More information

Product type designation. General information. Supply voltage. Input current. Power loss

Product type designation. General information. Supply voltage. Input current. Power loss Data sheet SIMATIC S7-300, CPU 315-2DP CPU WITH MPI INTERFACE INTEGRATED 24 V DC POWER SUPPLY 256 KBYTE WORKING MEMORY 2. INTERFACE DP-MASTER/SLAVE MICRO MEMORY CARD NECESSARY Product type designation

More information

HNC100 Profibus-DP interface: Connection to Siemens S7 and S5

HNC100 Profibus-DP interface: Connection to Siemens S7 and S5 Industrial Hydraulics Electric Drives and Controls Linear Motion and Assembly Technologies Pneumatics Service Automation Mobile Hydraulics HNC100 Profibus-DP interface: Connection to Siemens S7 and S5

More information

General information. Supply voltage. Input current

General information. Supply voltage. Input current Data sheet SIMATIC S7-300, CPU 315F-2DP FAILSAFE CPU WITH MPI INTERFACE INTEGRATED 24V DC POWER SUPPLY, 384 KB WORKING MEMORY, 40MM WIDE, 2. INTERFACE DP- MASTER/SLAVE MICRO MEMORY CARD REQUIRED General

More information

RM30xx Profibus Brief instructions efector400

RM30xx Profibus Brief instructions efector400 RM30xx Profibus Brief instructions efector400 706414/00 Page 1 of 14 ifm efector gmbh Contents The description may contain deviations from the user system, because different manufacturers or software versions

More information

Product type designation. General information. CiR - Configuration in RUN. Input current. Power loss. Memory

Product type designation. General information. CiR - Configuration in RUN. Input current. Power loss. Memory Data sheet SIMATIC S7-400, CPU 412-2 CENTRAL PROCESSING UNIT WITH: 512 KB WORKING MEMORY, (256 KB CODE, 256 KB DATA), 1. INTERFACE MPI/DP 12 MBIT/S, 2. INTERFACE PROFIBUS DP Product type designation General

More information

Connecting UniOP to Simatic S7 Profibus

Connecting UniOP to Simatic S7 Profibus Connecting UniOP to Simatic S7 Profibus This Technical Note contains all the information required to connect the UniOP panels to a Profibus DP system with a Simatic S7 master and to take advantage from

More information

Product type designation. General information. Supply voltage

Product type designation. General information. Supply voltage Data sheet SIMATIC S7-300, CPU 313C-2DP COMPACT CPU WITH MPI, 16 DI/16 DO, 3 FAST COUNTERS (30 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 128 KBYTE WORKING MEMORY, FRONT CONNECTOR (1

More information

Data sheet VIPA CPU 214PG (214-2BE03)

Data sheet VIPA CPU 214PG (214-2BE03) Data sheet VIPA CPU 214PG (214-2BE03) Technical data Order. General information Note - 214-2BE03 VIPA CPU 214PG Features Work memory [KB]: 96 Interface [RJ45]: Ethernet PG/OP communication Interface [RS485]:

More information

Provisional documentation, Profibus-DP and Profi-S-IO Contents

Provisional documentation, Profibus-DP and Profi-S-IO Contents Provisional documentation, Profibus-DP and Profi-S-IO Contents 1 INTRODUCTION 3 2 CONFIGURATION 3 2.1 INTERFACES 3 2.2 POSSIBLE COMBINATIONS 3 2.2.1 Overview 3 2.2.2 Configuration details 4 2.2.3 Recommended

More information

Data sheet CPU 015PN (015-CEFPR01)

Data sheet CPU 015PN (015-CEFPR01) Data sheet CPU 015PN (015-CEFPR01) Technical data Order no. Module ID - General information Note - Features Technical data power supply 015-CEFPR01 CPU 015PN Powered by SPEED7 Work memory [KB]: 256...512

More information

Drive System Application

Drive System Application Drive System Application Commissioning of the Control Unit CU230P-2 DP with PROFIBUS Application description for SINAMICS G120 and MICROMASTER 440 Warranty, liability and support Note The Application Examples

More information

Data sheet VIPA CPU 214NET PG (214-2BT13)

Data sheet VIPA CPU 214NET PG (214-2BT13) Data sheet VIPA CPU 214NET PG (214-2BT13) Technical data Order. 214-2BT13 VIPA CPU 214NET PG General information Note - Features Work memory [KB]: 96 Integrated Ethernet CP 243 Interface [RJ45]: active

More information

Data sheet CC 03, Commander Compact (603-1CC21)

Data sheet CC 03, Commander Compact (603-1CC21) Data sheet CC 03, Commander Compact (603-1CC21) Technical data Order. Type 603-1CC21 CC 03, Commander Compact General information Note - Features Display: 2 x 20 characters Interface: MP²I User memory:

More information

Commander compact. Commander compact Lines displays. System SLIO. System 100V. Lines displays Commander compact 603-1CC CC21.

Commander compact. Commander compact Lines displays. System SLIO. System 100V. Lines displays Commander compact 603-1CC CC21. 0-CC 0-CC Order number 0-CC 0-CC Figure Type CC 0, Commander Compact CC 0DP, Commander Compact, PROFIBUS-DP slave General information Note - - Features x 0 characters, x 0 characters, Integrated PLC-CPU,

More information

SIMATIC. Function modules FM 351 First Steps in Commissioning. Purpose of the Getting Started. Requirements 2

SIMATIC. Function modules FM 351 First Steps in Commissioning. Purpose of the Getting Started. Requirements 2 Purpose of the Getting Started 1 Requirements 2 SIMATIC Function modules FM 351 First Steps in Commissioning Getting Started Installing the configuration package on the PG 3 FM 351, installing and wiring

More information

Product type designation. General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory

Product type designation. General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory Data sheet SIMATIC S7-400, CPU 417-4 CENTRAL PROCESSING UNIT WITH: 30 MB WORKING MEMORY, (15 MB CODE; 15 MB DATA) 1. INTERFACE MPI 12 MBIT/S, 2. INTERFACE PROFIBUS DP, 3./4. IF IFM MODULES PLUGGABLE Product

More information

General information. Supply voltage. Input current

General information. Supply voltage. Input current Data sheet SIMATIC S7-300 CPU 317-2 PN/DP, CENTRAL PROCESSING UNIT WITH 1 MB WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY

More information

General information. Supply voltage. Input current

General information. Supply voltage. Input current Data sheet SIMATIC S7-300 CPU 315-2 PN/DP, CENTRAL PROCESSING UNIT WITH 384 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY

More information

CPU 412H. Function. Parameterizable properties

CPU 412H. Function. Parameterizable properties CPU 412H Function Block protection: In addition to the keylock switch, a password concept protects the user program from unauthorized access. Integrated HMI services: In the case of HMI devices, the user

More information

TECHNICAL NOTE TNOI30

TECHNICAL NOTE TNOI30 TECHNICAL NOTE TNOI30 Title: Profibus DP Slave communication Product(s): G3, Enhanced Modular Controller, and DSP ABSTRACT Red Lion Controls G3 HMI, Modular Controller enhanced master and Data Station

More information

SIPLUS CPU 313C-2DP. Function

SIPLUS CPU 313C-2DP. Function SIPLUS CPU 313C-2DP Function Password protection; a password concept protects the user program from unauthorized access. Block encryption; the functions (FCs) and function blocks (FBs) can be stored in

More information

General information. Supply voltage. Input current

General information. Supply voltage. Input current Data sheet SIMATIC S7-300 CPU315F-2 PN/DP, CENTRAL PROCESSING UNIT WITH 512 KBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE ETHERNET PROFINET, WITH 2 PORT SWITCH, MICRO MEMORY CARD NECESSARY

More information

Data sheet VIPA CPU M13C (M13-CCF0000)

Data sheet VIPA CPU M13C (M13-CCF0000) Data sheet VIPA CPU M13C (M13-CCF0000) Technical data Order no. M13-CCF0000 Type VIPA CPU M13C Module ID - General information Note - Features Technical data power supply Power supply (rated value) Power

More information

User Manual Connection to PROFIBUS-DP

User Manual Connection to PROFIBUS-DP User Manual Connection to PROFIBUS-DP Part Number: 80 860.655 Version: 2 Date: 22.11.2005 Valid for: TSwin.net 4.0x TSwin.net 4.1x Version Date Modifications 1 25.07.2005 First edition 2 22.11.2005 Validation

More information

1 1 Introduction Basics New Functions in DPV Example: Evaluation of Interrupt Information from OB 40 with SFB

1 1 Introduction Basics New Functions in DPV Example: Evaluation of Interrupt Information from OB 40 with SFB ss Product Information Conversion to DPV1 Edition 01/03 Contents 1 1 Introduction 1-1 2 2 Basics 2-1 3 3 New Functions in DPV1 3-1 4 4 Example: Evaluation of Interrupt Information from OB 40 with SFB 54

More information

Configuration and Parameter Assignment Frame for the CPU 31x-2

Configuration and Parameter Assignment Frame for the CPU 31x-2 Configuration and Parameter Assignment Frame for the CPU 31x-2 1 You don t need the information contained in this chapter if you configure and parameterize the CPU 31x-2 with STEP 7 or with COM PROFIBUS.

More information

64 kbyte ; 64 KB / 21K instructions RAM (integrated) Yes ; 4 KB: bit memory, counter, times and data

64 kbyte ; 64 KB / 21K instructions RAM (integrated) Yes ; 4 KB: bit memory, counter, times and data Product data sheet SIMATIC S7-300, CPU 315-2 DP CPU WITH INTEGRATED 24 V DC POWER SUPPLY, 64 KBYTE WORKING MEMORY 2ND INTERFACE DP- MASTER/SLAVE Supply voltage Rated voltage/dc permissible range, lower

More information

SIMATIC. S7 and Profibus- DP Configuration Guide G1026

SIMATIC. S7 and Profibus- DP Configuration Guide G1026 SIMATIC S7 and Profibus- DP Configuration Guide G1026 Preface:... 3 New Project Wizard... 4 HELP... 8 Terminology... 8 Project View... 9 Station View... 9 Processor View...10 Program Module View...10 Configuring

More information

SCHMIDT Sensor interface PROFIBUS Instructions for use

SCHMIDT Sensor interface PROFIBUS Instructions for use SCHMIDT Sensor interface PROFIBUS Instructions for use Table of contents 1 Important information... 3 2 Intended use... 4 3 Electrical connection... 4 4 Signalizations... 7 5 Startup... 9 6 Technical data...

More information

Product type designation. General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory

Product type designation. General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory Data sheet SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT FOR S7-400H AND S7-400F/FH, 5 INTERFACES: 1X MPI/DP, 1X DP, 1X PN AND 2 FOR SYNC MODULES 4 MB MEMORY (2 MB DATA/2 MB CODE) Product type designation

More information

Data sheet VIPA CPU 115DP (115-6BL22)

Data sheet VIPA CPU 115DP (115-6BL22) Data sheet VIPA CPU 115DP (115-6BL22) Technical data Order no. Type 115-6BL22 VIPA CPU 115DP General information Note - Features Work memory [KB]: 16 Load memory [KB]: 24 Onboard 16x DI / 12x DO / 4x DIO

More information

PACSystems* RX3i IC695PBM300

PACSystems* RX3i IC695PBM300 June 2010 PACSystems* RX3i IC695PBM300 PROFIBUS Master Module The PACSystems * RX3i PROFIBUS Master Module, IC695PBM300, allows the RX3i CPU to send and receive data on a PROFIBUS-DP network. The IC695PBM300

More information

S7-400, M7-400 Programmable Controllers

S7-400, M7-400 Programmable Controllers This Supplement contains additional information about the products. It is a separate component and should be considered more up-to-date than the information in the manuals and catalogs if uncertainties

More information

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE C1 Sequencer programming with S7-GRAPH

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE C1 Sequencer programming with S7-GRAPH Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE C1 T I A Training document Page 1 of 66 Module C1 This document was provided by Siemens A&D SCE (automation

More information

SIMATIC. Communications processor CP First Steps in Commissioning. Getting Started 09/2008 A5E

SIMATIC. Communications processor CP First Steps in Commissioning. Getting Started 09/2008 A5E SIMATIC Communications processor Getting Started 09/2008 A5E02291899-01 Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety,

More information

CPU 317F-2 DP. Page 1603 Mar 2008 Siemens ITS

CPU 317F-2 DP. Page 1603 Mar 2008 Siemens ITS CPU 317F-2 DP Function Password protection; a password concept protects the user program from unauthorized access. Diagnostics buffer; the last 100 errors and interrupt events are saved in a buffer for

More information

General information. Display. Control elements. Supply voltage

General information. Display. Control elements. Supply voltage Data sheet SIMATIC S7-1500F, CPU 1513F-1 PN, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 450 KB FOR PROGRAM AND 1.5 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 40 NS BIT-PERFORMANCE, SIMATIC

More information

FAQ about Drive Technology

FAQ about Drive Technology FAQ about Drive Technology Technology CPU Upgrading the CPU Type in a STEP7 Project FAQ Table of Contents Table of Contents... 2 Question... 3 How can I replace the configured Technology CPU by another

More information

General information. Configuration control. Display. Control elements. Supply voltage

General information. Configuration control. Display. Control elements. Supply voltage Data sheet SIMATIC S7-1500, CPU 1513-1 PN, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 300 KB FOR PROGRAM AND 1.5 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 40 NS BIT-PERFORMANCE, SIMATIC

More information

6ES7151-8AB01-0AB0. 5/18/2011 Siemens Industry IA/DT/BT Service&S. siemens.com/ww/llisapi.dll?func=csl 1/10 ET200S, IM151-8 PN/DP CPU, 192 KB

6ES7151-8AB01-0AB0. 5/18/2011 Siemens Industry IA/DT/BT Service&S. siemens.com/ww/llisapi.dll?func=csl 1/10 ET200S, IM151-8 PN/DP CPU, 192 KB Automation Technology > Automation Systems > Industrial Automation Systems SIMATIC > Distributed I/Os SIMATIC ET200 > ET 200 systems for the cabinet > ET 200S > Interface modules > Interface modules with

More information

Product type designation. General information. Supply voltage. Input current. Power losses

Product type designation. General information. Supply voltage. Input current. Power losses Data sheet SIMATIC S7-300, CPU317-2 DP, CENTRAL PROCESSING UNIT WITH 1 MBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE DP-MASTER/SLAVE, MICRO MEMORY CARD NECESSARY Product type designation

More information

CPU 319F-3 PN/DP. Page 1682 Mar 2008 Siemens ITS

CPU 319F-3 PN/DP. Page 1682 Mar 2008 Siemens ITS CPU 319F-3 PN/DP Function Password protection; a password concept protects the user program from unauthorized access. Diagnostics buffer; the last 100 error and interrupt events are stored in a buffer

More information

General information. Display. Control elements. Supply voltage

General information. Display. Control elements. Supply voltage Data sheet SIMATIC S7-1500F, CPU 1516F-3 PN/DP, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 1,5 MB FOR PROGRAM AND 5 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 2. INTERFACE: ETHERNET,

More information

General information. Configuration control. Display. Control elements. Supply voltage

General information. Configuration control. Display. Control elements. Supply voltage Data sheet SIMATIC S7-1500, CPU 1516-3 PN/DP, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 1 MB FOR PROGRAM AND 5 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 2. INTERFACE: ETHERNET, 3. INTERFACE:

More information

OPERATION MANUAL. PROFIBUS Model 9163

OPERATION MANUAL. PROFIBUS Model 9163 OPERATION MANUAL PROFIBUS Model 9163 2008 burster präzisionsmesstechnik gmbh & co kg All rights reserved Manufacturer: burster praezisionsmesstechnik gmbh & co kg Talstrasse 1 5 P.O. Box 1432 76593 Gernsbach,

More information

FACTORY AUTOMATION. MANUAL Absolute Rotary Encoder with PROFIBUS Interface

FACTORY AUTOMATION. MANUAL Absolute Rotary Encoder with PROFIBUS Interface FACTORY AUTOMATION MANUAL Absolute Rotary Encoder with PROFIBUS Interface R With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss Data sheet SIMATIC S7-1500, CPU 1516-3 PN/DP, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 1 MB FOR PROGRAM AND 5 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 2. INTERFACE: ETHERNET, 3. INTERFACE:

More information

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss Data sheet SIMATIC S7-1500, CPU 1515-2 PN, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 500 KB FOR PROGRAM AND 3 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 2. INTERFACE: ETHERNET, 30 NS

More information

NDI series displays with Profibus-DP UNI-TXT (ND) protocol

NDI series displays with Profibus-DP UNI-TXT (ND) protocol NDI series displays with Profibus-DP UNI-TXT (ND) protocol PARAMETRIZATION OF PROFIBUS-DP COMMUNICATION INTERFACE - 1 - CONTENT 1. INTRODUCTION... 3 2. GSD FILE INSTALLATION... 3 3. EXAMPLE PROJECT ELEN_UNI-TXT(ND)...

More information

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss

General information. Configuration control. Display. Control elements. Supply voltage. Input current. Power. Power loss Data sheet SIMATIC S7-1500, CPU 1511-1 PN, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 150 KB FOR PROGRAM AND 1 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 60 NS BIT-PERFORMANCE, SIMATIC

More information

First Steps with S7-PDIAG and ProAgent

First Steps with S7-PDIAG and ProAgent s SIMATIC S7-PDIAG for S7-300 and S7-400 Configuring Process Diagnostics Getting Started Edition 07/2005 First Steps with S7-PDIAG and ProAgent The Getting Started for This product is not a stand-alonedescription.

More information

Service & Support. Data Communication between S7 Station and PC Station, using SIMATIC NET OPC Server SIMATIC S7. Function description March 2013

Service & Support. Data Communication between S7 Station and PC Station, using SIMATIC NET OPC Server SIMATIC S7. Function description March 2013 Cover Data Communication between S7 Station and PC Station, using SIMATIC NET OPC Server Explanation of the Functionality of the S7 Variable Service, from the View of a SIMATIC User SIMATIC S7 Function

More information

TIA Portal Workshop. Unrestricted. Siemens AG All rights reserved.

TIA Portal Workshop. Unrestricted. Siemens AG All rights reserved. TIA Portal Workshop Unrestricted Siemens AG 2015. All rights reserved. SIMATIC S7-1500: Modular Controller for the Mid to Upper Performance Range Page 11 Siemens AG 2015 SIMATIC S7-1500: Modules Single-tier

More information

General information. Supply voltage. Input current

General information. Supply voltage. Input current Data sheet SIMATIC S7-300 CPU319F-3 PN/DP, CENTRAL PROCESSING UNIT WITH 2.5 MBYTE WORKING MEMORY, 1. INTERFACE MPI/DP 12MBIT/S, 2. INTERFACE DP-MASTER/SLAVE, 3. INTERFACE ETHERNET PROFINET, WITH 2 PORT

More information

SIMATIC S7-300 Product information for the S7-300 Automation System Manual, Module Data

SIMATIC S7-300 Product information for the S7-300 Automation System Manual, Module Data SIMATIC S7-300 Product information for the S7-300 Automation System Manual, Data Product Information Introduction The present product information describes additions and corrections to the S7-300 Automation

More information

TS8000. Profibus DP Slave Configuration Application Note TS8922U001

TS8000. Profibus DP Slave Configuration Application Note TS8922U001 TS8000 TS8922U001 Copyright SSD Drives, Inc. 2006 All rights strictly reserved. No part of this document may be stored in a retrieval system, or transmitted in any form or by any means to persons not employed

More information

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE B5 Structured programming with function blocks

Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE B5 Structured programming with function blocks Training document for the company-wide automation solution Totally Integrated Automation (T I A) MODULE B5 T I A Training document Page 1 of 20 Module B5 This document was provided by Siemens A&D SCE (automation

More information

Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366

Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366 Supplementary device manual AS-i controller e with Profibus DPV1 A AC1355, AC1356 AC1365, AC1366 AS-i master profile: M4 Firmware: from version RTS 3.0 onwards Target: from V.15 onwards for CoDeSys from

More information

How can you display error messages and warnings of a frequency converter on a panel? WinCC flexible RT and Panels FAQ

How can you display error messages and warnings of a frequency converter on a panel? WinCC flexible RT and Panels FAQ Cover How can you display error messages and warnings of a frequency converter on a panel? WinCC flexible RT and Panels FAQ February 2011 Service & Support Answers for industry. Question This entry is

More information

Product type designation

Product type designation Data sheet SIMATIC DP, CPU 1512SP-1 PN FOR ET 200SP, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 200 KB FOR PROGRAM AND 1 MB FOR DATA, 1. INTERFACE, PROFINET IRT WITH 3 PORT SWITCH, 48 NS BIT-PERFORMANCE,

More information

General information. Engineering with. Supply voltage. Load voltage L+ Input current. Power losses. Memory. Work memory.

General information. Engineering with. Supply voltage. Load voltage L+ Input current. Power losses. Memory. Work memory. Product data sheet SIMATIC S7-300, CPU 314C-2DP COMPACT CPU WITH MPI, 24 DI/16 DO, 4AI, 2AO, 1 PT100, 4 FAST COUNTERS (60 KHZ), INTEGRATED DP INTERFACE, INTEGRATED 24V DC POWER SUPPLY, 64 KBYTE WORKING

More information

IE/PB LINK PN IO. PROFINET applications

IE/PB LINK PN IO. PROFINET applications IE/PB LINK PN IO PROFINET applications Protection of investment due to simple connection of PROFIBUS DP slaves to PROFINET IO controller Enables the use also in plants with PROFIsafe applications Independence

More information

Profibus Getting Started User's Manual

Profibus Getting Started User's Manual www.infoplc.net Profibus Getting Started User's Manual Version: 1.00 (July 2006) Model No.: MAPBGETST-ENG We reserve the right to change the contents of this manual without warning. The information contained

More information

SIMATIC S Update to the S System Manual, edition 03/2014 Product Information

SIMATIC S Update to the S System Manual, edition 03/2014 Product Information SIMATIC S7-1200 Product Information In spite of efforts to ensure the accuracy and clarity in the product documentation, some of the pages in the S7-1200 Programmable Controller System Manual contain information

More information

OPERATOR INTERFACE PRODUCTS APPLICATION NOTE

OPERATOR INTERFACE PRODUCTS APPLICATION NOTE Page: 1 of 5 Description: The Profibus driver has 2 modes of operation for data transfer: Direct I/O and Packet Transfer. This document explains implementing the Direct I/O method of addressing. An associated

More information

ProfinetCommander User Manual 3.1 March 2010

ProfinetCommander User Manual 3.1 March 2010 ProfinetCommander User Manual 3.1 March 2010-1 - ProfinetCommander User Manual V3.1 Table of Contents ProfinetCommander...1 User Manual...1 1.0 Version History...2 2.0 Introduction...3 3.0 Hardware and

More information

Impressum. Internet:

Impressum.   Internet: Impressum leere Seite leere Seite Imprint Wachendorff Automation Industriestrasse 7 D-65366 Geisenheim Phone: +49 (0) 67 22 / 99 65 25 Fax: +49 (0) 67 22 / 99 65 70 Local Court of Wiesbaden HRA 8377 VAT

More information

Data sheet CPU 015PN (015-CEFPR00)

Data sheet CPU 015PN (015-CEFPR00) Data sheet CPU 015PN (015-CEFPR00) Technical data Order no. 015-CEFPR00 CPU 015PN Module ID - General information Note - Features Technical data power supply Power supply (rated value) Power supply (permitted

More information

ENCODER SERIES Pxx WITH PROFIBUS-DP INTERFACE

ENCODER SERIES Pxx WITH PROFIBUS-DP INTERFACE Profibus-DP Documentation ENCODER SERIES Pxx WITH PROFIBUS-DP INTERFACE PxxDocSTD R3/06/00 1 CONTENTS: 1. Mechanical installation:... 3 2. Electric installation:... 3 2.1 Connections... 3 2.2 Termination...

More information

Aotewell SIMATIC S7-PDIAG for S7-300 and S Configuring Process Diagnostic Getting St

Aotewell   SIMATIC S7-PDIAG for S7-300 and S Configuring Process Diagnostic Getting St SIMATIC S7-PDIAG for S7-300 and S7-400 - Configuring Process Diagnostic Getting Started Edition 01/2003 First Steps with S7-PDIAG and ProAgent The Getting Started for This product is not a stand-alonedescription.

More information

SIMATIC NET. S7-CPs for PROFIBUS. CP Extended for PROFIBUS. Manual Part B4

SIMATIC NET. S7-CPs for PROFIBUS. CP Extended for PROFIBUS. Manual Part B4 SIMATIC NET S7-CPs for PROFIBUS Manual Part B4 CP 443-5 Extended for PROFIBUS 6GK7 443-5DX04-0XE0 Version 1 or higher (Firmware Version V6.1 or higher) for SIMATIC S7-400 / S7-400H Status and fault LEDs

More information

Data sheet CPU 013C (013-CCF0R00)

Data sheet CPU 013C (013-CCF0R00) Data sheet CPU 013C (013-CCF0R00) Technical data Order no. 013-CCF0R00 Type CPU 013C Module ID - General information Note - Features Technical data power supply Power supply (rated value) Power supply

More information

Manual. MOVIAXIS MX Fieldbus Interface XFP11A PROFIBUS DP. Edition 04/2006 FB / EN

Manual. MOVIAXIS MX Fieldbus Interface XFP11A PROFIBUS DP. Edition 04/2006 FB / EN Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ Services MOVIAXIS MX Fieldbus Interface XFP11A PROFIBUS DP Edition 4/26 11355514 / EN FB41111 Manual SEW-EURODRIVE Driving the

More information

Manual Beginners manual Hardware configuration Series xx7

Manual Beginners manual Hardware configuration Series xx7 Manual Beginners manual Hardware configuration Series xx7 Document 26/835; Edition EN02 2013-12-13 Content 0 Inhalt 0 Inhalt 0.1 Document History... 0-2 0.2 Brands and trademarks... 0-2 0 1 Introduction

More information

Table of contents chapter 1:

Table of contents chapter 1: Table of contents chapter 1: 1. Characteristics of the Lumberg e2c-system...2 2. The e2c-components...3 2.1 The e2c-backplane...3 2.2 The e2c-plugbox...4 2.3 The e2c BusHead...5 2.4 The e2c I/O modules...6

More information

Data sheet CPU 315SB/DPM (315-2AG12)

Data sheet CPU 315SB/DPM (315-2AG12) Data sheet CPU 315SB/DPM (315-2AG12) Technical data Order no. 315-2AG12 CPU 315SB/DPM General information Note - Features SPEED-Bus - SPEED7 technology 1 MB work memory Memory extension (max. 2 MB) PROFIBUS-DP

More information

General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory

General information. CiR - Configuration in RUN. Supply voltage. Input current. Power loss. Memory Data sheet SIMATIC S7-400, CPU 412-2 PN CENTRAL PROCESSING UNIT WITH: 1 MB WORKING MEMORY, (0,5 MB CODE; 0,5 MB DATA) INTERFACES: 1. IF MPI/DP 12 MBIT/S (X1), 2. IF ETHERNET/PROFINET (X5), General information

More information

General information. Display. Control elements. Supply voltage

General information. Display. Control elements. Supply voltage Data sheet SIMATIC S7-1500F, CPU 1511F-1 PN, CENTRAL PROCESSING UNIT WITH WORKING MEMORY 225 KB FOR PROGRAM AND 1 MB FOR DATA, 1. INTERFACE: PROFINET IRT WITH 2 PORT SWITCH, 60 NS BIT-PERFORMANCE, SIMATIC

More information