1 Safety Application Example Using GuardShield Light Curtains (Safe 4, Micro 400, or 440L), with ArmorBlock Guard I/O and SmartGuard Controller Light Curtain with On-machine Components Safety Rating: Category 4, according to EN954-1 Introduction... 1 Important User Information... 2 General Safety Information... 3 Description... 3 Setup and Wiring... 4 Configure... 8 Safety System Demonstration Additional Resources Introduction This application example describes how to connect the GuardShield safety light curtain to an ArmorBlock Guard I/O module and control 700S safety contactors with a SmartGuard 600 safety controller. Features and Benefits On-machine installation with quick disconnect wiring Light curtain detection Programmable safety logic
2 2 Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. Identifies information that is critical for successful application and understanding of the product. Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
3 3 General Safety Information This application example is for advanced users and assumes that you are trained and experienced in safety system requirements. A risk assessment should be performed to make sure all task and hazard combinations have been identified and addressed. The risk assessment may require additional circuitry to reduce the risk to a tolerable level. Safety circuits must take into consideration safety distance calculations which are not part of the scope of this document. Contact Rockwell Automation to find out more about our safety risk assessment services. Description This machine safeguarding example shows the wiring configuration and programming setup for an application where the SmartGuard 600 controller controls a GuardShield light curtain that is connected to an ArmorBlock Guard I/O module. The SmartGuard 600 controller is programmed using RSNetWorx for DeviceNet software. You must be familiar with that software to use this document. Safety Function Access to the hazardous area is allowed during all parts of the machine cycle. When the light curtain field is blocked by an object (for example a hand or arm), the hazards monitored by the light curtain must stop before the operator can reach them. While the light curtain is blocked, the hazards cannot restart. When the light curtain is cleared, the hazards will not restart. A separate action, such as pressing the restart button, must initiate the hazards. For this example, the hazards are controlled by the two 700S Safety control relays.
4 4 Example Bill of Materials This application example uses these components. You can use any one of the three GuardShield light curtain options. Catalog Number 440L-P4J1280YD 445L-P4L1320YD 445L-P4C1200 FP Light Curtain Option 400L GuardShield light curtain 14mm resolution, 1280mm protected height GuardShield Safe 4 light curtain GuardShield Micro 400 light curtain Catalog Number Description Quantity See above GuardShield light curtain 1 871A-TS5-DM1 and 889D-F8AB-5 Field-attachable 5-pin QD cordset, 8-pin micro QD, 5m, female DS-IB8XOBV4 ArmorBlock Guard I/O module L24BBB SmartGuard 600 safety controller 1 700S-CFB440DLC Safety control relay 2 800FM-F6MX10 Push button (reset) 1 Setup and Wiring For detailed information on installing and wiring, refer to the product manuals listed in the Additional Resources on page 20. The three diagrams on the following pages illustrate the wiring for each of the three light curtains listed in the Example Bill of Materials.
5 5 Wiring for GuardShield Light Curtain 440L-P4J1280YD
6 6 Wiring for GuardShield Safe 4 Light Curtain 445L-P4L1320YD
7 7 Wiring for GuardShield Micro 400 Light Curtain 445L-P4C1200 FP
8 8 Configure Light curtains must be installed so that operators cannot access the hazard by reaching over, under, or around the light curtain. The location of the light curtain with respect to the hazard must take into account the response time of the safety system to shut down the hazard. Safety system response time is dependent on the actual configuration of the system. The operator must not be able to reach through the light curtain and reach the hazard until it is brought to a safe state. GuardShield 440L Light Curtain When connected to the ArmorBlock Guard I/O module, the light curtain cannot perform the following functions as the connections are not available: No external device monitoring (EDM) No auxiliary output signal The EDM function is performed by the SmartGuard 600 controller. The SmartGuard 600 controller can also generate an auxiliary signal to indicate the status of the light curtain, but this is not included in this application example. In Guard Only mode, the output of the light curtain turns off when the light curtain is interrupted and turns back on immediately when the light curtain is cleared. In Restart Interlock mode, the light curtain output turns off immediately when interrupted but does not turn back on until the scanning area is clear and an external restart signal is received. This application example uses the Restart Interlock function of the light curtain. The switch settings of the GuardShield receiver are as follows. DIP Switch Setting Function 1 OFF Interlock at interruption of the sensing area, restart 2 OFF by actuation of a momentary signal. 3 ON EDM disabled. 4 OFF Fixed blanking disabled. 5 OFF Floating blanking disabled. 6 OFF 7 OFF Beam coding disabled 8 OFF Not used. The GuardShield 440L sender switch settings remain in the factory default configuration.
9 9 GuardShield 445L Safe 4 Light Curtain The GuardShield Safe 4 light curtain does not have dipswitches and does not require any physical configuration changes. However, the SmartGuard 600 controller and ArmorBlock Guard I/O module configuration and programming sections in the example assume that the light curtain was wired properly in accordance with the wiring diagram on page 6. GuardShield 445L Micro 400 Light Curtain The GuardShield Micro 400 light curtain doesn not have dipswitches and does not require any physical configuration changes. However, since the Micro 400 light curtain is a three-box system, it must be wired to an MSR42 safety relay as shown in the wiring diagram on page 7. RSNetWorx for DeviceNet Software This application example uses three devices that can be seen in the graphics tab of RSNetWorx for DeviceNet software. Node 1 is used to configure and program the SmartGuard Controller (node 2) and the ArmorBlock Guard I/O module (node 3). See the SmartGuard 600 Controller Safety Reference Manual, publication 1752-RM001 for instructions on setting up the network.
10 10 ArmorBlock Module Setup The light curtain is connected to Input Position A of the AmorBlock Guard I/O module. The connector has five pins, which perform the following functions. Pin Name GuardShield 440L and Micro 400 Light Curtains Function GuardShield Safe 4 Light Curtain 1 Test Output 1 Restart interlock signal +24V supply 2 Safe Input 1 OSSD1 (safety output 1) OSSD2 (safety output 2) 3 Input Common 24V common 24V common 4 Safe Output 0 OSSD2 (safety output 2) OSSD1 (safety output 1) 5 Test Output 0 +24V supply Shield 1. On the network graph (in the offline mode), double-click the node 3 icon. 2. Click the Safety Configuration tab. Set Up Input Points The Safety Configuration for the inputs and test outputs must be set up as shown below. The light curtain does not use an output connection. 1. Double-click the Input Points 00/01 line. Position A corresponds to Input Points 00/01.Since this is a dual channel circuit with OSSD connections, the operation (parameter 55) is selected to be Equivalent, that is, both signals should open and close at the same time and should always be in the same state. 2. Click the current value field of parameter 55.
11 11 3. From the pull-down menu, choose Equivalent. The modes for both channels (parameters 25 and 29) are set to Safety, as they perform a safety function. Since the light curtain performs its own crossfault (Channel 1 to Channel 2 short) checking, you do not need to set up pulse testing. The Test Sources remain set to None. Test Output Points Two test outputs are assigned. 1. Scroll down and double-click Test Output Points. 2. Set Test Output 00 and Test Output 01 as shown in the table. Test Output GuardShield 440L and Micro 400 Light Curtains Function GuardShield Safe 4 Light Curtain 00 Power Supply Not Used 01 Standard Power Supply Test Output 01 is used to restart the light curtain. The remaining test outputs are not used.
12 12 GuardShield 440L and Micro 400 Light Curtains GuardShield Safe 4 Light Curtain No output points are used in this application. The 700S safety control relays are controlled by the SmartGuard 600 controller. 3. When completed, click Apply. 4. Click OK.
13 13 SmartGuard Controller Connections Two connections, an input and an output, are set for the SmartGuard controller when using GuardShield 440L light curtains. For GuardShield Safe 4 and Micro 400 light curtains, only the input connection is required. Input Connections Follow these steps to create an input connection. 1. In the graph view, double-click the SmartGuard controller icon to open the Controller Properties dialog box. 2. Click the Safety Connection tab.
14 14 3. Double-click the 1732DS line to add connections. 4. For the Connection Name, choose [IN] Safety. 5. Set the Connection type to Point to Point or Multicast. 6. Click Add. 7. If you are using a GuardShield Safe 4 light curtain, go to Review and Apply Connections on page 15. Otherwise, continue with Output Connection (GuardShield 440L and Micro 400 Light Curtains). Output Connection (GuardShield 440L and Micro 400 Light Curtains) 1. Double-click the 1732DS line to add the output connection. 2. Choose [OUT] Test for the output Connection Name. This signal powers the restart of the light curtain. 3. Choose Point to Point for the Connection Type. The signal is intended to go to only one point, the GuardShield light curtain. This is treated as a test signal from the input connection, but it is not a pulsed test signal.
15 15 4. Click Add. Review and Apply Connections GuardShield 440L and Micro 400 Light Curtains 1. After completing the safety connection selections, expand the connections by clicking on the + signs. 2. Use the vertical scroll bar to review the connections and click Apply. GuardShield Safe 4 Light Curtain
16 16 SmartGuard Controller I/O Setup This section describes how to set up the local input and output of the SmartGuard controller. The restart button is connected to an input of the SmartGuard controller. The SmartGuard controller outputs turn on two 700S safety control relays. The status of the 700S relays is fed back as an input to the SmartGuard controller. So this application needs two inputs, one pulse test output and two outputs. 1. Click the Local Input/Test Output tab. The General tab lists the inputs. 2. Set up the inputs as shown below. The restart input is a standard input. The relay feedback signal is pulse tested to check for potential faults (shorts to 24V). The wire connected to Terminal 0 of the SmartGuard controller is used to restart (to energize) the output of the 700S safety relays.
17 17 3. Set I/O Comment to Restart Button. 4. Set the channel mode parameter to Used as standard input and the Dual Channel Mode to Single Channel, as shown. 5. Click OK. The wire connected to Terminal 1 of the SmartGuard controller provides safety status information about the 700S safety relays. 6. Set the I/O comment to Relay Feedback. This is used as a single channel that with a pulse test. Note the Channel mode is set to Test pulse from test out. 7. Set the Test Source to Test Output 0.
18 18 8. Set the Dual Channel mode parameter to Single Channel. 9. Click OK. 10. Click the Local Input/Test Output tab. 11. Double-click the 00 line (or highlight the line and click Edit).
19 Set the mode for Test Output 00 as Pulse Test Output. This is used to check the integrity of the status signal from the 700S safety control relays. Set Up Outputs Follow these steps to set up each output. 1. Click the Local Output tab. 2. When finished, click Apply. 3. Double-click the 00 line (or highlight the line and click Edit). 4. Type a description of the device in the I/O Comment field.
20 20 5. Set the Channel Mode to Safety Pulse Test. Operation of the relays is a safety function. 6. Set Dual Channel > Channel Mode to Dual Channel. Dual relays are used. When this selection is made for the first device, the second device is automatically set for Dual Channel. 7. Double-click the 01 line. 8. Repeat steps 4 6 for the second output. When you are finished, both outputs are configured.
21 21 SmartGuard Controller Logic This section shows how to set up the logic and save it. 1. Click the Logic tab. 2. Click Edit. 3. Set up the logic as shown in the diagrams below. GuardShield 440L and Micro 400 Light Curtains GuardShield Safe 4 Light Curtain 4. When finished, click File. 5. Click Apply. 6. Exit to return to the 1752-L24BBB window. 7. Click Apply and then OK.
22 22 8. In the RSNetWorx window, click the Online button. 9. Save the file with an appropriate name. 10. Click Yes to upload or download. RSNetWorx software begins to browse the network. 11. When the three nodes are found, click Cancel to stop the browsing. 12. Right-click the SmartGuard controller icon (node 2). 13. Select Download to Device and click Yes. 14. Right-click the ArmorBlock icon (node 3). 15. Select Download to Device and click Yes. 16. Double-click the SmartGuard icon. 17. Click the Mode/Cycle Time tab. 18. Click Change Mode.
23 In the Change Mode dialog box, click Execute. 20. Click OK. The SmartGuard controller is now in Run mode. Both the MS and NS status indicators on the SmartGuard controller are solid green. The Network and Module status indicators on the ArmorBlock Guard I/O module are solid green. Safety System Demonstration Follow these steps to monitor the operation of the safety system. 1. In the 1752-L24BBB window, click the Logic tab. 2. Click Edit. 3. In the Logic window, click Function > Monitor Device. The icons in the logic diagram are color-coded. The Relay Feedback should be bright green, as the signal is present because the normally closed contacts of the relays are closed. The outputs are colored blue and are off. 4. Press and hold the restart button. The restart button icon turns bright green. 5. Release the restart button. The restart button turns light green. The 700S safety control relays energize and their icons turn bright green. 6. Place an object in the light curtain field. The 700S safety contactors de-energize. 7. Press the restart button with the object in the field. The 700S safety control relays remain de-energized. 8. Remove the object from the light curtain. The 700S relays remain off. 9. Block the light curtain.
24 Press and hold the restart button. 11. While holding the restart button, remove the object from the light curtain field. The 700S safety relays remain off. 12. Release the restart button. The 700S safety relays remain off. 13. Press and release the restart buttons to energize the 700S safety control relays. Additional Resources For more information about the products used in this example, refer to these resources. Resource ArmorBlock Guard I/O Module Installation Instructions, publication 1732DS-IN001 Guard I/O DeviceNet Safety Modules User Manual, publication 1791DS-UM001 SmartGuard 600 Controller Safety Reference Manual, publication 1752-RM001 Description Provides installation instructions for the ArmorBlock Guard I/O DeviceNet Safety Module. Provides general safety guidelines on using Guard I/O DeviceNet Safety Modules. Provides instructions for using SmartGuard 600 Controller. Safety Products Catalog, publication S116 Provides information on Guardshield Light Curtains. You can view or download publications at To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative. Allen-Bradley, ArmorBlock Guard I/O, Rockwell Automation, RSNetWorx, and SmartGuard are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Supersedes Publication SAFETY-AT013B-EN-P March 2009 Copyright 2009 Rockwell Automation, Inc. All rights reserved. Printed in U.SA.
Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller
Safety Application Example Using TLS3-GD2 Guardlocking Interlock with ArmorBlock Guard I/O and SmartGuard Controller Guardlocking with On-machine Components Safety Rating: Category 3, according to EN954-1
More informationUsing a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller
Safety Application Example Using a Guard Locking Interlock Switch and Light Curtains with DeviceNet Guard I/O and a GuardLogix Controller Safety Rating: Category 3, according to EN954-1 Introduction...
More informationGuardLogix: Safety Gate Application with SensaGuard Switch
Safety Application Example GuardLogix: Safety Gate Application with SensaGuard Switch Safety Rating: PLe, Cat. 4 to EN ISO 13849.1 2008 Introduction...2 Important User Information...2 General Safety Information...3
More informationGuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch
Safety Application Example GuardLogix: Dual Zone Gate Protection with E-stop and Trojan Interlock Switch Safety Rating: PLd, Cat. 3 to EN ISO 13849.1 2008 Introduction... 2 Important User Information...
More informationGuardLogix: TLS Guardlocking Application
Safety Application Example GuardLogix: TLS Guardlocking Application Safety Rating: PLd, Cat. 3 to EN ISO 13849.1 2008 Introduction... 2 Important User Information... 2 General Safety Information... 3 Description...
More informationPowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller
Safety Application Example PowerFlex 70 Safe-Off Control EtherNet/IP Guard I/O Safety Module and GuardLogix Integrated Safety Controller Safety Rating: Category 3 (also see Achieving a Cat. 4 Safety Rating)
More informationApplication Technique. Safety Function: Safety Camera with E-stop
Application Technique Safety Function: Safety Camera with E-stop Products: Guardmaster Dual-input Safety Relay, Guardmaster SC300 Safety Camera Safety Rating: PLd, Cat. 3 to EN ISO 13849-1: 2008 2 Safety
More informationGuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module
Safety Application Example GuardLogix Controller to Kinetix 6000 Drive with Safe-Off using EtherNet/IP CompactBlock Guard I/O Module Safety Rating: SIL3/Category 3 (also see SIL3/CAT4 section), according
More informationUsing the Safety Distribution R Box
Safety Application Example Using the Safety Distribution R Box Introduction...2 Important User Information...2 General Safety Information...3 Description...4 SensaGuard Connections...8 Tongue Interlock
More informationInView Firmware Update
Installation Instructions InView Firmware Update Topic Page Hazardous Voltage 3 Change EPROM on 2706-P72, 2706-P74 Display 3 Change EPROM on 2706-P42, 2706-P44 Displays 5 Firmware Upgrade Kit 7 2 InView
More informationPCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer
Installation Instructions PCI Expansion Slot Kit for 6181P (1500P) Series D Integrated Display Computer Catalog Number 6189V-2PCI15R Topic Page About This Publication 1 Important User Information 2 Safety
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Cable Pull Switch - Products: GuardLogix Series Connection of Cable Pull Switches Safety Rating: PLd, Cat. 3 to EN ISO 13849-1: 2008 Table
More informationTeaching Color-Sensing Connected Components Building Block. Quick Start
Teaching Color-Sensing Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.
More informationKinetix 6000 Axis Module and Shunt Module
Installation Instructions Kinetix 6000 and Shunt Module Catalog Numbers 2094-AMxx, 2094-BMxx 2094-AMxx-S, 2094-BMxx-S 2094-BSP2 Topic Page About This Publication 1 Important User Information 2 Before You
More informationBidirectional (4-sensor, T-type) Muting With MSR42 Relay Connected Components Building Block
Bidirectional (4-sensor, T-type) Muting With MSR42 Relay Connected Components Building Block Catalog Numbers MSR42, MicroLogix 1100, GuardShield Micro 400 Light Curtains Quick Start Important User Information
More informationPowerMonitor 5000 Unit Catalog Number Upgrade
Installation Instructions PowerMonitor 5000 Unit Catalog Number Upgrade Catalog Numbers 1426-MxE-xxx Topic Page Upgrade the Device Catalog Number with the ControlFLASH Utility 3 Determine Communication
More informationColor-Sensing Connected Components Building Block. Quick Start
Color-Sensing Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety
More informationBidirectional (2-sensor, T-type) Muting With Enable Using MSR42 Relay Connected Components Building Block
Bidirectional (2-sensor, T-type) Muting With Enable Using MSR42 Relay Connected Components Building Block Catalog Numbers MSR42, MicroLogix 1100, GuardShield Micro 400 Light Curtains Quick Start Important
More informationControlLogix SIL2 System Configuration
ControlLogix SIL2 System Configuration Using RSLogix 5000 Subroutines Application Technique (Catalog Numbers 1756 and 1492) Important User Information 8 / 2011 Solid state equipment has operational characteristics
More informationDriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual.
DriveGuard Safe-Off Option for PowerFlex 70 AC Drives User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical
More informationSolar Combiner Enclosure
Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the
More informationAllen-Bradley Motors
Installation Instructions Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers Purpose Firmware Update Kit Contents Hardware and Software Requirements This
More informationSmartGuard 600 Controllers
SmartGuard 600 Controllers Catalog Number 1752-L24BBB Safety Reference Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical
More informationAdapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout
Installation Instructions Adapter Kit for PanelView 1200/1200e Touch Screen Terminal Cutout Catalog Numbers 2711-NR5T, 2711P-RAT12E2 Topic Page About This Publication 1 Important User Information 2 About
More informationSimple Package Measurement Connected Components Building Block. Quick Start
Simple Package Measurement Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS SensaGuard Non-contact Interlock Switch with E-stop Table of Contents: Important User Information 45 General Safety Information 45 Introduction
More informationPowerMonitor 1000 Unit Catalog Number Upgrade
Installation Instructions PowerMonitor 1000 Unit Catalog Number Upgrade Catalog Numbers 1408-UPT1-E3, 1408-UPT2-E3, 1408-UPE1-E3, 1408-UPE2-E3, 1408-UP485-ENT, 1408-UPT3-E3 Topic Important User Information
More informationProcessLogix R510.0 Server Installation Instructions
ProcessLogix R510.0 Server Installation Instructions Installation Instructions Before you begin... This publication guides you through the remaining processes required to initialize a ProcessLogix Server.
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Emergency Stop Table of Contents: Introduction 6-121 Important User Information 6-121 Safety Function Realization 6-122 General Safety Information
More informationLogix5000 Controllers Produced and Consumed Tags
Logix5 Controllers Produced and Consumed Tags Catalog Numbers 1756 ControlLogix, 1756 GuardLogix, 1768 Compact GuardLogix, 1769 CompactLogix, 1789 SoftLogix, PowerFlex with DriveLogix Programming Manual
More informationDeviceNet Communications
DeviceNet Communications For PanelView Plus and PanelPlus CE Terminals 2711P User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical
More informationDigital ac/dc (24V) Input Module
Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge
More informationImport/Export Project Components. Programming Manual
Import/Export Project Components Programming Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
More informationSafety Function: Door Locking and Monitoring Products: TLS3-GD2 GuardLogix Controller POINT Guard Safety I/O Modules
Safety Function: Door Locking and Monitoring Products: TLS3-GD2 GuardLogix Controller POINT Guard Safety I/O Modules Safety Rating: PLe, Cat. 4 to EN ISO 13849.1 2008 Table of Contents Introduction 3 Important
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS E-Stop Safety Function Table of Contents: Introduction 6-18 Important User Information 6-18 General Safety Information 6-19 Safety Function Realization
More informationDifferential Liquid/Gas Pressure Transmitter
Installation Instruction Differential Liquid/Gas Pressure Transmitter Catalog Number(s) 1414-CPZ10FWFAA, 1414-IPZ10FWFAA Explosion Hazard WARNING Do not use in an explosive or hazardous environment, with
More informationSafety Function: Muting Products: Light Curtain RightSight Optical Sensors GuardLogix Controller
Safety Function: Muting Products: Light Curtain RightSight Optical Sensors GuardLogix Controller Safety Rating: PLe, Cat. 4 to EN ISO 13849.1 2008 Table of Contents Introduction 3 Important User Information
More informationSafety Function: Safety Camera
Safety Function: Safety Camera Products: SC300 Safety Camera, GuardLogix Controller Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008 Application Technique 2 Safety Function: Safety Camera Important User
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Light Curtain Table of Contents: Introduction 6-22 Important User Information 6-22 Safety Function Realization 6-23 General Safety Information
More informationInstallation Instructions
Installation Instructions (Cat. No. 1771-OBN Series B) Use this document as a guide when installing the catalog number 1771-OBN series B output module. Because of the variety of uses for the products described
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE 440C SAFETY FUNCTION DOCUMENTS Emergency Stop with a Configurable Safety Relay Products: Emergency Stop, Guardmaster 440C-CR30 Configurable Safety Relay, 100S-C Safety Contactors
More informationControlLogix Redundancy Update and Module Replacement Guidelines
Reference Manual Original Instructions ControlLogix Redundancy Update and Module Replacement Guidelines Product Family ControlLogix 5570 Controllers Important User Information Read this document and the
More informationDeviceNet Network Configuration
User Manual DeviceNet Network Configuration 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, Studio 5000 Logix Emulate Important User Information Solid-state
More informationLogix5000 Controllers Function Block Diagram
Logix5000 Controllers Function Block Diagram Catalog Numbers 1756 ControlLogix, 1769 CompactLogix, 1789 SoftLogix, 1794 FlexLogix, PowerFlex 700S with DriveLogix Programming Manual Important User Information
More informationCatalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE
Release Notes RSFieldbus Software Catalog Numbers 9308-RSFB64ENE, 9308-RSFB256ENE, 9308-RSFB1024ENE Topic Page Important User Information 2 Before You Begin 3 Software Requirements 4 Install the Software
More informationThroughout this manual we use notes to make you aware of safety considerations:
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have
More informationInView Communication Modules
Installation Instructions InView Communication Modules Catalog Numbers 2706-PxM, 2706-PxK, 2706-PxP Topic Page About This Publication 1 Important User Information 2 Power Supply Requirements 3 Mount the
More informationL01 - Effective Design Methods for Integrating Safety Using Logix Controllers. For Classroom Use Only!
L01 - Effective Design Methods for Integrating Safety Using Logix Controllers For Classroom Use Only! Important User Information This documentation, whether, illustrative, printed, online or electronic
More informationDataSite Electronic Flow Meter and Remote Terminal Unit
DataSite Electronic Flow Meter and Remote Terminal Unit Catalog Numbers 1758-FLO301, 1758-FLO302, 1758- RTU201, 1758-RTU202 Software User Manual FRN 1.30 Important User Information Solid state equipment
More informationKinetix 300 Memory Module Programmer
Kinetix 300 Memory Module Programmer Catalog Number 2097-PGMR Topic About the Memory Module Programmer 1 Parts List 3 Batteries Operation 4 Using Memory Module Programmer 6 Switch On/Off Memory Module
More informationInstallation Instructions
Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application
More informationSimple Motion Control Connected Components Building Block. Quick Start
Simple Motion Control Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.
More informationAllen-Bradley. User Manual. PLC-5 Backup Communication Module (1785-BCM, 1785-BEM) product icon
Allen-Bradley PLC-5 Backup Communication Module User Manual (1785-BCM, 1785-BEM) product icon Important User Information Because of the variety of uses for this product and because of the differences between
More informationApplication Guide. Considerations for 32 Bit Integer Parameters in 16 Bit Processors. PowerFlex 700VC, PowerFlex 700S. Introduction.
Topic: Drive Product: Introduction User Information Considerations for 32 Bit Integer Parameters in 16 Bit Processors PowerFlex 700VC, PowerFlex 700S An Application Guide provides generic information on
More informationT4HD: Installation Supplement R8.1.13
THD: Installation Supplement R8.. Smartscan Incorporated 08 Eight Mile Road Livonia MI 8 Tel: (8)77-900 Fax: (8) 77-7 Web: www.smartscaninc.com Smartscan Incorporated Livonia, Michigan THD The use of this
More informationCompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
More informationMicro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis
Quick Start Micro800 Programmable Controllers: Getting Started with Motion Control Using a Simulated Axis Catalog Numbers Bulletin 2080-LC30, 2080-LC50 Important User Information Solid-state equipment
More informationApplication Technique. Products: Guardmaster 440C-CR30 Configurable Safety Relay, PowerFlex 755 Drive. Safety Rating: CAT. 3, PLe to ISO : 2008
Application Technique Safety Function: Actuator Subsystems Stop Category 0 or Stop Category 1 via a Configurable Safety Relay and PowerFlex 755 Drive with Hardwired Safe Torque-off Products: Guardmaster
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS 2 Hand Control Safety Function 800Z Zero Force Buttons / MSR125 Safety Relay / GSR SI Safety Relay Table of Contents: Introduction 6-3 Important
More informationLogix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network
Quick Start Logix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network Catalog Numbers Logix5000 Controllers, 1734 POINT I/O Modules Important User Information Solid-state equipment
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Pneumatic Safety Valves- Products: GuardLogix Controller, E-stop, Safety I/O Module, DM 2 Safety Valve Safety Rating: CAT. 3, PLd to EN ISO
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Light Curtain with Muting Table of Contents: Introduction 6-4 Important User Information 6-4 Safety Function Realization 6-42 General Safety
More informationDeviceNet ArmorBlock Network Powered 16-input Module
Installation Instructions DeviceNet ArmorBlock Network Powered 16-input Module Catalog number 1732D-IBDPM12MND, Series A Table of Contents Topic Page Important User Information 2 Environment and Enclosure
More informationMicro800 Programmable Controllers
Micro800 Programmable Controllers Bulletin 2080 Selection Guide Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety
More informationMicro800 Controllers Starter Pack Quick Start
Quick Start Micro800 Controllers Starter Pack Quick Start Catalog Numbers Bulletin 2080-LC20, 2080-LC30, 2080-LC50 Important User Information Read this document and the documents listed in the additional
More informationUSB-to-DeviceNet Cable
Installation Instructions USB-to-DeviceNet Cable Catalog Number 1784-U2DN Topic Page Important User Information 2 Environment and Enclosure 3 About the Cable 4 Install the Cable 5 Status Indicators 10
More informationApplication Technique. Safety Function: SensaGuard Non-contact Interlock Switch
Application Technique Safety Function: SensaGuard Non-contact Interlock Switch Products: SensaGuard Switch, GuardLogix Controller Safety Rating: CAT. 4, PLe to EN ISO 13849-1: 2008 2 Safety Function: SensaGuard
More informationApplication Technique. Safety Function: Safe Limited Speed and Safe Maximum Speed
Application Technique Safety Function: Safe Limited Speed and Safe Maximum Speed Products: TLSZR-GD2 Guard Locking Switch/Guardmaster Safety Relay/ PowerFlex 70 Drive Safety Rating: PLd, Cat. 3 to EN ISO
More informationProduct Compatibility and Download Center
Product Compatibility and Download Center Important User Information This documentation, whether, illustrative, printed, online or electronic (hereinafter Documentation ) is intended for use only as a
More informationGV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, HP, 230V AC
Software Start-Up and Reference Manual D2-3416-2 GV3000/SE General Purpose (Volts/Hertz) and Vector Duty AC Drive, 30-100 HP, 230V AC Version 6.04 Important User Information Solid-state equipment has operational
More informationSequenceManager Controls
Reference Manual SequenceManager Controls 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, Studio 5000 Logix Emulate Important user information Read this
More informationPOINT Guard I/O Safety Modules
User Manual POINT Guard I/O Safety Modules Catalog Numbers 1734-IB8S, 1734-OB8S, 1734-IE4S Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
More informationPresence Sensing Safety Devices
Presence Sensing Devices GuardShield POC Type 4 440L Point of Operation Control (POC) for finger or hand protection Heavy-duty IP65 housing Large operating range 0.3 6 m (0.98 52.49 ft) Dip switch selectable
More informationLogix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network
Quick Start Logix5000 Control Systems: Connect a PanelView Plus Terminal over an EtherNet/IP Network Catalog Numbers Logix5000 Controllers, 2711P PanelView Plus Terminals Important User Information Solid-state
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GuardLogix SAFETY FUNCTION DOCUMENTS Safety Mat Stop Table of Contents: Introduction 6-204 Important User Information 6-204 General Safety Information 6-205 Safety Function Realization:
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE 440C SAFETY FUNCTION DOCUMENTS Light Curtain and Configurable Safety Relay Products: Guardmaster 440C-CR30 Configurable Safety Relay, 440L GuardShield Light Curtain, Table of
More informationInstallation Instructions
Installation Instructions (Cat. No. 71-A1B, -A2B, -A3B, -A3B1, -A4B Series B) Because of the variety of uses for the products described in this publication, those responsible for the application and use
More informationInstallation Instructions
Installation Instructions Cat. No. 1771 P3, P4, P5 and P5E Use this document as a guide when installing the catalog number 1771-P3, -P4, -P5 or -P5E power supplies. Because of the variety of uses for the
More informationAllen Bradley DeviceNet Monitor User (9240 Mon16) Manual Allen-Bradley HMIs
Allen-Bradley HMIs Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all
More informationLogix5000 Controllers Nonvolatile Memory Card
Programming Manual Logix5000 Controllers Nonvolatile Memory Card 1756 ControlLogix, 1756 GuardLogix, 1769 CompactLogix, 1769 Compact GuardLogix, 1789 SoftLogix, 5069 CompactLogix, Studio 5000 Logix Emulate
More informationNext Generation Guardmaster Safety Relay (GSR)
Wiring Diagram Next Generation Guardmaster Safety Relay (GSR) Bulletin 0R Quick Reference Page Safety Relay Modules Input Devices Output Devices SIL CL Category Number 6 SI E-stop PowerFlex d 0 SI MAB
More informationArmorBlock Guard I/O DeviceNet Safety Modules
Installation Instructions ArmorBlock Guard I/O DeviceNet Safety Modules Catalog Numbers 1732DS-IB8XOBV4, 1732DS-IB8 Topic Page Important User Information 2 Environment and Enclosure 3 Preventing Electrostatic
More informationNHP SAFETY REFERENCE GUIDE
NHP SAFETY REFERENCE GUIDE GSR SAFETY FUNCTION DOCUMENTS Safe Limited Speed and Safe Maximum Speed Table of Contents: General Safety Information 6-83 Introduction 6-85 Safety Function Realization: Risk
More informationProduct Compatibility and Download Center
Product Compatibility and Download Center Important User Information This documentation, whether, illustrative, printed, online or electronic (hereinafter Documentation ) is intended for use only as a
More informationPanelViewt 1200 Transfer Utility User Manual
User Manual Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State
More informationDeviceNet ArmorBlock Network Powered 16-input Module, Series A
Installation Instructions DeviceNet ArmorBlock Network Powered 16-input Module, Series A Catalog Number 1732D-IB161212D Topic Page Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic
More informationPowerFlex 700H AC Drive Safe Torque Off Option
User Manual PowerFlex 700H AC Drive Safe Torque Off Option Catalog Number 20C-DG01 Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
More informationLogix5000 Controllers Produced and Consumed Tags
Programming Manual Logix5 Controllers Produced and Consumed Tags Catalog Numbers 1756 ControlLogix, 1756 GuardLogix, 1768 Compact GuardLogix, 1769 CompactLogix, 1789 SoftLogix, PowerFlex with DriveLogix
More informationGuardShield Safety Light Curtain
User Manual Original Instructions GuardShield Safety Light Curtain Catalog Numbers 450L-B4FNxYD, 450L-B4HNxYD Important User Information Read this document and the documents listed in the additional resources
More informationMuting Applications with the MSR300 Table of Contents
Application Note Muting Applications with the MSR00 Table of Contents ) Purpose... ) References... ) Muting Input Module... ) Muting Sensors... 5) Muting Lamp Module... 6) Reset... 7) Saving the Configuration
More informationGuard I/O EtherNet/IP Safety Modules
User Manual Guard I/O EtherNet/IP Safety Modules Catalog Numbers 1791ES-IB8XOBV4, 1791ES-IB16, 1732ES-IB12XOB4, 1732ES-IB12XOBV2 Important User Information Read this document and the documents listed in
More informationStudio 5000 Architect Getting Results Guide
Getting Results Studio 5000 Architect Getting Results Guide Rockwell Automation Publication ARCH-GR001I-EN-E Supersedes Publication ARCH-GR001H-EN-E Important user information Read this document and the
More informationSafety Light Curtains GuardShield Remote Teach
Specifications Presence Sensing Safety Devices Description The system provides a remote means of changing a fixed blanking configuration within the GuardShield safety light curtain. This keyswitch box
More informationSimple Temperature Control Connected Components Building Block. Quick Start
Simple Temperature Control Connected Components Building Block Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.
More informationControlLogix Configurable Flowmeter Module
User Manual ControlLogix Configurable Flowmeter Module Catalog Numbers 1756-CFM Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical
More informationThe Guardmaster 440C-CR30 Software Configurable Safety Relay Training Demo Lab. For Classroom Use Only!
The Guardmaster 440C-CR30 Software Configurable Safety Relay Training Demo Lab For Classroom Use Only! Important User Information This documentation, whether, illustrative, printed, online or electronic
More informationControlNet Adapter. 20-COMM-C FRN 1.xxx. User Manual
ControlNet Adapter 20-COMM-C FRN 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines
More informationDisconnect Switch and Circuit Breaker Mechanism Specifications Bulletin Number 1494
Technical Data Disconnect Switch and Circuit Breaker Mechanism Specifications Bulletin Number 1494 Topic Page 1494U Disconnect Switch Specifications 2 1494C, 1494F, 1494G, 1494R, 1494V Disconnect Switch
More informationEmbedded I/O Expansion Board with 10 Outputs
Installation Instructions Embedded I/O Expansion Board with 10 Outputs Catalog Number 1799-OQ10X Topic Page Important User Information 2 Environment and Enclosure 3 About the Board 4 Install the Board
More informationAllen-Bradley. User Manual. DeviceView Configurator (2707-DNC)
Allen-Bradley DeviceView Configurator (2707-DNC) User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety
More information