1
2 Mechanical Installation Recommended Tools for MP200 Unit Installation: #2 Phillips screwdriver; 1/4-inch (0.250 ) nut driver, socket, box, or open-end wrench; wire cutters. OTE: The MP200 unit is designed to withstand harsh environmental conditions; however it is recommended you install it in a dry location, free from dirt and corrosive substances. 7.60in 3.03in 193.1mm 76.9mm 0.19in 4.8mm 0.80in 20.4mm 4.50in 114.3mm 0.12in centered 2.9mm 10.98in 278.9mm centered 11.28in 286.5mm 0.28in 7.2mm 1. Mount the unit against any firm, flat surface. 2. Use a #8 screw in each of the four slots on the flange to ensure that the MP200 unit is installed securely. IMPORTAT! For safety reasons, mount the MP200 unit in an enclosed and protected environment, such as in a switchgear cabinet. Connect an earth ground to the post on the side of the MP200 unit, using an AWG 12 wire. Install a switch or circuit breaker nearby; label it clearly as the MP200 unit s disconnecting mechanism. 0.81in 20.5mm 3.18in 80.6mm 7.62in 193.5mm 4.36in 110.6mm Doc# E V.1.02 QS - 1
3 Electrical Installation: WARIGS! For Electrical Installation: All Primary and Secondary circuits can, at times, produce lethal voltages and currents. Avoid contact with any current-carrying surfaces. The current inputs are only to be connected to external current transfomers (CTs). SERVICES: WYE, 4 WIRE. COECTIO TYPE: Direct Voltage, CTs LIE V3 V2 V1 CT Shorting Block EI# SB-6CT I1-LO I1-HI I2-LO I2-HI I3-LO I3-HI Only one 3 phase circuit is shown. Duplicate for additional circuits. V3 FUSES 3 x 0.1A V2 V1 FUSE 3A L(+) (-) Power Supply Connection LOAD Service: Three Phase, 4-Wire WYE Service Direct Voltage and 3 CT Connection for Metering 8 Three Phase Loads: MP200-Y IMPORTAT! All CTs must have one side grounded to reduce shock hazard. EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter can be removed from service while the CT is energized. You can order the EI SB-6TC at Doc# E V.1.02 QS - 2
4 SERVICES: WYE, 4 WIRE. 3 COECTIO TYPE: 3PTs, CTs 1 2 LIE V3 V2 V1 CT Shorting Block EI# SB-6CT I1-LO I1-HI I2-LO I2-HI I3-LO I3-HI Only one 3 phase circuit is shown. Duplicate for additional circuits. V3 FUSES 3 x 0.1A V2 V1 FUSE 3A L(+) (-) Power Supply Connection LOAD Service: Three Phase, 4-Wire WYE Service with 3 PT Voltage and 3 CT Connection for Metering 8 Three Phase Loads - MP200-Y IMPORTAT! All CTs must have one side grounded to reduce shock hazard. EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter can be removed from service while the CT is energized. You can order the EI SB-6TC at Doc# E V.1.02 QS - 3
5 SERVICES: SIGLE PHASE, 2-WIRE COECTIO TYPE: Direct Voltage, CTs 1 LIE VL CT Shorting Block EI# SB-6CT I1-LO I1-HI I2-LO I2-HI I3-LO I3-HI Only three circuits are shown. Duplicate for additional circuits. VL Short Voltage inputs together FUSE 3A L(+) (-) Power Supply Connection LOADS Single Phase, 2-Wire Service with Direct Voltage and 1 CT Connection for Metering 24 Single Phase Loads: MP200-S IMPORTAT! All CTs must have one side grounded to reduce shock hazard. EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter can be removed from service while the CT is energized. You can order the EI SB-6TC at Doc# E V.1.02 QS - 4
6 SERVICE: SIGLE PHASE, 3-WIRE COECTIO TYPE: Direct Voltage, CTs To monitor 24 individual loads. See accuracy table for limiting factors. 2 1 LIE VL1 VL2 CT Shorting Block EI# SB-6CT Run lines VL1 and VL2 through the CT in opposite directions Set PT ratio to half in the meter. VL2 VL1 I1-LO I1-HI I2-LO I2-HI I3-LO I3-HI Only one circuit is shown. Duplicate for additional circuits. VL1 FUSES 2 x 0.1A Short Voltage inputs together FUSE 3A VL2 L(+) (-) Power Supply Connection LOADS Service: Single Phase, 3-Wire Service with Direct Voltage and 1 CT Connection for Metering 24 Single Phase Loads - MP200-S IMPORTAT! All CTs must have one side grounded to reduce shock hazard. EIG highly recommends using shorting blocks like the EI SB-6TC so that the meter can be removed from service while the CT is energized. You can order the EI SB-6TC at Doc# E V.1.02 QS - 5
7 MP200 Metering System Configuration: 1. Connect to the MP200 unit through its USB port: Use a USB Type A to B plug to connect from your PC s USB port to the MP200 unit s USB port. If your PC doesn t automatically find the USB driver, download it from the product CD that came with the MP200 unit (see Appendix A in the MP200 USB Port Metering System Installation and Operation Manual on the CD). OTE: This Quickstart shows connection using the USB port. For Ethernet/Wifi or RS485 connection, see the MP200 Metering System Installation and Operation Manual. 2. Open Communicator EXT TM software (download from product CD). 3. Click Connect on the tool bar. You will see the Connect screen, shown on the right. Make sure the Address, Baud Rate, and Protocol settings match the ones here. 4. Click Connect - the Device Status screen confirms the connection; then click OK - the Communicator EXT TM application s main screen opens. Configuration Steps: 6. Click the Profile button on the tool bar. The Device Profile screen opens. The Tree menu on the left side of the screen lets you choose setting screens. 7. Click System Settings to open one of the screens shown below. Use this screen to name the MP200 unit (CPU) and to label the circuits (individual meters). You must give the MP200 CPU an individual, unique name to properly download data to the database. Doc# E V.1.02 QS - 6
8 8. Click Communications (see instructions below). 9. Click CT, PT Ratios and System Hookup (see instructions below). Communications Settings: COM 1: RS485/ Ethernet/WIFI (optional) Address: 1-247; Baud Rate: 57600; Protocol: Modbus RTU/Modbus ASCII; Response Delay: 0-750ms; Parity: Odd, Even or one COM 2: USB port OTE: The USB port settings are fixed. COM 3: RS485 Address: 1-247; Protocol: Modbus RTU/ASCII Baud Rate: 9600, 19200, 38400, Response Delay: 0-750ms OTE: Click the (1)Default to Ethernet or (2)Default to Display button to set either the (1)Ethernet settings for COM1 or (2)Display settings for COM3, to their default values. CT, PT Ratios and System Hookup: ote that the settings you see on the screen depend on your MP200 unit s circuit configuration. The top screen is for an MP200 unit with the single phase circuit configuration (MP200-S). The bottom screen is for an MP200 unit with the three phase circuit configuration (MP200-Y). For PT settings, see the MP200 Metering System Installation and Operation manual, on the enclosed CD. The CT settings are: CT Ratios CT umerator (Primary): CT Denominator (Secondary): 5 or 1 Amp, depending on the MP200 unit s ordered option (this field is display only). Update Device: 10. When changes are complete, click the Update button to send a new profile to the MP200 unit. 11. Click Cancel to Exit the screen. OTE: For further details and additional programming screens, refer to the Communicator EXT TM 3.0 Software User Manual on the enclosed CD (access the software manual by clicking Help>Contents from the Communicator EXT TM application s Title bar). Communicator EXT is a trademark of. Doc# E V.1.02 QS - 7
GE Digital Energy Multilin EPM 4600 Quickstart Guide TELEPHONE: FAX: HOME PAGE:
GE Digital Energy Multilin EPM 4600 Multi-feed Power and Energy Metering Solution Quickstart Guide GE publication number: GEK-119590 (1601-0297-A1) GE Digital Energy 650 Markland Street Markham, Ontario
More informationMultilin EPM 4600 Metering Solution
GE Digital Energy Multilin EPM 4600 Metering Solution Multi-feed Power and Energy Metering Solution Quick Start Guide GE publication code: 1601-0297-A2 (GEK-119590A) 1601-0297-A2 Copyright 2014 GE Multilin
More informationPowerLogic High Density Metering System 1-Meter Enclosure
PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these
More informationSEM3 - Embedded Micro Metering Module
SEM - Embedded Micro Metering Module Quick Reference Guide and Installation Instructions Scan QR Code for more information usa.siemens.com/sem Installation! DANGER Hazardous Voltage. Will cause death or
More informationPowerLogic ION7300 Series
PowerLogic ION7300 Series Power and Energy Meter Advanced Field Retrofit Instructions August 2006 Danger This symbol indicates the presence of dangerous voltage within and outside the product enclosure
More informationInstalling the Cisco AS5400XM Universal Gateway
CHAPTER 3 Installing the Cisco AS5400XM Universal Gateway This chapter guides you through the installation of the Cisco AS5400XM universal gateway and includes the following sections: Setting Up the Chassis,
More informationSAVE THESE INSTRUCTIONS
READ AD FOLLOW ALL SAFETY ISTRUCTIOS! SAVE THESE ISTRUCTIOS AD DELIVER TO OWER AFTER ISTALLATIO IMPORTAT SAFETY ISTRUCTIOS! WARIG To reduce the risk of death, injury or property damage from fire, electric
More informationAcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter
AcquiSuite Ally 12 & 48 Advanced Multi-Circuit Meter Install Guide Revision C (12/18) DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Revision C (12/18) Turn off all power supplying equipment
More informationHydroGuard 4 to 20 ma Output Module. For use with HydroGuard Water Quality Monitor and Controller
HydroGuard 4 to 20 ma Output Module For use with HydroGuard Water Quality Monitor and Controller Technician's Manual Installation, Operation, and Maintenance Guide Chapter 1: Preface... 3 1.1 Intended
More informationMU110-6U. Analog output module 6 channel. User guide
MU110-6U Analog output module 6 channel User guide MU110-6U_2016.12_0221_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Тел.: +49 (0)
More informationEM QUICK START GUIDE. Quick Start Guide EM BG0504 REV.A2
Quick Start Guide EM132-133 Mechanical Installation Figure 1: Instrument Dimensions 2 Mechanical Installation Figure 2: Mounting the EM133 on DIN Rail or on flat surface IMPORTANT! Only qualified personnel
More informationInstallation Instructions & User Manual
Installation Instructions & User Manual ZONEMASTER PRO AC Panel Transient Voltage Surge Suppressors The Wiremold Company In US: 60 Woodlawn Street, West Hartford, CT 06110 800-621-0049 FAX 860-232-2062
More informationUSP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10
UniStream HMI Panel Installation Guide USP-070-B10, USP-070-B08 USP-104-B10, USP-104-M10 USP-156-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for
More information3300 ACM. Installation & Operation Manual. Economical Digital Power Meter/Transducer CONTENTS
3300 ACM Economical Digital Power Meter/Transducer Installation & Operation Manual CONTENTS Danger During normal operation of this device, hazardous voltages are present which can cause severe injury or
More informationG5 PDU Installation Guide
G5 PDU Installation Guide 1 Contents Before You Begin... 3 Overview... 3 Important Safety Information... 3 Required Tools... 5 Section 1 Introduction... 6 Classification Overview... 6 Features... 7 Form
More informationPanduit Basic Rack PDU
Panduit Basic Rack PDU User Manual Release 1.0 Issue 1.0 Copyright 2014 Panduit Corp. All rights reserved. No part of this book shall be reproduced, stored in a retrieval system, or transmitted by any
More informationInstallation RA5112-C-16A-C20. Basic Rack Power Distribution Unit
Installation RA5112-C-16A-C20 Basic Rack Power Distribution Unit Contents Before You Begin........................1 Safety and grounding information..........1 How to Install the Rack PDU...............2
More informationAPPENDIX B SERIAL I/O MODULE INSTALLATION / OPERATION WHEN USING T&D VER. 5.2 OR 5.3
SERIAL I/O MODULE INSTALLATION / OPERATION WHEN USING T&D VER. 5.2 OR 5.3 APPENDIX B In This Appendix... H2 SERIO(-4) Overview................................B 2 Specifications........................................B
More information3700 SERIES USER MANUAL
SAFETY GUIDE This manual contains the precautions necessary to ensure your personal safety as well as for protection for the products and the connected equipment. These precautions are highlighted with
More informationCoPilot EXT. Electro Industries/GaugeTech. Installation & Operation Manual Revision PDA Based Software
CoPilot EXT PDA Based Software Installation & Operation Manual Revision 1.02 December 3, 2007 Doc #: E156701 V1.02 Electro Industries/GaugeTech 1800 Shames Drive Westbury, New York 11590 Tel: 516-334-0870
More informationModel 2380 Rack-Mount Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount
More informationDTS 310. DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter. Page 1. Measurlogic MQ A
DTS 310 DIN Rail Mounted, Indoor Rated Revenue Grade Electrical Sub-meter Page 1 1 PRODUCT OVERVIEW... 3 1.1 SUPPLIED ITEMS... 3 1.2 DOCUMENT CONVENTIONS... 4 1.3 PRODUCT SPECIFICATION... 4 1.3.1 Current
More informationEM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters
Power and Energy Meters Code No. LIT-1900845 Issued December 4, 2013 EM-1000 /EM-2000/ EM-3000 Series Multifunction Power and Energy Meters EM-1000 Series Meter Description The EM-1000 Series monitor is
More informationI/O SIGNAL CONDITIONER
Technical Data Sheet No. TD9809M Rev. F Date of Issue: December 9, 2009 OPERATING MANUAL I/O SIGNAL CONDITIONER CAUTION: THIS PRODUCT DOES NOT PROVIDE GALVANIC ISOLATION. DO NOT ATTEMPT USE OF THIS PRODUCT
More informationA1. Multilin EPM 4600 Meter Displays DIS3500/DIS5700. Quick Start Guide. GE Digital Energy
GE Digital Energy Multilin EPM 4600 Meter Displays DIS3500/DIS5700 Quick Start Guide Product version: 1.0x GE publication code: 1601-0500-A1 (GEK-119644) 1601-0500-A1 Copyright 2014 GE Multilin Inc. All
More informationThe power behind competitiveness. Delta Infrasuite Power Management. Power Distribution Unit. User Manual.
The power behind competitiveness Delta Infrasuite Power Management Power Distribution Unit User Manual www.deltapowersolutions.com Save This Manual This manual contains important instructions and warnings
More informationDM3058/DM3058E Digital Multimeter
Quick Guide RIGOL Publication number QGA03109-1110 Feb. 2014 DM3058/DM3058E Digital Multimeter 2008 RIGOL Technologies, Inc. All Rights Reserved Copyright 2008 RIGOL Technologies, Inc. All Rights Reserved.
More informationH704-42(H)(E), H704-42/1(H)(E)
POWER MONITORING INSTALLATION GUIDE H704-42(H)(E), H704-42/1(H)(E) Branch Current Monitor DANGER NOTICE Installer's Specifications General: Operating Temp. Range 0 to 60 C (32 to 140 F) (
More informationCisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2
Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2 Cisco CRS 3-Phase AC Power Distribution Unit 2 Revised: November 18, 2016,
More informationOptical Multiplexer. Quick Start Guide
Optical Multiplexer Quick Start Guide Part Number: 07M1195-QS, Rev. A Revised: February 12, 2009 Sales Office: +1 (301) 975-1000 Technical Support: +1 (301) 975-1007 E-mail: support@patton.com WWW: www.patton.com
More informationPowerLogic ION7300 series Power and energy meter
70002-0198-08 06/2010 PowerLogic ION7300 series Power and energy meter Installation guide Danger This symbol indicates the presence of dangerous voltage within and outside the product enclosure that may
More informationPanduit Basic Rack PDU with Local Meter
Panduit Basic Rack PDU with Local Meter User Manual Release 1.0 Issue 1.0 Copyright 2014 Panduit Corp. All rights reserved. No part of this book shall be reproduced, stored in a retrieval system, or transmitted
More informationRGM180 Display Series
Quick Start Guide RGM180 Display Series BG0509 REV.A2 RGM180 QUICKSTART LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or
More informationInstruction Manual: IM E
Innovative Technology TVSS Products The I.T. Equalizer Installation Instruction Manual: IM01005011E Rev. 2 May 2009 Contents Page 1 Introduction... 1 1.1 Scope... 1 1.2 I.T. Equalizer Catalog Numbering
More informationModel 2380 Rack-Mount Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.tek.com/keithley Model 2380 Rack-Mount Kit Installation Instructions Introduction The Model 2380 Fixed Rack-Mount
More informationPower Xpert Meter 2000 Gateway Card Kit
Quick Start Guide IL02601011E PXM 2250 PXM 2260 IQ 250 IQ 260 Power Xpert Meter 2000 Gateway Card Kit Table of Contents Remove the Meter From Service.... 2 Disconnect Power Connections, CTs, and Modbus....
More informationEnerSure Installation Guide
EnerSure Installation Guide Danger!!! The electrical components of this system may contain voltage and /or amperage sufficient to injure or kill. Installation is only to be performed by a licensed, bonded
More informationPower Xpert Meter 2000 Gateway Card Kit
Quick Start Guide IL02601011E Rev. 2 December 2011 PXM 2250 PXM 2260 IQ 250 IQ 260 Power Xpert Meter 2000 Gateway Card Kit Table of Contents Remove the Meter From Service.... 2 Disconnect Power Connections,
More informationPower Xpert Meter 2000 Gateway Card Kit
Quick Start Guide IL02601011E PXM 2250 PXM 2260 IQ 250 IQ 260 Power Xpert Meter 2000 Gateway Card Kit Table of Contents Remove the Meter From Service... 2 Disconnect Power Connections, CTs, and Modbus....
More information9200 Power Meter. Installation & Operation Guide
9200 Power Meter Installation & Operation Guide Notices Danger This symbol indicates the presence of dangerous voltage within and outside the product enclosure that may constitute a risk of electric shock,
More informationElectronic Submeter with Advanced WiFi Ethernet Capability
SH RK 100S Electronic Submeter with Advanced WiFi Ethernet Capability AGGRESSIVE TECHNOLOGY W NEIndustry Leading Technology High Performance Metering Technology 0.2% Accuracy Class Revenue Certifiable
More informationTraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE
TTDM-128 TraceTek Leak Detection Master Module Installation Instructions TRACETEK APPROVALS AND CERTIFICATIONS TYPE NM General Signaling Equipment 76LJ GENERAL INFORMATION Please read these instructions
More informationMulti Unit Enclosed Meter
Contents Description Page Introduction Preliminary comments and safety precautions............................... 2 Warranty and liability information................ 2 Safety precautions..............................
More informationINTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual. PCMNET V 7. xx
INTEGRATED SYSTEMS AND CONTROL, INC. User s Hardware Manual PCMNET V 7. xx INTEGRATED SYSTEMS AND CONTROLS, INC. PCMNET Users Manual Revised 2/4/2005 2003-2005 Integrated Systems and Control. Inc. PO Box
More informationRS232C/RS485 Data can be easily monitored by LAN
KS SIGNAL CVERTER (AKS) RSC/RS8 Data can be easily monitored by LAN KS SIGNAL CVERTER FEATURES The connectors are located on the front panel. Easy to connect Easy to operate Can be connected to the LAN
More informationQuick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport
PTX5000 Packet Transport Router Quick Start September 2017 Part Number: 530-066788 Revision 01 This document describes how to install the Juniper Networks PTX5000 Packet Transport Router. Contents Quick
More informationTechnical Specifications. Dual Source kwh Energy Meter
Technical Specifications of Dual Source kwh Energy Meter (SPKG300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email
More informationH3G-48B Production Description
H3G-48B Production Description Designed for communication battery strings of 24 batteries each of VRLA and Ni-Cd battery 1 Applications For strings of 24 batteries each Base Station (2V X 24 batteries)
More informationH3G-TA ENGINEERING MANUAL
ENGINEERING MANUAL Table of Contents Tools required for installation and Debugging... 1 1 Overview... 4 2 System Components and Module Description...5 2.1 System Components... 5 2.2 TA Module...6 2.3 CM
More informationInstallation & Operation Manual
IQ 250/260 High Performance Multifunction Electricity Meter Installation & Operation Manual IB0260006E Rev..4 IQ 250/260 Meter Table of Contents INTRODUCTION - About this Manual - Warranty and Liability
More informationQUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Raritan DANGER!
QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationBCM2 Series Branch Circuit Monitors Quick Setup Guide
BCM2 Series Branch Circuit Monitors Quick Setup Guide Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationHPE Intelligent Power Distribution Unit Installation Instructions
HPE Intelligent Power Distribution Unit Installation Instructions Important safety information For important safety, environmental, and regulatory information, see Safety and Compliance Information for
More informationWiring Section 3-3. NQ-Series communication ports support various types of (serial) communication.
3-3 Wiring NQ-Series models have, besides one power connector, a number of communication ports. Please refer to Table 2.2: Common specifications for NQ-Series and Table 2.3: Specifications per NQ-Series
More informationGeneral Specifications. P2-SCM Serial Communications
General Specifications Module Type Intelligent Modules per Base I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to Logic
More informationTechnical Specificaions. kwh Energy Meter
Technical Specificaions of kwh Energy Meter (SPK301) Class 1.0S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email : info@spowerz.com
More informationPower Xpert Branch Circuit Monitor
Technical Data TD150021E Power Xpert ranch ircuit Monitor Introduction The Power Xpert ranch ircuit Monitor (PX M) meter module strip provides SI 12.20 0.5% revenue class branch circuit metering in panelboard
More informationOilCop Component Wiring Installation Manual
OilCop Component Wiring Installation Manual This info sheet contains important information. READ AND KEEP FOR REFERENCE. 2311 S. Edwards Wichita, KS 67213 TEL: 316-943-5477 FAX: 316-943-4760 TOLL FREE:
More informationUniStream HMI Panel. CPU-for-Panel
UniStream HMI Panel Installation Guide USP-070-B10,USP-104-B10, USP-156-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This
More informationSLATE. Digital I/O Module INSTALLATION INSTRUCTIONS R8001D4001
SLATE Digital I/O Module R8001D4001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform
More informationsatech TSB-14 MAIN FEATURES
satech TSB-14 ARTECHE satech TSB test block allows the testing of the protection relay, in a safe and easy way, ensuring isolation between the relay and field elements and eliminating any risk for the
More informationMultilin EPM Energy and Demand Submeter with Wi-Fi. Monitoring & Metering. Communications. Key Benefits. Applications
Multilin EPM 6100 Energy and Demand Submeter with Wi-Fi The EPM 6100 is a powerful tool that allows customers to monitor and manage their energy usage within factories, businesses and across campuses.
More informationQUICK SETUP GUIDE. BCM2 Series Branch Circuit Monitors. Safety Information. Equipment Maintenance and Service. Product Overview. Raritan DANGER!
QUICK SETUP GUIDE BCM2 Series Branch Circuit Monitors Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA 70E in the USA, or applicable
More informationMC 11 EB-2 Power supply cabinet with external bus, AC version
MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures
More informationP3-SCM. General Specifications
General Specifications Module Type Modules per Base Modules per Group I/O Points Used Field Wiring Connector Operating Temperature Storage Temperature Humidity Environmental Air Vibration Shock Field to
More informationINSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:
DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated
More informationInfinity 1U 19 Converter Shelf Models: J L217 - Individual +24V Inputs Bulk -48V Output L218 - Individual -48V Input Bulk+24V Output
GE Critical Power Quick Start Guide Infinity 1U 19 Converter Shelf Models: J5964803 L217 - Individual +24V Inputs Bulk -48V Output L218 - Individual -48V Input Bulk+24V Output Edge Controller This shelf
More informationPACSystems RX7i IC698CHS009/119
January 2010 The RX7i rack can be used for all RX7i CPU and I/O configurations, Series 90-70 I/O, and VME modules. Backplane connectors are spaced on 0.8" (20.3mm) centers to accommodate single-width RX7i
More informationETC One Plus Network Communicator Installation and Operation Manual
ETC One Plus Network Communicator Installation and Operation Manual BG0596 Rev. A1 LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship
More informationAC Power Meter GPM-8212 USER MANUAL
AC Power Meter GPM-8212 GW INSTEK PART NO. 82PM-82120MB This manual contains proprietary information, which is protected by copyrights. All rights are reserved. No part of this manual may be photocopied,
More informationNanoServ. Setup Guide. Thin System/Ultra-Thin System. 1.0 What s included with the NanoServ. 2.0 Steps for setting up the NanoServ
NanoServ Thin System/Ultra-Thin System Setup Guide 1.0 What s included with the NanoServ The following items are included with the NanoServ : 1. NanoServ 2. AC Power Adaptor 3. CD-ROM with User s Manual
More informationUser Guide Automatic Transfer Switch (ATS)
User Guide Automatic Transfer Switch (ATS) V.1.0 Table of Contents 1. Introduction... 2 2. Product Overview... 2 3. Important Safety Warnings... 3 4. Operation Indicators & Status... 3 5. Installation...
More informationAD-8923-BCD. Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD
AD-8923-BCD Remote Controller (BCD) INSTRUCTION MANUAL 1WMPD4002137 2010 A&D Company, Limited. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, or translated
More informationRack Installation Instructions
Rack Installation Instructions For System Storage EXP2512 and EXP2524 Express Storage Enclosures Use the instructions in this document to install an IBM System Storage EXP2512 Express Storage Enclosure
More information2.1 MANAGEMENT UNIT INSTALLATION
2 Install the Management Unit and 2.1 MNGEMENT UNIT INSTLLTION Ensure the C and DC disconnect switches are in the OFF position for the inverter. Mount the Maximizer Management Unit (MMU) in a location
More informationP3-RS Remote Slave Module
P3-RS Rack with CPU Module Racks with P3-RS Modules The P3-RS is a full-featured, highperformance, Remote Slave module. Features include a line x 0 charactor LCD display and five communications ports
More informationPM Series Power Meter
PM Series Power Meter Quick Setup Guide - PMC-1000, PMC- 1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See
More informationSmartZone Gateway- Enabled M Series Rack PDU
SmartZone Gateway- Enabled M Series Rack PDU User Manual Release 1.0 Issue 1.0 Copyright 2014 Panduit Corp. All rights reserved. No part of this book shall be reproduced, stored in a retrieval system,
More informationQUICK SETUP GUIDE. Raritan PXE. Safety Precautions. Before You Begin. Mounting the PDU. Unpacking the PXE. 1U Size
QUICK SETUP GUIDE Raritan PXE Thank you for purchasing the Raritan PXE intelligent power distribution unit (PDU). The intended use of the PXE is distribution of power to information technology equipment
More informationQUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB PM Series Power Meter. Safety Information. Equipment Maintenance and Service.
PM Series Power Meter QUICK SETUP GUIDE PMC-1000, PMC-1001, PMM-1000, PMB-1960 Safety Information DANGER! HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Follow safe electrical work practices. See NFPA
More informationTechnical Specifications. Multi Function Meter
Technical Specifications of Multi Function Meter (SPM300) Class 0.5S Sai PowerrZerve 29/3B, Rajalakshmi Nagar, 1 st Main Road, Velachery Bye Pass, Chennai 600 042. Website :www.spowerz.com Email : info@spowerz.com
More informationInstallation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.
Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable
More informationL300 user manual. Programmable DC Electronic Load CONTENTS. Electronic Load Software CAUTION...2 SAFETY NOTES...2
Programmable DC Electronic Load L300 user manual CONTENTS CAUTION......2 SAFETY NOTES......2 Chapter 1 General Introduction...3 1.1 General Introduction......3 1.2 Specification......3 1.3 Features......3
More information9500 and 9600 I/O Card Installation Instructions
9500 and 9600 I/O Card Installation Instructions This document describes how to install, configure, and verify the operation of the optional Input/Output card ( I/O card ) into your 9500 or 9600 power
More informationF1000 User's Manual. (Version: V1.01)
(Version: V1.01) Contents Chapter 1 Overview... 2 Chapter 2 Installation... 3 2.1 Installation guide... 3 2.1.1 Installation position... 3 2.1.2 NEMA4 standard installation... 3 2.1.3 Environment precautions...
More informationUser s Manual for SafeConnect
User s Manual for SafeConnect Summit Technology, Inc. Walnut Creek, CA 94597 Tel: 1-925-944-1212 Fax: 1-925-944-7126 support@powersight.com http://www.powersight.com Rev 2 Copyright 2007 by Summit Technology
More information*Approved by CSA for non-hazardous locations (Group Safety Publication IEC Third Edition).
PowerCore Model MPC-20 Installation Manual *Approved by CSA for non-hazardous locations (Group Safety Publication IEC 61010-1 Third Edition). Products covered in this document comply with European Council
More informationVAT series controller and transmitter. Manual
VAT series controller and transmitter Manual 1. General describe.. 2. Notice for use.. 1 1 3. Panel & connection introduce.. 2 4. Operate introduce.. 5. Application introduce. 6. Communication. 7. Specification..
More informationInstallation and Configuration Guide
Installation and Configuration Guide Trademark Notices Comtrol, NS-Link, and DeviceMaster are trademarks of Comtrol Corporation. Microsoft and Windows are registered trademarks of Microsoft Corporation.
More informationM40e and M160 CIP Installation Instructions
Part No. 530-005365-01 Revision 2 23 January 2002 CIP Description This document describes how to remove and replace the Connector Interface Panel (CIP) on a Juniper Networks M40e Internet router or M160
More informationConfigurable Output Distribution. 120V / 208V / 240V 60Hz. User Manual English
Configurable Output Distribution 120V / 208V / 240V 60Hz User Manual English TABLE OF CONTENTS IMPORTANT SAFETY INSTRUCTIONS.......................... 1 GLOSSARY OF SYMBOLS....................................
More informationE2460GS Oscilloscope Upgrade Kit
Installation Instructions for E2460GS Oscilloscope Upgrade Kit Agilent 1670G-Series Logic Analyzers This kit upgrades either the Agilent Technologies 1670G, Agilent 1671G, Agilent 1672G, or the Agilent
More informationCarbon Monoxide Sensor - ModBus
Introduction The CO Sensor uses an electrochemical sensor to monitor CO level in a range of 0 to 500 ppm and communicates via an RS-485 network configured for ModBus protocol. Before Installation Read
More informationInstallation Instructions for the AUTOcard-SA System
Installation Instructions for the AUTOcard-SA System IMPORTANT NOTICE The AUTOcard-SA system is a very reliable and easy to use system. However, damage could occur if it is installed incorrectly. In particular,
More informationThis Datasheet for the IC660BBD110. Block 115Vac Input 16 Circuits.
This Datasheet for the IC660BBD110 Block 115Vac Input 16 Circuits http://www.cimtecautomation.com/parts/p-14435-ic660bbd110.aspx Provides the wiring diagrams and installation guidelines for this GE Series
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 2713 ELECTRICITY METERING PART 1 - GENERAL 1.1 SUMMARY A. Section includes equipment for metering of the electrical power system. B. Related Sections: 1. Section 26 2300 for metering installed
More informationLeased-Line Extenders over IP
SmartNode 2290 Series Leased-Line Extenders over IP Quick Start Guide Important This is a Class A device and is intended for use in a light industrial environment. It is not intended nor approved for use
More informationNEW ERA METER. Installation & Operation Guide NE METER
NEW ERA METER Installation & Operation Guide NE METER Autoranging Power Supply Installation Diagnostics Per Phase Voltage & Current kwh, Demand and TOU 0.2% Accuracy -40 C to +85 C Watertight Enclosure
More informationH3G-380 Production Description
H3G-380 Production Description Designed for UPS battery strings of 15 to 48 batteries each of VRLA and Ni-Cd battery 1 Applications For strings of 15 to 48 batteries each Data Center IT Data Room 2 Product
More informationTRP-C08M. USB To 4 RS232/422/485 Isolated Converter. User s Manual. Printed Jun Rev 1.0
TRP-C08M USB To 4 RS232/422/485 Isolated Converter User s Manual Printed Jun. 2013 Rev 1.0 Trycom Technology Co., Ltd 1F, No.2-11, Sihu street, Yingge Township, Taipei, Taiwan ROC Tel: 886-2-86781191,
More information