MicroTech III Water Source Heat Pump Unit Controller Protocol Information

Size: px
Start display at page:

Download "MicroTech III Water Source Heat Pump Unit Controller Protocol Information"

Transcription

1 Engineering Data ED Group: Controls Part Number: ED15103 Date: June 2012 Supersedes: ED MicroTech III Water Source Heat Pump Unit Controller Protocol Information Networks Networks Enfinity Single Stage Compressor Models: MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW Vertical Stack Models: VHC/VHF SmartSource Single and Two-Stage Horizontal and Vertical Models: GSV/GSH, GTV/GTH 2012 Daikin

2 Table of Contents REVISION HISTORY... 3 REFERENCE DOCUMENTS... 4 NOTICE... 4 LIMITED WARRANTY... 4 UNIT CONTROLLER DATA POINTS... 5 PROTOCOL DEFINITIONS... 5 PARAMETERS REQUIRED FOR CONFIGURATION... 6 ACCESSING THE CONFIGURATION MENU... 6 BACNET STANDARD OBJECTS... 7 VARIABLES APPLICATION MODE INPUT AUXILIARY HEAT ENABLE INPUT BINARY INPUT STATUS BINARY OUTPUT STATUS BROWNOUT VOLTAGE READING CLEAR ALARM COMPRESSOR ENABLE INPUT CONDENSATE OVERFLOW CURRENT ALARM DISCHARGE AIR TEMPERATURE EFFECTIVE OCCUPANCY OUTPUT EFFECTIVE SETPOINT OUTPUT EFFECTIVE SPACE TEMPERATURE OUTPUT ENERGY HOLD OFF INPUT ENTERING WATER TEMPERATURE FAN ON/AUTO REMOTE INPUT FAN ON/AUTO STATUS FAN RUNNING OUTPUT FAN SPEED OUTPUT FAN SPEED OUTPUT HEAT/COOL/AUTO STATUS HUMIDISTAT REMOTE INPUT HUMIDISTAT STATUS LEAVING WATER TEMPERATURE LOCAL SETPOINT OUTPUT LOCAL SETPOINT SHIFT OUTPUT LOCAL SPACE TEMPERATURE OUTPUT WSHP STATUS OCCUPANCY OVERRIDE INPUT OCCUPANCY SCHEDULER INPUT OCCUPANCY SENSOR INPUT PREVIOUS ALARM PUMP REQUEST OUTPUT REQUEST SETPOINT OFFSET INPUT SPACE TEMPERATURE INPUT STATUS SUCTION TEMPERATURE COMPRESSOR # SUCTION TEMPERATURE COMPRESSOR # TEMPERATURE SETPOINT INPUT UNIT STATUS OUTPUT BROWNOUT REFERENCE SETPOINT HVAC UNIT-TYPE IDENTIFIER LOCAL BYPASS TIME SETPOINT LOCATION LABEL LOW PRESSURE ALARM DELAY ED

3 LOW TEMPERATURE PROTECTION DIFFERENTIAL LOW TEMPERATURE PROTECTION SETPOINT LOW TEMPERATURE PROTECTION SP FOR GLYCOL MINIMUM COMPRESSOR OFF TIMER SETPOINT MINIMUM COMPRESSOR ON TIMER SETPOINT MINIMUM SEND TIME OCCUPIED SETPOINT DIFFERENTIAL OCCUPANCY TEMPERATURE SETPOINTS RECEIVE HEARTBEAT ROOM SENSOR SETPOINT ENABLE SEND HEARTBEAT SOFTWARE IDENTIFICATION (MAJOR VERSION) SOFTWARE IDENTIFICATION (MINOR VERSION) SOFTWARE JUMPER CONFIGURATION UNIT APPLICATION (MAJOR VERSION) UNIT APPLICATION (MINOR VERSION) UNOCCUPIED SETPOINT DIFFERENTIAL COOLING INTERSTAGE TIMER SETPOINT HEATING INTERSTAGE TIMER SETPOINT COOLING SETPOINT HIGH LIMIT COOLING SETPOINT LOW LIMIT HEATING SETPOINT HIGH LIMIT HEATING SETPOINT LOW LIMIT HYDRONIC COOLING ON SETPOINT HYDRONIC HEATING ON SETPOINT HYDRONIC SETPOINT DIFFERENTIAL INTERSTAGE OFF TIMER SETPOINT INTERSTAGE ON TIMER SETPOINT LONG RANGE SETPOINT ADJUST MAXIMUM LONG RANGE SETPOINT ADJUST MINIMUM LOW ENTERING WATER TEMPERATURE SETPOINT FOR GLYCOL LOW ENTERING WATER TEMPERATURE SETPOINT FOR WATER LOW LEAVING WATER TEMPERATURE DIFFERENTIAL SECOND STAGE SETPOINT DIFFERENTIAL THIRD STAGE HEATING SETPOINT DIFFERENTIAL FOURTH STAGE HEATING SETPOINT DIFFERENTIAL INSTANCE NAME LOCATION DESCRIPTION UNITS (ENGLISH/METRIC) BAUDRATE MAXMASTERS ADDRESS SWITCH BACNET TERMINAL SETTINGS OFFLINE ONLINE RESET WINK COMMAND DEVICECOMMUNICATIONCONTROL - DISABLE DEVICECOMMUNICATIONCONTROL - ENABLE REINITIALIZEDEVICE (RESET) REINITIALIZEDEVICE (WINK) PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT APPENDIX C: BACNET PICS SMARTSOURCE WATER SOURCE HEAT PUMP MODELS GTH/GTV AND GSH/GSV PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT ED

4 Revision History Document Name Revision Date Description ED September 2008 Initial release. ED March 2010 Changed default baud rate to ( MS/TP Setup) Corrected range and descriptions of setpoint shift parameters (Protocol Point Summary) Moved Configuration section ( Configuration) Added references to no flow control ( Configuration and Terminal Settings) Changed the for all Multistate Values from Enumerated to Unsigned (Detailed Protocol Point Information) Changed PIC statement Application Version to 2.6 and Firmware Revision to 2.7 ED March 2011 Updated nvobinaryin and nvobinaryout status for dual compressors or dual stage capacity compressor, with automatic multiple fan speed control. New ncisetpoints heating & cooling standby default values. Updated ncihtgspthilim and nicclgsptlolim to also limit long range setpoint adjust input. Added PIC statement (Appendix C) for two-stage compressor control. ED June 2012 Added SmartSource variables and updated PIC statements. Range changes to: ncilowewtsptgly, ncilowewtsptwtr. Added new alarms. Modify low pressure alarm delay range. Added the following configuration properties: ncisptadjmax, ncisptadjmin, ncilowlwtdiff, ncihydroclgonspt. Added the humidistat variables: nvihumidistat and nvohumidistat. Added the fan switch nvifanonauto variable. Deleted Dual Stage compressor references. Updated Daikin logo and associated references. ED

5 Reference Documents Number Company Title Source G LONMARK Interoperability Association LONMARK Layers 1-6 Interoperability Guidelines, Version G LONMARK Interoperability Association LONMARK Application Layer Interoperability Guidelines, Version G Echelon Corporation FTT-10A Free Topology Transceiver Users Guide LONMARK Interoperability Association WSHP Functional Profile IM 927 Daikin MicroTech III Water Source Heat Pump Communication Module Installation Manual IM 928 Daikin MicroTech III Water Source Heat Pump communication module Installation Manual OM 931 Daikin MicroTech III Water Source Heat Pump Unit Controller Operation and Maintenance Notice 2012 Daikin, Minneapolis MN. All rights reserved throughout the world Daikin reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this product is appropriate for his or her application. The following are trademarks or registered trademarks of their respective companies: from American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Echelon,, LONMARK, and LonTalk from Echelon Corporation, Windows from Microsoft Corporation, and Daikin and MicroTech III from Daikin. LONMARK and the LONMARK logo are managed, granted, and used by LONMARK International under a license granted by Echelon Corporation. Limited Warranty Consult your local Daikin Representative for warranty details. Refer to Form Y. To find your local Daikin Representative, go to ED

6 Introduction This document contains the necessary information you need to incorporate a MicroTech III Water Source Heat Pump (WSHP) unit controller into a building automation system (BAS). It lists all properties, variables, and corresponding MicroTech III WSHP Unit Controller data points. This document supports the network integration parameters available for the Enfinity and Vertical Stack WSHP (single stage compressor) and SmartSource WSHP model types. It also contains two Protocol Implementation Conformance Statements (PICS) for each WSHP model. Unit Controller Data Points The MicroTech III WSHP Unit Controller contains data points or unit variables that are accessible from a MS/TP (Master/Slave Token Passing) network or a network. Not all points are accessible from each interface. This document contains the network details necessary to incorporate the MicroTech III WSHP Unit Controller into the network. Certain data points are available, depending on the model of WSHP unit. The parameters specific to each model are noted in the appropriate locations throughout this document. Protocol Definitions The MicroTech III WSHP Unit Controller can be configured in either an interoperable MS/TP or network. The controller must have the corresponding MicroTech III communication module installed for network integration (see Reference Document section of this document for corresponding literature). Protocol is a standard communication protocol for Building Automation and Control Networks developed by the American National Standards Institute (ANSI) and American Society of Heating, Refrigeration and Airconditioning Engineers (ASHRAE) specified in ANSI/ASHRAE standard It addresses all aspects of the various systems that are applied to building control systems. provides the communication infrastructure needed to integrate products manufactured by different vendors and to integrate building services that are now independent. See following section, Configuration, for details regarding the configuration of the communication module into a network. The MicroTech III WSHP Unit Controller is tested according to the Testing Laboratory (BTL) Test Plan. It is designed to meet the requirements of the Standard (ANSI/ASHRAE ) as stated in the Protocol Implementation and Conformance Statement (PICS). However, it is not BTL listed. The PICS are located at the end of this manual. Networks A control network specification for information exchange built upon the use of the LonTalk protocol for transmitting data developed by the Echelon Corporation. LonTalk Protocol A protocol developed and owned by the Echelon Corporation. It describes how information should be transmitted between devices on a control network. LONMARK Certification LONMARK certification is an official acknowledgement by the LONMARK Interoperability Association that a product communicates using the LonTalk protocol and transmits and receives data per a standard LONMARK functional profile. The communication module is in accordance with the LONMARK Heat Pump with Temperature Control functional profile and is LONMARK 3.4 certified. ED

7 Configuration A communication module must be configured before it can be connected to a network. This section describes how to set parameters using the communication module s built-in configuration menu (see Figure 1). The configuration menu is accessed using an application such as Microsoft Windows HyperTerminal. It is assumed that the user is familiar with such an application. Certain parameters are can also be configured via the network (BAS) and are noted as such within the detailed data section for the respective parameter. Parameters Required for Configuration The parameters listed below require configuration in order for the communication module to properly integrate to the network. They must be set using the communication module s configuration menu. Device Instance - must be set to a unique value on the network Device Name - must be set to a unique value on the network MS/TP Baud Rate - must be set according to the network requirements Address Switch - must be set according to the network requirements Accessing the Configuration Menu The communication module s configuration menu is accessed through the DB9 serial connector on the module itself. Any serial terminal device or application (such as Microsoft Windows HyperTerminal) can be used to view the menu and change the configuration parameters. Follow these steps to connect to the configuration menu (see Figure 1): 1. Verify that the terminal application communication settings are set to: bps, 8 data bits, no parity, 1 stop bit, and no flow control. 2. Use a DB9 female-female Modem to Modem (DCE to DCE) serial cross over cable to connect the computer to the communication module. 3. Once connected, press the Enter key to display the following menu: Table 1. Configuration Menu ============ Configuration Menu ============ Daikin MTIIIUC_WSHP FW HP0 v3.0 UnitApp HP0 v3.0 ======= SW PN ====================== DEVICE 1) Instance ) Name... MTIIIUC_WSHP_ ) Location... 4) Description... 5) Units... English MS/TP 6) Baudrate ) MaxMasters Address Switch... 1 TERMINAL 8) EIA-232 Baudrate B) Backup Configuration R) Restore Configuration S) Save settings Enter Selection: ED

8 Comprehensive Data Point Tables These comprehensive data point tables contain the significant parameters of specific data points. Table 2 defines the objects and Table 3 defines the variables available for the specific model of WSHP. Standard Objects Table 2. Comprehensive List of Standard Objects Network Control (Attributes available as Standard Objects for network control of the unit) Page Read Only, Writeable, Commandable Object Type Instance Flash Value 1 Range / Enumeration Description Device Description 81 W Dev * Y 32 Character String Device description of the WSHP Instance 80 W Dev * Y 1 to (*user assigned) Device Instance default = 300* Location 80 W Dev * Y 32 Character String Device Location of the WSHP Name 80 W Dev * Y 32 Character String Device Object Name Software Identification 65 R Dev * N 32 Character String Firmware-revision for the module Unit Application Version 66 R Dev * N 32 Character String Application-software-revision for the WSHP MaxMasters 82 W Dev * Y 1 to 127 Highest MS/TP MAC address on the segment Analog Inputs Local Space Temperature 40 R AI 1 N ºC/0ºF to 70ºC/158 F Local space temperature sensor input Leaving Water Temperature 36 R AI 2 N ºC/0ºF to 70ºC/158 F Leaving water temperature sensor input Entering Water Temperature 29 R AI 3 N ºC/0ºF to 70ºC/158 F Entering water temperature sensor input Discharge Air Temperature 25 R AI 4 N ºC/0ºF to 70ºC/158 F Discharge air temperature sensor input Local Setpoint Output 37 R AI 5 N C/55 F to 35 C/95 F Local long range setpoint adjust output Suction Temperature Compressor #1 50 R AI 6 N ºC/0ºF to 70ºC/158 F Compressor #1 suction temperature sensor Suction Temperature Compressor #2 (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and 51 R AI 7 N ºC/0ºF to 70ºC/158 F Compressor #2 suction temperature sensor Vertical Stack Models VHC/VHF Only, v3.0 and Older) Brownout (Shutdown) 21 R AI 8 N 0 to 1023 Counts Brownout reference voltage Analog Values Occupied Cooling Setpoint 61 W AV 1 Y 10 C/50 F to 35 C/95 F Occupied Cooling Setpoint Standby Cool Setpoint 61 W AV 2 Y 10 C/50 F to 35 C/95 F Standby Cooling Setpoint Unoccupied Cool Setpoint 61 W AV 3 Y 10 C/50 F to 35 C/95 F Unoccupied Cooling Setpoint Occupied Heat Setpoint 61 W AV 4 Y 10 C/50 F to 35 C/95 F Occupied Heating Setpoint Standby Heat Setpoint 61 W AV 5 Y 10 C/50 F to 35 C/95 F Standby Heating Setpoint Unoccupied Heat Setpoint 61 W AV 6 Y 10 C/50 F to 35 C/95 F Unoccupied Heating Setpoint Local Bypass Time Setpoint 55 W AV 7 Y 0, 30 to 120 Minutes Minutes the unit will remain in Bypass mode Brownout Reference Setpoint 54 W AV 9 Y 25 to 1023 Counts Brownout Reference setpoint for factory setup Occupied Setpoint Differential 60 W AV 10 Y.55 C/1 F to 2.78 C/5 F Occupied Setpoint Off differential Low Temperature Protection SP (Glycol) 58 W AV 11 Y C/0 F to 10 C/50 F Glycol low temperature protection setpoint Low Temperature Protection Setpoint 58 W AV 12 Y C/0 F to 10 C/50 F Low temperature protection setpoint Low Temperature Protection Differential 57 W AV 13 Y 1.11 C/2 F to 8.34 C/15 F Low temperature differential for hysteresis Minimum Compressor Off Timer Setpoint 59 W AV 15 Y 0 to 1200 Seconds Minimum time compressor must stay off before turning on. Minimum Compressor On Timer Setpoint 59 W AV 16 Y 0 to 1200 Seconds Minimum time compressor must stay on before turning off. Unoccupied Setpoint Differential 67 W AV 17 Y 1.11 C/2 F to 5.56 C/10 F Unoccupied setpoint differential Space Temperature Input 48 C AV 18 N -10ºC/14ºF to 50ºC/122 F Network Space Temperature Input Temperature Setpoint Input 52 C AV 19 N 10 C/50 F to 35 C/95 F Temperature Setpoint Input Receive Heartbeat 62 W AV 20 Y 0 to Received message timer Send Heartbeat 64 W AV 21 Y 0 to Send timer Effective Space Temperature 28 R AV 22 N º/0ºF to 70ºC/158 F Effective Space Temperature Output Effective Setpoint Output 27 R AV 23 N 10 C/50 F to 35 C/95 F This will display either the Heating or Cooling setpoint depending on the unit status. Occupied Cool Shift (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and Vertical Stack Models VHC/VHF Only, v3.0 and Older ) Effective Shift Output (SmartSource Models GTH/GTV and GSH/GSV Only, v5.0 and Newer) 38 R AV 24 N C/-3 F to C/+3 F C/-5 F to C/+5 F Room Sensor: Single Stage Occupied Cooling Setpoint Offset / Effective Setpoint Shift Output. ED

9 Network Control (Attributes available as Standard Objects for network control of the unit) Page Read Only, Writeable, Commandable Object Type Instance Flash Value 1 Range / Enumeration Description Standby Cool Shift (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and 38 R AV 25 N C/-3 F to C/+3 F Room Sensor Standby Cooling Setpoint Offset Vertical Stack Models VHC/VHF Only, v3.0 and Older ) Unoccupied Cool Shift (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and 38 R AV 26 N 0 Not Used Vertical Stack Models VHC/VHF Only, v3.0 and Older ) Occupied Heat Shift (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and 38 R AV 27 N C/-3 F to C/+3 F Room Sensor Occupied Heating Setpoint Offset Vertical Stack Models VHC/VHF Only, v3.0 and Older) Standby Heat Shift (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and 38 R AV 28 N C/-3 F to C/+3 F Room Sensor Standby Heating Setpoint Offset Vertical Stack Models VHC/VHF Only, v3.0 and Older) Unoccupied Heat Shift (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and 39 R AV 29 N 0 Not Used Vertical Stack Models VHC/VHF Only, v3.0 and Older ) Low Pressure Alarm Delay 56 W AV 34 Y 0 to 120 Seconds 1 Temperature Setpoint Offset Input 48 C AV 35 N -10 C/-18 F to +10 C/+18 F Temperature Setpoint offset Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and Vertical Stack Models VHC/VHF Only (v3.0 and Older) Cooling Interstage Timer Setpoint 68 W AV 8 Y 0 to 1200 Seconds Time between the cooling stages Heating Interstage Timer Setpoint 68 W AV 14 Y 0 to 1200 Seconds Time between the heating stages Cooling Setpoint High Limit 69 W AV 30 Y 10 C/50 F to 35 C/95 F Cooling Setpoint High Limit Cooling Setpoint Low Limit 70 W AV 31 Y 10 C/50 F to 35 C/95 F Cooling Setpoint Low Limit Heating Setpoint High Limit 70 W AV 32 Y 10 C/50 F to 35 C/95 F Heating Setpoint High Limit Heating Setpoint Low Limit 71 W AV 33 Y 10 C/50 F to 35 C/95 F Heating Setpoint Low Limit SmartSource Models GTH/GTV and GSH/GSV Only (v5.0 and Newer) Interstage Off Timer Setpoint 73 W AV 8 Y 0 to 1200 Seconds Off Time Between The Stages Interstage On Timer Setpoint 74 W AV 14 Y 0 to 1200 Seconds On Time Between The Stages Long Range Setpoint Adjust Maximum 74 W AV 25 Y C/55 F to 35 C/95 F Long Range Setpoint Adjust Maximum Setpoint Long Range Setpoint Adjust Minimum 75 W AV 26 Y C/55 F to 35 C/95 F Long Range Setpoint Adjust Minimum Setpoint Hydronic Cooling On Setpoint 71 W AV 27 Y 10 C/50 F to C/70 F Hydronic Cooling On Setpoint Hydronic Setpoint Differential 73 W AV 28 Y 1.11 C/2 F to 5.56 C/10 F Hydronic Differential Setpoint Low Leaving Water Temp Differential 77 W AV 29 Y 1.11 C/2 F to 8.34 C/15 F Low Leaving Water Differential Setpoint Low Entering Water Temp for Glycol 76 W AV 30 Y C/15 F to 4.45 C/40 F Glycol Low Entering Water Temp Setpoint Low Entering Water Temp for Water 76 W AV 31 Y 4.44 C/40 F to C/65 F Water Low Entering Water Temp Setpoint Hydronic Heating On Setpoint 72 W AV 32 Y C/70 F to C/90 F Hydronic Heating On Setpoint Second Stage Setpoint Differential 77 W AV 33 Y 0.55 C/1 F to 2.78 C/5 F Stage #2 Setpoint Differential Third Stage Heating Setpoint Differential 78 W AV 36 Y 0.55 C/1 F to 5.56 C/10 F Stage #3 Heating Setpoint Differential Fourth Stage Heating Setpoint Differential 79 W AV 37 Y 0.55 C/1 F to 5.56 C/10 F Stage #4 Heating Setpoint Differential Fan Speed Output 33 R AV 38 N 0 to 100% Displays the current fan speed Binary Inputs Binary Input Status 16 R BI 1 N Binary Values Clear Alarm 21 W BV 1 N Binary Output Status 19 R BV 2 N Multi-State Inputs Condensate Overflow 23 R MSI 1 N Fan On/Auto Status 31 R MSI 2 N 0 = Normal 1 = Clear Alarm 1 = Dry 2 = Wet 3 = Null 1 = Fan On 2 = Auto 3 = Null Shows the raw value of the digital intputs in the description text Clears active alarms. After the alarm is cleared, this value is automatically returned to Normal (0). Shows the raw value of the digital outputs in the description text Show the status of the condensate overflow sensor Used to monitor the fan on/auto switch. ED

10 Network Control (Attributes available as Standard Objects for network control of the unit) Page Read Only, Writeable, Commandable Object Type Instance Flash Value 1 Range / Enumeration Description Heat/Cool/Auto Status 34 R MSI 3 N Humidistat Status (SmartSource Models GTH/GTV and GSH/GSV Only, v5.0 and Newer) Fan Running Status (SmartSource Models GTH/GTV and GSH/GSV Only, v5.0 and Newer) Multi-State Values 36 R MSI 4 N 31 R MSI 5 N Compressor Enable Input 22 C MSV 1 N Current Alarm 21 R MSV 2 N Fan Speed Output (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and Vertical Stack Models VHC/VHF Only, v3.0 and Older) Fan On/Auto Remote Input (SmartSource Models GTH/GTV and GSH/GSV Only, v5.0 and Newer ) 32 R MSV 3 N 30 C MSV 3 N WSHP Status 41 R MSV 4 N Previous Alarm 44 R MSV 5 N Effective Occupancy Output 26 R MSV 6 N Occupancy Override Input 42 C MSV 7 N Occupancy Scheduler Input 43 C MSV 8 N Occupancy Sensor Input 44 C MSV 9 N Application Mode Input 14 C MSV 10 N Auxiliary Heat Enable Input 15 C MSV 11 N 1 = Off (Not Used) 2 = Heat 3 = Cool 4 = Auto 5 = Null 1 = Not Humid 2 = Is Humid 3 = Null 1 = Fan is OFF 2 = Fan is ON 1 = Disabled 2 = Enabled 3 = Null Valid Values: 1 to 15 (Enfinity Single Stage and Vertical Stack) 1 to 16 (SmartSource) 1 = Off 2 = Low 3 = Medium 4 = High 5 = On 1 = Fan Auto 2 = Fan On 3 = Null 1 = Off Alarm 2 = Off 3 = Start 4 = Fan Only 5 = Prepare To Heat 6 = Heating 7 = Prepare To Cool 8 = Cooling 9 = Prepare To Dehumidify 10 = Dehumidification Valid Values: 1 to 15 (Enfinity Single Stage and Vertical Stack) 1 to 16 (SmartSource) 1 = Occupied 2 = Unoccupied 3 = Bypass 4 = Standby 5 = Null 1 = Occupied 2 = Unoccupied 3 = Bypass 4 = Standby 5 = Null 1 = Occupied 2 = Unoccupied 3 = Standby 4 = Null 1 = Occupied 2 = Unoccupied 3 = Null 1 = Auto 2 = Heat 3 = Cool 4 = Off 5 = Fan Only 6 = Dehumid 7 = Null 1 = Disabled 2 = Enabled 3 = Null Used to display the heat/cool/auto commands from the network. Used to monitor the humidistat binary input status. Used to monitor the fan running ON/OFF status. Used to indicate proof of flow. Current WSHP Alarm Displays the current fan speed Used to override local fan on/auto switches Indicates the operating status of the WSHP Previous WSHP Alarm Displays the current occupancy Occupancy variable with the highest priority. Used to override the local sensor or tenant override. Used to command the WSHP into different occupancy modes from the network Commands the mode of the unit. For normal operation this value should be set to Auto or Null. Enables or Disables the Auxiliary Heat ED

11 Network Control (Attributes available as Standard Objects for network control of the unit) Page Read Only, Writeable, Commandable Object Type Instance Flash Value 1 Range / Enumeration Description Energy Hold Off Input 28 C MSV 12 N Pump Request Output 46 R MSV 13 N Room Sensor Setpoint Enable/Disable 63 W MSV 14 Y Units (English / Metric) 81 W MSV 15 Y Humidistat Remote Input (SmartSource Models GTH/GTV and GSH/GSV Only, v5.0 and newer ) 35 W MSV 16 Y 1 = Normal 2 = Energy Hold Off 3 = Null 1 = No Request for Flow 2 = Request for Flow 3 = Null 1 = Disabled 2 = Enabled 3 = Null 1 = English 2 = Metric 1 = No Request for Dehumidification 2 = Dehumidification Request 3 = Null 1 The range for Enfinity and Vertical Stack models with software v2.9 and older is 0 to 99 seconds. Stops Heating and Cooling of the space but provides protection from temperature extremes Tells the BAS to turn on the loop pump Used to Enable/Disable the room setpoint adjustments Global conversion selection for temperatures Command to override the local humidistat input. ED

12 Variables Table 3. LonWorks Network Variable Inputs (NVIs) and Outputs (NVOs) Network Variable Inputs (NVI) Variable Description (nvi) Page Name SNVT Type SNVT Index Application Mode Input 14 nviapplicmode SNVT_hvac_mode 108 Auxiliary Heat Enable Input 15 nviauxheatenable SNVT_switch 95 Clear Alarm 22 nviclearalarm SNVT_switch 95 Compressor Enable Input 23 nvicomprenable SNVT_switch 95 Energy Hold Off Input 29 nvienergyholdoff SNVT_switch 95 Fan On/Auto Remote Input (SmartSource Models GTH/GTV and GSH/GSV Only, 30 nvifanonauto SNVT_switch 95 v5.0 and Newer ) Humidistat Remote Input (SmartSource Models GTH/GTV and GSH/GSV Only, 35 nvihumidistat SNVT_switch 95 v5.0and Newer) Occupancy Override Input 42 nvioccmancmd SNVT_occupancy 109 Occupancy Scheduler Input 43 nvioccschedule SNVT_tod_event 128 Occupancy Sensor Input 44 nvioccsensor SNVT_occupancy 109 Setpoint Offset Input 48 nvisetptoffset SNVT_temp_p 105 Space Temperature Input 49 nvispacetemp SNVT_temp_p 105 Temperature Setpoint Input 52 nvisetpoint SNVT_temp_p 105 Network Variable Outputs (NVO) Binary Input Status 16 nvobinaryin SNVT_state_ Binary Output Status 19 nvobinaryout SNVT_state 83 Brownout (Shutdown) 21 nvobrownout SNVT_count 8 Condensate Overflow 23 nvocondoverflow SNVT_switch 95 Current Alarm 24 nvocurrentalarm SNVT_str_asc 36 Discharge Air Temperature 25 nvodischairtemp SNVT_temp_p 105 Effective Occupancy Output 26 nvoeffectoccup SNVT_occupancy 109 Effective Setpoint Output 27 nvoeffectsetpt SNVT_temp_p 105 Effective Space Temperature Output 28 nvospacetemp SNVT_temp_p 105 Entering Water Temperature 29 nvoewt SNVT_temp_p 105 Fan On/Auto Status 31 nvofanonauto SNVT_switch 95 Fan Speed Output (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and Vertical Stack Models 32 nvofanspeed SNVT_switch 95 VHC/VHF Only, v3.0 and Older) Fan Speed Output (SmartSource Models GTH/GTV and GSH/GSV Only, v nvofanspeed SNVT_switch 95 and Newer ) Heat/Cool/Auto Status 34 nvoheatcoolauto UNVTheatCoolAuto 8 Humidistat Status (SmartSource Models GTH/GTV and GSH/GSV Only, v nvohumidistat SNVT_switch 95 and Newer ) Leaving Water Temperature 37 nvolwt SNVT_temp_p 105 Local Setpoint Output 37 nvosetpoint SNVT_temp_p 105 Local Setpoint Shift Output 39 nvosetptshift SNVT_temp_setpt 106 Local Space Temperature Output 40 nvolocalspacetmp SNVT_temp_p 105 WSHP Status 41 nvomcqhpunitstat UNVTmcqHPUnitStat 8 Previous Alarm 45 nvopreviousalarm SNVT_str_asc 36 Pump Request Output 46 nvopumprequest SNVT_switch 95 Status 2 49 nvostatus SNVT_obj_status 93 Suction Temperature Compressor #1 50 nvosuctiontemp1 SNVT_temp_p 105 Suction Temperature Compressor #2 (Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and 51 nvosuctiontemp2 SNVT_temp_p 105 Vertical Stack Models VHC/VHF Only, v3.0 and Older) Unit Status Output 2 52 nvounitstatus SNVT_hvac_status 112 ED

13 Table 4. LonWorks Configuration Properties Configuration Inputs (NCI) 3 Variable Description (nci) Page Name SNVT/UCPT Type UCPT Index SCPT Index Brownout Reference Setpoint 54 ncibrownoutref UCPTbrownoutRef N/A 8 HVAC Unit-Type Identifier 2 54 ncihvactype SCPThvacType N/A Local Bypass Time Setpoint 55 ncibypasstime SCPTbypassTime N/A Location Label 56 ncilocation SCPTlocation N/A Low Pressure Alarm Delay 56 ncilowpresalmdly UCPTlowPresAlmDly N/A 107 Low Temperature Protection Differential 57 ncilowtmpprotdif UCPTlowTmpProtDif N/A 147 Low Temperature Protection Setpoint 58 ncilowtempprot UCPTlowTempProt N/A 105 Low Temp Protection SP for Glycol 58 ncilowtempprotgl UCPTlowTempProtGL N/A 147 Minimum Compressor Off Timer Setpoint 59 ncimincompofftmr UCPTminCompOffTmr N/A 107 Minimum Compressor On Timer Setpoint 60 ncimincompontmr UCPTminCompOnTmr N/A 107 Minimum Send Time 60 nciminouttm SCPTminSendTime N/A 52 N/A Occupied differential 61 ncioccdiff UCPToccDiff N/A 147 Occupancy Temperature Setpoints 62 ncisetpoints SCPTsetPnts N/A Receive Heartbeat 63 ncircvhrtbt SCPTmaxRcvTime N/A Room Sensor Setpoint Enable/Disable 64 ncilocsptenable UCPTlocSptEnable N/A N/A Send Heartbeat 64 ncisndhrtbt SCPTmaxSendTime N/A Software Identification (Major Version) 65 ncidevmajver SCPTdevMajVer N/A 165 N/A Software Identification (Minor Version) 2 65 ncidevminver SCPTdevMinVer N/A 166 N/A Software Jumper Configuration 66 ncisoftjumpers UCPTsoftJumpers N/A 83 Unit Application (Major Version) 67 nciunitappmajver UCPTunitAppMajVer N/A N/A N/A Unit Application (Minor Version) 2 67 nciunitappminver UCPTunitAppMinVer N/A N/A N/A Unoccupied Differential 67 nciunoccdiff UCPTunOccDiff N/A 147 Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and Vertical Stack models VHC/VHF (v3.0 and Older) Cooling Interstage Timer Setpoint 68 ncicoolintstgtmr UCPTcoolIntStgTmr N/A 107 Heating Interstage Timer Setpoint 69 nciheatintstgtmr UCPTheatIntStgTmr N/A 107 Cooling Setpoint High Limit 69 nciclgspthilim UCPTclgSptHiLim N/A 105 Cooling Setpoint Low Limit 70 nciclgsptlolim UCPTclgSptLoLim N/A 105 Heating Setpoint High Limit 70 ncihtgspthilim UCPThtgSptHiLim N/A 105 Heating Setpoint Low Limit 71 ncihtgsptlolim UCPThtgSptLoLim N/A 105 SmartSource Models GTH/GTV and GSH/GSV Only (v5.0 and Newer) Hydronic Cooling On Setpoint 72 ncihydroclgonspt UCPThydroClgOnSpt N/A 105 Hydronic Heating On Setpoint 72 ncihydrohtgonspt UCPThydroHtgOnSpt N/A 105 Hydronic Setpoint Differential 73 ncihydronicdiff UCPThydronicDiff N/A 147 Interstage Off Timer Setpoint 73 nciintstgofftmr UCPTintStgOffTmr N/A 107 Interstage On Timer Setpoint 74 nciintstgontmr UCPTintStgOnTmr N/A 107 Long Range Setpoint Adjust Maximum 75 ncisptadjmax UCPTsptAdjMax N/A 105 Long Range Setpoint Adjust Minimum 75 ncisptadjmin UCPTsptAdjMin N/A 105 Low Entering Water Temp for Glycol 76 ncilowewtsptgly UCPTlowEwtSptGly N/A 105 Low Entering Water Temp for Water 76 ncilowewtsptwtr UCPTlowEwtSptWtr N/A 105 Low Leaving Water Temp Differential 77 ncilowlwtdiff UCPTlowLwtDiff N/A 147 Second Stage Setpoint Differential 78 ncistg2sptdiff UCPTstg2SptDiff N/A 147 Third Stage Heating Setpoint Differential 78 ncistg3sptdiff UCPTstg3SptDiff N/A 147 Fourth Stage Heating Setpoint Differential 79 ncistg4sptdiff UCPTstg4SptDiff N/A Indicates a variable needed for Master/Slave operation. only. 2 Indicates the item is not supported in. 3 Configuration properties reside in flash memory that has a write cycle limit of approximately writes. Do not unnecessarily write to configuration properties as this can limit the life of the device. 4 Indicates the property is Read Only, Writeable, or Commandable in. Commandable means a priority array is supported. SNVT Index ED

14 Detailed Protocol Point Information The data points or properties (attributes) defined in this section reference data that is generated by the MicroTech III WSHP unit controller. Refer to Table 5 below for a summary of data point differences between the software versions available on the various WSHP models. Use the information in this table to identify point mapping changes in or LonWorks parameters. This section also includes the detailed data description for each network parameter previously summarized in the and LonWorks Tables 3 and 4. Important Software Compatibility Information MicroTech III WSHP unit controller software version 5.0 and newer (PN ) is used with SmartSource models GTH/GTV and GSH/GSV. MicroTech III WSHP unit controller software version 3.0 and older (PN ) is used with Enfinity WSHP models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and Vertical Stack models VHC/VHF. Table 5. Data Point Differences by Software Version Object AV-24 AV-25 AV-26 AV-27 AV-28 AV-29 AV-30 AV-31 AV-32 LonWorks Variable MicroTech III Unit Controller Software Version* Description (Function) Short range setpoint shift when in the occupied cooling mode AV-24 as a single object replaces the use of objects AV-24 thru AV Short range setpoint shift when in the standby cooling mode 5.0 Long range setpoint adjust input maximum clamp value 3.0 Short range setpoint shift when in the unoccupied cooling mode 5.0 Long range setpoint adjust input minimum clamp value 3.0 Short range setpoint shift when in the occupied heating mode 5.0 Not used 3.0 Short range setpoint shift when in the standby heating mode 5.0 Not used 3.0 Short range setpoint shift when in the unoccupied heating mode 5.0 LWT differential added to selected low suction temp setpoint to determine freeze fault alarm temperature 3.0 Upper clamp value of the cooling setpoints 5.0 Low EWT setpoint when using glycol loop fluid. Disables compressor in the heating mode 3.0 Lower clamp value of the cooling setpoints 5.0 Low EWT setpoint when using water loop fluid. Disables compressor in the heating mode 3.0 Upper clamp value of the heating setpoints 5.0 Hydronic valve heating setpoint AV Lower clamp value of the heating setpoints nciclgspthilim nciclgsptlolim ncihtgspthilim ncihtgsptlolim 3.0 Upper clamp value of the cooling setpoints 5.0 Not used 3.0 Lower clamp value of the cooling setpoints 5.0 Not used 3.0 Upper clamp value of the heating setpoints 5.0 Not used 3.0 Lower clamp value of the heating setpoints 5.0 Not used *See Important Software Compatibility section above for a complete description of part numbers and WSHP models that correspond to each version of software. ED

15 Application Mode Input This input network variable coordinates the WSHP with a system controller or other building automation system (BAS). This read/write attribute sets the unit in an application mode (auto, off, heat only, cool only, fan only, or dehumidification). Application Mode does not "force" the unit into any state. However, it disables certain unit operation. For example, an Application Mode of "Cool Only" disables heating, "Heat Only" disables cooling, and "Fan Only" disables heating and cooling. Multistate Value Present Value 85 MTIIIUC_WSHP.#######.ApplicMode. Value 1 = Auto 2 = Heat 3 = Cool 4 = Off 5 = Fan Only 6 = Dehumid 7 = Null Read, Writable, Commandable Unsigned 1 byte 1-7 Enumeration N C LonWorks Name Profile SNVT Type SNVT Number nviapplicmode SCC Heat Pump SNVT_hvac_mode 108 Uses Receive Heartbeat hvac_t Enumeration hvac_t Enumeration 1 byte hvac_t Enumeration Yes Value Identifier Notes 0xFF HVAC_NUL Invalid 0 HVAC_AUTO Controller automatically changes between application modes 1 HVAC_HEAT Heating only 2 HVAC_MRNG_WRMUP Application-specific morning warm-up (Not Used) 3 HVAC_COOL Cooling only 4 HVAC_NIGHT_PURGE Application-specific night purge (Not Used) 5 HVAC_PRE_COOL Application-specific pre-cool (Not Used) 6 HVAC_OFF Controller not controlling outputs 7 HVAC_TEST Equipment being tested (Not Used) 8 HVAC_EMERG_HEAT Emergency heat mode (heat pump) (Not Used) 9 HVAC_FAN_ONLY Air not conditioned, fan turned on 10 HVAC_FREE_COOL Cooling with compressor not running (Not Used) 11 HVAC_ICE Ice-making mode (Not Used) 12 HVAC_MAX_HEAT Max Heat (Not Used) 13 HVAC_ECONOMY Economy (Not Used) 14 HVAC_DEHUMID Dehumidification 15 HVAC_CALIBRATE Calibrate (Not Used) 16 HVAC_EMERG_COOL Emergency Cool Mode (Not Used) 17 HVAC_EMERG_STEAM Emergency Steam Mode (Not Used) 0xFF = HVAC_NU ED

16 Auxiliary Heat Enable Input While a WSHP normally provides heating by running a compressor to transfer heat from the water loop to the space, some models have a secondary source of heat (i.e. electric heat). This input network variable is used to enable or disable auxiliary heat for models with supplemental electric heat. The default state is Null, in which case auxiliary heat is enabled. Auxiliary heat is typically used during an energy demand situation to save energy. When the entering water temperature is too low and auxiliary heating is the only source of heating, this variable setting is ignored, enabling auxiliary heating. Multistate Value Present _Value 85 MTIIIUC_WSHP.#######.AuxHeatEnable. Value 1 = Disabled 2 = Enabled 3 = Null Unsigned 1 byte 1-3 N Read, Writable, Commandable C LonWorks Name Profile SNVT Type SNVT Number nviauxheatenable SCC Heat Pump SNVT_switch 95 Uses Receive Heartbeat Switch Yes Typedef struct { } SNVT_switch; unsigned signed Value; State; Field Definitions Field Units Valid Range Notes Value % of Full Scale 0, 200 (0% or 100%) Intensity as percentage of full scale, resolution 0.5% State N/A 0, 1, -1 See table below. State Value Equivalent Percent Description 0 N/A N/A Disabled % Disabled 1 1 to to 99.5% Partially Enabled % Enabled -1 N/A N/A Null (no action from network) Note: Auxiliary heat is either fully enabled or it is disabled. There is no partially enabled state. If network setting is Null, then network command is ignored and Aux Heat is enabled. State = NULL ED

17 Binary Input Status This binary input is used to view the digital inputs of the unit controller for diagnostic purposes. The Service/Test Mode jumper position is returned as the present value. The bit description section includes a separate table for the single stage compressor and dual stage compressor WSHP units. Binary Input 3 1 Present Value 85 MTIIIUC_WSHP.#######.BinaryIn.(index) Boolean 1 byte Valid Range Array Index Array Index NULL returns Bit Number 0. N Read, Writable, Commandable R BI1.Description All the status bits are returned in the BI1.description property, high bit on the left and low bit on the right. For example: shows the Service/Test Mode jumper is true (shorted). LonWorks Name Profile SNVT Type SNVT Number nvobinaryin DaikinSCC_WSHP SNVT_state_ Service Type Uses Send Heartbeat Typedef struct { } SNVT_state_64; State Vector 8 bytes Unackd_rpt No unsigned bit0 unsigned bit1 unsigned bit63 Bit Description for Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and Vertical Stack Models VHC/VHF (v3.0 and Older) Bit Number Bit Description Jumper Setting Model Option Description Main Board Jumpers 0 Normal / Test Mode Jumper 1 = Open (0) Normal Operation Jumper 1 = Shorted (1) Service Test Mode Operation 1 Continuous / Cycling Fan Jumper 2 = Open (0) Continuous Fan, ignored if room sensor fan switch is present Jumper 2 = Shorted (1) Cycling Fan, ignored if room sensor fan switch is present 2 Loop Fluid Jumper 3 = Open (0) Water Loop Fluid Jumper 3 = Shorted (1) Glycol Loop Fluid 3 Not Used Jumper 4 = Open (0) 4 Room Sensor Setpoint Potentiometer Jumper 5 = Open (0) Short Range: -3º to +3º F (-1.67 º to º C) Range Jumper 5 = Shorted (1) Long Range: 55º to 95º F (12.78 º to ºC) 5 Thermostat / Room Sensor Jumper 6 = Open (0) Thermostat Control Jumper 6 = Shorted (1) Room Sensor Control 6 Not Used Jumper 7 = Open (0) 7 Not Used Jumper 8 = Open (0) ED

18 Bit Number Bit Description Jumper Setting Model Option Description 8 Low Pressure Switch Compressor #1 Main Board Inputs Closed (1) Low Pressure Switch for Compressor #1 is normal Open (0) Low Pressure Switch for Compressor #1 is in alarm 9 High Pressure Switch Compressor #1 Closed (1) High Pressure Switch for Compressor #1 is normal Open (0) High Pressure Switch for Compressor #1 is in alarm 10 Emergency Shutdown Open (0) Unit shuts down. 11 Occupancy Switch Open (0) Unoccupied 1 Switch Closed (1) Occupied 12 Timed Override (O on Thermostat) Switch Closed (1) In the unoccupied mode, if the timed override switch is pressed for more than 3 seconds but less than 10 seconds, the unit will go into the timed override mode (Thermostat has a pushbutton for timed override) 13 Fan (G on Thermostat) Switch Closed (1) Fan operation is requested 14 Cool Stage 1 (Y1 on Thermostat) Switch Closed (1) First stage of cooling is requested 15 Cool Stage 2 (Y2 on Thermostat) Switch Closed (1) Second stage of cooling is requested 16 Heat Stage 1 (W1 on Thermostat) Switch Closed (1) First stage of heating is requested 17 Heat Stage 2 (W2 on Thermostat) Switch Closed (1) Second stage of heating is requested 18 Number of Compressors Expansion Board Jumpers Jumper 1 = Open (0) Jumper 1 = Shorted (1) 19 Hot Gas/Water Reheat (HGR) Jumper 2 = Open (0) Jumper 2 = Shorted (1) 20 & 21 Secondary Heating Options Jumper 3 = Open (0) (2 Jumpers) Jumper 4 = Open (0) Jumper 3 = Shorted (1) Jumper 4 = Open (0) Jumper 3 = Open (0) Jumper 4 = Shorted (1) 22 & 23 Fan Speed Selection Jumper 5 = Open (0) (2 Jumpers) Jumper 6 = Open (0) Jumper 5 = Shorted (1) Jumper 6 = Open (0) Jumper 5 = Open (0) Jumper 6 = Shorted (1) 24 Not Used Jumper 7 = Open (0) 25 Not Used Jumper 8 = Open (0) 26 Low Pressure Switch Compressor #2 Expansion Board Inputs Closed (1) Open (0) 27 High Pressure Switch Compressor #2 Closed (1) Open (0) 28 Dehumidification Request (Humidistat) Closed (1) Open (0) 29 Not Used N/A 30 Not Used N/A 31 2 Unit Heat/Cool/Dehumid Mode Provided by Unit Controller Single Compressor Dual Compressor None Hot Gas/Water Reheat (HGR) None Supplemental Electric Heat Boilerless Electric Heat Single Speed Fan Two Speed Fan Three Speed Fan Low Pressure Switch for Compressor #2 is normal Low Pressure Switch for Compressor #2 is in alarm High Pressure Switch for Compressor #2 is normal High Pressure Switch for Compressor #2 is in alarm Dehumidification is required Dehumidification is not required 0=Heating, 1=Cooling or Dehumidification Provides Mode awareness in Fan Only State ED

19 Bit Description for SmartSource Models GTH/GTV and GSH/GSV (v5.0 and Newer) Bit Number Bit Description Jumper Setting Model Option Description 0 Normal / Test Mode Main Board Jumpers Jumper 1 = Open (0) Normal Operation Jumper 1 = Shorted (1) Service Test Mode Operation 1 Continuous / Cycling Fan Jumper 2 = Open (0) Continuous Fan, ignored if room sensor fan switch is present Jumper 2 = Shorted (1) Cycling Fan, ignored if room sensor fan switch is present 2 Loop Fluid Jumper 3 = Open (0) Water Loop Fluid Jumper 3 = Shorted (1) Glycol Loop Fluid 3 Freeze Fault Protection Jumper 4 = Open (0) None Jumper 4 = Shorted (1) Freeze Fault Protection is Enabled 4 Room Sensor Setpoint Potentiometer Jumper 5 = Open (0) Short Range: -5º to +5º F (-2.78º to +2.78º C) Range Jumper 5 = Shorted (1) Long Range: 55º to 95º F (12.78º to 35.00º C) 5 Thermostat / Room Sensor Jumper 6 = Open (0) Thermostat Control Jumper 6 = Shorted (1) Room Sensor Control 6 Compressor Heating Source Jumper 7 = Open (0) Allow Compressor Heating Mode Operation Jumper 7 = Shorted (1) Disable Compressor Heating Mode Operation 7 I/O Expansion Module Jumper 8 = Open (0) I/O Expansion Board Not Present Jumper 8 = Shorted (1) I/O Expansion Board Is Required 8 Compressor Low Pressure Switch Main Board Inputs Closed (1) Compressor Low Pressure Switch is Normal Open (0) Compressor Low Pressure Switch is in Alarm 9 Compressor High Pressure Switch Closed (1) Compressor High Pressure Switch is Normal Open (0) Compressor High Pressure Switch is in Alarm 10 Emergency Shutdown Open (0) Unit shuts down. 11 Occupancy Switch Open (0) Unoccupied 1 Switch Closed (1) Occupied 12 Heat Stage #3 (W3 on Thermostat) Switch Closed (1) Third stage of heating is requested. 13 Fan (G on Thermostat) Switch Closed (1) Fan operation is requested. 14 Cool Stage #1 (Y1 on Thermostat) Switch Closed (1) First stage of cooling is requested. 15 Cool Stage #2 (Y2 on Thermostat) Switch Closed (1) Second stage of cooling is requested. 16 Heat Stage #1 (W1 on Thermostat) Switch Closed (1) First stage of heating is requested. 17 Heat Stage #2 (W2 on Thermostat) Switch Closed (1) Second stage of heating is requested. Expansion Board Jumpers 18 Not Used Jumper 1 = Open (0) & 21 Not Used Secondary Heating Options (2 Jumpers) Jumper 2 = Open (0) Jumper 3 = Open (0) Jumper 4 = Open (0) Jumper 3 = Shorted (1) Jumper 4 = Open (0) Jumper 3 = Open (0) Jumper 4 = Shorted (1) 22 & 23 Dehumidification Options Jumper 5 = Open (0) (2 Jumpers) Jumper 6 = Open (0) Jumper 5 = Shorted (1) Jumper 6 = Open (0) Jumper 5 = Open (0) Jumper 6 = Shorted (1) 24 Not Used Jumper 7 = Open (0) 25 Compressor Capacity Option Jumper 8 = Open (0) Jumper 8 = Shorted (1) None Supplemental Electric Heat Boilerless Electric Heat None Hot Gas/Water Reheat (HGR) Waterside Economizer Single Stage Capacity Compressor Dual Stage Capacity Compressor Expansion Board Inputs 26 Heat Stage #4 (W4 on Thermostat) Switch Closed (1) Fourth stage of heating is requested. 27 Compressor High Capacity High Pressure Cutout Switch Closed (1) Compressor High Capacity High Pressure Switch is Normal Open (0) Compressor High Capacity High Pressure Switch is in Alarm 28 Dehumidification Request (Humidistat) Closed (1) Dehumidification is required Open (0) Dehumidification is not required 29 & 30 Fan Speed Lookup Table Row Select Binary: 00, 01, 10, 11 Fan speed duty cycle lookup table row selection 31 2 Unit Heat/Cool/Dehumid Mode Provided by Unit Controller 0=Heating, 1=Cooling or Dehumidification Provides Mode awareness in Fan Only State 1 This switch is effective only when the network scheduling is not in use. 2 msb = Most Significant Bit ED

20 All bits = 0 Binary Output Status This binary output is used to view the digital outputs of the unit controller for diagnostic purposes. Compressor #1 state is returned in the present value. The bit description section includes separate tables for Enfinity (single stage compressor/vertical stack) and SmartSource WSHP units. Binary Value 5 2 Present Value 85 MTIIIUC_WSHP.#######.BinaryOut.(index) Boolean 1 byte Valid Range Array Index Array Index NULL returns Bit Number 0. N Read, Writable, Commandable R BO1.Description All the status bits are returned in the BO1.description property, high bit on the left and low bit on the right. For example: shows Compressor#1 is on. Fan On/Low is indicated in the next bit. LonWorks Name Profile SNVT Type SNVT Number nvobinaryout DaikinSCC_WSHP SNVT_state 83 Service Type Uses Send Heartbeat Typedef struct { }SNVT_state unsigned bit0 unsigned bit1... unsigned bit15 State Unackd_rpt No Bit Description for Enfinity Models MHC/MHW, CCH/CCW, VFC/VFW, LVC/LVW and Vertical Stack models VHC/VHF (v3.0 and Older) Bit Number Bit Description Value Description Main Board Outputs 0 Compressor #1 ON Compressor #1 Request 1 Fan or Fan Low Speed ON Fan Request On (Single Speed Fan) or Fan Request At Low Speed (Multispeed Fan) 2 Reversing Valve #1 ON Heating Position For Compressor #1 OFF Cooling Position For Compressor #1 3 Pump Request / Isolation Valve ON Water Flow Is Required 4 Thermostat Alarm ON Alarm light is energized when there is no fault (Thermostat Only) OFF Alarm light is de-energized when there is a fault 5 Remote Circuit #1 Red LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #1. 6 Remote Circuit #1 Green LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #1. ED

21 Bit Number Bit Description Value Description 7 Remote Circuit #1 Yellow LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #1. 8 Room Sensor Status LED ON Indicates the room sensor status LED is on steady. Will be on when the unit controller is in either the occupied or bypass modes. OFF Indicates the room sensor status LED is either flashing or constantly off. Expansion Board Outputs 9 Compressor #2 or Fan Medium Speed ON Compressor #2 Request or Fan Request At Medium Speed 10 Reversing Valve #2 or Secondary Heating ON Heating Position For Compressor #2 or Secondary Heating On Request OFF Cooling Position For Compressor #2 or Secondary Heating Off Request 11 Hot Gas Reheat (HGR) ON Hot Gas Reheat (HGR) Request 12 Fan High Speed ON Fan Request At High Speed 13 Remote Circuit #2 Red LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #2. 14 Remote Circuit #2 Green LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #2. 15 (MSB) 1 Remote Circuit #2 Yellow LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #2. Bit Description for SmartSource Models GTH/GTV and GSH/GSV (v5.0 and Newer) Bit Number Bit Description Value Description Main Board Outputs 0 Compressor ON Compressor Request 1 Fan Main ON Fan Main Request 2 Reversing Valve ON Heating Position For Compressor OFF Cooling Position For Compressor 3 Pump Request / Isolation Valve ON Water Flow Is Required 4 Thermostat Alarm ON Alarm light is energized when there is a fault (Thermostat Only) OFF Alarm light is de-energized when there is no fault 5 Remote Circuit #1 Red LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #1. 6 Remote Circuit #1 Green LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #1. 7 Remote Circuit #1 Yellow LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #1. 8 Room Sensor Status LED ON Indicates the room sensor status LED is on steady. Will be on when the unit controller is in either the occupied or bypass modes. OFF Indicates the room sensor status LED is either flashing or constantly off. Expansion Board Outputs 9 Compressor High Stage Capacity ON Compressor High Stage Capacity Request 10 Auxiliary Heat Stage #1 ON Auxiliary Heat Stage #1 On Request 11 HGR / Waterside Economizer ON HGR / Waterside Economizer Request 12 Auxiliary Heat Stage #2 ON Auxiliary Heat Stage #2 On Request 13 Remote Circuit #2 Red LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #2. 14 Remote Circuit #2 Green LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #2. 15 (MSB) 1 Remote Circuit #2 Yellow LED ON / OFF Red, Green, and Yellow LED s are used in combination to indicate the unit controller fault / status mode for circuit #2. 1 MSB = Most Significant Bit All bits = 0 ED

MicroTech 2000 Water Source Heat Pump Unit Controller Protocol Information

MicroTech 2000 Water Source Heat Pump Unit Controller Protocol Information Engineering Data ED 15054-3 Group: Controls Part Number: ED15054 Date: October 2012 Supersedes: ED15054-2 MicroTech 2000 Water Source Heat Pump Unit Controller Protocol Information LonWorks Networks Table

More information

Packaged Fresh Air Unit With Tracer LCI-I

Packaged Fresh Air Unit With Tracer LCI-I Product Data Sheet Packaged Fresh Air Unit With Tracer LCI-I Order No. FAXA-SLM001-EN Date: April 2002 Figure 1. Packaged Fresh Air unit with Tracer LCI-I Packaged Fresh Air Unit Overview Packaged Fresh

More information

Installation- & user instructions

Installation- & user instructions Installation- & user instructions for NILAN LON module for CTS6000 Valid for: CTS6000, - SW 1.0064. Version 1.04, 08.12.2011 Contents Contents... 2 Figure table... 3 General description of NilLON... 4

More information

CORRIGO R10. LonMark Functional Profile: Chilled Ceiling Controller Corrigo R10 LonWorks Interface: LonMark Chilled Ceiling Controller

CORRIGO R10. LonMark Functional Profile: Chilled Ceiling Controller Corrigo R10 LonWorks Interface: LonMark Chilled Ceiling Controller CORRIGO R10 LonMark Functional Profile: Chilled Ceiling Controller 8070 1 P0109 TLM Corrigo R10 Manual.doc 2 P0109 TLM Corrigo R10 Manual.doc Content CONTENT...3 OVERVIEW...5 R10-LON FUNCTIONAL DESCRIPTION...5

More information

Maverick I Commercial Packaged Rooftop Systems Protocol Information

Maverick I Commercial Packaged Rooftop Systems Protocol Information Engineering Data ED 15125-1 Group: Controls Part Number: ED 15125 Date: September 2010 Supersedes: ED 15125 Maverick I Commercial Packaged Rooftop Systems Protocol Information Networks Networks 2010 McQuay

More information

Maverick I Commercial Packaged Rooftop Systems Protocol Information

Maverick I Commercial Packaged Rooftop Systems Protocol Information Engineering Data ED 15125-3 Group: Controls Part Number: ED 15125 Date: July 2013 Supersedes: ED 15125-2 Maverick I Commercial Packaged Rooftop Systems Protocol Information Networks Networks 2014 Daikin

More information

Installation- & user instructions

Installation- & user instructions Installation- & user instructions for NILAN LON module for CTS6000 Valid for: CTS6000, SW 1.0092 Version 1.07, 16-12-2015 Contents Contents... 2 Figure table... 3 General description of NilLON... 4 Installation...

More information

Magnitude TM Chiller Unit Controller Protocol Information

Magnitude TM Chiller Unit Controller Protocol Information Engineering Data ED 15117 Group: Controls Part Number: ED 15117 Date: April 2010 Supersedes: New Magnitude TM Chiller Unit Controller Protocol Information Networks (MS/TP, IP, Ethernet) Networks Daikin

More information

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928-2 Group: Controls Part Number: 669207702 Date: March 2011 Supersedes: IM 928-1 MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module NOTICE

More information

MODEL 2000T Initial Draft

MODEL 2000T Initial Draft TEMPERATURE DISPLAY AND COMMAND MODULE On-board temperature sensor. Mounts on any standard single-gang wiring conduit box. Compact, thin and stylish design. Only 2.8 W x 4.55 H x 0.79 D Sensing element

More information

KITS AND ACCESSORIES. Prodigy LonTalk MODULE KIT INSTALLATION INSTRUCTIONS FOR LONTALK MODULE KIT (54W27) USED WITH ENERGENCE ROOFTOP UNITS.

KITS AND ACCESSORIES. Prodigy LonTalk MODULE KIT INSTALLATION INSTRUCTIONS FOR LONTALK MODULE KIT (54W27) USED WITH ENERGENCE ROOFTOP UNITS. 2011 Lennox Industries Inc. Dallas, Texas, USA KITS AND ACCESSORIES 506693 01 07/11 Supersedes 04/11 INSTALLATION INSTRUCTIONS FOR LONTALK MODULE KIT (54W27) USED WITH ENERGENCE ROOFTOP UNITS Litho U.S.A.

More information

Installation and Maintenance Manual IM 928-5

Installation and Maintenance Manual IM 928-5 Installation and Maintenance Manual IM 928-5 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module Group: Controls Part Number: IM 928 Date: February 2016 Table of Contents Introduction....

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1013-1 MicroTech III Fan Coil BACnet MS/TP Communication Module Group: Controls Part Number: IM 1013 Date: February 2016 Table of Contents Introduction.... 3 Revision

More information

VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications

VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications Product overview VT7200 Series 24 Vac Low Voltage Zoning Thermostats For Commercial HVAC Applications 1 The VT7200 PI thermostat family is specifically designed for zoning applications. Typical applications

More information

MicroTech 2000 Water Source Heat Pump Unit Controller

MicroTech 2000 Water Source Heat Pump Unit Controller Installation Manual IM 660-4 Group: Controls Part Number: IM 660 Date: June 2012 Supersedes: IM 660-3 MicroTech 2000 Water Source Heat Pump Unit Controller NOTICE Use this manual to physically install

More information

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module

MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928- Group: Controls Part Number: 66920770 Date: July 2009 Supersedes: IM 928 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module NOTICE Use this

More information

LonWorks Integration Manual ITG-VT72_73-PIR-LON-E07 ( R7 Issue Date: February 3, 2009)

LonWorks Integration Manual ITG-VT72_73-PIR-LON-E07 ( R7 Issue Date: February 3, 2009) PIR Ready VT72xx & VT73xx Series 24 Vac Fan Coil and Zoning Thermostats For Commercial and Lodging HVAC Applications LonWorks Integration Manual ITG-VT72_73-PIR-LON-E07 (028-6008 R7 Issue Date: February

More information

PIR Ready SE72xx & SE73xx Series 24 VAC Fan Coil and Zoning Controllers For Commercial and Lodging HVAC Applications LonWorks Integration Manual

PIR Ready SE72xx & SE73xx Series 24 VAC Fan Coil and Zoning Controllers For Commercial and Lodging HVAC Applications LonWorks Integration Manual 1 PIR Ready SE72xx & SE73xx Series 24 VAC Fan Coil and Zoning Controllers For Commercial and Lodging HVAC Applications LonWorks Integration Manual 2 SE7200x Series Product Overview The SE7200 PI controller

More information

Functional Profile: Chiller

Functional Profile: Chiller Version: 1.0 Chiller: 8040 LONMARK Functional Profile: Chiller LONMARK Functional Profile: Chiller 1 8040-10 1996, LONMARK Interoperability Association. Echelon, LON, LONWORKS, LONMARK, and the LONMARK

More information

RCM Room Command Module New Style

RCM Room Command Module New Style LONWoRKS Compatible Controllers Manual Product Bulletin Issue Date 08 2005 RCM Room Command Module New Style The newly styled RCM Room Command Module is designed for use with LONMARK compliant space comfort

More information

PIR Ready VT7600 Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. LonWorks Integration Manual (September 1, 2010)

PIR Ready VT7600 Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications. LonWorks Integration Manual (September 1, 2010) PIR Ready VT7600 Series Programmable & Non-Programmable Thermostats For Commercial HVAC Applications LonWorks Integration Manual (September 1, 2010) 1 Product Overview The VT7600 PI thermostat family is

More information

LonWorks Integration Manual ITG-VT(R)72_73-PIR-LON-E08 ( R8 Issue Date: January 17, 2013)

LonWorks Integration Manual ITG-VT(R)72_73-PIR-LON-E08 ( R8 Issue Date: January 17, 2013) PIR Ready VT72xx & VT(R)73xx Series 24 Vac Fan Coil and Zoning Controllers For Commercial and Lodging HVAC Applications LonWorks Integration Manual ITG-VT(R)72_73-PIR-LON-E08 (028-6008 R8 Issue Date: January

More information

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller

WSHP-IOP-2 May Installation, Operation, and Programming. Tracer ZN510 Controller WSHP-IOP-2 May 1998 Installation, Operation, and Programming Tracer ZN510 Controller Literature History The Trane Company has a policy of continuous product improvement and it reserves the right to change

More information

M7410G LINEAR VALVE ACTUATOR WITH LON CAPABILITIES AND OPTIONAL PI-CONTROL

M7410G LINEAR VALVE ACTUATOR WITH LON CAPABILITIES AND OPTIONAL PI-CONTROL M7410G LINEAR VALVE ACTUATOR WITH LON CAPABILITIES AND OPTIONAL PI-CONTROL CONTENTS APPLICATION... 2 FEATURES... 2 DEVICE SPECIFICATIONS... 3 OPERATION... 3 VERSIONS... 3 PLUG-INS, XIF FILES AND DRF FILES...

More information

Itho Lon module for DCW

Itho Lon module for DCW Itho Lon module for DCW Functional Profile: Ventilation Unit UFPTventilationUnit Ventilation Unit: 20100 Version 1.0 August 2008 Compliant with LonMark Application- Layer Interoperability Guidelines Ver.

More information

MicroTech II Self-Contained Unit Controller Protocol Information

MicroTech II Self-Contained Unit Controller Protocol Information Engineering Data ED15061-0 Group: Controls Date: May 2002 MicroTech II Self-Contained Unit Controller Protocol Information Networks Networks Contents Figures Figures... 1 Revision History... 2 Software

More information

BACnet MS/TP Interface User s Guide

BACnet MS/TP Interface User s Guide PoolPak MPK with CommandPak Control System CPCS BACnet MS/TP Interface User s Guide DOCUMENT #: SVW07-BACNET-MSTP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1084-2 Group: WSHP Part Number: 910167578 Date: July 2015 MicroTech III Boilerless System Kit for use with all MicroTech III Controlled Water Source Heat Pumps Description

More information

LonWorks Integration Instructions

LonWorks Integration Instructions LonWorks Communicating Room Controllers LonWorks Integration Instructions PIR Ready SE7600 Series Programmable & Non-Programmable Controllers for Commercial HVAC Applications CONTENTS Product Overview

More information

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification

Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification Viconics VT76x6W Water-source Heat Pump Controllers Engineering Guide Specification General The VT76xxW series is designed for single-stage and multi-stage control of water source heat pumps with dedicated

More information

Software Application wrf08_03 (Lighting, Blinds, Air-Conditioning Control) For model WRF08 T6 T8 T5 T6 T7 T8. Messwert Value

Software Application wrf08_03 (Lighting, Blinds, Air-Conditioning Control) For model WRF08 T6 T8 T5 T6 T7 T8. Messwert Value wrf08_03 Software Application wrf08_03 (Lighting, Blinds, Air-Conditioning Control) For model WRF08 The multi-function room operating panel WRF08 is designed for temperature detection and integrated control

More information

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide

Quick Start Guide DDC (2014/02) Subject to change without prior notice Quick Start Guide Quick Start Guide 560/583 DDC 8733914716(2014/02) Please refer to the included Hardware User s Guide and BACview Installation and Operation Manual for more detailed information on setting up and using

More information

MicroTech II AAF -HermanNelson Unit Ventilator Unit Controller Protocol Information

MicroTech II AAF -HermanNelson Unit Ventilator Unit Controller Protocol Information Engineering Data ED15065-5 Group: Controls Part Number: ED15065 Date: August 2007 Supersedes: ED15065-4 MicroTech II AAF -HermanNelson Unit Ventilator Unit Controller Protocol Information Networks Networks

More information

MicroTech II AAF -HermanNelson Unit Ventilator Unit Controller Protocol Information

MicroTech II AAF -HermanNelson Unit Ventilator Unit Controller Protocol Information Engineering Data ED15065-3 Group: Controls Part Number: ED15065-3 Date: July 2004 Supersedes: ED15065-2 MicroTech II AAF -HermanNelson Unit Ventilator Unit Controller Protocol Information Networks LONWORKS

More information

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP

PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP PoolPak MPK with CommandPak Control System CPCS BACnet /IP User s Guide DOCUMENT #: SVW07-MPKBACNIP-20171020 UPDATED: OCTOBER 2017 INTRODUCTION PoolPak dehumidifiers equipped with an CommandPak Control

More information

Introduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers

Introduction. To use Carrier wireless sensors, you must have: A i-vu v6.5 or later system v6-00 or later drivers Wireless Sensor CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-583-01 6/2/2017 Verify that you have the most current version of this

More information

Applications Application is compatible with Q1 Hardware. Compatible with Roof Top Unit equipment up to 4 stages of cooling or heating, analog or floating-point valves or digital stages, discharge pressure/variable

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 852-2 Group: Controls Part Number: IM 852 Date: January 2008 Supercedes: IM 852-1 MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module

More information

Modbus Integration Integration for Modbus Functionality for VTR8300 Series

Modbus Integration Integration for Modbus Functionality for VTR8300 Series Modbus Integration Integration for Modbus Functionality for VTR8300 Series Building Management System *For data visualization and analysis Modbus Controller VT8000 Series room controllers 2 TABLE OF CONTENTS

More information

NB-ASC Family Protocol Implementation Conformance Statement (PICS)

NB-ASC Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-ASC Family Product l Number: NB-ASC, NB-ASCe, NB-Rooftop, NB-Heat Pump, NB-Fancoil Firmware Revision: 6.03 BACnet Protocol Revision: 4 Product Description:

More information

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller Technical Specification Sheet Document No. 149-851 September 24, 2014 Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller The Siemens BACnet PTEC Dual Duct Controller provides

More information

TAC Xenta 121-HP Programmable Heat Pump Application

TAC Xenta 121-HP Programmable Heat Pump Application TAC Vista TAC Xenta 121-HP Programmable Heat Pump Application TAC Xenta 121-HP is an easily programmable controller intended for heat pumps, with or without re-heat. It can be configured for use with 1,

More information

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN

Tracer Controls. Tracer ZN517 Unitary Controller BAS-PRC012-EN Tracer Controls Tracer Unitary Controller 7 April 2003 BAS-PRC012-EN Introduction The Tracer unitary controller provides digital control that is similar to that of a wall thermostat. It supports the following

More information

Siemens BACnet Programmable TEC Constant Volume

Siemens BACnet Programmable TEC Constant Volume Technical Specification Sheet Document No. 149-852 September 24, 2014 Siemens BACnet Programmable TEC Constant Volume Returns from power failure without operator intervention. No calibration required,

More information

LONWORKS Plug-In Software

LONWORKS Plug-In Software Installation and Maintenance Manual IM 933 Group: McQuay Controls Part Number: IM 933 Date: September 2008 Supercedes: New LONWORKS Plug-In Software For use with the MicroTech III Unitary Controller -

More information

Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet

Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE , BACnet Engineering Data ED 15126 Group: Controls Part Number: ED 15126 Date: April 2010 Supersedes: New Maverick I Commercial Packaged Rooftop Systems Unit Controller Protocol Implementation Conformance Statement

More information

MicroTech II Vertical Self-contained Systems Unit Controller

MicroTech II Vertical Self-contained Systems Unit Controller Installation and Maintenance IM-710 Group: Applied Systems Part Number: IM710 Date: February 2002 MicroTech II Vertical Self-contained Systems Unit Controller Used with McQuay models: SWP and SWT BACK

More information

NB-VAV Family Protocol Implementation Conformance Statement (PICS)

NB-VAV Family Protocol Implementation Conformance Statement (PICS) Vendor Name: American Auto-Matrix Product Name: NB-VAV Family Product Model Number: NB-VAVta, NB-VAVtf, NB-VAVra, NB-VAVrf, NB-VAVr, NB-VAVta-IAQ, NB-VAVtf-IAQ Firmware Revision: 6.03 BACnet Protocol Revision:

More information

Daikin McQuay. Enfinity Water Source Heat Pump Ceiling Mounted. WCCH, WCCW 072, 096, 120 Design 1

Daikin McQuay. Enfinity Water Source Heat Pump Ceiling Mounted. WCCH, WCCW 072, 096, 120 Design 1 Replacement Parts List No. 700017500 Revision C 10/2015 Daikin McQuay Enfinity Water Source Heat Pump Ceiling Mounted WCCH, WCCW 072, 096, 120 Design 1 To find your Daikin Applied parts distributor, call

More information

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller

Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller Technical Specification Sheet Document No. 149-851 August 12, 2011 Siemens BACnet Programmable TEC Dual Duct Two Air Velocity Sensors Controller The Siemens BACnet PTEC Dual Duct Controller provides high

More information

SE8000 Series BACnet Integration Terminal Equipment Controller. Commercial and Lodging HVAC Applications

SE8000 Series BACnet Integration Terminal Equipment Controller. Commercial and Lodging HVAC Applications BACnet Integration Terminal Equipment Controller Commercial and Lodging HVAC Applications 2 SER8300 AND SE8300 SERIES PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS) Vendor Name: Schneider Electric

More information

Modbus Register Map: InRow ACRD60x / ACRC60x

Modbus Register Map: InRow ACRD60x / ACRC60x Modbus Map: InRow ACRD60x / ACRC60x Notes: 1. 16-bit registers (INT16, UINT16, ENUM) are transmitted MSB first (i.e., big-endian). 2. INT32 and UINT32 are most-significant word in n+0, least significant

More information

NB-V3Tb Protocol Implementation Conformance Statement (PICS)

NB-V3Tb Protocol Implementation Conformance Statement (PICS) NB-V3Tb Vendor Name: American Auto-Matrix Product Name: NB-V3Tb Product Model Number: NB-V3Tb Firmware Revision: 6.03 BACnet Protocol Revision: 4 Product Description: NB-V3Tb is a full-featured VVT system

More information

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet DataSheet ev 1.12.307/4.0 June 14, 2018 Operating Sequence Standard Occupied During normal occupied

More information

LONMARK Functional Profile: Refrigerated Display Case Controller: Defrost Object

LONMARK Functional Profile: Refrigerated Display Case Controller: Defrost Object Version 1.0 Refrigerated Display Case Controller Defrost Object : 10010 LONMARK Functional Profile: Refrigerated Display Case Controller: Defrost Object 10010-10 1997, LONMARK Interoperability Association

More information

Siemens BACnet Programmable TEC Unit Vent Controller

Siemens BACnet Programmable TEC Unit Vent Controller Technical Specification Sheet Document No. 149-833 August 12, 2011 Siemens BACnet Programmable TEC Unit Vent Controller The Siemens BACnet PTEC Unit Vent Controller provides high performance Direct Digital

More information

Siemens BACnet Programmable TEC Unit Conditioner Controller

Siemens BACnet Programmable TEC Unit Conditioner Controller Technical Specification Sheet Document No. 149-831 September 24, 2014 Siemens BACnet Programmable TEC Unit Conditioner Controller Returns from power failure without operator intervention. No calibration

More information

Tracer Controls. Tracer MP.501 Controller BAS-PRC008-EN. June 2001

Tracer Controls. Tracer MP.501 Controller BAS-PRC008-EN. June 2001 Tracer Controls Tracer MP.501 Controller June 2001 BAS-PRC008-EN Introduction The Tracer MP.501 controller is a configurable, multi-purpose controller used to provide direct-digital control for heating,

More information

Excel 10 W7751B,D,F VAV II Controllers

Excel 10 W7751B,D,F VAV II Controllers Excel 10 W7751B,D,F VAV II Controllers FEATURES W7751D GENERAL W7751B W7751F The W7751B,D,F are Variable Air Volume (VAV) Controllers in the Excel 10 family product line. These VAV systems provide pressure

More information

MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP)

MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) Installation and Maintenance Manual IM 967 Group: Controls Part Number: IM 967 Date: October 2009 Supercedes: New MicroTech III McQuay Chiller Unit Controller BACnet Communication Module (MS/TP) Pathfinder

More information

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller Technical Specification Sheet Document No. 149-831 August 12, 2011 Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller No calibration required, thereby reducing maintenance costs. PID

More information

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control

Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control Technical Specification Sheet Document No. 149-841 August 12, 2011 Siemens BACnet Programmable TEC Unit Vent Controller for Smoke Control The Siemens BACnet PTEC Unit Vent Controller provides high performance

More information

Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)

Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet) Installation and Maintenance Manual IM 963 Group: Controls Part Number: IM 963 Date: April 2010 Supercedes: New Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet) Daikin

More information

Applications Application is compatible with Q1 Hardware. Compatible with Air Handling Unit equipment up to 6 stages of cooling or heating, analog or floating point valves or digital stages, discharge pressure/variable

More information

Applications Application is compatible with Q2 Hardware. Compatible with Air Handling Unit equipment up to 6 stages of cooling or heating, analog or floating point valves or digital stages, discharge pressure/variable

More information

1201L-1K RTD Controller. Revision 1.1. Nico Technology Ltd. 1 Rev.1.1

1201L-1K RTD Controller. Revision 1.1. Nico Technology Ltd. 1 Rev.1.1 1201L-1K RTD Controller Revision 1.1 Nico Technology Ltd. 24F,No.37,SanMin Rd, 2.Sec, PanChiao City, Taipei County, Taiwan Phone +886-2-2954-5338 Fax +886-2-2954-5308 Product Info Thomas@nico-tech.com

More information

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010

Product Catalog. Tracer Controls Tracer ZN517 Unitary Control BAS-PRC012-EN. August 2010 Product Catalog Tracer Controls Tracer Unitary Control August 2010 BAS-PRC012-EN Introduction The Tracer unitary controller provides digital control that is similar to that of a wall thermostat. It supports

More information

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC. RATING IS 1 AMP COND. B ENABLE COOL B ENABLE.

COND. A ENABLE RELAY CONTACT COOLA ENABLE 24 VAC.   RATING IS 1 AMP COND. B ENABLE COOL B ENABLE. Factory Packaged Controls Coil Products Two Head Pressure Module Orion No.:OE370-23-HP2C 1 2 3 4 www.aaon.com www.orioncontrols.com Circuit A1 TRANSDUCER #1 Circuit A2 TRANSDUCER #2 Circuit B1 TRANSDUCER

More information

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet

ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet ExactLogic BACnet Communicating Thermostat EXL01816 Sequence Datasheet DataSheet ev 1.12.307/4.0 Jun 20, 2018 Operating Sequence Standard Occupied During normal occupied operation the display will show

More information

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control

Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control Technical Specification Sheet Document No. 149-844 August 12, 2011 Siemens BACnet Programmable TEC Unit Conditioner (Fan Coil) Controller for Smoke Control Returns from power failure without operator intervention.

More information

VTR8300 User Interface Guide VTR8300 Room Controller Series

VTR8300 User Interface Guide VTR8300 Room Controller Series VTR8300 User Interface Guide VTR8300 Room Controller Series CONTENTS Home Screen Display 2 How to Enter Setup Screen 3 Setup Screen Display 3 Network Settings 4 ZigBee Network Settings 4 BACnet Network

More information

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet DataSheet ev 1.12.302/4.3 October 27, 2014 Operating Sequence Standard Occupied During normal occupied operation the display will

More information

SE8000 Series BACnet Integration

SE8000 Series BACnet Integration SE8000 Series BACnet Integration BACnet Integration for SE8000 Series Room Controller BACnet CONTROLLER Version 4 2 Table of Contents SE8000 BACnet Compatibility Specifications 3 Object Properties 4-8

More information

LX Series Application-Specific Controllers

LX Series Application-Specific Controllers LX Series Application-Specific Controllers Product Bulletin LX-FCUL-1, LX-RTUL-1,LX-HPUL-1, LX-UVL-1 Code No LIT-12011494 Issued June 22, 2009 The LX Series application-specific controller family includes

More information

BACnet VAV Actuator Start-up Guide IM 1040

BACnet VAV Actuator Start-up Guide IM 1040 BACnet VAV Actuator Start-up Guide IM 1040 Group: Controls Part Number: IM 1040 Date: 3/4/2010 Supersedes: New BACnet VAV Actuator--Electronic Output Start-up Procedures 2010 McQuay International Table

More information

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005

Tracer Controls. Tracer MP501 Controller BAS-PRC008-EN. January 2005 Tracer Controls Tracer MP501 Controller January 2005 BAS-PRC008-EN Introduction The Tracer MP501 controller is a configurable, multi-purpose controller used to provide direct-digital control for heating,

More information

BACnet FF Configuration Wizard Guide

BACnet FF Configuration Wizard Guide BACnet FF Configuration Wizard Guide TABLE OF CONTENTS SYSTEM ENGINEERING GUIDE INTRODUCTION... 3 WEBStation-AX... 3 Features... 3 BACnet FF Configuration Wizard... 3 BACnet FF Configuration Requirement...

More information

MicroTech Unit Ventilator Controller

MicroTech Unit Ventilator Controller Installation & Maintenance Data IM 613-1 MicroTech Unit Ventilator Controller Group: Unit Ventilator Part No.: 106102101 Date: July 1999 Used with AAF-HermanNelson Models AVS, AVV, AVR, AHF, AHV, AHR,

More information

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet or IP Installation and Maintenance Manual IM 853 Group: Controls Part Number: IM 853 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module, Ethernet

More information

MicroTech II ServiceTools for Applied Air Handling Unit Controllers

MicroTech II ServiceTools for Applied Air Handling Unit Controllers Users Manual UM 734-6 Group: Controls Part Number: UM 734 Date: June 2007 Supersedes: UM 734-5 MicroTech II ServiceTools for Applied Air Handling Unit Controllers Rooftop Models RPS, RAH, RDT, RFS/RCS,

More information

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules Technical Specification Sheet Document No. 149-855 October 5, 2012 BACnet Lab and Pressurized Room Controllers with Off-board Air Modules Off-board Air Module Figure 1. Lab Controller Module. The OAM (Figure

More information

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN Installation and Operation Tracer MP501 Controller CNT-SVX08B-EN Installation and Operation Tracer MP501 Controller CNT-SVX08B-EN April 2005 CNT-SVX08B-EN Tracer MP501 Controller Installation and Operation

More information

Applications Application is compatible with Q1 Hardware. Compatible with any supply/exhaust fans or space heating/cooling equipment. Will control up to 8 individual spaces on a single controller. A cost

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

Grundfos CIM 100 and CIU 100

Grundfos CIM 100 and CIU 100 GRUNDFOS INSTRUCTIONS Grundfos CIM 100 and CIU 100 LONworks for Grundfos E-pumps and Hydro Multi-E Functional profile and user manual Pump connected to CIU 100 via GENIbus LON network CIU 100 GENIbus RS-485

More information

MLM Integration with BMS

MLM Integration with BMS DOCUMENT NUMBER: BW0070-3 June 2015 Technopark STELLENBOSCH 7600 June 2015 Table of Contents MLM Integration with BMS... 1 MCU 2 Gateway Overview... 3 Output from BMS... 3 Input to BMS... 4 Zone/Master/Slave

More information

SER8300 / SE8300 Series BACnet Integration Terminal Equipment Controller

SER8300 / SE8300 Series BACnet Integration Terminal Equipment Controller 1 BACnet Integration Terminal Equipment Controller Commercial and Lodging HVAC Applications BACnet CONTROLLER 2 BACnet Integration Manual SER8300 AND SE8300 SERIES PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT

More information

System Controls Suggested Specification

System Controls Suggested Specification 1. Description A. Rooftop Unit Controller The Rooftop Unit Controller shall come equipped with a proportional-integral (PI) controller for accurate temperature control. The rooftop unit controller shall

More information

M1000 INTELLIGENT ZONE CONTROL SYSTEM

M1000 INTELLIGENT ZONE CONTROL SYSTEM HARDWARE GUIDE DIMENSIONS & SPECIFICATIONS REV. 5.2 M1000 INTELLIGENT ZONE CONTROL SYSTEM ROOFTOP CONTROLLER 2 Table of Contents GENERAL INFORMATION... 3 PL-M1000 Rooftop Controller...3 Description...3

More information

ECC-VAVS and ECC-VAV Series

ECC-VAVS and ECC-VAV Series LONMARK Certified Single Duct VAV/VVT Configurable Controllers Applications Designed to meet the requirements of single duct VAV zone applications, including: Cooling Only VAV Boxes Cooling with Reheat

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15119-3 Daikin Chiller Unit Controller Protocol Implementation Conformance Statement (PICS) ANSI/ASHRAE 135-2004, BACnet Model WME Magnetic Bearing Centrifugal Chiller

More information

Table of Contents RTU-MP

Table of Contents RTU-MP RTU-MP Third Party Integration Guide CARRIER CORPORATION 2008 A member of the United Technologies Corporation family. Stock symbol UTX, 48-50H-T-1SB, Rev. 7/23/2008 Table of Contents Safety Considerations...

More information

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers

Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers Engineering Data SED: 8012 Group: Centrifugal Chiller Date: March 2002 Supercedes: New Supplement to PM WSC/WDC-1 MicroTech II for Centrifugal Compressor Water Chillers Model WSC/WDC 2002 McQuay International

More information

Table of Contents. RTU Open Controller

Table of Contents. RTU Open Controller RTU Open Controller Integration Guide CARRIER CORPORATION 2010 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-428-01 11/19/2010 Table of Contents Introduction...

More information

BACnet Terminal Box (VAV) Controller

BACnet Terminal Box (VAV) Controller Technical Specification Sheet May 30, 2012 BACnet Terminal Box (VAV) Controller Figure 1. BACnet Terminal Box Controller. The BACnet Terminal Box Controller (Figure 1) provides high performance Direct

More information

Excel 10 W7752D,E,F,G AND W7754K,P,Q,R,S,T,V FAN COIL UNIT CONTROLLERS LNS PLUG-INS

Excel 10 W7752D,E,F,G AND W7754K,P,Q,R,S,T,V FAN COIL UNIT CONTROLLERS LNS PLUG-INS HONEYWELL EXCEL 5 OPEN SYSTEM Excel W775D,E,F,G AND W7754K,P,Q,R,S,T,V FAN COIL UNIT CONTROLLERS LNS PLUG-INS USER GUIDE CONTENTS Introduction... Description of Devices... Products Covered... Organization

More information

VTR8300 / VT8300 Series BACnet Integration Terminal Equipment Controller

VTR8300 / VT8300 Series BACnet Integration Terminal Equipment Controller BACnet Integration Terminal Equipment Controller Commercial and Lodging HVAC Applications BACnet CONTROLLER 2 BACnet Integration Manual VTR8300 and VT8300 series Protocol Implementation Conformance Statement

More information

Manual PCD7.L611 room controllers LON

Manual PCD7.L611 room controllers LON Manual PCD7.L611 room controllers LON Document 26/876; Edition EN03 2014-04-07 Content 0 Contents 0 Contents 0.1 Document History... 0-3 0.2 About this manual... 0-3 0.3 Brands and trademarks... 0-3 0

More information

TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS)

TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS) TB7300 Series Fan Coil Unit Communicating Thermostats BACnet Protocol Implementation Conformance Statement (PICS) Topic: BACnet Protocol Implementation Conformance Statement (PICS) Date: November 2006

More information

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS)

ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS) ASHRAE s BACnet Protocol Implementation Conformance Statement (PICS) Date: February 7, 2018 Vendor Name: Lutron Electronics Co., Inc. Product Name: myroom BACnet Integration Applications Version: 2.0 Firmware

More information