PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13)

Size: px
Start display at page:

Download "PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13)"

Transcription

1 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 1 Quick Start PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Introduction This document is designed to guide you through the basic steps needed to install, start-up, and program PowerFlex 700S AC drives with Phase II Control and frame sizes The information provided does not replace the user manual and is intended for qualified personnel only. For detailed PowerFlex 700S information refer to the appropriate publications: Title Publication Available User Manual - PowerFlex 700S Drive with Phase II Control 20D-UM006 Installation Instructions - PowerFlex 700S and PFLEX-IN H High Power Drives Reference Manual - PowerFlex 700S Drive PFLEX-RM003 with Phase II Control Wiring and Grounding Guidelines for Pulse DRIVES-IN001 Width Modulated Drives

2 2 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13)

3 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 3 Table of Contents Step 1: Read General Information Class 1 LED Product General Precautions CE Conformity Essential Requirements for CE Compliance Step 2: Identifying the Frame Size of the Drive Step 3: Lifting the Drive Frame 9 Size Drives Frame Size Drives Step 4: Mounting the Drive Operating Temperatures Minimum Mounting Clearances and Dimensions Floor and Wall Mounting for Frame Size Drives Step 5: Removing Protective Covers Removing the Covers from Frame 9 Size Drives Removing the Covers from Frame Size Drives Step 6: Configuring Drive for Ground System Frame 9 Size Drives Frame Size Drives Step 7: Power Wiring Wire Recommendations General Grounding Requirements DC Input Precharge Wiring Power Wiring Instructions Step 8: Control Wiring Wiring Recommendations DIP Switch Settings Auxiliary Power Supply I/O Terminal Blocks I/O Wiring Examples Step 9: Verifying the Start-up Check List Before Applying Power to the Drive Applying Power to the Drive Step 10: Performing Assisted Start Step 11: Running Drive from HIM (Optional) Additional Information Parameter Files & Groups Frequently Used Parameters Fault & Alarm Clearing HIM Indication Manually Clearing Faults ATEX Approved PowerFlex 700S Phase II Drives in Group II Category (2) Applications with ATEX Approved Motors Technical Support Drive Options

4 4 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13)

5 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 5 Step 1: Read General Information Class 1 LED Product! ATTENTION: Hazard of permanent eye damage exists when using optical transmission equipment. This product emits intense light and invisible radiation. Do not look into module ports or fiber optic cable connectors. General Precautions!!!!!!!! ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference Allen-Bradley publication , Guarding Against Electrostatic Damage or any other applicable ESD protection handbook. ATTENTION: An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or application errors such as under sizing the motor, incorrect or inadequate AC supply, or excessive surrounding air temperatures may result in malfunction of the system. ATTENTION: Only qualified personnel familiar with the PowerFlex 700S Drive and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage. ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged completely before servicing. Check the DC bus voltage at the Power Terminal Block by measuring between the +DC and -DC terminals, between the +DC terminal and the chassis, and between the -DC terminal and the chassis. The voltage must be zero for all three measurements. ATTENTION: Risk of injury or equipment damage exists. DPI or SCANport host products must not be directly connected together via 1202 cables. Unpredictable behavior can result if two or more devices are connected in this manner. ATTENTION: Risk of injury or equipment damage exists. Parameters 365 [Encdr0 Loss Cnfg] [VoltFdbkLossCnfg] let you determine the action of the drive in response to operating anomalies. Precautions should be taken to ensure that the settings of these parameters do not create hazards of injury or equipment damage ATTENTION: Risk of injury or equipment damage exists. Parameters 383 [SL CommLoss Data] [NetLoss DPI Cnfg] let you determine the action of the drive if communications are disrupted. You can set these parameters so the drive continues to run. Precautions should be taken to ensure the settings of these parameters do not create hazards of injury or equipment damage. ATTENTION: The sheet metal cover and mounting screws on the ASIC Board located on the power structure are energized at (-) DC bus potential high voltage. Risk of electrical shock, injury, or death exists if someone comes in contact with the assembly.

6 6 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) CE Conformity Conformity with the Low Voltage (LV) Directive and Electromagnetic Compatibility (EMC) Directive has been demonstrated using harmonized European Norm (EN) standards published in the Official Journal of the European Communities. PowerFlex Drives comply with the EN standards listed below when installed according to the PowerFlex 700S AC Drives with Phase II Control User Manual, publication 20D-UM006 and the PowerFlex 700S AC Drives with Phase II Control Reference Manual, publication PFLEX-RM003. CE Declarations of Conformity are available online at: Low Voltage Directive (73/23/EEC) EN50178 Electronic equipment for use in power installations. EMC Directive (89/336/EEC) EN Adjustable speed electrical power drive systems Part 3: EMC product standard including specific test methods. General Notes The motor cable should be kept as short as possible in order to avoid electromagnetic emission as well as capacitive currents. Use of line filters in ungrounded systems is not recommended. PowerFlex drives may cause radio frequency interference if used in a residential or domestic environment. The user is required to take measures to prevent interference, in addition to the essential requirements for CE compliance listed below, if necessary. Conformity of the drive with CE EMC requirements does not guarantee an entire machine or installation complies with CE EMC requirements. Many factors can influence total machine/installation compliance. PowerFlex drives can generate conducted low frequency disturbances (harmonic emissions) on the AC supply system. More information regarding harmonic emissions can be found in the PowerFlex Reference Manual. Essential Requirements for CE Compliance Conditions 1-6 listed below must be satisfied for PowerFlex drives to meet the requirements of EN

7 Cat No. 20D J 300 N 0 NNNBNNNN UL Open Type/IP00 540V 650V Normal Duty Power 160 kw Heavy Duty Power 132 kw Input: DC, DC Voltage Range kw 200 kw Amps Output: 3 Phase, 0-320Hz AC Voltage Range Base Hz (default) 50 Hz 60 Hz Continuous Amps 300/ / /368 1 Min Overload Amps 330/368 2 Sec Overload Amps 450/ /490 MFD. in 1989 on Nov 9 Frame #: 9 Serial Number: MADE IN THE USA (FAC 1B) Series: A Standard I/O: NONE Original Firmware No C U Æ L US LISTED IND CONT EQ 9D PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 7 1. Standard PowerFlex High Power CE compatible Drive. For Frame 10, the drive must also be installed in a suitable Rittal TS 8 (or equivalent) enclosure. 2. Review important precautions/attention statements throughout this manual before installing the drive. 3. Grounding as described on page Output power, control (I/O) and signal wiring must be braided, shielded cable with a coverage of 75% or better, metal conduit or equivalent attenuation. 5. All shielded cables should terminate with the proper shielded connector. 6. Conditions in Table A. Table A PowerFlex High Power EN EMC Compatibility Second Environment Restrict Motor Cable to 30 m (98 ft.) Any Drive and Option Frame Step 2: Identifying the Frame Size of the Drive Determine the frame size of your drive by checking the data nameplate on the Control Frame. The frame number is printed just above the serial number. L1 L2 L3 L1 L2 L3 U/T1 V/T2 W/T3 U/T1 V/T2 W/T3 X50 Cat No. 20D J 300 N 0 NNNBNNNN UL Open Type/IP00 540V 650V Series: A Normal Duty Power 160 kw 250 kw Standard I/O: NONE Original Firmware No Heavy Duty Power Input: DC, 132 kw 200 kw C U Æ L US IND CONT EQ DC Voltage Range Amps LISTED Output: 3 Phase, 0-320Hz 9D42 AC Voltage Range Base Hz (default) 50 Hz 60 Hz Continuous Amps 300/ /245 1 Min Overload Amps 330/ /368 2 Sec Overload Amps 450/ /490 MFD. in 2006 on Nov 9 Frame #: 9 Serial Number: MADE IN THE USA (FAC 1B) Frame Number

8 8 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Step 3: Lifting the Drive For lifting instructions for frame 9 size drives, see Frame 9 Size Drives below. For lifting instructions for frame size drives, see "Frame Size Drives" on page 9. Frame 9 Size Drives Important: When lifting a frame 9 size drive, a rod must be placed between the lifting holes as shown in Table B.! ATTENTION: To guard against possible personal injury and/or equipment damage... Remove any wiring access covers at the top of the drive. Do Not allow any part of the drive or lifting mechanism to make contact with electrically charged conductors or components. At no time should a person or their limbs be directly underneath the items being lifted. Do not subject the load to high rates of acceleration or deceleration. Inspect all lifting hardware for proper attachment before lifting drive unit. Table B Frame 9 - Approximate Drive and Enclosure Weights Voltage Class 400/480V AC (540/650V DC) 400/480V AC (540/650V DC) 600/690V AC (810/932V DC) 600/690V AC (810/932V DC) AC Input Drive Drive Rating & Enclosure AC Input Drive & Packaging DC Input Drive & Enclosure DC Input Drive & Packaging Amps Weight kg (lbs.) Weight kg (lbs.) Weight kg (lbs.) Weight kg (lbs.) (315) 143 (315) 109 (240) 109 (240) (333) 151 (333) 117 (258) 117 (258) (315) 143 (315) 109 (240) 109 (240) (315) 143 (315) 109 (240) 109 (240)

9 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 9 Frame Size Drives When lifting frame size drives you must: attach the lifting hardware. remove the skid and shipping feet.! ATTENTION: To guard against possible personal injury and/or equipment damage... Do Not allow any part of the drive or lifting mechanism to make contact with electrically charged conductors or components. At no time should a person or their limbs be directly underneath the items being lifted. Do not subject the load to high rates of acceleration or deceleration. Inspect all lifting hardware for proper attachment before lifting drive unit. Table C Frame Approximate Drive and Enclosure Weights Frame Size Voltage Class /480V AC (540/650V DC) 600/690V AC (810/932V DC) /480V AC (540/650V DC) 600/690V AC (810/932V DC) /480V AC (540/650V DC) 600/690V AC (810/932V DC) /480V AC (540/650V DC) 600/690V AC (810/932V DC) Drive Rating Amps AC Input Drive & Enclosure Weight kg (lbs.) AC Input Drive & Packaging Weight kg (lbs.) DC Input Drive & Enclosure Weight kg (lbs.) DC Input Drive & Packaging Weight kg (lbs.) (842) 432 (952) 267 (589) 317 (699) (842) 432 (952) 267 (589) 317 (699) (842) 432 (952) 267 (589) 317 (699) (705) 370 (816) 267 (589) 317 (699) (774) 401 (884) 267 (589) 317 (699) (774) 401 (884) 267 (589) 317 (699) (774) 401 (884) 267 (589) 317 (699) (1243) 614 (1354) 396 (873) 446 (983) (1243) 614 (1354) 396 (873) 446 (983) (1243) 614 (1354) 396 (873) 446 (983) (1127) 561 (1237) 396 (873) 446 (983) (1127) 561 (1237) 396 (873) 446 (983) (1380) 676 (1490) 396 (873) 446 (983) (1795) 864 (1905) 584 (1287) 634 (1398) (1795) 864 (1905) 584 (1287) 634 (1398) (1795) 864 (1905) 584 (1287) 634 (1398) (1658) 802 (1768) 584 (1287) 634 (1398) (1658) 802 (1768) 584 (1287) 634 (1398) (1658) 802 (1768) 584 (1287) 634 (1398) (2972) 1468 (3236) 600 (1323) 720 (1587) (3086) 1520 (3351) 600 (1323) 720 (1587) (3086) 1520 (3351) 600 (1323) 720 (1587) (2751) 1368 (3016) 600 (1323) 720 (1587) (2751) 1368 (3016) 600 (1323) 720 (1587) (2751) 1368 (3016) 600 (1323) 720 (1587)

10 10 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Attaching the Lifting Hardware to Frames Size Drives A B C A B > A Min. 60 TIP: To ensure that this angle is greater than 60, make the length of chain or cable between the center and the corners (B) longer than the distance between the opposite corners (A). Table D Frame Open Type Drives - Approximate Weights Drive Voltage Class Drive Rating Amps AC Input Drive & Packaging Weight kg Power Structure (1) AC Choke (2) Frame Size Weight kg (lbs.) Weight kg (lbs.) (lbs.) (4) Frame (265) 115 (254) 235 (519) (265) 115 (254) 235 (519) (265) 115 (254) 235 (519) (265) 53 (117) 173 (382) (265) 84 (185) 204 (450) (265) 84 (185) 204 (450) (265) 84 (185) 204 (450) Frame (463) 84 (185) (3) 378 (833) (463) 84 (185) (3) 378 (833) (463) 84 (185) (3) 378 (833) (463) 115 (254) 325 (717) (463) 115 (254) 325 (717) (463) 115 (254) (3) 440 (970) Frame (265) 115 (254) 350 (772) (265) 115 (254) 350 (772) (265) 115 (254) 350 (772) (265) 84 (185) 288 (635) (265) 84 (185) 288 (635) (265) 84 (185) 288 (635) (1) Two power structures are required per Frame 12 Drive (2) Two reactors are required per Frame 12 AC Drive (3) Two reactors are required per Frame 11 AC Drive (4) DC input drive and packaging weight is equal to the weight of the power structure

11 ! DANGER Risk of electric shock and death. Disconnect power, wait 5 minutes and verify DC bus voltage before servicing. Follow instructions in manual before use. Earth ground required. PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 11 Drive Voltage Drive Rating Weight kg (lbs.) Weight kg (lbs.) Weight kg (lbs.) Frame Size Class Amps AC Choke Power Structure NFE Module Frame (287) (1) 306 (675) 67 (148) (1) (254) (2) 306 (675) 67 (148) (2) (254) (2) 306 (675) 67 (148) (2) (287) (1) 306 (675) 67 (148) (1) (287) (1) 306 (675) 67 (148) (1) (287) (1) 306 (675) 67 (148) (1) (1) Two reactors and NFE Modules are required per Frame 13 AC Drive (2) Three reactors and NFE Nodules are required per Frame 13 AC Drive Directions for Open Type Drives A B! DANGER Risk of electric shock and death. Disconnect power, wait 5 minutes and verify DC bus voltage before servicing. Follow instructions in manual before use. Earth ground required. Frame 11 Shown C D Fasten the module symmetrically in at least two (2) holes (Frame 11 shown).

12 12 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Removing the Skid and Shipping Feet! ATTENTION: To guard against personal injury and equipment damage, do not work under the drive unless the drive is securely mounted on appropriate blocks. Task A AB AC ACD Description Using a 15 mm wrench, remove the hardware which secures the drive to the skid. Lift the drive off the skid. Place the drive on proper blocks on a hard, level surface. The blocks should be approximately 10 cm (4 inches) high. Using a 17 mm wrench, remove the hardware which secures the feet to the drive and remove the feet. B A A C D C A D D

13 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 13 Step 4: Mounting the Drive Operating Temperatures Frame Size N/A = Not Available at time of printing Surrounding Air Temperature Required Airflow m 3 /h (cfm) Voltage Class Amp Rating Normal Duty Heavy Duty (765) , to 40 degrees C 0 to 40 degrees C (32 to 104 degrees F) (32 to 104 degrees F) to 40 degrees C 0 to 40 degrees C (32 to 104 degrees F) (32 to 104 degrees F) to 35 degrees C (32 to 95 degrees F) 0 to 40 degrees C (32 to 104 degrees F) (1530) , 460, 0 to 40 degrees C 0 to 40 degrees C 500 (32 to 104 degrees F) (32 to 104 degrees F) , 325, 0 to 40 degrees C 0 to 40 degrees C 385 (32 to 104 degrees F) (32 to 104 degrees F) to 35 degrees C (32 to 95 degrees F) 0 to 40 degrees C (32 to 104 degrees F) (2295) , 650, 0 to 40 degrees C 0 to 40 degrees C 730 (32 to 104 degrees F) (32 to 104 degrees F) , to 40 degrees C 0 to 40 degrees C (32 to 104 degrees F) (32 to 104 degrees F) to 35 degrees C (32 to 95 degrees F) 0 to 35 degrees C (32 to 95 degrees F) (3060) , to 40 degrees C 0 to 40 degrees C (32 to 104 degrees F) (32 to 104 degrees F) to 40 degrees C 0 to 35 degrees C (32 to 104 degrees F) (32 to 95 degrees F) , to 40 degrees C 0 to 40 degrees C (32 to 104 degrees F) (32 to 104 degrees F) to 35 degrees C (32 to 95 degrees F) 0 to 35 degrees C (32 to 95 degrees F) (2472) Inverter Unit , 1300, 0 to 40 degrees C 0 to 40 degrees C 1450 (32 to 104 degrees F) (32 to 104 degrees F) , to 40 degrees C 0 to 40 degrees C (32 to 104 degrees F) (32 to 104 degrees F) 1150 (677) each Converter Unit , 1300, 0 to 40 degrees C 0 to 40 degrees C 1450 (32 to 104 degrees F) (32 to 104 degrees F) to 35 degrees C (32 to 95 degrees F) 0 to 35 degrees C (32 to 95 degrees F) For minimum mounting clearances for frame 9 size drives, see Frame 9 Size Drives Mounting Clearances below. For minimum mounting clearances for frame 10 size drives, see page 15. For minimum mounting clearances for frame 11 size drives, see page 17. For minimum mounting clearances for frame 12 size drives, see page 19. For minimum mounting clearances for frame 13 size drives, see page 21. Also: For floor and wall mounting of frame size drives, see page 23.

14 14 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Minimum Mounting Clearances and Dimensions Frame 9 Size Drives Mounting Clearances mm (15.75 in.) mm (15.75 in.) 50.0 mm (1.97 in.) 80.0 mm (3.2 in.) 50.0 mm (1.97 in.) mm (13.8 in.) mm (13.8 in.) Frame 9 size Drive Dimensions 5.0 (0.20) 14.0 (0.55) (18.90) (15.75) (9.45) 9.0 (0.35) (14.32) (13.37) 45.0 (1.77) Nameplate Wire Way (45.28) (44.09) Nameplate 9.0 (0.35) Lifting Hole 21.0 (0.83) 62.5 (2.46) (14.67) (11.52) (5.61) 59.0 (2.32) (7.54) (3.94) (9.67) (11.22) Detail A Brake Option Top Hat Dimensions are in millimeters and (inches).

15 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 15 Frame 10 Size Drives Mounting Clearances 200 mm (7.87 in.) 800 mm (31.50 in.) 50 mm (2.0 in.) CLEARANCE TO WALL 50 mm (2.0 in.) CLEARANCE TO WALL

16 16 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Frame 10 Size Drive Dimensions (NEMA/UL Type 1, IP21 Enclosure Code A ) (23.50) (21.05) 32.3 (1.27) 632.5* (24.90) (23.84) (19.61) 42.0 (1.65) (89.57) (87.95) (86.68) * This dimension is the depth for drives with the optional door-mounted HIM installed Dimensions are in millimeters and (inches).

17 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 17 Frame 11 Size Drives Mounting Clearances 200 mm (7.87 in.) 800 mm (39.3 in.) 50 mm (2.0 in.) CLEARANCE TO WALL 50 mm (2.0 in.) CLEARANCE TO WALL

18 ! DANGER 18 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Frame 11 Size Drive Dimensions (NEMA/UL Type 1 - IP21 Enclosure Code A ) (31.38) (28.98) (1.27) * (24.48) (23.84) (19.61) 42.0 (1.65) (89.57) (87.95) (86.81) * This dimension is the depth for drives with the optional door-mounted HIM installed Dimensions are in millimeters and (inches).

19 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 19 Frame 12 Size Drives Mounting Clearances 200 mm (7.87 in.) 800 mm (31.50 in.) 50 mm (2.0 in.) CLEARANCE TO WALL 50 mm (2.0 in.) CLEARANCE TO WALL

20 20 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Frame 12 Size Drive Dimensions (NEMA/UL Type 1 - IP12 Enclosure A ) (21.05) (47.09) 32.3 (1.27) 632.5* (24.90) (23.84) (19.61) 42.0 (1.65) (89.57) (87.95) (86.68) * This dimension is the depth for drives with the optional door-mounted HIM installed Dimensions are in millimeters and (inches).

21 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 21 Frame 13 Size Drive Mounting Clearances 200 mm (7.87) 800 mm (31.50 in.) 50 mm (2.0 in.) CLEARANCE TO WALL 50 mm (2.0 in.) CLEARANCE TO WALL 1800 mm Cabinet Shown.

22 22 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Frame 13 Size Drives - Dimensions Voltage Class Amps A B C D E F 400V (56) 1329 (52) 1264 (50) 535 (21) 735 (29) 1264 (50) (63) 1529 (60) 1464 (58) 735 (29) 735 (29) 1464 (58) 600V (56) 1329 (52) 1264 (50) 535 (21) 735 (29) 1264 (50) Dimensions are in mm and (in.) A B C (24.4) 603 (23.7) 44 (1.73) 2275 (89.6) 2197 (86.5) 2231 (87.8) (43.6) D 65 (2.6) E 535 (21.1) F Dimensions are in millimeters and (inches).

23 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 23 Floor and Wall Mounting for Frame Size Drives Floor Only Mounting Secure drive to the floor with anchor bolts in the front corner holes of the enclosure base plate. Additionally secure the drive using the mounting plates as needed (Rittal part no or equivalent). Do this as close to the choke assembly plate as possible. With this method the holes through base plate must be drilled on-site. Important: If it is important to align the drive cabinet vertically with adjacent Rittal cabinets, you may need to place shims under the drive cabinet or use leveling feet throughout the cabinet line-up. The Allen-Bradley factory may have removed the standard plastic plugs from the bottom of the cabinet when installing the shipping feet. This reduces the height of the cabinet by 2 mm. Wall Mounting Secure drive to the floor with anchor bolts in the front corner holes of the enclosure base plate. Secure the drive by bolting the adjustable lifting rails to the rear wall or supporting structure. wall

24 24 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Enclosed Frame 13 Drives with DC Input Enclosed Frame 13 Drives with DC Input are shipped with the control pan mounted in the motor connection area of the right-hand cabinet. The control pan must be moved from this location to another cabinet, away from the power connections. Step 5: Removing Protective Covers For removing the protective covers from frame 9 size drives, see Removing the Covers from Frame 9 Size Drives below. For removing the protective covers from frame size drives, see page 25. Removing the Covers from Frame 9 Size Drives A Removing the Connection Cover L1 L2 L3 L1 L2 L3 U/T1 V/T2 W/T3 U/T1 V/T2 W/T3 (8 Screws) B (8 Screws) Removing the Power Cover L1 L2 L3 L1 L2 L3 U/T1 V/T2 W/T3 U/T1 V/T2 W/T3 X50 (3 Screws) L1 L2 L3 L1 L2 L3 U/T1 V/T2 W/T3 U/T1 V/T2 W/T3 C Removing the Conduit Cover When you have completed removing the covers, continue with Step 6: Configuring Drive for Ground System on page -27.

25 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 25 Removing the Covers from Frame Size Drives To remove the protective covers from frame size drives, you must first move the Protective Screens (frame 13 only), Control Frame (frames only) and the Airflow Plate. Removing Protective Screens (Frame 13 Only) Task A Description For NEMA/UL Type 1 enclosures, remove the screws that secure the protective screens to the right-hand enclosure only and remove the screens. A Moving Control Frame (Frames Only) Task A B Description Loosen the two T8 Torx-head screws, which secure the Control Frame to the drive enclosure (Frame 10 drives, from early production runs, have holes instead of slots for these screws. You must completely remove the screws from these drives in order to swing-open the control frame.). Swing the Control Frame out and away from the power structure. A or A B Frame 10 Drive Shown

26 ! 26 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Removing the Airflow Plate(s) Removing the Covers from Frame Size Drives, Continued Task C D Description Remove the four T8 Torx-head screws which secure the airflow plate to the drive. Slide airflow plate off of the drive. C D C D C C Frame 10 Drive Shown Removing Protective Covers (Frames 10-12) Task E F G Description Remove the four M5 Pozi-drive screws which secure the top and bottom protective covers to the main front protective cover, then remove the top and bottom protective covers. Note: You only need to remove the top and bottom covers to gain access to the power terminals. You can remove the other covers without removing the top and bottom covers. Remove the four M5 Pozi-drive screws which secure the main front protective cover to the drive, then remove the protective cover. Remove side protective covers (Not necessary for frame 11 and 12 size drives). E F E E E Frame 10 Drive Shown G G Removing Protective Covers (Frame 13 Only) Task E Description Remove the four M5 Pozi-drive screws which secure each of the three main and bottom protective covers to the drive, then remove the main and bottom protective covers. Note: You only need to remove the bottom cover to gain access to the power terminals. E DC BUS CONDUCTORS AND CAPACITORS OPERATE AT HIGH VOLTAGE. REMOVE POWER AND WAIT 5 MINUTES BEFORE SERVICING DANGER

27 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 27 Step 6: Configuring Drive for Ground System For configuring frame 9 size drives for a ground system, see Frame 9 Size Drives below. For configuring frame size drives for a ground system, see "Frame Size Drives" on page 28. Frame 9 Size Drives CE frame 9 size drives are equipped with common mode capacitors that are referenced to ground. Operating a CE frame 9 drive on a resistive ground or ungrounded distribution system could result in drive damage.! ATTENTION: If you intend to operate a Frame 9 drive on a resistive ground or ungrounded distribution system, you must order a non-ce PowerFlex High Power drive. All frame 9 drives (CE and non-ce) are equipped with a Metal Oxide Varistor (MOV) assembly to provide voltage surge protection. The MOV is designed for transient surge suppression only (not continuous operation). With a resistive ground or ungrounded distribution system the phase-to-ground MOV connection could become a continuous current path. Therefore, you should disconnect the MOV ground connection when installing a frame 9 drive on a resistive ground or ungrounded distribution system. Refer to publication PFLEX-RM003, PowerFlex 700S with Phase II Control Reference Manual, for information on resistive ground or ungrounded system installations. L1 L2 L3 Disconnect and insulate this wire on resistive ground or ungrounded distribution systems Ground stud on Cross Plate! ATTENTION: Risk of equipment damage exists if this wire contacts other circuits in the drive while the drive is energized. Insulate the lug on this wire with several turns of electrical tape and anchor the wire so it does not contact other circuits. Continue with Step 7: Power Wiring on page -34.

28 28 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Frame Size Drives Frame size drives are equipped with common mode capacitors that are referenced to ground. To guard against drive damage, these capacitors should be disconnected if the drive is installed on a resistive ground or ungrounded distribution system or on a grounded B phase Delta system. For installations on a resistive ground or ungrounded distribution system, refer to "Installation on a Resistive Ground or Ungrounded Distribution System" on page 29. For installations on a grounded B phase Delta system on a voltage distribution system, refer to "Installation on a Grounded B Phase Delta System" on page 31. Note: Refer to publication PFLEX-RM003, PowerFlex 700S with Phase II Control Reference Manual, for information on a resistive ground or ungrounded distribution system installation. Important: There is one jumper on each Rectifying Module. For drives with multiple Rectifying Modules, all jumpers must be in the same position. Frame Size Number of Rectifying Modules (Number of Jumpers) Location of Rectifying Module(s) 10 1 Upper-right side of the drive s power structure Upper-right side of the center and right hand power stacks of the drive s power structure Upper-right side of the right hand power stacks in each cabinet of the drive s power structure. Note: The jumpers on both Rectifying Modules must be in the same position V class drives and 400V, 1150A drives 3-400V, 1300A and 1450A drives Upper-right side of the power stacks in the left hand cabinet of the drive s power structure. Note: The jumpers on all of the Rectifying Modules must be in the same position.

29 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 29 Installation on a Resistive Ground or Ungrounded Distribution System The jumper on frame size drives is different than the jumper on frame 13 size drives. Refer to Frame Size Drives below or to "Frame 13 Size Drives:" on page 30 for the appropriate procedure for your drive frame size. Frame Size Drives: 1. To disconnect the capacitors, move the jumper as shown below. Task A B C D Description Loosen the upper screw. Remove the lower screw. Move the jumper to the horizontal position. Install and tighten all screws. Continue with step 2 on page 33. A D C B Rectifying Circuit Board

30 30 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Installation on a Resistive Ground or Ungrounded Distribution System, Continued Frame 13 Size Drives: To disconnect the capacitors, move the jumper as shown below. Task A B C Description Loosen the three screws. Rotate the jumper to the lower position. Tighten the three screws. Continue with Step 7: Power Wiring on page 34. Rectifying Circuit Board B A C

31 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 31 Installation on a Grounded B Phase Delta System The jumper on frame size drives is different than the jumper on frame 13 size drives. Refer to Frame Size Drives below or to "Frame 13 Size Drives:" on page 32 for the appropriate procedure for your drive frame size. Frame Size Drives: 1. To use a grounded B phase delta system, follow the steps below. Task A B C D E F Description Loosen the upper screw on the common mode capacitor jumper. Remove the lower screw. Move the jumper to the horizontal position. Install and tighten all screws. Remove the screw from the X4 connection on the Rectifying circuit board. Insulate the top and bottom of the X4 connection on the Rectifying circuit board. Continue with step 2 on page 33. A D C B Rectifying Circuit Board E F X4 X1 X4 X1 X41 X41 Rectifying Circuit Board

32 32 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Installation on a Grounded B Phase Delta System, Continued Frame 13 Size Drives: Task A B C D E Description Loosen the three screws. Rotate the jumper to the lower position. Tighten the three screws. Remove the screw from the X4 connection on the Rectifying circuit board. Insulate the top and bottom of the X4 connection on the Rectifying circuit board. Continue with Step 7: Power Wiring on page 34. Rectifying Circuit Board B C A Rectifying Circuit Board X41 X41 X1 X4 X1 X4 D Jumper E

33 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Insulate the capacitors from the drive s input power terminals. Task A B C Description Remove the screws and lock washers that secure each of the three capacitor supply wires to the input power terminals. Insulate the capacitor leads. Install and tighten the screws and lock washers only. Important: It is not necessary to remove the power wiring from the terminals in order to insulate the capacitor leads. L1 L2 L3 Input power terminal Insulator B A Capacitor Capacitor lead C Continue with Step 7: Power Wiring on page 34.

34 34 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Step 7: Power Wiring Wire Recommendations! ATTENTION: National Codes and standards (NEC, VDE, BSI etc.) and local codes outline provisions for safely installing electrical equipment. Installation must comply with specifications regarding wire types, conductor sizes, branch circuit protection and disconnect devices. Failure to do so may result in personal injury and/or equipment damage. Cable Types Acceptable for Volt Installations A variety of cable types are acceptable for drive installations. For many installations, unshielded cable is adequate, provided it can be separated from sensitive circuits. As an approximate guide, allow a spacing of 0.3 meters (1 foot) for every 10 meters (32.8 feet) of length. In all cases, long parallel runs must be avoided. Do not use cable with an insulation thickness less than or equal to 15 mils (0.4mm/0.015 in.). Use Copper wire only. Wire gauge requirements and recommendations are based on 75 degrees C. Do not reduce wire gauge when using higher temperature wire. Important: For detailed information on motor cable length restrictions, refer to Appendix A, Motor Cable Length Restrictions Tables in Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001. Unshielded Cable THHN, THWN or similar wire is acceptable for drive installation in dry environments provided adequate free air space and/or conduit fill rates limits are provided. Do not use THHN or similarly coated wire in wet areas. Any wire chosen must have a minimum insulation thickness of 15 Mils and should not have large variations in insulation concentricity. Shielded Cable Shielded cable contains all of the general benefits of multi-conductor cable with the added benefit of a copper braided shield that can contain much of the noise generated by a typical AC Drive. Strong consideration for shielded cable should be given in installations with sensitive equipment such as weigh scales, capacitive proximity switches and other devices that may be affected by electrical noise in the distribution system. Applications with large numbers of drives in a similar location, imposed EMC regulations or a high degree of communications/ networking are also good candidates for shielded cable. Shielded cable may also help reduce shaft voltage and induced bearing currents for some applications. In addition, the increased impedance of shielded cable may help extend the distance that the motor can be located from the drive without the addition of motor protective devices such as terminator networks. Refer to Chapter 5, Reflected Wave in Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001. Consideration should be given to all of the general specifications dictated by the environment of the installation, including temperature, flexibility, moisture

35 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 35 characteristics and chemical resistance. In addition, a braided shield should be included and be specified by the cable manufacturer as having coverage of at least 75%. An additional foil shield can greatly improve noise containment. A good example of recommended cable is Belden 295xx (xx determines gauge). This cable has four (4) XLPE insulated conductors with a 100% coverage foil and an 85% coverage copper braided shield (with drain wire) surrounded by a PVC jacket. Other types of shielded cable are available, but the selection of these types may limit the allowable cable length. Particularly, some of the newer cables twist 4 conductors of THHN wire and wrap them tightly with a foil shield. This construction can greatly increase the cable charging current required and reduce the overall drive performance. Unless specified in the individual distance tables as tested with the drive, these cables are not recommended and their performance against the lead length limits supplied is not known. Armored Cable Cable with continuous aluminum armor is often recommended in drive system applications or specific industries. It offers most of the advantages of standard shielded cable and also combines considerable mechanical strength and resistance to moisture. It can be installed in concealed and exposed manners and removes the requirement for conduit (EMT) in the installation. It can also be directly buried or embedded in concrete. Because noise containment can be affected by incidental grounding of the armor to building steel (see Chapter 2. Wire Types, of publication DRIVES-IN001, Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives) when the cable is mounted, it is recommended the armored cable have an overall PVC jacket. Interlocked armor is acceptable for shorter cable runs, but continuous welded armor is preferred. Best performance is achieved with 3 spaced ground conductors, but acceptable performance below 200 HP is provided via a single ground conductor. See Table E. Table E Recommended Shielded / Armored Cable Location Rating/Type Description Standard (Option 1) Standard (Option 2) 600V, 90 C (194 F) Four tinned copper conductors with XLPE insulation. XHHW2/RHW-2 Copper braid/aluminum foil combination shield and tinned Anixter B B209507, Belden copper drain wire , or equivalent PVC jacket. Tray rated 600V, 90 C (194 F) RHH/RHW-2 Anixter OLF-7xxxxx or equivalent Class I & II; Tray rated 600V, 90 C (194 F) Division I & II RHH/RHW-2 Anixter 7V-7xxxx-3G or equivalent Three tinned copper conductors with XLPE insulation. 5 mil single helical copper tape (25% overlap min.) with three bare copper grounds in contact with shield. PVC jacket. Three bare copper conductors with XLPE insulation and impervious corrugated continuously welded aluminum armor. Black sunlight resistant PVC jacket overall. Three copper grounds on #10 AWG and smaller.

36 36 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) General Grounding Requirements The drive Safety Ground - PE must be connected to system ground. Ground impedance must conform to the requirements of national and local industrial safety regulations and/or electrical codes. The integrity of all ground connections should be periodically checked. For installations within a cabinet, a single safety ground point or ground bus bar connected directly to building steel should be used. All circuits including the AC input ground conductor should be grounded independently and directly to this point/ bar. Figure 1 Typical Grounding R (L1) S (L2) T (L3) U (T1) V (T2) W (T3) PE SHLD Safety Ground - PE This is the safety ground for the drive that is required by code. This point must be connected to adjacent building steel (girder, joist), a floor ground rod or bus bar (see above). Grounding points must comply with national and local industrial safety regulations and/or electrical codes. Shield Termination - SHLD The Shield terminal provides a grounding point for the motor cable shield. It must be connected to an earth ground by a separate continuous lead. The motor cable shield should be connected to this terminal on the drive (drive end) and the motor frame (motor end). A shield terminating cable gland may also be used. When shielded cable is used for control and signal wiring, the shield should be grounded at the source end only, not at the drive end. RFI Filter Grounding Using an optional RFI filter may result in relatively high ground leakage currents. Therefore, the filter must only be used in installations with grounded AC supply systems and be permanently installed and solidly grounded (bonded) to the building power distribution ground. Ensure that the incoming supply neutral is solidly connected (bonded) to the same building power distribution ground. Grounding must not rely on flexible cables and should not include any form of plug or socket that would permit inadvertent disconnection. Some local codes may require redundant ground connections. The integrity of all connections should be periodically checked. Refer to the instructions supplied with the filter.

37 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 37 DC Input Precharge Wiring If you are installing a DC input drive with a precharge interlock you must make the following connections on the X50 terminal block from the precharge circuit. Important: Precharge circuitry is external to the drive. Figure 2 Sample Precharge Wiring Diagram (Frame 9 Shown) X X1 DC Bus Precharge Control CR1 CR1 Pilot Relay M Main DC Contactor M 5 6 X9 X6 M CR2 Precharge X10 X7 Table F X50 Terminal Block Connections Frame X50 Terminal Description 9 1 Charge Relay Contact 2 Charge Relay Contact 5 Precharge Complete Signal (+24V DC) 6 Precharge Complete Signal (Common) 10, 11, & 13 3 Charge Relay Contact 4 Charge Relay Contact 1 Precharge Complete Signal (+24V DC) 2 Precharge Complete Signal (Common) 12 Power Module 1 3 Charge Relay Contact (Jumper to Power Module 2 Terminal 23) 4 Charge Relay Contact 1 Precharge Complete Signal (+24V DC) 2 Precharge Complete Signal (Common) Power Module 2 3 Charge Relay Contact 4 Charge Relay Contact (Jumper to Power Module 1 Terminal 21) 1 Precharge Complete Signal (+24V DC) 2 Precharge Complete Signal (Common) Table G X50 Terminal Block Specifications Wire Size Range (1) Torque Maximum Minimum Recommended 6.0 mm 2 (10 AWG) 1.0 mm 2 (18 AWG) 0.8 N-m (7.0 lb.-in.) (1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

38 38 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Figure 3 Frame 9 X50 Terminal Block Location X50 Terminal Block X50 Figure 4 Frame X50 Terminal Block Location Control Frame X50 Terminal Block Note: 700S control mounting plate and HIM not shown for clarity only

39 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 39 Power Wiring Instructions For power wiring instructions for frame 9 size drives, see Frame 9 Size Drives below. For power wiring instructions for frame 10 size drives, see page 40. For power wiring instructions for frame 11 size drives, see page 41. For power wiring instructions for frame 12 size drives, see page 44. For power wiring instructions for frame 13 size drives, see page 47. Note: If you are installing an ATEX approved drive and motor, refer to "ATEX Approved PowerFlex 700S Phase II Drives in Group II Category (2) Applications with ATEX Approved Motors" on page 70 for more information on power wiring. Frame 9 Size Drives Wire Size Range (1) Torque No. Name Description Maximum Minimum Recommended ➊ Input Power Terminal Block (2) Input power mm mm 2 40 N-m L1, L2, L3 (350 MCM) (4/0 AWG) (354 lb.-in.) ➋ Output Power Terminal Block(2) Motor connections mm mm 2 40 N-m U/T1, V/T2, W/T3 (350 MCM) (4/0 AWG) (354 lb.-in.) ➌ SHLD Terminal, PE, Motor Ground Terminating point for wiring shields 95.0 mm 2 (4/0 AWG) 5.0 mm2 (10 AWG) 22 N-m (195 lb.-in.) ➍ DC Bus(3) (2 Terminals; DC, DC+) DC Bus w/brake (3) (3 Terminals; DC, DC+/R+, R ) DC input or external brake (Internal Brake option not ordered) DC input/internal brake (Internal Brake option is ordered) mm 2 (350 MCM) mm 2 (350 MCM) 95.0 mm 2 (4/0 AWG) 95.0 mm 2 (4/0 AWG) 40 N-m (354 lb.-in.) 40 N-m (354 lb.-in.) ➎ Cable Clamp for Shield (1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations. (2) Do Not exceed maximum wire size. Parallel connections may be required. (3) DC terminal and brake lugs can be removed. ➌ ➍ DC DC+/R+ R ➊ ➋ ➌ Power Terminal Block (2) ➎ L1 L2 L3 L1 L2 L3 U/T1 V/T2 W/T3 U/T1 V/T2 W/T3 AC Line Input Power To Motor Leads

40 40 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Frame 10 Size Drives Wire Size Range (1)(2) Torque Terminal Bolt No. Name Description Maximum Minimum Recommended Size (3) (4) ➊ Input Power Terminal Block Input power 300 mm mm 2 40 N-m M12 L1, L2, L3 (3) (600 MCM) (14 AWG) (354 lb.-in.) ➋ Output Power Terminal Block ((3) U/T1, V/T2, W/T3 Motor connections 300 mm 2 (600 MCM) 2.1 mm 2 (14 AWG) 40 N-m (354 lb.-in.) M12 ➌ SHLD Terminal, PE, Motor Terminating point for wiring shields 300 mm 2 Ground (3) (600 MCM) 2.1 mm 2 (14 AWG) 40 N-m (354 lb.-in.) M10 ➍ DC Bus (3) (2 Terminals; DC, DC+) DC Bus w/brake (3) (3 Terminals; DC, DC+/R+, R ) DC input or external brake (Internal Brake option not ordered) DC input/internal brake (Internal Brake option is ordered) 300 mm 2 (600 MCM) 300 mm 2 (600 MCM) 2.1 mm 2 (14 AWG) 2.1 mm 2 (14 AWG) 40 N-m (354 lb.-in.) 40 N-m (354 lb.-in.) M12 M12 ➎ Cable Clamp for Shield (1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations. (2) Do Not exceed maximum wire size. Parallel connections may be required. (3) These connections are bus bar type terminations and require the use of lug type connectors. (4) Apply counter torque to the nut on the other side of terminations when tightening or loosening the terminal bolt in order to avoid damage to the terminal. ➍ DC+/R+ DC- R- V/T2 ➋ U/T1 W/T3 ➊ L1 L2 L3 ➌ ➎

41 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) 41 Frame 11 Size Drives AC Input Wiring for Frame 11 Drives 600V class and 502 amp frame 11 drives contain only one rectifying module and therefore only one set of input power terminals. 400V class and 600V class amp frame 11 size drives utilize two parallel input rectifying modules, and therefore have two sets of input power terminals. You must supply power to both sets of input terminals. There are several methods for accomplishing this. Each of these methods is shown below. Important: Parallel wiring must have the same cable dimensions, type and routing. Non-symmetrical wiring may cause unequal loading between the converters and reduce the drive s ability to deliver current to the motor. Figure 5 Frame 11 AC Wiring Example: Two Fuses per Phase AC Input Power Wiring, Fuses, and L1 L2 L3 Disconnect Device Provided by Customer AC Input Power Terminals Inside Drive 1L1 1L2 1L3 2L1 2L2 2L3

42 42 PowerFlex 700S Drives - Phase II Control (Frame Sizes 9-13) Figure 6 Frame 11 AC Wiring Example: One Fuse per Phase L1 L2 L3 1L1 1L2 1L3 2L1 2L2 2L3 Figure 7 Frame 11 AC Wiring Example: Circuit Breaker L1 L2 L3 1L1 1L2 1L3 2L1 2L2 2L3 Table H Frame 11 Power Terminal Specifications Wire Size Range (1)(2) Torque Terminal Bolt No. Name Description Maximum Minimum Recommended (3) (4) Size ➊ Input Power Terminal Block AC Input power 300 mm mm 2 40 N-m M12 1L1, 1L2, 1L3, 2L1, 2L2, 2L3 (3) (600 MCM) (14 AWG) (354 lb.-in.) ➋ Output Power Terminal Block ((3) U/T1, V/T2, W/T3 Motor connections 300 mm 2 (600 MCM) 2.1 mm 2 (14 AWG) 40 N-m (354 lb.-in.) M12 ➌ SHLD Terminal, PE, Motor Terminating point for wiring shields 300 mm 2 Ground (3) (600 MCM) 2.1 mm 2 (14 AWG) 40 N-m (354 lb.-in.) M10 ➍ DC Bus (3) (2 Terminals; DC, DC+) DC input or external brake (Internal Brake option not ordered) 300 mm 2 (600 MCM) 2.1 mm 2 (14 AWG) 40 N-m (354 lb.-in.) M12 ➎ Cable Clamp for Shield (1) Maximum/minimum sizes that the terminal block will accept - these are not recommendations. (2) Do Not exceed maximum wire size. Parallel connections may be required.

PowerFlex 700S Drives - Phase I Control (Frame Sizes 9 & 10)

PowerFlex 700S Drives - Phase I Control (Frame Sizes 9 & 10) Quick Start PowerFlex 700S Drives - Phase I Control (Frame Sizes 9 & 10) Introduction This document is designed to guide you through the basic steps needed to install, start-up, and program PowerFlex 700S

More information

Application Guide. Considerations for 32 Bit Integer Parameters in 16 Bit Processors. PowerFlex 700VC, PowerFlex 700S. Introduction.

Application Guide. Considerations for 32 Bit Integer Parameters in 16 Bit Processors. PowerFlex 700VC, PowerFlex 700S. Introduction. Topic: Drive Product: Introduction User Information Considerations for 32 Bit Integer Parameters in 16 Bit Processors PowerFlex 700VC, PowerFlex 700S An Application Guide provides generic information on

More information

PowerFlex 700S Adjustable Frequency AC Drive - Phase I (Frames 1-6)

PowerFlex 700S Adjustable Frequency AC Drive - Phase I (Frames 1-6) Quick Start PowerFlex 700S Adjustable Frequency AC Drive - Phase I (Frames 1-6) Introduction Reference Materials This document is designed to guide you through the basic steps needed to install, start-up,

More information

PowerFlex 700S Adjustable Frequency AC Drive - Phase II (Frames 1-6)

PowerFlex 700S Adjustable Frequency AC Drive - Phase II (Frames 1-6) Quick Start PowerFlex 700S Adjustable Frequency AC Drive - Phase II (Frames 1-6) Introduction Reference Materials This document is designed to guide you through the basic steps needed to install, start-up,

More information

PowerFlex 700S and 700H Frame 13 Replacement Power Structures

PowerFlex 700S and 700H Frame 13 Replacement Power Structures Installation Instructions PowerFlex 700S and 700H Frame 13 Replacement Power Structures Introduction Use this document to install a replacement power structure on a PowerFlex 700S or 700H frame 13 drive.

More information

PowerFlex 700 Power Jumpers

PowerFlex 700 Power Jumpers PowerFlex 700 Power Jumpers Installation Instructions The PowerFlex 700 drive contains protective s and Common Mode Capacitors referenced to ground (see below). To guard against unstable operation and/or

More information

PowerFlex 700 Adjustable Frequency AC Drive

PowerFlex 700 Adjustable Frequency AC Drive Installation Instructions PowerFlex 700 Adjustable Frequency AC Drive Frames 7 10 160 500 kw (250 700 Hp) When reading this document, look for this symbol Step x to guide you through the 5 BASIC STEPS

More information

PowerFlex SCR Bus Supply Firmware Version 1.xxx

PowerFlex SCR Bus Supply Firmware Version 1.xxx PowerFlex SCR Bus Supply Firmware Version 1.xxx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety

More information

PowerFlex 400 Adjustable Frequency AC Drive for Fan & Pump Applications

PowerFlex 400 Adjustable Frequency AC Drive for Fan & Pump Applications User Manual Original Instructions PowerFlex 400 Adjustable Frequency AC Drive for Fan & Pump Applications Catalog Numbers 22C, Series B Important User Information Read this document and the documents listed

More information

Siemens Industrial s

Siemens Industrial s SINAMICS G130 Operating Instructions 05/2010 SINAMICS Siemens Industrial s Sinusoidal filter Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical

More information

PowerFlex 700S and 700H Frame 11 Replacement Power Structures

PowerFlex 700S and 700H Frame 11 Replacement Power Structures Installation Instructions PowerFlex 700S and 700H Frame 11 Replacement Power Structures Introduction Use this document to install a replacement power structure on a PowerFlex 700S or 700H frame 11 drive.

More information

PowerFlex 700S Drive

PowerFlex 700S Drive Quick Start PowerFlex 700S Drive Introduction This document is designed to guide you through the basic steps needed to install, start-up and program the PowerFlex 700S Drive. The information provided does

More information

Migration Guide. Bulletin 160 SSC Variable Speed Drives to PowerFlex 525 AC Drives

Migration Guide. Bulletin 160 SSC Variable Speed Drives to PowerFlex 525 AC Drives Migration Guide Bulletin 160 SSC Variable Speed Drives to PowerFlex 525 AC Drives Important User Information Read this document and the documents listed in the additional resources section about installation,

More information

MC 11 EB-2 Power supply cabinet with external bus, AC version

MC 11 EB-2 Power supply cabinet with external bus, AC version MC 11 EB-2 Power supply cabinet with external bus, AC version USER/MAINTENANCE MANUAL 1 SLOT 0 SLOT 1 SLOT 2 SLOT 3 SLOT 4 SLOT 5 SLOT 6 SLOT 7 SLOT 8 SLOT 9 SLOT 10 SLOT 11 EB-2 (a) MC11 (b) (c) Figures

More information

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.6 11/2013 A5E32845290B AA

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive FRN 1.xx - 2.xx User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Installation Job Aid for Ethernet Routing Switch 3600 Series

Installation Job Aid for Ethernet Routing Switch 3600 Series Installation Job Aid for Ethernet Routing Switch 3600 Series Notices NN47213-303 Issue 03.01 November 2017 Notice paragraphs alert you about issues that require your attention. Following are descriptions

More information

DriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual.

DriveGuard. Safe-Off Option for PowerFlex 70 AC Drives. User Manual. DriveGuard Safe-Off Option for PowerFlex 70 AC Drives User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Introduction to Proper Variable Frequency Drive Installation Practices. Copyright 2012 Rockwell Automation, Inc. All rights reserved.

Introduction to Proper Variable Frequency Drive Installation Practices. Copyright 2012 Rockwell Automation, Inc. All rights reserved. Introduction to Proper Variable Frequency Drive Installation Practices Copyright 2012 Rockwell Automation, Inc. All rights reserved. Field Installations Do These Look Familiar To You? Spacing above drive

More information

PowerFlex 700S Phase II Drives DriveLogix Option Card Battery Extension Cable

PowerFlex 700S Phase II Drives DriveLogix Option Card Battery Extension Cable Installation Instructions PowerFlex 700S Phase II Drives DriveLogix Option Card Battery Extension Cable!!!!! ATTENTION: To avoid an electric shock hazard, ensure that all power to the drive has been removed

More information

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2

dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Safety information 1 General 2 dv/dt filter compact plus Voltage Peak Limiter SINAMICS SINAMICS G120P dv/dt filter compact plus Voltage Peak Limiter Operating Instructions Safety information 1 General 2 Mechanical installation 3 Electrical

More information

USER MANUAL Series B, Vector Control Firmware & Up

USER MANUAL Series B, Vector Control Firmware & Up PowerFlex 7 AC Drives USER MANUAL Series B, Vector Control Firmware 4. & Up Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

Site Preparation CHAPTER

Site Preparation CHAPTER CHAPTER 3 Site Preparation This chapter describes the steps to take and the considerations you should keep in mind prior to installing the modules in an open rack. It also contains information that applies

More information

SINAMICS. SINAMICS G120P dv/dt filter plus Voltage Peak Limiter. Safety information 1. General. Mechanical installation. Electrical installation 4

SINAMICS. SINAMICS G120P dv/dt filter plus Voltage Peak Limiter. Safety information 1. General. Mechanical installation. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G120P dv/dt filter plus Voltage Peak Limiter Operating Instructions Mechanical installation 3 Electrical installation 4 Maintenance and servicing 5 Technical

More information

PowerFlex 750-Series Power Option Cabinets

PowerFlex 750-Series Power Option Cabinets Installation Instructions PowerFlex 750-Series Power Option Cabinets Topic Page Introduction 1 Additional Resources 2 What the Kits Contain 2 Bus-bar Selection Tables 4 Approximate Dimensions 8 Remove

More information

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation

Line reactors SINAMICS. SINAMICS G130 Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.7 04/2014 A5E00331462A Legal

More information

Temperature. Power requirements. Weight. Dimensions

Temperature. Power requirements. Weight. Dimensions Installing the Tracer Summit BMTX Building Control Unit Ordering numbers: BMTX001AAB000, BMTX001AAB010, BMTX001AAB001, BMTX001AAB011, BMTX001BAB000, BMTX001BAB010, BMTX001BAB001, BMTX001BAB011, BMTX001DAB000

More information

Adjustable Frequency AC Drive for Fan & Pump Applications

Adjustable Frequency AC Drive for Fan & Pump Applications Adjustable Frequency AC Drive for Fan & Pump Applications FRN 1.xx - 7.xx User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from

More information

PanelView Plus/VersaView CE Terminals and Display Modules

PanelView Plus/VersaView CE Terminals and Display Modules Installation Instructions PanelView Plus/VersaView CE Terminals and Display Modules (Catalog Numbers 2711P-xxxxxx, 6182H-xxxxxx) English Inside: Overview...2 For More Information...2 Modular Components...3

More information

T107 - Installation Considerations for AC drives

T107 - Installation Considerations for AC drives T107 - Installation Considerations for AC drives PUBLIC Field Installations Do These Look Familiar To You? High Power, signal wire, unshielded Ethernet cable and 24VDC were mixed together throughout this

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety

More information

PowerLogic High Density Metering System 1-Meter Enclosure

PowerLogic High Density Metering System 1-Meter Enclosure PowerLogic High Density Metering System 1-Meter Enclosure Installation Guide 63230-508-211A1 Safety information PowerLogic High Density Metering System 1-Meter Enclosure Important information Read these

More information

Installation Requirements for Conformance to Standards

Installation Requirements for Conformance to Standards User Manual for Industrial Control Products Installation Requirements for Conformance to Standards Fourth Edition 26 September 2000 MAN0005-04 MAN0005-04 26 SEP 2000 PAGE 3 PREFACE This manual explains

More information

Installation Job Aid for Ethernet Routing Switch 5900 Series

Installation Job Aid for Ethernet Routing Switch 5900 Series Installation Job Aid for Ethernet Routing Switch 5900 Series Notices NN47211-301 Issue 05.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs

More information

MICHIGAN DEPARTMENT OF TRANSPORTATION

MICHIGAN DEPARTMENT OF TRANSPORTATION MICHIGAN DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION FOR GROUNDING, BONDING, LIGHTNING PROTECTION AND SURGE PROTECTION FOR INTELLIGENT TRANSPORTATION SYSTEM EQUIPMENT ITS:CLC 1 of 5 APPR:LWB:DBP:07-31-13

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive FRN 4.xx User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

Recommended Practices for Installation For EC Directive 2004/108/EC Relating to EMC Supplement to Installation and Operating Manual

Recommended Practices for Installation For EC Directive 2004/108/EC Relating to EMC Supplement to Installation and Operating Manual Recommended Practices for Installation For EC Directive 2004/108/EC Relating to EMC Supplement to Installation and Operating Manual 6/09 MN1383 Any trademarks used in this manual are the property of their

More information

PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board

PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board Service Bulletin PowerFlex 400 Frame G and H Replacement Procedure for Gate Power Board Contents This publication provides instructions for replacing the gate power board for PowerFlex 400 Frame G and

More information

Installation Job Aid for VSP 4850GTS

Installation Job Aid for VSP 4850GTS Installation Job Aid for VSP 4850GTS Notices Release 6.1.0.0 NN46251-308 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs describe

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive FRN 1.xx - 4.xx User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive FRN 1.xx - 3.xx User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport PTX5000 Packet Transport Router Quick Start September 2017 Part Number: 530-066788 Revision 01 This document describes how to install the Juniper Networks PTX5000 Packet Transport Router. Contents Quick

More information

VTAC 9 AC Drive. Firmware Version 3.xx. User Manual

VTAC 9 AC Drive. Firmware Version 3.xx. User Manual VTAC 9 AC Drive Firmware Version 3.xx User Manual Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

More information

Adjustable Frequency AC Drive for Fan & Pump Applications

Adjustable Frequency AC Drive for Fan & Pump Applications Adjustable Frequency AC Drive for Fan & Pump Applications FRN 1.xx - 5.xx User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from

More information

Line filter SINAMICS. SINAMICS G130 Line filter. Safety information 1. General 2. Mechanical installation 3. Electrical installation 4

Line filter SINAMICS. SINAMICS G130 Line filter. Safety information 1. General 2. Mechanical installation 3. Electrical installation 4 Safety information 1 General 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5 Operating Instructions Control version V4.8 07/2016 A5E00331460A Legal

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive FRN 2.xx User Manual Revision C February 04 Approved 2/24/04 Revision D Next www.abpowerflex.com Important User Information Solid state equipment has operational characteristics

More information

Installation Job Aid for VSP 4450GTX-HT- PWR+

Installation Job Aid for VSP 4450GTX-HT- PWR+ Installation Job Aid for VSP 4450GTX-HT- PWR+ Notices Release 6.1.0.0 NN46251-305 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive FRN 1.xx - 7.xx User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive FRN 7.xx User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment.

More information

Installation Instructions

Installation Instructions Installation Instructions (1771-ODD Series B) Use this document as a guide when installing the catalog number 1771-ODD series B output module. The ac isolated output module is shipped in static-shielded

More information

PowerFlex DC Drive Frame B Pulse Transformer Circuit Board

PowerFlex DC Drive Frame B Pulse Transformer Circuit Board Installation Instructions PowerFlex DC Drive Frame B Pulse Transformer Circuit Board ATTENTION: Only qualified personnel familiar with DC drives and associated machinery should plan or implement the installation,

More information

Adjustable Frequency AC Drive Series B. Firmware Versions User Manual.

Adjustable Frequency AC Drive Series B. Firmware Versions User Manual. Adjustable Frequency AC Drive Series B Firmware Versions 4. User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical

More information

Digital ac/dc (24V) Input Module

Digital ac/dc (24V) Input Module Installation Instructions Digital ac/dc (24V) Input Module Catalog Number 1771-IND, Series C Topic Page Important User Information 2 Before You Begin 3 Power Requirements 3 Prevent Electrostatic Discharge

More information

PowerFlex 755 Common DC Input Drives, Frames Interlock Assembly and Precharge Assembly Left-front Cover Retrofit Kit

PowerFlex 755 Common DC Input Drives, Frames Interlock Assembly and Precharge Assembly Left-front Cover Retrofit Kit Installation Instructions PowerFlex 755 Common DC Input Drives, Frames 8...10 Interlock Assembly and Precharge Assembly Left-front Cover Retrofit Kit Catalog Numbers 20G14x, 21G14x Topic Page General Precautions

More information

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD)

HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) HUBBELL SPIKESHIELD Wired-In Branch Panels Surge Protective Device (SPD) Instruction Bulletin 8222-0513B Retain for future use. SPIKESHIELD Wired-In Branch Panels 8222-0513B 05/2012 Table of Contents Precautions...

More information

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS SINAMICS G130 Operating Instructions 03/2013 SINAMICS s Safety information 1 General information 2 SINAMICS SINAMICS G130 Mechanical installation 3 Electrical installation 4 Technical specifications 5

More information

PowerFlex 755 Transition Section and Splicing Kit for Floormount Drives and CENTERLINE 2100 Motor Control Centers

PowerFlex 755 Transition Section and Splicing Kit for Floormount Drives and CENTERLINE 2100 Motor Control Centers Installation Instructions PowerFlex 755 Transition Section and Splicing Kit for Floormount Drives and CENTERLINE 2100 Motor Control Centers Topic Page Introduction, Compatibility 1 Additional Resources

More information

AF-600 FP TM Fan & Pump Drive. (230V to 60HP, 460/575V to 125HP Operating Instructions

AF-600 FP TM Fan & Pump Drive. (230V to 60HP, 460/575V to 125HP Operating Instructions GE AF-600 FP TM Fan & Pump Drive (230V to 60HP, 460/575V to 125HP Operating Instructions Safety Safety WARNING HIGH VOLTAGE! Frequency converters contain high voltage when connected to AC mains input power.

More information

MINI-PS AC/10-15DC/8

MINI-PS AC/10-15DC/8 Primary-Switched Power Supply, Narrow Design Data Sheet 08/2004 MINI POWER provides: An extra narrow design, with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a

More information

SMVector Additional I/O Module Installation and Operation Manual

SMVector Additional I/O Module Installation and Operation Manual SMVector Additional I/O Module Installation and Operation Manual About These Instructions This documentation applies to the optional Additional I/O module for the SMVector inverter and should be used in

More information

Installation Instructions

Installation Instructions Installation Instructions This document provides information on: important pre-installation considerations power supply requirements initial handling procedures installing the module using the indicators

More information

Ferrite Core for Internal DPI Cables on PowerFlex 700S Frame 3 and 4 Drives

Ferrite Core for Internal DPI Cables on PowerFlex 700S Frame 3 and 4 Drives Installation Instructions Ferrite Core for Internal DPI Cables on PowerFlex 700S Frame 3 and 4 Drives ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged

More information

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS SINAMICS G130 Operating Instructions 05/2010 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Voltage Sensing Module 10 (VSM10) Mechanical installation 3 Electrical installation 4 Technical

More information

Installation Instructions

Installation Instructions 50ES, 50EZ, 50GL, 50GS, 50GX, 50JS, 50JX, 50JZ, 50SD, 50SZ, 50VL, 50VT, 50XP, 50XZ 601A, 602A, 602B, 604A, 604B, 604D, 607C, 701A, 702A, 702B, 704A, 704B, 704D, 707C PA1P, PA2P, PA3P, PH1P, PH2P, PH3P

More information

Voltage Current Front-mounting bracket

Voltage Current Front-mounting bracket Switching Power Supply S8PS Compact DIN-Rail Mounting Industrial Power Supplies with Capacities Up to 600 W Models range from 0 W to 600 W. Universal input: voltage range 0 to 240 VAC. Power Factor Correction

More information

MDM 011-Z1 Regen Resistor

MDM 011-Z1 Regen Resistor MDM 011-Z1 Regen Resistor Date of creation: 10.04.2017 Version date: 10.04.2017 Article number: 09-402-011-Z1-E Publisher: SIGMATEK GmbH & Co KG A-5112 Lamprechtshausen Tel.: 06274/4321 Fax: 06274/4321-18

More information

PowerFlex 700S Power Jumpers Frames 1 6

PowerFlex 700S Power Jumpers Frames 1 6 PowerFlex 700S Power Jumpers s 1 6 Installation Instructions The PowerFlex 700S drive contains protective s and ommon Mode apacitors referenced to ground (see below). To guard against unstable operation

More information

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1 200 HP)

More information

Solar Combiner Enclosure

Solar Combiner Enclosure Installation Instructions Solar Combiner Enclosure Catalog Numbers 1000-SB006, 1000-SB012 Topic Page Description 1 Important Safety Instructions 3 Nameplate Data 4 Planning for Installation 4 Install the

More information

Appendix D. EMC Installation Guidelines. Safety Considerations. Ferrite Absorbers and P-Clips. General Product Philosophy

Appendix D. EMC Installation Guidelines. Safety Considerations. Ferrite Absorbers and P-Clips. General Product Philosophy Appendix D EMC Installation Guidelines General Product Philosophy The ZETA6xxx was not designed originally for EMC compliance. Therefore, it will require specific measures to be taken during installation.

More information

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating instructions 03/2011 SINAMICS SINAMICS G130 Operating instructions 03/2011 SINAMICS s Safety information 1 General 2 SINAMICS SINAMICS G130 Voltage Sensing Module 10 (VSM10) Mechanical installation 3 Electrical installation 4 Technical

More information

PowerFlex 527 Adjustable Frequency AC Drive

PowerFlex 527 Adjustable Frequency AC Drive User Manual PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C Original Instructions Important User Information Solid-state equipment has operational characteristics differing from those of

More information

P216 Series Condenser Fan Speed Controller

P216 Series Condenser Fan Speed Controller P216 Series Condenser Fan Speed Controller Installation Instructions P216xxx-x Part No. 24-85895-18, Rev. D Issued 27 August 2015 Applications Refer to the QuickLIT website for the most up-to-date version

More information

Series Amp Pad Mount Quick Connect Input and Output Power Panels

Series Amp Pad Mount Quick Connect Input and Output Power Panels Series 300 2000-4000 Amp Pad Mount Quick Connect Input and Output Power Panels DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury.

More information

PowerFlex DC Drive - Frame A Switching Power Supply Circuit Board

PowerFlex DC Drive - Frame A Switching Power Supply Circuit Board Installation Instructions PowerFlex DC Drive - Frame A Switching Power Supply Circuit Board ATTENTION: Only qualified personnel familiar with DC drives and associated machinery should plan or implement

More information

ArmorPoint I/O Field Potential Distributor, Series A

ArmorPoint I/O Field Potential Distributor, Series A Installation Instructions ArmorPoint I/O Field Potential Distributor, Series A (Cat. No. 1738-FPD) The field potential distributor (Cat. no. 1738-FPD) lets you change the field power distribution source

More information

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual

User s Manual. ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual User s Manual ACS550-PD Stock 3R Irrigation Packaged Drive Supplement to ACS550-U1 User s Manual 2 ACS550-PD 3R Irrigation Packaged Drive ACS550 Drive Manuals GENERAL MANUALS ACS550-U1 User s Manual (1

More information

PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board

PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board Installation Instructions PowerFlex DC Drive - Frame A SCR Modules for Drives with a Power Traces Circuit Board!!! ATTENTION: Only qualified personnel familiar with DC drives and associated machinery should

More information

Redundancy unit CP-A RU

Redundancy unit CP-A RU 2CDC 271 010 F0t06 Features Decoupling of CP power supply units with 2 inputs, each up to 20 A per input / channel Output up to 40 A True redundancy by 100 % decoupling of two parallel connected power

More information

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2

Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2. Cisco CRS 3-Phase AC Power Distribution Unit 2 Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide Cisco CRS 3-Phase AC Power Distribution Unit Installation Guide 2 Cisco CRS 3-Phase AC Power Distribution Unit 2 Revised: November 18, 2016,

More information

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx

Obtaining Documentation and Submitting a Service Request, page xvii Safety Warnings, page xvii Safety Guidelines, page xx Preface Obtaining Documentation and Submitting a Service Request, page xvii Safety s, page xvii Safety Guidelines, page xx Obtaining Documentation and Submitting a Service Request For information on obtaining

More information

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death.

DANGER DANGER: is used in this manual to warn of high voltages capable of causing shock, burns, or death. Installation/Operation Manual TABLE OF CONTENTS Page UNPACKING AND INSTALLATION Unpacking and Preliminary Inspection...2, 3 Model Number...9 LOCATION CONSIDERATIONS Environment, Equipment Performance,

More information

H Manual Stretch Wrap Machine uline.com FILM ROLL CAPACITY TECHNICAL DATA ELECTRICAL SPECIFICATIONS TURNTABLE SPECIFICATIONS

H Manual Stretch Wrap Machine uline.com FILM ROLL CAPACITY TECHNICAL DATA ELECTRICAL SPECIFICATIONS TURNTABLE SPECIFICATIONS H-2304 Manual Stretch Wrap Machine 1-800-295-5510 uline.com SYSTEM SpecificationS IMPORTANT! Read this manual thoroughly and familiarize yourself with ALL controls and operating features. Keep this manual

More information

PV Rapid Shutdown device

PV Rapid Shutdown device PV Rapid Shutdown device Installation and Operation Manual Solis-RSD-1G(1:1) Solis-RSD-1G(2:2) Manufacturer: Ginlong (Ningbo) Technologies Co.,Ltd., Ningbo, Zhejiang, P.R.China US Office: 565 Metro Pl.

More information

PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start

PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start Quick Start PowerFlex 520-Series Adjustable Frequency AC Drive Quick Start Quick Start Guide for PowerFlex 523 and PowerFlex 525 AC Drives PowerFlex 523 Catalog Number 25A, Series B PowerFlex 525 Catalog

More information

Installation Notes TII Model 341 Protector

Installation Notes TII Model 341 Protector Installation Notes TII Model 341 Protector (ATT-IS PEC 32918) for MERLIN Communications System In Range Out of Building (IROB) Station Installation By Trained Technician Only WARNING: Failure to follow

More information

Installation Instructions

Installation Instructions Installation Instructions This document provides information on: important pre-installation considerations power supply requirements initial handling installing the module using the indicators for troubleshooting

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

Installation Instructions

Installation Instructions Installation Instructions Cat. No. 1771-IQ16 Series C This document provides information on: The dc isolated input module is shipped in static-shielded packaging to guard against electrostatic discharge

More information

Product Overview. PowerFlex 520-Series AC Drives Feature. Modular Design. Packaging and Mounting. Optimized Performance

Product Overview. PowerFlex 520-Series AC Drives Feature. Modular Design. Packaging and Mounting. Optimized Performance Product Overview The PowerFlex 520-Series AC drive delivers an innovative design that is remarkably versatile and can accommodate systems ranging from standalone machines to simple system integration.

More information

SynchLink Board for PowerFlex 700S Drives with Phase II Control

SynchLink Board for PowerFlex 700S Drives with Phase II Control Installation Instructions SynchLink Board for PowerFlex 700S Drives with Phase II Control ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before

More information

SP500 AC Drive Installation and Operation Manual Version 3.1

SP500 AC Drive Installation and Operation Manual Version 3.1 SP500 AC Drive Installation and Operation Manual Version 3. Instruction Manual D2-3356-5 The information in this manual is subject to change without notice. Throughout this manual, the following notes

More information

Adjustable Frequency AC Drive

Adjustable Frequency AC Drive Adjustable Frequency AC Drive User Manual www.abpowerflex.com Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety

More information

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation: DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated

More information

ABB industrial drives. Safety instructions ACS880 multidrive cabinets and modules

ABB industrial drives. Safety instructions ACS880 multidrive cabinets and modules ABB industrial drives Safety instructions ACS880 multidrive cabinets and modules Safety instructions ACS880 multidrive cabinets and modules Table of contents 2. Safety instructions 2017 ABB Oy. All Rights

More information

ICS Entrance Management Sign Installation Guide. Version 1.0

ICS Entrance Management Sign Installation Guide. Version 1.0 ICS Entrance Management Sign Installation Guide Version 1.0 Thank you for purchasing your new ICS Entrance Management System (EMS) from Innovative Control Systems, Inc. Installation Overview This document

More information

FLEX Ex Spring Clamp Terminal Base

FLEX Ex Spring Clamp Terminal Base Installation Instructions FLEX Ex Spring Clamp Terminal Base (Cat. No. 1797-TB3S) 1 10 11 4 Only remove this cover plug if connecting another terminal base unit. 3 5 6 12 2 7 8 9 41253 Component Identification

More information

User guide. SRC Pumpdrive with SmartRun functionality, dedicated for waste water pump station

User guide. SRC Pumpdrive with SmartRun functionality, dedicated for waste water pump station User guide SRC 311 - Pumpdrive with SmartRun functionality, dedicated for waste water pump station Table of Contents Table of Contents Introduction and Safety...2 SRC 311...2 Electromagnetic Compatibility...4

More information

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Rhino Buffer Module PSM24-BFM600S. Operating Instructions Rhino Buffer Module PSM24-BFM600S Operating Instructions RHINO BUFFER MODULE PSM24-BFM600S Description The PSM24-BFM600S Buffer Module will hold the output voltage of a 24 VDC power supply after brownouts

More information

PACSystems RX7i IC698CHS009/119

PACSystems RX7i IC698CHS009/119 January 2010 The RX7i rack can be used for all RX7i CPU and I/O configurations, Series 90-70 I/O, and VME modules. Backplane connectors are spaced on 0.8" (20.3mm) centers to accommodate single-width RX7i

More information