1 3710 ACM 3750 PDC 3800 RTU ISOCOM Communications Card Retrofit Instructions
2
3 Danger During normal operation of this device, hazardous voltages are present which can cause severe injury or death. These voltages are present on the terminal strips of the device and throughout the connected potential transformer (PT), current transformer (CT), status input, relay, and control power circuits. Installation and servicing should be performed only by qualified, properly trained personnel. See the Installation and Operation Manual for the specific device for additional warnings. Warning This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference in which case the operator will be required to take whatever measures may be required to correct the interference. Limitation of Liability Power Measurement Limited reserves the right to make changes in the devices or the device specifications identified in this Retrofit Installation Instructions without notice. Power Measurement Limited advises customers to obtain the latest version of device specifications before placing orders to verify that the information being relied upon by the customer is current. In the absence of written agreement to the contrarypower Measurement Limited assumes no liability for Power Measurement Limited applications assistance, customer's system design, or infringement of patents or copyrights of third parties by or arising from the use of devices described herein. Nor does Power Measurement Limited warrant or represent that any license, either expressed or implied, is granted under any patent right, copyright, or other intellectual property right of Power Measurement Limited covering or relating to any combination, machine, or process in which such device might be used. For further information or technical assistance, please contact your local Power Measurement representative, or Customer Service at one of the following locations: World Wide Web support@pml.com Worldwide Headquarters POWER MEASUREMENT LTD Keating Cross Rd., Saanichton, B.C., Canada V8M 2A5 Tel: Fax: Europe & Middle East POWER MEASUREMENT EUROPE Bayreuther Str. 6 D Forchheim Germany Tel: Fax: Asia & Pacific POWER MEASUREMENT AUSTRALIA Unit 7/16 Ledgar Road, Balcatta, Perth, Western Australia 6021 Tel: Fax: EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, UNDER NO CIRCUMSTANCES SHALL POWER MEASUREMENT LIMITED BE LIABLE FOR CONSEQUENTIAL DAMAGES SUSTAINED IN CONNECTION WITH SAID PRODUCT AND POWER MEASUREMENT LIMITED NEITHER ASSUMES NOR AUTHORIZES ANY REPRESENTATIVE OR OTHER PERSON TO ASSUME FOR IT ANY OBLIGATION OR LIABILITY OTHER THAN SUCH AS IS EXPRESSLY SET FORTH HEREIN. ISO Registration Cert # Revision Date: June 8, Power Measurement Ltd. All rights reserved Printed in Canada
4
5 Introduction NOTE For complete communication port details, refer to the Installation & Operation Manual for the specific device. The ISOCOM communications card provides a remote communications port for the following compatible instrumentation packages: 3710 ACM (Rev A & Rev B) power meters 3750 PDC power demand controller 3800 Mini RTU NOTE Two models of the ISOCOM are manufactured by PML, the ISOCOM and ISOCOM2. The ISOCOM2 card is not compatible with the devices listed above. The ISOCOM is a direct replacement for the previously used C01 card. Communications using either the RS-232C or RS-485 standards is possible. Improvements include full isolation for both RS-232C and RS-485. Optical coupling provides isolation between the communications lines and the metering equipment. Protection circuitry provides protection from common mode voltages and incorrect connection of the ISOCOM. All inputs pass the ANSI/IEEE C37-90A-1989 surge withstand and fast transient tests. This document describes the steps necessary to retrofit any device listed above with an ISOCOM card. Configuration instructions and wiring requirements for direct connection with a master computer station are provided. Refer to the Installation and Operation Manual for the device for additional information regarding remote connections made via modem. ;%62-2 It is important that all instructions provided in this document are performed exactly as described to avoid injury and to ensure the device is protected from any damage. Installation Procedure You will require the following tools to install the ISOCOM: 1. One Philips screwdriver. 2. An anti-static wrist strap or equivalent protection.
6 Preparing the 3710 ACM, 3750 PDC or 3800 RTU for Installation (%2)6 During normal operation of the 3710 ACM, 3750 PDC, or 3800 RTU, hazardous voltages are present which can cause severe injury or death. These voltages are present on the terminal strips of the device and throughout the connected potential transformer (PT), current transformer (CT), status input, relay, and control power circuits. Installation and servicing should be performed only by qualified, properly trained personnel. To prepare the 3710 ACM, 3750 PDC, or 3800 RTU for installation: 1. Open all PT fuses (or direct voltage input fuses) and close all CT shorting blocks. 2. Turn off all power to the 3710 ACM, 3750 PDC, or 3800 RTU and disconnect the Line and Neutral (or DC power) wires from the Power inputs to the unit. 3. Disconnect all other wiring (or power off all other circuits) which may present potentially hazardous voltage levels to the unit, such as connections to the relay outputs, status inputs, etc. 4. Ensure that all cables still connected to the device are NOT live. Removing the Existing CO1 Communications Card CAUTION The components inside the device are extremely sensitive to staticelectric discharge. To prevent damage to the unit, wear an antistatic wrist strap at all times when working inside the unit. Failure to use proper equipment during servicing will void the warranty. The existing CO1 Communications Card must be removed before you can install the new ISOCOM. You can remove the CO1 while the unit is still mounted in its switchgear panel (or other mounting location). The CO1 is on the right of the 3710 ACM, 3750 PDC, or 3800 RTU rear panel as depicted below:
7 ISOCOM Card Installation 1. Carefully disconnect all communication wiring from the existing card. 2. Remove the four machine screws from the rectangular communications card mounting plate with the screwdriver. 3. Pulling the plate away from the rear panel will remove the CO1 from the device. CAUTION Touch the ISOCOM only by the sides of the card or by the metal mounting plate to prevent damage to its components. The ISOCOM consists of a metal mounting plate and a barrier terminal strip connector. The mounting plate is attached to a circuit board which has a row of contacts that plug into a matching edge connector socket inside the base unit.
8 To install the ISOCOM Card: 1. Touch the side of the 3710 ACM, 3750 PDC, or 3800 RTU chassis to ground any static charge that could damage electronic components when installing the ISOCOM. 2. Locate the socket where the CO1 was previously inserted. 3. Hold the ISOCOM by the metal mounting plate and lower it into the base unit so that the two LED s face the outside edge of the case. 4. Line up the edge of the circuit board with the edge connector socket and press the ISOCOM firmly into place. The ISOCOM will be securely inserted into the socket when the mounting plate meets the chassis. The ISOCOM mounting plate is shown below: Final Steps 1. Align the holes in the metal mounting plate of the ISOCOM with the mounting holes on the base unit. Use the Philips screwdriver to replace the four machine screws. 2. Reinstall the Line and Neutral (or DC power) wiring to the Power inputs of the unit. 3. Reconnect all other wiring (or re-enable all other circuits). Close the PT fuses (or direct voltage input fuses) and open the CT shorting blocks. Turn on power to the device and verify the correct operation.
9 Terminal and LED Functions 7KH,62&20FRPPXQLFDWLRQVFDUGSURYLGHVDEDUULHUVW\OHWHUPLQDOVWULS7HUPLQDO IXQFWLRQVLQFOXGH Ground GND Chassis Ground RS-485 RS-485 Shield (electrically connected to chassis ground) - RS-485 Data Minus RS-485 Data Plus RS-232C RXD RS-232C Receive Data (i.e. data into device) TXD RS-232C Transmit Data (i.e. data out of device) SG RS-232C Signal Ground RTS RS-232C Request To Send (optional, see Chapter 6 ) Two LED indicators, TXD and RXD, show activity on the RS-485 or RS-232C communications lines and can be used to verify correct communications operation. The TXD indicator flashes when data is sent out by the device. The RXD indicator flashes when data is received by the device. RS-232C Connections NOTE Use of the RTS and CTS lines is optional. Some types of modems (e.g. radio modems) may require the use of these lines. The figure on the following page illustrates all RS-232C cable configurations and wiring connections. The cable used between a computer and modem (if used) is a standard straighthrough RS-232C communications cable with a maximum length of 50 feet (15.2 m). Refer to the installation manuals for both the computer and modem for cable requirements. Typically, a computer is configured as a DTE device, whereas a modem is configured as a DCE device. Note that this is not always the case; refer to the manual for the computer or modem for correct configuration. The cables used between a DTE or DCE device and an ISOCOM equipped device are each custom RS-232C cables. In each case, one end is equipped with a DB25 or DB9, male or female connector. The connector required depends on the mating connector of the DTE or DCE device serial port. The other end of the cable consists of discrete wires which connect to the RS-232C terminals of the ISOCOM. Cable length is 50 feet (15.2 m) maximum.
10 RS-232C Serial Cable Wiring Connections DB9 Pins (Male) DB25 Pins (Male) DB9 Pins (Female) DB25 Pins (Female) Always jumper RTS to CTS at computer end. Always jumper DSR to DTR at modem end. Jumper RTS to CTS at modem end if not Always jumper DSR to DTR at modem end. DTE ISOCOM RS-232C Port DB9 DB25 Function Function 3 2 TX RXD 2 3 RX TXD 5 7 Signal Ground SG 7 4 RTS RTS 8 5 CTS CTS 6 6 DSR 4 20 DTR DCE ISOCOM RS-232C Port DB9 DB25 Function Function 2 3 TX RXD 3 2 RX TXD 5 7 Signal Ground SG 7 4 RTS RTS 8 5 CTS CTS 6 6 DSR 4 20 DTR
11 RS-485 Connections RS-485 communications allows multiple devices to be connected on the same bus. Up to 32 devices can be connected on a single RS-485 bus, which consists of a shielded twisted pair cable. The overall length of the RS-485 cable connecting all devices cannot exceed 4000 ft. (1219 m). To connect an RS-485 communications bus to a computer or other RS-232C equipped device, an RS-232C to RS-485 converter is required, such as Power Measurement s COM32 TM or COM128 TM. The COM32 offers a single RS-485 port, while the COM128 offers a total of four RS-485 ports that can each support up to 32 devices. CAUTION Do not connect ground to the shield at both ends of a segment. Doing so allows ground loop currents to flow in the shield, inducing noise into the communications cable. General Bus Wiring Considerations s connected on the bus, including ISOCOM equipped devices, converter(s) and other instrumentation, must be wired as follows: Use a good quality shielded twisted pair cable for each RS-485 bus. It is recommended that AWG 22 (0.33 square mm) or larger conductor size be used. Ensure that the polarity is correct when connecting to the RS-485 port () and (-) terminals of each device. The shield of each segment of the RS-485 cable must be connected to ground at one end only. Isolate cables as much as possible from sources of electrical noise. Use an intermediate terminal strip to connect each device to the bus. This allows for easy removal of a device for servicing if necessary. CORRECT METHOD RS-485 Cable Terminal Strip To next device To next device Distance X Terminal Strip DO NOT CONNECT! 3-way T connection point NOT ALLOWED To next device To next device
12 Recommended Topologies s on an RS-485 bus are connected in a point-to-point configuration, with the () and (-) terminals of each device connected to the associated terminals on the next device. While there are many topologies that can be used to connect devices on an RS-485 communication bus, the two recommended methods are the straight-line and loop topologies. NOTE The COM128 can support up to four RS-485 buses simultaneously. The converter can exist at any position on the RS-485 bus, including an end point. Straight-Line Topology Terminate each device at the end point of a straight-line bus with a 1/4 watt resistor connected between the () and (-) terminals. These termination resistors reduce signal reflections that may corrupt data on the bus. The resistor should match the line impedance of the cable being used. For AWG 22 (0.33 square mm) shielded twisted pair cable, values between 150 and 300 ohms are typical. Consult the cable manufacturer s documentation for the exact impedance of your cable. RS-232 to RS-485 Converter RS485 Cable Last R T Last R T Loop Topology One advantage of the loop topology is that a single open circuit fault condition anywhere on the loop will not result in the loss of communication between the computer station and any of the remote devices. The loop topology does not require termination resistors at any point on the bus. RS-232 to RS-485 Converter RS485 Cable
13 Calculating Overall Cable Length When determining the overall length of an RS-485 communication straight-line or loop connection, it is important to account for all cable segments. For example, when RS-485 connections to the device are made via an intermediate terminal block, the lengths of cable between the device and the terminal block must be added to the total cable distance. This length is equal to 2 times distance X in the diagram on page 8. Connection Methods to Avoid Any device connection that causes a branch in the main RS-485 bus should be avoided. This includes star and tee (T) methods. These wiring methods cause signal reflections that may cause interference. RULE OF THUMB At any connection point on the RS- 485 bus, no more than two cables should be connected. This includes connection points on instruments, converters, and terminal strips. Following this guideline ensures that both star and tee connections are avoided. DO NOT CONNECT! 3-way Star connection point NOT ALLOWED RS-232 to RS-485 Converter RS485 Cable DO NOT CONNECT! RS-232 to RS-485 Converter 3-way T connection point NOT ALLOWED
14
15
16 U~ Revision date: June 8, 2000
PowerLogic ION7300 Series
PowerLogic ION7300 Series Power and Energy Meter Advanced Field Retrofit Instructions August 2006 Danger This symbol indicates the presence of dangerous voltage within and outside the product enclosure
More informationCOM32. Installation & Operation Manual
COM32 Installation & Operation Manual DANGER ElectricaI equipment contains hazardous voltages and high speed moving parts. Can cause death, serious injury or property damage. See safety instruction contained
More information3300 ACM. Installation & Operation Manual. Economical Digital Power Meter/Transducer CONTENTS
3300 ACM Economical Digital Power Meter/Transducer Installation & Operation Manual CONTENTS Danger During normal operation of this device, hazardous voltages are present which can cause severe injury or
More information9500 and 9600 I/O Card Installation Instructions
9500 and 9600 I/O Card Installation Instructions This document describes how to install, configure, and verify the operation of the optional Input/Output card ( I/O card ) into your 9500 or 9600 power
More informationIC-485S /IC-485SI. If anything is damaged or missing, contact your dealer.
User Manual IC-485S /IC-485SI Read this guide thoroughly and follow the installation and operation procedures carefully in order to prevent any damage to the units and/or any devices that connect to them.
More informationService Considerations
Danger This symbol indicates the presence of dangerous voltage within and outside the product enclosure that may constitute a risk of electric shock, serious injury or death to persons if proper precautions
More informationEnclosure TS-530 User Manual
Enclosure TS-530 User Manual 16525 East Laser Drive Fountain Hills, AZ 85268 TEL 480.837.5200 FAX 480.837.5300 info@embeddedx86.com http://www.embeddedx86.com/ Technologic Systems, Inc. COPYRIGHT 1998-200
More informationCOM128. Installation & Operation Manual
COM128 Installation & Operation Manual DANGER ElectricaI equipment contains hazardous voltages and high speed moving parts. Can cause death, serious injury or property damage. See safety instruction contained
More informationEasySync Ltd. ES-R-2x01-M RS232 to RS422 / RS485 Converter. User Guide. Document Reference No.: ES_ Version draft Issue Date:
EasySync Ltd ES-R-2x01-M RS232 to RS422 / RS485 Converter User Guide Document Reference No.: ES_000011 Issue Date: 2009-04-10 The ES-R-2001-M and ES-R-2101-M provide a simple method of converting RS232
More information3300 ACM ACM / Modicon Modbus. Advanced Digital Power Instrumentation Package. Serial Communications Protocol and Register Map. Version 1.
3300 ACM Advanced Digital Power Instrumentation Package 3300 ACM / Modicon Modbus Serial Communications Protocol and Register Map Version 1.1 Limitation of Liability Power Measurement Limited reserves
More informationSoundwebTM. Installation Guide
105 SoundwebTM Soundweb TM 9000 Installation Guide Soundweb TM Regulatory Information An example of this equipment has been tested and found to comply with the following European and international Standards
More informationFCC Information. RoHS This product is RoHS compliant. SJ/T The following contains information that relates to China.
FCC Information This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection
More informationMoxa TCC-100 Series Hardware Installation Guide
Moxa TCC-100 Series Hardware Installation Guide Twelfth Edition, January 2015 www.moxa.com/product 2015 Moxa Inc. All rights reserved. P/N: 1802001000319 Moxa TCC-100 Series Hardware Installation Guide
More informationSerial Communications Accessories SITRANS RD200/300. Operating Instructions 05/2013 SITRANS
Serial Communications Accessories SITRANS RD200/300 Operating Instructions 05/2013 SITRANS Siemens Auto SIT SITRANS RD300RANS RD300 Safety Guidelines: Warning notices must be observed to ensure personal
More informationPowerLogic ION7550 / ION7650 Hardware Lockable Meter
70052-0194-01 PRODUCT OPTION 11/2006 PowerLogic ION7550 / ION7650 Hardware Lockable Meter This document provides an overview of ION7550 and ION7650 hardware lockable meters. NOTE Industry Canada approval
More informationUSER MANUAL MODEL 2017P MODEL 2017P60. RS-232 to 20mA and. RS-232 to 60mA Current Loop Converters
USER MANUAL MODEL 2017P RS-232 to 20mA and MODEL 2017P60 RS-232 to 60mA Current Loop Converters 07M2017P-E Doc# 073051UE Revised 5/7/96 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007 1.0
More informationSerial Communication Converters & Adapters Instruction Manual
Serial Communication Converters & Adapters Instruction Manual RS-232 to RS-422/485 Converter Isolated RS-232 to RS-422/485 Converter USB to RS-232 Converter USB to RS-422/485 Converter Isolated USB to
More informationTRC-190 User s Manual
First Edition, November 2008 www.moxa.com/product 2008 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. The software described in this manual is furnished under a license agreement
More informationMoxa TCC-100 Series User s Guide
Moxa TCC-100 Series User s Guide Eighth Edition, February 2009 www.moxa.com/product 2009 Moxa Inc. All rights reserved. Reproduction without permission is prohibited. Moxa TCC-100 Series User s Guide The
More informationInstallation Instructions
Installation Instructions (Catalog Number 1771-OD) This document provides information on: Because of the variety of uses for the products described in this publication, those responsible for the application
More informationInstallation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V C30B and V T40B.
Vision OPLC Installation Guide V290 (Color) This guide provides basic information for Unitronics LCD color touchscreen models V290-19-C30B and V290-19-T40B. General Description Vision OPLCs are programmable
More informationInterface Converter. Installation Manual IC485S IC485SGB IC485SEU. RS-232 to RS-485/422 Serial Interface Converter
Interface Converter RS-232 to RS-485/422 Serial Interface Converter Installation Manual GB EU 1 Overview Changing line signals is no longer a problem. StarTech.com s / GB / EU converts RS-232 serial interfaces
More informationUnitronics Devices and RS485 Table Of Contents
Unitronics Devices and RS485 Table Of Contents RS485 Options... 1 About RS485... 1 Network Topology & Wiring... 1 RS485 Network Wiring... 1 RS485 wiring considerations... 2 RS485, by controller type...
More informationSMM Series 3G and GSM Modems. Quick Start Guide. Document Number: Version: 1.2 (20 October, 2015)
SMM Series 3G and GSM Modems Quick Start Guide Document Number: 0013-001-000272 () Documentation Control Generation Date: October 20, 2015 Cybertec Pty Limited All rights Reserved. No part of this publication
More informationEnhanced Mini-Chansim Model VCS-232
Enhanced Mini-Chansim Model VCS-232 Operations Manual ViaSat Inc. 6155 El Camino Real Carlsbad, CA 92009 http://www.viasat.com SAFETY WARNING Always observe standard safety precautions during installation,
More informationCardax FT Controller 3000
Installation Note Cardax FT Controller 000 CAUTION This equipment contains components that can be damaged by electrostatic discharge. Ensure both you and the equipment are earthed before beginning any
More information16/24 Port 10/100 Auto-Sensing Dual Speed Ethernet Switch
12 Omnitron Systems Technology, Inc. Omnitron Systems Technology, Inc. 1 FlexSwitch TM 600X 16/24 Port /0 -Sensing Dual Speed Ethernet Switch User s ual 27 Mauchly #201, Irvine, CA 92618 (949) 250-65 Fax:
More informationInstallation Instructions
Installation Instructions Cat. No. 1771 P3, P4, P5 and P5E Use this document as a guide when installing the catalog number 1771-P3, -P4, -P5 or -P5E power supplies. Because of the variety of uses for the
More informationInstruction Bulletin
Instruction Bulletin 63249-401-200/A4 03/2005 POWERLINK TM G3 Controller NF1000G3 for use with POWERLINK G3 Systems Retain for future use. NOTICE Read these instructions carefully and look at the equipment
More informationICD200A Quick Start Guide. Convert RS-232 data signals to RS-422/485 signals in heavy industrial areas.
Industrial Opto-Isolated RS-232 to RS-422/485 Converter Convert RS-232 data signals to RS-422/485 signals in heavy industrial areas. Rugged IP30-rated metal case for panel mounting. Quick Start Guide Customer
More informationInstallation Job Aid for Ethernet Routing Switch 5900 Series
Installation Job Aid for Ethernet Routing Switch 5900 Series Notices NN47211-301 Issue 05.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs
More informationMiniature Asynchronous 4-Wire High Speed Modems
ME1862A-F ME1863A-F JULY 2003 ME1862A-M ME1863A-M Miniature Asynchronous 4-Wire High Speed Modems CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S.: Call 877-877-BBOX (outside U.S. call 724-746-5500)
More informationTRC-190 User s Manual
User s Manual Edition 3.2, May 2017 www.moxa.com/product 2017 Moxa Inc. All rights reserved. User s Manual The software described in this manual is furnished under a license agreement and may be used only
More informationMT8050iE series. Installation Instruction (1) (2)
MT8050iE series 3 Installation Instructions Installation Instruction Secure the operator panel in position, using all the fastening holes and the provided brackets and screws: (A) 1 Installation and Startup
More informationINSTALLATION GUIDE. Remote RMM-700 Intelligent Site Management Device. Installation Guide WESTELL.COM
Remote RMM-700 Intelligent Site Management Device Guide INSTALLATION GUIDE Westell Technologies April 2015 Part # 030-300653 Rev. A Copyright 2015 by Westell, Inc. All Rights Reserved. Westell, Kentrox,
More informationControlKeeper 4. General Information. Connecting Relay Loads. Installation Sheet. Getting Started. Power Supply Wiring. Mounting the Cabinet
General Information ControlKeeper 4 Installation Sheet Model# CK4-120NO- Model# CK4-277NO The ControlKeeper-4 model is shipped in one package and is configured with either a 120V or a 277V transformer.
More informationMicroTech III Water Source Heat Pump BACnet MS/TP Communication Module
Installation and Maintenance Manual IM 928- Group: Controls Part Number: 66920770 Date: July 2009 Supersedes: IM 928 MicroTech III Water Source Heat Pump BACnet MS/TP Communication Module NOTICE Use this
More informationPS/IO Circuit Board Retrofit
S&C 6800 Series Automatic Switch Controls PS/IO Circuit Board Retrofit Table of Contents Section Page Introduction Qualified Persons.... 2 Read this Instruction Sheet.... 2 Retain this Instruction Sheet....
More informationDVAA Series Disk Array for DVR1 Series Digital Video Recorder
DVAA Series Disk Array for DVR1 Series Digital Video Recorder Eng Installation Instructions Philips Communication, Security & Imaging Warning! To prevent fire and electronic shock, do not expose this product
More informationAn ISO-9001 Certified Company
USER MANUAL MODEL 1002 and 1002S Asynchronous 2-Wire / Coax Short Range Modem An ISO-9001 Certified Company Part #07M1002-C Doc. #050011UC Revised 4/28/98 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT
More informationPCI Serial Card 2 Port RS-422/RS-485 PCI Serial Card with Terminal Block Connectors PCI2S422TB Instruction Manual Actual product may vary from photo
PCI Serial Card 2 Port RS-422/RS-485 PCI Serial Card with Terminal Block Connectors PCI2S422TB Actual product may vary from photo FCC Compliance Statement This equipment has been tested and found to comply
More informationIntegrity Instruments Application Notes. Release 1
Integrity Instruments Application Notes Release 1 What is EIA/TIA/RS-485 What is EIA/TIA/RS-422 Half Duplex and Full Duplex Communication Asynchronous Communicatin Grounding EIA/TIA/RS-485/422 Shielding
More informationSerial PROFIBUS Interface
Installation Manual Serial PROFIBUS Interface Version: EN-062016-2.3 Copyright 2016 Softing Industrial Automation GmbH Disclaimer of liability The information contained in these instructions corresponds
More informationInstruction Guide. Two Port ISA Serial Card ISA2S550. The Professionals Source For Hard-to-Find Computer Parts
SERIAL CARD Two Port 16550 ISA Serial Card ISA2S550 Instruction Guide * Actual product may vary from photo The Professionals Source For Hard-to-Find Computer Parts FCC COMPLIANCE STATEMENT This equipment
More informationModel 7705 Control Module
www.keithley.com Model 7705 Control Module User s Guide PA-696 Rev. D / October 2006 A G R E A T E R M E A S U R E O F C O N F I D E N C E Safety Precautions The following safety precautions should be
More informationThis guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens).
Vision OPLC Installation Guide Models 230/260/280/290 (Non-color Screens) This guide provides basic information for Unitronics Models 230/260/280/290 (Non-color Screens). General Description Vision OPLCs
More informationSeries 3700 Screw Terminal Assemblies Installation Instructions
Keithley Instruments, Inc. 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY www.keithley.com Series 3700 Screw Terminal Assemblies Installation Instructions Introduction This document contains handling
More informationTable 8 shows the pin configuration and function of a standard computer-to-printer parallel cable. Table 8 Parallel Cable Pin Configuration
Advanced Printer Inion Parallel Data Port Parallel Data Port The parallel data interface supports IEEE 1 bidirectional parallel communications in nibble mode. The parallel interface provides a means of
More informationF1000 User's Manual. (Version: V1.01)
(Version: V1.01) Contents Chapter 1 Overview... 2 Chapter 2 Installation... 3 2.1 Installation guide... 3 2.1.1 Installation position... 3 2.1.2 NEMA4 standard installation... 3 2.1.3 Environment precautions...
More informationWhen any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Vision OPLC V350-35-R34/V350-J-R34 Installation Guide The Unitronics V350-35-R34/V350-J-R34 offers the following onboard I/Os: 22 Digital Inputs, configurable via wiring to include 2 Analog and 3 HSC/Shaft-encoder
More informationSC32A OPTICALLY ISOLATED RS232 INTERFACE INSTRUCTION MANUAL
SC32A OPTICALLY ISOLATED RS232 INTERFACE INSTRUCTION MANUAL REVISION: 1/93 COPYRIGHT (c) 1987, 1993 CAMPBELL SCIENTIFIC, INC. WARRANTY AND ASSISTANCE The SC32A OPTICALLY ISOLATED RS232 INTERFACE is warranted
More informationQuick Start Installation Guide
apc/l Quick Start Installation Guide Version A2 Document Part Number UM-201 May 2010 OVERVIEW The apc/l is an intelligent access control and alarm monitoring control panel which serves as a basic building
More informationIntegrated Stepper Drive & Motor
SMD23 Integrated Stepper Drive & Motor Manual #: 940-0S050 User Manual AMCI Motion Control Products Important User Information The products and application data described in this manual are useful in a
More information4 Port PCI Express PCIe Serial Combo Card - 2 x RS232 2 x RS422 / RS485
4 Port PCI Express PCIe Serial Combo Card - 2 x RS232 2 x RS422 / RS485 PEX4S232485 *actual product may vary from photos DE: Bedienungsanleitung - de.startech.com FR: Guide de l'utilisateur - fr.startech.com
More informationALPHA Plus and A3 ALPHA Switchboard Meters with the CPS Power Supply
October 2012 IL42-4031C ALPHA Plus and A3 ALPHA Switchboard Meters with the CPS Power Supply General This leaflet contains general installation instructions for ALPHA Plus and A3 ALPHA meters with the
More informationUser Guide CPSMP VAC Power Supply Module: PointSystem CPSMC Accessory CPSMC Accessory. Contents.
User Guide CPSMP-205 110 240 VAC Power Supply Module: PointSystem CPSMC1800-200 Accessory CPSMC1900-100 Accessory Contents Contents...1 Description...1 Cautions and Warnings...2 Definitions...2 Power supply
More informationModel 2460-KIT. Screw Terminal Connector Kit. Description / September 2014 *P * 1
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-800-935-5595 http://www.keithley.com Model 2460-KIT Screw Terminal Connector Kit Description The Model 2460-KIT Screw Terminal Connector Kit
More informationFrame Relay Cabling This section describes the cabling and connector pinouts for the Frame Relay cards.
A P P E N D I X B Cabling Summary Introduction This appendix contains details on the MGX 8850 cabling. Note In all cable references, the transmit direction is away from the switch, and the receive direction
More informationWhen any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Vision OPLC V130 COM Modules: V100-17-CAN, V100-17-RS4/X, V100-17-ET2 This guide shows you how to install an additional communication module in a V130 controller. Instructions and technical specifications
More informationMicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 852-2 Group: Controls Part Number: IM 852 Date: January 2008 Supercedes: IM 852-1 MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module
More informationEX-RC1 Remote I/O Adapter
EX-RC1 Remote I/O Adapter The EX-RC1 interfaces between Unitronics Vision OPLCs and remote I/O Expansion Modules distributed throughout your system. The adapter is connected to a PLC via CANbus. Each adapter
More informationUSER MANUAL. MODEL 2011 High Speed Asynchronous to Synchronous Converter
USER MANUAL MODEL 011 High Speed Asynchronous to Synchronous Converter Part# 07M011-A Doc# 0601UA Revised 03/16/94 SALES ICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007 http://www.patton.com 1.0 WARRANTY
More informationABB Drives. User s Manual Modbus Adapter Module FMBA-01
ABB Drives User s Manual Modbus Adapter Module FMBA-01 Modbus Adapter Module FMBA-01 User s Manual 3AFE68586704 REV A EN EFFECTIVE: 27.06.2005 2005 ABB Oy. All Rights Reserved. 5 Safety instructions
More information4 10/100/1000T Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch. User Manual SISTP LRT
4 10/100/1000T + 2 1000 Mini-GBIC with 4 IEEE 802.3at High Power PoE Industrial Wide Temperature Switch User Manual V1.0 September-2013 FCC Warning This Equipment has been tested and found to comply with
More informationDATA CONNECT ENTERPRISE
DATA CONNECT ENTERPRISE User s Manual IG202T and IGV23 Modem Document Number 520-01005-001 Rev. A DATA CONNECT Contents Contents... iii Figures... iv Chapter 1 Introduction... 5 Features...6 Applications...7
More informationInstallation Instructions
TM Installation Instructions Manual 10 - Star Driver Modules PY-STR, PY-STR-L, PY-STR-H and PY-STR-2-H Read also: Installation Instructions, Manual 2 - Network Wiring Please read this manual completely
More informationWR-5e Remote Control
1. Introduction WR-5e Remote Control The WR-5e is a microprocessor based serial data remote control unit for Ashly NE or NX products. Compatible products currently include Pema amplifiers, ne8800 and ne4800
More informationCable and Port Specifications
Send documentation comments to mdsfeedback-doc@cisco.com APPENDIXC This appendix includes the cables and connectors used with the Cisco MDS 9100 Series Fixed Configuration Fabric Switch, and it includes
More informationSelect a Data Communication Interface
Printer Setup and Operation Select a Data Communication Interface Select a Data Communication Interface You may connect your print engine to a computer using one or more of the available connections. The
More informationInstallation Instructions
Installation Instructions (1771-ODD Series B) Use this document as a guide when installing the catalog number 1771-ODD series B output module. The ac isolated output module is shipped in static-shielded
More informationISOLATED RS-232 TO RS-422/485 CONVERTER
QUICK START GUIDE ICD400A ISOLATED RS-232 TO RS-422/485 CONVERTER 24/7 TECHNICAL SUPPORT AT 877.877.2269 OR VISIT BLACKBOX.COM STEP 1 - Specifications Complies with FCC Class B and CE requirements. Withstands
More informationUSER MANUAL. MODEL 1052 idsl Modem with RS-232 Interface. An ISO-9001 Certified Company SALES OFFICE (301) TECHNICAL SUPPORT (301)
USER MANUAL MODEL 1052 idsl Modem with RS-232 Interface An ISO-9001 Certified Company Part# 07M1052-B Doc# 058061UB Revised 5/24/02 SALES OFFICE (301) 975-1000 TECHNICAL SUPPORT (301) 975-1007 TABLE OF
More informationANC Series RS-422 Serial Communications Adapter
Rev. B $ 5.00 ANC - 6000 Series RS-422 Serial Communications Adapter Antona Corporation, Los Angeles, CA Antona Corporation (818)783-4299 FAX (818)783-4216 1 Antona Corporation Copyright Copyright (c)
More informationUSB to RS232 Adapter
USB to RS232 Adapter 4 port USB to RS232 Adapter ICUSB2324 Actual product may vary from photo FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class B digital
More information4170 POS System Installation Guide
4170 POS System 4170 Installation Guide Thank you for selecting UTC RETAIL s innovative Model 4170 Point of Sale solution! This Installation Guide will help you efficiently install the 4170 POS. The document
More informationICD105A 1008 page 1/ r001 ICD105A. Industrial RS-232 to RS-422/485 Converter
ICD105A 1008 page 1/5 7319 r001 ICD105A Industrial RS-232 to RS-422/485 Converter Data Rates up to 115.2 Kbps 10 48 VDC Input Power Range Wide Operating Temperature 3-Way 2000V Optical Isolation Modbus
More informationfiber optic gateway control box
fiber optic gateway control box Product Overview Celerity Fiber Optic Gateway (FOG) products are designed for high performance, dependability and convenient installation in professional AV applications.
More informationResolver to Digital Expansion Board
Resolver to Digital Expansion Board Catalog No. EXB009A01 Installation and Operating Manual 6/98 MN1313 Table of Contents Section 1 General Information............................. 1-1 Introduction....................................
More informationSquare D Clipsal Pascal Automation Controller
Square D Clipsal Pascal Automation Controller SLC5500PACA For Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal Pascal Automation Controller 63249-420-258A2 Instruction
More informationABB Drives. User s Manual. Modbus Adapter Module RMBA-01
ABB Drives User s Manual Modbus Adapter Module RMBA-01 Modbus Adapter Module RMBA-01 User s Manual 3AFE 64498851 REV A EN EFFECTIVE: 1.3.2002 2002 ABB Oy. All Rights Reserved. Safety instructions Overview
More informationDCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies
DCS-E 1kW Series, DLM-E 3kW & 4kW Power Supplies M51A Option: Isolated Analog Programming Manual Power Supplies Elgar Electronics Corporation 9250 Brown Deer Road San Diego, CA 92121-2294 1-800-73ELGAR
More informationRS-232/RS-422 Optical Isolator
MAY 1998 IC457A-F IC457A-M RS-232/RS-422 Optical Isolator CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S. 24 hours, 7 A.M. Monday to midnight Friday: 877-877-BBOX FREE technical support, 24 hours
More informationAI port High Speed Asynchronous Line Card Installation Guide
AI232 32-port High Speed Asynchronous Line Card Installation Guide Part Number QR-232 Rev 3 2008 by Kentrox, Inc. All rights reserved. Copyright 2008 by Kentrox, Inc. All Rights Reserved. The material
More informationTraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE
TTDM-128 TraceTek Leak Detection Master Module Installation Instructions TRACETEK APPROVALS AND CERTIFICATIONS TYPE NM General Signaling Equipment 76LJ GENERAL INFORMATION Please read these instructions
More informationSATA II HDD Canister KISS DA 435 Quick Reference Guide
SATA II HDD Canister KISS DA 435 Quick Reference Guide If it s embedded, it s Kontron 1. Table of Contents SATA II HDD Canister KISS DA 435 1. Table of Contents 1. Table of Contents... 1 2. Important Information...
More informationInstalling and Configuring Rialto Analytic Appliances
Installing and Configuring Rialto Analytic Appliances Important Safety Information This manual provides installation and operation information and precautions for the use of this camera. Incorrect installation
More informationBluetooth RS-232 Dongle. User s Manual BTS-100
Bluetooth RS-232 Dongle User s Manual BTS-100 Table of Contents 1. INTRODUCTION... 2 2. PHYSICAL DIAGRAM... 3 3. BLUETOOTH PAIRING AND CONNECTING... 4 4. RS-232 INSTALLATION... 10 5. HYPERTERMINAL SETTING
More informationMicroTech III Applied Terminal Systems BACnet MS/TP Communication Module
Installation and Maintenance Manual IM 928-2 Group: Controls Part Number: 669207702 Date: March 2011 Supersedes: IM 928-1 MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module NOTICE
More information13 MMC for PC Option Modules
Part Number M.1300.8684 MMC for PC Option Modules Manual V3.0 The information in this document is also available in the MMC for PC Hardware Manual. 13 MMC for PC Option Modules 13.1 General The MMC for
More information8-Port USB-to-Serial RS232 Adapter Hub with Daisy Chain - Rack Mountable
8-Port USB-to-Serial RS232 Adapter Hub with Daisy Chain - Rack Mountable ICUSB23208FD *actual product may vary from photos FR: Guide de l utilisateur - fr.startech.com DE: Bedienungsanleitung - de.startech.com
More informationVision OPLC V TR6/V350-J-TR6
Vision OPLC V350-35-TR6/V350-J-TR6 Installation Guide The Unitronics V350-35-TR6/V350-J-TR6 offers the following onboard I/Os: 8 Digital Inputs, configurable via wiring to include 2 Analog (current/voltage)
More informationInstallation Manual. Table of Contents
Table of Contents Table of Contents... 4-1 4.1 Confirming the Installation Preparations... 4-1 4.2 Installation Flowchart... 4-1 4.3 Mounting the Switch to the Designated Position... 4-2 4.3.1 Mounting
More informationHEC. General Operating, Maintenance and Installation Manual
HEC General Operating, Maintenance and Installation Manual D-91056 Erlangen Phone: +49 9131 7677 47 Fax: +49 9131 7677 78 Internet : http://www.ipcomm.de Email: info@ipcomm.de Edition November 2005 Version
More informationATX12V 2.2 Power Supply for HP & Compaq Systems
ATX12V 2.2 Power Supply for HP & Compaq Systems 350 Watt ATX12V 2.2 Power Supply 400 Watt ATX12V 2.2 Power Supply ATXPW350HPCQ ATXPW400HPCQ Actual product may vary from photo FCC Compliance Statement This
More informationAgilent OBSAI Protocol Tester
Agilent OBSAI Protocol Tester Hardware Reference Guide Agilent Technologies Notices Agilent Technologies, Inc. 2008 No part of this manual may be reproduced in any form or by any means (including electronic
More information16950 RS-232 Dual Voltage / Dual Profile Serial Card
16950 RS-232 Dual Voltage / Dual Profile Serial Card 1 Port PCI 16950 RS-232 Dual Voltage / Dual Profile Serial Card 2 Port PCI 16950 RS-232 Dual Voltage / Dual Profile Serial Card PCI1S950DV PCI2S950DV
More informationSMD Series Integrated Stepper Driver and Motor Revision 1.3
The AMCI Integrated Stepper Motor and Microstepping Drive Combination represents the future of Stepper Motor Control applications. The SMD is a self-contained stepper motor and driver package, capable
More informationChannel Switch CS. General Operating, Maintenance and Installation Manual
Channel Switch CS General Operating, Maintenance and Installation Manual D-91056 Erlangen Phone: +49 9131 7677 47 Fax: +49 9131 7677 74 Internet: http://www.ipcomm.de Email: info@ipcomm.de Edition September
More informationEasySYNC Ltd. USB to Serial Converters Manual
EasySYNC Ltd Document Reference No.: ES_000061 Issue Date: 2011-08-23 The ES-U-xxxx-x adapters are a series of USB Serial Converters from EasySYNC Ltd. They provide a simple method of adapting legacy RS-232
More informationR325P Single Axis Driver
R325P Single Axis Driver User Manual And Commands Guide Version 1.3 Thank you for purchasing the R325P Single-Axis Step & Direction Driver. This product is warranted to be free of manufacturing defects
More information