Risk Implications of Digital RPS Operating Experience

Size: px
Start display at page:

Download "Risk Implications of Digital RPS Operating Experience"

Transcription

1 Risk Implications of Digital RPS Operating Experience For Presentation at IAEA Technical Meeting on Common-Cause Cause Failures in Digital Instrumentation and Control Systems of Nuclear Power Plants June 19-21, 2007 Bethesda, Maryland, USA Dr. John H. Bickel 1

2 Motivations for this work: No prior risk or importance analysis of existing digital RPS failure experience exists Prior NRC Research reports concluded LER data too sparse to use Only found: 18 microprocessor failures, 4 software failures Suggested need to consider data from aerospace, medical, transport systems Lack of data implied: inability to risk-inform digital I&C applications and issues My belief: Much more data actually exists on CE CPCS Risks from CPCS experience should be assessed 2

3 CE Digital Core Protection Calculator Basics: CE High LPD, Low DNBR RPS design switched from analog Thermal Margin/Low Pressure Trip to digital Core Protection Calculators in mid 1970 s Used 6 specially qualified minicomputers running stored computer software and addressable constants CPCS performs static/dynamic projections of local power density and DNBR based upon: Ex-core neutron flux Pressurizer pressure Reactor Tcold, Thot RCP pump speed Control rod positions CPCS generates: alarms, pre-trip, and trip safety actions Original system was licensed on ANO-2 2 in 1978 Subsequently utilized at: SONGS-2/3, Waterford-3, Palo Verde-1/2/3. and Korean Standard NPPs 3

4 CE Digital Core Protection Calculator Basics: CPCS credited for reactor trip for following events: Uncontrolled Control Rod withdrawal from critical (>10-4 power) Uncontrolled Boron Dilution from critical (>10-4 power) Uncontrolled Control Rod withdrawal from power operation Dropped, or mis-positioned Control Rods Ejected Control Rods Single RCP loss of flow Single RCP shaft seizure 4-RCP loss of flow Electrical grid under-frequency Excess secondary steam flow (including turbine bypass valve malfunction) Excess feedwater flow Loss of feedwater heater Steam line break Single MSIV closure Rapid increase in local power 4

5 CE Digital CPCS Software Basics: Software Design: One Good Version not N-Version 5

6 CE Digital CPCS Interchannel Communications Basics: 4 CPC computers evaluate: LPD, DNBR using neutron flux, temperature, RCS flow and control rod position inputs in each quadrant 2 CEA computers (CEACs) monitor all quadrants for CEA deviations within groups and generate Penalty Factors transmitted to all 4 CPCs CEACs communicate to CPCs via one-way simplex communication links 6

7 CE Reactor Protection System PRA Basics: PRA Assessments of overall CE RPS have existed for some time (2001) Component unavailabilities based on time averaged values NUREG/CR-5500 Vol.10: Q RPS = 7.2E-6 6 (Digital CPCS, w/o Operator Action) Q RPS = 1.6E-6 6 (Digital CPCS, w/ Operator Action) Relay and breaker CCF dominates predicted Q RPS : CCF of master trip relays (K-1 1 through K-4) K CCF of reactor trip breaker is not as significant on CE design due to configuration 7

8 How This Study was Carried Out: Failure experience from on-line NRC LER data base currently goes back to 1984 (NOTE: misses first 6 years ANO-2 2 experience) Post-1984 CPC LERs on CE plants were evaluated CPCS Failure experience categorized by subsystem Size of operating experience pool: 141 LERs ( ) ~145.5 Rx years (or: 1.27x10 6 Rx hr) 70 actual CPC reactor trip demands 26 events involving latent CCF (including: 1 latent software CCF) Subsystem failure rates calculated via Bayesian estimation using Jeffrey s non-informative prior CCDP risk estimated via ASP approach Method highlights CCDP impact of higher than average unavailability ility 8

9 How Component Population Was Estimated: Total CPCS subsystem operating time estimation was based upon above component inventory per plant Total CPCS operating time (for 4/4 Channel CCF estimation) was simply s total plant operating time. 9

10 How Subsystem Operating Time Was Estimated Each of 4 CPC Computers and 2 CEAC Computers contain: 1 processor board, 1 memory board, 1 multiplexer board, 1 external Watchdog Timer Each of 4 CPC Channels contains: 1 PZR pressure sensor, 3 ex-core neutron flux inputs, 4 RCP speed sensors, 2 Tcold and 2 Thot inputs 10

11 Subsystem failure rates were calculated via Bayesian estimation using Jeffrey s non-informative prior Technique allows bounding failure rate estimation for 0 observed ed failures 11

12 Failure Rate and Unavailability Estimation Issues Data Needs for Risk Estimation Process: Ability to estimate CCDP given specific event demands and event-conditional system unavailabilities (such as RPS) Includes conditional unavailability due to specific combinations of input conditions to digital system Certain software bugs only triggered by unusual input sets Overall RPS unavailability must consider combinations of random and CCF events Operating experience estimates failure rates: λ Conversion to RPS unavailability uses estimate of time to detect and restore: P = λ x (fault duration) In many cases for latent Digital CCFs fault durations are many months 12

13 Actual Design Basis CPCS Trip Demands 13

14 Estimated CPCS Single Subsystem Failure Rates 14

15 CPCS Single Subsystem Failure Rates Also important to note: Failure modes of recent regulatory concern which have not occurred in population exposure time Recall failure rates can be estimated as: λ ~ 0.5/T Faults propagated via inter-channel communication: 2 events noted involving loss of CPCS -> > Plant Computer communications link that resulted in failure to perform Tech. Spec. required cross oss-checks, λ = 2.5 / ( 6 x 1.27x10 6 hours) = 3.3 x10-7 /hr Other events in which communication link failure occurred without operation impairment likely occurred but not reported in LER data a base Events involving a failure propagating to CPC or CEAC would be in LER data base if they occurred 0 events noted in which a communication link failure caused corruption to CPC or CEAC channel, λ ~ 0.5 / ( 6 x 1.27x10 6 hours), or: ~ 6.6 x10-8 /hr 15

16 Estimated CPCS Double Event Failure Rates 16

17 Estimated CPCS System CCF Failure Rates 17

18 Results: CPCS System CCF Failure Rates Breakdown of Common Mode Failures 4% 4%4% 4% 4% 8% 11% 8% 4% 8% Computer Technicians insert Wrong Data Sets to all 4 CPCS Channels Reactor Vendor supplies Erroneous Data Sets input to all 4 CPCS Channels Reactor Vendor Supplies Software Update Containing Latent Software Error Operators Fail to Confirm ASI in all four CPCS Channels when Reactor Power > 20% Incorrect Acceptance Criteria Used for Excore Data Set Calibration Checks >80% Inaccurate Cross Calibration of Excore Data Sets (Cross Channel, COLSS, etc.) High Log Power Bypass Removal Setpoints (1E-4) Incorrect 11% 26% 4% Inaccurate Cross Calibration of RCS Flow Data Sets (Cross Channel, COLSS, etc.) Operators Fail to Perform 12hr Auto-RESTART Surveillance on all CPCS Channels Operators Fail to Perform Refueling Interval Surveillance on all CPCS Channels Communication Data Link Failure to Plant Computer results in Missed Surveillances on both CEAC Channels 2 of 2 CEACs Inoperable 3 of 4 CPCS Neutron Flux Cross Channel Calibrations OOT The issue of latent software CCF represents only 4% of the CCF experience Calibration, generating, loading of incorrect data sets are the dominant sources of CCF 18

19 Types of Observed CCF Events: Inaccurate cross-calibration calibration of all Ex-core neutron flux (7 events) or all RCS flow channels (2 events) Computer technicians insert wrong addressable constant data sets into all 4 CPCS channels (3 events) Swapping addressable data sets between units CE supplies erroneous data sets (2 events) Software update provided to plant with incorrect logic for processing of indicated failed sensors (1 event) 19

20 Risk significance of this failure experience? None of actual CCF events resulted in core damage (all were latent faults missing triggering event ) Need to consider CCDP implications of specific failure modes Intent: apply risk screening process similar to NRC ASP program which focuses on higher than average values of system unavailability Use: ASP-type failure rate data, SPAR plant specific risk models, actual observed unavailability CCDP = Σ λ i x P CPCS-CCF CCF x HEP NR P CPCS-CCF CCF = λ CPCS-CCF CCF x (duration of latent fault) First: How sensitive is CCDP to RPS Logic CCF? 20

21 How sensitive is CCDP to RPS Logic CCF? RPS failure considers: Mechanical CCF jamming of control rods Relay/Breaker CCF failure RPS Logic CCF Operators fail to manually trip Operators fail to trip MG sets Loss of Offsite Power generates reactor trip without RPS Sensitivity studies conducted using NRC SPAR PRA models 21

22 How sensitive is CCDP to RPS Logic CCF? Variations in RPS-LOGIC LOGIC-CCF CCF are not risk significant until > 1x

23 Some example risk assessments of actual Digital CCF events 23

24 1995 SONGS Addressable Data Swapped Rod shadowing constants (on data disks) were swapped between adjacent SONGS units for 10,968 hours. Units at different power and burnup history, rod shadowing corrections thus different. Rod shadowing constants only impact power density predictions when control rods dropped, or partially inserted. P CPCS-CCF = 2.75x10-6 /hr x 10,968 hr = 3.0 x10-2 Summing over all initiating events involving dropped control rods and rod cycling tests, yields: CCDP < 0.488/yr x 3.0 x10-2 x 0.01 = 1.5 x 10-4 This represents bounding conservative estimate because better knowledge of duty cycle of rod cycling tests would likely reduce by factor of 10 or more. 24

25 1984 Erroneous F x,y factors supplied by CE and uploaded to SONGS-2 Incorrect F x,y factors generated by CE and used for CPCS LPD calculations from to (1,032 hrs). Events such as this have occurred twice. P CPCS-CCF = 1.96x10-6 /hr x 1,032 hr = 2.0 x10-3 CCDP = 0.488/yr x 2.0 x10-3 x 0.01 = 1.5 x

26 2005 Software Design Error in Software Upgrade at Palo Verde 2 for 2,736 hrs. Original software design: Trip CPC channel if sensor detected to be Failed Out of Range Software hardware upgrade: Use inputs from two sets of instruments and multiplexers (primary y and secondary) Out of Range Sensor Failure: Primary detected sensor failure results in switchover to secondary. Out of Range Failure on secondary reverts to last stored good value v CCF of all sensors of one type could result in continuous use of last good value in all 4 CPCS channels rather than TRIP. P CPCS-CCF = 8 x P Sensor-CCF x 2.75x10-6 /hr x 2,736 hr =8 x 8.4 x10-4 x 2.75x10-6 /hr x 2,736 hr = 5.0 x10-5 Given CCF of instruments, no credit for operators, HEP=1.0 CCDP = 0.289/yr x 5.0 x10-5 x 1.0 = 1.44 x

27 PRPS-CCF values from single events span many decades Fault duration times drive PRPS-CCF values Latent data uploading errors are dominant unavailability contributors Data uploading errors larger than relay and breaker CCF found in NUREG/CR-5500 (which used time-averaged values) 27

28 Event specific CCDP also dominated by data uploading errors Latent software CCF event is smaller due to unlikelihood of triggering condition. 28

29 Observations from this Total Picture of RPS : Designers of Digital I&C not particularly surprised by relative dominance of: Calibration problems and human errors uploading wrong data sets CCF due to errors by vendor in generating data sets These failure modes also existed in NPPs with Analog I&C CCF Unavailability and event CCDP estimates from operating experience are dominated by latent events with very long fault duration intervals Software-related CCF, while important, isn t dominant CCF source when actual operating experience is evaluated Likely because: software V&V processes more rigorous than operational controls after deployment at NPP Most-obvious software bugs generally caught by burn-in testing and qualification programs Software bugs triggered by highly unlikely input combinations are not key sources of RPS unavailability or CCDP risk 29

30 What is Concluded from all this? To assess Digital I&C risk it s necessary to view Total Picture of RPS not just software or : microprocessors : Final trip relays and trip breakers - will still be there Problems cross calibrating nuclear with thermal - will still be there Human errors inputting set-points and coefficients - will still be there When this is done - Total Picture of RPS risk emerges NPPs with CPCS have been operating since 1978 in typical, controlled, nuclear operations environment, which includes: Vendor generation of cycle specific constants, set-points Routine hardware, software upgrades developed and installed Routine operation, trouble alarms, and alarm response Impact of Technical Specifications, Testing, Calibrations Actual nuclear field reliability experience is better source of data than non-nuclear nuclear sources or theoretical models Ability to estimate, or bound risks of specific Digital I&C CCF failure modes thus: clearly exists 30

Common Technical Issue On I&C

Common Technical Issue On I&C Common Technical Issue On I&C Chashma Unit-1 and 2 Pakistan by M.Ramzan Tahir IAEA Technical Meeting on Instrumentation and Control in SMRs At VIC Vienna, Austria (21 ~ 24 May, 2013) Contents Plants Design

More information

IMPLEMENTATION OF FLEX STRATEGIES IN SURRY PRA. Aram Hakobyan and Craig Nierode Dominion Energy

IMPLEMENTATION OF FLEX STRATEGIES IN SURRY PRA. Aram Hakobyan and Craig Nierode Dominion Energy IMPLEMENTATION OF FLEX STRATEGIES IN SURRY PRA Aram Hakobyan and Craig Nierode Dominion Energy PSA-2017 Pittsburgh, PA FLEX strategies OVERVIEW Surry plant features and risk contributors Flooding SBO FLEX

More information

DEVELOPMENT OF AN ADVANCED CORE PROTECTION CALCULATOR SYSTEM NAMED RCOPS

DEVELOPMENT OF AN ADVANCED CORE PROTECTION CALCULATOR SYSTEM NAMED RCOPS DEVELOPMENT OF AN ADVANCED CORE PROTECTION CALCULATOR SYSTEM NAMED RCOPS Seung-Min Kim 1, Seung-Yeob Baeg 1, Jong-Sik Bae 1, Dong-Wook Kim 2, Sung-Ho Kim 3, Hang-Bae Kim 3, Wang-Kee In 4, Young-Ho Park

More information

SIS Operation & Maintenance 15 minutes

SIS Operation & Maintenance 15 minutes 2005 Emerson Process Management. All rights reserved. View this and other courses online at www.plantwebuniversity.com. SIS 301 - Operation & Maintenance 15 minutes In this course: 1 Overview 2 Planning

More information

A Treasure is Hidden in Every Nuclear Power Plant AMS Corporation Duplication Prohibited Slide 2

A Treasure is Hidden in Every Nuclear Power Plant AMS Corporation Duplication Prohibited Slide 2 H.M. Hashemian 1 A Treasure is Hidden in Every Nuclear Power Plant What is it? Where is it? How to get to it? Slide 2 What Can We Do With It? Slide 3 What Happens When You Go To The Doctor Slide 4 Diagnostics

More information

DESIGN BASIS VERIFICATION AND PRESERVICE TESTING CONSIDERATIONS FOR OM CODE MANDATORY APPENDIX III

DESIGN BASIS VERIFICATION AND PRESERVICE TESTING CONSIDERATIONS FOR OM CODE MANDATORY APPENDIX III Proceedings of the ASME/NRC 2017 13th Pump and Valve Symposium PVS2017 July 17-18, 2017, Silver Spring, Maryland PVS2017-3504 DESIGN BASIS VERIFICATION AND PRESERVICE TESTING CONSIDERATIONS FOR OM CODE

More information

CONSIDERING DUAL-UNIT LOSS OF OFFSITE POWER INITIATING EVENT IN A SINGLE-UNIT LEVEL 1 PSA

CONSIDERING DUAL-UNIT LOSS OF OFFSITE POWER INITIATING EVENT IN A SINGLE-UNIT LEVEL 1 PSA CONSIDERING DUAL-UNIT LOSS OF OFFSITE POWER INITIATING EVENT IN A SINGLE-UNIT LEVEL 1 PSA Dong-San Kim 1, Jin Hee Park 2, Ho-Gon Lim 3 1-3 Integrated Safety Assessment Division, Korea Atomic Energy Research

More information

TIMED-FAULT TREE GENERATION FROM DYNAMIC FLOWGRAPH METHOD

TIMED-FAULT TREE GENERATION FROM DYNAMIC FLOWGRAPH METHOD TIMED-FAULT TREE GENERATION FROM DYNAMIC FLOWGRAPH METHOD Chireuding Zeliang Graduate Research Assistant Faculty of Energy Systems and Nuclear Science University of Ontario Institute of Technology Oshawa,

More information

EXPERIENCE AND EVALUATION OF ADVANCED ON-LINE CORE MONITORING SYSTEM BEACON AT IKATA SITE

EXPERIENCE AND EVALUATION OF ADVANCED ON-LINE CORE MONITORING SYSTEM BEACON AT IKATA SITE EXPERIENCE AND EVALUATION OF ADVANCED ON-LINE CORE MONITORING SYSTEM BEACON AT IKATA SITE Nobumichi Fujitsuka, Hideyuki Tanouchi, Yasuhiro Imamura, Daisuke MizobuchiI IKATA Power Station Shikoku Electric

More information

Summary. Business Value

Summary. Business Value Summary Feedwater control systems Tricon Triple Modular Redundant (TMR) Digital System for Feedwater Control and Safety Application in Nuclear Power Plants are critical to the safe and efficient operation

More information

Knowledge Management in Licensing & Design Bases. Thomas Koshy, Head Nuclear Power Technology Development Division of Nuclear Power

Knowledge Management in Licensing & Design Bases. Thomas Koshy, Head Nuclear Power Technology Development Division of Nuclear Power Knowledge Management in Licensing & Design Bases Thomas Koshy, Head Nuclear Power Technology Development Division of Nuclear Power Outline of Presentation 2 Purpose Global Nuclear Safety & Security Framework

More information

Modeling the Instrumentation and Control Systems of Fast Breeder Nuclear Reactor

Modeling the Instrumentation and Control Systems of Fast Breeder Nuclear Reactor Journal on Intelligent Electronic Systems, Vol.1, No.1, November 2007 Modeling the Instrumentation and Control Systems of Fast Breeder Nuclear Reactor Abstract P. Swaminathan Director, Electronics & Instrumentation

More information

Intelligent nuclear power. Your partner for lifetime savings

Intelligent nuclear power. Your partner for lifetime savings Intelligent nuclear power Your partner for lifetime savings More power for longer Our products and services find new ways of improving the availability and efficiency of your power stations. We combine

More information

Internal Flooding According to EPRI Guidelines Detailed Electrical Mapping at Ringhals

Internal Flooding According to EPRI Guidelines Detailed Electrical Mapping at Ringhals Internal Flooding According to EPRI Guidelines Detailed Electrical Mapping at Ringhals Per Nyström a, Carl Sunde a, and Cilla Andersson b a Risk Pilot, Gothenburg, Sweden b Ringhals AB, Varberg, Sweden

More information

Type 9160 / Transmitter supply unit / Isolating repeater. Safety manual

Type 9160 / Transmitter supply unit / Isolating repeater. Safety manual Type 9160 / 9163 Transmitter supply unit / Isolating repeater Safety manual Safety manual English Content 1 General information... 3 1.1 Manufacturer... 3 1.2 Information regarding the Safety Manual...

More information

Digitalization of Nuclear Power Plants at EDF

Digitalization of Nuclear Power Plants at EDF Digitalization of Nuclear Power Plants at EDF Patrick Morilhat Program Director R&D, Nuclear Performance patrick.morilhat@edf.fr January 2018 Disclaimer This presentation is aimed at presenting EDF R&D

More information

USER MANUAL OF THERMAL POWER PLANT (TPP) SIMULATOR SOFTWARE

USER MANUAL OF THERMAL POWER PLANT (TPP) SIMULATOR SOFTWARE USER MANUAL OF THERMAL POWER PLANT (TPP) SIMULATOR SOFTWARE This is the manual for Thermal Power Plant (TPP) Simulator laboratory exercise. The manual consists of useful information about simulator software,

More information

Rosemount Transmitter Diagnostics Reduce Maintenance Costs

Rosemount Transmitter Diagnostics Reduce Maintenance Costs Rosemount Transmitter Diagnostics Reduce Maintenance Costs ROSEMOUNT TRANSMITTER DIAGNOSTICS... Reduce the Necessity of Trips to the Field by 85% Eliminate Ghost Chasing by Checking Transmitter Diagnostics

More information

COMPUTER SECURITY DESIGN METHODOLOGY FOR NUCLEAR FACILITY & PHYSICAL PROTECTION SYSTEMS

COMPUTER SECURITY DESIGN METHODOLOGY FOR NUCLEAR FACILITY & PHYSICAL PROTECTION SYSTEMS NUCLEAR REGULATORY AUTHORITY, GHANA COMPUTER SECURITY DESIGN METHODOLOGY FOR NUCLEAR FACILITY & PHYSICAL PROTECTION SYSTEMS Nelson K. Agbemava ICT and Computer Security Section Head Instrumentation & ICT

More information

IMPROVEMENTS TO MONK & MCBEND ENABLING COUPLING & THE USE OF MONK CALCULATED ISOTOPIC COMPOSITIONS IN SHIELDING & CRITICALITY

IMPROVEMENTS TO MONK & MCBEND ENABLING COUPLING & THE USE OF MONK CALCULATED ISOTOPIC COMPOSITIONS IN SHIELDING & CRITICALITY IMPROVEMENTS TO MONK & MCBEND ENABLING COUPLING & THE USE OF MONK CALCULATED ISOTOPIC COMPOSITIONS IN SHIELDING & CRITICALITY N. Davies, M.J. Armishaw, S.D. Richards and G.P.Dobson Serco Technical Consulting

More information

nuclearsafety.gc.ca Implications of the Fukushima Daiichi Accidents for the New Builds Design Requirements in Canada

nuclearsafety.gc.ca Implications of the Fukushima Daiichi Accidents for the New Builds Design Requirements in Canada Implications of the Fukushima Daiichi Accidents for the New Builds Design Requirements in Canada R.P. Rulko () IAEA Technical Meeting on Evaluation of Nuclear Power Plant Design Safety in the Aftermath

More information

White Paper. The Tricon Turbine Control System

White Paper. The Tricon Turbine Control System White Paper The Tricon Turbine Control System Author: Naresh Desai, Sr. Technical Consultant, Invensys What s Inside: 1. Abstract 2. Introduction 3. Major Requirements 4. Tricon Architecture 5. Critical

More information

BRIDGING THE SAFE AUTOMATION GAP PART 2

BRIDGING THE SAFE AUTOMATION GAP PART 2 BRIDGING THE SAFE AUTOMATION GAP PART 2 Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions Bridging the Safe Automation Gap Part 2, 2002 Instrumentation Symposium, Texas A&M University, College

More information

INSIGHTS ABOUT EMERGENCY DIESEL GENERATOR FAILURES FROM THE USNRC S COMMON CAUSE FAILURE DATABASE

INSIGHTS ABOUT EMERGENCY DIESEL GENERATOR FAILURES FROM THE USNRC S COMMON CAUSE FAILURE DATABASE meqm.m@cd473 NSGHTS ABOUT EMERGENCY DESEL GENERATOR FALURES FROM THE USNRC S COMMON CAUSE FALURE DATABASE Frances M. Marshall daho National Engineering and Environmental Laboratory P. O. BOX 1625 daho

More information

Type Switching repeater. Safety manual

Type Switching repeater. Safety manual Type 9170 Switching repeater Safety manual Safety manual English Content 1 General information... 3 1.1 Manufacturer... 3 1.2 Information regarding the Safety Manual... 3 1.3 Area of application... 3 1.4

More information

OVERVIEW. Invensys Operations Management

OVERVIEW. Invensys Operations Management Invensys Operations Management OVERVIEW 2009 Invensys. All Rights Reserved. The names, logos, and taglines identifying the products and services of Invensys are proprietary marks of Invensys or its subsidiaries.

More information

Deckblatt. APL Operator Guide SIMATIC PCS 7. Application description June Applikationen & Tools. Answers for industry.

Deckblatt. APL Operator Guide SIMATIC PCS 7. Application description June Applikationen & Tools. Answers for industry. Deckblatt SIMATIC PCS 7 Application description June 2011 Applikationen & Tools Answers for industry. Industry Automation and Drive Technologies Service & Support Portal This article is taken from the

More information

Report on Current IAEA I&C Projects For Research Reactors May By Charles R Morris RR Section of NEFW

Report on Current IAEA I&C Projects For Research Reactors May By Charles R Morris RR Section of NEFW Report on Current IAEA I&C Projects For Research Reactors May 2013 By Charles R Morris RR Section of NEFW Personal History The IAEA Research Reactor Section IAEA has 6 main departments with a total of

More information

NNR Regulatory Position on FPGA Based Digital I&C Systems

NNR Regulatory Position on FPGA Based Digital I&C Systems NNR Regulatory Position on FPGA Based Digital I&C Systems Gerard Lekhema National Nuclear Regulator - South Africa 11th International Workshop on Application of FPGAs in Nuclear Power Plants 8 11 October

More information

CORE MONITORING EXPERIENCE WITH GARDEL

CORE MONITORING EXPERIENCE WITH GARDEL CORE MONITORING EXPERIENCE WITH GARDEL Axel Becker, Alejandro Noël Studsvik Scandpower GmbH Studsvik Scandpower Suisse GmbH Abstract The GARDEL core surveillance and analysis system is a standard, modular

More information

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system

Fair City Plaza. Task: Diagnose problems, recommend improvements for small municipal district cooling system Fair City Plaza Task: Diagnose problems, recommend improvements for small municipal district cooling system The Fair City Plaza district cooling system provides chilled water to five buildings in a downtown

More information

An Exterior Communications Interface for the USNRC Consolidated Code

An Exterior Communications Interface for the USNRC Consolidated Code An Exterior Communications Interface for the USNRC Consolidated Code J. Mahaffy 1, C. Murray 2 1 Penn State University, Applied Research Laboratory, P.O. Box 30, State College, PA 16804, USA Tel: 814-863-4018,

More information

M. Middleton, R.E. Williams, Bryan Eyers and Dan Khan NIST Center for Neutron Research TRTR 2016 August 25, 2016

M. Middleton, R.E. Williams, Bryan Eyers and Dan Khan NIST Center for Neutron Research TRTR 2016 August 25, 2016 Lessons Learned using a PLC for Process Control M. Middleton, R.E. Williams, Bryan Eyers and Dan Khan NIST Center for Neutron Research TRTR 2016 August 25, 2016 Lessons Learned using a PLC for Process

More information

Protect Your Device Against Power-Related Damage Understand and Make Best Use of Protection Features in System DC Power Supplies

Protect Your Device Against Power-Related Damage Understand and Make Best Use of Protection Features in System DC Power Supplies Protect Your Device Against Power-Related Damage Understand and Make Best Use of Protection Features in System DC Power Supplies August 20 th, 2014 Edward Brorein Power and Energy Division 1 Agenda The

More information

Mark Bitto / ABB Inc / PSPG / CIBO Technical Focus Group / June Instrumented and Actuated Systems Condition Monitoring of Rotating Equipment

Mark Bitto / ABB Inc / PSPG / CIBO Technical Focus Group / June Instrumented and Actuated Systems Condition Monitoring of Rotating Equipment Mark Bitto / ABB Inc / PSPG / CIBO Technical Focus Group / June 2015 Instrumented and Actuated Systems Condition Monitoring of Rotating Equipment About the speaker Speaker name: Speaker title: Company

More information

Jakob Christensen 23 June 2014 Internal Flooding according to EPRI guidelines Detailed Electrical Mapping at Ringhals Nuclear Power Plant

Jakob Christensen 23 June 2014 Internal Flooding according to EPRI guidelines Detailed Electrical Mapping at Ringhals Nuclear Power Plant Jakob Christensen 23 June 2014 Internal Flooding according to EPRI guidelines Detailed Electrical Mapping at Ringhals Nuclear Power Plant On behalf of paper authors: Per Nyström, Carl Sunde, and Cilla

More information

Kurz Instruments, Inc. MFT B-Series

Kurz Instruments, Inc. MFT B-Series HART Field Device Specification: Kurz Instruments, Inc. MFT B-Series Document 360209-AQ, rev. A Initial release: 30 June 2010 Current release: 30 June 2010 Author: Ruth Ward Kurz Instruments, Inc. 2411

More information

Developing Generic Prior Distributions for Common Cause Failure Alpha Factors

Developing Generic Prior Distributions for Common Cause Failure Alpha Factors Developing Generic Prior Distributions for Common Cause Failure Alpha Factors Zhegang Ma *, John Schroeder, and Curtis Smith Idaho National Laboratory, Idaho Falls, USA Abstract: Common cause failures

More information

Quantum HD Release Notes

Quantum HD Release Notes Quantum HD Release Notes OS Version 10.17 Released 7-14-2014 To upgrade to OS version 10.17 directly the current OS version must be 10.13 through 10.16. To check the current OS version on the Quantum HD

More information

Monitored Analog Safety System. Bob Queenan I&C Manager, Scientech a Curtiss Wright Flow Control company

Monitored Analog Safety System. Bob Queenan I&C Manager, Scientech a Curtiss Wright Flow Control company Monitored Analog Safety System Bob Queenan I&C Manager, Scientech a Curtiss Wright Flow Control company Brief Background I&C Division Manager for Scientech, a CWFC company I&C Manager at DC Cook during

More information

Fast and Easy CWDM Network Assessment, Using ITU-T G.695 application codes

Fast and Easy CWDM Network Assessment, Using ITU-T G.695 application codes Application Note Fast and Easy CWDM Network Assessment, Using ITU-T G.695 application codes MU909020A Network Master Optical Channel Analyzer Introduction Although Coarse wavelength-division multiplexing

More information

Understanding MFC Metrology & Calibration

Understanding MFC Metrology & Calibration Understanding MFC Metrology & Calibration Factors Impacting MFC Performance in Biopharmaceutical Process Systems 1 Understanding MFC Metrology & Calibration Mass flow controllers (MFCs) precisely deliver

More information

The contribution to safety of a diverse backup system for digital safety I&C systems in Nuclear Power Plants, a probabilistic approach

The contribution to safety of a diverse backup system for digital safety I&C systems in Nuclear Power Plants, a probabilistic approach The contribution to safety of a diverse backup system for digital safety I&C systems in Nuclear Power Plants, a probabilistic approach W. Postma a*, J.L. Brinkman a a NRG, Arnhem, the Netherlands Abstract:

More information

Plant Performance 2017 User Symposium

Plant Performance 2017 User Symposium Plant Performance 2017 User Symposium D. C. Cook Reactor Controls and Instrumentation Upgrade 1 February 6, 2017 2014 Curtiss-Wright D. C. Cook Reactor Controls and Instrumentation Upgrade Replacement

More information

Quick Start Installation and User Manual

Quick Start Installation and User Manual 1 Quick Start Installation and User Manual Contents 1. Overview 2. Technical Specifications 3. Installation Mounting Electrical Installation Clamp Installation Wiring Diagrams 4. Installation Settings

More information

FLEX Implementation. Roy Harter RLH Global Services. SAMG-D course, IAEA, Vienna, Austria October

FLEX Implementation. Roy Harter RLH Global Services. SAMG-D course, IAEA, Vienna, Austria October FLEX Implementation Roy Harter RLH Global Services rlharter@aol.com SAMG-D course, IAEA, Vienna, Austria 19-23 October 2015 What is FLEX? US Nuclear Industry Response to NRC Mitigating Strategies Order

More information

Accord Builder. User Guide

Accord Builder. User Guide User Guide Document: V 3.6 User Guide R01 V3.6 User Guide R01 Page 1 of 110 Table of Contents 1 Introduction... 7 2 General Summary and Definitions... 8 2.1 Accord Platform and Plant... 8 2.2 PLC Control

More information

Graphical User Interface Development for the MARS Code

Graphical User Interface Development for the MARS Code GENES4/ANP2003, Sep. 15-19, 2003, Kyoto, JAPAN Paper 1093 Graphical User Interface Development for the MARS Code J.-J. Jeong, M. Hwang, Y. J. Lee, K. D. Kim, B. D. Chung Korea Atomic Energy Research Institute

More information

Improved Situational Awareness with OSIsoft PI for the U.S. Nuclear Regulatory Commission (NRC)

Improved Situational Awareness with OSIsoft PI for the U.S. Nuclear Regulatory Commission (NRC) Improved Situational Awareness with OSIsoft PI for the U.S. Nuclear Regulatory Commission (NRC) Matt McDonald, Vice President April 16, 2015 Agenda About PPC Story of the project OSIsoft PI Solution for

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: PLC Tutorials PLC Ladder Logic : Contacts and coils The most elementary objects in Ladder Diagram programming are contacts and coils, intended to mimic the contacts

More information

Supplemental Information

Supplemental Information Retirement of NPCC Directory# 3 Supplemental Information On April 1, 2015, NPCC Directory# 3 was retired upon the effective date of PRC-005-2 Protection System Maintenance which is subject to a 12 year

More information

POST ALARM ANALYSIS USING ACTIVE CONNECTION

POST ALARM ANALYSIS USING ACTIVE CONNECTION POST ALARM ANALYSIS USING ACTIVE CONNECTION A Thesis submitted to the Division of Research and Advanced Studies of the University of Cincinnati In partial fulfillment of the requirements for the degree

More information

2. Develop guidelines regarding level of detail in system analysis and screening of components, failure modes and dependencies

2. Develop guidelines regarding level of detail in system analysis and screening of components, failure modes and dependencies 1 (7) PROJECT PLAN Project name: Project's short name: Project number: Guidelines for reliability analysis of digital systems in PSA context DIGREL 1 Background and state-of-the-art 2 Objectives Digital

More information

Present Status of Development of the NuScale SMR

Present Status of Development of the NuScale SMR Present Status of Development of the NuScale SMR Innovation for Cool Earth Forum October 10. 2018 Dr. José N. Reyes, Jr. Co-Founder and Chief Technology Officer NuScale Nonproprietary Copyright 2018 NuScale

More information

Cyber Security Requirements for Supply Chain. June 17, 2015

Cyber Security Requirements for Supply Chain. June 17, 2015 Cyber Security Requirements for Supply Chain June 17, 2015 Topics Cyber Threat Legislation and Regulation Nuts and Bolts of NEI 08-09 Nuclear Procurement EPRI Methodology for Procurement Something to think

More information

DEKKER KNOWLEDGE DATABASE KNOWLEDGE IS POWER

DEKKER KNOWLEDGE DATABASE KNOWLEDGE IS POWER DEKKER KNOWLEDGE DATABASE For Use with DEKKER Vacuum Systems Equipped with the DEKKER Controller Each Vmax system is tested and checked at the factory prior to shipment to ensure trouble-free operation.

More information

Instrumentation, Controls, and Automation - Program 68

Instrumentation, Controls, and Automation - Program 68 Instrumentation, Controls, and Automation - Program 68 Program Description Program Overview Power generators need to improve their ability to detect damage to plant equipment while preserving the focus

More information

COBRIX 2 On-line Beverage Analyzer. Anton Paar

COBRIX 2 On-line Beverage Analyzer. Anton Paar COBRIX 2 On-line Beverage Analyzer Anton Paar Introduction Continuous and automatic measurement of Brix, % Diet and carbon dioxide content directly on the soft-drink production line with the new COBRIX

More information

Removal of Hardware ESD, Independent of Safety Logic Solver

Removal of Hardware ESD, Independent of Safety Logic Solver Removal of Hardware ESD, Independent of Safety Logic Solver by Sam Roy Executive summary This is a discussion to remove independent hardware based Emergency Shutdown for Logic Solver as identified in ANSI/ISA-84.00.01-2004,

More information

solid model rotor dynamics

solid model rotor dynamics solid model rotor dynamics A traditional practice in the rotor dynamics analysis is to use beam models for both the lateral and the torsion analysis. Such an analysis limits the capabilities for the modern

More information

The Fukushima accident Consequences for Japan and France

The Fukushima accident Consequences for Japan and France The Fukushima accident Consequences for Japan and France André-Claude Lacoste Chairman of the French Nuclear Safety Authority (ASN) 16 March 2012 16 March 2012 - The Georges Washington University ASN s

More information

Developing Generic Prior Distributions for Common Cause Failure Alpha Factors

Developing Generic Prior Distributions for Common Cause Failure Alpha Factors Developing Generic Prior Distributions for Common Cause Failure Alpha Factors www.inl.gov Zhegang Ma, Ph.D., PE John Schroeder Curtis Smith, Ph.D. Idaho National Laboratory PSAM14, UCLA, Los Angeles, CA

More information

Page 1 MRK-D-0011, V1.1 Aeroqual SM50 User Guide

Page 1 MRK-D-0011, V1.1 Aeroqual SM50 User Guide Page 1 Table of Contents 1. Description... 3 2. Operating Instructions... 3 2.1. Power... 3 2.2. Warm Up... 3 2.3. Input and Output signals... 3 2.3.1. ZERO CAL... 4 2.3.2. RESET... 4 2.3.3. SPAN... 4

More information

TT /12b INSTALLATION INSTRUCTIONS. Introduction

TT /12b INSTALLATION INSTRUCTIONS. Introduction TT-1545 11/12b INSTALLATION INSTRUCTIONS Original Issue Date: 6/10 Model: 20-300 kw Generator Sets Market: Industrial Subject: Decision-Maker 3000 Controller Service Replacement Kit GM75376 Introduction

More information

90F Guy L Warden & Sons Thrush Model 720 4 X 2.5 Flow Guide 90F Guy L Warden & Sons 90F PART 1 GENERAL OVERVIEW Product Scope: SECTION 15 iqpump ENGINEERING SPECIFICATIONS VARIABLE FREQUENCY DRIVES The

More information

INFO GMM EC. Advanced controls system for ECOSS. The New Choice In Evaporative Cooling

INFO GMM EC. Advanced controls system for ECOSS. The New Choice In Evaporative Cooling INFO GMM EC Advanced controls system for ECOSS The New Choice In Evaporative Cooling Intelligence for Heat Exchangers with EC Fans For many years, Güntner Controls has been providing performant, high quality

More information

Athena Series RMC Hot Runner Controller Configuration and Operation Manual

Athena Series RMC Hot Runner Controller Configuration and Operation Manual Athena Series RMC Hot Runner Controller Configuration and Operation Manual Athena and CompuStep are registered trademarks, and Multi-Comm and SafeChange are trademarks of Athena Controls, Inc. MODBUS is

More information

Features. Measuring and Monitoring Relays K8AB Series. Cut by 50% Industry First! Two SPDT Outputs Available in New Models DIN Sized at 22.

Features. Measuring and Monitoring Relays K8AB Series. Cut by 50% Industry First! Two SPDT Outputs Available in New Models DIN Sized at 22. Measuring and Monitoring Relays CSM_K8AB_series_Outline_DS_E_3_2 Industry First! Two SPDT Outputs Available in New Models DIN Sized at 22.5 mm Eight slim models featuring a variety of innovative new functions.

More information

Operating Plants Data Sources for Consideration in Long Term Operation

Operating Plants Data Sources for Consideration in Long Term Operation Operating Plants Data Sources for Consideration in Long Term Operation Jerry Head Chicago, IL June, 2016 GEH Proprietary Information Class II Long Term Operation Beyond 60 Years LTO in the US has multiple

More information

Failure Modes Taxonomy: Assessing the Reliability of FPGA-Based I&C Systems

Failure Modes Taxonomy: Assessing the Reliability of FPGA-Based I&C Systems Failure Modes Taxonomy: Assessing the Reliability of FPGA-Based I&C Systems 9 th International Workshop on the Application of FPGA s in NPP s October 3-6, 2016 Lyon, France P. McNelles, Z.C. Zeng, G. Renganathan,

More information

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA SELECTION AND APPLICATIONS OF PROGRAMMABLE LOGIC CONTROLLERS UNIT 25 - NQF LEVEL 3 OUTCOME 2 - PROGRAMMING

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA SELECTION AND APPLICATIONS OF PROGRAMMABLE LOGIC CONTROLLERS UNIT 25 - NQF LEVEL 3 OUTCOME 2 - PROGRAMMING EDEXCEL NATIONAL CERTIFICATE/DIPLOMA SELECTION AND APPLICATIONS OF PROGRAMMABLE LOGIC CONTROLLERS UNIT 25 - NQF LEVEL 3 OUTCOME 2 - PROGRAMMING CONTENT Be able to use programming techniques to produce

More information

MEASURING AND MONITORING RELAYS

MEASURING AND MONITORING RELAYS MEASURING AND MITORING RELAYS Slim Models for Monitoring Current and Voltage NEW Measuring and Monitoring Relays Measuring and Monitoring Relays K8AB Industry First! Measuring and Monitoring Relays Two

More information

High Motor Current Shutdown High Motor Current Warning Low Motor Current Shutdown Compressor Auxiliary Shutdown

High Motor Current Shutdown High Motor Current Warning Low Motor Current Shutdown Compressor Auxiliary Shutdown Important: To upgrade from Quantum HD version 10.21 or earlier to Quantum HD Unity version 10.30 or later requires the flashcard to be changed. These are available through the Baltimore Parts Center, part

More information

DeltaV SIS TM. Logic Solver. DeltaV SIS Logic Solver. Introduction. DeltaV SIS Product Data Sheet. World s first smart SIS Logic Solver

DeltaV SIS TM. Logic Solver. DeltaV SIS Logic Solver. Introduction. DeltaV SIS Product Data Sheet. World s first smart SIS Logic Solver February 2016 Page 1 DeltaV SIS TM Logic Solver The DeltaV SIS platform is the world s smart SIS system to use the power of predictive intelligence for increasing the availability of the entire safety

More information

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of

More information

Coke Drum MOV PLC Permissive Interlock System Availability

Coke Drum MOV PLC Permissive Interlock System Availability Coke Drum MOV PLC Permissive Interlock System Availability Presented by Mitch Moloney of ExxonMobil Research & Engineering mitchell.j.moloney@exxonmobil.com @ Mumbai coking.com October-2016 a This material

More information

Hardware Safety Integrity. Hardware Safety Design Life-Cycle

Hardware Safety Integrity. Hardware Safety Design Life-Cycle Hardware Safety Integrity Architecture esign and Safety Assessment of Safety Instrumented Systems Budapest University of Technology and Economics epartment of Measurement and Information Systems Hardware

More information

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA SST7000 SST7100. Speed Switch / Transmitter 5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL 33309 3211 Fruitland Ave Los Angeles, CA 90058 SST7000 SST7100 Speed Switch / Transmitter Installation and Operation Manual Rev. C P/N145F-13112 PCO 00009270

More information

ED17: Architectures for Process Safety Applications

ED17: Architectures for Process Safety Applications ED17: Architectures for Process Safety Applications Name Pete Skipp Title Process Safety Architect Date November 5 th & 6 th 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. Agenda An

More information

3500 ENCORE System Overview Bently Nevada* Asset Condition Monitoring

3500 ENCORE System Overview Bently Nevada* Asset Condition Monitoring 3500 ENCORE System Overview Bently Nevada* Asset Condition Monitoring Description The 3500 ENCORE System provides continuous, online monitoring suitable for machinery protection applications and is designed

More information

SERPENT Cross Section Generation for the RBWR

SERPENT Cross Section Generation for the RBWR SERPENT Cross Section Generation for the RBWR Andrew Hall Thomas Downar 9/19/2012 Outline RBWR Motivation and Design Why use Serpent Cross Sections? Modeling the RBWR Generating an Equilibrium Cycle RBWR

More information

HART COMMUNICATION. A Digital Upgrade For Existing Plants

HART COMMUNICATION. A Digital Upgrade For Existing Plants HART COMMUNICATION 1. The majority of smart field devices installed worldwide today are HART-enabled. But some new in the automation field may need a refresher on this powerful technology. Simply put,

More information

Westinghouse Non-Proprietary Class 3. From: Richard W. Rolland III Ext: +1 (860) Our ref: LTR-RAM Fax: +1 (860)

Westinghouse Non-Proprietary Class 3. From: Richard W. Rolland III Ext: +1 (860) Our ref: LTR-RAM Fax: +1 (860) To: File Date: cc: From: Richard W. Rolland III Ext: +1 (860) 731-6447 Fax: +1 (860) 731-4669 Subject: User s Manual for the Tool for Risk-Informed Operations, Version 1.0 This letter constitutes the User

More information

Detector Data Extractor V3.5 User Manual

Detector Data Extractor V3.5 User Manual TDRL, DetectorExtractor V3.5 Manual, Page 1 Detector Data Extractor V3.5 User Manual Provided by Transportation Data Research Laboratory A Division of Northland Advanced Transportation Systems Research

More information

Redundant Governor Control Upgrade for Helms Pumped Storage

Redundant Governor Control Upgrade for Helms Pumped Storage Abstract Redundant Governor Control Upgrade for Helms Pumped Storage By Roger Clarke-Johnson, American Governor Company, Kirkland, WA As part of a major plant upgrade, Pacific Gas & Electric (PG&E) is

More information

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 12/99 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC 1000 and UDC 1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers

More information

Int3233. Soldering Station. Instruction Manual

Int3233. Soldering Station. Instruction Manual Int3233 Soldering Station Instruction Manual Thank you for purchasing the Aoyue int 3233 Soldering Station. Please read the manual before using the unit. Keep manual in accessible place for future reference.

More information

SCADA and Central Applications An introduction

SCADA and Central Applications An introduction SCADA and Central Applications An introduction Course map Outline of the lecture Power System Operation - Centralised Control Applications SCADA - SCADA architecture & Components - SCADA system functions

More information

The Small Modular Reactor

The Small Modular Reactor The Small Modular Reactor September 18, 2018 Presentation to: Southern States Energy Board (SSEB) Nils Breckenridge Regional Sales Manager 1970-1980s U.S Nuclear Technology Dominance France Framatome =

More information

AUTOMATION. Dr. Ibrahim Al-Naimi

AUTOMATION. Dr. Ibrahim Al-Naimi AUTOMATION Dr. Ibrahim Al-Naimi Chapter Three Introduction to Automation Automation Automation is the technology by which a process or procedure is accomplished without human assistance. It is implemented

More information

Front End Engineering and Design (FEED)

Front End Engineering and Design (FEED) Front End Engineering and Design (FEED) Freedom to Choose. Power to Integrate. Yeo Hwee Khoen Honeywell On behalf of Fieldbus Foundation 1 Freedom to Choose. Power to Integrate. FEED Benefits Applying

More information

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Safety Instructions 1-1 Avoid unintended Start General Description 2-2 Contents Contents 1 Safety and precautions 1-1 Safety Instructions 1-1 Avoid unintended Start. 1-1 2 Introduction 2-1 General Description 2-2 3 Supported Configuration 3-1 Introduction 3-1 Fixed-speed

More information

ACT20X-(2)HTI-(2)SAO Temperature/mA converter. Safety Manual

ACT20X-(2)HTI-(2)SAO Temperature/mA converter. Safety Manual ACT20X-(2)HTI-(2)SAO Temperature/mA converter Safety Manual 1.1 Revision history Version Date Change 00 04/2014 First Edition 01 11/2017 Products added 1.2 Validity This manual is valid for the following

More information

UK EPR GDA PROJECT. Name/Initials Date 30/06/2011 Name/Initials Date 30/06/2011. Resolution Plan Revision History

UK EPR GDA PROJECT. Name/Initials Date 30/06/2011 Name/Initials Date 30/06/2011. Resolution Plan Revision History RP unique number: GI-UKEPR-CI-01-RP 0 30/06/2011 1 of 19 Approved for EDF by: A. PETIT Approved for AREVA by: C. WOOLDRIDGE Name/Initials Date 30/06/2011 Name/Initials Date 30/06/2011 Resolution Plan History

More information

AUTOMOBILE APPLICATIONS USING CAN PROTOCOL

AUTOMOBILE APPLICATIONS USING CAN PROTOCOL AUTOMOBILE APPLICATIONS USING CAN PROTOCOL 1 VEERESH B M, 2 JEEVAN C N, 3 MAHESH PATIL 1,2,3 Department of Electronics and Communication, G.S.S.I.T, Bangalore, India Abstract- The main objective of the

More information

Circuit Breaker Sentinel (CBS) for SF 6. power circuit breakers

Circuit Breaker Sentinel (CBS) for SF 6. power circuit breakers Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers Circuit Breaker Sentinel (CBS) for SF 6 power circuit breakers It is widely recognized that the concept of periodic equipment maintenance

More information

Altec Systems Inc 16 Goldpark Court Woodbridge, Ontario L4L 8V5. Monday October 22, 2007 Project Number

Altec Systems Inc 16 Goldpark Court Woodbridge, Ontario L4L 8V5. Monday October 22, 2007 Project Number Altec Systems Inc 16 Goldpark Court Woodbridge, Ontario L4L 8V5 Monday October 22, 2007 Project Number 20070901 S. Areibi School of Engineering University of Guelph Guelph, Ontario N1G 2W1 Subject: Construction

More information

Measuring and Monitoring Relays

Measuring and Monitoring Relays Measuring and Monitoring Relays K8AB Series/61F-D21T Industry First! Two SPDT Outputs Available in New Models DIN Sized at 22.5 mm Seven slim models featuring a variety of innovative new functions. Single-phase

More information

Web- and System-code Based, Interactive, Nuclear Power Plant Simulators. S. Goodwin Ave, Urbana, IL 61801, USA,

Web- and System-code Based, Interactive, Nuclear Power Plant Simulators. S. Goodwin Ave, Urbana, IL 61801, USA, Web- and System-code Based, Interactive, Nuclear Power Plant Simulators Kyung-Doo Kim 1, Prashant Jain and Rizwan-Uddin 2 1 Korea Atomic Energy Research Institute, 150 Dukjin-dong, Yuseong, Taejeon, 305-353,

More information

Defense-in-Depth & Diversity (D3) Charles Kim Electrical and Computer Engineering Howard University

Defense-in-Depth & Diversity (D3) Charles Kim Electrical and Computer Engineering Howard University EECE499-01: Computers and Nuclear Energy Defense-in-Depth & Diversity (D3) Charles Kim Electrical and Computer Engineering Howard University www.mwftr.com 1 Defense in Depth Military Strategy Front Line

More information