Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power

Size: px
Start display at page:

Download "Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power"

Transcription

1 Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power By S G Patki M V Kini P K Jain G T Jawale Presented at: International Conference on Power System Protection, CPRI, Bangalore st February,

2 Overview Introduction Need for Simulation Tool Methodology Adopted for Power System Simulation Salient features of Dynamic test kit Setup of Dynamic test kit Benefits of Analyzing faults using Simulation Tool Two case studies 1. Mal-operation of Protection 2. Non-operation of Protection 2

3 Introduction TPC Inducted Numerical Protection Relays and Fault Disturbance Recorders (FDRs) since early 90s Fault details can be obtained from the Software supplied by FDR Manufacturers. Some software include tools for a) Distance to fault location b) Impedance Locus c) Harmonic analysis, etc Advantage of stand-alone FDR High Sampling Rate for event recording. Therefore, Reproduction of disturbance record captured by Standalone FDR found to be better than the events recorded by Numerical Protection Relay 3

4 Need for Simulation Tool Numerical Protection relays of different makes, types and version can exhibit different behavior during abnormal power system condition Selection of Appropriate relays Routine and Acceptance Testing by conventional methods may not reveal the deficiencies in the relays either due to inherent protection algorithm or due to incorrect adopted configuration / setting 4

5 Methodology Adopted for PS Simulation Analyzing and comparing performance of Numerical relays during dynamic power system condition. Dynamic Simulation tool allows simulation of power system condition as well as replay of captured current and voltage signals from fault disturbance records Computer aided system simulation tool for analysing mal-operation / non-operation of protective relays 5

6 Salient features of Dynamic test kit Can be used without PC (local mode) or with PC Can be used for testing relays based on Voltage, Current and Frequency in local mode However, With PC, few advanced functions such as Replaying of disturbance records, injection of Harmonic voltages / currents, Automatic Relay Testing etc. Attaching a pre-fault waveform to the waveform recorded during fault Selection of CTR / PTR is possible in software depending on 1 / 5 Amp for currents and PT ratio for Voltage Waveform Truncation of waveform to find out the point on the waveform where the relay has operated 6

7 Setup of Dynamic test kit 7

8 Benefits of using Simulation Tool The disturbance records captured by the numerical relays and fault disturbance recorders can be used to simulate the disturbance and play the same on various types of devices Fault library can be maintained and used for evaluating / accepting new relay products Reduction in Cycle Time for acceptance testing of new relays Analysis of the protection performance will help in improving the power system protection and maintaining grid stability 8

9 Case Study I: Mal-operation of Distance Relay 220 kv 220 kv 220 kv G Salsette 220 kv TPCL N/W Kalwa 3 Lines MSETCL Trombay Tata Trombay MSEB N/W 9 Bkrs Tripped 220 kv Trombay Salsette line # 1 / 2 tripped by Distance Protection for fault in reverse direction Details of the Line: Line Length km; CTR 2000/1; PTR 240 kv / 120 V Line Impedance: Z+/- = j 9.428; Zo = +j30.806

10 Case Study I: Mal-operation of Distance Relay Waveform captured by Disturbance Recorder during the fault Waveform Produced by simulation tool for replaying on the relays 10

11 Case Study I: Mal-operation of Distance Relay Protection Provided on Line Main I (Distance), Main II (Distance) and Directional O/C relays During the disturbance Main II relay, which is of switched Distance relay type operated and Main I relay, which is of nonswitched distance relay type did not operate The Fault Disturbance Record captured is replayed on another type of non-switched relays and the relays found to be stable 11

12 Case Study II: Non-operation of Under frequency Relay Under frequency relays at receiving & Generating stations for Load shedding and Islanding Scheme Under frequency relay of Islanding scheme at 110 kv Salsette R/S failed to operate during one of the System Disturbances. However, the fault got isolated by the operation of distance protection Under frequency relay settings: Stage I: 47.6 Hz, 0.15 Sec Stage II: 47.0 Hz, 0.2 Sec During the disturbance, frequency dropped from 50.3 to 46.7 Hz and TPC system islanded from rest of the Grid 12

13 Case Study II: Non-operation of Under frequency Relay Frequency Trend System islanding on 21/09/05 at 0958 hrs Frequency(Hz) df/dt = 2.5 Hz/s df/dt = 0.45 Hz/s s time (s) frequency plot during system disturbance (recorded by frequency trend monitor) 13

14 Case Study II: Non-operation of Under frequency Relay Waveform captured by Disturbance Recorder during the fault Waveform Produced by simulation tool for replaying on the relays 14

15 Case Study II: Non-operation of Under frequency Relay Under frequency relays was of static type self powered relay (Powered by PT Supply) with built-in U/V block at voltage below 70 % of rated voltage Relay operation was getting inhibited due to under voltage condition on 110 kv bus during system disturbance The Waveform was replayed on Numerical Relay on which U/V blocking can be set manually. Initially Numerical relay also did not operate with U/V setting at 70 %. However, by lowering the U/V block setting, the relay operated correctly 15

16 Conclusions Numerical Protection relays of different makes, types and version can exhibit different behavior during abnormal power system condition. Conventional testing of the relays may not reveal the deficiencies in the relays either due to inherent protection algorithm or due to incorrect adopted configuration / setting The disturbance records captured by the numerical relays and fault disturbance recorders can be used to simulate the disturbance and play the same on various types of devices The typical fault records can be preserved as fault library and used for evaluating new relay products Analysis of the protection performance will help in improving the power system protection and hence contribute to grid reliability and stability 16

USE CASE 14 CONTROLLED ISLANDING

USE CASE 14 CONTROLLED ISLANDING I USE CASE 14 CONTROLLED ISLANDING Use Case Title Centralized application separates grid into islands to prevent blackout Use Case Summary Controlled islanding is a method that can significantly improve

More information

Using the Bitronics 70 Series to Improve Local Monitoring and Control

Using the Bitronics 70 Series to Improve Local Monitoring and Control Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application

More information

RecordGraph. v5.3. Release Description

RecordGraph. v5.3. Release Description RecordGraph v5.3 Release Description FEATURE ENHANCEMENTS Export a single COMTRADE file with all measured and derived channels. L-PRO 4500: Added support for the following analog input product variants:

More information

Implementation of Online ABT monitoring System In The TATA Power Co. Ltd. Mumbai. S. G. Patki, S. C. Dhapre, S. G. Joshi, S. A.

Implementation of Online ABT monitoring System In The TATA Power Co. Ltd. Mumbai. S. G. Patki, S. C. Dhapre, S. G. Joshi, S. A. 1 Implementation of Online ABT monitoring System In The TATA Power Co. Ltd. Mumbai S. G. Patki, S. C. Dhapre, S. G. Joshi, S. A. Wangade 2 Topics Discussed Metering system between TPC & MSETCL. Need for

More information

Bus Protection Application Challenges

Bus Protection Application Challenges Bus Protection Application Challenges KN Dinesh Babu - Megger JC Theron, Lubomir Sevov GE Grid Solutions 2017 Texas A&M Protective Relay Conference Content Introduction Application Challenges Increase

More information

Aurora Vulnerability Mitigation Techniques using UR Technology

Aurora Vulnerability Mitigation Techniques using UR Technology Technical Note Aurora Vulnerability Mitigation Techniques using UR Technology GE Publication Number: GET-20039 Copyright 2015 GE Inc. 1. Introduction The US Department of Energy s Idaho laboratory had

More information

Advanced Features. High Performance Stepper Drive Description. Self Test and Auto Setup

Advanced Features. High Performance Stepper Drive Description. Self Test and Auto Setup www.applied-motion.com STAC6 High Performance Stepper Drive Description The STAC6 represents the latest developments in stepper drive technology, incorporating features that will derive the highest performance

More information

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU

SOUTHERN REGIONAL POWER COMMITTEE BENGALURU SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Additional Agenda for the 80 th Meeting of Protection Coordination Sub-Committee of SRPC to be held on 20-21 December, 2018 1. Grid Occurrences Additional Grid

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee

More information

Implementing the protection and control of future DC Grids

Implementing the protection and control of future DC Grids Implementing the protection and control of future DC Grids Hengxu Ha, Sankara Subramanian Innovation and Technology Department, SAS, Alstom Grid 1. The challenge of the DC Grid protection 1 High speed

More information

PG&E Transmission Interconnection Handbook

PG&E Transmission Interconnection Handbook Table of Contents TABLE OF CONTENTS... 1 UPDATE HISTORY... UP-1 INTRODUCTION... IN-1 I-1. PURPOSE... IN-1 I-2. INTRODUCTORY DEFINITIONS... IN-1 I-3. HANDBOOK APPLICABILITY... IN-2 I-3.1. New Load, New

More information

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems

An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems By Eng. Sameh Moustafa Mohamed Abd Elgowad Elbana A thesis submitted to The Faculty

More information

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.

SR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators. SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering

More information

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68 The Challenges and Opportunities Faced by Utilities using Modern Protection and Control Systems - Paper Unavailable Trends in Protection and Substation Automation Systems and Feed-backs from CIGRE Activities

More information

PROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY S.E.P TRAINING CENTRE

PROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY S.E.P TRAINING CENTRE PROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY INDEX CHAPTER 1: 1. INTERFACING PC WITH RELAY 2. EXTRACTING SETTINGS FROM THE RELAY CHAPTER 2: 1. SETTING VALUES AS PER

More information

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India

Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India SCADA in Transmission Line Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India ABSTRACT: Transmission line equivalent circuit parameters are often 25%

More information

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation: DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated

More information

Testing of Real Time Power System Control Software

Testing of Real Time Power System Control Software Testing of Real Time Power System Control Software Transpower s Pole 3 Project Presentation to Special Interest Group of ANZTB 7 October 2013 Richard Sherry 1 Summary 1. What does the HVDC Control System

More information

SDG&E s Accomplishments and Future Plans

SDG&E s Accomplishments and Future Plans SDG&E s Accomplishments and Future Plans Tariq Raman and Subbu Sankaran San Diego Gas & Electric Work Group Meeting October 23-24, 2018 San Diego Gas & Electric San Francisco SDG&E Los Angeles San Diego

More information

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation

Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation 111 Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation Z. Gajić (ABB, Sweden) JP Wang / PW Gong / YS Xu (ABB China) ZX Zhou (CERPI, China) Summary Power utilities

More information

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy

Reyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy Reyrolle Protection Devices 7SG118 Argus 8 Voltage & Frequency Relay Answers for energy 7SG118 Argus 8 Voltage and Frequency Relay Data Storage and Communication Serial communications conform to IEC60870-5-103

More information

POWER METER HC Features

POWER METER HC Features Introduction The power quality meter HC 6030 is an ideal device to power monitoring in power quality when continuous monitoring to a power system is required. The HC 6030 provides metering for current,

More information

Busbar protection REB 670

Busbar protection REB 670 Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features

More information

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application

DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and

More information

Load Flow Analysis. I Objectives

Load Flow Analysis. I Objectives EE342 Electrical Power Lab Experiment PS3 Load Flow Analysis I Objectives To demonstrate load flow concepts. To study system performance under different operating conditions. To experience the real feel

More information

Lowering Lifecycle Costs

Lowering Lifecycle Costs Lowering Lifecycle Costs with Intelligent Motor Control Centers Standards Certification Education & Training Publishing Conferences & Exhibits Speakers: Presented and Authored by Jeff M. Miller, PE, ENV

More information

KILOVAC WD Series, DIN Rail or Screw Mounted Protective Relays

KILOVAC WD Series, DIN Rail or Screw Mounted Protective Relays KILOVAC WD Series, DIN Rail or Screw Mounted Protective Relays n WD25 Paralleling (Synch Check) Relays n WD2759 Over/undervoltage Relays n WD32 Reverse Power Relays n WD47 Phase Sequence Relays n WD5051

More information

URC Utility Relay Company

URC Utility Relay Company communications i-comm modbus / rs-485 AC-PRO Communicating Trip Units instruction manual ZERO-Hertz Communicating Trip Units URC Utility Relay Company Chagrin Falls, OH 44023 Phone: 888.289.2864 www.utilityrelay.com

More information

We will discuss two types of loss-of-potential (LOP) logic during this presentation:

We will discuss two types of loss-of-potential (LOP) logic during this presentation: 1 We will discuss two types of loss-of-potential (LOP) logic during this presentation: Traditional LOP, which uses traditional voltage and current elements to detect an LOP condition. Advanced LOP, which

More information

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection

i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing

More information

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online): 2321-0613 Comparison of Shunt Facts Devices for the Improvement of Transient Stability of Two Machine

More information

Short-Circuit Calculation Methods

Short-Circuit Calculation Methods Short-Circuit Calculation Methods Oct 1, 2004 12:00 PM, By Massimo Mitolo, Ph.D., Chu & Gassman Consulting Engineers Ref.: http:// ecmweb.com/mag/electric_shortcircuit_calculation_methods/ The task may

More information

Lessons Learned Implementing an IEC based Microgrid Power- Management System. K.A. GRAY, J.J. MRAZ* POWER Engineers, Inc.

Lessons Learned Implementing an IEC based Microgrid Power- Management System. K.A. GRAY, J.J. MRAZ* POWER Engineers, Inc. 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Lessons Learned Implementing an IEC 61850-based Microgrid Power- Management System K.A.

More information

Power System Monitoring Recorder TESLA 3000

Power System Monitoring Recorder TESLA 3000 Power System Monitoring Recorder TESLA 3000 Product Overview TESLA 3000 is an easy-to-use and cost-effective, stateof-the-art, multi-time frame (simultaneous) power system recording monitor. The optional

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft

More information

USE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION

USE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION H USE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION Use Case Title Adaptive Transmission Line Protection Use Case Summary The requirements for improvement in the performance of protection relays under

More information

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI

Automation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Automation in Large Urban Power Distribution System Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Need for Automation and Current trends Automation Systems and Functionality

More information

High impedance protection relay

High impedance protection relay High impedance protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features High impedance type differential current earth-fault protection, so called restricted

More information

B5-111 APPLICATION OF INTRANET TECHNOLOGIES FOR POWER SYSTEM PROTECTION

B5-111 APPLICATION OF INTRANET TECHNOLOGIES FOR POWER SYSTEM PROTECTION 21, rue d'artois, F-75008 Paris http://www.cigre.org B5-111 Session 2004 CIGRÉ APPLICATION OF INTRANET TECHNOLOGIES FOR POWER SYSTEM PROTECTION A. TAKEUCHI F. KUMURA M. NAKAHARA Chubu Electric Power Co.

More information

About Georgia Transmission Corporation (GTC)

About Georgia Transmission Corporation (GTC) About Georgia Transmission Corporation (GTC) Transmission-only, not-for-profit cooperative Formed in March 1997 from the restructuring of Oglethorpe Power Corporation (OPC) GTC provides network transmission

More information

Table of Issues and Directives Project Relay Loadability: Stable Power Swings

Table of Issues and Directives Project Relay Loadability: Stable Power Swings Table of Issues and Directives Project 2010-13.3 Relay Loadability: Stable Power Swings FERC Order 733 150. We will not direct the ERO to modify PRC-023-1 to address stable power swings. However, because

More information

SDG&E s EPIC Demonstration Projects on Emerging Communication Standards. IEC Europe 2017 Conference. Frank Goodman, SDG&E EPIC Program Manager

SDG&E s EPIC Demonstration Projects on Emerging Communication Standards. IEC Europe 2017 Conference. Frank Goodman, SDG&E EPIC Program Manager SDG&E s EPIC Demonstration Projects on Emerging Communication Standards Frank Goodman, SDG&E EPIC Program Manager IEC 61850 Europe 2017 Conference September 26-28, 2017 2017 San Diego Gas & Electric Company.

More information

PFC-10 Power Factor Controller

PFC-10 Power Factor Controller PFC-10 Power Factor Controller Instruction Manual Ver. 6.0 / 2002 (2-2005 update) Table of Contents Page Subject 3 Starter ion 4-5 Installation Notes 6-7 Terminals Review & Control Wiring 8 Front-panel

More information

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching

7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching 7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that

More information

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators

NewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators NewCode Comprehensive Motor Protection and Control Relay Relay Field Input and Output LEDs LED Fault Indicators Configurable Memory Module on a T-Bus IrDA and USB Connectors Profibus Address Indicator

More information

4-W HDSL/56Kbps Isolation Card With 130/190V Span Powering. Description & Installation P30140

4-W HDSL/56Kbps Isolation Card With 130/190V Span Powering. Description & Installation P30140 4-W HDSL/56Kbps Isolation Card With 130/190V Span Powering Description & Installation P30140 Printed in USA 11/12 TO506 Rev. A Table of Contents 1.0 PRODUCT SCOPE 3 2.0 PRODUCT OVERVIEW 3 2.1 System Requirements

More information

Advanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA

Advanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Advanced Fuse-Saving Techniques T. ROUSAN Ameren Illinois USA J. JERMAKOWICZ S&C Electric

More information

GE Power Management. MMII Intelligent MCC Controller

GE Power Management. MMII Intelligent MCC Controller A concept that will offer reduced overall installed cost and production efficiency through information availability to operators and maintenance. Presentation Overview 6 Applications 6 Protection and Control

More information

AP SERIES SYSTEMS POWER SUPPLIES. Autoranging power supplies for bench or systems use FEATURES

AP SERIES SYSTEMS POWER SUPPLIES. Autoranging power supplies for bench or systems use FEATURES AP SERIES Autoranging power supplies for bench or systems use The AP series power supplies utilise an autoranging concept and can provide a wide and adjustable range of voltage and current combinations

More information

An expert solution is within your reach. EORSys. We take care of it.

An expert solution is within your reach. EORSys. We take care of it. We take care of it. EORSys An expert solution is within your reach. System solution for compensated, isolated and solidly grounded grids Precise control of arc suppression coils Reliable locating of earth

More information

A Case for Multi-Function PMU

A Case for Multi-Function PMU A Case for Multi-Function PMU Harish I. Mehta Mehta Tech, Inc. www.mehtatech.com NASPI Chattanooga, TN Meeting PMU Definition PMU is generally defined as: IEEE C37.118 compliant device Time synchronized

More information

Commission Testing Methods for Protection Systems

Commission Testing Methods for Protection Systems Commission Testing Methods for Protection Systems Tom Ernst GE Grid Solutions Ken Sletten Minnesota Power Abstract Commission testing should be designed to assure that the protection system is set and

More information

Smart Power Flow Monitoring and Control

Smart Power Flow Monitoring and Control IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 10 April 2016 ISSN (online): 2349-784X John Richardson. J Mathivathani. N Karthikeyan. K Preethi. PA Vivekanandhan. C Vice

More information

ABB Data Center Forum 2017

ABB Data Center Forum 2017 ABB DATA CENTER FORUM 2017, 11 TH JULY 2017 ABB Data Center Forum 2017 Perfecting Data Center availability with Ultra-Fast Protection Devices Barbara Schlegel ABB DATA CENTER FORUM 2017, 11 TH JULY 2017

More information

High Impedance Protection Relay SPAE010, SPAE011. Product Guide

High Impedance Protection Relay SPAE010, SPAE011. Product Guide SPAE010, SPAE011 SPAE010, SPAE011 1MRS750383-MBG Issued: April 1999 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features High impedance type differential current earth-fault

More information

CASE STUDY : Transient Stability Simulation Package

CASE STUDY : Transient Stability Simulation Package CASE STUDY : Transient Stability Simulation Package CLIENT NAME : A major T&D solutions provider in the world END CUSTOMER : A public T&D utility in one of the SAARC nations PROJECT TITLE : Customized

More information

e 2 TANGO -400 Overcurrent Relay K Catalogue EN

e 2 TANGO -400 Overcurrent Relay K Catalogue EN e 2 TANGO -400 Overcurrent Relay K-33.1.3 Catalogue EN We Create Ideas With Power! e 2 TANGO-400 protection relay is a solution developed by ELEKTROMETAL ENERGETYKA SA R&D department consisting of engineers

More information

Auto-Changeover & Feeder Automation. Reclosers & Sectionalizers

Auto-Changeover & Feeder Automation. Reclosers & Sectionalizers Auto-Changeover & Feeder Automation Reclosers & Sectionalizers WHY AUTOMATE? COMPETITION SERVICE VALUE QUALITY RELIABILITY REGULATION RATES BASED ON RELIABITY & PERFORMANCE PENALTIES REGULATION SAIDI (System

More information

Bus Bar Protection Relay B-PRO 4000

Bus Bar Protection Relay B-PRO 4000 Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation

More information

Power Test Equipment

Power Test Equipment Power Test Equipment for the global power industry T&R Test Equipment design and manufacture high quality test equipment for the power industry. Our equipment is used world-wide in transmission and distribution,

More information

PUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System

PUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System PUBLIC SERVICE OF NEW HAMPSHIRE Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System September 2013 1.0 Purpose of this document Public Service of New Hampshire

More information

RT4F-120V/20A-WAC RECTIFIER

RT4F-120V/20A-WAC RECTIFIER The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with

More information

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field

DTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,

More information

LE ELECTRONICS Pvt. Ltd.

LE ELECTRONICS Pvt. Ltd. LE ELECTRONICS Pvt. Ltd. Monitoring Relays: LVM Line Voltage Monitors LCM - Line Current Monitors VMR Voltage Monitoring Relays CMR Current Monitoring Relays VCMR Voltage Current Monitoring Relays LFM

More information

DS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation /

DS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation   / 5kA rms - 8kA DC Fluxgate current transducer Features DC 8000A AC 5000A rms Maximum gain error DC to 1kHz - 0.1% Transducer core optimized for high level of immunity against external magnetic fields Operating

More information

Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600

Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600 Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600 Contents COM600 Product Overview Business Overview Product News Overview June 12-14, 2012 Slide

More information

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts. Binary Output 23BO62 Characteristics The binary output is made via relay contacts. The 8 outputs are potential isolated against the electronic by optocoupler. All 8 outputs have a separate return. Application

More information

2C138. Sensitive Earth Fault Relay. Features. Application. Operation

2C138. Sensitive Earth Fault Relay. Features. Application. Operation Technical Bulletin 2C138 Sensitive Earth Fault Relay Features High sensitivity (0.1% of I n ) 2 nd & 3rd harmonic & HF noise suppression - tuned to 50 Hz Optional reset functions Instantaneous (Fast),

More information

SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD

SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD Tejpal P. Purohit 1, Prashant K. Bhavsar 2 Department of Electrical Engineering, Government Polytechnic Palanpur,

More information

BRC SERIES 20kW High Voltage Power Supply

BRC SERIES 20kW High Voltage Power Supply BRC SERIES 20kW High Voltage Power Supply Description UNIPOWER s line of BRC switching power supplies are notable for low ripple, fast transient response, endurance to repetitive arcing and stable output

More information

Power System Monitoring Recorder

Power System Monitoring Recorder Power System Monitoring Recorder TESLA 4000 Model 4000 Model 4003 Product Overview TESLA 4000 is an easy-to-use and cost effective, state of the art, multi-time frame (simultaneous) power system monitoring

More information

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016

SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:

More information

Date of Publication: THREE PHASE LINE FAULT DETECTION ON DISTRIBUTION LINES USING GSM TECHNIQUE

Date of Publication: THREE PHASE LINE FAULT DETECTION ON DISTRIBUTION LINES USING GSM TECHNIQUE International Journal of Emerging Technology and Innovative Volume 2, Issue 3, March 2016 (ISSN: 2394 6598) Date of Publication: 29.03.2016 THREE PHASE LINE FAULT DETECTION ON DISTRIBUTION LINES USING

More information

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field

DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description

More information

Transient Stability Analysis with PowerWorld Simulator

Transient Stability Analysis with PowerWorld Simulator Transient Stability Analysis with PowerWorld Simulator T14: Large-Scale Simulation Examples 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com

More information

STAC5 Stepper Drives. A high performance, compact and cost-effective stepper drive with advanced features and control options

STAC5 Stepper Drives. A high performance, compact and cost-effective stepper drive with advanced features and control options STAC5 Stepper Drives A high performance, compact and cost-effective stepper drive with advanced features and control options Ethernet & EtherNet/IP Advanced Current Control Anti-Resonance Torque Ripple

More information

UR Plus Series. Revision 1.73 Release Notes. GE Digital Energy. Overview. GE Publication Number: GER Summary. Copyright 2013 GE Multilin Inc.

UR Plus Series. Revision 1.73 Release Notes. GE Digital Energy. Overview. GE Publication Number: GER Summary. Copyright 2013 GE Multilin Inc. G Digital nergy UR Plus Series Revision 1.73 Release Notes G Publication Number: GR-4372 Copyright 2013 G Multilin Inc. Overview Summary Release 1.73 of the UR Plus series introduces product-specific and

More information

High-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY

High-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY S&C Remote Supervisory V ista Outdoor Distribution (15.5 kv through 38 kv) Electric utility customers are increasingly concerned about the frequency and duration of outages they are experiencing, and are

More information

Miniature. Circuit Breakers. reliable solutions for protection of installations against over-current phenomenon. Advantages for you : Technical data :

Miniature. Circuit Breakers. reliable solutions for protection of installations against over-current phenomenon. Advantages for you : Technical data : Miniature Circuit Breakers reliable solutions for protection of installations against over-current phenomenon Advantages for you : Bi-connect terminals for simultaneous termination of bus bar & wires Unique

More information

TM241CE40R controller M IO relay Ethernet

TM241CE40R controller M IO relay Ethernet Characteristics controller M241 40 IO relay Ethernet Main Range of product Product or component type [Us] rated supply voltage Mar 09, 2017 Modicon M241 Logic controller 100...240 V AC Discrete input number

More information

Programozható, nagyteljesítményű AC tápegység, SP300VAC-2000W

Programozható, nagyteljesítményű AC tápegység, SP300VAC-2000W is a switching mode single-channel output high-precision programmable AC power source, which adopts high speed DSP+CPLD control, high frequency PWM power technology and active PFC design to realize AC/DC

More information

ELG4125: System Protection

ELG4125: System Protection ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.

More information

SED2 Variable Frequency Drives

SED2 Variable Frequency Drives SED2 Variable requency Drives Description The SED2 variable frequency drives are designed specifically for HVA applications. The SED2 supports a wide variety of digital and analog I/O for diverse control

More information

www. ElectricalPartManuals. com .Basler Electric BE1-878 HIGH IMPEDANCE BUS DIFFERENTIAL RELAY ADVANTAGES ADDITIONAL INFORMATION APPLICATION Page2

www. ElectricalPartManuals. com .Basler Electric BE1-878 HIGH IMPEDANCE BUS DIFFERENTIAL RELAY ADVANTAGES ADDITIONAL INFORMATION APPLICATION Page2 The Bus Differential Relay provides economical high speed protection in a conventional package for all high impedance differential applications. ADVANTAGES Proven performance of High Impedance Differential

More information

Dynamic State Estimation Based Protection: Laboratory Validation

Dynamic State Estimation Based Protection: Laboratory Validation Dynamic State Estimation Based Protection: Laboratory Validation Paul Myrda - EPRI & A.P. Meliopoulos and G. J. Cokkinides - Georgia Tech October 21, 2014, Houston, TX Contents Background and Motivation

More information

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors

D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors Ron Boe 5/15/2014 This user guide details the servo drives capabilities and physical interfaces. Users will be able to

More information

Power System Resilience & Reliability. Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 28, 2017

Power System Resilience & Reliability. Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 28, 2017 Power System Resilience & Reliability Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 28, 2017 NERC, Reliability, & Resilience NERC has addressed reliability

More information

UR Universal Relay Series

UR Universal Relay Series GE Digital Energy UR Universal Relay Series Revision 4.43 Release Notes GE Publication Number: GER-4380Rev1 Copyright 2010 GE Multilin Summary Overview GE Multilin issues the UR 4.43 release that introduces

More information

TM241CE40R controller M IO relay Ethernet

TM241CE40R controller M IO relay Ethernet Characteristics controller M241 40 IO relay Ethernet Main Range of product Product or component type [Us] rated supply voltage Apr 10, 2018 Modicon M241 Logic controller 100...240 V AC Discrete input number

More information

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5

SPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5 Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System

More information

ASPEN Software - Introduction

ASPEN Software - Introduction ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical

More information

An adaptive limited wide area differential protection for power grid with microsources

An adaptive limited wide area differential protection for power grid with microsources Wu Protection and Control of Modern Power Systems (2017) 2:21 DOI 10.1186/s41601-017-0052-2 Protection and Control of Modern Power Systems ORIGINAL RESEARCH An adaptive limited wide area differential protection

More information

Opal Pro to DeviceNet. Opal Pro MS6 SERIES. DeviceNet Interface Users Manual. Revision Page 1

Opal Pro to DeviceNet. Opal Pro MS6 SERIES. DeviceNet Interface Users Manual. Revision Page 1 Opal Pro MS6 SERIES DeviceNet Interface Users Manual Revision 1.01 Page 1 Page 2 FOR YOUR SAFETY Only qualified personnel should install this equipment, after first reading and understanding all the information

More information

Impulse Generator Digital Control & Measuring System

Impulse Generator Digital Control & Measuring System Impulse Generator Digital Control & Measuring System HCS2000A Digital Control System Item Qty. Description 6 1 Control system parameter: Charging voltage: Setting range 0~100.0kV Operating space 10.0~100.0kV

More information

RT4B-110V/12A RECTIFIER

RT4B-110V/12A RECTIFIER The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs

More information

SEL Event Report Frequently Asked Questions

SEL Event Report Frequently Asked Questions Event Analysis Introduction Session SEL Event Report Frequently Asked Questions 1. How is an event report generated by an SEL relay? A. Relay trip from trip equation (TR). Example 1: TR := 49T OR 50P1T

More information

Applying Intelligent Fast Load Shed Using IEC GOOSE

Applying Intelligent Fast Load Shed Using IEC GOOSE Applying Intelligent Fast Load Shed Using IEC 61850 GOOSE JC Theron, Steven Rowe GE Grid Solutions Troy Wilsey, Anthony Colonnese Ameresco Russell Gagner Civilian Naval Facilities Engineering Command 71

More information

TM241C24R. Main. Discrete output type. Discrete output number. 14 (remote I/O architecture) 50 µs turn-on operation with I0...I13 terminal(s) input

TM241C24R. Main. Discrete output type. Discrete output number. 14 (remote I/O architecture) 50 µs turn-on operation with I0...I13 terminal(s) input Product datasheet Characteristics TM241C24R Complementary Discrete I/O number 24 Number of I/O expansion module Supply voltage limits Network frequency Discrete input logic Discrete input voltage Discrete

More information

Distributed by. Keor T UPS THREE-PHASE UPS. from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Distributed by. Keor T UPS THREE-PHASE UPS. from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES Distributed by Keor T UPS THREE-PHASE UPS from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES T THREE-PHASE UPS T has been designed with advanced technologies and the

More information

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options

DEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options Description of options Option A and B, Loss of mains protection package Automatic Gen-set controller 4189340394B SW 2.3X.X Description of options Functional descriptions DEIF A/S Parameter list DEIF A/S,

More information