1 Simulation of Power System Faults for Protection Performance Analysis -Case Studies of Tata Power By S G Patki M V Kini P K Jain G T Jawale Presented at: International Conference on Power System Protection, CPRI, Bangalore st February,
2 Overview Introduction Need for Simulation Tool Methodology Adopted for Power System Simulation Salient features of Dynamic test kit Setup of Dynamic test kit Benefits of Analyzing faults using Simulation Tool Two case studies 1. Mal-operation of Protection 2. Non-operation of Protection 2
3 Introduction TPC Inducted Numerical Protection Relays and Fault Disturbance Recorders (FDRs) since early 90s Fault details can be obtained from the Software supplied by FDR Manufacturers. Some software include tools for a) Distance to fault location b) Impedance Locus c) Harmonic analysis, etc Advantage of stand-alone FDR High Sampling Rate for event recording. Therefore, Reproduction of disturbance record captured by Standalone FDR found to be better than the events recorded by Numerical Protection Relay 3
4 Need for Simulation Tool Numerical Protection relays of different makes, types and version can exhibit different behavior during abnormal power system condition Selection of Appropriate relays Routine and Acceptance Testing by conventional methods may not reveal the deficiencies in the relays either due to inherent protection algorithm or due to incorrect adopted configuration / setting 4
5 Methodology Adopted for PS Simulation Analyzing and comparing performance of Numerical relays during dynamic power system condition. Dynamic Simulation tool allows simulation of power system condition as well as replay of captured current and voltage signals from fault disturbance records Computer aided system simulation tool for analysing mal-operation / non-operation of protective relays 5
6 Salient features of Dynamic test kit Can be used without PC (local mode) or with PC Can be used for testing relays based on Voltage, Current and Frequency in local mode However, With PC, few advanced functions such as Replaying of disturbance records, injection of Harmonic voltages / currents, Automatic Relay Testing etc. Attaching a pre-fault waveform to the waveform recorded during fault Selection of CTR / PTR is possible in software depending on 1 / 5 Amp for currents and PT ratio for Voltage Waveform Truncation of waveform to find out the point on the waveform where the relay has operated 6
7 Setup of Dynamic test kit 7
8 Benefits of using Simulation Tool The disturbance records captured by the numerical relays and fault disturbance recorders can be used to simulate the disturbance and play the same on various types of devices Fault library can be maintained and used for evaluating / accepting new relay products Reduction in Cycle Time for acceptance testing of new relays Analysis of the protection performance will help in improving the power system protection and maintaining grid stability 8
9 Case Study I: Mal-operation of Distance Relay 220 kv 220 kv 220 kv G Salsette 220 kv TPCL N/W Kalwa 3 Lines MSETCL Trombay Tata Trombay MSEB N/W 9 Bkrs Tripped 220 kv Trombay Salsette line # 1 / 2 tripped by Distance Protection for fault in reverse direction Details of the Line: Line Length km; CTR 2000/1; PTR 240 kv / 120 V Line Impedance: Z+/- = j 9.428; Zo = +j30.806
10 Case Study I: Mal-operation of Distance Relay Waveform captured by Disturbance Recorder during the fault Waveform Produced by simulation tool for replaying on the relays 10
11 Case Study I: Mal-operation of Distance Relay Protection Provided on Line Main I (Distance), Main II (Distance) and Directional O/C relays During the disturbance Main II relay, which is of switched Distance relay type operated and Main I relay, which is of nonswitched distance relay type did not operate The Fault Disturbance Record captured is replayed on another type of non-switched relays and the relays found to be stable 11
12 Case Study II: Non-operation of Under frequency Relay Under frequency relays at receiving & Generating stations for Load shedding and Islanding Scheme Under frequency relay of Islanding scheme at 110 kv Salsette R/S failed to operate during one of the System Disturbances. However, the fault got isolated by the operation of distance protection Under frequency relay settings: Stage I: 47.6 Hz, 0.15 Sec Stage II: 47.0 Hz, 0.2 Sec During the disturbance, frequency dropped from 50.3 to 46.7 Hz and TPC system islanded from rest of the Grid 12
13 Case Study II: Non-operation of Under frequency Relay Frequency Trend System islanding on 21/09/05 at 0958 hrs Frequency(Hz) df/dt = 2.5 Hz/s df/dt = 0.45 Hz/s s time (s) frequency plot during system disturbance (recorded by frequency trend monitor) 13
14 Case Study II: Non-operation of Under frequency Relay Waveform captured by Disturbance Recorder during the fault Waveform Produced by simulation tool for replaying on the relays 14
15 Case Study II: Non-operation of Under frequency Relay Under frequency relays was of static type self powered relay (Powered by PT Supply) with built-in U/V block at voltage below 70 % of rated voltage Relay operation was getting inhibited due to under voltage condition on 110 kv bus during system disturbance The Waveform was replayed on Numerical Relay on which U/V blocking can be set manually. Initially Numerical relay also did not operate with U/V setting at 70 %. However, by lowering the U/V block setting, the relay operated correctly 15
16 Conclusions Numerical Protection relays of different makes, types and version can exhibit different behavior during abnormal power system condition. Conventional testing of the relays may not reveal the deficiencies in the relays either due to inherent protection algorithm or due to incorrect adopted configuration / setting The disturbance records captured by the numerical relays and fault disturbance recorders can be used to simulate the disturbance and play the same on various types of devices The typical fault records can be preserved as fault library and used for evaluating new relay products Analysis of the protection performance will help in improving the power system protection and hence contribute to grid reliability and stability 16
USE CASE 14 CONTROLLED ISLANDING
I USE CASE 14 CONTROLLED ISLANDING Use Case Title Centralized application separates grid into islands to prevent blackout Use Case Summary Controlled islanding is a method that can significantly improve
More informationUsing the Bitronics 70 Series to Improve Local Monitoring and Control
Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application
More informationRecordGraph. v5.3. Release Description
RecordGraph v5.3 Release Description FEATURE ENHANCEMENTS Export a single COMTRADE file with all measured and derived channels. L-PRO 4500: Added support for the following analog input product variants:
More informationImplementation of Online ABT monitoring System In The TATA Power Co. Ltd. Mumbai. S. G. Patki, S. C. Dhapre, S. G. Joshi, S. A.
1 Implementation of Online ABT monitoring System In The TATA Power Co. Ltd. Mumbai S. G. Patki, S. C. Dhapre, S. G. Joshi, S. A. Wangade 2 Topics Discussed Metering system between TPC & MSETCL. Need for
More informationBus Protection Application Challenges
Bus Protection Application Challenges KN Dinesh Babu - Megger JC Theron, Lubomir Sevov GE Grid Solutions 2017 Texas A&M Protective Relay Conference Content Introduction Application Challenges Increase
More informationAurora Vulnerability Mitigation Techniques using UR Technology
Technical Note Aurora Vulnerability Mitigation Techniques using UR Technology GE Publication Number: GET-20039 Copyright 2015 GE Inc. 1. Introduction The US Department of Energy s Idaho laboratory had
More informationAdvanced Features. High Performance Stepper Drive Description. Self Test and Auto Setup
www.applied-motion.com STAC6 High Performance Stepper Drive Description The STAC6 represents the latest developments in stepper drive technology, incorporating features that will derive the highest performance
More informationSOUTHERN REGIONAL POWER COMMITTEE BENGALURU
SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Additional Agenda for the 80 th Meeting of Protection Coordination Sub-Committee of SRPC to be held on 20-21 December, 2018 1. Grid Occurrences Additional Grid
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection System Protection and Control Subcommittee
More informationImplementing the protection and control of future DC Grids
Implementing the protection and control of future DC Grids Hengxu Ha, Sankara Subramanian Innovation and Technology Department, SAS, Alstom Grid 1. The challenge of the DC Grid protection 1 High speed
More informationPG&E Transmission Interconnection Handbook
Table of Contents TABLE OF CONTENTS... 1 UPDATE HISTORY... UP-1 INTRODUCTION... IN-1 I-1. PURPOSE... IN-1 I-2. INTRODUCTORY DEFINITIONS... IN-1 I-3. HANDBOOK APPLICABILITY... IN-2 I-3.1. New Load, New
More informationAn Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems
An Artificial Intelligence Based Approach for Bus Bar Differential Protection Faults Analysis in Distribution Systems By Eng. Sameh Moustafa Mohamed Abd Elgowad Elbana A thesis submitted to The Faculty
More informationSR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.
SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering
More informationp. 1 p. 9 p. 26 p. 56 p. 62 p. 68
The Challenges and Opportunities Faced by Utilities using Modern Protection and Control Systems - Paper Unavailable Trends in Protection and Substation Automation Systems and Feed-backs from CIGRE Activities
More informationPROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY S.E.P TRAINING CENTRE
PROCEDURE FOR TESTING P122 THREE PHASE OVERCURRENT & EARTH FAULT PROTECTION RELAY INDEX CHAPTER 1: 1. INTERFACING PC WITH RELAY 2. EXTRACTING SETTINGS FROM THE RELAY CHAPTER 2: 1. SETTING VALUES AS PER
More informationShabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India
SCADA in Transmission Line Shabnam Rukhsar Electrical Engineering Department, Anjuman College of Engineering and Technology.India ABSTRACT: Transmission line equivalent circuit parameters are often 25%
More informationINSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:
DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER The DKM-409 is a precision instrument designed for displaying various AC parameters in 3-phase distribution panels. Thanks to its isolated
More informationTesting of Real Time Power System Control Software
Testing of Real Time Power System Control Software Transpower s Pole 3 Project Presentation to Special Interest Group of ANZTB 7 October 2013 Richard Sherry 1 Summary 1. What does the HVDC Control System
More informationSDG&E s Accomplishments and Future Plans
SDG&E s Accomplishments and Future Plans Tariq Raman and Subbu Sankaran San Diego Gas & Electric Work Group Meeting October 23-24, 2018 San Diego Gas & Electric San Francisco SDG&E Los Angeles San Diego
More informationVerification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation
111 Verification of Utility Requirements on Modern Numerical Busbar Protection by Dynamic Simulation Z. Gajić (ABB, Sweden) JP Wang / PW Gong / YS Xu (ABB China) ZX Zhou (CERPI, China) Summary Power utilities
More informationReyrolle Protection Devices. 7SG118 Argus 8 Voltage & Frequency Relay. Answers for energy
Reyrolle Protection Devices 7SG118 Argus 8 Voltage & Frequency Relay Answers for energy 7SG118 Argus 8 Voltage and Frequency Relay Data Storage and Communication Serial communications conform to IEC60870-5-103
More informationPOWER METER HC Features
Introduction The power quality meter HC 6030 is an ideal device to power monitoring in power quality when continuous monitoring to a power system is required. The HC 6030 provides metering for current,
More informationBusbar protection REB 670
Gunnar Stranne Busbar protection REB 670 Rio de Janeiro April 23-25, 2006 ABB Power Technologies AB 2 3 4 REB 500 is enabled for use with IEC61850 communication Benefits of REB 670 outstanding features
More informationDGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION. Field of application
DGBV-EP DIGITAL GENERATOR AND GENERATOR-TRANSFORMER UNIT PROTECTION Field of application The devices of the EuroProt complex protection family are modular devices. The modules are selected, assembled and
More informationLoad Flow Analysis. I Objectives
EE342 Electrical Power Lab Experiment PS3 Load Flow Analysis I Objectives To demonstrate load flow concepts. To study system performance under different operating conditions. To experience the real feel
More informationLowering Lifecycle Costs
Lowering Lifecycle Costs with Intelligent Motor Control Centers Standards Certification Education & Training Publishing Conferences & Exhibits Speakers: Presented and Authored by Jeff M. Miller, PE, ENV
More informationKILOVAC WD Series, DIN Rail or Screw Mounted Protective Relays
KILOVAC WD Series, DIN Rail or Screw Mounted Protective Relays n WD25 Paralleling (Synch Check) Relays n WD2759 Over/undervoltage Relays n WD32 Reverse Power Relays n WD47 Phase Sequence Relays n WD5051
More informationURC Utility Relay Company
communications i-comm modbus / rs-485 AC-PRO Communicating Trip Units instruction manual ZERO-Hertz Communicating Trip Units URC Utility Relay Company Chagrin Falls, OH 44023 Phone: 888.289.2864 www.utilityrelay.com
More informationWe will discuss two types of loss-of-potential (LOP) logic during this presentation:
1 We will discuss two types of loss-of-potential (LOP) logic during this presentation: Traditional LOP, which uses traditional voltage and current elements to detect an LOP condition. Advanced LOP, which
More informationi-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection
i-pcgrid Workshop 2014 PG&E Order No. 754 Analysis: Protection 1 Process PG&E Order No. 754 Analysis Receive Bus List from Planning that Meet the Criteria in Table A Protection Computes Actual Clearing
More informationIJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online):
IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 10, 2015 ISSN (online): 2321-0613 Comparison of Shunt Facts Devices for the Improvement of Transient Stability of Two Machine
More informationShort-Circuit Calculation Methods
Short-Circuit Calculation Methods Oct 1, 2004 12:00 PM, By Massimo Mitolo, Ph.D., Chu & Gassman Consulting Engineers Ref.: http:// ecmweb.com/mag/electric_shortcircuit_calculation_methods/ The task may
More informationLessons Learned Implementing an IEC based Microgrid Power- Management System. K.A. GRAY, J.J. MRAZ* POWER Engineers, Inc.
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Lessons Learned Implementing an IEC 61850-based Microgrid Power- Management System K.A.
More informationPower System Monitoring Recorder TESLA 3000
Power System Monitoring Recorder TESLA 3000 Product Overview TESLA 3000 is an easy-to-use and cost-effective, stateof-the-art, multi-time frame (simultaneous) power system recording monitor. The optional
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Description of Current Draft
More informationUSE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION
H USE CASE 13 ADAPTIVE TRANSMISSION LINE PROTECTION Use Case Title Adaptive Transmission Line Protection Use Case Summary The requirements for improvement in the performance of protection relays under
More informationAutomation in Large Urban Power Distribution System. Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI
Automation in Large Urban Power Distribution System Dr. K Rajamani CENTRAL TECHNICAL SERVICES, RELIANCE ENERGY LIMITED, MUMBAI Need for Automation and Current trends Automation Systems and Functionality
More informationHigh impedance protection relay
High impedance protection relay Page 1 Issued: April 1999 Status: New Data subject to change without notice Features High impedance type differential current earth-fault protection, so called restricted
More informationB5-111 APPLICATION OF INTRANET TECHNOLOGIES FOR POWER SYSTEM PROTECTION
21, rue d'artois, F-75008 Paris http://www.cigre.org B5-111 Session 2004 CIGRÉ APPLICATION OF INTRANET TECHNOLOGIES FOR POWER SYSTEM PROTECTION A. TAKEUCHI F. KUMURA M. NAKAHARA Chubu Electric Power Co.
More informationAbout Georgia Transmission Corporation (GTC)
About Georgia Transmission Corporation (GTC) Transmission-only, not-for-profit cooperative Formed in March 1997 from the restructuring of Oglethorpe Power Corporation (OPC) GTC provides network transmission
More informationTable of Issues and Directives Project Relay Loadability: Stable Power Swings
Table of Issues and Directives Project 2010-13.3 Relay Loadability: Stable Power Swings FERC Order 733 150. We will not direct the ERO to modify PRC-023-1 to address stable power swings. However, because
More informationSDG&E s EPIC Demonstration Projects on Emerging Communication Standards. IEC Europe 2017 Conference. Frank Goodman, SDG&E EPIC Program Manager
SDG&E s EPIC Demonstration Projects on Emerging Communication Standards Frank Goodman, SDG&E EPIC Program Manager IEC 61850 Europe 2017 Conference September 26-28, 2017 2017 San Diego Gas & Electric Company.
More informationPFC-10 Power Factor Controller
PFC-10 Power Factor Controller Instruction Manual Ver. 6.0 / 2002 (2-2005 update) Table of Contents Page Subject 3 Starter ion 4-5 Installation Notes 6-7 Terminals Review & Control Wiring 8 Front-panel
More information7000 SERIES Power Switching Solutions. Closed Transition Transfer Switching. Delayed Transition Transfer Switching
7000 SERIES Power Switching Solutions Fig. 2: Four pole, Closed Transition Switch rated 1000 Amperes in Type 1 enclosure. Closed Transition Switching Closed Transition Switches feature main contacts that
More informationNewCode. Comprehensive Motor Protection and Control Relay. Relay Field Input and Output LEDs. LED Fault Indicators
NewCode Comprehensive Motor Protection and Control Relay Relay Field Input and Output LEDs LED Fault Indicators Configurable Memory Module on a T-Bus IrDA and USB Connectors Profibus Address Indicator
More information4-W HDSL/56Kbps Isolation Card With 130/190V Span Powering. Description & Installation P30140
4-W HDSL/56Kbps Isolation Card With 130/190V Span Powering Description & Installation P30140 Printed in USA 11/12 TO506 Rev. A Table of Contents 1.0 PRODUCT SCOPE 3 2.0 PRODUCT OVERVIEW 3 2.1 System Requirements
More informationAdvanced Fuse-Saving Techniques. T. ROUSAN Ameren Illinois USA. J. JERMAKOWICZ S&C Electric Company USA
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Advanced Fuse-Saving Techniques T. ROUSAN Ameren Illinois USA J. JERMAKOWICZ S&C Electric
More informationGE Power Management. MMII Intelligent MCC Controller
A concept that will offer reduced overall installed cost and production efficiency through information availability to operators and maintenance. Presentation Overview 6 Applications 6 Protection and Control
More informationAP SERIES SYSTEMS POWER SUPPLIES. Autoranging power supplies for bench or systems use FEATURES
AP SERIES Autoranging power supplies for bench or systems use The AP series power supplies utilise an autoranging concept and can provide a wide and adjustable range of voltage and current combinations
More informationAn expert solution is within your reach. EORSys. We take care of it.
We take care of it. EORSys An expert solution is within your reach. System solution for compensated, isolated and solidly grounded grids Precise control of arc suppression coils Reliable locating of earth
More informationA Case for Multi-Function PMU
A Case for Multi-Function PMU Harish I. Mehta Mehta Tech, Inc. www.mehtatech.com NASPI Chattanooga, TN Meeting PMU Definition PMU is generally defined as: IEEE C37.118 compliant device Time synchronized
More informationCommission Testing Methods for Protection Systems
Commission Testing Methods for Protection Systems Tom Ernst GE Grid Solutions Ken Sletten Minnesota Power Abstract Commission testing should be designed to assure that the protection system is set and
More informationSmart Power Flow Monitoring and Control
IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 10 April 2016 ISSN (online): 2349-784X John Richardson. J Mathivathani. N Karthikeyan. K Preethi. PA Vivekanandhan. C Vice
More informationABB Data Center Forum 2017
ABB DATA CENTER FORUM 2017, 11 TH JULY 2017 ABB Data Center Forum 2017 Perfecting Data Center availability with Ultra-Fast Protection Devices Barbara Schlegel ABB DATA CENTER FORUM 2017, 11 TH JULY 2017
More informationHigh Impedance Protection Relay SPAE010, SPAE011. Product Guide
SPAE010, SPAE011 SPAE010, SPAE011 1MRS750383-MBG Issued: April 1999 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features High impedance type differential current earth-fault
More informationCASE STUDY : Transient Stability Simulation Package
CASE STUDY : Transient Stability Simulation Package CLIENT NAME : A major T&D solutions provider in the world END CUSTOMER : A public T&D utility in one of the SAARC nations PROJECT TITLE : Customized
More informatione 2 TANGO -400 Overcurrent Relay K Catalogue EN
e 2 TANGO -400 Overcurrent Relay K-33.1.3 Catalogue EN We Create Ideas With Power! e 2 TANGO-400 protection relay is a solution developed by ELEKTROMETAL ENERGETYKA SA R&D department consisting of engineers
More informationAuto-Changeover & Feeder Automation. Reclosers & Sectionalizers
Auto-Changeover & Feeder Automation Reclosers & Sectionalizers WHY AUTOMATE? COMPETITION SERVICE VALUE QUALITY RELIABILITY REGULATION RATES BASED ON RELIABITY & PERFORMANCE PENALTIES REGULATION SAIDI (System
More informationBus Bar Protection Relay B-PRO 4000
Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation
More informationPower Test Equipment
Power Test Equipment for the global power industry T&R Test Equipment design and manufacture high quality test equipment for the power industry. Our equipment is used world-wide in transmission and distribution,
More informationPUBLIC SERVICE OF NEW HAMPSHIRE. Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System
PUBLIC SERVICE OF NEW HAMPSHIRE Technical Requirements for Non Utility Generation Interconnecting to the PSNH Distribution System September 2013 1.0 Purpose of this document Public Service of New Hampshire
More informationRT4F-120V/20A-WAC RECTIFIER
The RT4F-120V/20A-WAC is a switched mode rectifier/charger module designed to provide up to 20A of output current into a 120V nominal system. This charger has been designed for use in conjunction with
More informationDTRV-EP. COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS. Application field
DTRV-EP COMPLEX DIGITAL PROTECTION FOR 120 kv / MEDIUM VOLTAGE TRANSFORMERS Application field The DTRV type of complex transformer protection is designed to protect 120 kv / medium voltage transformers,
More informationLE ELECTRONICS Pvt. Ltd.
LE ELECTRONICS Pvt. Ltd. Monitoring Relays: LVM Line Voltage Monitors LCM - Line Current Monitors VMR Voltage Monitoring Relays CMR Current Monitoring Relays VCMR Voltage Current Monitoring Relays LFM
More informationDS5000-IBFS. 5kA rms - 8kA DC Fluxgate current transducer. Features. Description. Application. Precision Innovation /
5kA rms - 8kA DC Fluxgate current transducer Features DC 8000A AC 5000A rms Maximum gain error DC to 1kHz - 0.1% Transducer core optimized for high level of immunity against external magnetic fields Operating
More informationJehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600
Jehanpour Ranjkesh, Integrator Partner Seminar 2012 Station level product news Automation Controller COM600 Contents COM600 Product Overview Business Overview Product News Overview June 12-14, 2012 Slide
More informationRTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.
Binary Output 23BO62 Characteristics The binary output is made via relay contacts. The 8 outputs are potential isolated against the electronic by optocoupler. All 8 outputs have a separate return. Application
More information2C138. Sensitive Earth Fault Relay. Features. Application. Operation
Technical Bulletin 2C138 Sensitive Earth Fault Relay Features High sensitivity (0.1% of I n ) 2 nd & 3rd harmonic & HF noise suppression - tuned to 50 Hz Optional reset functions Instantaneous (Fast),
More informationSYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD
SYMPATHETIC INRUSH PHENOMENA IN PARALLEL AND SERIES CONNECTED TRANSFORMERS USING PSCAD Tejpal P. Purohit 1, Prashant K. Bhavsar 2 Department of Electrical Engineering, Government Polytechnic Palanpur,
More informationBRC SERIES 20kW High Voltage Power Supply
BRC SERIES 20kW High Voltage Power Supply Description UNIPOWER s line of BRC switching power supplies are notable for low ripple, fast transient response, endurance to repetitive arcing and stable output
More informationPower System Monitoring Recorder
Power System Monitoring Recorder TESLA 4000 Model 4000 Model 4003 Product Overview TESLA 4000 is an easy-to-use and cost effective, state of the art, multi-time frame (simultaneous) power system monitoring
More informationSRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016
SRI LANKA STANDARD CODE OF PRACTICE FOR GRID CONNECTED PHOTOVOLTAIC POWER SYSTEMS SLS 1522:2016 BY H S W Karunaratne Assistant Director - Engineering Sri Lanka Standards Institution. 1 DEFINITIONS Ac module:
More informationDate of Publication: THREE PHASE LINE FAULT DETECTION ON DISTRIBUTION LINES USING GSM TECHNIQUE
International Journal of Emerging Technology and Innovative Volume 2, Issue 3, March 2016 (ISSN: 2394 6598) Date of Publication: 29.03.2016 THREE PHASE LINE FAULT DETECTION ON DISTRIBUTION LINES USING
More informationDGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field
DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description
More informationTransient Stability Analysis with PowerWorld Simulator
Transient Stability Analysis with PowerWorld Simulator T14: Large-Scale Simulation Examples 2001 South First Street Champaign, Illinois 61820 +1 (217) 384.6330 support@powerworld.com http://www.powerworld.com
More informationSTAC5 Stepper Drives. A high performance, compact and cost-effective stepper drive with advanced features and control options
STAC5 Stepper Drives A high performance, compact and cost-effective stepper drive with advanced features and control options Ethernet & EtherNet/IP Advanced Current Control Anti-Resonance Torque Ripple
More informationUR Plus Series. Revision 1.73 Release Notes. GE Digital Energy. Overview. GE Publication Number: GER Summary. Copyright 2013 GE Multilin Inc.
G Digital nergy UR Plus Series Revision 1.73 Release Notes G Publication Number: GR-4372 Copyright 2013 G Multilin Inc. Overview Summary Release 1.73 of the UR Plus series introduces product-specific and
More informationHigh-Reliability Fault-Clearing System solution. Application Guide. Outdoor Distribution (15.5 kv through 38 kv) S&C ELECTRIC COMPANY
S&C Remote Supervisory V ista Outdoor Distribution (15.5 kv through 38 kv) Electric utility customers are increasingly concerned about the frequency and duration of outages they are experiencing, and are
More informationMiniature. Circuit Breakers. reliable solutions for protection of installations against over-current phenomenon. Advantages for you : Technical data :
Miniature Circuit Breakers reliable solutions for protection of installations against over-current phenomenon Advantages for you : Bi-connect terminals for simultaneous termination of bus bar & wires Unique
More informationTM241CE40R controller M IO relay Ethernet
Characteristics controller M241 40 IO relay Ethernet Main Range of product Product or component type [Us] rated supply voltage Mar 09, 2017 Modicon M241 Logic controller 100...240 V AC Discrete input number
More informationProgramozható, nagyteljesítményű AC tápegység, SP300VAC-2000W
is a switching mode single-channel output high-precision programmable AC power source, which adopts high speed DSP+CPLD control, high frequency PWM power technology and active PFC design to realize AC/DC
More informationELG4125: System Protection
ELG4125: System Protection System Protection Any power system is prone to 'faults', (also called short-circuits), which occur mostly as a result of insulation failure and sometimes due to external causes.
More informationSED2 Variable Frequency Drives
SED2 Variable requency Drives Description The SED2 variable frequency drives are designed specifically for HVA applications. The SED2 supports a wide variety of digital and analog I/O for diverse control
More informationwww. ElectricalPartManuals. com .Basler Electric BE1-878 HIGH IMPEDANCE BUS DIFFERENTIAL RELAY ADVANTAGES ADDITIONAL INFORMATION APPLICATION Page2
The Bus Differential Relay provides economical high speed protection in a conventional package for all high impedance differential applications. ADVANTAGES Proven performance of High Impedance Differential
More informationDynamic State Estimation Based Protection: Laboratory Validation
Dynamic State Estimation Based Protection: Laboratory Validation Paul Myrda - EPRI & A.P. Meliopoulos and G. J. Cokkinides - Georgia Tech October 21, 2014, Houston, TX Contents Background and Motivation
More informationD115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors
D115 The Fast Optimal Servo Amplifier For Brush, Brushless, Voice Coil Servo Motors Ron Boe 5/15/2014 This user guide details the servo drives capabilities and physical interfaces. Users will be able to
More informationPower System Resilience & Reliability. Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 28, 2017
Power System Resilience & Reliability Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 28, 2017 NERC, Reliability, & Resilience NERC has addressed reliability
More informationUR Universal Relay Series
GE Digital Energy UR Universal Relay Series Revision 4.43 Release Notes GE Publication Number: GER-4380Rev1 Copyright 2010 GE Multilin Summary Overview GE Multilin issues the UR 4.43 release that introduces
More informationTM241CE40R controller M IO relay Ethernet
Characteristics controller M241 40 IO relay Ethernet Main Range of product Product or component type [Us] rated supply voltage Apr 10, 2018 Modicon M241 Logic controller 100...240 V AC Discrete input number
More informationSPECIFIC INTERCONNECTION PROTECTION REQUIREMENTS... 5
Central Hudson Gas & Electric Corporation (CHG&E) Interconnection Protection Requirements for Distributed Generators of Greater than 300 kva Connected in Parallel with the CHG&E Electrical Delivery System
More informationASPEN Software - Introduction
ASPEN Software - Introduction ASPEN is a very user-friendly software package that is capable of doing load-flow and shortcircuit studies, as well as relay application and coordination. Its simple graphical
More informationAn adaptive limited wide area differential protection for power grid with microsources
Wu Protection and Control of Modern Power Systems (2017) 2:21 DOI 10.1186/s41601-017-0052-2 Protection and Control of Modern Power Systems ORIGINAL RESEARCH An adaptive limited wide area differential protection
More informationOpal Pro to DeviceNet. Opal Pro MS6 SERIES. DeviceNet Interface Users Manual. Revision Page 1
Opal Pro MS6 SERIES DeviceNet Interface Users Manual Revision 1.01 Page 1 Page 2 FOR YOUR SAFETY Only qualified personnel should install this equipment, after first reading and understanding all the information
More informationImpulse Generator Digital Control & Measuring System
Impulse Generator Digital Control & Measuring System HCS2000A Digital Control System Item Qty. Description 6 1 Control system parameter: Charging voltage: Setting range 0~100.0kV Operating space 10.0~100.0kV
More informationRT4B-110V/12A RECTIFIER
The RT4B-110V/12A is a switched mode rectifier (SMR) module designed to provide up to 12A of output current into a 110V nominal system. It can be used with or without a cooling fan. With a fan it runs
More informationSEL Event Report Frequently Asked Questions
Event Analysis Introduction Session SEL Event Report Frequently Asked Questions 1. How is an event report generated by an SEL relay? A. Relay trip from trip equation (TR). Example 1: TR := 49T OR 50P1T
More informationApplying Intelligent Fast Load Shed Using IEC GOOSE
Applying Intelligent Fast Load Shed Using IEC 61850 GOOSE JC Theron, Steven Rowe GE Grid Solutions Troy Wilsey, Anthony Colonnese Ameresco Russell Gagner Civilian Naval Facilities Engineering Command 71
More informationTM241C24R. Main. Discrete output type. Discrete output number. 14 (remote I/O architecture) 50 µs turn-on operation with I0...I13 terminal(s) input
Product datasheet Characteristics TM241C24R Complementary Discrete I/O number 24 Number of I/O expansion module Supply voltage limits Network frequency Discrete input logic Discrete input voltage Discrete
More informationDistributed by. Keor T UPS THREE-PHASE UPS. from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
Distributed by Keor T UPS THREE-PHASE UPS from 10 to 120 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES T THREE-PHASE UPS T has been designed with advanced technologies and the
More informationDEIF A/S. Description of options. Option A and B, Loss of mains protection package Automatic Gen-set controller. Description of options
Description of options Option A and B, Loss of mains protection package Automatic Gen-set controller 4189340394B SW 2.3X.X Description of options Functional descriptions DEIF A/S Parameter list DEIF A/S,
More information