1 , GH Q The coupler can be used as a line The coupler is installed in the distribution board on the data rail of the coupler or a backbone coupler. CDC 07 0 F000 As a line coupler, it links a line with a main line. As a backbone coupler, it links a main line with the backbone line. It thus ensures electrical isolation. Telegrams can be filtered at the same time. It is possible to route only those telegrams that are intended for the other line. For diagnostics purposes, all the telegrams can be routed or disabled. secondary line. The main line is plugged onto the bus connecting terminal on the top of the device. Device replacement: When replacing an LK/S. with a new line coupler, only the file LK_Dummy.vd needs to be imported into ETS. In this case, the old parameters of the line coupler (and the old application) can be loaded into the new line coupler. Technical Data Power supply EIB 4 VDC, via the bus line Operating and display elements green LED () ON, device is ready for operation red LED (6) and push button (7) For programming the physical address yellow LED () Telegram traffic on the secondary line (line) yellow LED () Telegram traffic on the primary line (main line) Connections EIB, secondary line Pressure contacts on data rail EIB, primary line Bus connection terminal Type of protection IP 0, EN Ambient temperature range Operation 5 C 45 C Storage/transport 5 C 70 C Design Modular installation device, MDC Housing, colour Plastic housing, grey Mounting on 5 mm mounting rail, DIN EN 6075 Dimensions 90 x 8 x 64 mm (H x W x D) Mounting depth/width module at 8 mm Weight kg Certification EIB-certified Electrical safety Degree of pollution (in acc. with IEC ): Type of protection (in acc. with EN 6059): IP 0 Protection class (in acc. with IEC 640): III Overvoltage category (in acc. with EN ): III Bus: safety extra-low voltage SELV DC 4 V Device complies with EN and IEC EMC requirements complies with EN , EN and EN Page of 6 LKS TD_EN_V-0 CDC D00

2 V AC Hz 0V DC I 0V DC I - 5 C...45 C I I + <_ 640 ma On 0V DC Main S EIB ESET eset 0V DC EIB, GH Q Application program Number of Max. number of Max. number of communication objects group addresses associations /backbone coupler epeater Circuit diagram 6 On Main Operational LED (ON) 4 Bus connection terminal for EIB connection of primary/main line LED for telegram traffic on 5 Data rail contacts (underside) secondary line (line) for EIB connection of secondary line LED for telegram traffic on 6 Programming LED primary/main line 7 Programming button L N PE L N SV/S SV/S ON I >I max 0 V DC 5 A VB/S. VB/S.. S 4 B D/S. ESET VB/S 4.4 D/S. 0 VDC output of EIB power 5 -pole connector, VB/S.. supply without choke A /repeater: segment coupler, B Main line/repeater: line 4-pole connector, VB/S Choke, D/S. Page of 6 LKS TD_EN_V-0 CDC D00

3 , GH Q /backbone coupler.0 /backbone coupler With the parameter Check filter table, it is possible to switch this checking Selection in ETS ABB System components Coupler The coupler links two lines for data transfer but isolates them electrically. If the coupler receives telegrams (for example during the commissioning of an EIB installation) which use a physical address as a target address, it compares the physical addresses of the sender and receiver with its own physical address and then decides whether it must route the telegrams or not. If the coupler has not yet received its own physical address, it can cause faults when commissioning other devices. The coupler reacts to telegrams with group addresses in accordance with its parameter settings. function on or off. When the checking function is activated, the parameter On error in filter table determines the reaction of the coupler. So that any errors are detected as quickly as possible, the setting block can be selected. In the default setting route, the installation will generally operate without any problems for the user. In installations with a high volume of telegrams, there could be time delays. There is no space for main groups 4 and 5 in the filter table. They should therefore normally not be configured. If they are used however, the parameter Main group 4/5 must be set to route. During normal operation (default setting), the coupler only routes the telegrams whose group addresses have been entered in its filter table. Particularly during commissioning and for diagnostics purposes, it may be a good idea to set the first two parameters Group telegrams main line -> line and Group telegrams line -> main line to route. If the EIB installation then functions without any errors after the commissioning of the sensors and actuators, the ETS program can calculate the correct filter table (in the Project Design module via the Filter button). The two parameters can now be reset to the default values again. The application must then be reprogrammed (in the Commissioning module). The correct filter table is then transferred into the coupler. If the coupler routes a telegram and does not receive an acknowledgement or if a bus device establishes a transmission error, the coupler repeats the telegrams up to three times. With the parameters epetitions if errors, this behaviour can be set separately for both lines. This can be advisable if the couplers are operating without filter tables in an installation and are routing all the telegrams. The bus load can be reduced in this case. These parameters should be left in the default setting. Normally, the coupler only acknowledges the telegrams that it routes. With the parameters Telegram confirmation, it can be set separately for both lines that the coupler acknowledges each telegram. These parameters should also be left in the default setting. When programming the filter table, a check sum is determined which the coupler uses during continuous operation to establish whether the filter table has changed. Page of 6 LKS TD_EN_V-0 CDC D00

4 , GH Q Parameters Group telegrams route The default setting for the values main line -> line block is printed in bold type. nomal Group telegrams route line -> main line block normal Check filter table no yes Main group4/5 route block On error in filter table block route ignore errors epetitions if errors on none main line epetitions if errors on line none Telegram comfirmation always on main line only if routed Telegram comfirmation always on line only if routed Page 4 of 6 LKS TD_EN_V-0 CDC D00

5 , GH Q epeater.0 repeater If an error occurs during the transmission of a telegram with the physical Selection in ETS ABB System components Coupler A coupler can also be used as a line repeater. In its function as a repeater, it links two line segments for data transfer but isolates them electrically. Up to three line repeaters can be used behind a line coupler. As a result, up to four line segments can form a complete line. The line repeaters do not have any filter tables. This means that a telegram is sent to all line segments, whether it is processed in the corresponding line segment or not. It is therefore not important whether the telegram has been triggered within the lines or whether it has been sent from the main line to the lines via the line coupler. If the line repeater receives telegrams for example during the commissioning of an EIB installation, which use a physical address as a target address, it compares the physical addresses of the sender and receiver with its own physical address and then decides whether it must route the telegrams or not. If the line repeater has not yet received its own physical address, it can cause faults when commissioning other devices. address of a receiver, the line repeater can repeat the telegram. It is not repeated in the default setting in order to keep the telegram load as small as possible. This behaviour can be set separately for both line segments with the parameters epetitions if errors in assigning physical addresses. If the line repeater routes a telegram and does not receive an acknowledgement or if a bus device establishes a transmission error, the line repeater by default repeats the telegram twice at most. This behaviour can be set separately for both line segments with the parameters epetitions if errors in group telegrams. Backbone line Backbone coupler Main line coupler = epeater The EIB segments are connected to the secondary line (data rail contacts) of the line repeater. The line is linked with the bus connecting terminal Segments (Part 0) (Part ) (Part ) (Part ) Connection of repeaters to a line Page 5 of 6 LKS TD_EN_V-0 CDC D00

6 , GH Q Parameters epetitions if errors on line in none The default setting for the values assigning physical addresses is printed in bold type. epetitions if errors on line in none group telegrams epetitions if errors on segment none in assigning physical addresses epetitions if errors on segment none in group telegrams Page 6 of 6 LKS TD_EN_V-0 CDC D00

Line Coupler, MDRC LK/S 2.1, GH Q R0001

Line Coupler, MDRC LK/S 2.1, GH Q R0001 , GH Q605 0019 R0001 The coupler can be used as a line In the distribution board the coupler is coupler or as an area coupler. Used as installed on the secondary line of the a line coupler it joins up

More information

ABB i-bus EIB. Shutter Actuator, 2-fold, 6 A, 230 VAC, MDRC JA/S 2.6.1, GH Q R0111

ABB i-bus EIB. Shutter Actuator, 2-fold, 6 A, 230 VAC, MDRC JA/S 2.6.1, GH Q R0111 , GH Q31 0022 R0111 The 2-fold shutter actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus connecting terminal. It is used to control two

More information

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001

Control unit for lux control, MDRC Type: SL/S 50.1, GH Q R0001 SK 0012 B 98 The control unit is a DIN rail mounted device for insertion in the distribution board. It is used to control digitally dimmable electronic ballast devices or transformers via the EIB. In a

More information

IP gateway, MDRC IG/S 1.1, GH Q R0001

IP gateway, MDRC IG/S 1.1, GH Q R0001 , GH Q631 0067 R0001 The IP gateway IG/S is the interface The IP address of the IG/S can be between EIB / KNX installations and IP fixed or received from a DHCP server. CDC 071 130 F0003 networks. Data

More information

Linienkoppler S KNX. Line coupler S KNX. Line coupler S KNX Status: March 16 (Subject to change) Page 1 of 29

Linienkoppler S KNX. Line coupler S KNX. Line coupler S KNX Status: March 16 (Subject to change) Page 1 of 29 Linienkoppler S KNX Line coupler S KNX Line coupler S KNX 9070880 Status: March 16 (Subject to change) Page 1 of 29 KNX Contents Contents Page 1 General... 3 1.1 Using the product manual... 3 1.1.1 Structure

More information

Switch Actuator, 4-fold, 16 A, MDRC AT/S , GH Q R0111

Switch Actuator, 4-fold, 16 A, MDRC AT/S , GH Q R0111 , GH Q631 0021 R0111 The 4-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus connecting terminal. Using four floating contacts,

More information

The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal.

The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. , GH Q631 0047 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. Using eight floating contacts, it switches

More information

Switch Actuator, 4-fold, 20 A, MDRC AT/S , GH Q R0111

Switch Actuator, 4-fold, 20 A, MDRC AT/S , GH Q R0111 , GH Q631 0028 R0111 The 4-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus connecting terminal. It is particularly suited

More information

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A)

Product and functional description. Application Program. instabus EIB Technical product information. April (6 x AC 230 V / 0,05 A) Product and functional description also functions if the bus cable is not connected or if the bus communication fails. After a long push button action (> 2 s), the other valve group is selected. The yellow

More information

KNX USB INTERFACE UIMtp

KNX USB INTERFACE UIMtp KNX USB INTERFACE UIMtp TECHNICAL AND APPLICATION DESCRIPTION Author: Peter Hauner Last modification: 13 November 2017 2001-2017 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details, modifications

More information

Product and Applications Description

Product and Applications Description IP N146/02 Product and Applications Description The IP N146/02 is a DIN rail mounted device. The device implements the KNXnet/IP standard and connects KNX/EIB lines via data networks using the Internet

More information

Operating and mounting instructions

Operating and mounting instructions General Usage IPAS DALI Gateways bring together the crossfunctional KNX installation bus and the lighting control specific DALI-Bus (IEC 60929). Lights with cost-effective, digital DALI ECGs can therefore

More information

Operating voltage Maximum

Operating voltage Maximum , 2CDG 110 0x R0011 2CDC 071 023 F000 The ABB i-bus Light Controllers, (x = 2 or 4) are KNX modular installation devices in ProM Design for installation in the distribution board on 35 mm mounting rails.

More information

ABB i-bus KNX IP Router, MDRC IPR/S 3.1.1, 2CDG110175R0011

ABB i-bus KNX IP Router, MDRC IPR/S 3.1.1, 2CDG110175R0011 Technical Data 2CDC502086D0201 Product description IP Router 3.1.1 is the interface between KNX installations and IP networks. It can be used as a line coupler or area coupler and can utilize the local

More information

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005

Product and Applications Description. Application Programs. Note. instabus EIB Technical Product Information. June 2005 Product and Applications Description Application Programs The application programs of the dimmer UP 525/01 consist of two elements: the actuating and the sensor program element. The tasks actuating program

More information

Product and Applications Description. Application Programs. Example of Operation. Installation Instructions. load circuit AC 230/400V L1 L2 L3 N

Product and Applications Description. Application Programs. Example of Operation. Installation Instructions. load circuit AC 230/400V L1 L2 L3 N Product and Applications Description Application Programs 20 A4 Binary 906401 4 binary outputs 1 status request available for each output 1 relation can be set allows 1 positive drive for each output initial

More information

ABB i-bus KNX Analogue Actuator, 4-fold, MDRC, 0-10 V, 0-20 ma AA/S 4.1.2, 2CDG110202R0011

ABB i-bus KNX Analogue Actuator, 4-fold, MDRC, 0-10 V, 0-20 ma AA/S 4.1.2, 2CDG110202R0011 Technical Data 2CDC505168D0201 ABB i-bus KNX Product description The Analogue Actuator converts telegrams received via KNX into analog output signals. The device has four outputs. The analog outputs can

More information

Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011 , 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in prom design. It is intended for installation in the distribution board on 35 mm mounting rails.

More information

ABB i-bus KNX Switch Actuator, x-fold, 6 A, MDRC SA/S x.6.1.1, 2CDG x R0011

ABB i-bus KNX Switch Actuator, x-fold, 6 A, MDRC SA/S x.6.1.1, 2CDG x R0011 , 2CDG 110 15x R0011 SA/S 12.6.1.1 2CDC 071 033 S0012 The 6 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are suitable for

More information

Push button UP 287, 4 - fold

Push button UP 287, 4 - fold Product DELTA profil DELTA style Push button 1-fold pearl grey 5WG1 241-2AB01 titanium white 5WG1 285-2AB11 titanium white 5WG1 241-2AB11 basalt black 5WG1 285-2AB21 anthracite 5WG1 241-2AB21 titanium

More information

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING

Product and Applications Description. Note. Example of Operation. Installation Instructions. Application Programs WARNING Product and Applications Description Note If the application program is not loaded completely by the ETS, you had better interrupt the 24 V voltage supply of the I/O-module during the loading interval.

More information

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs

Product and Applications Description. Example of Operation. Installation Instructions WARNING. Note. Application Programs Product and Applications Description Example of Operation dimmer UP 525/11 load circuit AC 230 V L1 N The dimmer UP 525/11 is a dimming actuator for mounting in box mounts (a.o. 60 mm Ø, 60 mm depth).

More information

PRODUCT MANUAL. ABB i-bus KNX SV/S KNX-Power Supplies

PRODUCT MANUAL. ABB i-bus KNX SV/S KNX-Power Supplies PRODUCT MANUAL ABB i-bus KNX SV/S KNX-Power Supplies Contents Contents side 1 General... 3 1.1 Using the product manual...3 1.1.1 Structure of the product manual...4 1.1.2 Notes...4 1.2 Product and functional

More information

Product and functional description

Product and functional description Product and functional description The RS 520/23 shutter / blind actuator is a KNX device with one relay output. The device is installed in an AP 118 Control Module Box or an AP 641 Room Control Box. The

More information

Power supply. Interface technology in modular housing DIN rail devices, IM series. Features

Power supply. Interface technology in modular housing DIN rail devices, IM series. Features Features 2,2 kò,5 W 5 V 5,1 V,3 W 24 VDC 2,5 A GN / L 85...264 VAC 9...375 VDC / N Safety extra-low voltage SELV IEC/ EN 695 Output voltage adjustable 24 28 VDC Nominal current 2.5 A Single/parallel operating

More information

ABB i-bus KNX Binary Inputs BE/S Product Manual

ABB i-bus KNX Binary Inputs BE/S Product Manual kg ABB i-bus KNX Binary Inputs BE/S Product Manual Contents Contents Page 1 General 5 1.1 Using the product manual...5 1.1.1 Structure of the product manual...5 1.1.2 s...6 1.2 Product and functional

More information

ABB i-bus KNX AC/S Application Controller

ABB i-bus KNX AC/S Application Controller ABB i-bus KNX AC/S 1.2.1 Application Controller Description of product Automation controller with pre-defined automation modules for comprehensive heating, ventilation and air conditioning automation (HVAC

More information

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011

ABB i-bus KNX DALI Light Controller, 8-fold, MDRC DLR/S M, 2CDG110101R0011 Technical data 2CDC507101D0202 ABB i-bus KNX Product description The ABB i-bus KNX DALI Light Controller DLR/S 8.16.1M is a KNX modular installation device (MDRC) in ProM design for installation in the

More information

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011

ABB i-bus KNX Analogue Input, 4-fold, MDRC AE/S , 2CDG110190R0011 Technical Data 2CDC504084D0201 ABB i-bus KNX Product description The device is used to record analogue data. Four conventional sensors can be connected to the device. The connection to the bus is established

More information

Contents 1. Summary

Contents 1. Summary Guangzhou Video-star Electronics Industrial Co., Ltd K-BUS R KNX IP Router User manual-ver.1 BNIPR-00/00.1 KNX/EIB Intelligent Installation Systems Contents 1. Summary------------------------------------------------------------------------------------------------------------------------------

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer main module N 528/31 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

DOCUMENTATION MECrf TECHNICAL AND APPLICATION DESCRIPTION. Last modification: 24 November 2017

DOCUMENTATION MECrf TECHNICAL AND APPLICATION DESCRIPTION. Last modification: 24 November 2017 DOCUMENTATION MECrf TECHNICAL AND APPLICATION DESCRIPTION Author: Peter Hauner Last modification: 24 November 2017 2001-2017 Apricum d.o.o. Mažuranićeva 4, 21312 Podstrana, Hrvatska Details, modifications

More information

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D D600S - D600D INSTRUCTI MANUAL SIL Switch/Proximity Detector Repeater Relay, DIN Rail, Models D600S, D600D D600 - SIL Switch/Proximity Detector Repeater Relay G.M. International ISM0- Characteristics General

More information

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2TAZ710xx1R2161

ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x , 2TAZ710xx1R2161 Technical Data 9AKK107045A4913 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are

More information

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input

AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input Safety + standard I/O in one module Safety relay output with galvanically isolated contact sets, approved up to 230 V IEC 61508 SIL 3, EN ISO 13849-1/PLe Kat 4, EN 62061 SIL 3 Protection category IP20

More information

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E EN 60204-1 Stop category 0 EN 954-1 Safety category 4 Basic device to EN 60204-1 and EN 954-1 single E-stop monitoring. Manual or automatic start Application up to safety category 2 and stop category 0

More information

AS-i Safety Output Module, IP20

AS-i Safety Output Module, IP20 a AS-i Safety Output Module Safe outputs and standard inputs in one module Protection category IP20 Figure Housing Inputs digital Outputs Safety, SIL3, cat.4 Input voltage (sensor supply) 1 Output voltage

More information

ABB i-bus EIB / KNX Blower/Fan Coil-Aktuator LFA/S 1.1, LFA/S 2.1. Product Manual. Intelligent Installation Systems ABB

ABB i-bus EIB / KNX Blower/Fan Coil-Aktuator LFA/S 1.1, LFA/S 2.1. Product Manual. Intelligent Installation Systems ABB Product Manual ABB i-bus EIB / KNX Blower/Fan Coil-Aktuator LFA/S 1.1, LFA/S 2.1 Intelligent Installation Systems ABB This manual describes the application of the function of the Blower/Fan Coil Actuator

More information

ABB i-bus KNX HCC/S Heating/cooling circuit controller

ABB i-bus KNX HCC/S Heating/cooling circuit controller ABB i-bus KNX HCC/S 2.2.1.1 Heating/cooling circuit controller Description of product The device is a modular DIN rail component (MDRC) in pro M design. It is intended for installation in distribution

More information

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET safe via BUS or NET AS-i 3.0 Gateways, safe via NET or BUS safe and Safe Link in one device up to 450 devices 2 / 1 Master, NET / BUS Slave AS-i Safety input slaves report via safe AS-i Safety output slaves

More information

AS-i 3.0 PROFIBUS Gateways with integrated Safety Monitor

AS-i 3.0 PROFIBUS Gateways with integrated Safety Monitor AS-i 3.0 Gateways 2 / 1 AS-i Master, Slave 1 AS-i Safety Monitor for 2 s Operation using a single Monitor! Monitor processes safety slaves on two s Coupling between the two networks superfluous Up to 32

More information

ABB i-bus KNX BCI/S Boiler/Chiller Interface

ABB i-bus KNX BCI/S Boiler/Chiller Interface ABB i-bus KNX BCI/S 1.1.1 Boiler/Chiller Interface Description of product The boiler/chiller interface is a modular DIN rail component that acts as an interface to the heating/cooling system generator.

More information

Product and functional description

Product and functional description Product and functional description The RS 525/23 Universal Dimmer is a KNX device with one dimmer output. The device is installed in an AP 118 Control Module Box or an AP 641 Room Control Box. The bus

More information

ABB i-bus KNX Switch Actuator, x-fold, 10 A, MDRC SA/S x , 2CDG11015xR0011

ABB i-bus KNX Switch Actuator, x-fold, 10 A, MDRC SA/S x , 2CDG11015xR0011 Technical Data 2CDC505054D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.6.2.1, 10 A are modular installation devices in ProM design for installation in the distribution board. They are

More information

Weather station AP 257/51

Weather station AP 257/51 Gamma instabus Weather station GPS AP 257/61 Weather station AP 257/51 Technical product information 5WG1 257-3AB61 5WG1 257-3AB51 Weather station with sensors to survey temperature, brightness, rain and

More information

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

Product and functional description

Product and functional description Product and functional description The instabus / DAI gateway 141 is a KX EIB device with one DAI output to which up to 64 DAI actuators (e.g. DAI ballasts) can be connected to. It is not allowed to connect

More information

PA ROUTERS. The following criteria can be applied when choosing the network transition:

PA ROUTERS. The following criteria can be applied when choosing the network transition: PA ROUTERS To create a smooth network transition between PROFIBUS DP and PROFIBUS PA, the SIMATIC product range offers two versions: the DP/PA coupler and the PA link. The following criteria can be applied

More information

Device technology. Supply Bus voltage V DC. Current consumption via bus. Accuracy in the range 300 1,000 ppm 1,000 2,000 ppm 2,000 5,000 ppm

Device technology. Supply Bus voltage V DC. Current consumption via bus. Accuracy in the range 300 1,000 ppm 1,000 2,000 ppm 2,000 5,000 ppm 2 2.1 Air Quality Sensor LGS/A 1.1 The ABB i-bus KNX Air Quality Sensor 1.1 is a combined sensor for CO 2, temperature and humidity measurement (relative humidity). Three independent thresholds can be

More information

Product and Application Description

Product and Application Description Technical Product-Information Product and Application Description The IP Gateway KNX-BACnet N 143 is is a DIN rail mounted device connecting a KNX installation with a system using BACnet/IP communication.

More information

ABB i-bus KNX Application Unit Time ABZ/S 2.1 Product Manual

ABB i-bus KNX Application Unit Time ABZ/S 2.1 Product Manual ABB i-bus KNX Application Unit Time ABZ/S 2.1 Product Manual ABZ/S, Application Unit Time Contents Page 1 General 6 1.1 Product and functional description...7 2 Device technology 8 2.1 Technical data...8

More information

Safety control unit B1 / B1. for 2 to 16 machine safety sensors. Use. Types. + PLd according to EN ISO

Safety control unit B1 / B1. for 2 to 16 machine safety sensors. Use. Types. + PLd according to EN ISO Safety control unit for 2 to 16 machine safety sensors 470 121 B1 / 470 125 B1 + PLd according to EN ISO 13849-1 + two safety outputs and external contactor monitoring + for sensors with N.O./N.C. system

More information

ABB i-bus KNX Switch Actuator, Current Detection, x-fold, 16/20 A, C-Load, MDRC SA/S x , 2CDG1101xxR0011

ABB i-bus KNX Switch Actuator, Current Detection, x-fold, 16/20 A, C-Load, MDRC SA/S x , 2CDG1101xxR0011 Technical Data 2CDC505082D0203 ABB i-bus KNX Product description Switch Actuators SA/S x.16.6.1, 16/20 A are modular installation devices in ProM design for installation in the distribution board. They

More information

XPSMCMDO Digital output pairs expansion modules with screw term

XPSMCMDO Digital output pairs expansion modules with screw term Characteristics 2 Digital output pairs expansion modules with screw term Main Range of product Product or component type Device short name Electrical connection [Us] rated supply voltage Number of inputs

More information

Interface AP 146 5WG AB01 for Ethernet-UDP/IP. EIB Device. EIB Device. EIB Device

Interface AP 146 5WG AB01 for Ethernet-UDP/IP. EIB Device. EIB Device. EIB Device Product and Applications Description With the ETS (EIB Tool Software) the application program is selected, its parameters and addresses are assigned appropriately, and downloaded to the interface AP 146.

More information

Catalog. Arc Guard System TM TVOC-2

Catalog. Arc Guard System TM TVOC-2 Catalog Arc Guard System TM TVOC-2 Introduction An even better Arc Guard System TVOC-2, ABB s latest Arc Monitor, builds on the well known TVOC design. Its new functions and features improve an already

More information

See instructions to download and install the latest version of LinkBoxLON and the user's manual at

See instructions to download and install the latest version of LinkBoxLON and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

Positioning modules with DC V output signals, and storage of positioning value

Positioning modules with DC V output signals, and storage of positioning value 8 16 PTM1.1S PTM1.41S PTM1.1S-M DESIO I/O modules Positioning modules with DC...1V output signals, and storage of positioning value PTM1.1S PTM1.41S PTM1.1S-M Signal converters for connection to P-bus,

More information

Push Button Interface UP 220D31

Push Button Interface UP 220D31 Product and Applications Description Application programs UP 220/31 07 B0 S4 On-off-toggle/Dim/Shu/Value 982203 The push button interface is a binary input and output devices for installation in in-wall

More information

PHOENIX CONTACT Features

PHOENIX CONTACT Features Electronic monitoring relay for temperature monitoring Data sheet 107385_en_00 1 Description PHOENIX CONTACT - 2016-05-10 Features Safety and system availability requirements are constantly on the increase

More information

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions DALI gateway Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Serious injuries, fire or property damage possible. Please

More information

USB RF INTERFACE UIMrf

USB RF INTERFACE UIMrf USB RF INTERFACE UIMrf TECHNICAL AND APPLICATION DESCRIPTION Author: Peter Hauner Last modification: 13 November 2017 2001-2017 TAPKO Technologies GmbH Im Gewerbepark A15, 93059 Regensburg, Germany Details,

More information

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

See instructions to download and install the latest version of LinkBoxMB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

DELTA profil wall switch, single UP 241/2 5WG AB_2

DELTA profil wall switch, single UP 241/2 5WG AB_2 UP 241/2 5WG1 241-2AB_2 UP 241/3,with status LED 5WG1 241-2AB_3 UP 243/2 5WG1 243-2AB_2 UP 243/3,with status LED 5WG1 243-2AB_3 UP 245/2 5WG1 245-2AB_2 UP 245/3,with status LED 5WG1 245-2AB_3 UP 245/4,with

More information

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at Safety Instructions WARNING Follow carefully this safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the IntesisBox and/or any

More information

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET

AS-i 3.0 Gateways, PROFIsafe via PROFIBUS or PROFINET safe via BUS or NET AS-i 3.0 Gateways, safe via NET or BUS safe and Safe Link in one device up to 450 devices 2 / 1 Master, NET / BUS Slave AS-i Safety input slaves report via safe AS-i Safety output slaves

More information

Product and functional description

Product and functional description Product and functional description Connection example The universal dimmer submodule N 528/41 is an installation device for DIN-rail mounting, with N-system dimensions. It is designed for lighting control,

More information

Product and Applications Description. Application programs. instabus EIB Technical Product Information. February 2012

Product and Applications Description. Application programs. instabus EIB Technical Product Information. February 2012 Product and Applications Description Application programs UP 220/31 07 B0 S4 On-off-toggle/Dim/Shu/Value 982201 The push button interface UP 220/31 is a binary input and output devices for installation

More information

Operating instructions Evaluation system for flow sensors VS / / 2013

Operating instructions Evaluation system for flow sensors VS / / 2013 Operating instructions Evaluation system for flow sensors VS3000 7097 / 0 07 / 203 Contents Preliminary note...2 2 Safety instructions...3 3 Function and features... Mounting.... Mounting of the sensors...

More information

Product and functional description

Product and functional description Product and functional description The UP 525/13 Universal Dimmer is a KNX device with one dimmer output. The device is installed in a flushmount wall box (60 mm Ø, depth 60 mm) or an installation box.

More information

Faults on the system Proximity switch connection technology:

Faults on the system Proximity switch connection technology: Speed monitor for connection to a base unit from the PNOZmulti modular safety system Approvals Unit features Monitoring of 2 independent axes Connection of 2 incremental encoders or 4 proximity switches

More information

Electrical devices may only be mounted and connected by electrically skilled persons.

Electrical devices may only be mounted and connected by electrically skilled persons. DALI gateway TW Art. No. : 2099REGHE Operating instructions 1 Safety instructions Electrical devices may only be mounted and connected by electrically skilled persons. Serious injuries, fire or property

More information

DELTA i-system wall switch single UP 221/2 5WG AB_2

DELTA i-system wall switch single UP 221/2 5WG AB_2 DELTA i-system wall switch single UP 221/2 5WG1 221-2AB_2 UP 221/3,with status LED 5WG1 221-2AB_3 wall switch double UP 222/2, 5WG1 222-2AB_2 UP 222/3,with status LED 5WG1 222-2AB_3 wall switch triple

More information

AS-i Safety Relay Output Module with Diagnostic Slave

AS-i Safety Relay Output Module with Diagnostic Slave AS-i Safety Relay Output Module with Diagnostic Slave User Manual...supports the requirements for AS-i Safety up to SIL3 Revision date: 2016-03-9 Subject to modifications without notice. Generally, this

More information

XPSMCMMX inputs 2 output pairs expansion module with screw term

XPSMCMMX inputs 2 output pairs expansion module with screw term Characteristics 8 inputs 2 output pairs expansion module with screw term Main Range of product Product or component type Device short name Electrical connection [Us] rated supply voltage Number of inputs

More information

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX

Switching Actuators N530, 6AX Switching Actuators N532, 10AX Switching Actuators N534, 16/20AX Gamma instabus Technical Product nformation Switching Actuators N53, 6AX Switching Actuators N532, 1AX Switching Actuators N534, 16/2AX 4x AC 23V 5WG1 53-1DB31 5WG1 532-1DB31 5WG1 534-1DB31 8x AC 23V 5WG1

More information

Status display unit with P-bus connection

Status display unit with P-bus connection 8 917 DESIO TM I/O modules with P-bus connection PHM1.36TL for connections to automation stations with P-bus for status indication of up to 24 messages for remote control of up to 12 operating points in

More information

Operating Instructions. DALI-Gateway

Operating Instructions. DALI-Gateway Operating Instructions 1. Safety instructions Electrical equipment must be installed and fitted by qualified electricians only. Failure to observe the instructions may cause damage to the device and result

More information

SensoTrans DMS A 20220

SensoTrans DMS A 20220 ProLine Interface Technology Strain Gauge Transmitters The transmitter for strain gauge full bridges in a 6 mm housing. The Task In many different industrial applications strain gauges are used to continuously

More information

Original operating instructions Safety relay with relay outputs G1501S / / 2016

Original operating instructions Safety relay with relay outputs G1501S / / 2016 Original operating instructions Safety relay with relay outputs G50S UK 8023637 / 00 02 / 206 Contents Preliminary note...4. Symbols used...4 2 Safety instructions...5 3 Items supplied...6 4 Functions

More information

SITOP in the SIMATIC Design

SITOP in the SIMATIC Design Siemens AG 2017 /2 Introduction /3 1-phase, 24 V DC (for S7-300 and ET 200M) /9 1-phase, 24 V DC (for S7-1200) /11 1-phase, 24 V DC (for S7-1500 and ET 200MP) /14 3-phase, 24 V DC (ET 200pro) Siemens KT

More information

584 5WG AB_1 DELTA

584 5WG AB_1 DELTA Product DELTA profil DELTA style DELTA ambiente Display and control unit 5WG1 585-2AB01 pearl grey 5WG1 585-2AB11 titanium white 5WG1 585-2AB21 anthracite 5WG1 585-2AB71 silver 5WG1 585-2AB11 titanium

More information

Datasheet - SLB 200-C04-1R

Datasheet - SLB 200-C04-1R 14.02.2013-17:06:30h Datasheet - SLB 200-C04-1R Safety light barriers / Safety monitoring modules to monitor safety light barriers / SLB 200-C Up to 2 light barrier pairs SLB 200 can be connected 1 safety

More information

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description

ETD-BL-1T-230(-PT) Multifunctional time relay with various functions and adjustable times. Data sheet. 1 Description (-PT) Multifunctional time relay with various functions and adjustable times Data sheet 106395_en_02 PHOENIX CONTACT 20-06-08 1 Description Requirements pertaining to safety and system availability increase

More information

ABB i-bus KNX Logic Controller ABA/S 1.2.1, 2CDG110192R0011

ABB i-bus KNX Logic Controller ABA/S 1.2.1, 2CDG110192R0011 Technical data 2CDC509078D0201 ABB i-bus KNX Product description The device provides extensive logic functions. The logic is defined via a graphic editor integrated in the ETS. Up to 3,000 logic gates

More information

QUINT-PS/ 1AC/24DC/ 5

QUINT-PS/ 1AC/24DC/ 5 Extract from the online catalog QUINT-PS/ 1AC/24DC/ 5 Order No.: 2866750 DIN rail power supply unit 24 V DC/5 A, primary switched-mode, 1- phase. The SFB technology (Selective Fuse Breaking Technology)

More information

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway Technical Information Fieldgate Intelligent Ethernet/PROFIBUS gateway Application Fieldgate is a system component that provides an independent access route to a PROFIBUS network. It may be used in a variety

More information

Installation Instructions

Installation Instructions Dual EIB bus coupler Order no.: 1246 651, 1246 661, 1246 671 rmation The Gira SmartSensor is a product of the Instabus KNX/EIB System and complies with KNX/EIBA directives. The functions of the device

More information

The output variables can be force-controlled from a coordinating control system.

The output variables can be force-controlled from a coordinating control system. Produktname: 4-channel analog actuator Bauform: rail-mounted device Artikel-Nr.: 1022 00 ETS-Suchpfad: Gira Giersiepen / Output / Analog output 4fach / Analog actuator 4fach Scope of application: The analog

More information

AS-i 3.0 Sercos Gateways with integrated Safety Monitor

AS-i 3.0 Sercos Gateways with integrated Safety Monitor AS-i 3.0 Sercos Gateways with Safety on Sercos and Safe Link in one device up to 456 Devices Safely monitoring safety drives with Safety on Sercos 2 / 1 AS-i master, Sercos slave switch integrated (figure

More information

Article no. BWU2045: AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input 1.23 NC

Article no. BWU2045: AS-i Safety Relay Output Module with Diagnostic Slave and 1 EDM Input 1.23 NC Safety + standard I/O in one module AS-i Safety relay output with galvanically isolated contact sets, approved up to 230 V IEC 61508 SIL 3, EN ISO 13849-1/PLe Kat 4, EN 62061 SIL 3 Protection category

More information

CU-DIN USB KNX EC

CU-DIN USB KNX EC CU-DIN USB KNX EC10430541 MA00653301 Table of contents 1 Description...2 2 Safety instructions...3 3 Dimension drawings...4 4 Technical data...5 5 Product disposal...6 6 ESYLUX manufacturer s guarantee...6

More information

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output Product datasheet Characteristics XPSMF4000 Preventa safety PLC compact - Safe Ethernet Main Range of product Product or component type Safety module name Safety module application Preventa Safety automation

More information

252F 5WG FB_1 DELTA

252F 5WG FB_1 DELTA Product DELTA i-system DELTA profil Fan-Coil Unit Operator Panels Hotel titanium white 5WG1 237-2FB11 pearl grey 5WG1 252-2FB01 carbon metallic 5WG1 237-2FB21 titanium white 5WG1 252-2FB11 aluminum metallic

More information

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

PHOENIX CONTACT - 08/2009. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area. Primary-switched power supply for building automation INTERFACE Data sheet 103505_en_02 1 Description PHOENIX CONTACT - 08/2009 Features STEP POWER power supply units for building automation The new STEP

More information

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC

RM35TF. Main. Product or component type. Product specific application. Relay monitored parameters 250 V AC 5 A AC Characteristics multifunction phase control relay RM35-T - range 194..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage

More information

Installation and commissioning guide SmartLink PSD Power Supply Module (DC)

Installation and commissioning guide SmartLink PSD Power Supply Module (DC) Installation and commissioning guide SmartLink PSD Power Supply Module (DC) Rev. 1 September 2012 Part No. 4417551 Enraf B.V. P.O. Box 812 2600 AV Delft Netherlands Tel. : +31 15 2701 100 Fax : +31 15

More information

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.:

IL CAN BK-TC-PAC. Extract from the online catalog. Order No.: Extract from the online catalog IL CAN BK-TC-PAC Order No.: 2718701 CANopen bus coupler, 24 V DC, bus interface 2 x 5-pos. TWIN- COMBICON connector, complete with accessories (connector and labeling field)

More information

Power Supply System KNX PS640-IP

Power Supply System KNX PS640-IP Power Supply System KNX PS640-IP with Ethernet Interface Installation and Adjustment Elsner Elektronik GmbH Steuerungs- und Automatisierungstechnik Herdweg 7 D-75391 Gechingen Germany Phone: +49 (0) 70

More information