F35. Multilin FEEDER PROTECTION SYSTEM. Cost-effective protection and control for single/multiple distribution feeders KEY BENEFITS APPLICATIONS
|
|
- Evelyn May
- 5 years ago
- Views:
Transcription
1 Multilin F35 FEEDER PROTECTON SYSTEM Cost-effective protection and control for single/multiple distribution feeders KEY BENEFTS Cost effective and flexible protection and control device for distribution feeder applications Complete EC 850 Process Bus solution providing resource optimization and minimizing total P&C life cycle costs mproved system stability at reduced cost - Control schemes using hi-speed communications High-end fault and disturbance recording, including internal relay operating signals thus eliminating the need for redundant recording devices Robust network security enabling Critical nfrastructure Protection through user command logging, and dual permission access control APPLCATONS Primary protection and control for multiple distribution feeders Distribution load shedding schemes based on voltage and frequency elements FEATURES Protection and Control nstantaneous and time phase overcurrent protection Thermal overload, nstantaneous and time ground/ neutral/negative sequence overcurrent protection Neutral and auxiliary overvoltage Phase and auxiliary undervoltage Under frequency Four shot autoreclose for up six breakers and Broken conductor elements Built-in selector switch Communications Networking interfaces 00Mbit Fiber Optic Ethernet, RS485, RS3, RS4, G.703, EEE C37.94 Multiple Protocols - EC850, DNP 3.0 Level, Modbus RTU, Modbus TCP/P, EC , Ethernet Global Data (EGD) Direct /O secure, high-speed exchange of data between URs for Direct Transfer Trip applications Embedded Managed Ethernet Switch with 4-00 Mbit Fiber optic ports and copper ports g Digital Energy Accurate built-in metering functions - Eliminates auxiliary metering devices and reduces cost Advanced automation capabilities for providing customized protection and control solutions Simplified system integration with communications supporting serial and Ethernet interfaces and multiple protocols Reduced relay to relay wiring and associated installation costs through high-speed inter-relay communications Embedded EC850 Protocol with no external communications hardware required Ambient temperature monitoring with alarming when outside temperature exceeds upper thresholds Busblocking/ interlocking schemes Throw over schemes (bus transfer scheme applications) Distributed Generation (DG) interconnect protection, including active and passive anti-islanding EC 850 Process Bus nterface Robust communications with up to 8 HardFiber Bricks Seamless integration with existing F35 functions Redundant architecture for dependability and security Monitoring and Metering Metering - current, voltage, power, energy, frequency Oscillography analog and digital parameters at 4 samples/cycle Event Recorder - 04 time tagged events with 0.5ms scan of digital inputs Data Logger - channels with sampling rate up to sample / cycle Setting Security Audit Trail for tracking changes to F35 configuration Enerista Software Graphical Logic Designer and Logic Monitor to simplify designing and testing procedures Document and software archiving toolset to ensure reference material and device utilities are up-to-date Enerista ntegrator providing easy integration of data in the F35 into new or existing monitoring and control systems 309
2 Protection and Control The F35 Feeder Protection System provides feeder protection, control, monitoring and metering in an integrated, economical, and compact package. As part of the Universal Relay (UR) Family, the F35 provides costeffective solutions and features high performance protection, expandable /O options, integrated monitoring and metering, high-speed communications, and extensive programming and configuration capabilities. The F35 can be configured to protect up to six feeders or protect up to five feeders when bus voltage measurement is required. t also provides fast and deterministic execution of programmable logic necessary for substation automation applications. Graphical programming tools (iewpoint Engineer), supported by a library of logic components, make the F35 simple to use and configure. The F35 has a wide range of protection elements that have many years of proven field experience. Protection and control features includes: Overcurrent Protection The F35 has built-in standard EEE, EC, AC and FlexCurves overcurrent characteristics (TOC), most commonly used for primary and back up protection in various protective zones. The F35 has Thermal overload and phase OC elements with level detectors for each phase. Each TOC element has the following programmable characteristics: F35 - Protection, Metering, Monitoring and Control The F35 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like iewpoint Monitoring as shown. Pickup current level for trip, alarm, or control Choice of 7 curve shapes (including FlexCurves) and curve multipliers nstantaneous or linear reset time characteristic to coordinate with upstream transformer damage curves and downstream reclosers and fuses. oltage restraint to increase sensitivity The majority of distribution systems are either solidly grounded or through a low impedance. Fast fault clearance is required due to the ground fault impact. Following functions are incorporated in F35 to provide ground protection: Neutral OC and TOC Ground OC and TOC Negative Sequence OC and TOC Sensitive Ground nput The F35 CT/T modules may be ordered with a sensitive ground current input, which provides ground fault protection on high impedance grounded systems. This can be especially important when using a residual CT connection to detect ground faults. Functional Block Diagram 5 Monitoring 50P 5P 50_ 5_ 49 50N 50G 79 5G CLOSE TRP METERNG FlexElement TM Transducer nputs 5N Same Functions as Breaker For Breaker 7X 7P 8U 59N 59X ANS Device Numbers & Functions Device Number Function 7P Phase Undervoltage 7X Auxiliary Undervoltage 49 Thermal Overload 50G Ground nstantaneous Overcurrent 50N Neutral nstantaneous Overcurrent 50P Phase nstantaneous Overcurrent 50_ Negative Sequence nstantaneous Overcurrent 5G Ground Time Overcurrent 5N Neutral Time Overcurrent 5P Phase Time Overcurrent 5_ Negative Sequence Time Overcurrent 5 AC Circuit Breaker 59N Neutral Overvoltage 59X Auxiliary Overvoltage 79 Automatic Recloser 8 Underfrequency F35 Multiple Feeder Protection System 30
3 Comprehensive Protection & Control CB Cost-effective single box auto-transfer scheme solution Under/Over oltage Protection The F35 includes the following voltage elements: Up to phase undervoltage elements Up to 3 auxiliary undervoltage/ overvoltage elements Up to 3 neutral overvoltage elements The following are some of the key applications where voltage elements can be used: Source transfer schemes Load shedding schemes Back up capacitor bank protection and control Backup motor protection to prevent automatic restart. Source CB Fault F35 CB TCB CB3 CB4 CB5 CB Autorecloser Up to programmable breaker autoreclosers for a variety of reclosing practices are provided. These elements are intended for use with distribution lines in tripping schemes for single breaker applications. Up to four selectable reclosers shots are possible prior to locking out. EC 850 Process Bus The EC 850 Process Bus module is designed to interface with the Multilin HardFiber System, allowing bi-directional EC 850 fiber optic communications. The HardFiber System is designed to integrate seamlessly with the existing Universal Relay applications, including protection functions, FlexLogic, metering and communications. Fiber LAN, single or redundant, for added security Fault Reverse zone interlocking protection - By using the EC850 GOOSE or hi-speed Direct /O capability blocking signals can be transferred upstream, allowing minimal coordination delays. Fast clearance can be provided for Fault and still maintain coordination for Fault. CB3 CB The Multilin HardFiber System offers the following benefits: Communicates using open standard EC 850 messaging Drastically reduces P&C design, installation and testing labor by eliminating individual copper terminations ntegrates with existing F35 s by replacing traditional CT/T inputs with EC 850 Process Bus module Does not introduce new Cyber Security concerns isit the HardFiber System product page on the GE Digital Energy web site for more details. Advanced Automation The F35 incorporates advanced automation features including powerful FlexLogic programmable logic, communication, and SCADA capabilities that far surpass what is found in the average line relay. The F35 integrates seamlessly with other UR relays for complete system protection, including the unit and auxiliary transformers, and Balance of Plant protection. FlexLogic FlexLogic is the powerful UR-platform programming logic engine that provides the ability of creating customized protection and control schemes thereby minimizing the need, and the associated costs, of auxiliary components and wiring. Using FlexLogic, the F35 can be programmed to provide required tripping logic along with custom scheme logic for line phase comparison (including interlocking with external synchronizers), transfer tripping schemes for remote breakers and dynamic setting group changes. Scalable Hardware The F35 is available with a multitude of /O configurations to suit the most demanding application needs. The expandable modular design allows for easy configuration and future upgrades. Multiple CT/T configurations allow for implementation of many differential schemes, including concurrent splitphase and differential protection 3
4 FlexLogic TM Designer Advanced Device Health Diagnostics The F35 performs comprehensive device health diagnostic tests during startup and continuously at runtime to test its own major functions and critical hardware. These diagnostic tests monitor for conditions that could impact security and availability of protection, and present device status via SCADA communications and front panel display. Providing continuous monitoring and early detection of possible issues helps improve system uptime. Comprehensive device health diagnostic performed during startup Monitors the CT/T input circuitry to validate the integrity of all signals nput, outputs, trip circuits and analog channels are continuously monitored for accuracy and performance FlexLogic allows for customizing the F35 to operate and control the breakers and other auxiliary devices needed to fit most protection schemes and applications. Up to 80 digital inputs and up to 5 digital outputs are available Types of digital outputs include triprated Form-A and Solid State Relay (SSR) mechanically latching, and Form-C outputs Form-A and SSR outputs available with optional circuit continuity monitoring and current detection to verify proper operation of the connected primary equipment Mechanically latching outputs can be used to develop secure interlocking applications and replace electromechanical lockout relays RTDs and DCmA inputs are available to monitor equipment parameters such as temperature & pressure Monitoring and Metering The F35 includes high accuracy metering and recording for all AC signals. oltage, current, and power metering are built into the relay as a standard feature. Current and voltage parameters are available as total RMS magnitude, and as fundamental frequency magnitude and angle. Fault and Disturbance Recording The advanced disturbance and event recording features within the F35 can significantly reduce the time needed for postmortem analysis of power system events and creation of regulatory reports. Recording functions include: Sequence of Event (SOE) - 04 time stamped events Oscillography, - 4 digital & up to 40 Analog channels Data Logger, disturbance recording channels up to sample / cycle / channel Fault Reports - Powerful summary report of pre-fault and fault values The very high sampling rates and large amount of storage space available for data recording in the F35 can eliminate the need for installing costly standalone recording equipment. Communications The F35 provides advanced communications technologies for remote data and engineering access, making it the easiest and most flexible feeder protection relay to use and integrate into new and existing infrastructures. Direct support for fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available redundant Ethernet option and the embedded managed Ethernet switch provide the means of creating fault tolerant communication architectures in an easy, cost-effective manner without the need for intermediary communication hardware. The F35 supports the most popular industry standard protocols enabling easy, direct integration into DCS and SCADA systems. EC850 DNP3.0 Ethernet Global Data (EGD) EC Modbus RTU, Modbus TCP/P 3
5 nteroperability with Embedded EC850 Use the F35 with integrated EC850 to lower costs associated with substation protection, control and automation. GE Energy s leadership in EC850 comes from thousands of installed devices and follows on seven years of development experience with UCA.0. Replace expensive copper wiring between devices with direct transfer of data using GOOSE messaging Configure systems based on EC850 and also monitor and troubleshoot them in real-time with Enerista iewpoint Engineer ntegrate Multilin EDs and generic EC850-compliant devices seamlessly in Enerista iewpoint Monitoring Direct /O Messaging Direct /O allows for sharing of high-speed digital information between multiple UR relays via direct back-to-back connections or multiplexed through a standard DS0 multiplexer channel bank. Regardless of the connection method, Direct /O provides continuous real-time channel monitoring that supplies diagnostics information on channel health. Direct /O provides superior relay-to-relay communications that can be used in advanced interlocking, generation rejection and other special protection schemes. Communication with up to UR relays in single or redundant rings rather than simplistic point-to-point configurations Connect to standard DS0 channel banks through standard RS4, G.703 or EEE C37.94 interfaces or via direct fiber optic connections Built-in continuous loop and channel monitoring provides real-time diagnostics of your communication channels no external or handheld tester required Multi-Language The F35 supports English, French, Russian, and Chinese languages on the front panel, Enerista setup software, and product manual. Easily switch between English and an additional language on the local displays without uploading new firmware. Enerista TM Software The Enerista Suite is an industry-leading set of software programs that simplifies every aspect of using the F35 relay. The Enerista suite provides all the tools to monitor the status of feeders, maintain the relay, and integrate information measured by the F35 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR Setup software included with every UR relay, to carry out postmortem event analysis to ensure proper protection system operation. Enerista Launchpad Enerista Launchpad is a powerful software package that provides users with all of the setup and support tools needed for configuring and maintaining Multilin products. The setup software within Power System Troubleshooting The F35 contains many tools and reports that simplify and reduce the amount of time required for troubleshooting power system events. Analyze feeder faults using both analog and digital power system quantities that are measured and recorded up to a rate of 4 samples per cycle. Record the operation of the internal F35 elements and external connected devices with ms time-stamped accuracy to identify the Sequence of Operation of station devices during feeder faults and disturbances. 33
6 Launchpad allows configuring devices in real-time by communicating using serial, Ethernet, or modem connections, or offline by creating setting files to be sent to devices at a later time. ncluded in Launchpad is a document archiving and management system that ensures critical documentation is up-to-date and available when needed. Documents made available include: Manuals Application Notes Guideform Specifications Brochures Wiring Diagrams FAQ s Service Bulletins iewpoint Monitoring iewpoint Monitoring is a simple-to-use and full-featured monitoring and data recording software package for small systems. iewpoint Monitoring provides a complete HM package with the following functionality: Plug-&-Play Device Monitoring System Single-Line Monitoring & Control Annunciator Alarm Screens Trending Reports Automatic Event Retrieval Automatic Waveform Retrieval iewpoint Engineer iewpoint Engineer is a set of powerful tools that will allow you to configure and test UR relays at a system level in an easy-to-use graphical drag-and-drop environment. iewpoint Engineer provides the following configuration and commissioning utilities: Graphical Logic Designer Graphical System Designer Graphical Logic Monitor Graphical System Monitor iewpoint Maintenance iewpoint Maintenance provides tools that will create reports on the operating status of the relay, simplify the steps to download fault and event data, and reduce the work required for cyber-security compliance audits. Tools available in iewpoint Maintenance include: Settings Security Audit Report Device Health Report Single Click Fault Data Retrieval Enerista ntegrator Enerista ntegrator is a toolkit that allows seamless integration of Multilin devices into new or existing automation systems. ncluded in Enerista ntegrator is: OPC/DDE Server Multilin Drivers Automatic Event Retrieval Automatic Waveform Retrieval User nterface The F35 front panel provides extensive local HM capabilities. The local display is used for monitoring, status messaging, fault diagnosis, and device configuration. User configurable messages that combine text with live data, can be displayed when user-defined conditions are met. LED ndicators Multi-Language Display English Russian French Chinese User Programmable Pushbuttons 34
7 F35 Feeder Protection System Typical Wiring F35-H00-HCH-F8H-HG-M8H-PG-U8F-WG 8377A5.CDR Power Supply 9 CPU 8 CT nputs/ outputs 8 CT 8 CT/T nputs/ outputs nputs/ outputs J U M X L W K B H T D N G F P S R F35 DC UR COMPUTER TXD RXD RXD TXD SGND SGND CONNECTOR CONNECTOR RS-3 (front) DB-9 CRTCAL FALURE OUTPUT CONTROL POWER H LO FLTER SURGE B3a Bb B8a Bb B8b Ba B3b Ba Bb B5b Pa Pb Pc Pb Pc Pa P4a P4c P3b P3a P4b P3c SURGE Pa P8a P5b P7b P8b P5a P7a Pc P8c P5c P7c P P P3 P4 G Ha Hb Hc Hb Hc Ha H4a H4c H3b H3a H4b H3c SURGE Ha H8a H5b H7b H8b H5a H7a Hc H8c H5c H7c H H H3 H4 G Wa Wb Wc Wb Wc Wa W4a W4c W3b W3a W4b W3c SURGE Wa W8a W5b W7b W8b W5a W7a Wc W8c W5c W7c W W W3 W4 G Uc U4a U3c U5a U5c U7c Ua U7a Uc Uc A B C U4c Ua U4b Ub Ua U3a Ub U3b A B C A B C G A5 A B5 C5 G5 B C G F7c F8c F8b F8a F5c F5a F5b F7b F3c F4b F4a F4c Fc Fa Fb F7a Fa Fb Fc Fc Fa Fb F3a F3b A B C G A5 A B5 C5 G5 B C G A B C G A5 A B5 C5 G5 B C G C A M7c M8c M8b M8a M5c M5a M5b M7b M3c M4b M4a M4c Mc Ma Mb M7a Ma Mb Mc Mc Ma Mb M3a M3b A B C G A5 A B5 C5 G5 B C G A B C G A5 A B5 C5 G5 B C G A B C Minimum PRODED TC TC CONNECTON U8c U8a X X U5a U5c U7c Ua U7a Uc A B C A B C Da Da D4b D3a D4a RG-B nput RG-B Output COM RS485 ALTERNATE NORMAL com 0BaseT 0BaseFL 0BaseFL Tx Rx Tx Rx BNC BNC Fibre Optic * Remote Device Shielded Co-axial Co-axial Digital Energy Multilin
8 Ordering F35 - * ** - H * * - F ** - H ** - M ** - P **- U ** - W * For Full Sized Horizontal Mount Base Unit F35 Base Unit CPU E RS485 + RS485 (EC850 option not available) G RS485 + Multi-mode ST 0BaseF H RS485 + Mutli-mode ST Redundant 0BaseF J RS485 + Multi-mode ST 00BaseFX K RS485 + Multi-mode ST Redundant 00BaseFX N RS /00 BaseT S RS485 + port, 00 Mbps, Managed Ethernet Switch Software Options 00 No Software Options 03 EC850 Mount / Coating H Horizontal (9" rack) - Standard A Horizontal (9" rack) - Harsh Chemical Environment Option ertical (3/4 size) - Standard B ertical (3/4 size) - Harsh Chemical Environment Option User nterface K Enhanced English Front Panel L Enhanced English Front Panel with User-Programmable Pushbuttons M Enhanced French Front Panel N Enhanced French Front Panel with User-Programmable Pushbuttons Q Enhanced Russian Front Panel T Enhanced Russian Front Panel with User-Programmable Pushbuttons U Enhanced Chinese Front Panel Enhanced Chinese Front Panel with User-Programmable Pushbuttons F ertical Front Panel with English display Power Supply H 5 / 50 AC/DC H RH 5/50 AC/DC with redundant 5/50 AC/DC power supply L 4-48 (DC only) CT/T DSP 8F 8F 8F Standard 4CT/4T 8G 8G 8G Sensitive Ground 4CT/4T 8H 8H 8H Standard 8CT 8J 8J 8J Sensitive Ground 8CT 8L 8L 8L Standard 4CT/4T w/ enhanced diagnostics 8M 8M 8M Sensitive Ground 4CT/4T w/ enhanced diagnostics 8N 8N 8N Standard 8CT w/ enhanced diagnostics 8R 8R 8R Sensitive Ground 8CT w/ enhanced diagnostics EC 850 Process Bus 8 8 Port EC 850 Process Bus Module Digital /O XX XX XX XX XX No Module 4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs 4C 4C 4C 4C 4C 4 Solid State (Current w/opt oltage) MOSFET Outputs 4D 4D 4D 4D 4D Digital nputs with Auto-Burnish 4L 4L 4L 4L 4L 4 Form-A (No Monitoring) Latchable Outputs Form-A (No Monitoring) Outputs C C C C C 8 Form-C Outputs D D D D D Digital nputs E E E E E 4 Form-C Outputs, 8 Digital nputs F F F F F 8 Fast Form-C Outputs K K K K K 4 Form-C & 4 Fast Form-C Outputs L L L L L Form-A (Current w/ opt oltage) & Form-C Outputs, 8 Digital nputs M M M M M Form-A (Current w/ opt oltage) & 4 Form-C Outputs, 4 Digital nputs N N N N N 4 Form-A (Current w/ opt oltage) Outputs, 8 Digital nputs P P P P P Form-A (Current w/ opt oltage) Outputs, 4 Digital nputs R R R R R Form-A (No Monitoring) & Form-C Outputs, 8 Digital nputs S S S S S Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital nputs T T T T T 4 Form-A (No Monitoring) Outputs, 8 Digital nputs U U U U U Form-A (No Monitoring) Outputs, 4 Digital nputs Form-A (Cur w/ opt olt) Form-C Output, Latching Outputs, 8 Digital nputs Transducer /O 5A 5A 5A 5A 5A 4 dcma nputs, 4 dcma Outputs 5C 5C 5C 5C 5C 8 RTD nputs 5D 5D 5D 5D 5D 4 RTD nputs, 4 dcma Outputs 5E 5E 5E 5E 5E 4 dcma nputs, 4 RTD nputs 5F 5F 5F 5F 5F 8 dcma nputs nter-relay Communications 7A 80 nm, multi-mode, LED, Channel 7B 300 nm, multi-mode, LED, Channel 7C 300 nm, single-mode, ELED, Channel 7H 80 nm, multi-mode, LED, Channels nm, multi-mode, LED, Channels 7J 300 nm, single-mode, ELED, Channels 7S G.703, Channels 7T RS4, Channel 7W RS4, Channels 7 EEE C37.94, 80 nm, multimode, LED, Channel 77 EEE C37.94, 80 nm, multimode, LED, Channel S port, 00 Mbps, Managed Ethernet Switch, H (5/50 AC/DC) T port, 00 Mbps, Managed Ethernet Switch, LO (4-48 dc) Accessories for the F35 UR Applications Learning CD TRCD-URA-C-S- Multilink Ethernet Switch ML400-F-H-H-A-A-A-G iewpoint Engineer PE- iewpoint Maintenance PM- iewpoint Monitoring EC850 P--850 isit to: iew Guideform specifications Download the instruction manual Review applications notes and support documents Buy a F35 online iew the UR Family brochure Ordering Note: To view the latest options available for the F35, or to order the UR Classic Front Panel, please visit our online store for more details v3
T35. g Multilin. Cost effective differential protection for transformers with up to 6 sets of CTs. Protection and Control
T35 Transformer Protection System Cost effective differential protection for transformers with up to sets of CTs Key Benefits Secure high-speed transformer differential protection with advanced features
More informationN60. Network Stability. Load shedding, remedial action, special protection schemes and synchrophasors. Features. Protection and Control
N60 Network Stability and synchrophasor Load shedding, remedial action, special protection schemes and synchrophasors Key differentiators Scalable Synchrophasor measurements with up to 4 PMUs per ED reducing
More informationN60. Multilin. NETWORK STABILITY & SYNCHROPHASOR MEASUREMENT Synchrophasors, load shedding, remedial action, special protection schemes KEY BENEFITS
Multilin N60 NETWORK STABLTY & SYNCHROPHASOR MEASUREMENT Synchrophasors, load shedding, remedial action, special protection schemes KEY BENEFTS Scalable Synchrophasor measurements with up to 4 PMUs per
More informationT35. Multilin TRANSFORMER PROTECTION SYSTEM. Cost-Effective Differential Protection for Transformers with up to 6 Sets of CTs KEY BENEFITS
Multilin T35 TRANSFORMER PROTECTON SYSTEM Cost-Effective Differential Protection for Transformers with up to Sets of CTs KEY BENEFTS Secure high-speed transformer differential protection with advanced
More informationC30. Multilin CONTROLLER SYSTEM. Substation Hardened Programmable Logic Controller KEY BENEFITS APPLICATIONS FEATURES. IEC Process Bus Interface
Multilin C30 CONTROLLER SYSTEM Substation Hardened Programmable Logic Controller KEY ENEFTS Powerful and deterministic programmable logic suitable for creating most customized automated substation control
More informationL90. Multilin LINE CURRENT DIFFERENTIAL SYSTEM. Phase segregated line current differential and distance protection KEY BENEFITS APPLICATIONS FEATURES
Multilin L90 LNE CURRENT DFFERENTAL SYSTEM Phase segregated line current differential and distance protection KEY BENEFTS Phase segregated differential protection ensures secure high-speed single pole
More informationKEY BENEFITS APPLICATIONS FEATURES
KEY BENEFTS Easily meet stability requirements - sub-cycle trip time (average of 0.75 power cycle, maximum 1 power cycle) Dependable and secure - Performance backed up by many years of field experience
More informationB30. Multilin BUS DIFFERENTIAL SYSTEM. Cost effective low impedance biased bus differential protection for up to six feeders KEY BENEFITS APPLICATIONS
Multilin B30 BU DFFERENTAL YTEM Cost effective low impedance biased bus differential protection for up to six feeders KEY BENEFT High speed differential protection algorithm for enhanced with ubcycle trip
More informationT60. Multilin TRANSFORMER PROTECTION SYSTEM. Fully featured, multiple winding transformer protection KEY BENEFITS APPLICATIONS FEATURES
ultilin T0 TRANSFORER PROTECTON SYSTE Fully featured, multiple winding transformer protection KEY BENEFTS Secure high-speed protection for transformers, compliant with EEE C37.91 Complete EC 1850 Process
More informationG30. Multilin GENERATOR PROTECTION SYSTEM. Protection for Small to Medium Generators, Combined Generators and Transformers KEY BENEFITS APPLICATIONS
Multilin G30 GENERATOR PROTECTON SYSTEM Protection for Small to Medium Generators, Combined Generators and Transformers KEY BENEFTS Complete protection for small to medium-sized generators Advanced automation
More informationF60. Multilin FEEDER PROTECTION SYSTEM. Advanced Protection, Control and Automation for Distribution Feeders KEY BENEFITS APPLICATIONS FEATURES
Multilin 60 EEDER PROTECTION SYSTEM Advanced Protection, Control and Automation for Distribution eeders KEY BENEITS The most flexible protection and control device for distribution feeder applications
More informationD60. Multilin LINE DISTANCE PROTECTION SYSTEM. High-speed transmission line protection with three/single pole tripping KEY BENEFITS APPLICATIONS
Multilin D60 LNE DSTANCE PROTECTON SYSTEM High-speed transmission line protection with three/single pole tripping KEY BENETS High-speed cost effective five zone quad or mho, phase and ground distance protection
More informationL60. Multilin LINE PHASE COMPARISON SYSTEM. Sub-Cycle Phase Comparison and Distance Protection KEY BENEFITS APPLICATIONS FEATURES
Multilin L0 LNE PHASE COMPARSON SYSTEM Sub-Cycle Phase Comparison and Distance Protection KEY BENEFTS Extremely fast and secure phase comparison protection with a typical tripping time of ¾ of a power
More informationC70. Multilin CAPACITOR BANK PROTECTION SYSTEM. Capacitor Banks Protection & Control KEY BENEFITS APPLICATIONS FEATURES
Multilin 70 APATOR BANK PROTETON SYSTEM apacitor Banks Protection & ontrol KEY BENEFTS Protect capacitor banks of a variety of configurations with sensitive current and voltage balance protection functions
More informationMultilin N60. Protection & Control. Synchrophasors, Load Shedding, Remedial Action, Special Protection Schemes. Communications. Monitoring & Metering
Multilin N60 Synchrophasors, Load Shedding, Remedial Action, Special Protection Schemes The Multilin N60 network stability and synchrophasor measurement system is a flexible device intended for the development
More informationMultilin D30. High-Speed Primary and Backup Distance Protection. Protection & Control. Advanced Communications. Cyber Security. Monitoring & Metering
Multilin D30 High-Speed Primary and Backup Distance Protection The Multilin D30 is a cost-effective distance protection relay intended for protecting sub-transmission lines and underground cables of different
More informationMultilin F60. Advanced Protection, Control & Automation for Distribution Feeders. Protection & Control. Communications.
Multilin 60 Advanced Protection, Control & Automation for Distribution eeders The Multilin 60 eeder Protection System provides feeder protection, control, monitoring and metering in an integrated, economical,
More informationL90. Multilin LINE CURRENT DIFFERENTIAL SYSTEM. Line Protection System with Segregated Line Current Differential and Complete Distance Protection
Multilin L90 LNE CURRENT DFFERENTAL SYSTEM Line Protection System with Segregated Line Current Differential and Complete Distance Protection KEY BENEFTS Phase segregated differential protection ensures
More informationT60. Multilin TRANSFORMER PROTECTION SYSTEM. Full-Featured, Multiple-Winding Transformer Protection KEY BENEFITS APPLICATIONS FEATURES
ultilin T0 TRANSFORER PROTECTON SYSTE Full-Featured, ultiple-winding KEY BENEFTS Secure high-speed protection for transformers, compliant with EEE C37.91 mproved security for transformer energization and
More informationMultilin F60. Grid Solutions. Advanced Protection, Control & Automation for Distribution Feeders. Protection & Control. Advanced Communications
Grid Solutions Multilin 60 Advanced Protection, Control & Automation for Distribution eeders The Multilin TM 60 eeder Protection System provides feeder protection, control, monitoring and metering in an
More informationMultilin B30. Low Impedance Biased Bus Differential Protection for up to Six Feeders. Protection and Control. Communications.
Multilin B30 Low mpedance Biased Bus Differential Protection for up to ix Feeders The Multilin B30 bus differential system provides secure and sub-cycle low impedance bus protection for a single busbar
More informationC60. Multilin BREAKER PROTECTION SYSTEM. Breaker Monitoring and Control for Substation and Industrial Automation KEY BENEFITS APPLICATIONS FEATURES
ultilin C60 BREAKER PROTECTON SYSTE Breaker onitoring and Control for Substation and ndustrial Automation KEY BENETS g imagination Complete breaker control, protection, monitoring and integration in a
More informationMultilin T60. Grid Solutions. Protection & Control. Full-Featured, Multiple-Winding Transformer Protection. Communications. Monitoring & Metering
Grid Solutions ultilin T0 Full-Featured, ultiple-winding Transformer Protection The ultilin T0 transformer protection system is a comprehensive three-phase transformer relay designed to protect medium
More informationMultilin G60. Grid Solutions. Comprehensive Protection for Generators. Protection and Control. Advanced Communications.
Grid Solutions Multilin G60 Comprehensive Protection for Generators The Multilin TM G60 generator protection system provides comprehensive protection for medium and large generators, including large steam
More informationF650 - More than Feeder Protection & Control. GE Consumer & Industrial Multilin
F650 - More than Feeder Protection & Control F650 Bay Controller A Comprehensive Protection and Control solution for Transmission and Distribution Networks 2 Introduction: What is the F650? Protection,
More informationGE Multilin 350 Feeder Protection Relay Specifications
GE Multilin 350 Feeder Protection Relay Specifications The feeder protection relay shall provide primary protection of medium voltage distribution feeders. The relay shall be equipped with the following
More informationSR489 SR489. Generator Management Relay. Economical protection, metering, and monitoring functions for small and medium sized generators.
SR489 Generator Management Relay Economical protection, metering, and monitoring functions for small and medium sized generators. 1 Product Highlights Inputs / Outputs Generator Protection Power Metering
More informationGE Power Management. UR F60 Feeder Management Relay An integrated feeder protection and metering solution
UR An integrated feeder protection and metering solution Power to Manage your Facility Connectivity ModBus RTU MMS/UCA2 TM Protocols SI Compatibility Flexibility FlexCurves FlexLogic The first Relay designed
More informationM60 Motor Relay. UR Series Instruction Manual. GE Industrial Systems. Title Page. M60 Revision: 3.4x
Title Page g GE Industrial Systems M60 Motor Relay UR Series Instruction Manual M60 Revision: 3.4x Manual P/N: 1601-0108-F4 (GEK-106446C) Copyright 2009 GE Multilin 833711A1.CDR E83849 GE Multilin 215
More informationIndustrial & Plant Communication Applications Seminar. April 3, 2006 College Station TX
Industrial & Plant Communication Applications Seminar April 3, 2006 College Station TX Why Network or Integrate? Meet Facility Operations & Engineering Goals Keep Plant Up & Running Operate Plant Efficiently
More informationUR Universal Relay Series
GE Digital Energy UR Universal Relay Series Revision 4.43 Release Notes GE Publication Number: GER-4380Rev1 Copyright 2010 GE Multilin Summary Overview GE Multilin issues the UR 4.43 release that introduces
More informationRecloser Controller for feeder protection and automation siemens.com/distribution-automation
SIPROTEC 7SC80 Control Controller for feeder protection and automation siemens.com/distribution-automation SIPROTEC 7SC80 Control Designed for feeder automation applications This solution allows very fast
More informationg GE Power Management UR - The Universal Relay
UR - The Universal Relay UR Features FAMILY of relays built on a common platform Common look & feel for ease of use product to product All bells & whistles, present and future, available to whole family
More informationB30 Bus Differential Relay
Title Page g GE Industrial Systems B30 Bus Differential Relay UR Series Instruction Manual B30 revision: 3.4x Manual P/N: 1601-0109-F4 (GEK-106436C) Copyright 2009 GE Multilin 836770A1.CDR E83849 GE Multilin
More informationA low-cost, economical solution for distribution feeder protection
SEL-351A Protection System A low-cost, economical solution for distribution feeder protection Achieve sensitive and secure fault detection using comprehensive protection functions. Track breaker status
More informationUR Universal Relay Series
GE Consumer & Industrial UR Universal Relay Series Revision 5.40 Release otes GE Publication umber: GER-4109 Copyright 2007 GE Multilin Overview Summary GE Multilin issues the UR 5.40 release that introduces
More informationSIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities.
www.siemens.com/protection SIPROTEC 7SC80 Feeder Protection and Automation Answers for infrastructure and cities. designed for feeder automation applications This solution allows very fast fault detection
More informationB30 Bus Differential Relay
Title Page g GE Industrial Systems B30 Bus Differential Relay UR Series Instruction Manual B30 revision: 4.9x Manual P/N: 1601-0109-M2 (GEK-113119A) Copyright 2006 GE Multilin 836770A1.CDR GE Multilin
More informationN60 Network Stability and Security Relay
Title Page g GE Industrial Systems N60 Network Stability and Security Relay UR Series Instruction Manual N60 Revision: 4.4x Manual P/N: 1601-0125-J2 (GEK-112996A) Copyright 2005 GE Multilin 832761A1.CDR
More informationAdvanced distribution feeder solution with integrated protection, monitoring, and control
Protection System Advanced distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions. Keep track
More informationBus Bar Protection Relay B-PRO 4000
Bus Bar Protection Relay B-PRO 4000 Product Overview The IEC 61850 station bus embedded B-PRO 4000 relay provides complete bus and substation differential protection (low impedance) with CT saturation
More informationAdvanced Line Differential Protection, Automation, and Control System. Combine subcycle line protection with traveling-wave fault locating
Advanced Line Differential Protection, Automation, and Control System Combine subcycle line protection with traveling-wave fault locating Subcycle differential and distance protection minimizes damage
More informationProtection, Automation, and Control System. Combine subcycle line protection with complete substation bay control
Protection, Automation, and Control System Combine subcycle line protection with complete substation bay control Subcycle distance protection minimizes damage and expensive repairs on transmission lines.
More informationSubstation Automation Products. Line differential protection RED670 Relion 670 series
Substation Automation Products Line differential protection RED670 Relion 670 series For maximum reliability of your power system The RED670 IED (Intelligent Electronic Device) is designed for protection,
More informationSEL-487B. A Powerful Solution for Busbar Differential Protection. Bus Differential and Breaker Failure Relay
Bus Differential and Breaker Failure Relay A Powerful Solution for Busbar Differential Protection Features and Benefits Select the for the differential protection of busbar systems with up to 18 terminals.
More informationg Energy Multilin Voltage Regulator Controller DGCV KEy BENEFITS APPLICATIONS FEATURES Metering & Monitoring Voltage Regulation Communications
Multilin Voltage Regulator DGCV KEy BENEFITS Increases grid efficiency by optimizing voltage regulation Through deployment of the Volt/VAR system, the Multilin DGCV: - Enables up to a 6% reduction in energy
More informationMultiLink. HARDENED ETHERNET SWITCHES Ethernet Communications for Industrial Automation, Power Utility, and Traffic Control markets KEY BENEFITS
MultiLink KEY BENEFITS HARDENED ETHERNET SWITCHES Ethernet Communications for Industrial Automation, Power Utility, and Traffic Control markets Physically hardened and environmentally ruggedized for reliability
More informationC30. Controller System. Instruction Manual AF2. GE Grid Solutions. Product version: 7.6x GE publication code: AF2 (GEK A)
GE Grid Solutions C30 Controller System Instruction Manual Product version: 7.6x GE publication code: 1601-0088-AF2 (GEK-130993A) E83849 LISTED IND.CONT. EQ. 52TL 1601-0088-AF2 Copyright 2017 GE Multilin
More informationUR Universal Relay Series
GE Digital Energy UR Universal Relay Series Revision 5.90 Release otes GE Publication umber: GER-4401 Copyright 2010 GE Multilin Summary Overview GE Multilin issues the UR 5.90 release that introduces
More informationMIN II. Complete numerical ground directional protection. Digital Energy Multilin. Protection and Control. Monitoring and Metering.
MIN II Key Benefits Reduce troubleshooting and maintenance cost - event recording, and analogy/digital oscillography Design flexibility - Easy to use programming logic Access to information - Modbus RTU
More informationN60 Network Stability and Synchrophasor Measurement System
Title Page g GE Industrial Systems N60 Network Stability and Synchrophasor Measurement System UR Series Instruction Manual N60 Revision: 4.9x Manual P/N: 1601-0125-M2 (GEK-113212A) Copyright 2006 GE Multilin
More informationProtection relays.
Protection relays www.vamp.fi Vamp Ltd Vamp Ltd, with a strong experience of designing devices, is an independent supplier of relays and monitoring equipment. The company has an established reputation
More informationSEL Real-Time Automation Controller (RTAC)
SEL Real-Time Automation Controller (RTAC) Product Family Rugged, deterministic, and reliable automation controllers for any environment 1 ms deterministic processing intervals support critical protection
More informationMultilink. Ethernet Communications for Industrial Automation, Power Utility, and Traffic Control markets. Multilin
Multilink Ethernet Communication switches Ethernet for Industrial Automation, Power Utility, and Traffic Control markets Key Benefits The MultiLink family is a line of Industrial and Substation Hardened
More informationRelease 5.83 of the Universal Relay (UR) series introduces improvements for general and protection functions. Highlights of version 5.
GE Digital Energy UR Series Revision 5.83 Release Notes GE Publication Number: GER-4648A Copyright 2015 GE Multilin Inc. Overview Summary Release 5.83 of the Universal Relay (UR) series introduces improvements
More informationUR Universal Relay Series
G Digital nergy UR Universal Relay Series Revision 5.80 Release otes G Publication umber: GR-4377 Copyright 2010 G Multilin Summary Overview G Multilin issues the UR 5.80 release that introduces new improvements
More informationThe engine for substation automation. g Power Management. The Universal Relay. The Universal
The Universal elay Family The engine for substation automation 1 The Universal elay The Challenges of the Universal elay Performance Universal Universal elay Busbar Transmission Line Generator Transformer
More informationB90. Low Impedance Bus Differential System. Instruction Manual AB1. GE Digital Energy
GE Digital Energy B90 Low Impedance Bus Differential System Instruction Manual Product version: 7.3x GE publication code: 1601-0115-AB1 (GEK-119611) E83849 LISTED IND.CONT. EQ. 52TL 1601-0115-AB1 Copyright
More informationMiCOM P521. Fast feeder differential protection
01 Fast feeder differential protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More informationMM300. Integrated automation and protection for low voltage motors. Digital Energy Multilin. Metering & Monitoring. Protection and Control
Key Benefits MM300 Motor management System Integrated automation and protection for low voltage motors Full-featured protection for low voltage AC motors Advanced automation capabilities for providing
More informationMiCOM P521. Fast Feeder Differential Protection
01 Fast Feeder Differential Protection The relay provides high-speed two-ended current differential unit protection of overhead lines and underground cables in applications such as ring mains and parallel
More information2 ms arc-flash protection and feeder relay in one platform
Feeder Protection Relay 2 ms arc-flash protection and feeder relay in one platform Combine light sensor inputs with high-speed overcurrent protection to achieve secure arc-flash protection in as fast as
More informationHardFiber. Process Bus System. Instruction Manual AB2. GE Grid Solutions
GE Grid Solutions HardFiber Process Bus System Instruction Manual Product version: 7.3x GE publication code: 1601-0011-AB2 (GEK-130923) 1601-0011-AB2 Copyright 2016 GE Grid Solutions Inc. All rights reserved.
More informationLightweight and flexible recloser control for single-phase applications
SEL-35S Kestrel Single-Phase ecloser Control Lightweight and flexible recloser control for single-phase applications Plug-and-work operation with popular single-phase reclosers simplifies new and retrofit
More informationSOLKOR-N (7SR18) Feeder Differential Protection. Make the ight choice! Choose EYROLLE Protection
SOLKO-N (7S18) Feeder Differential Protection CLASSIFICATION OF UNIT TYPE POTECTION Summation Transformer, Circulating Current Protection B B 3 1 1 O O 3 1 1 SUMMATION TANSFOME SUMMATION TANSFOME O - Operating
More informationVAMP 50 series. with native IEC and arc flash protection
VAMP 50 series with native EC 61850 and arc flash protection V VAMP 50 series protection relays VAMP 50 family low and mid range relay series with EC 61850 The VAMP 50 series protection relay family is
More informationProtection, Automation, and Bay Control System. Advanced feeder protection and complete substation bay control in one economical system
SEL-451 Protection, Automation, and Bay Control System Advanced feeder protection and complete substation bay control in one economical system Customize distribution protection using multiple instantaneous,
More informationFunction permission: yes/no. Operating range: 0.10 to 30 xin (step 0.01) Operating time: 0.02 to 300 s (step 0.01 s) Activation level 100%
Operating range: 0.10 to 30 xin (step 0.01) 50P(2) Activation level 100% Deactivation level 95% Timer accuracy: 30 ms Operating range: 0.10 to 30 xin (step 0.01) 50N/G(2) Activation level 100% Deactivation
More informationTransformer Protection and Control RET630 Numerical transformer protection in medium voltage networks
GUIDEFORM SPECIFICATION Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks The freely configurable relay is intended for protection, control, measurement
More informationUR Series. Revision 7.21 Release Notes. GE Digital Energy. Overview. GE Publication Number: GER-4631_rev2 Copyright 2013 GE Multilin Inc.
GE Digital Energy UR Series Revision 7.21 Release Notes GE Publication Number: GER-4631_rev2 Copyright 2013 GE Multilin Inc. Overview Summary Release 7.21 of the Universal Relay (UR) series introduces
More informationwww. ElectricalPartManuals. com C60 Breaker Management Relay UR Series Instruction Manual GE Industrial Systems C60 Revision: 2.9X
g GE Multilin 215 Anderson Avenue, Markham, Ontario Canada L6E 1B3 Tel: (905) 294-6222 Fax: (905) 201-2098 Internet: http://www.geindustrial.com/multilin C60 Breaker Management Relay UR Series Instruction
More informationLM10 to MM200 Retrofit
Grid Solutions LM10 to MM200 Retrofit Replace old LM10 Motor Controller relays with the Multilin TM MM200 Motor Management System The LM10 Motor Controller (discontinued in 2013) has been replaced by new
More informationSubstation Automation Products. High impedance differential busbar protection REB650 Relion 650 series
Substation Automation Products High impedance differential busbar protection REB650 Relion 650 series One IED for a wide range of high impedance differential protection applications ABB introduces a new,
More informationContent REF615 Technical Presentation
Distribution Automation Relion 615 series Feeder Protection and Control Ver. 2.0 Technical Presentation March 30, 2010 1MRS756407 E Slide 1 Content Technical Presentation highlights March 30, 2010 Slide
More informationRelion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation
Relion 615 series Feeder Protection and Control REF615 Ver. 2.0 Technical Presentation Distribution Automation May 13, 2010 1MRS756407 E Slide 1 Content REF615 Technical Presentation highlights May 13,
More informationUR Universal Relay Series
GE Digital Energy UR Universal Relay Series Revision 3.50 Release Notes GE ublication Number: GER-4432 Copyright 2009 GE Multilin Overview Summary GE Multilin issues the UR 3.50 release that introduces
More informationPerfect protection smallest space
www.siemens.com/energy/protection Perfect protection smallest space The SIPROTEC Compact device range redefines protection technology Answers for energy. SIPROTEC Compact is the ideal solution for almost
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationSubstation Automation Products. Line distance protection REL670/650 Relion 670 and 650 series
Substation Automation Products Line distance protection REL670/650 Relion 670 and 650 series For maximum reliability of your power system REL670 and REL650 line distance protection IEDs (Intelligent Electronic
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationProtection, Monitoring, and Control System for Distribution Substations ALARM HISTORY SYSTEM COMM. On-Line Documentation TRANSFORMER 12 MW
SEL Distribution Substation Protection and Automation System Protection, Monitoring, and Control System for Distribution Substations Data Sheet SYSTEM ONE-LINE RELAY TARGETS ALARM HISTORY SYSTEM COMM.
More informationUsing the Bitronics 70 Series to Improve Local Monitoring and Control
Automate a Substation and Preserve the Electromechanical Relay Investment Part Two of Four Using the Bitronics 70 Series to Improve Local Monitoring and Control Paul Grabowski - Bitronics Senior Application
More informationMaximize protection. Sepam series 10, 20, 40, 60, 80. Modular range of digital protection relays
Maximize protection Sepam series 10, 20, 40, 60, 80 Modular range of digital protection relays Fast Dependable Simple Increase energy availability 100% available energy Fast response Maximum dependability
More informationPackaged Solutions. Grid Solutions. Value Added Solutions for Protection, Control and Automation Applications. Flexible and Expandable
Grid Solutions Packaged Solutions Value Added Solutions for Protection, Control and Automation GE s Packaged Solutions provide fully integrated, modular solution sets comprising of engineering, design,
More informationDGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION. Application field
DGSZV-EP DIGITAL GALVANIC LONGITUDINAL DIFFERENTIAL PROTECTION The digital galvanic longitudinal differential protection of type DGSZV-EP is part of device family named EuroProt. This short description
More informationMiCOM Agile P541 & 542. Grid Solutions. High-speed current differential unit protection. Key Benefits. Key Features. Current Differential Protection
GE Grid Solutions MiCOM Agile P541 & 542 High-speed current differential unit protection The P54x is designed for all overhead line and cable applications, as it interfaces readily with the longitudinal
More informationGE Power Management. MMII Intelligent MCC Controller
A concept that will offer reduced overall installed cost and production efficiency through information availability to operators and maintenance. Presentation Overview 6 Applications 6 Protection and Control
More informationDS Agile C264. Grid Solutions. Dual-bay Modular Substation Controller. Multi-function Controller. Automation and Control. Advanced Communication
GE Grid Solutions DS Agile C264 Dual-bay Modular Substation Controller The DS Agile C264 substation controller is a sophisticated solution supporting multiple applications and functions for substation
More informationSR750/760 Feeder Management Relay
G Digital nergy S750/760 Feeder Management elay Firmware Version 7.31 elease Notes G Publication Number: G-4364 Copyright 2010 G Multilin Summary Overview G Multilin issues the S750/760 Feeder Management
More informationBus Differential and Breaker Failure Relay. Advanced bus protection with built-in breaker failure detection
SEL-487B Bus Differential and Breaker Failure Relay Advanced bus protection with built-in breaker failure detection Protect busbars with up to 21 terminals using high-speed, low-impedance bus differential
More informationREL52002 Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: V, DI: V, RS-485
Characteristics Easergy P3U30, 4L, 4U, 16DI/8DO, Uaux: 48-230V, DI: 220-230V, RS-485 Main Range of product Product or component type Relay application Device short name [Us] rated supply voltage Type of
More informationSACE Emax 2 Specification guide
SACE Emax 2 Specification guide Specification Number: 26 01 20.17 Product Name: LOW VOLTAGE POWER CIRCUIT BREAKERS PART 1 GENERAL NOTE: ( ) Indicates option or a selection is to be made for quantity or
More informationMultilin P30 Phasor Data Concentrator
Multilin P30 Phasor Data Concentrator Secure high performance Phasor Data Concentrator (PDC) for wide area monitoring and dynamic disturbance analysis KEY BENEFITS Reduce deployment and operation cost
More informationMiCOM P122C Time-Overcurrent Protection
Protection Relays 01 MiCOM P122C Time-Overcurrent Protection Customer Benefits 1A/5A software setting 4 function keys Compact unit for flush and wall-surface mounting Comprehensive measurements Disturbance
More informationNEO 3000 Substation System THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES. Energy Sector
THE FAMILY OF EQUIPMENT DEDICATED FOR POWER UTILITIES Introduction The supply of electrical energy occupies an important position in the life of modern society. Operation of commerce, industry, transport,
More information7SR21 Non-Directional 7SR22 Directional Overcurrent Relay
7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Additional Comms module
More informationSubstation Automation Products. Bay control REC670/650 Relion 670 and 650 series
Substation Automation Products Bay control REC670/650 Relion 670 and 650 series For optimized control and reliable operation of your switchyard The REC670 and REC650 Bay control IEDs (Intelligent Electronic
More informationSR 750 Feeder Management Relay
G Digital nergy S 750 Feeder Management elay Firmware Version 7.30 Software Version 7.30 elease Notes G Publication Number: G-4354 Copyright 2010 G Multilin Summary Overview G Multilin issues the S 750
More informationPower Systems Communications Implementation of IEC61850 in a Substation Environment
Power Systems Communications Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0 Document Control Document ID: DOCUMENT1 Rev No Date Revision Details
More informationCurrent Fault Signatures and Analysis Auto-calibrating metrology means the meter maintains its accuracy over temperature and time
Multilin EPM 9900 High Performance Power Quality and Transient Recorder Meter The EPM 9900 is one of the most advanced monitoring products on the market today, providing you with the total picture of energy
More information