Compact Non-Contact Door Switch/Flexible Safety Unit D40A/G9SX-NS

Size: px
Start display at page:

Download "Compact Non-Contact Door Switch/Flexible Safety Unit D40A/G9SX-NS"

Transcription

1 Compact Non-Contact Do Switch/Flexible Safety Unit D40A/G9SX-NS Electronic Detection Mechanism f Better Stability in Non-contact Do Switch Operation CSM_D40A_G9SX-NS_DS_E_3_2 Be sure to read the Safety Precautions on page 24 and the Precautions f All Safety Do Switches. Features Easy-to-see 2-Col Indicats Switch status is easy to see at a glance with these red/yellow LED indicats. Mount from Either Side Mount from whichever side provides the easiest wiring path to enable mounting to all types of dos. Red: Open do detected. Yellow: Closed do detected. Not lit: Power OFF failure Swinging dos Sliding dos Small Actuat An actuat that is smaller than the switch saves space, even inside the do. Even when mounted with an L-bracket, the actuat's height will not hinder installation operation. Compact Switch Actuat Connect Up to 30 Switches to a Single Controller Reduce costs by connecting up to 30 Switches to a single Controller. Up to 30 Switches 1

2 Solves Conventional Switch Issues to Provide Stable Detection Issue 1 The Switch does not accurately detect the do when it is closed slowly, resulting in an err. Conventional switch Do closed slowly. An err can occur if the do is closed slowly with conventional switches. Solution 1 Magnet Conventional Switches Slow Reed switch contacts Magnet Reed switch contacts Err If the switching timing of reed switch contacts 1 and 2 varies too much, the Controller detects an err and turns OFF the output to maintain safety. Note: The figure is intended only as an illustration. Stable Detection with the D40A's New System The D40A does not use reed switches and provides stable detection with electronic switches. Slow Detects slow lateral operation. Detects slow rotating operation. Issue 2 It is nearly impossible to tell which do is open in a multi-do application. If an err occurs... The system cannot be started because the Controller has turned OFF the output even though all dos appear to be closed. It's impossible to tell if there is a do open if an err has occurred. All dos must be opened and closed befe operation can be started. Solution 2 With the D40A... The auxiliary outputs can be used to easily indicate which do is open. And with two-col indicats, mounting adjustments are also easy. The D40A is the first Non-contact Do Switch to combine 2-col indicats, auxiliary outputs, and 30-switch connection capacity, allowing you to create a better safety environment. 2

3 Two Types of Controller to Solve Productivity, Expandability, and Maintenance Issues The G9SX-NS and G9SX-NSA are designed specifically f use with the D40A, and with the G9SX-NSA you can also connect mechanical safety do switches. Among other features, these Controllers suppt logical AND connections that enable partial stops. These Controllers make the most of D40A Switches. Two Different Controllers AND connection input AND connection instantaneous safety plus mechanical safety do switch input, channel 1 instantaneous safety OFF-delay safety AND connection AND connection output Indicats That Make Maintenance Easier The indicats show the location and cause of wiring errs and any other errs that are detected. Auxiliary outputs f errs also contribute to reducing down time. Input err Logical AND connection err Output err Mechanical Safety Do Switches Can Also Be Connected with the G9SX-NSA Inputs can be accepted from both D40A Switches and mechanical switches to reduce the number of Controllers and costs. D40A Safety Do Switches Expansion Units to Easily Increase the Number of Outputs with the G9SX-NSA The number of outputs can be easily increased using connects. Up to 25 outputs can be configured. G9SX-EX Expansion Unit Up to 25 Outputs 3

4 Reduce Costs with these New-Concept Controllers Issue 1 Two Controllers are required f emergency stop switches and non-contact do switches. Application One hazard. The system must be stopped when either a do is opened an emergency stop switch is pressed. D40B D40B-J1 Solution 1 Emergency stop switch * D40A Emergency stop switch * The D40A Simplifies the Configuration The G9SA must be added to connect the emergency stop switch. G9SA Two Controllers With only one G9SX-NSA222-T03@ Controller, both a Non-contact Do Switch and an emergency stop switch can be connected. G9SX-NSA One Controller Issue 2 Another Controller has to be added to use an OFF-delay timer. Application Two hazards. The power supply must be turned OFF immediately when the emergency stop switch is pressed. When a do is opened, a stop signal is sent to only servomot B and then the power supply is turned OFF. Emergency stop switch * Wiring D40B D40B-J1 Solution 2 The D40A Simplifies the Configuration Emergency stop switch * G9SX-BC D40A G9SX-NSA The G9SA must be added to use an OFF-delay timer. A G9SA B G9SA-321-T@ OFF-delay output Three Controllers A Controller can be eliminated because the G9SX-NSA222-T03@ provides an OFF-delay output. A Logical AND connection B Two Controllers * Always use a manual reset when using an emergency stop. Refer to G9SX f the features of the G9SX Series. 4

5 Model Number Structure Model Number Legend Non-Contact Do Switch (Switch/Actuat) D40A Type 1: Standard model 2. Auxiliary outputs C: 1NO (PNP transist output) 3. Cable length 2: 2 m 5: 5 m D40A/G9SX-NS Non-Contact Do Switch Controller G9SX Functions NS/NSA: D40A Controller EX: Expansion Unit 2. Output Configuration (Instantaneous Safety Outputs) 2: 2 outputs 4: 4 outputs 3. Output Configuration (OFF-delayed Safety Outputs) 0: None 2: 2 outputs 4. Output Configuration (Auxiliary Outputs) 1: 1 output 2: 2 outputs 5. Max. OFF-delay Time D40A Controller T03: 3 s (Variable) Expansion Unit Blank: No OFF delay T: OFF delay 6. Terminal Block Type RT: Screw terminals RC: Spring-cage terminals Ordering Infmation Non-Contact Do Switches (Switch/Actuat) Classification Appearance Auxiliary outputs Cable length Model Standard models *2 Semiconduct outputs *1 2 m D40A-1C2 5 m D40A-1C5 Note: Must be used in combination with a Non-contact Do Switch Controller. *1. PNP open-collect semiconduct output. *2. Ask your OMRON representative f the connect models. Non-Contact Do Switch Controllers (Controllers f D40A) Safety outputs *1 Instantaneous 2 (Semiconducts) OFF-delayed *2 0 2 (Semiconducts) Auxiliary outputs *3 2 (Semiconducts) Logical AND connection input Logical AND connection output 1 1 Max. OFF delay time *4 Rated voltage *1. P channel MOS FET transist output *2. The OFF-delayed output becomes an instantaneous output by setting the OFF-delay time to 0 s. *3. PNP transist output *4. The OFF-delay time can be set in 16 steps as follows: 0/0.2/0.3/0.4/0.5/0.6/0.7/0.8/0.9/1.0/1.2/1.4/1.8/2.0/2.5/3.0 s s 24 VDC Terminal block type Screw terminals Spring-cage terminals Screw terminals Spring-cage terminals Model G9SX-NS202-RT G9SX-NS202-RC G9SX-NSA222-T03-RT G9SX-NSA222-T03-RC Expansion Units Instantaneous Safety outputs OFF-delayed Auxiliary outputs OFF-delay time 4PST-NO (Semiconduct) * PST-NO *2 Rated voltage 24 VDC Terminal block type Screw terminals Spring-cage terminals Screw terminals Spring-cage terminals *1. PNP transist output *2. The OFF-delay time is synchronized to the OFF-delay time setting in the connected Controller (G9SX-NSA222-T03-@). Model G9SX-EX401-RT G9SX-EX401-RC G9SX-EX041-T-RT G9SX-EX041-T-RC 5

6 Specifications D40A/G9SX-NS Ratings and Characteristics (Non-contact Do Switches) Item Model Operating characteristics *1 Ambient operating temperature Operating distance OFF ON Operating distance ON OFF 5 mm min. 15 mm max. Differential travel Refer to Detection Ranges on page 11 Influence of temperature (max.) ±20% of operating distance at 23 C, within temperature range of 10 to 55 C Ambient operating humidity 25% to 85% Insulation resistance (between charged parts and case) Dielectric strength (between charged parts and case) Vibration resistance Shock resistance Degree of protection Material Mounting method Terminal screw tightening tque Power consumption Auxiliary outputs *2 LED indicats Connection cables Number of connectable switches *3 Weight 10 to 55 C (no icing condensation) 50 MΩ max. (at 500 VDC) 1,000 VAC f 1 min 10 to 55 to 10 Hz (single amplitude: 0.75 mm, double amplitude: 1.5 mm) 300 m/s 2 min. IP67 PBT resin M4 screws 1 N m 0.6 W max. 24 VDC, 10 ma (PNP open-collect outputs) Actuat not detected (red); actuat detected (yellow) 2 m, 5 m 30 max. (wiring length: 100 m max.) Switch: approx. 145 g, actuat: approx. 20 g (D40A-1C2) *1. This is the distance where the switch operates from OFF to ON when approaching and the distance where the switch operates from ON to OFF when separating when the switch and actuat target marks are on the same axis, and the sensing surfaces coincide. *2. Turns ON when the actuat is approaching. The G3R series of the SSR can be driven at an auxiliary output of 10 ma. Contact your OMRON representative f details. *3. F details, refer to item 5 on page 25. 6

7 Ratings (Non-contact Do Switch Controllers) Power input Item Model Rated supply voltage Operating voltage range Rated power consumption * 3 W max. 4 W max. 2 W max. * Power consumption of loads not included. Inputs *1. Only applies to the G9SX-NSA222-T03-@. Refers to input other than that from the Non-contact Do Switch. *2. Provide a current equal to higher than that of the minimum applicable load of the connected input control device. Outputs 24 V DC 15% to 10% of rated supply voltage Item Model G9SX-NS202-@/G9SX-NSA222-T03-@ Safety input *1 Feedback/reset input Operating voltage: 20.4 VDC to 26.4 VDC, internal impedance: approx. 2.8 kω *2 Item Model G9SX-NS202-@/G9SX-NSA222-T03-@ Instantaneous safety output *1 OFF-delayed safety output *1 Auxiliary output P channel MOS FET transist output Load current: 0.8 A DC max. *2 PNP transist output Load current: 100 ma max. *1. While safety outputs are in the ON state, the following signal sequence is output continuously f diagnosis. When using the safety outputs as input signals to control devices (i.e. Programmable Controllers), consider the OFF pulse shown below. ON Approx.100 ms OFF *2. The following derating is required when Units are mounted side-by-side. G9SX-NS202-@/G9SX-NSA222-T03-@: 0.4 A max. load current Expansion Unit 360 μs max. Item Model G9SX-EX-@ Rated load 250 VAC, 3 A/30 VDC, 3 A (resistive load) Rated carry current 3 A Maximum switching voltage 250 VAC, 125 VDC 7

8 Characteristics Item Model Over-voltage categy (IEC/EN ) Operating time (OFF to ON state) *1 Response time (ON to OFF state) *1 ON-state residual voltage OFF-state leakage current Maximum wiring length of safety input, logical AND connection input, and Non-contact Do Switch input Reset input time (Reset button pressing time) II 100 ms max. (Logical AND connection input ON and Non-contact Do Switch input ON) 15 ms max. (Logical AND connection input: OFF) 20 ms max. (Non-contact Do Switch input OFF) *6 3.0 V max. (safety output, auxiliary output) 0.1 ma max. (safety output, auxiliary output) 50 ms max. (Safety input: ON) *2 100 ms max. (Logical AND connection input ON and Non-contact Do Switch input ON) *3 15 ms max. (Safety input OFF and logical AND connection input OFF) 20 ms max. (Non-contact Do Switch input: OFF) *6 100 m max. (External connection impedance: 100 Ω max. and 10 nf max.) 100 ms min. II (Relay outputs 13 to 43 and 14 to 44: III) 30 ms max. *4 10 ms max. *4 Accuracy of OFF-delay time *5 --- Within ±5% of the set value Within ±5% of the set value Insulation resistance Dielectric strength Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected together Between all terminals connected together and DIN rail Between logical AND connection terminals, and power supply input terminals and other input and output terminals connected together Between all terminals connected together and DIN rail Between different poles of outputs Between relay outputs connected together and other terminals connected together 20 MΩ min. (at 100 VDC) 500 VAC f 1 min. Vibration resistance 10 to 55 to 10 Hz, mm single amplitude (0.75 mm double amplitude) Shock Destruction 300 m/s 2 resistance Malfunction 100 m/s 2 Durability Electrical --- Mechanical --- Ambient operating temperature Ambient operating humidity 25% to 85% Terminal tightening tque 100 MΩ min. (at 500 VDC) *1. When two me Units are connected by logical AND, the operating time and response time are the sum total of the operating times and response times, respectively, of all the Units connected by logical AND. *2. Represents the operating time when the safety input turns ON with all other conditions set. *3. Represents the operating time when the logical AND input and the Non-contact Do Switch input turn ON with all other conditions set. *4. This does not include the operating time response time of that are connected. *5. This does not include the operating time response time of internal relays in the G9SX-EX-@. *6. The failure detection time f 24 V sht-circuit failure on the input to Non-contact Do Switches is 35 ms max. If using the Switch f an application other than as a Do Switch, calculate the safe distance using a failure detection time of 35 ms to 55 C (no icing condensation) 0.5 N m (F the -RT (with screw terminals) only) ,200 VAC f 1 min 2,200 VAC f 1 min Weight Approx. 125 g Approx. 200 g Approx. 165 g 100,000 cycles min. rated load, switching frequency: 1,800 cycles/hour) 5,000,000 cycles min. (switching frequency: 7,200 cycles/hour) 8

9 Logical AND Connection Item Model Number of Units connected per logical AND output Total number of Units connected by logical AND *1 Number of Units connected in series by logical AND Max. number of Expansion Units connected *2 Maximum cable length f logical AND input 4 Units max Units max Units max Units max. 100 m max. --- Note: See Logical AND Connection Combinations below f details. *1. The number of G9SX-EX401-@ Expansion Units G9SX-EX041-T-@ Expansion Units (OFF-delayed Model) not included. *2. G9SX-EX401-@ Expansion Units and G9SX-EX041-T-@ Expansion Units (OFF-delayed Model) can be mixed. Logical AND Connection Combinations 1. One logical AND connection output from a Controller can be logical AND connected to up to four Controllers. 3. The largest possible system configuration contains a total of 20 Controllers, Advanced Units, and G9SX-BC Basic Units. In this configuration, each Controller Advanced Unit can have up to five Expansion Units. G9SX-@ 2. Any Controller that receives a logical AND connection input can be logically connected to other Controllers on up to five layers. Number of Units connected per logical AND output: 4 Units max. Note: The in the above diagram can be replaced by the Advanced Unit. F details on Advanced Units, refer to the G9SX-series Flexible Safety Unit catalog. (Cat. No. J150). Number of Units connected in series by logical AND: 5 Units max. Total number of Units connected by logical AND: 20 Units max. 9

10 Response Time and Operating Time 1. Logical AND input Non-contact Do Switch input Max. response time (excluding Expansion Units) *1 Max. operating time (excluding Expansion Units) *2 Non-contact Do Switch input 20 ms 100 ms Logical AND input 15 ms 100 ms *1. The maximum response time is the time it takes the output to switch from ON to OFF after the input switches from ON to OFF. *2. The maximum operating time is the time it takes the output to switch from OFF to ON after the input switches from OFF to ON. 2. Logical AND input Non-contact Do Switch input D4NS Safety input Max. response time (excluding Expansion Units) *1 Max. operating time (excluding Expansion Units) *2 Non-contact Do Switch input 20 ms 100 ms Safety input 15 ms 50 ms Logical AND input 15 ms 100 ms *1. The maximum response time is the time it takes the output to switch from ON to OFF after the input switches from ON to OFF. *2. The maximum operating time is the time it takes the output to switch from OFF to ON after the input switches from OFF to ON. 3. Multiple Non-contact Do Switch Controllers When multiple Controllers are logically connected with AND connections, the response time is the sum of the response times given in 1 and 2 above. (It is the same f the operating time.) D40A (1) D4NS Safety input Case 1 Response Time from When D40A (1) Turns from ON to OFF until Safety Output (2) Turns from ON to OFF ( 20 ms + 15 ms = 35 ms (D40A (1)) (Logical AND connection (1)) Logical AND (1) D40A (2) Safety output (1) Case 2 Response Time from When D4NS Turns from ON to OFF until Safety Output (3) Turns from ON to OFF 15 ms + 15 ms + 15 ms = 45 ms (D4NS) (Logical AND (Logical AND connection (1)) connection (2)) Safety output (2) Logical AND (2) D40A (3) Safety output (3) 10

11 Engineering Data D40A/G9SX-NS Detection Ranges (Typical Characteristics Data) Operating distance Y (mm) OFF X Y Sensing surface Operating distance Y (mm) OFF Z Sensing surface Y 6 4 ON Target marks 6 4 ON Target marks Distance from the target mark on the switch X (mm) Distance from the target mark on the switch Z (mm) Note: 1. The operating distance is the distance between the switch and actuat sensing surfaces. 2. Data in the diagram is typical data at an ambient temperature of 23 C. Actual operating values may vary. The operating distance may be affected by ambient metal, magnet catches, and temperature. Connections Internal Connection G9SX-NS202-@ (Non-contact Do Switch Controller) A1 Power supply circuit *1 D1 D2 Non-contact Do Switch control D3 D4 T31 T32 T33 T41 T42 Safety output control Reset/Feedback Input *2 Logical AND input Auxiliary output control G9SX-NSA222-T03-@ (Non-contact Do Switch Controller) A1 Power supply circuit *1 T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42 Safety input 1 Safety input 2 Safety output control Reset/Feedback Input Cross fault detection input Auxiliary output control Non-contact Do Switch control *2 Logical AND input Expansion Unit output control A2 S14 *3 S24 L1 X1 X2 A2 S14 S24 S44 S54 L1 X1 X2 *1. Internal power supply circuit is not isolated. *2. Logical AND input is isolated. *3. Outputs S14 to S24 are internally redundant. G9SX-EX401-@/G9SX-EX041-T-@ (Expansion Unit/Expansion Unit OFF-delayed Model) A Exp. sig. IN *1 Power supply circuit Safety output control Auxiliary output control K1 K2 *2 Exp. sig. OUT *3 *1. Internal power supply circuit is not isolated. *2. Logical AND input is isolated. *3. Outputs S14 to S54 are internally redundant. A2 X *1. Internal power supply circuit is not isolated. *2. Relay outputs are isolated. Internal Circuit Diagram D40A-1C@ Brown Blue Internal circuit White Black Yellow 11

12 Dimensions and Terminal Arrangement Non-contact Do Switch (Switch/Actuat) D40A-1C2 D40A-1C5 Two, 4.2 dia. (2) Indicat D40A/G9SX-NS 9.5 (Unit: mm) 7.2 dia. Sensing surface 7.2 dia dia. Sensing surface 7.2 dia (2) Two, 4.2 dia. Vinyl-insulated round cd, dia. 4, 5-conduct (conduct cross-sectional area: 0.2 mm 2,Insulat diameter: 1.0 mm) Standard length: 2 m/5 m (Actuat) (Switch) Non-contact Do Switch Controller G9SX-NS202-@ (6) (See note 2.) Terminal arrangement T31 T32 T33 D3 D1 D2 X1 A1 T31 T32 T33 D3 D1 D2 X1 A1 G9SX-NS202 24VDC PWR FB AND NS EI ERR No. 100 max. PWR AND EI FB NS ERR T41 T42 X2 A2 S14 S24 L1 D4 T41 T42 X2 A2 S14 S24 L1 D4 23 max. (22.5) * 115 max. (6) (See note 2.) Note: 1. Above outline drawing is f models with spring-cage terminals (-RC). 2. F models with spring-cage terminals (-RC) only. * Typical dimension Non-contact Do Switch Controller G9SX-NSA222-T03-@ (6) (See note 2.) Terminal arrangement T31 T32 T33 T11 T12 D1 D2 D3 Y1 X1 X2 A1 T31 T11 T32 T33 D1 D2 D3 T12 PWR T1 AND Y1 FB T2 NS EI ED ERR OFF-DELAY X1 G9SX-NSA222-T03 24VDC X2 No. A1 100 max. PWR T1 AND EI FB T2 NS ED ERR T21 T22 T41 T42 A2 S14 S24 S44 S54 L1 D4 T21 T22 T41 T42 A2 S14 S24 S44 S54 L1 D max. (35) * (10) 115 max. (6) (See note 2.) Note: 1. Above outline drawing is f models with spring-cage terminals (-RC). 2. F models with spring-cage terminals (-RC) only. * Typical dimension 12

13 Expansion Unit Expansion Unit (OFF-delayed Model) Terminal arrangement (6) (See note 2.) (Expansion Unit) (Expansion Unit with OFF Delay) PWR EI ERR PWR ED ERR 100 max. A1 X2 A A1 X2 A max. (22.5) * 115 max. (6) (See note 2.) Note: 1. Above outline drawing is f models with spring-cage terminals (-RC). 2. F models with spring-cage terminals (-RC) only. * Typical dimension 13

14 Non-contact Do Switch and Non-contact Do Switch Controller Wiring Example: Wiring a Single Switch Example: Wiring Multiple Switches Connect Up to 30 Non-contact Do Switches D40A-1C@ White Black Brown Blue Yellow Auxiliary output load * White Black Brown Blue White Black Brown Blue White Black Brown Blue D1 D2 D3 D4 A2 G9SX-NS202-@ G9SX-NSA222-T03-@ * The auxiliary output load current must be 10 ma max. D1 D2 D3 D4 G9SX-NS202-@ G9SX-NSA222-T03-@ Wiring of Inputs and Outputs Signal name Wire col Description of operation Non-contact Do Switch power supply input Non-contact Do Switch input Non-contact Do Switch output Brown Blue White Black Supplies power to the D40A. Connect to the D3 and D4 terminal of the. Auxiliary output Yellow Turns ON when actuat is detected. Inputs signals from the. The Non-contact Do Switch input must be ON as a required condition f the Non-contact Do Switch output to be ON. Turns ON and OFF accding to actuat detection and the status of the Non-contact Do Switch input. 14

15 Wiring of Inputs and Outputs Signal name Power supply input Terminal name A1, A2 Description of operation Connect the power source to the A1 and A2 terminals. Wiring Connect the power supply plus (24 VDC) to the A1 terminal. Connect the power supply minus (GND) to the A2 terminal. Non-contact Do Switch input D1, D2, D3, D4 All Non-contact Do Switch inputs connected to the must be ON as a required condition f the safety outputs to be ON. Otherwise the safety outputs cannot be in the ON state. White Black Brown Blue D1 D2 D3 D4 Feedback/reset input T31, T32, T33 To set the safety outputs in the ON state, the ON state signal must be input to T33. Otherwise the safety outputs cannot be in the ON state. To set the safety outputs in the ON state, the signal input to T32 must change from the OFF state to the ON state, and then to the OFF state. Otherwise the safety outputs cannot be in the ON state. Auto reset Manual reset Reset Switch T31 T31 Feedback loop KM T32 T33 Feedback loop KM T32 T33 Logical AND connection input T41, T42 A logical AND connection means that one unit (Unit A) outputs a safety signal a to a subsequent unit (Unit B) and Unit B calculates the logical AND (i.e., outputs the AND) of the signal a and safety signal b, which is input to Unit B. Thereby the logic of the safety output of Unit B is (AND). (An AND of inputs a and b is output.) To set the safety outputs of the subsequent Unit in the ON state, its logical AND connection preset switch must be set to AND (enable) and the high signal must be input to T41 of the subsequent unit. Unit A G9SX-NS/NSA Output (a) L1 A2 Unit B T41 T42 G9SX-NS/NSA Output (a&b) L1 A2 T41 T42 G9SX-NS/NSA L1 A2 Input a Logical AND connection sig. (1st layer) Input b Logical AND connection sig. (2nd layer) Next unit (4 unit max.) T41 T42 G9SX-NS/NSA Next unit (4 unit max.) Instantaneous safety output Logical AND connection output Auxiliary monit output Auxiliary err output S14, S24 L1 X1 Turns ON/OFF accding to the state of the safety inputs, Non-contact Do Switch inputs, feedback/ reset inputs, and logical AND connection inputs. During OFF-delay state, the Instantaneous safety outputs are not able to turn ON. Outputs a signal of the same logic and at the same time as the instantaneous safety outputs. Outputs a signal of the same logic and at the same time as the instantaneous safety outputs. Next unit (5 layers max.) Keep these outputs open when not used. Keep these outputs open when not used. Keep these outputs open when not used. X2 Outputs when the err indicat is lit flashing. Keep these outputs open when not used. 15

16 Signal name Power supply input Terminal name A1, A2 Description of operation Connect the power source to the A1 and A2 terminals. Wiring Connect the power supply plus (24 VDC) to the A1 terminal. Connect the power supply minus (GND) to the A2 terminal. Safety input 1 T11, T12 Cresponds to Safety Categy 2 T11 T12 T21 T22 Y1 To set the safety outputs in the ON state, the high state signals must be input to both safety input 1 and safety input 2. Otherwise the safety outputs cannot be in the ON state. Cresponds to Safety Categy 3 (without sht-circuit moniting between systems) T11 T12 T21 T22 Y1 Safety input 2 T21, T22 Cresponds to Safety Categy 3 (Cross fault detecting mode (f safety inputs)) T11 T12 T21 T22 NC Y1 Non-contact Do Switch input D1, D2, D3, D4 All Non-contact Do Switch inputs connected to the G9SX-NS must be ON as a required condition f the safety outputs to be ON. Otherwise the safety outputs cannot be in the ON state. White Black Brown Blue D1 D2 D3 D4 Feedback/reset input T31, T32, T33 To set the safety outputs in the ON state, the ON state signal must be input to T33. Otherwise the safety outputs cannot be in the ON state. To set the safety outputs in the ON state, the signal input to T32 must change from the OFF state to the ON state, and then to the OFF state. Otherwise the safety outputs cannot be in the ON state. Auto reset Manual reset Reset Switch T31 T31 Feedback loop KM T32 T33 Feedback loop KM T32 T33 Logical AND connection input T41, T42, T51, T52 A logical AND connection means that one unit (Unit A) outputs a safety signal a to a subsequent unit (Unit B) and Unit B calculates the logical AND (i.e., outputs the AND) of the signal a and safety signal b, which is input to Unit B. Thereby the logic of the safety output b is output.) To set the safety outputs of the subsequent Unit in the ON state, its logical AND connection preset switch must be set to AND (enable) and the high signal must be input to T41 of the subsequent unit. Unit A G9SX-NS/NSA Output (a) L1 A2 Unit B T41 T42 G9SX-NS/NSA Output (a&b) L1 A2 T41 T42 G9SX-NS/NSA L1 A2 Input a Logical AND connection sig. (1st layer) Input b Logical AND connection sig. (2nd layer) Next unit (4 unit max.) T41 T42 G9SX-NS/NSA Next unit (4 unit max.) Cross fault detection input Instantaneous safety output OFF-delayed safety output Logical AND connection output Auxiliary monit output Auxiliary err output Y1 S14, S24 S44, S54 L1 X1 Selects the mode f the failure detecting (cross fault detecting) function f the safety inputs of G9SX cresponding to the connection of the cross fault detection input. Turns ON/OFF accding to the state of the safety inputs, feedback/reset inputs, and logical AND connection inputs. During OFF-delay state, the Instantaneous safety outputs are not able to turn ON. OFF-delayed safety outputs. The OFF-delay time is set by the OFF-delay preset switch. When the delay time is set to zero, these outputs can be used as non-delay outputs. Outputs a signal of the same logic and at the same time as the instantaneous safety outputs. Outputs a signal of the same logic and at the same time as the instantaneous safety outputs. Next unit (5 layers max.) Keep Y1 open when using T11, T21. (Cross fault detecting mode (f safety inputs)) Connect Y1 to 24 VDC when not using T11, T21. (Wiring cresponding to categy 2 3, when connecting safety senss) Keep these outputs open when not used. Keep these outputs open when not used. Keep these outputs open when not used. Keep these outputs open when not used. X2 Outputs when the err indicat is lit flashing. Keep these outputs open when not used. Connecting Safety Senss Safety senss cannot be connected to safety inputs f the G9SX-NSA222-T03-@. 16

17 Operation Functions Logical AND Connection A logical AND connection means that the G9SX outputs a safety signal a to another G9SX, and that G9SX creates the logical AND of safety signal a and safety signal b. The safety output of the G9SX-NSA222-T03-@ with the logical AND connection shown in the following diagram is a AND b. G9SX-NS202-@ a b G9SX-NSA222-T03-@ D40A/G9SX-NS Connecting Expansion Units The G9SX-EX and G9SX-EX-T Expansion Units can be connected to a G9SX-NSA222-T3-@ Non-contact Do Switch Controller to increase the number of safety outputs. (They cannot be connected to a G9SX-NS202-@.) A maximum of five Expansion Units can be connected to one G9SX-NSA222-T03-@. This may be a combination of G9SX-EX instantaneous models and G9SX-EX-T OFF-delayed models. Remove the terminating connect from the receptacle on G9SX-NSA222-T03-@ and insert the Expansion Unit cable connect into the receptacle. Insert the terminating connect into the receptacle on the Expansion Unit at the very end (rightmost). When Expansion Units are connected to a Controller, make sure that power is supplied to every Expansion Unit. (Refer to the following diagram f actual Expansion Unit connection.) a a (AND) b This is illustrated using the application in the following diagram as an example. The equipment here has two hazards identified as Robot 1 and Robot 2, and it is equipped with Non-contact Do Switches and an emergency stop button as safety measures. If the do to Robot 2 is opened, only Robot 2 is stopped (i.e., a partial stop). If the do to Robot 1 is opened the emergency stop button is pressed, both Robot 1 and Robot 2 stop (i.e., a complete stop). The actual situation using a G9SX f this application is shown in this example. Note: The logical AND setting on the G9SX-NS202-@ must be set to AND (enabled). G9SX-NSA222-T03-@ Terminating connect Expansion Unit Non-contact Do Switch 2 Non-contact Do Switch 1 Emergency stop button Robot 1 Robot 2 Emergency stop switch * D40A D40A G9SX- NSA222-T03-@ G9SX- NS202-@ Robot 1 Robot 2 * A manual reset is required when an emergency stop is used. 17

18 Setting Procedure 1. Cross Fault Detection Set the cross fault detection mode f safety inputs by shting Y1 to 24 V leaving it open. When cross fault detection is set to ON, sht-circuit failures are detected between safety inputs T11-T12 and T When a cross fault is detected, the following will occur. (1) The safety outputs and logical AND outputs lock out. (2) The LED err indicat is lit. (3) The err output (auxiliary output) turns ON. Cross fault detection OFF ON Cresponds to Safety Categy 2. Cresponds to Safety Categy 3. Cresponds to Safety Categy 3 (Cross fault detecting mode (f safety inputs)). Wiring 2. Reset Mode (G9SX-NS202-@/NSA222-T03-@) Set the reset mode using feedback/reset input terminals T31, T32, and T33. Auto reset mode is selected when terminal T32 is shted to 24 V and manual reset mode is selected when terminal T33 is shted to 24 V. Auto reset mode KM1 T11 T11 T11 T12 T12 T21 T21 T22 T12 Manual reset mode KM1 T21 T22 T22 Y1 Y1 Y1 3. Setting Logical AND Connection (G9SX-NS202-@/ NSA222-T03-@) When connecting two me Non-contact Do Switch Controllers by logical AND connection, set the logical AND connection preset switch on the Controller that is on the input side (Unit B in the following diagram) to AND. The default setting of the logical AND connection preset switch is set to OFF. Note: A setting err will occur and Unit B will lock out if the logical AND setting switch on the Unit B is set to OFF. 4. Setting the OFF-delay Time (G9SX-NSA222-T03-@) The OFF-delay preset time on G9SX-NSA222-T03-@ is set from the OFF-delay time preset switch (1 each on the front and back of the Unit). Nmal operation will only occur if both switches are identically set. An err will occur if the switches are not identically set. The default setting of the OFF-delay time preset switch is set to 0 s. Front Back Switch L1 T41 Refer to the following illustration f details on setting switch positions. G9SX-NSA222-T03-@ Unit A Unit B A2 T42 AND OFF AND OFF Switch T31 KM2 KM3 KM4 KM5 T32 T33 Reset switch T31 KM2 KM3 KM4 KM5 T32 T OFF-DELAY Example 1: 0-second Notch OFF-DELAY Example 2: 0.8-second 18

19 LED Indicats Marking Col Name G9SX-NS202 PWR Green T1 Orange T2 Orange NS Orange Power supply indicat Safety input #1 indicat Safety input #2 indicat Non-contact Do Switch input indicat FB Orange Feedback/reset input indicat AND Orange EI ED Orange Orange Logical AND input indicat Instantaneous safety output indicat OFF-delayed safety output indicat * Refer to Fault Detection on the next page f details. G9SX- NSA222 G9SX-EX G9SX-EX-T Function Reference Lights while power is supplied Lights while a high signal is input to T12. Flashes when an err relating to safety input #1 occurs. Lights while a high signal is input to T22. Flashes when an err relating to safety input #2 occurs. Lights when the Non-contact Do Switch input turns ON. Flashes when an err relating to the Non-contact Do Switch input occurs. Lights in the following cases: With automatic reset while a high signal is input to T33. With manual reset while a high signal is input to T32. Flashes when an err relating to feedback/ reset input occurs. Lights while a high signal is input to T41. Flashes when an err relating to logical AND connection input occurs. Lights while the Instantaneous safety outputs (S14, S24, S34) are in the ON state. Flashes when an err relating to the instantaneous safety output occurs. Lights while OFF-delayed safety outputs (S44, S54) are in the ON-state. Flashes when an err relating to OFF-delayed safety output occurs. ERR Red Err indicat Lights flashes when an err occurs. Settings Indication (at Power ON) Settings f the G9SX can be checked by the ange indicats f approx. 3 seconds after the power is turned ON. During this settings indication period, the ERR indicat will light, however the auxiliary err output will remain OFF. Indicat T1 FB AND Item Cross fault detection mode Reset mode Logical AND connection input mode Setting position Y1 terminal T32 T33 terminal Logical AND connection preset switch Indicat status Setting mode Setting status Lit Detection mode Y1 = open Not lit Non-detection mode Y1 = 24 VDC Lit Manual reset mode T33 = 24 VDC Not lit Auto reset mode T32 = 24 VDC Lit Enable logical AND input AND Not lit Disable logical AND input OFF * 19

20 Fault Detection When the Non-contact Do Switch Controller detects a fault, the ERR indicat and/ other indicats light up flash to infm the user about the fault. Check and take necessary measures referring to the following table, and then re-supply power to the Non-contact Do Switch Controller. (G9SX-NS202-@/NSA222-T03-@) ERR indicat Flashes Lights Other indicat --- T1 flashes T2 flashes NS flashes FB flashes EI flashes ED flashes Fault Expected causes of the fault Check points and measures to take Fault due to electromagnetic disturbance of internal circuits. Fault involved with safety input 1 Fault involved with safety input 2 Fault involved with Non-contact Do Switch input Fault involved with feedback/reset inputs Fault in Expansion Unit Fault involved with instantaneous safety outputs, logical AND connection outputs, auxiliary monit output Fault involved with OFF-delayed safety outputs 1. Excessive electromagnetic disturbance 2. Failure of the internal circuit 1. Err in the wiring of safety input 1 2. Increct setting of cross fault detection input 3. Failure of the circuit of safety input 1 1. Err in the wiring of safety input 2 2. Increct setting of cross fault detection input 3. Failure of the circuit of safety input 2 1. Err in the wiring of Non-contact Do Switch input 2. Err in the wiring of Non-contact Do Switch inputs in series connections. 3. Failure of the internal circuits of Non-contact Do Switch inputs 4. Failure of the Non-contact Do Switch 1. Err in the wiring of feedback/reset input. 2. Failure of the circuit of feedback/ reset input 1. Improper feedback signals from Expansion Unit 2. Abnmal supply voltage to Expansion Unit 3. Failure of the circuit of safety relay contact outputs 1. Err in the wiring of instantaneous safety outputs 2. Failure of the circuit of instantaneous safety outputs 3. Err in the wiring of the logical AND connection output 4. Failure of the circuit of the logical AND connection output 5. Err in the wiring of the auxiliary monit output 6. Impermissible high ambient temperature 1. Err in the wiring of OFF-delayed safety relay contact outputs 2. Increct set values f OFF-delay time 3. Failure of the circuit of OFF-delayed safety relay contact outputs 4. Impermissible high ambient temperature 1. Check the disturbance level around the G9SX and the related system. 2. Replace with a new product. 1. Check the wiring to T11 and T Check the wiring to Y1. 3. Replace with a new product. 1. Check the wiring to T21 and T Check the wiring to Y1. 3. Replace with a new product. 1. Check the wiring to D1 and D2. 2. Check the wiring to the D40A. 3. Replace with a new product. 4. Replace with a new D40A. 1. Check the wiring to T31, T32 and T Replace with a new product. 1. Check the connecting cable of Expansion Unit and the connection of the termination socket. 2. Check the supply voltage to Expansion Unit. Note: Make sure that all Expansion Units' PWR indicats are lit. 3. Replace with a new product. 1. Check the wiring to S14 and S Replace with a new product. 3. Check the wiring to L1. 4. Replace with a new product. 5. Check the wiring to X1. 6. Check the ambient temperature and spacing around the G9SX. 1. Check the wiring to S44 and S Check the settings of the OFF-delay time setting switch. 3. Replace with a new product. 4. Check the ambient temperature and spacing around the G9SX. 20

21 ERR indicat Lights Other indicat AND flashes Fault Expected causes of the fault Check points and measures to take Fault involved with logical AND connection input 1. Err in the wiring of the logical AND connection input 2. Increct setting f the logical AND connection input 3. Failure of the circuit of the logical AND connection input 1. Check the wiring to T41 and T42. Note: 1. Make sure that the wiring length f the T41, T42 terminal is 100 meters less. 2. Make sure that the logical AND connection signal is branched f 4 units fewer. 2. Confirm the set value of the logical AND connection preset switch. 3. Replace with a new product. When indicats other than the ERR indicat flash, check and take necessary actions referring to the following table. ERR indicat Off All indicats except PWR flash (Expansion Unit) ERR indicat Lights Other indicats T1 T2 flash Other indicats --- Supply voltage outside the rated value 1. Supply voltage outside the rated value 1. Check the supply voltage to the Units. Fault Expected cause of the fault Check points and measures to take Mismatch between input 1 and input 2. The input status between input 1 and input 2 is different, due to contact failure a sht circuit of safety input device(s) a wiring fault. Check the wiring from safety input devices to the G9SX. Or check the input sequence of safety input devices. After removing the fault, turn both safety inputs 1 and 2 to the OFF state. Fault Expected cause of the fault Check points and measures to take Fault involved with safety relay outputs of Expansion Units 1. Welding of relay contacts 2. Failure of the internal circuit Replace with a new product. 21

22 Application Examples D40A/G9SX-NS (24 VDC) (1-channel Emergency Stop Switch Input + Non-contact Do Switch/Manual Reset) S2 11 Feedback Loop KM1 Actuat Non-contact Do Switch Mot controller S14 S1 12 S3 KM2 KM1 A1 NC NC NC NC AND T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42 OFF G9SX-NSA222-T03 White Control circuit Black Brown blue KM2 M1 Emergency stop switch S1 Timing chart Emergency stop switch operation A2 S14 S24 S44 S54 L1 KM1 KM2 X1 X2 PLC etc. Non-contact Do Switch S2 Reset switch S3 G9SX S14 GND Mot controller (Operation command) S1: Emergency Stop Switch S2: Non-contact Do Switch S3: Reset Switch KM1, KM2: Contact M1: 3-phase mot Note: 1. This example cresponds to categy F details on Non-contact Do Switch wiring, refer to pages 15 and 16 to the User s Manual. G9SX S44,S54 KM1, KM2 N.C. contact KM1, KM2 N.O. contact Operation command Rotation of mot OFF-delay time OFF-delay time G9SX-NSA222-T03-@ (24 VDC) (2-channel Safety Limit Switch Input + Non-contact Do Switch/Auto Reset) 23 S S1 12 Feedback Loop KM1 Actuat S3 Non-contact Do Switch Mot controller S14 KM2 KM1 open A1 NC NC NC AND T11 T12 T21 T22 T31 T32 T33 Y1 D1 D2 D3 D4 T41 T42 OFF G9SX-NSA222-T03 White Black Brown Blue KM2 M1 Control circuit Timing chart Safety limit switch S1 A2 S14 S24 S44 S54 L1 KM1 KM2 X1 X2 PLC etc. Limit switch S2 Non-contact Do Switch S3 GND Mot controller (Operation command) S1: Safety limit switch S2: Limit switch S3: Non-contact Do Switch KM1, KM2: Contact M1: 3-phase mot G9SX S14 G9SX S44, S54 KM1, KM2 N.C. contact KM1, KM2 N.O. contact Operation command Note: 1. This example cresponds to categy F details on Non-contact Do Switch wiring, refer to pages 15 and 16 to the User s Manual. Rotation of mot OFF-delay time OFF-delay time 22

23 G9SX-BC202 (24 VDC) (2-channel Emergency Stop Switch Input/Manual Reset) + G9SX-NS202-@ (24 VDC) (Non-contact Do Switch Input/Auto Reset) Feedback Loop S1 A S2 KM1 KM2 NC T11 T12 T21 T22 T31 T32 T33 Y1 G9SX-BC202 (Unit 1) KM1 KM2 M1 A2 Control circuit S14 S24 L1 L2 X1 X2 S1: Emergency Stop Switch S2: Reset Switch KM1, KM2: Contact M1: 3-phase mot KM1 KM2 PLC etc. S3 Actuat Non-contact Do Switch Feedback Loop KM3 KM4 White Black Brown Blue A1 D1 D2 D3 D4 T31 T32 T33 T41 T42 G9SX-NS202 (Unit 2) AND OFF G9SX-BC202 (Unit 1) Emergency stop switch S1 Timing chart Emergency stop switch operation Control circuit KM3 Reset switch S2 Unit 1 S14, S24 KM4 KM1, KM2 N.C. contact A2 S14 S24 KM3 KM4 L1 X1 X2 PLC etc. M2 KM1, KM2 N.O. contact Logical AND output L1 Rotation of mot M1 S3: Non-contact Do Switch KM3, KM4: Contact M2: 3-phase mot Note: 1. This example cresponds to categy F details on Non-contact Do Switch wiring, refer to pages 15 and 16 to the User s Manual. G9SX-NS202-@ (Unit 2) Logical AND input T41 Non-contact Do Switch S3 Unit 2 S14, S24 KM3, KM4 N.C. contact KM3, KM4 N.O. contact Rotation of mot M2 23

24 Safety Precautions Refer to the Precautions f All Switches and Precautions f All Safety Do Switches.!CAUTION Serious injury may possibly occur due to breakdown of safety outputs. Do not connect loads beyond the rated value to the safety outputs. Serious injury may possibly occur due to loss of required safety functions. Wire the D40A and G9SX-NS properly so that supply voltages voltages f loads do NOT touch the safety outputs accidentally. Serious injury may possibly occur due to damage to safety outputs. Provide protective circuits against counter-electromotive fce if inductive loads are connected to safety outputs. Serious injury may possibly occur due to loss of safety functions. Use appropriate devices referring to the infmation provided below. The machine may start operating and may result in serious injury death. Do not put the actuat close to the switch when the do is open. Control device Emergency stop switch Safety do switch, Safety limit switch Non-contact Do Switch Relay with fcibly guided contacts Contact Other devices Requirements Use approved device with direct opening mechanism complying with IEC/EN Use approved device with direct opening mechanism complying with IEC/EN and capable of switching micro loads of 24 VDC, 5 ma. The G9SX-NS must be used with D40A Non-contact Do Switches. Use approved devices with fcibly guided contacts complying with EN F feedback, use devices with contacts capable of switching micro loads of 24 VDC, 5 ma. Use contacts with fcibly guided mechanism to input the signal to the Feedback/Reset input of the G9SX-NS through the NC contact of the contact. F feedback, use devices with contacts capable of switching micro loads of 24 VDC, 5 ma. Failure to open contacts of a contact cannot be detected by connecting NC contact of the contact without a fcibly guided mechanism to the Feedback/Reset input. Evaluate whether devices used are appropriate to satisfy the requirements of the safety categy level. Precautions f Safe Use 1. Disconnect the G9SX-NS from the power supply when wiring the D40A. 1. Turn OFF the load power supply befe wiring. Failure to do so may cause electric shock. 2. Devices connected to the product may operate unexpectedly. 2. Do not operate the product in atmospheres containing flammable explosive gas. Arcs heating of relays during switching may cause fire explosion. 3. Wire conducts crectly and verify the operation of the product befe using the system in which the product is incpated. Increct wiring may lead to loss of safety functions. 4. Auxiliary moniting outputs are NOT safety outputs. Do not use auxiliary moniting outputs as safety outputs. Such increct use will cause loss of safety function of D40A and peripheral devices. 5. After installing the D40A, qualified personnel must confirm the installation, and must conduct test operations and maintenance. The qualified personnel must be qualified and authized to secure safety at each phases of design, installation, running, maintenance, and disposal of the system. 6. A qualified person in charge, who is familiar with the machine in which the D40A is to be installed, must conduct and verify the installation. 7. Be sure to inspect the D40A daily and every 6 months. Otherwise, serious injury may possibly occur due to system malfunctions. 8. Connect the D40A to only appropriate components devices complying with relevant safety standards cresponding to the required level of safety categy. Confmity to requirements of the safety categy must be determined f the entire system. It is recommended to consult an authized certification body regarding assessment of confmity to the required safety level. 9. Do not dismantle, repair, modify the product. Doing so may lead to loss of safety functions. 10. Use the G9SX within an enclosure with a IP54 degree of protection higher accding to IEC/EN Do not apply DC voltages exceeding the rated voltages, n any AC voltages to. 12. Use a DC supply satisfying the requirements given below to prevent electric shock. A DC power supply with double reinfced insulation, f example, accding to IEC/EN EN 50178, a transfmer accding to IEC/EN A DC supply satisfying the requirements f class 2 circuits limited voltage/current circuits stated in UL Properly apply the specified voltages to the inputs. Applying inappropriate voltages may cause the product to fail to perfm its specified function, which could lead to the loss of safety functions damages to the product. 14. Auxiliary err outputs and auxiliary moniting outputs are NOT safety outputs. Do not use these outputs as safety outputs. Such increct use will cause loss of safety functions of the G9SX and its relevant system. Also logical AND connection outputs can only be used f logical AND connections with the G9SX-@. 15. After installing the, qualified personnel must confirm the installation, and must conduct test operations and maintenance. The qualified personnel must be qualified and authized to secure safety at each phases of design, installation, running, maintenance, and disposal of system. 16. A qualified person in charge, who is familiar with the machine in which is to be installed, must conduct and verify the installation. 17. Perfm daily and 6-month inspections f the. Otherwise, the system may fail to wk properly, resulting in serious injury. 24

25 18. Connect to the only appropriate components devices complying with relevant safety standards cresponding to the required level of safety categy. Confmity to requirements of safety categy must be determined as an entire system. It is recommended to consult an authized certification body regarding assessment of confmity to the required safety level. 19. OMRON is not responsible f confmity with any safety standards covering the customer's entire system. 20. Be careful not to have your fingers caught when mounting terminal blocks. 21. The service life will depend on the switching conditions. Be sure to check the actual operating conditions using the actual devices, and make sure that the number of switching operations will not cause perfmance problems. Precautions f Crect Use 1. Connection with Non-contact Do Switch Wire conducts between the and the D40A Non-contact Do Switch crectly and verify operation, befe using the system. 2. The D40A must be used with a designated actuat and Controller. 3. Handle with Care. Do not drop the product expose it to excessive vibration mechanical shock. The product may be damaged and may not function properly. 4. Stage and Operating Conditions Do not ste use the products under the following conditions. 1. In direct sunlight 2. At ambient temperatures not between 10 and 55 C 3. At relative humidity not between 25% and 85% under temperature changes that could causes condensation 4. In crosive combustible gases 5 Where subject to vibration mechanical shock beyond the rated values 6. Where subject to contact with water, oil, chemicals 7. In an atmosphere containing excessive dust, saline, metal powder 8. Where iron filings powder may fall on the product 5. Use cables with a length of less than 100 m total to connect D40A Switches. Total wiring length 100 m max. D1 D2 D3 D4 G9SX-NS202-@ G9SX-NSA222-T03-@ 6. Disconnect the from the power supply when replacing the D40A. Devices connected to the may operate unexpectedly. 7. Do not use the D40A in a magnetic field of 1.5 mt higher. The D40A may not function properly. 8. Do not use the D40A in the water in an environment continuously exposed to water. Water may penetrate into the D40A. (The IP67 degree of protection f this switch means that it has been checked f penetration of water after having been left in water f a fixed period of time.) 9. Be sure to mount a guard stopper and guide to prevent the D40A Non-contact Do Switch from being subjected to impact. 10. Do not use the switch actuat as a stopper. Protect the switch and the actuat by installing a stopper. Separate the switch and the actuat to a distance of 1 mm me. 25

Compact Non-Contact Door Switch/Non-Contact Door Switch Controller D40A/G9SX-NS

Compact Non-Contact Door Switch/Non-Contact Door Switch Controller D40A/G9SX-NS Compact Non-Contact Do Switch/Non-Contact Do Switch Controller D40A/G9SX-NS Electronic Detection Mechanism f Better Stability in Non-contact Do Switch Operation Connection is also possible to a G9SP Safety

More information

Compact Non-Contact Door Switch/Non-Contact Door Switch Controller D40A/G9SX-NS

Compact Non-Contact Door Switch/Non-Contact Door Switch Controller D40A/G9SX-NS Compact Non-Contact Do Switch/Non-Contact Do Switch Controller D40A/G9SX-NS Electronic Detection Mechanism f Better Stability in Non-contact Do Switch Operation Be sure to read the Safety Precautions on

More information

Making Hazardous Operations Safe and Productive

Making Hazardous Operations Safe and Productive NEW Safety Guard Switching Unit G9SX-GS Making Hazardous Operations Safe and Productive Making Hazardous Operations Safe and Productive This new addition to the model of Flexible Safety Unit G9SX series

More information

G9SX-GS. Safety Guard Switching Unit. A Safety Measure for Hazardous Operations That Does Not Lower Productivity. Auto Switching Function

G9SX-GS. Safety Guard Switching Unit. A Safety Measure for Hazardous Operations That Does Not Lower Productivity. Auto Switching Function Safety Guard Switching Unit CSM DS_E_6_1 A Safety Measure for Hazardous Operations That Does Not Lower Productivity Two functions support two types of application: Auto switching: For applications where

More information

Expansion Unit G9SX-EX Safety 2 Instantaneous safety outputs

Expansion Unit G9SX-EX Safety 2 Instantaneous safety outputs Flexible Safety Unit / Safety Guard Switching Unit G9SX/G9SX-GS CSM_G9SX_G9SX-GS_DS_E_8_1 Logical Function Adds Flexibility to Various Safety Circuits Be sure to read the Safety Precautions on page 45.

More information

G9SX-LM. Low-speed Monitoring Unit. Low-speed Monitoring Function Ensures Safety for Maintenance Work. Model Number Structure.

G9SX-LM. Low-speed Monitoring Unit. Low-speed Monitoring Function Ensures Safety for Maintenance Work. Model Number Structure. Low-speed Monitoring Unit G9SX-LM Low-speed Monitoring Function Ensures Safety for Maintenance Work Motor rotation speed detected by Proximity Sensor. Monitors and confirms that speed does not exceed the

More information

For full product information, visit Use the SpeedSPEC Code for quick access to the specific web page.

For full product information, visit   Use the SpeedSPEC Code for quick access to the specific web page. Safety Relays G9SX-GS G9SXGS For full product information, visit www.sti.com. Use the SpeedSPEC Code for quick access to the specific web page. Safety Guard Switching Unit A safety measure for hazardous

More information

Main contacts Auxiliary contact Number of input channels Rated voltage Model Category 24 VAC/VDC 3PST-NO SPST-NC 1 channel or 2 channels possible

Main contacts Auxiliary contact Number of input channels Rated voltage Model Category 24 VAC/VDC 3PST-NO SPST-NC 1 channel or 2 channels possible Safety Relay Unit Four kinds of -mm wide Units are available: A -safety contact model, a -safety contact model, and models with safety contacts and OFF-delay safety contacts. Also available are 7.-mm wide

More information

DPST-NO None 2 channels Auto-reset Inverse (+/-) 24 VAC/VDC 4 G9SB-2002-A 1 channel or 2

DPST-NO None 2 channels Auto-reset Inverse (+/-) 24 VAC/VDC 4 G9SB-2002-A 1 channel or 2 Safety Relay Unit Ultra Slim Safety Relay Unit 17.5 mm wide models available with 2 or 3 poles. 22.5 mm wide 3 pole models also available EN Standards (TÜV approval) DIN-track mounting possible Ordering

More information

Safety Door Switches. Contents. Selection Guide F-2. Tongue Switches D4NS F-6 T5009 & T F-14 T4012 F-20 T4016 F-20 T2008 F-21 D4GS-N F-26

Safety Door Switches. Contents. Selection Guide F-2. Tongue Switches D4NS F-6 T5009 & T F-14 T4012 F-20 T4016 F-20 T2008 F-21 D4GS-N F-26 Safety Do Switches Contents Selection Guide F-2 Tongue Switches D4NS F-6 T5009 & T5009-6 F-14 T4012 F-20 T4016 F-20 T2008 F-21 D4GS-N F-26 Guardlocking Switches D4SL-N F-27 D4NL F-45 TL4019 F-55 TL4024

More information

G9SA. Ordering Information. Safety Relay Unit. The G9SA Series Offers a Complete Line of Compact Units. H Several types of 45-mm wide Units are

G9SA. Ordering Information. Safety Relay Unit. The G9SA Series Offers a Complete Line of Compact Units. H Several types of 45-mm wide Units are Safety Relay Unit The G9SA Series Offers a Complete Line of Compact Units H Several types of -mm wide Units are available: a -pole model, a -pole model, models with poles and OFF-delay poles H 7.-mm wide

More information

G9SA. Safety Relay Unit. The G9SA Series Offers a Complete Line-up of Compact Units. Model Number Structure

G9SA. Safety Relay Unit. The G9SA Series Offers a Complete Line-up of Compact Units. Model Number Structure Safety Relay Unit G9 CSM_G9_DS_E The G9 Series Offers a Complete Line-up of Compact Units. Four kinds of -mm wide Units are available: A -pole model, a -pole model, and models with poles and OFF-delay

More information

Safety Relay Unit (I/O Unit Type)

Safety Relay Unit (I/O Unit Type) Safety Relay Unit (I/O Unit Type) CQM1-SF200/ CS1W-SF200 Same Dimensions as I/O Unit Less Installation Space and Wiring Required Safety Relay Unit that can be used as an I/O Unit for OMRON s CQM1H and

More information

Thread length (overall length) material

Thread length (overall length) material Cylindrical Proximity Sensor for Mobile Usage Designed and tested to keep your machines moving IP69k tested and certified for highest water resistance e1 type approval (according to automotive directive

More information

Installation Sensing distance Connection Output configuration Operation mode NO Operation mode NC

Installation Sensing distance Connection Output configuration Operation mode NO Operation mode NC Standard (thin shape) Inductive Proximity Sensor Thin shape for space saving surface mounting Direct side wall mounting for bracket-less installation Ordering Information DC 3-wire Models Installation

More information

E2Q4 Square Proximity Sensor

E2Q4 Square Proximity Sensor Inductive Square Slim, compact size M2 Plug-in connection Integrated short circuit and reverse polarity protection Active face positioning: Y-axis 5, X-axis 90 incremets Ordering Information DC type Connection

More information

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions HITACHI EH-150 series PLC Resistance Temperature Detective input module Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction

More information

E2A. Ordering Information. Cylindrical Proximity Sensor. Safe Mounting with Greater Sensing Distance. E2A Cylindrical Proximity Sensor 1

E2A. Ordering Information. Cylindrical Proximity Sensor. Safe Mounting with Greater Sensing Distance. E2A Cylindrical Proximity Sensor 1 Cylindrical Proximity Sensor E2A Safe Mounting with Greater Sensing Distance Ensures a sensing distance approximately 1. to 2 times larger than that of any conventional OMRON Sensor. Problems such as the

More information

D40Z. Versatile applications. Compact Non-contact Door Switch. Wide range of applications at the highest safety level

D40Z. Versatile applications. Compact Non-contact Door Switch. Wide range of applications at the highest safety level Compact Non-contact Door Switch Wide range of applications at the highest safety level» Visible safety Ultimate safety level» Versatile applications Compliant with Safety Category 4/PLe (ISO 13849-1) The

More information

Safety Monitoring Relays

Safety Monitoring Relays Safety Monitoring Relays G9SA G9SA Safety Relay Unit Four kinds of 45-mm wide units are available: A 3-pole model, a 5-pole model, and models with 3 poles and 2 OFF-delay poles, as well as a two-hand controller.

More information

Inductive Proximity Sensor

Inductive Proximity Sensor Inductive Proximity Sensor Subminiature Sensor with Cable Amplifier Offers Greater Mounting Flexibility Programmable Controller-compatible Subminiature, shielded sensing head (3 or 8 dia.) allows the Sensor

More information

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION H Series PLC EH-150 Analog input module EH-AXH8M Instruction manual Thank you for purchasing a Hitachi Programmable Logic Controller. To operate it safely, please read this instruction manual and all the

More information

Inductive Proximity Sensor

Inductive Proximity Sensor Inductive Proximity Sensor Miniature, Slim-styled Proximity Sensor Space-saving Sensor ideal for timing cam and dog detection. Four mounting holes provided: two each mounting from side or rear of the housing.

More information

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm

Thread length. 27 (40) mm. 27 (44) mm. 27 (40) mm. 34 (50) mm. 34 (49) mm. 39 (60) mm. 39 (54) mm. 44 (65) mm. 44 (59) mm Long Distance Cylindrical. Extra long for increased protection and sensing performance triple proximity sensors for flush mounting requirements. designed and tested for extra long life. Ordering Information

More information

Compact Non-contact Door Switch D40Z. Wide range of applications at the highest safety level

Compact Non-contact Door Switch D40Z. Wide range of applications at the highest safety level Compact Non-contact Door Switch Wide range of applications at the highest safety level» V i s i b l e s a f e t y U l t i m a t e s a f e t y l e v e l» V e r s a t i l e a p p l i c a t i o n s Compliant

More information

Solid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately)

Solid-state Timer. Ordering Information. Miniature Timer with Multiple Time Ranges and Multiple Operating Modes H3YN- - Accessories (Order Separately) Solid-state Timer Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple

More information

Tecnología en Electrónica y Control SRL Ficha Técnica

Tecnología en Electrónica y Control SRL Ficha Técnica Tecnología en Electrónica y Control SRL Ficha Técnica Relé de seguridad Tecnología en Electrónica y Control SRL Oficina Central Wüthrich 949 San Carlos Centro (S3013DES) / Santa Fe / Argentina Tel./Fax/Líneas

More information

Classification Applicable models Specification Type Model

Classification Applicable models Specification Type Model Connect Terminal Box (Muting Terminals) F39-TC5 CSM_F39-TC5_DS_E_4_1 Significantly reduces amount of wiring between Safety Light Curtains and Muting Senss. As of August 2008 Provides IP67 protection against

More information

Safety Monitoring Relays

Safety Monitoring Relays Safety Monitoring Relays Contents Selection Guide I-2 Safety Monitoring Relays G9SA I-6 SR101A I-12 SR103AM I-13 SR104P I-17 SR105E I-17 SR106ED I-21 SR108AD & SR109AD I-18 SR120MP I-21 SR125SMS45 I-22

More information

Slim Relay G2RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. Relay and Socket Combinations

Slim Relay G2RV. Model Number Structure. Ordering Information. Model Number Legend. List of Models. Relay and Socket Combinations Slim Relay G2RV The World's First Industrial Slim Relay Large plug-in terminals for reliable connection. LED indicator and mechanical flag to check operation. Transparent housing enables checking relay

More information

Solid-state Timer. Ordering Information. Ultra-slim Timer for G2R Relay Socket. H3RN-jj. Accessories (Order Separately) Connecting Socket

Solid-state Timer. Ordering Information. Ultra-slim Timer for G2R Relay Socket. H3RN-jj. Accessories (Order Separately) Connecting Socket Solid-state Timer Ultra-slim Timer for G2R Relay Socket Pin configuration compatible with G2R Relay and mounts to the P2R/P2RF Socket. Standard multiple time ranges and multiple operating modes. Conforms

More information

Ordering Information. Smart Sensors (Inductive Displacement Type) ZX Series. Sensors

Ordering Information. Smart Sensors (Inductive Displacement Type) ZX Series. Sensors Smart Sensors (Inductive Displacement Type) ZX Series Smart Sensors that use the eddy current method are now available. Develop new applications with sub-micron sensing technology.. Ordering Information

More information

4 mm. 8 mm. Proximity Sensor. Sensing head Sensing distance Output configuration Part Number M18 Shielded 4 mm DC 3-wire PNP-NO E2EZ-X4B1 M30

4 mm. 8 mm. Proximity Sensor. Sensing head Sensing distance Output configuration Part Number M18 Shielded 4 mm DC 3-wire PNP-NO E2EZ-X4B1 M30 Sensing distance Supply voltage Output 4 mm 8 mm 12 to 24 VDC 100 to 220 VAC 200 ma max. 100 ma max. Proximity Sensor Detects Objects without Being Influenced by Aluminum and Cast Iron Cut Chips Sense

More information

Conductive Level Controller

Conductive Level Controller Conductive Level Controller 61F-D21T-V1 Ideal for level control for industrial facilities and equipment. Outputs can be set to self-hold at ON or OFF using self-holding circuits. Sensitivity adjustment

More information

BGS (at min. setting) BGS (at max. setting)

BGS (at min. setting) BGS (at max. setting) Compact Photoelectric Sensor with Built-in Amplifier EZ-LS CSM_EZ-LS_DS_E_7_ Distance-settable Sensor Unaffected by Workpiece Color and Background Distance-settable triangulation model unaffected by color.

More information

Model Number Structure

Model Number Structure Solid State Relays with Failure Detection Function G3PC Detects failures in SSR used for heater temperature control and simultaneously outputs alarm signal. This SSR supports the safe design of heater

More information

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m. Built-in Amplifier (Medium Size) ES-A Be sure to read Safety Precautions on page 0. Ordering Information Built-in Amplifier s Red light Infrared light Sensing method Appearance Connection method Sensing

More information

D40Z. Versatile applications. Compact Non-contact Door Switch. Wide range of applications at the highest safety level

D40Z. Versatile applications. Compact Non-contact Door Switch. Wide range of applications at the highest safety level Compact Non-contact Door Switch Wide range of applications at the highest safety level» Visible safety Ultimate safety level» Versatile applications Compliant with Safety PLe/Category 4 (ISO 13849-1) The

More information

Model Number Structure

Model Number Structure Solid State Relays with Failure Detection Function G3PC CSM_G3PC_DS_E_1_1 Refer to Safety Precautions for All Solid State Relays. Detects failures in SSR used for heater temperature control and simultaneously

More information

Thread length (overall length)

Thread length (overall length) Cylindrical Proximity Sensor E2A Safe Mounting with Greater Sensing Distance Ensures a sensing distance approximately 1. to 2 times larger than that of any conventional OMRON Sensor. Problems such as the

More information

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend

G3PC. Model Number Structure. Solid State Relays with Failure Detection Function. Model Number Legend Solid State Relays with Failure Detection Function G3PC Refer to Warranty and Application Considerations (page 1), Safety Precautions (page 4), and Technical and Safety Information (page 6). Detects failures

More information

Number of input channels

Number of input channels Safety Relay Unit (Sensor Connector Type) CSM DS_E_3_1 Less Wiring Required with Safety Light Curtain Sensor connector allows direct connection to OMRON 3SJ Safety Light Curtains with PNP outputs. Reduces

More information

G9SX-SM Sensor-less Monitoring of Standstill for Machines with Long Inertia

G9SX-SM Sensor-less Monitoring of Standstill for Machines with Long Inertia New Product Standstill Monitoring Unit Sensor-less Monitoring of Standstill for Machines with Long Inertia Standstill is monitored by the motor's back electromotive force (BEMF) signal. Features a "Standard

More information

E2K-X4ME1 2M E2K-X4ME2 2M

E2K-X4ME1 2M E2K-X4ME2 2M Cylindrical Proximity Sensor EK- CSM_EK-_DS_E 1 General-purpose Threaded Sensor That Detects Metals and Non-metals Alike Detects both metallic and nonmetallic objects (water, oil, glass, plastic, etc.).

More information

E2EC-CR8D2 5.4 mm dia. 1.5 mm (0.06 in) NO E2EC-C1R5D1 NC. E2EC-C1R5D2 8mmdia. 3 mm (0.12 in) NO E2EC-C3D1 NC

E2EC-CR8D2 5.4 mm dia. 1.5 mm (0.06 in) NO E2EC-C1R5D1 NC. E2EC-C1R5D2 8mmdia. 3 mm (0.12 in) NO E2EC-C3D1 NC R Miniature Inductive Prox Subminiature Sensor with Inline Amplifier Offers Greater Mounting Flexibility H Subminiature, shielded sensing head (3-mm or 8-mm dia.) allows the Sensor to be flush-mounted

More information

Solid-state Timer H3YN

Solid-state Timer H3YN Solid-state Timer H3YN Miniature Timer with Multiple Time Ranges and Multiple Operating Modes Minimizes stock. Pin configuration compatible with MY Power Relay. Standard multiple operating modes and multiple

More information

E2KQ-X. Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster. Chemical-resistant Proximity Sensor. Ordering Information

E2KQ-X. Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster. Chemical-resistant Proximity Sensor. Ordering Information Chemical-resistant Proximity Sensor E2KQ-X CSM_E2KQ-X_DS_E_4_3 Fluororesin-coated Capacitive Sensor with Sensitivity Adjuster Excellent resistance against chemicals and oil with fluororesincoated case.

More information

Cylindrical Proximity Sensor

Cylindrical Proximity Sensor Cylindrical Proximity Sensor A New Series of Easy-to-use and Tough Models with a Yellow Indicator New series of TL-X2C1-GE models with improved performance over the previous TL-X-E models. Also, in addition

More information

Classification Enclosure rating Input voltage Type of

Classification Enclosure rating Input voltage Type of Slim Relay G2RV The World's First Industrial Slim Relay Large plug-in terminals for reliable connection. LED indicator and mechanical flag to check operation. Special input type with gold plated contacts.

More information

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS

OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS OPERATING INSTRUCTIONS 7 SERIES STATIC GENERATORS GB Contents Page 1 Introduction 4 2 Safety 5 3 Use 6 4 Checking on Delivered Equipment 6 5 General Specification and Dimensions 7 6 Positioning 10 7 Operating

More information

Ultra Slim Relays 24

Ultra Slim Relays 24 Ultra Slim Relays 24 Technical Data... 1 Specifications.2 Model Number Structure - Relays...3 Model Number Selection...4 Accessories...5 Safety Precautions...6 Ultra Slim Relays WERNER`s embody the latest

More information

PRODUCT SPECIFICATION. PC Board Relays. Series.

PRODUCT SPECIFICATION. PC Board Relays. Series. PRODUCT SPECIFICATION PC Board Relays 26 Series www.wernerelektrik.com Technical Data... Specifications...2 Model Number Structure - Relays...3 Model Number Selection...4 Dimensions... 5-6 Accessories...7

More information

7. Approved Standards US: UL, CSA UL: FILE No.E CSA: FILE No.LR31928) 8. Special Function None : Standard U : For ultrasonically cleanable

7. Approved Standards US: UL, CSA UL: FILE No.E CSA: FILE No.LR31928) 8. Special Function None : Standard U : For ultrasonically cleanable Subminiature, Sensitive SPDT Signal Switching Relay High sensitivity: 98-mW (Rated power consumption: mw) pickup coil power. Impulse withstand of 1,V ( 1 μs) meets FCC requirements. Stick packing employed

More information

A16. Separate Construction with Cylindrical 16-dia. Body. Pushbutton Switch (Detachable) (Lighted/Non-Lighted) (Cylindrical 16-dia.

A16. Separate Construction with Cylindrical 16-dia. Body. Pushbutton Switch (Detachable) (Lighted/Non-Lighted) (Cylindrical 16-dia. Pushbutton Switch (Detachable) (Lighted/Non-Lighted) (Cylindrical 16-dia.) Separate Construction with Cylindrical 16-dia. Body Miniature design of 28.5 mm, the smallest class in the industry. Detachable

More information

Solid-state Timer. Ordering Information. Specifications. Miniature Timer Compatible with the MY Relay. Accessories. Time Ranges

Solid-state Timer. Ordering Information. Specifications. Miniature Timer Compatible with the MY Relay. Accessories. Time Ranges Solid-state Timer Miniature Timer Compatible with the MY Relay Large transparent time-setting knob facilitates time setting. Flat-blade and Phillips screwdrivers can also be used for time setting. Approved

More information

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m.

E3S-A. Built-in Amplifier Photoelectric Sensor (Medium Size) Ordering Information. Built-in Amplifier Photoelectric Sensors. Horizontal. 7 m. Built-in Amplifier (Medium Size) ES-A CSM_ES-A_DS_E Be sure to read Safety Precautions on page 0. Ordering Information Built-in Amplifier s Red light Infrared light Sensing method Appearance Connection

More information

Safety Control. FS1A Multi-function Safety Relay. Optional Parts. Marked Cable Tie. DIN Rail BNDN1000 Aluminum, 1m 35mm wide

Safety Control. FS1A Multi-function Safety Relay. Optional Parts. Marked Cable Tie. DIN Rail BNDN1000 Aluminum, 1m 35mm wide Control Multi-function Relay Key features: No programming required. Configuration complete by turning on a logic switch A safety circuit can be configured easily just by selecting a logic from eight preprogrammed

More information

Long-time range model (0.1 min to 10 h) 24 VAC; SPDT H3RN-1 H3RN-11 12, 24 VDC DPST-NO H3RN-2 H3RN-21

Long-time range model (0.1 min to 10 h) 24 VAC; SPDT H3RN-1 H3RN-11 12, 24 VDC DPST-NO H3RN-2 H3RN-21 Solid-state timer CSM DS_E_3_2 Ultra-slim Timer for G2R Relay Socket Pin configuration compatible with G2R Relay and mounts to the P2R/P2RF Socket. Standard multiple time ranges and multiple operating

More information

must Operate Voltage (V)

must Operate Voltage (V) force-guided relays g7sa G7SA compact, Slim relays conforming to en Standards Relays with forcibly guided contacts (EN50205 Class A, certifi ed by VDE) Supports the CE marking of machinery (Machinery Directive)

More information

E3FS. Connect up to 4 sets of E3ZS/E3FS per B1 Module for F3SX Safety Controller

E3FS. Connect up to 4 sets of E3ZS/E3FS per B1 Module for F3SX Safety Controller Single-beam Safety Sensor Type 2 Safety Photoelectric Sensor for Hazardous Gaps in Machines Note: Be sure to read the Safety Precautions International standards: IEC6496- (type 2 ESPE) IEC6496-2 (type

More information

Aluminum-detecting Proximity Sensor (Separate Amplifier Type)

Aluminum-detecting Proximity Sensor (Separate Amplifier Type) Aluminum-detecting Proximity Sensor (Separate Amplifier Type) ECY Simple Teaching Function for Simple Adjustment. Easy-to-see Excess Gain Level Indicators. Detects aluminum, copper, and other non-ferrous

More information

E3X-NA. Adjuster type standard that is the culmination of true ease and simplicity. Super Manual Fiber Amplifier. Features

E3X-NA. Adjuster type standard that is the culmination of true ease and simplicity. Super Manual Fiber Amplifier. Features Super Manual Fiber Amplifier Adjuster type standard that is the culmination of true ease and simplicity Features Self-explanatory LED bar displays of light levels The previous manual type used the stability

More information

Light ON 5m. * Light ON. 2.5m (3m) Light ON. (5m)

Light ON 5m. * Light ON. 2.5m (3m) Light ON. (5m) All voltage photoelectric sensors Built-in amplifier accepts wide supply voltage range. Slim, space-saving construction measures only x x 7.4 mm. s with long life expectancy and high switching capacity

More information

Safety Control. FS1A Multi-function Safety Relay. Optional Parts. Connecting Tool. Marked Cable Tie. DIN Rail BNDN1000 Aluminum, 1m 35mm wide

Safety Control. FS1A Multi-function Safety Relay. Optional Parts. Connecting Tool. Marked Cable Tie. DIN Rail BNDN1000 Aluminum, 1m 35mm wide Multi-function Relay Key features: No programming required. Configuration complete by turning on a logic switch A safety circuit can be configured easily just by selecting a logic from eight preprogrammed

More information

Oil-resistive, Long-range Photoelectric Sensor with Metal Housing

Oil-resistive, Long-range Photoelectric Sensor with Metal Housing Oil-resistive, Long-range with Metal Housing ES-C Water- and Oil-resistive with Metal Housing Used for Long-range Sensing Satisfies the water- and oil-resistive requirements and safe enough for use in

More information

I/O delay. (0.32 in ±0.06 in)

I/O delay. (0.32 in ±0.06 in) R Inductive Power Couplers Allows Wireless Transmission of ON/OFF Signals from Input Devices and Power to Input Devices H Use the electromagnetic coupler to transmit input signals to the B7A Output Unit

More information

Mini Photoelectric Sensor

Mini Photoelectric Sensor Mini Photoelectric Sensor High cost-performance Mini Photoelectric Sensor Saves Installation Space and Wiring Effort and Detects Minute Sensing Objects Pin-point beam (1 to 2-mm dia.) makes it possible

More information

Switching Power Supply

Switching Power Supply Switching Power Supply Highly Reliable and Full-functioned 1-year Life Expectancy, 12, 1, or 24 V output voltages, and 30, 60, 0, or 10 W power ratings. 8 to 132 VAC or 170 to 264 VAC switchable input

More information

SYSMAC Remote Transistor Module

SYSMAC Remote Transistor Module 9 SYSMAC Remote Transistor Module Ultra-compact Remote I/O Modules to Match Most Applications 1 4-point, 8-point and 16-point models 1 4-point models measure 82 W x 32 D x 64.5 H mm; 8- and 16-point models

More information

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4. Flat Proximity Sensor EK-F CSM_EK-F_DS_E Flat Capacitive Sensor with a Thickness of Only mm Flat Sensor with excellent space efficiency. (Model with built-in Amplifier is only mm thick.) Direct mounting

More information

Bulletin 700-SH Solid-State Relays. Overview/Product Selection. Bulletin 700-SH. Product Selection

Bulletin 700-SH Solid-State Relays. Overview/Product Selection. Bulletin 700-SH. Product Selection Overview/Product Selection Bulletin 700-SH 40 A (resistive) Max. Continuous (Output) Current with Heat Sink 264V AC or 528V AC Max. Voltage Range Options 5 24V DC, 100 120V AC, 200 240V AC Control Input

More information

D5B. Detects Objects in Multiple Directions with High Sensitivity, Ideal for Robotics. Mechanical Touch Switch. Model Number Structure

D5B. Detects Objects in Multiple Directions with High Sensitivity, Ideal for Robotics. Mechanical Touch Switch. Model Number Structure Mechanical Touch Switch D5B CSM_D5B_DS_E_3_2 Detects Objects in Multiple Directions with High Sensitivity, Ideal for Robotics Slow-action switching mechanism used. Gold-plated contact with coil spring

More information

Conforms to VDE0435/2021 C/250, VDE0110, VDE0106/P100 Conforms to EN , pren

Conforms to VDE0435/2021 C/250, VDE0110, VDE0106/P100 Conforms to EN , pren Solid-state Power OFF-delay Timer II DIN 22.5-mm Solid-state Power OFF-delay Timer High immunity to invertor noise. Long power OFF-delay times; S-series: up to 12 seconds, L-series: up to 120 seconds.

More information

Safety outputs Auxiliary outputs Rated voltage Terminal block type Model SPDT-NO SPDT-NC 24 VDC Screw terminals MC3

Safety outputs Auxiliary outputs Rated voltage Terminal block type Model SPDT-NO SPDT-NC 24 VDC Screw terminals MC3 / Controller UM/ CSM_UM DS_E_5_1 New That Is Easy to Install and Maintain Meets Safety Category 3, PLd (EN ISO13849-1) requirements when used in combination with a dedicated controller. Simple connection

More information

Model Number Structure

Model Number Structure Solid State Relays CSM DS_E_3_1 Compact, Low-cost, SSR Switching 5 to 20 A Wide load voltage range: 75 to 264 VAC. Both 100-V and 200-V loads can be handled with the same model. Dedicated, compact aluminum

More information

EE-SX97 40% Built-in connector enables downsizing and easier connection. Protective circuit for safe operation. Slot-type Photomicrosensor.

EE-SX97 40% Built-in connector enables downsizing and easier connection. Protective circuit for safe operation. Slot-type Photomicrosensor. Slot-type Photomicrosensor EE-SX CSM_EE-SX_DS_E Built-in connector enables downsizing and easier connection. Protective circuit for safe operation. A built-in connector minimizes the shape and dimensional

More information

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4.

E2K-F. Flat Capacitive Sensor with a Thickness of Only 10 mm. Flat Proximity Sensor. Ordering Information. Sensors [Refer to Dimensions on page 4. Flat Proximity Sensor EK-F CSM_EK-F_DS_E Flat Capacitive Sensor with a Thickness of Only mm Flat Sensor with excellent space efficiency. (Model with built-in Amplifier is only mm thick.) Direct mounting

More information

2. Actuator B: Ball type P: Pin type F: Flat type

2. Actuator B: Ball type P: Pin type F: Flat type Contact Displacement Sensor Built-in Amplifier Ensures Ease of Use and Saves Wiring Effort. Sensor Operates with a Low Force in a Wide Range of Applications. H Works with a low operating force (30 gf)

More information

Voltage Current Front-mounting bracket

Voltage Current Front-mounting bracket Switching Power Supply S8PS Compact DIN-Rail Mounting Industrial Power Supplies with Capacities Up to 600 W Models range from 0 W to 600 W. Universal input: voltage range 0 to 240 VAC. Power Factor Correction

More information

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M Chip-immune Inductive EEZ CSM_EEZ_DS_E Chip-immune Inductive Correct operation even with aluminum or iron chips sticking to the. Only the sensing object is detected. Pre-wired Smartclick Connector s also

More information

Cable specifications PVC

Cable specifications PVC IO-Link Proximity Sensor (Spatter-resistant Models) EEQ-@-IL@ IO-Link Makes Sensor Level Information Visible and Solves the hree Major Issues at Manufacturing Sites! A Proximity Sensor hat Can Be Used

More information

Aluminum Excellent Performance, with Aluminum Chip Immunity! The indicator is visible from any direction.

Aluminum Excellent Performance, with Aluminum Chip Immunity! The indicator is visible from any direction. All Metals and Long- Types CSM DS_E and Both Detectable from Long Distances times the aluminum detection of previous models Twice the max. Equipped with a function to prevent the detection of aluminum

More information

S8VE (60/90/120/180/240-W Models)

S8VE (60/90/120/180/240-W Models) Switch Mode Power Supply S8VE (60/90/120/180/240-W Models) CSM_S8VE_DS_E_1_1 60/90/120/180/240-W Models Improved Versions of Standard-type Power Supplies without Indication Monitor. Safety standards: UL508/60950-1,

More information

(Applicable output load) to 264 (see note 2) (see note 1) (2Aat75to264VAC) G3R-202SLN-US PCB Yes 2 A at 100 to 120 VDC. (2 A at 75 to 132 VDC)

(Applicable output load) to 264 (see note 2) (see note 1) (2Aat75to264VAC) G3R-202SLN-US PCB Yes 2 A at 100 to 120 VDC. (2 A at 75 to 132 VDC) Solid-state Relay Compact SSRs Ideal for Built-in Applications Vertical, compact SSRs with an operation indicator offered in versatile variations. Can be mounted side by side with an electromagnetic relay

More information

Model Number Structure

Model Number Structure Total Counter/Time Counter (DIN 8 x ) CSM DS_E DIN 8 x -mm Total Counter/Time Counter with Easy-to-read Displays and Water and Oil Resistance Equivalent to IP66 High-visibility, negative transmissive LCD

More information

Sensing method Appearance Connection method Sensing distance Part number NPN output PNP output Through-beam Prewired (2 m) E3Z-T61A E3Z-T81A 10 m

Sensing method Appearance Connection method Sensing distance Part number NPN output PNP output Through-beam Prewired (2 m) E3Z-T61A E3Z-T81A 10 m Through-Beam Sensor with Visible Red LED Visible Beam Allows Visual Confirmation of the Detection Spot, for Easy Installation and Maintenance Built-in amplifier Mutual interference protection filter included

More information

NPN output PNP output Cord connection Cord length: 2 m Through-beam 7 m Light-ON. 2 m. (selectable by wiring) Diffuse reflective 0.

NPN output PNP output Cord connection Cord length: 2 m Through-beam 7 m Light-ON. 2 m. (selectable by wiring) Diffuse reflective 0. Built-in Amplifier Photoelectric Sensor E3V3 Easy-to-use, Low-cost Photoelectric Sensor Incorporating s that can be clearly seen from a distance. A series of models with an M8 metal junction connector

More information

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E

LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E LOGIC CONTROLLER INSTALLATION MANUAL NTR 756 B /E Table of contents 1. INTRODUCTION...1 2. HARDWARE DESCRIPTION...2 3. INSTALLATION...6 4. CONNECTION...8 5. USER SAFETY AND PROTECTION OF THE EQUIPMENT...11

More information

Common to all H7E. Accessories (Order Separately) New H7E (Except for PCB-mounting Counter) Y92F-35 Compact Flush Mounting Bracket

Common to all H7E. Accessories (Order Separately) New H7E (Except for PCB-mounting Counter) Y92F-35 Compact Flush Mounting Bracket RST Common to all H7E Accessies (Order Separately) New H7E (Except f PCB-mounting Counter) The New H7E models are supplied with a mounting bracket (Y92F-34) and nut. Additionally, the Y92F-75/-76/-77B

More information

D2VW. Sealed Miniature Basic Switch. Ordering Information Model Number Legend D2VW- -

D2VW. Sealed Miniature Basic Switch. Ordering Information Model Number Legend D2VW- - Sealed Miniature Basic Switch Sealed Miniature Basic Switch Conforms to IP67 (Molded Lead Wire Type Only) Use of epoxy resin assures stable sealing, making this switch ideal for places subject to water

More information

Operating instructions. Switching amplifier DN0210 DN / / 2015

Operating instructions. Switching amplifier DN0210 DN / / 2015 Operating instructions Switching amplifier DN0210 DN0220 UK 80011079 / 00 01 / 2015 Contents 1 Preliminary note...4 1.1 Symbols used...4 1.2 Warning signs used...4 2 Safety instructions...5 2.1 General...5

More information

Shape Model Measurement range Model Straight 50 to 300 mm. Straight 70 to 800 mm

Shape Model Measurement range Model Straight 50 to 300 mm. Straight 70 to 800 mm Digital Amplifier Ultrasonic Sensor CSM DS_E_1_1 A Reflective Sensor That Handles All Types of Sensing Object Colors and Patterns Compact with a Broad Selection of Side-view Heads Slim with analog outputs

More information

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M Chip-immune Inductive EEZ CSM_EEZ_DS_E_6_ Chip-immune Inductive Correct operation even with aluminum or iron chips sticking to the. Only the sensing object is detected. Pre-wired Smartclick Connector s

More information

Operating instructions. Standstill monitor A / / 2011

Operating instructions. Standstill monitor A / / 2011 Operating instructions Standstill monitor A300 UK 1 2 3 4 5 6 7 8 7390337 / 01 02 / 2011 1 2 3 4 5 6 7 8 switchpoint min max pulse/min power Made in Germany ifm electronic gmbh D 45127 Essen func. I II

More information

EE-SPX74/84. Ordering Information. Compact Sensor for High-Density Mounting with Easy Snap-In Connector. H Connector features a built-in safety

EE-SPX74/84. Ordering Information. Compact Sensor for High-Density Mounting with Easy Snap-In Connector. H Connector features a built-in safety Compact for High-Density Mounting with Easy Snap-In Connector H Connector features a built-in safety lock for shock and vibration resistance H replacement made simple without rewiring H Cables can be bent

More information

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M

E2EZ-X2D1-N 2M E2EZ-X2D2-N 2M Chip-immune Inductive EEZ CSM_EEZ_DS_E Chip-immune Inductive Correct operation even with aluminum or iron chips sticking to the. Only the sensing object is detected. Pre-wired Smartclick Connector s also

More information

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor

E2EY. A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Aluminum-detecting Proximity Sensor Aluminum-detecting Proximity Sensor EEY CSM_EEY_DS_E_5_1 A Proximity Sensor for Aluminum, Brass and Other Non-ferrous Metals. Iron Is Not Detected. Non-ferrous metals, such as aluminum and brass, are detected.

More information

Switching Power Supply S8E1. Ordering Information. Compact and Economical Switching Power Supply

Switching Power Supply S8E1. Ordering Information. Compact and Economical Switching Power Supply Switching Power Supply Compact and Economical Switching Power Supply Models range from 10 to 50 W Open-frame and covered types Wide range of output voltage: 5-, 12-, 15- and 24-V models UL, CSA approved

More information

G3NE. Model Number Structure. Solid State Relays. Model Number Legend. Compact, Low-cost, SSR Switching 5 to 20 A

G3NE. Model Number Structure. Solid State Relays. Model Number Legend. Compact, Low-cost, SSR Switching 5 to 20 A Solid State Relays CSM DS_E_4_1 Compact, Low-cost, SSR Switching 5 to 20 A Wide load voltage range: 75 to 264 VAC. Both 100-V and 200-V loads can be handled with the same model. Dedicated, compact aluminum

More information

Model Number Structure

Model Number Structure Analogue Temperature Controller E5C2 DIN-sized (48 x 48 mm) Temperature Controller with Analog Setting Compact, low-cost Temperature Controller. Incorporates proportional control and reset adjustment function.

More information