Parallel SelfSensing Modulating Pump Controller

Size: px
Start display at page:

Download "Parallel SelfSensing Modulating Pump Controller"

Transcription

1 Parallel SelfSensing Modulating Pump Controller Installation, Operation, and Maintenance Manual SUPERSEDES: New EFFECTIVE: November 15, 2016 Plant ID: Table of Contents Connecting Controler... 4 Wiring to the other SelfSensing pumps Button Discription... 2 Start-up/Initialization... 2 System Display... 3 Pump Status and Settings... 4 Setting ON/OFF... 4 Setting Minimum Speed... 5 Setting Maximum Speed... 5 Setting the address... 6 System Settings... 6 Control Curves... 6 Offline... 7 Constant Head... 7 Constant Flow Proportional Pressure Variable Flow Number of Pumps/Alternation/Switching Speed Units Controller Setup BACnet settings Modbus settings System Resume Controller Info Advanced Settings PID Setting Minimum pump On/Off time... 27

2 Setpoint Delta Manual Alternation Factory Reset Setting the Clock Alarms/Errors Run Control Startup/Installation Instructions and Checklist

3 3

4 Connecting Controler If the controller is not already wired to the SelfSensing drives you will want to run communication wire between them. The wire location for the controller is shown below The location of the communication wire from Drive 1 at positions (+)68 & (-) The location to the 24VDC power to the controller from drive 1 positions 12(24V DC) & 20(Common). 3. The location of the communication wire to the Building Management System (BACnet or Modbus). 4. The location on the controller for the Run/Stop command for all pumps will require a jumper at ID1 & GRD. 2 4 Wiring to the other SelfSensing pumps. Wire will need to be supplied by installer for this operation. For the SelfSensing pumps to operate in parallel they will need to be daisy chained together. All wiring is to be 20AWG copper, stranded twisted pair Installer is to run shielded wire twisted pair for communication at positions (+)68 & (-)69 Installer will need to run wire from positions 12(24V DC) & 20(Common) so that if one drive should be powered off then the MPC will stay active for the other drives still powered on. Illustration of wiring is displayed on the next page. 4

5 Drive 1 Drive 2 Drive 3 Drive 4 Connector 1 Connector 1 Connector 1 Connector 1 Position 12 Position 12 Position 12 Position 12 Position 13 Position 13 Position 13 Position 13 Position 18 Position 18 Position 18 Position 18 Position 20 Position 20 Position 20 Position 20 Connector 2 Connector 2 Connector 2 Connector 2 Position 61 Position 61 Position 61 Position 61 Position 68 Position 68 Position 68 Position 68 Position 69 Position 69 Position 69 Position 69 Connector 1 provides four programmable digital inputs terminals, two additional digital terminals programmable as either input or output, a 24 V DC terminal supply voltage, and a common for optional customer supplied 24 V DC voltage Connector 2 terminals (+)68 and (-)69 are for an RS-485 serial communications connection Connector 3 provides two analog inputs, one analog output, 10 V DC supply voltage, and commons for the inputs and output Connector 4 is a USB port available for use with the MCT 10 Set-up Software

6 Button Discription The escape button is set as a global escape. This will quit the current function and bring you back to the main screen from any of the menus. Start-up/Initialization Turn each pump to Auto On then connect power to the Multi-pump control. Upon start-up the system will go through an initialization procedure. See Startup/Installation procedure for instructions on setting up the control. The initialization procedure will include the following steps: 2

7 1. Finding the drives connected via the Modbus communication channel. These drive must be have address 1-4 with no drive having the same address. The drive the control finds will be initialized to Online if no drive is present it will be left blank. The third state Offline is for drive that are connected but not to be used. 2. Setting each drive to the correct parameters for control. 3. Starting each drive/pump to reach its maximum speed, this checks the drive for functionality. If changes need to be made to system setting, for example maximum speed, then leave the Modbus connections unconnected. The system will start-up with no errors then changes can be made. Pump number is set by address. With the default settings Pump 1 is at address 1, Pump 2 is at address 2. The lead pump will be the one with the lowest address. When the initialization procedure is done the Initializing will change to Offline. If during initialization or run time the ramp up and ramp down times of the drive are too slow or too fast this should be changed to the individual drives. This is done under 3-80 Jog Ramp Time. The control initializes this to seconds. Changing this value may result in having an effect on the PID, proceed with caution. System Display To Display the system variable scroll down to the selected system using the up/down buttons, line below pump 4, and press the enter button. The following screen will appear. Each pump can have one of three different states: 1. Running if pump is Online and running. 2. Stopped if pump is Online but not running. 3. Blank if no pump is present. The Flow, Head and Power will be continuously updated from information read from the drives. The total flow is the sum of each pumps individual flow. The total head is the average head of all pumps running. The power is the sum of all the power being used. 3

8 Pump Status and Settings Each pump will have an identical menu structure, one will be shown here for simplicity. Scroll down to the desired pump using the up/down buttons then press enter, Pump 1 is selected in this example. The Flow, Head and Power will be displayed for the pump selected. Press the enter button to access the settings menu. There are 4 options, use the up and down buttons to scroll through the menu then press the enter button to select the desired setting. Setting ON/OFF The current status of each pump will be displayed at the top of each screen. In this example the pump is Online. Use the Up/Down buttons to scroll to desired state, press enter to select. Press esc to quit and return to the main menu. Caution: wait a minimum of 5 minutes between shutting off or adding a pumps. 4

9 Setting Minimum Speed This is the minimum speed setting for each pump. The control will set the minimum speed of the system to which ever minimum speed has the highest value. 1. Use the Up/Down buttons to scroll to the desired speed. 2. Press the Program button to set. If no change is desired press the enter button. 3. Press the Enter button to exit. The range of speed is 10Hz 40Hz. Caution: Check with Taco Comfort Solutions before setting minimum speed below 20Hz. Extended use of pump with a speed below 20Hz may cause damage to the pump. Setting Maximum Speed This is the maximum speed setting for each pump. The control will set the Maximum speed of the system to whichever the maximum speed has the lowest value. 1. Use the Up/Down buttons to scroll to the desired speed. 2. Press the Program button to set. If no change is desired press the enter button. 3. Press the Enter button to exit. The range of speed is 40Hz 65Hz. Caution: Check with Taco Comfort Solutions before setting maximum speed above 60Hz. Prolonged use of pump above 60Hz can cause damage to the pump. 5

10 Setting the address This setting is for setting the Modbus address of Pump. This is only for addressing on the control side, the desired address needs to also be set at the pump, see the included pump manual for instructions. 1. Use the Up/Down buttons to scroll through the address 2. Press the Program button to set. 3. Press the Enter button to exit. Address of 1-4 are selectable. Caution: If the same address is assigned to two different pump will cause errors and the system will not function. System Settings There are 5 different options in the System Setting menu. Use the Up/Down buttons to scroll though the menu then use the Enter button to select. The Escape button will return to the Main screen. Control Curves The control curves menu is where the user can modify all the parameters of each of the selectable system functions. 6

11 Use the Up/Down Buttons to scroll to the desired function press the enter button to select the function. Press the Escape button anytime to get back to the main menu. Offline The Offline mode will switch all of the pumps that are Online to Offline. This will stop the flow of water. The control will still be in communication with the pump via the Modbus communication bus. Use the Up/Down Buttons to scroll to the Offline selection on the Control Curves Menu then press the enter button. Press the Enter button to accept and set the system to Offline or the escape button to quit and continue with current setting. Constant Head The Constant Head system function will keep the pumps running at a user defined Head set point. 7

12 To access the Constant Head submenu scroll Down the Control Curves menu using the up/down buttons to Constant Head and press the enter button. The current set point is displayed on the second line and the menu options are below. Setting Constant Head Setpoint Scroll down to Modify Head Setpoint using the up/down buttons and press the enter button. 1. Use the Up/Down buttons to set the desired setting. 2. Press the Program button to set the value. 3. Press the Enter button to exit. The system will ask you to verify the setpoint. Press the Enter button to accept the setting, press the Escape button to go back and modify. 8

13 Setting Controller for Constant Head Function To set the unit to start the Constant Head function scroll to Set Controller for Constant Head using the up/down buttons and press the enter button. The controller will verify it has been set for Constant Head. Setting Constant Head minimum Lag pump off speed The minimum speed at which the lag pump will be shut off can be adjusted. There is only two reasons this should be done. 1. If after the system switches the lag pump off the controller switches it back on after the minimum time, then switches it off again, going in a cycle. In this case the minimum switching speed can be lowered. This can also be due to the fact that the PID controller is too fast, adjust the PID first. 2. If it seems like the Lag pump is left on too long and perhaps energy savings could be had by switching it off soon. The limit can be raised but only in small increments to make sure there are no adverse effects. Use the Up/Down buttons to select OFF switching Speed then press the Enter button. 9

14 Use the Up/Down buttons to adjust the speed then the Program button to set then the Enter button to exit. Constant Flow The Constant Flow system function will keep the pumps running at a user defined Flow set point. To access the Constant Flow submenu scroll Down the Control Curves menu to Constant Flow using the up/down buttons and press enter. The current set point is displayed on the second line and the menu options are below. Setting flow setpoint To modify the Flow setpoint scroll down to Flow Setpoint using the up/down buttons the Enter button. then press 10

15 1. Use the Up/Down buttons to set the desired setting 2. Press the Program button to set the value. 3. Press the Enter button to exit. The system will ask you to verify the setpoint. Press the Enter button to accept the setting, press the Escape button to go back and modify. Setting Controller for Constant Flow function To set the unit to start the Constant Flow function scroll to Set Controller for Constant Head using the up/down buttons and press the enter button. 11

16 The controller will verify it has been set for Constant Flow. Setting Constant Flow minimum Lag pump off speed The minimum speed at which the lag pump will be shut off can be adjusted. There is only two reasons this should be done. 1. If after the system switches the lag pump off the controller switches it back on after the minimum time, then switches it off again, going in a cycle. In this case the minimum switching speed can be lowered. This can also be due to the fact that the PID controller is too fast, adjust the PID first. 2. If it seems like the Lag pump is left on too long and perhaps energy savings could be had by switching it off soon. The limit can be raised but only in small increments to make sure there are no adverse effects. Use the Up/Down buttons to select OFF switching Speed then press the Enter button. 1. Use the Up/Down buttons to adjust the speed. 2. Press the Program button to set. 3. Press the Enter button to exit. Proportional Pressure The Proportional Pressure function will calculate the required system Head based to the Flow using a linear function. To access the Proportional Pressure submenu scroll Down the Control Curves menu to Proportional Pressure using the up/down buttons and press the Enter button. 12

17 Setting Design Setpoint Use the Up/Down buttons to scroll to Set Design Setpoint then press the Enter button. The controller will display the current Head and Flow values for the design point. To set: 1. Use the Up/Down buttons to scroll to the desired Head value. 2. Press the Program button to set the desired Head point. At this point the Flow value will become active. 3. Use the Up/Down buttons to scroll to the desired Flow value. 4. Press the Program button to set the desired Flow point. No the No Flow Head percentage will be active 5. Use the Up/Down buttons to scroll to the No Flow Head Percentage (Percentage of Design Point Head). 6. Press the Program button to set the desired No Flow Head percentage. Now the Head variable will be active again. 7. Press the Enter button to exit the screen and verify. Proportional pressure and Variable Flow use the same Design Setpoint. 13

18 Press the Enter button to accept or the Escape button to return and modify the design setpoint. Setting Single Pump Setpoint. Use the Up/Down buttons to scroll to Single Pump Setpoint then press the Enter button. The controller will display the current Head and Flow values for the single pump point. To set: 1. Use the Up/Down buttons to scroll to the desired Head value. 2. Press the Program button to set the desired Head point. At this point the Flow value will become active. 3. Use the Up/Down buttons to scroll to the desired Flow value. 4. Press the Program button to set the desired Flow point. No the No Flow Head percentage will be active 5. Use the Up/Down buttons to scroll to the No Flow Head Percentage (Percentage of Design Point Head). 6. Press the Program button to set the desired No Flow Head percentage. Now the Head variable will be active again. 7. Press the Enter button to exit the screen and verify. 14

19 Proportional pressure and Variable Flow use the same Design Setpoint. Press the Enter button to accept or the Escape button to return and modify the single pump setpoint. Setting Controller for Proportional Pressure Function To set the unit to start the Proportional Pressure function scroll to Set Controller for Proportional Pressure using the up/down buttons and press the Enter button. The controller will verify it has been set for proportional pressure press the Enter button to get to the main menu. Setting proportional pressure Lag pump hysteresis This is an adjustment to the turn on/off hysteresis of Lag pumps during Proportional pressure operation. A value of 1 would be no hysteresis, range is.1 to 1. Proportional pressure and Variable Flow use the same Lag pump hysteresis. There is only two reasons this should be done. 1. If after the system switches the lag pump off the controller switches it back on after the minimum time, then switches it off again, going in a cycle. In this case the minimum switching 15

20 speed can be lowered. This can also be due to the fact that the PID controller is too fast, adjust the PID first. 2. If it seems like the Lag pump is left on too long and perhaps energy savings could be had by switching it off soon. The limit can be raised but only in small increments to make sure there are no adverse effects. Use the Up/Down buttons to select OFF switching Speed then press the Enter button. 1. Use the Up/Down buttons to adjust the speed 2. Press the Program button to set 3. Press the Enter button to exit. Variable Flow The Variable Flow function will calculate the required system Head based to the Flow using a quadratic function. To access the Variable Flow submenu scroll Down the Control Curves menu to Variable Flow using the up/down buttons and press the Enter button. Setting Design Setpoint 16

21 Use the Up/Down buttons to scroll to Set Design Setpoint then press the Enter button. The controller will display the current Head and Flow values for the design point. To set: 1. Use the Up/Down buttons to scroll to the desired Head value. 2. Press the Program button to set the desired Head point. At this point the Flow value will become active. 3. Use the Up/Down buttons to scroll to the desired Flow value. 4. Press the Program button to set the desired Flow point. No the No Flow Head percentage will be active 5. Use the Up/Down buttons to scroll to the No Flow Head Percentage (Percentage of Design Point Head). 6. Press the Program button to set the desired No Flow Head percentage. Now the Head variable will be active again. 7. Press the Enter button to exit the screen and verify. Proportional pressure and Variable Flow use the same Design Setpoint. Press the Enter button to accept or the Escape button to return and modify the design setpoint. 17

22 Setting Single Pump Setpoint. Use the Up/Down buttons to scroll to Single Pump Setpoint then press the Enter button. The controller will display the current Head and Flow values for the single pump point. To set: 1. Use the Up/Down buttons to scroll to the desired Head value. 2. Press the Program button to set the desired Head point. At this point the Flow value will become active. 3. Use the Up/Down buttons to scroll to the desired Flow value. 4. Press the Program button to set the desired Flow point. No the No Flow Head percentage will be active 5. Use the Up/Down buttons to scroll to the No Flow Head Percentage (Percentage of Design Point Head). 6. Press the Program button to set the desired No Flow Head percentage. Now the Head variable will be active again. 7. Press the Enter button to exit the screen and verify. Proportional pressure and Variable Flow use the same Single Pump Setpoint. 18

23 Press the Enter button to accept or the Escape button to return and modify the single pump setpoint. Setting Controller for Variable Flow Function To set the unit to start the Variable Flow function scroll to Set Controller for Variable Flow using the up/down buttons and press the Enter button. The controller will verify it has been set for proportional pressure. Setting Variable Flow Lag pump hysteresis This is an adjustment to the turn on/off hysteresis of Lag pumps during Variable Flow operation. A value of 1 would be no hysteresis, range is.1 to 1. Proportional pressure and Variable Flow use the same Lag pump hysteresis. There is only two reasons this should be done. 1. If after the system switches the lag pump off the controller switches it back on after the minimum time, then switches it off again, going in a cycle. In this case the minimum switching speed can be lowered. This can also be due to the fact that the PID controller is too fast, adjust the PID first. 2. If it seems like the Lag pump is left on too long and perhaps energy savings could be had by switching it off soon. The limit can be raised but only in small increments to make sure there are no adverse effects. Use the Up/Down buttons to select OFF switching Speed then press the Enter button. 19

24 1. Use the Up/Down buttons to adjust the speed 2. Press the Program button to set. 3. Press the Enter button to exit. Number of Pumps/Alternation/Switching Speed Adjusting the Number of Pumps adjust the number of pumps that is allowed to run at one time. For example, there are three pumps connected and the number of pumps is set to two. There will be one lead pump and a one lag pump. However, during alternation the third pump will be cycled in. The alternation time is also adjustable in this setting. The options are one day, two days, three days, one week, two weeks, three weeks and one month. To access the number of pumps setting from the Settings menu use the Up/Down buttons to scroll to the Number of Pumps selection the press the Enter button. 20

25 To set the number of pumps and the alternation time: 1. Use the Up/Down buttons to scroll to the desired number of pumps. 2. Press the Program button to set the desired number of pumps. At this point the alternation time will become active. 3. Use the Up/Down buttons to scroll to the desired alternation time. 4. Press the Program button to set the desired alternation time. Now the switching speed will be active. 5. Use the Up/Down buttons to scroll to the desired switching speed. 6. Press the Program button to set the desired alternation time. Now the number of pumps will be active again. 7. Press the Enter button to exit. Units The units setting will set the units displayed by the controller. There are 2 options, US standard imperial and International System (SI). The following table shows the difference: US Standard Imperial Units (Std.) International System (SI)(Int.) Flow Gallons per minute (GPM) Liters per Second (lps) Head Feet of Head (FT) Kilopascal (KPa) Power Horsepower (Hp) Kilowatts (KW) Speed Hertz (Hz) Hertz (Hz) To access the units setting from the Settings menu use the Up/Down buttons to scroll to the Units selection the press the Enter button. 21

26 To change the setting: 1. Use the Up/Down buttons to scroll to the desired units system. 2. Press the Program button to set the desired units system. 3. Press the Enter button to exit. Controller Setup In the controller setup the user can modify the Building Management System (BMS) communication protocol, set the system resume and see the controller info. To access the Controller Setup from the Settings menu use the Up/Down buttons to select Controller Setup then press the enter button. BACnet settings In the BACnet settings the Address and Baud rate are both modifiable. Baud rates are 9600 bps, bps, bps, bps, bps, and Controllers will either have the BACnet protocol or Modbus protocol but not both. To access the BACnet menu from the Controller Setup menu use the Up/Down buttons to scroll to BACnet Setup then press the enter button. 22

27 1. Use the Up/Down buttons to scroll to the desired Instance. 2. Press the Program button to set the desired Instance. At this point the baud rate will become active. 3. Use the Up/Down buttons to scroll to the desired baud rate. 4. Press the Program button to set the desired baud rate. At this point the address will become active. 5. Use the Up/Down buttons to scroll to the desired Address. 6. Press the Program button to set the desired Address. Now the address will be active again. 7. Press the Enter button to exit and verify. Press the Enter button to accept or the Escape button to return and modify the address or the baud rate. Modbus settings In the Modbus settings the Address and Baud rate are both modifiable. Baud rates are 9600 bps, bps, bps, bps, bps, and Controllers will either have the BACnet protocol or Modbus protocol but not both. This Modbus setup is for use with the building management system, the Modbus protocol to use with the drive is set and non-modifiable. To access the Modbus menu from the Controller Setup menu use the Up/Down buttons to scroll to Modbus Setup then press the enter button. 23

28 1. Use the Up/Down buttons to scroll to the desired address. 2. Press the Program button to set the desired address. At this point the baud rate will become active. 3. Use the Up/Down buttons to scroll to the desired baud rate. 4. Press the Program button to set the desired baud rate. Now the address will be active again. 5. Press the Enter button to exit and verify. Press the Enter button to accept or the Escape button to return and modify the address or the baud rate. The rest of the Modbus protocol is as follows: Data Length: 8 Stop bits: 1 Parity: Even 24

29 System Resume The system resume function determines the function of the control after an event. These events include a power outage or after the stop relay is opened. The stop relay is a relay that is connected between ID1 and GND on J8. When shorted this will turn the system offline. Is system resume is active then the controller will resume the function running before the event took place. If system resume is inactive then the controller will be offline after the event. To access the System resume function from the Controller Setup menu use the Up/Down buttons to scroll to System resume then press the enter button. 1. Toggle between active and inactive by pressing the Up/Down buttons. 2. Press the Program button to set 3. Press the Enter button to exit. Controller Info The controller information provides general information about the controller. There are no adjustable settings in this menu. To access from the Controller Setup menu use the Up/Down buttons to scroll to Controller Info then press the enter button. 25

30 Advanced Settings The advanced settings menu contains setting intended for the installer. These setting should not have to be adjusted after the installation to the system is complete. Adjustment may be necessary if there is a change in the system after installation. The Advanced Setting menu can be accessed from the Setting menu, using the Up/Down buttons scroll to Advanced Settings then press the Enter button. PID Setting Changing the PID setting will either slow down or speed up the response of the controller to changes in the system. Caution must be taken to make sure that it is not too fast as to cause oscillation, it is better to be to slow then work up to the optimal value slowly. To access the PID setting use the Up/Down buttons to scroll to PID setting in the Advanced Settings menu then press the Enter button. To change the setting: 1. Use the Up/Down buttons to scroll to the desired percentage. 26

31 2. Press the Program button to set the desired percentage. 3. Press the Enter button to exit. The range will be from.01% to 100%, with.01% being the slowest and 100% being the fastest. Minimum pump On/Off time The minimum pump on/off time is the minimum amount of time that after a pump is switched on or off the controller will not do any further pump switching. However, pump speeds will still be adjusted based on demand. This time is for settling time for the system. To access the minimum on/off time setting use the Up/Down buttons to scroll to Min On/Off Time in the Advanced Settings menu then press the Enter button. To change the setting: 1. Use the Up/Down buttons to scroll to the desired time in seconds. 2. Press the Program button to set the desired time. 3. Press the Enter button to exit. Setpoint Delta The setpoint delta setting allows the user to select how close to the setpoint the system needs to be. The Delta is a percentage of the actual setpoint. For example if the system is setup for constant flow with a setpoint delta of 1% and the setpoint is 500 GPM. The controller will try and hold the system to within +/- 5 GPM. Caution should be used when making this small as noise in the system will cause the controller to speed up and slow down unnecessarily. A wider setpoint delta would have no decrease in performance to the system but allow the motors to run smoother. Each system function will have its own delta. 27

32 To access the setpoint delta setting use the Up/Down buttons to scroll to Setpoint Delta in the Advanced Settings menu then press the Enter button. Use the Up/Down buttons to scroll to the desired function then press the Enter button to select. To change the setting: 1. Use the Up/Down buttons to scroll to the desired percentage. 2. Press the Program button to set the desired percentage. 3. Press the Enter button to exit. Manual Alternation The manual alternation function allows the user to test the alternation function. To access the manual alternation setting use the Up/Down buttons to scroll to Manual Alternation in the Advanced Settings menu then press the Enter button. 28

33 Press the Enter button to have the system perform the alternation routine, press the escape button to return to the main screen. Factory Reset To access the factory reset use the Up/Down buttons to scroll to Factory Reset in the Advanced Settings menu then press the Enter button. The Factory reset will reset some of the settings to the original factory values. See below for settings that are reset and settings that are not reset. The controller will ask you to input a password. Call Taco Technical Services to receive this password. The procedure for entering the password is 29

34 1. Scroll to the first number using the up/down buttons then press program. At this point the second number will become active. 2. Repeat this for all 4 number when finished inputting the values the first number will be active again. 3. Press the Enter Button. The control will now ask the user to press the Enter button to start a reset. If a reset is not desired then press the Escape button. Once the reset is complete the control will ask the user to re-enter the settings that are specific to the installation. See the below tables. Settings that ARE reset Setting Reset Value PID percentage 1.0 % Constant Head Setpoint Delta 2.0 % Constant Flow Setpoint Delta 2.0 % Proportional Pressure/Variable Flow Setpoint Delta 2.0 % Constant Head minimum lag pump off speed 45.0 Hz Constant Flow minimum lag pump off speed 30.0 Hz Proportional Pressure/Variable Flow lag pump off percentage 70 % Design (system) zero flow head percentage 50 % Single pump zero flow head percentage 50 % Pump minimum on/off time 60 sec Lag pump turn on speed (switching speed) 60 Hz Pump1/Pump2/Pump3/Pump4 min speed 20 Hz Pump1/Pump2/Pump3/Pump4 max speed 60 Hz 30

35 Settings that ARE NOT reset Instructions: This table should be updated when new values are set and approved. Keep the Installed value in the table in case need for future reference. Make sure to write down units, example, Constant Flow setpoint should be in either GPM or LPS, see units section on page 22 for available units. Setting Installed values Updated value Units Number of Pumps Switching Speed (speed of lead pump when a lag pump will turn on) System resume function Bacnet/Modbus baud rate Bacnet Instance number Bacnet/Modbus address Constant flow setpoint Constant head setpoint Proportional Pressure/Variable Flow single pump head Proportional Pressure/Variable Flow single pump flow Proportional Pressure/Variable Flow design head Proportional Pressure/Variable Flow design flow Alternation Time N/A Hz N/A N/A N/A N/A Setting the Clock To set the system clock start by pressing the Alarm and Enter buttons simultaneously for 5 seconds. The following menu will appear. Use the Up/Down buttons to scroll to SETTINGS then press the Enter button. 31

36 Use the Up/Down buttons to scroll to CLOCK SETTINGS then press the Enter button. Press the Enter button to select DATE/TIME. To change the setting: 1. Use the Up/Down buttons to scroll through the number. 2. Press the Enter button to go to the next field. 3. When done change the Update date/time? to yes and press the Enter button. Alarms/Errors There are two alarms that will require user intervention. The first is a Modbus alarm, this is usually do to a break in the Modbus connection. The second is a no flow condition from a pump that is running. For the Modbus alarm do a quick check of connectivity between the control and the Pump. If a quick fix can be made and the system is functional restore connectivity, the alarm will reset when connectivity is reestablished and the system will continue to function as normal. If not then follow the following steps, these steps are required for the no flow alarm: 1. Bring the pump offline (see page 5). 2. Change the number of pumps (see page 21). 32

37 3. Fix the problem. 4. Bring the pump back online. 5. Change the number of pumps. The system will then function as normal. If there are any difficulties call Taco Comfort Solutions Technical Services. Run Control The user is able to control if the system is running or not by the state of a relay between Pins ID1 and GND on J8 and the state of the system resume function. If the Relay is closed the Unit will function in whatever mode the user select. As soon as this relay is opened the system will go offline shutting down all the pumps. The state of the control when the relay is closed again depends the selection of the system resume menu selection. Startup/Installation Instructions and Checklist Instructions to start up a new system. If the system is already running and flow cannot be interrupted call Taco Comfort Solutions technical services for instructions. 1. With the power off to the controller unplug the Modbus connection to the VFD s 2. Power up the controller 3. Set Address VFD s (1-4), make sure they match in the control. There can t be a duplicate, this will cause errors. 4. Set/Check the Flow/Pressure setting(s) for desired Curve. 5. Set Alternation Time. 6. Turn off power to the control then plug in the Modbus connection to the VFD s. 7. Repower the control, the control should discover all the drives connected. 8. When the initialization is complete set the number of pumps. * 9. After the number of pumps is set start the control by selecting the function to run. 33

38 10. When the system is up and running normally fill out the installed values in the table on pages 32. * The number of pumps should be set to the number of pumps that can be running at any one time. For example, if there are 3 pumps but only 2 should be running at any one time, the third is alternated in, then set the number of pumps to 2. 34

39 35

40 36

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC.

INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL STATION CONTROLLER SC1000 MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road, Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Revision Date: 9-11-08 Applications: Simplex,

More information

PROGRAMMING MANUAL IM262R00. AQUAVAR Intelligent Pump Controller START-UP GENIE PROGRAMMING MANUAL

PROGRAMMING MANUAL IM262R00. AQUAVAR Intelligent Pump Controller START-UP GENIE PROGRAMMING MANUAL PROGRAMMING MANUAL IM262R00 AQUAVAR Intelligent Pump Controller START-UP GENIE PROGRAMMING MANUAL TABLE OF CONTENTS Introduction 3 Chapter 1: Motor 4 Chapter 2: Application 5 2.1. Single Pump 5 2.2. Constant

More information

Operating Instructions Extended Cascade Controller MCO 101

Operating Instructions Extended Cascade Controller MCO 101 Operating Instructions Extended Cascade Controller MCO 101 VLT AQUA Drive FC 200 Extended Cascade Controller Option Contents Contents 1. Safety and precautions 3 Safety Instructions 3 Avoid unintended

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website:

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. (407) Phone: Website: SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision: 12 Revision Date: 8-27-14

More information

Safety Instructions 1-1 Avoid unintended Start General Description 2-2

Safety Instructions 1-1 Avoid unintended Start General Description 2-2 Contents Contents 1 Safety and precautions 1-1 Safety Instructions 1-1 Avoid unintended Start. 1-1 2 Introduction 2-1 General Description 2-2 3 Supported Configuration 3-1 Introduction 3-1 Fixed-speed

More information

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

SC2000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703 SC2000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Operating Program Revision: 10 Revision Date: 1-9-12 STATION

More information

Taco System Logic (TSL)

Taco System Logic (TSL) Taco System Logic (TSL) 302-370 Installation, Operation, and Maintenance Manual SUPERSEDES: June 27, 2014 EFFECTIVE: December 21, 2015 Table of Contents 1 ELECTRICAL CONNECTIONS................. 2 1.1

More information

PC-3000x PC-3000xC PUMP CONTROLLER. User Manual 844-4PRIMEX ( ) WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER

PC-3000x PC-3000xC PUMP CONTROLLER. User Manual 844-4PRIMEX ( )   WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER PC-3000x PC-3000xC PUMP CONTROLLER User Manual WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER 844-4PRIMEX (477-4639) WWW.PRIMEXCONTROLS.COM PRIMEX TABLE OF CONTENTS Warnings... 1 Introduction and Specifications...

More information

Installation & Operation Guide

Installation & Operation Guide Installation & Operation Guide (Shown with optional Override Board Cover) KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller 902-019-04B 1 Introduction This section provides a brief

More information

Neon pr. ph/ ORP measurement. Applications. Description

Neon pr. ph/ ORP measurement. Applications. Description Easy handling by graphical menue Fitting for your application by modular setup Simple firmware update and configuration using SD-card Applications Process Water Drinking Water / Beverages Waste Water Treatment

More information

SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703

SC1000 MOTOR PROTECTION ELECTRONICS, INC. INSTRUCTION MANUAL. Phone: (407) Fax: (407) Vulcan Road Apopka, Florida 32703 SC1000 INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: (407) 299-3825 Fax: (407) 294-9435 Operating Program Revision: 8 Revision Date: 5-16-11 STATION

More information

MicroTrans EQ Signal Processor. Operation & Maintenance Manual

MicroTrans EQ Signal Processor. Operation & Maintenance Manual MicroTrans EQ Signal Processor Operation & Maintenance Manual Engineered for accuracy, applicability, durability and simplicity in HVAC air systems and industrial process control loops TABLE OF CONTENTS

More information

Millennium Simplicity Elite Parameter Points and Quirks

Millennium Simplicity Elite Parameter Points and Quirks Millennium Simplicity Elite Parameter Points and Quirks How to access, view and change parameter settings Program Button Test Reset UP Alarms Change Data Address Down 1. Push the Program button once. The

More information

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882

1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 1/32-DIN TEMPERATURE CONTROLLER INSTALLATION, WIRING AND OPERATION MANUAL FORM 3882 This manual is intended for use in support of installation, commissioning and configuration of the 1/32-DIN Temperature

More information

Operator s Manual. Morbark Integrated Control System Woodhog Series Model 2600

Operator s Manual. Morbark Integrated Control System Woodhog Series Model 2600 Operator s Manual Morbark Integrated Control System Woodhog Series Model 2600 Contents Introduction 4 Parts Identification 6 Display Module Display Pages 9 Main Page 11 Engine Information Page 12 Hydraulic

More information

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions

GRUNDFOS INSTRUCTIONS. Control MPC. Installation and operating instructions GRUNDFOS INSTRUCTIONS Control MPC Installation and operating instructions English (GB) English (GB) Installation and operating instructions Original installation and operating instructions CONTENTS Page

More information

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02

pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual ASPX Digital Scroll, Air Packaged Chiller For Version MCDSV_A02 pco 3 Controller User Manual Introduction The Airstack Chiller is a modular air-cooled chiller composed of

More information

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL

700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL 1 700 SERIES DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM 700 DPC MANUAL 072114 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features WIRING

More information

AUTOMATION. Operator s Manual PG-7. Full Access. Doc Part Rev B, 07/18. Automation Products Group, Inc.

AUTOMATION. Operator s Manual PG-7. Full Access. Doc Part Rev B, 07/18. Automation Products Group, Inc. AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual PG-7 Full Access Doc. 9003312 Part 200180 Rev B, 07/18 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com PG7

More information

QUICK START. Installation & Programming Guide

QUICK START. Installation & Programming Guide QUICK START Installation & Programming Guide PRECAUTIONS READ AND FOLLOW ALL SAFETY INSTRUCTIONS. CAUTION - RISK OF ELECTRICAL SHOCK. To prevent electrical shock, turn off power at the circuit breaker

More information

Operator Interface Terminal Manual Standard Two or Three Pump VFD Booster

Operator Interface Terminal Manual Standard Two or Three Pump VFD Booster DOCUMENT: ECOIT2-1 EFFECTIVE: 02/14/07 SUPERSEDES: 02/26/03 Operator Interface Terminal Manual Standard Two or Three Pump VFD Booster The Operator Interface Terminal (OIT) allows the operator to monitor

More information

Trident and Trident X2 Digital Process and Temperature Panel Meter

Trident and Trident X2 Digital Process and Temperature Panel Meter Sign In New User ISO 9001:2008 Certified Quality System Home Products Online Tools Videos Downloads About Us Store Contact Policies Trident and Trident X2 Digital Process and Temperature Panel Meter Products

More information

User s Guide TG Series C. Senva Sensors 9290 SW Nimbus Ave Beaverton, OR 97008

User s Guide TG Series C. Senva Sensors 9290 SW Nimbus Ave Beaverton, OR 97008 User s Guide TG Series Senva Sensors 9290 SW Nimbus Ave Beaverton, OR 97008 154-0031-0C Rev. Release Date By Description of Change ECR 0A 4/14/2016 CKB Initial Release --- 0B 3/7/2017 CKB Updated for RS485

More information

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016 Interface Definition RISH EM 2340/1320/30/40 1 2-60-006-00-00494_Rev. D - 8/2016 2 Section DIGITAL MULTIFUNCTION INSTRUMENT Contents 1. Introduction Programmable Multi-function Energy Meter Installation

More information

Optidrive Applications Support Library

Optidrive Applications Support Library Optidrive Applications Support Library Application Note Title AN-ODV-3-038 Related Products Optidrive Eco Overview Level 3 Modbus RTU Control and Register Mapping 1 Fundamental - No previous experience

More information

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS UDC 1000 and UDC 1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS EN0I-6041 12/99 PRODUCT SPECIFICATION SHEET OVERVIEW The UDC 1000 and UDC 1500 are microprocessor-based 1/16 DIN and 1/8 DIN controllers

More information

Vacon HVAC100 Commissioning Guide

Vacon HVAC100 Commissioning Guide Vacon HVAC100 Commissioning Guide INDEX 1. Glossary of terms 2. Wiring diagrams 3. Set up procedures a. Motor settings input b. Low level start, analogue input speed reference in AUTO position. Low level

More information

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions

User Guide. For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units. CNT-SVU005C-GB Original instructions User Guide For controller on CXAO / RTXB heat pumps CGCM / CXCM 2 circuit units CNT-SVU005C-GB Original instructions Table of contents Advanced electronics... 3 Technical Specifications... 4 Display description...

More information

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA UM Channel Monitor.

5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL Fruitland Ave Los Angeles, CA UM Channel Monitor. 5450 NW 33rd Ave, Suite 104 Fort Lauderdale, FL 33309 3211 Fruitland Ave Los Angeles, CA 90058 UM-600 6-Channel Monitor Version 2 Installation and Operation Manual Rev. G P/N145F-12990 PCO 00007462 (c)

More information

FREQUENCY CONVERTER FC102 (QUICK GUIDE)

FREQUENCY CONVERTER FC102 (QUICK GUIDE) FREQUENCY CONVERTER FC102 (QUICK GUIDE) INSTALLATION AND MAINTENANCE Content Page Safety instructions 2 IT system 3x230VAC 2 Connections 3 Control unit (LCP) 4 Manual operation 4 Reverse the direction

More information

Sidewinder Pumps Inc. AC Timer/Controller

Sidewinder Pumps Inc. AC Timer/Controller Sidewinder Pumps Inc. AC Timer/Controller Page 1 of 12 Rev 032417 Table of Contents 1. Warnings-------------------------------------------------------------------------------------------------- 3 1.1.

More information

GPD 506/P5 Apogee - FLN Technical Manual

GPD 506/P5 Apogee - FLN Technical Manual GPD 506/P5 Apogee - FLN Technical Manual Table of Contents 1. INTRODUCTION... 2 2. HARDWARE INSTALLATION... 3 2.1 OPTION CARD MOUNTING... 3 2.2 DRIVE SET-UP... 5 2.3 NETWORK CONNECTION... 5 2.3.1 Bus Terminating

More information

VLT 2800 DRIVE SPECIFICATIONS

VLT 2800 DRIVE SPECIFICATIONS VLT 2800 DRIVE SPECIFICATIONS Drive Input Power Input voltage 3 phase... 200 through 240, or 380 through 460; 3-phase all ratings 200 through 240, 1-phase through 2 HP Input voltage range for full output...

More information

PowerFlex 400 AC Drive Guide Specification

PowerFlex 400 AC Drive Guide Specification PowerFlex 400 AC Drive Guide Specification Adjustable Frequency Drives with Bypass 3.0 50HP @ 208V AC 3.0 350HP @ 480V AC PART 1 GENERAL 1.01 Quality Assurance A. The manufacturer shall have minimum 5

More information

System-10 BTU Meter BACnet Network Interface Installation Guide

System-10 BTU Meter BACnet Network Interface Installation Guide BACnet ONICON Flow and Energy Measurement System-10 BTU Meter BACnet Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 0652-12

More information

AND OPTIONAL ACCESSORIES

AND OPTIONAL ACCESSORIES USER S GUIDE Revision A Rapid City, SD, USA, 11/2010 MODEL 777-KW/HP-P2-DEMO AND OPTIONAL ACCESSORIES POWER MONITOR II_KW/HP-P2-DEMO_A 2880 North Plaza Drive, Rapid City, South Dakota 57702 8242 Loop Rd.

More information

700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL 1 700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM 700 SERIES FLOAT OPERATED DUPLEX/TRIPLEX PUMP MANUAL 042814 TABLE OF CONTENTS 2 INTRODUCTION

More information

SRO100 Programmable Digital Indicator And Frequency Counter

SRO100 Programmable Digital Indicator And Frequency Counter USERS MANUAL SRO100 Programmable Digital Indicator And Frequency Counter Introduction The SRO100 Programmable Digital Indicator/ Frequency Counter may be used in any application requiring a programmable

More information

EMCP 4.4 Simulator Manual. Author: Lucas Tolbert CIC Engineering 345 Center Street East Peoria, IL

EMCP 4.4 Simulator Manual. Author: Lucas Tolbert CIC Engineering 345 Center Street East Peoria, IL EMCP 4.4 Simulator Manual Author: Lucas Tolbert CIC Engineering 345 Center Street East Peoria, IL Date of Origin: 11/23/2010 Overview This document will detail the features and operation of the EMCP 4.4

More information

GFC111-MB. Flow Computer With RS485 MODBUS FEATURES 1. DESCRIPTION APPLICATIONS

GFC111-MB. Flow Computer With RS485 MODBUS FEATURES 1. DESCRIPTION APPLICATIONS Flow Computer With RS485 MODBUS FEATURES l RS485 MODBUS RTU, 1/8 LOAD l PROGRAMMABLE ADDRESS, BAUD RATE, PARITY AND STOP BITS l UNIVERSAL INPUT, 5 khz, CAN POWER THE SENSOR l NO NEED OF AMPLIFIERS OR LINEARIZERS

More information

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat Features Modern Appearance Stylish rotary dial and buttons Large LCD with backlight Support Modbus RTU protocol Support standalone operation

More information

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications Real Time Clock with Temperature Sensor and RS485/Modbus Comunications April 29, 2014 Power 8 20 VDC @ less than 100 MA. Battery connect jumper RS485 Bus Load Jumpers Model: RTC-TI2C Page 1 of 6 Features:

More information

ADVANCED OPERATOR PANEL (AOP)

ADVANCED OPERATOR PANEL (AOP) ADVANCED OPERATOR PANEL (AOP) Operating Instructions Issue 04/02 English Contents 1 Warnings and Notes 3 1.1 Special Key Functions 4 2 Applications Examples 4 2.1 Single drive control using the AOP 4 2.2

More information

AUTOMATION. Operator s Manual PG10. Full Access. Automation Products Group, Inc. APG...Providing tailored solutions for measurement applications

AUTOMATION. Operator s Manual PG10. Full Access. Automation Products Group, Inc. APG...Providing tailored solutions for measurement applications AUTOMATION P R O D U C T S GROUP, INC. Operator s Manual PG10 Full Access DOC. 9003470 Rev B 6/11 Tel: 1/888/525-7300 Fax: 1/435/753-7490 www.apgsensors.com E-mail: sales@apgsensors.com PG10 Rev. B, 6/11

More information

Multi-Point Gas Detection and Control System

Multi-Point Gas Detection and Control System Multi-Point Gas Detection and Control System Specifications subject to change without notice. USA 40804 Page of 7 DESCRIPTION Wall mounted, microprocessor-based, multi-point, analog electronic control

More information

Multi-Point Digital Gas Detection and Control System

Multi-Point Digital Gas Detection and Control System Multi-Point Digital Gas Detection and Control System Specifications subject to change without notice. USA 80308 Page of 0 DESCRIPTION Wall mounted, microprocessor-based, multi-point, RS-85 digital communicating

More information

PFC-10 Power Factor Controller

PFC-10 Power Factor Controller PFC-10 Power Factor Controller Instruction Manual Ver. 6.0 / 2002 (2-2005 update) Table of Contents Page Subject 3 Starter ion 4-5 Installation Notes 6-7 Terminals Review & Control Wiring 8 Front-panel

More information

The new generation of dedicated HVAC drives

The new generation of dedicated HVAC drives The new generation of dedicated HVAC drives Contents Selection guides p. 8 Presentation p. 14 References p. 18 Bus and communication networks p. 26 Motor starters p. 28 Altivar 212 Orientated towards performance,

More information

Multi-Point Gas Detection and Control System

Multi-Point Gas Detection and Control System Multi-Point Gas Detection and Control System Specifications subject to change without notice. USA 50729 Page of 9 DESCRIPTION Wall mounted, microprocessor-based, multi-point, analog electronic control

More information

Optidrive Applications Support Library

Optidrive Applications Support Library Optidrive Applications Support Library Application Note Title AN-ODE-3-038 Related Products Optidrive E3 Overview Level 3 Modbus RTU Control and Register Mapping 1 Fundamental - No previous experience

More information

Heatronic Introduction. BAS Integration Manual. Table of Contents

Heatronic Introduction. BAS Integration Manual. Table of Contents Heatronic 4000 BAS Integration Manual Introduction The Heatronic 4000 can communicate with a Building Automation System (BAS) using either BACnet IP or Modbus. This manual provides information about boiler

More information

700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL 1 700 SERIES TPC TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL VISIT OUR WEBSITE SIGMACONTROLS.COM 700SERIESTPCMANUAL071414 2 TABLE OF CONTENTS INTRODUCTION 3 Ordering Information Specifications Features

More information

Time Mark Corporation Model 42A Pump Controller User s Guide

Time Mark Corporation Model 42A Pump Controller User s Guide Time Mark Corporation Model 42A Pump Controller User s Guide Graphic display User friendly Expandable Communications capable 2009 Time Mark Corporation. All rights reserved. Made in the U.S.A. Time Mark

More information

Graphical User Interface V1.0.3

Graphical User Interface V1.0.3 Graphical User Interface V1.0.3 Application User Guide 2015 MCI Solutions. All rights reserved. 240815-01 www.mcisolutions.ca Page ii Getting Started Table Of Contents Introduction.................................................

More information

Mercury 11-10PV Pack / Condenser Controller Installation & User Guide V6 or Higher

Mercury 11-10PV Pack / Condenser Controller Installation & User Guide V6 or Higher PR0334 PR0335 PR0332 PR0333 Mercury 11-10PV Pack / Condenser Controller Installation & User Guide V6 or Higher For Products: - PR0710, PR0711, PR0720, PR0721 Resource Data Management Ltd 80 Johnstone Avenue,

More information

Voltsys Inverter Control Unit

Voltsys Inverter Control Unit Voltsys Inverter Control Unit Coomanore North, Bantry, info@voltsys.com Co. Cork. Republic of Ireland tel. +353 (0) 27 52773 Contents Important Safety Instructions... 3 Controller Layout & Wiring... 4

More information

Carbon Monoxide Sensor - ModBus

Carbon Monoxide Sensor - ModBus Introduction The CO Sensor uses an electrochemical sensor to monitor CO level in a range of 0 to 500 ppm and communicates via an RS-485 network configured for ModBus protocol. Before Installation Read

More information

Vorne Industries. 2000S Series Serial Input Alphanumeric Display User's Manual

Vorne Industries. 2000S Series Serial Input Alphanumeric Display User's Manual Vorne Industries 2000S Series Serial Input Alphanumeric Display User's Manual 1445 Industrial Drive Itasca, IL 60143-1849 Telephone (630) 875-3600 Telefax (630) 875-3609 2000S Series Serial Input Alphanumeric

More information

CURRENT PROTECTION RELAY SMPR-1

CURRENT PROTECTION RELAY SMPR-1 CURRENT PROTECTION RELAY SMPR-1 1.- ORION ITALIA SERIES MODBUS PROTOCOL. The ORION ITALIA SERIES implement a subset of the AEG Modicon Modbus serial communication standard. Many devices support this protocol

More information

OVEN INDUSTRIES, INC.

OVEN INDUSTRIES, INC. OVEN INDUSTRIES, INC. OPERATING MANUAL MODEL 5C7-195 THERMOELECTRIC MODULE TEMPERATURE CONTROLLER TABLE OF CONTENTS Page Features...1 Description...2 Block Diagram...2 Mechanical Package Drawing...3 RS232

More information

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B Metasys N2 Instruction Manual VLT 6000 Adjustable Frequency Drive 12/99-6110-00 Revision B 2 Table of Contents Overview Page Introduction... 5 About this Manual... 5 References... 5 Instructions Abbreviations

More information

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D

PART 1: GENERAL PART 2: PRODUCT. Effective: 12/29/10 Page 1 of 6 FECA-TE-104D Specification Number: 23 09 33 Product Name: FRENIC-Eco AC Drives for Variable Torque Fan & Pump Applications (1-125Hp at 208/230V and 1-900Hp at 460V) PART 1: GENERAL 1.01 SUMMARY A. This specification

More information

Products no longer available

Products no longer available Technical data sheet BKS24-.. MONICO-Controller BKS24-.. Forms an efficient fire protection system together with the motorisation sets BF(G)24MP Controller with application software for control and monitoring

More information

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module

MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module Installation and Maintenance Manual IM 928-2 Group: Controls Part Number: 669207702 Date: March 2011 Supersedes: IM 928-1 MicroTech III Applied Terminal Systems BACnet MS/TP Communication Module NOTICE

More information

User Manual SolarTracker

User Manual SolarTracker User Manual SolarTracker Management Software for Inverter Table of Contents 1. SolarTracker Overview... 1 1.1. Introduction... 1 1.2. Features... 1 2. SolarTracker Install and Uninstall... 1 2.1. System

More information

System-10 BTU Meter BACnet Network Interface Installation Guide

System-10 BTU Meter BACnet Network Interface Installation Guide BACnet System-10 BTU Meter BACnet Network Interface Installation Guide 0652-3 1500 North Belcher Road, Clearwater, FL 33765 Tel (727) 447-6140 Fax (727) 442-5699 www.onicon.com sales@onicon.com 04-12 System-10-BAC

More information

32MP Gateway. Overview and Configuration Manual

32MP Gateway. Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual 32MP Gateway Overview and Configuration Manual This document is the property of Carrier Corporation and is delivered on the express condition that it is not

More information

AF-600 FP AC Drive AC Adjustable Frequency Drive Guide-Form Specification

AF-600 FP AC Drive AC Adjustable Frequency Drive Guide-Form Specification AF-600 FP AC Drive AC Adjustable Frequency Drive Guide-Form Specification Contents 1.0 General Information 2.0 Operating Conditions 3.0 Standards 4.0 Input Power Section 5.0 Output Power Section 6.0 Drive

More information

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION

MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS PLUS TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 3 May 2010 David Walker Initial release.

More information

RTD-W Installation Instructions

RTD-W Installation Instructions RTD-W Installation Instructions 0V +V POWER 15-24VDC 0V S1 S2 S3 0V S4 S5 S6 English RTD-W Installation Instructions 100.00 RTD-W Control Interface realtime Control Systems 24VAC/30VDC, 1A REMC P1 P2 RS485

More information

Analog Input and Output Options for Syringe Pumps

Analog Input and Output Options for Syringe Pumps Analog Input and Output Options for Syringe Pumps Installation and Operation Instructions Syringe Pumps Technical Bulletin TB03 Overview Teledyne Isco offers several options for external analog control

More information

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner

PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION. v1.0 DRAFT Revised Dec 4, 2014 Last Revised by Alex Messner PF2100 MODBUS LOGGER CARD SYSTEM SPECIFICATION Revised Last Revised by Alex Messner This page was intentionally left blank. Table of Contents 1 Overview... 2 2 User Interface... 3 2.1 LEDs... 3 2.2 Buttons...

More information

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm)

12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 4-20 ma & Relay Output Features 4-20 ma, ± 10 V, TC & RTD Inputs 12-36 VDC/12-24 VAC Power Option 4-Digit Display, 0.56 (14.2 mm) or 1.20 (30.5 mm) 24 VDC @ 200 ma Transmitter Power Supply Options Type

More information

ADDJOG User Guide 7/30/10. Overview

ADDJOG User Guide 7/30/10. Overview ADDJOG User Guide 7/30/10 Overview The ADDJOG is a PLC expansion board used to add digital inputs and outputs to a compatible host PLC. The ADDJOG has 64 open collector outputs and 64 non-isolated inputs.

More information

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB

User Guide. Multipipe Units CMAA / RTMA CNT-SVU004B-GB User Guide Multipipe Units CMAA / RTMA CNT-SVU004B-GB USER GUIDE WARNING Supply the unit at least 24 hours before the initial startup to heat the compressor oil. In conditions of low water temperature,

More information

NF760 Batch Controller

NF760 Batch Controller NF760 Batch Controller Overview The NF760 Batch Controller is suited to flow applications where precise measurement and control of batch quantities is required. Batch total, flow rate, accumulated total

More information

Pump Station Controller. Quick Start

Pump Station Controller. Quick Start Pump Station Controller Quick Start Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application,

More information

FCU-4 FAN COIL CONTROLLER

FCU-4 FAN COIL CONTROLLER FCU-4 FAN COIL CONTROLLER BACnet Enabled Description The FCU-4 is designed to provide complete control of fan coil units. The FCU-4 incorporates all the inputs and outputs to ensure that this advanced

More information

High Voltage DC Meter

High Voltage DC Meter High Voltage DC Meter Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications

LAUREL. Laureate RTD Temperature Panel Meter / Controller ELECTRONICS, INC. Features. Description. Specifications LAUREL ELECTRONICS, INC. Laureate RTD Temperature Panel Meter / Controller Features Factory calibrated for 100Ω platinum, 10Ω copper & 120Ω nickel RTDs 2, 3 or 4-wire connection with lead resistance compensation

More information

Status line The top line of the LCD display shows the basic status information of the drive.

Status line The top line of the LCD display shows the basic status information of the drive. Control panels 91 Status line The top line of the LCD display shows the basic status information of the drive. LOC 49.1Hz LOC MAIN MENU 1 No. Field Alternatives Significance 1 Control location LOC Drive

More information

LAUREL. Laureate Pulse or Analog Input Batch Controller Automatic batch control for repetitive liquid fill operations ELECTRONICS, INC.

LAUREL. Laureate Pulse or Analog Input Batch Controller Automatic batch control for repetitive liquid fill operations ELECTRONICS, INC. Description LAUREL ELECTRONICS, INC. Laureate Pulse or Analog Input Batch Controller Automatic batch control for repetitive liquid fill operations Features Available for turbine flow meter pulse signals

More information

Metasys Integrator Caterpillar Application

Metasys Integrator Caterpillar Application Application Note Issue Date May, 00 APPLICATION NOTE Metasys Integrator Caterpillar Application Introduction Application Details Component Requirements Vendor Contact Information Design Considerations

More information

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION

MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION ICP PANEL-TEC MICROBRIDGE INSTALLATION AND OPERATION GUIDE MODBUS/TCP TO SIEMENS G110/G120/MM440 APPLICATION Revision History Revision Date Author Comments 000 02 June 2009 David Walker Initial release.

More information

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL

INTRINSICALLY SAFE DUPLEXER PROTECTION. ELECTRONICS, INC Vulcan Road Apopka, Florida MOTOR INSTRUCTION MANUAL INTRINSICALLY SAFE DUPLEXER INSTRUCTION MANUAL MOTOR PROTECTION ELECTRONICS, INC. 2464 Vulcan Road Apopka, Florida 32703 Phone: Website: (407) 299-3825 www.mpelectronics.com Operating Program Revision:

More information

PDS100 Programmable Dispensing System SAFETY INSTRUCTIONS

PDS100 Programmable Dispensing System SAFETY INSTRUCTIONS PDS100 Programmable Dispensing System INSTRUCTION MANUAL SAFETY INSTRUCTIONS Before using any Fluid Metering, Inc. product read the following safety instructions as well as specific product specifications

More information

180 Series Keypad. Handbook. Revision 2.1

180 Series Keypad. Handbook. Revision 2.1 180 Series Keypad Handbook Revision 2.1 Revision History Revision 1.0 Initial release Revision 2.0 Major update with addition of 180-40 Added 180-40 to document and various headings Note regarding unique

More information

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09 Application Note Title AN-ODE-01 E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/08 1.03 Revised to new format PAE 09/03/09 General This document

More information

PumpDrive DPM. Installation and Operating Instructions Dual Pump Module (DPM) /4--10

PumpDrive DPM. Installation and Operating Instructions Dual Pump Module (DPM) /4--10 4070.83/4--10 PumpDrive DPM Installation and Operating Instructions Dual Pump Module (DPM) These installation and operating instructions are not valid on their own. They must always be applied in conjunction

More information

BACnet Flow Controller for Fan Filter Units

BACnet Flow Controller for Fan Filter Units MANUAL SERVICE + INSTALLATION BACnet Flow Controller for Fan Filter Units BFC Series v300 Issue Date: 08/23/17 2017 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview General

More information

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide MODBUS D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide 11451 Belcher Road South, Largo, FL 33773 USA Tel +1 (727) 447-6140 Fax +1 (727) 442-5699 www.onicon.com sales@onicon.com 03-18 0657-9

More information

M2500 Engine Controller Configuration Manual

M2500 Engine Controller Configuration Manual M2500 Engine Controller Configuration Manual Revision: 08-04-2011 Page 1 Contents 1 Preface... 4 2 Configuration from front panel... 5 2.1 Engine Controller Configuration... 6 2.1.1 RPM settings... 6 2.1.2

More information

Getting Started Manual Rev. 2.3 DB-MAGNUM HARDWARE VERSION 8.1+

Getting Started Manual Rev. 2.3 DB-MAGNUM HARDWARE VERSION 8.1+ Getting Started Manual Rev. 2.3 DB-MAGNUM HARDWARE VERSION 8.1+ The MCS Commitment: Our commitment is to provide practical solutions for the industry s needs and to be both a leader and partner in the

More information

Power Monitor Sensor User Manual

Power Monitor Sensor User Manual Power Monitor Sensor User Manual Help Version updated till firmware 404p Copyright 2012, AKCess Pro Co., Ltd.. PMS User Manual - 2 What is the Power Monitoring Sensor? The Power Monitoring Sensor or PMS

More information

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions

MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Specialists in Liquid Level Indication MTII4200 Level Transmitter Installation, Operation & Maintenance Instructions Section: M500 Bulletin: M500.31 Date: 05-17-16 Supersedes: 09-30-11 1. INTRODUCTION

More information

CENTAC Communicating with the Centac Control Systems

CENTAC Communicating with the Centac Control Systems CENTAC Communicating with the Centac Control Systems INGERSOLL-RAND AIR COMPRESSORS COMMUNICATING WITH THE CENTAC CONTROL SYSTEMS Copyright Notice Copyright 1992 Ingersoll-Rand Company THE CONTENTS OF

More information

HIGH-VOLTAGE DC METER

HIGH-VOLTAGE DC METER HIGH-VOLTAGE DC METER Javelin D PD644 0-300 VDC input NEMA 4X, IP65 front Scale in engineering units Sunlight readable LED display 4-20 ma analog output Two form C 3 A relays option RS-485 serial communications

More information

EzView User Manual RevD June 2016 (V2.6.3) Supersedes: RevC (March 2014) EZ-View User Manual

EzView User Manual RevD June 2016 (V2.6.3) Supersedes: RevC (March 2014) EZ-View User Manual EzView User Manual RevD June 2016 (V2.6.3) Supersedes: RevC (March 2014) EZ-View User Manual 1 Getting Started... 1.1 1.1 Hardware Requirements... 1.1 1.2 Connecting Controllers to EZ-View... 1.2 1.2.1

More information

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50

MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287. Installation and Operations Manual Section 50 MODBUS RTU I/O Expansion Modules - Models C267, C277, and C287 Installation and Operations Manual 00-02-0651 09-01-09 Section 50 In order to consistently bring you the highest quality, full featured products,

More information

AUTOMOTIVE CONTROLLER

AUTOMOTIVE CONTROLLER SA-2793 USER GUIDE BR LEE 8515/8816 PAVER AUTOMOTIVE CONTROLLER Table of Contents I. Revisions.2 II. Software Specification.......2 III. Description of Operation...3 IV. Fault Codes for Status LED..8 V.

More information