9910-UPS Rack Chart Updated Oct 05
|
|
- Ira Watts
- 5 years ago
- Views:
Transcription
1 All devices and UPS in One rack? es One to Two* or Two or Four** PDUs? es es If LPAR s or Web/SNMP connectivity (interface) required, select FC 934 If no LPAR s ensure p5 has #573 for serial communications P30 (No PDU) Fig 6,100W U IEC kit (IEC309) or, xx country P30 Options: U Battery module P33 (One* Fig 3 or two** Fig 5 9/7188 PDUs),700W U (if S11 or S5 rack) IEC kit PDU to UPS (IEC309) or, xx country P33 Options: U Battery module wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page 1 of 10 October, 005 No Calculate power draw, select UPS with watt rating higher than power draw P33 (No PDU) Fig 6,700W U IEC kit (IEC309) or: xx country P33 Options: U Battery module Figures on Following Pages No One 9177 PDU? (Figure x) Select from P30, P33, P64 or UPS The following texts describes various UPSs and the configuration (eg No PDU ) and features necessary for a proper configuration *Non-redundant ** Dual-Redundant P30 (One* Fig 3 or two** Fig 5 9/7188 PDUs),100W U IEC kit (IEC309) or, xx country PDU to UPS P30 Options: U Battery module 9910-UPS Chart Updated Oct 05 No 9188 & 7188 PDU NOTES: P30 & P33 ou will not use the 9/7188 PDU #66xx, store for future use Go to Tower UPS Charts or Contact Eaton (Powerware) Model Watts Qty , way Base CEC way nd CEC way 3rd CEC way 4th CEC A A /595 Base 0, , U U , EX B H DS L L3, 3581-F L All D , CR D11, D TF3 0 Other TOTAL: P64 (One* Fig 8 or two** Fig 9 9/7188 PDUs) 4,00W 5U rail kit (IEC309) or 973 PDU to UPS P64 Options: U Battery module rail kit p5 Table 1 TTL Watts (One* Fig 8, two* Fig 9 or 10 or four** Fig 11 or 1 9/7188 PDUs) 4,500W 3U rail kit (IEC309) or 973 PDU to UPS NOTE: The can support one (1) additional PDU Select one PDU to UPS for second PDU Options: U Battery module rail kit
2 Table Attribute P30 P33 P64 Level of protection (Type/Series) 9 = Double conversion, 5 = Line interactive Hot Swap Batteries Hot Swap Electronics - - Load Segments - No PDU supported, non-redundant No PDU supported, dual-redundant 4 Height U 5 3 Output Watts,100,700 4,00 4,500 Watts per U 1,050 1, ,500 Optional Extended Battery Modules (EBM) (#6640) Max: 4 (#6607) Max: 4 (#6641) Max: 4 (#6641) Max: 4 Optional Relay-Serial Card (dual AS/400 & serial communications) (939) Optional 10V Convenience PDU (916) (1) (1) Requires 9188, 7188 or 9177 to power 10V Convenience PDU wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page of 10 October, 005
3 Step 1: Determine your rack model: 7014-T4 = 4U 7014-S5 = 5U 7014-S11 = 11U PDUs can be installed in side pockets (4U only) or EIA space (all) The 5U and 11U racks support 9910-P33 UPS A minimum of one PDU will be included with each rack Choose the figure closest to your application PDU (side pocket) 4U (T4) PDU (side pocket) Model UPS Support by racks: T4 supports P30, P33, P64 and (Figure 1A) S5 supports P33 (Figure 1B) S11 supports P33 (Figure 1C) 5U (S5) PDU (side pocket) Device PDU (side pocket) 11U (S11) Device Device PDU (EIA space) PDU (EIA space) PDU (EIA space) UPS (varies) UPS (P33) UPS (P33) Figure 1A Figure 1B Figure 1C wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page 3 of 10 October, 005
4 Battery (autonomy) runtimes Table 3 Battery (Autonomy) Watt load (power draw level) Std Internal Batts +1 EBM + EBMs +3 EBMs +4 EBMs (Max) P30 (EBM #6640) 875 Watts 16 min W W W P33 (EBM #6607) 1350 W W P64 (EBM #6641) 1400 W W W W W (EBM #6641) 900 W W W W W W Table 4 Mains (input) Power Cord Plug & Receptacle Descriptions Type 18 FC 9866 CEE 7VII Type FC 9867 SABS 164 Type 5 FC 9868 CEI 3-16 Type 3 FC 987 SII Type 46 (16A) FC 9871 IEC309 P+N+G Type 46 (3A) FC 144, 976 IEC309 P+N+G Type 54 FC 9874 SAA-AS 311 Type 64 FC 9875 inmetro Type KP FC 145 KP 30A Type PDL FC 146, 147 PDL, PDL-NZ wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page 4 of 10 October, 005
5 Each Figure shows a rack with a different quantity of PDUs (zero to four) and with various input power for the P30 & P33 The Figures showing two PDUs are show in *Non- & **Dual-Redundant (two separate power sources) configurations The figures showing four PDUs are shown in Dual-Redundant configurations only Choose the figure closest to your application LEGEND for Understanding Figures Description of rack configuration Rear view of rack showing device(s) PDU(s) shown mounted in side pocket Input power cord plug mates to mains receptacle Mains (wall) receptacle is supplied by end user EXAMPLE Figure (not to scale) UPS Device to PDU Device with one power supply (if dual redundant, will have two power supplies) PDU to UPS UPS (Model) at bottom of rack Figure 3 : 976 IEC309 P+N+G 3A #9866 CEE7 VII #9867 SABS 164 #9868 CEI 3-16 #9871 IEC309 P+N+G 16A #987 SII #9874 SAA-AS 311 #9875 inmetro (See Table 4 for graphics) One 9188 PDU: P30/P33 with one PDU *NON-REDUNDANT (not to scale) connections) to 9188 PDU 9188/ 7188 Connector Type: UTG (Burndy) C19/C0 PDU to UPS power cord 6, P30 or P33 3A UPS input 976 IEC309 3A 4m 16A UPS input #9866 IEC309 or other 98xx Or P30 or P33 wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page 5 of 10 October, 005
6 Figure 4 See Fig 3 for UPS input line One 9177 PDU: P30/P33 with 9855 with one PDU *NON-REDUNDANT (not to scale) Up to 9 Devices (power connections) to 9177 NOTE: If you want a 3A, you must delete the 98xx from the UPS configuration, then select #9855 Then you must order #144 (4m) PDU 9177 IEC309 53P1969 IEC309 #9855 consists of two parts and connects: 1) PDU to UPS (PN 53P1968) ) UPS input to PDU (PN 53P1969) C19/C0 53P1968 P30 or P33 IEC309 IEC309 P30 or P33 Figure 5 Two 9/7188 PDUs: P30/P33 Figure 6 No PDU: P30/P33 with two PDU **DUAL-REDUNDANT (not to scale) with No PDU *NON-REDUNDANT (not to scale) See Fig 3 for UPS input line connections) to each 9/7188 PDU C13 to C14 See Fig 3 for UPS input line Up to 9 Devices (power connections) to P33 Up to 4 power connections to P P30 or P33 P30 or P33 p5 Flow Chart v1ppt Page 6 of 10 October, 005
7 Figure 7 Four 9/7188 PDUs: Two P33 s Figure 8 One 9188 PDU: P64 or 974 PDU #3 to UPS cord See Fig 3 for UPS input line with four PDUs **DUAL-REDUNDANT PDUs #1 & #3 powered by UPSs PDUs # & 4 powered by utility (mains) connections) to each 9/7188 PDU #4 PDU : #144 IEC309 P+N+G 3A #145 PDL #146 KP #147 PDL NZ with one PDU *NON-REDUNDANT connections) w/ 9188 P33 97/3 cord P33 #1 P64 or 974 cord Figure 9 Two 9/7188 PDUs: P64 or Figure 10 Two 9/7188 PDUs: with two PDUs **DUAL-REDUNDANT PDU #1 powered by UPS PDU powered from utility (mains) with two PDUs *NON-REDUNDANT PDU #1 & powered by UPS See Fig 8 for connections) w/ 9/7188 PDU See Fig 8 for connections) to each 9/ PDU to UPS cord 97/3 cord 97/3 cord P64 or wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page 7 of 10 October, 005
8 Figure PDU #3 to UPS cord See Fig 8 for Four 9/7188 PDUs: with four PDUs **DUAL-REDUNDANT PDUs #1 & #3 powered by UPS PDUs # & 4 powered by utility (mains) connections) to each 9/ / 3 cord PDU #4 PDU Figure 1 Two s: (requires 1x 97 or #6654 and 1x 974) #1 with two PDUs *REDUNDANT PDU powered by UPS with two PDUs *REDUNDANT PDU #1 powered by UPS See PDU input line connections) to each 7188 See Fig 8 for connections) to each 7188 PDU 974 cord 97 or #6654 PDU to UPS cord wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page 8 of 10 October, 005
9 Figure 13 IEC309 (P+N+G) 3A, 30V used with UPS input #144 NEMA L6-30P (P+G) 30A, 30V used with PDU to UPS 973 and input power cable (15ft) and P64/ outlet IEC309 (P+N+G) 16A, 30V used with UPS input #9866 C13 connector- 10A rated (female) PDU, P30/P33/ UPS outlets Mating connector to server C14 connector- 10A rated (male) The inlet on most servers & options jumper cords C19 connector- 16A rated (female) P30/P33/ UPS outlet and UPS input (975, 976) C0 connector- 16A rated (male) BladeCenter, some i5 devices and P30/P33 inlets Figure 14 FC 97, 973 & 6654 PDU to UPS 14ft/4m, 4ft/1m (respectively) Burndy to L6-30P Figure 15 FC 975 UPS input (mains) 8ft L6-30P to IEC-30-C19 C19 Figure 16 FC 974 PDU to UPS 6ft/18m Burndy to IEC-30-C0 C0 Figure 17 FC 976 UPS input (mains) 4m IEC309 (P+N+G) 3A to IEC-30-C19 C19 wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page 9 of 10 October, 005
10 UPS Rear Panels P30 Figure 18 P33 Figure 19 P64 Figure 0 Figure 1 wwwoempowerwarecom/ibm-ups p5 Flow Chart v1ppt Page 10 of 10 October, 005
Configuration Questions:
Configuration Questions: 1 What equipment will be protected? Calculate using Table 1 What do I want the UPS to do? Shutdown server(s) interface? Provide extended battery (autonomy) runtime? 3 Where do
More informationConfiguration Questions:
Configuration Questions: 1 What equipment will be protected? Calculate using Table 1 What do I want the UPS to do? Shutdown server(s) interface? Provide extended battery (autonomy) runtime? 3 Where do
More information9910-UPS Rack Chart Updated March 08
All devices and UPS in One rack? 7188 or 5889 PDUs? Qty: Zero to Ten es es E30 (No PDU, Fig 6) 2,100W 2U 9910-0243 rack specify code 9910-9860/61 (L6-20) or: 9910-2975 (L6-30) E30 Options: 9910-6644 2U
More information9910-UPS Rack Chart (IEC309 16A) power cord
All devices and UPS in One rack? Zero to Two* or Two or Four** 7188 PDUs? Yes No No One 5161 PDU? (Figure 2) 9910-UPS Chart No Go to Tower UPS Charts or Contact Eaton (Powerware) +44 add number here i5
More informationPowerware P60/61
ware 51405 9910 P60/61 Runtime and Rack Connections P60 & P61 Runtime and Rack Connections v5.ppt Battery Runtime Matrix Battery Runtime (in minutes)* Standard (Std) Watts Internal Batteries 1 EBM 2 EBMs
More informationPowerware 5125 (9910-P33) UPS Installation Guide for IBM Applications
Powerware 5125 (9910-P33) UPS Installation Guide for IBM Applications IBM, pseries, AIX, xseries, AS/400, OS/400, and RS/6000 are registered trademarks and iseries, OpenPower, and i5/os are trademarks
More informationPowerware 5125 (9910-E33) UPS Installation Guide for IBM Applications
Powerware 5125 (9910-E33) UPS Installation Guide for IBM Applications Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF
More informationPowerware 9125 (9910-E30) UPS Installation Guide for IBM Applications
Powerware 9125 (9910-E30) UPS Installation Guide for IBM Applications Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF
More informationIBM 9910 UPSs for IBM iseries and pseries safeguard your equipment and data from power problems
Hardware Announcement April 20, 2004 IBM 9910 UPSs for IBM iseries and pseries safeguard your equipment and data from power problems Overview To meet the changing power protection needs of IBM servers,
More informationIBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems
IBM United States Announcement 108-068, dated January 29, 2008 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Key prerequisites...2 Description...2 Publications...
More informationeserver Integration
9125 - eserver TOPICS Installation Startup Optional Features Help/Resources 9125 Prep - eserver rev April 01 Page 1 Obtain a copy of Powerware 9125 9910 Installation Guide for IBM Applications and Powerware
More informationPowerware 9125 (9910-E64) UPS Installation Guide for IBM Applications
Powerware 9125 (9910-E64) UPS Installation Guide for IBM Applications Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF
More informationAxxium Pro - iseries (AS/400) Integration
Axxium Pro - iseries () TOPICS Preparation Installation Optional Features Help/Resources www.invensys-power.com/ibm-ups/9910solutions.html, ProStart - iseries Dec, 2000 Page 1 Step 1 - Turn Off Server
More informationIBM eserver System x and BladeCenter IBM DPI PDU+ Power Distribution Units. 10/9/ IBM Corporation
IBM eserver System x and BladeCenter IBM DPI PDU+ Power Distribution Units 10/9/2007 Agenda System x Options Program and PDU market overview What is a PDU? Why do you need an IBM DPI PDU? IBM DPI PDU offering
More informationPrestige - eserver Integration
Prestige - eserver TOPICS Installation Startup Optional Features Help/Resources PrestPrep - eserver rev Apr 01 Page 1 Obtain a copy of Powerware Prestige User s Guide from URL noted: EP5 (21H1572) U33
More informationAxxium Pro - iseries (AS/400) Integration
Axxium Pro - iseries (AS/400) TOPICS Installation Startup Optional Features Help/Resources www.invensys-power.com/ibm-ups/9910solutions.html, ProPrep - iseries Dec, 2000 Page 1 Obtain a copy of Axxium
More informationPowerware 9910-P11 and 9910-P16
Powerware 9910-P11 and 9910-P16 High Performance High Reliability & Availability Flexible & Configurable Advanced Communications 2002 Eaton Corporation. All rights reserved. P11 and P16 Features Fourth-Generation
More information7014-T V, 30 or 60Amp, 3-Ph or 1-Ph
7311-D10: p570 I/O Drawer 200-240V Holds (1) or (2) D10 Drawers Max Drwr =.21KVA,.2KW,.683KBtu Drawer = 8.6Wx28Dx6.6H @37lbs. F/C 7311 = 2 Position Drawer Enclosure Enclosure = 4U 17.5Wx28Dx6.9H @86lbs.
More informationIBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems
IBM United States Hardware Announcement 111-139, dated July 26, 2011 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Table of contents 1 Overview 3 Publications
More informationCable and Port Specifications
Send documentation comments to mdsfeedback-doc@cisco.com APPENDIXC This appendix includes the cables and connectors used with the Cisco MDS 9100 Series Fixed Configuration Fabric Switch, and it includes
More informationQuickSpecs. HP Basic Power Distribution Units (bpdu) Overview
Overview HP Basic PDUs are designed to provide reliable and cost effective power distribution for your HP and non-hp IT racks. Offering simple 0U and 1U installation options, HP Basic PDUs are available
More informationNATIONAL DEVICES. Modular Design Receptacles, Switches, Pilot Lights. (45 mm)... Page 46
SECTION C NATIONAL DEVICES Modular Design Receptacles, Switches, Pilot Lights Product Installation Guide... Pages 38, 39 Modular Receptacles ( mm)... Page 40 Modular Devices ( mm)... Page 41 Dimensional
More informationeserver Integration
9125 - eserver TOPICS Preparation Startup Optional Features Help/Resources 9125Install - iseries Dec, 2000 Page 1 Step 1 - Remove UPS equipment from Cartons UPS must be placed near the installation site
More informationQuickSpecs. HPE Basic Power Distribution Units (PDU) Overview
Overview HPE Basic PDUs are designed to provide reliable and cost effective power distribution for your Hewlett Packard Enterprise and non-hewlett Packard Enterprise IT racks. Offering simple 0U and 1U
More informationPowerware P64
Powerware 91259 9910 - P64 High Performance High Reliability & Availability Flexible & Configurable Advanced Communications p64pres.ppt rev 4.16.04 1 P64 Features Double-conversion online High-power density
More informationIBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems
IBM Latin America Hardware Announcement LG10-0100, dated May 18, 2010 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Table of contents 1 Overview 2 Product
More informationIBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems
IBM United States Hardware Announcement 110-077, dated May 18, 2010 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Table of contents 1 Overview 2 Product number
More information9910 P18. Advanced power protection for mission-critical System p, System x, Storage and Networking rack products and applications. P18.
9910 P18 Advanced power protection for mission-critical System p, System x, Storage and Networking rack products and applications 2002 Eaton Corporation. All rights reserved. P18.ppt P18 snapshot High
More informationEATON Transformer Module
www.eaton.com EATON Module Quick Start Standard Features When used with standard system, EATON Module provides isolated and Step-down 0/08/0 V AC outputs. Multiple Output receptacles: 0/08/0 V AC. 86-86000-0
More informationCable and Port Specifications
APPENDIXC This appendix provides cable and port specifications, and includes the following sections: Cables and Adapters Provided, page C-1 Console Port, page C-2 COM1 Port, page C-3 MGMT 10/100/1000 Ethernet
More informationIBM 1U Switched and Monitored Power Distribution Units IBM System x at-a-glance guide
IBM 1U Switched and Monitored Power Distribution Units IBM System x at-a-glance guide The IBM 1U Switched and Monitored Power Distribution Units (PDUs) make it quick and simple to deploy, protect, and
More informationQuickSpecs. HP Remote Monitoring Power Distribution Units. Overview
QuickSpecs Overview (PDU) provide rack level power monitoring over the network. With billing grade accuracy these PDUs are excellent choices for data centers wanting to make the most of circuit capacity
More informationIBM UPS5000 HV Uninterruptible Power Supply for IBM System x Product Guide
IBM UPS5000 HV Uninterruptible Power Supply for IBM System x Product Guide The IBM UPS5000 HV is a 5 KVA rack-mountable uninterruptible power supply (UPS) that utilizes advanced backup power technology
More informationQuickSpecs. HPE Standard Series G2 Basic Power Distribution Units (PDU) Overview. Basic, reliable power distribution for your HPE IT solutions
Overview Basic, reliable power distribution for your HPE IT solutions G2 Basic PDUs are designed to work precisely with HPE Infrastructure and Compute solutions. Designed for use with HPE Standard, Advanced,
More informationPrestige - eserver Integration
Prestige - eserver TOPICS Preparation Startup Optional Features Help/Resources PrestInstall - eserver rev Apr 01 Page 1 Step 1 - Remove UPS equipment from Cartons UPS must be placed near the installation
More informationProduct comparison. 700 VA 120V tower
Product comparison Eaton 9SX vs 9130 UPS comparison Combining reliable double-conversion topology, internal static bypass and an easy-to-read LCD menu display, the Eaton 9SX UPS provides the highly efficient
More informationFamily Uninterruptible Power System (UPS) for RS/6000/pSeries IBM U.S. Sales Manual Revised: October 10, 2005.
Page 1 of 39 Family 9910+01 Uninterruptible Power System (UPS) for RS/6000/pSeries IBM U.S. Sales Manual Revised: October 10, 2005. Table of contents Document options IBM U.S. Product Life Cycle Dates
More informationRack- and Panel-Mount Power Distribution Units (PDUs)
Spec-00193 Cable and Power Management Power Distribution Units (PDUs) Rack- and Panel-Mount Power Distribution Units (PDUs) FEATURES Power on/off LED indicates whether power is available at the PDU External
More informationAPC APPLICATION NOTE #74
#74 Configuration of InfraStruXure for Data Centers to Support Dell PowerEdge 1855 Abstract Many companies are making plans to incorporate Dell PowerEdge Blade Servers into their data center applications.
More informationRack- and Panel-Mount Power Distribution Units (PDUs)
Spec-00193 Cable and Power Management Power Distribution Units (PDUs) Rack- and Panel-Mount Power Distribution Units (PDUs) FEATURES INDUSTRY STANDARDS UL/cUL 60950 listed UL 1449 (Surge protector models
More informationIBM 1000VA and 1500VA LCD Tower UPS Product Guide
IBM 1000VA and 1500VA UPS Product Guide The IBM 1000VA and 1500VA Uninterruptible Power Supply (UPS) offerings provide power protection with increased efficiency and simplified power management to safeguard
More informationSolutions Guide for Cisco UCS B and C Series Servers
Solutions Guide for Cisco UCS B and C Series Servers The Cisco Unified Computing System is a next-generation data center platform that unites compute, network, storage access, and virtualization into a
More informationPowerware P95
Powerware 93059 9910 - P95 Reliable power with proven double conversion online technology p95pres.ppt Rev 15.04.04 1 P95 Features Double-conversion, online technology protects against the 9 power problems
More informationQuickSpecs. HPE Metered and Switched Power Distribution Units (PDU) Overview
HPE Metered and Switched Power Distribution Units (PDU) Overview Looking for a power distribution unit that meets the demands of high temperature operating environments and provides monitoring and switching
More informationProduct Snapshot. The Powerware Uninterruptible Power System. Product Focus
Powerware 9120 Uninterruptible Power System Product Focus Product Snapshot Power Rating: 700-3000VA Voltage: 120 and 230 Vac Frequency: 50/60 Hz (auto-sensing) Configuration: tower Features True double-conversion
More informationPower distribution solutions for the ProLiant DL580 G2 server
Power distribution solutions for the ProLiant DL580 G2 server Introduction... 2 Symbols in text... 2 Executive summary... 2 Glossary... 2 ProLiant DL580 G2 server power requirements... 3 Power distribution
More informationHP Rackmountable 3 Phase Uninterruptible Power Systems Overview
Overview Crowded data centers and racks filled to capacity with storage devices, monitors, servers communications devices, and other equipment are driving the need for uninterruptible power with increased
More informationNetfinity White Paper Netfinity Technology Center
Netfinity White Paper Netfinity Technology Center Rack Storage Expansion Enclosure Planning Guide Abstract This paper is designed for use by Pre-Sales technical marketing representatives. This includes
More informationQuickSpecs. HP 1x4 USB/PS2 KVM Switch. HP 1x4 USB/PS2 KVM Switch. Models HP 1x4 USB/PS2 KVM Switch
Overview The provides the ideal mix of features and functionality in a compact 4 Port KVM Switch. Support for both USB and PS/2 devices, including USB peripherals such as Printers, Scanners and storage,
More informationIntelligent-Remote Monitoring (3) Environmental Port (4) Power Outlet Level (5)
Faster. Enclosure Power Distribution Units (PDUs) (continued) PDU Selection: Basic, with Local and Intelligent PDU mounted display option for local current or power monitoring, making phase balancing easier
More informationProduct Snapshot. Powerware 9140 Uninterruptible Power System. Superior de-centralized power protection for medium- and high-density rack environments
Powerware 9140 Uninterruptible Power System Product Focus Superior de-centralized power protection for medium- and high-density rack environments Product Snapshot Features Protects mission-critical rackmount
More informationStorNext M440 Site Planning Guide
StorNext M440 Contents StorNext M440 Site Planning Guide Included with Your StorNext M440... 1 Professional Installation Requirements. 2 Site Requirements... 2 Shipping Information... 3 StorNext M440 System
More informationP/N Operation & Installation Manual Serial Control Transfer Switch Model TM-STS
P/N 92 53626 000-11 Operation & Installation Manual Serial Control Transfer Switch Model TM-STS 92 53626 000 Table of Contents 1.0 SCOPE 1 2.0 INTRODUCTION 1 3.0 SPECIFICATIONS 2 4.0 EQUIPMENT DESCRIPTION
More informationSmartOnline 20kVA On-Line Double-Conversion UPS, N+1, 14U Rack/Tower, 208/120V or 240/120V NEMA & C19 outlets
SmartOnline 20kVA On-Line Double-Conversion UPS, N+1, 14U Rack/Tower, 208/120V or 240/120V NEMA & C19 outlets MODEL NUMBER: SU20KRT-1TF Description Tripp Lite SU20KRT-1TF 20,000VA / 20kVA / 18,000 watt
More informationHP PDU Best Practices
HP PDU Best Practices Abstract... 2 Introduction... 2 Product Highlights... 2 HP PDU Models Available... 2 Modular PDUs... 2 Modular PDUs... 3 Monitored PDUs... 3 HP Modular PDU Advantages... 4 HP Monitored
More informationProduct brochure. Eaton 9PXM UPS. A scalable, modular, flexible solution for a wide range of applications. Plan > Grow > Manage
Product brochure Eaton 9PXM UPS A scalable, modular, flexible solution for a wide range of applications. Plan > Grow > Manage Highest level of reliability. Lowest cost of ownership. The Eaton 9PXM UPS
More informationOmniSmart 230V 350VA 225W CE/IEC Medical Grade Line-Interactive UPS with Built-In Isolation Transformer
OmniSmart 230V 350VA 225W CE/IEC 60601-1 Medical Grade Line-Interactive UPS with Built-In Isolation Transformer MODEL NUMBER: OMNIX350HG Highlights 350VA line interactive tower UPS Professional features
More informationCable and Port Specifications
APPENDIXD This appendix provides the cable and port specifications, and includes the following sections: Cables and Adapters Provided, page D-1 Console Port, page D-2 COM1 Port, page D-3 MGMT 10/100/1000
More informationSmartPro LCD 230V 1.5kVA 900W Line-Interactive UPS, 2U Rack/Tower, LCD display, USB, DB9 Serial
SmartPro LCD 230V 1.5kVA 900W Line-Interactive UPS, 2U Rack/Tower, LCD display, USB, DB9 Serial MODEL NUMBER: SMX1500LCD Highlights 1500VA / 1.5kVA 2U rack/tower 230V line interactive UPS with LCD display
More informationIBM 7014 racks help organize smaller rack-mount systems and expansion drawers
Hardware Announcement October 4, 2005 IBM 7014 racks help organize smaller rack-mount systems and expansion drawers Overview Manufactured to meet the EIA 310-D standard, the IBM 7014 Model S11 Rack and
More informationTripp Lite PDUs POWER DISTRIBUTION UNITS. Reliable rack power distribution for high-density IT environments. Introduction 2-3.
POWER DISTRIBUTION UNITS Tripp Lite rack power distribution for high-density IT environments. Introduction 2-3 Basic 4 Metered 5 Monitored 6 Switched 7 ATS 8 Hot-Swap 8 INTRODUCTION Tripp Lite Rack increase
More informationReference Data Eaton 9PX 6000i Rack/Tower 3U UPS
Eaton 9PX 6000i Rack/Tower 3U UPS Eaton 9PX 6000i Energy efficient Online Double conversion UPS (up to 94% efficiency in online mode), 6000VA/5400W, Versatile Rack/Tower 3U, Parallel operation (power extension
More informationModels HP Tablet Charging Module HP Charging Module LAN Kit
Overview Models HP Tablet Charging Module HP Charging Module LAN Kit J6X15AA K7H15AA Introduction Quickly and easily charge, update, store, and secure up to 10 tablet PCs inside the HP Tablet Charging
More informationRetired. Full Rack Vertical PDU Model (Ideal for 36U to 47U racks)
Overview The HP Monitored PDUs allow administrators and facility personnel to monitor current draw directly at the rack and per PDU. HP Monitored PDUs are available in both 1 phase and 3 phase and in single
More informationProduct Snapshot. the Powerware Uninterruptible Power System. Double-conversion, online design offers superior reliability and protection
Powerware 9125 Uninterruptible Power System Product Focus 700-6000 VA Powerware 9125 6000 VA Features Protects mission-critical applications from downtime, data loss and corruption, and process interruption
More informationAcumentrics UPS Accessories List
Part Number ACG9010 ACG9012 ACG9013 ACG9019 ACG9021 ACG9022 ACG9200 ACG9201 ACG9202 ACG9203 ACG9205 ACG9206 ACG9208 ACG9209 ACG9210 ACG9211 ACG9214 ACG9215 ACG9216 ACG9217 ACG9218 Acumentrics UPS Accessories
More informationMaking the switch: 9130 rackmount to 9PX
Cross reference Making the switch: 9130 rackmount to 9PX The 9PX 700-3000 VA UPS models are here reliable, versatile, powerful, efficient power for IT equipment. If you re looking to upgrade your 9130
More informationIBM 3000VA LCD 3U Rack Uninterruptible Power Supply for IBM System x Product Guide
IBM 3000VA LCD 3U Rack Uninterruptible Power Supply for IBM System x Product Guide The IBM 3000VA LCD 3U Rack uninterruptible power supply (UPS) delivers 2700 watts of power in only 3U of rack space, providing
More informationPowerware Software Connectivity Service. > Powerware Software Suite ensures data integrity; free updates on
Powerware 9120 Features True double conversion online technology give you protection from all nine power problems Simple installation and operation Intuitive LCD screen provides realtime updates of UPS
More informationQuickSpecs HP T750 UPS. Overview
Overview Rated at 750 VA/500 Watts, the features a unique design and easy-to-configure front panel display. Ideal for desktop, workstation, or entry-level server environments, this Uninterruptible Power
More informationIntelligent-Remote Monitoring (3) Power Circuit Environmental Port (4) Power Outlet Level (5) PDU De-Rated Power Watts (W) PDU Nominal.
Enclosure Power Distribution Units (PDUs) (continued) PDU Selection: Basic, with ocal Monitoring and Intelligent Highly secure access with admin, control and view-only accounts Intuitive Ethernet-based
More informationBest Practices Guide. EMC VMAX3 Family. Best Practices Guide for AC Power Connections REVISION 2.0. August, 2015
Best Practices Guide EMC VMAX3 Family Best Practices Guide for AC Power Connections REVISION 2.0 August, 2015 Best practices overview for AC power connections... 3 Selecting the proper AC power connection
More informationAudio/Video Solutions - Power Filter (Line Noise, Surge & Spike Protection)
Retail Pricing Pricing subject to change without notice. Audio/Video Solutions - Power Filter (Line Noise, Surge & Spike Protection) Many products may have EMI/RFI noise rejection, but it is typically
More informationQuickSpecs. HPE Standard Series G2 Basic Power Distribution Units (PDU) Overview. Basic, reliable power distribution for your HPE IT solutions
Overview Basic, reliable power distribution for your HPE IT solutions G2 Basic PDUs are designed to work precisely with HPE Infrastructure and Compute solutions and guarantee a compatible fit for use with
More informationINTERNATIONAL MODULAR WIRING DEVICES
INTERNATIONAL MODULAR WIRING DEVICES International Configurations Inc s product range of Country specific modular wiring devices are designed for Worldwide construction projects, data centers, medical
More information5125 Family Uninterruptible Power System
Powerware series 5125 Family Uninterruptible Power System 5125 rackmount 5000 to 6000 VA Features Protects connected from common power anomalies including surges, sags, brownouts, and over-voltage Provides
More informationRT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies Product Guide
RT1.5kVA, RT2.2kVA and RT3kVA 2U Rack or Tower Uninterruptible Power Supplies Product Guide The RT1.5kVA, RT2.2kVA, and RT3kVA 2U Rack or Tower Uninterruptible Power Supply (UPS) offerings provide extended
More informationAPC by Schneider Electric Solutions for Cisco Unified Computing System (UCS) Blade Applications
APC by Schneider Electric Solutions for Cisco Unified Computing System (UCS) Blade Applications The Cisco Unified Computing System is a next-generation data center platform that unites compute, network,
More informationSmartOnline 208/240 & 120V 20kVA 18kW, Double-Conversion UPS, N+1, 14U, Network Card Slot, USB, DB9, Bypass Switch
SmartOnline 208/240 & 120V 20kVA 18kW, Double-Conversion UPS, N+1, 14U, Network Card Slot, USB, DB9, Bypass Switch MODEL NUMBER: SU20KRT-1TF Highlights 20kVA / 20,000VA / 18,000W on-line double-conversion
More informationInstallation Job Aid for VSP 4450GTX-HT- PWR+
Installation Job Aid for VSP 4450GTX-HT- PWR+ Notices Release 6.1.0.0 NN46251-305 Issue 02.01 November 2017 Notice paragraphs alert you about issues that require your attention. The following paragraphs
More informationPW9170+ CTO Configuration Guide CTO Configuration Guide
CTO Configuration Guide Eaton 9170+ UPS 9170PCG January 1, 2018 Configuring Your PW9170+ UPS PW9170+ chassis s must be ordered using a Configure To Order (CTO) Number that reflects the cabinet style, isolation
More informationOmniVS 230V 800VA 475W Line-Interactive UPS, USB port, C13 Outlets
OmniVS 230V 800VA 475W Line-Interactive UPS, USB port, C13 Outlets MODEL NUMBER: OMNIVSINT800 Highlights 800VA tower 230V line interactive UPS Corrects brownouts as low as 159V without using battery power
More informationQuickSpecs. HP Intelligent Power Distribution Unit (ipdu) Overview
Overview You cannot control what you cannot monitor. The new brings state of the art management and control to rack mounted power distribution units (PDU) to prevent over provisioning of power from restricting
More informationHP Uninterruptible Power Supplies Overview
NOTE: Additional information on these and additional HP UPS products at: http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/index.html Description HP rack mountable UPSs, designed
More informationTripp Lite PDUs POWER DISTRIBUTION UNITS. Reliable rack power distribution for high-density IT environments. Introduction 2-3.
POWER DISTRIBUTION UNITS Tripp Lite rack power distribution for high-density IT environments. Introduction 2-3 Basic 4 Metered 5 Monitored 6 Switched 7 ATS 8 Hot-Swap 8 INTRODUCTION Tripp Lite Rack increase
More informationSmartPro 230V 1kVA 500W Line-Interactive UPS, Tower, LCD, USB, 6 Outlets
SmartPro 230V 1kVA 500W Line-Interactive UPS, Tower, LCD, USB, 6 Outlets MODEL NUMBER: SMX1000LCD Highlights Corrects under- and overvoltages from 171V to 266V 6 C13 outlets 3 surge-only Interactive LCD
More informationAudio/Video Solutions - Power Filter (Line Noise, Surge & Spike Protection)
Retail Pricing Pricing subject to change without notice. Audio/Video Solutions - Power Filter (Line Noise, Surge & Spike Protection) Many products may have EMI/RFI noise rejection, but it is typically
More informationMetered Rack PDU Rack PDU, Metered, Zero U, 5.7kW,208V,(36)C13& (6)C19; 10' Cord
Metered Rack PDU Rack PDU, Metered, Zero U, 5.7kW,208V,(36)C13& (6)C19; 10' Cord APC Metered Rack PDU, Input: 208V 3PH, Input Connections: NEMA L21-20P, Cord Length: 10 feet ( 3.05 meters ), Output: 208V,
More informationEaton BladeUPS 12 60kW
Power Quality Solution for Data Centres Eaton BladeUPS 12 60kW The power quality solution that simply grows with your needs Delivering power reducing costs Two key trends have emerged in the data centre:
More informationFrame Relay Cabling This section describes the cabling and connector pinouts for the Frame Relay cards.
A P P E N D I X B Cabling Summary Introduction This appendix contains details on the MGX 8850 cabling. Note In all cable references, the transmit direction is away from the switch, and the receive direction
More informationOmniVS 230V 1500VA 940W Line-Interactive UPS, Extended Run, Tower, USB port, C13 Outlets
OmniVS 230V 1500VA 940W Line-Interactive UPS, Extended Run, Tower, USB port, C13 Outlets MODEL NUMBER: OMNIVSINT1500XL Highlights 1500VA / 1.5kVA tower 230V line interactive extended-run UPS Corrects brownouts
More informationXTREME POWER CONVERSION THE VALUE LEADER IN POWER PROTECTION
CONVERSION THE VALUE LEADER IN POWER PROTECTION Xtreme Power is a global manufacturer of power quality and data center solutions Xtreme Power manufactures UPS from 400VA to 40kVA Designs, engineers, and
More informationIBM 11000VA LCD 5U Rack Uninterruptible Power Supply Product Guide
IBM 11000VA LCD 5U Rack Uninterruptible Power Supply Product Guide Did you know? Unlike other competing UPS topologies, the IBM 11000VA UPS features online double-conversion technology to fully protect
More informationUPS Systems With functionality, flexibility, and ease of installation at top of mind, V7 UPS systems are designed with high grade durable components
UPS Systems With functionality, flexibility, and ease of installation at top of mind, V7 UPS systems are designed with high grade durable components and materials. Rigorous load and performance testing
More informationThe Basics of Selecting Rack-Mount Power Distribution Units (PDUs) and Power Strips
WHITE PAPER The Basics of Selecting Rack-Mount Power Distribution Units (PDUs) and Power Strips By David Knapp Product Marketing Manager Chatsworth Products (CPI) Published: January 2019 US & Canada +1-800-834-4969
More informationQuickSpecs. Compaq Uninterruptible Power Systems M ODELS
M ODELS Rack-Mountable UPS Models 242704-001 242705-001 h-na 242705-003 Tower UPS Models 295372-B21 242688-001 242688-003 242688-005 T2400h-NA 242688-007 OVERVIEW Compaq UPS Products Compaq has developed
More informationBC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets
BC Pro 120V 1400VA 940W Standby UPS, Tower, USB port, 6 Outlets MODEL NUMBER: BCPRO1400 Highlights 1400VA / 1.4kVA tower 120V standby UPS Maintains AC output during power failures USB port, Front panel
More informationRE Series Rack from Eaton Product Presentation
RE Series Rack from Eaton Product Presentation AUG 2018 Quick Overview What is Eaton s RE Series Rack Platform? RE Series is an amalgamation of the NR & RE Series with many value-add component enhancements;
More informationIBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems
Hardware Announcement ZG09-0284, dated July 28, 2009 IBM 9910 Uninterruptible Power Systems safeguard your equipment and data from power problems Table of contents 1 At a glance 3 Publications 1 Overview
More informationAVR Series 230V 550VA 300W Ultra-Compact Line-Interactive UPS with USB port, C13 Outlets
AVR Series 230V 550VA 300W Ultra-Compact Line-Interactive UPS with USB port, C13 Outlets MODEL NUMBER: AVRX550U Highlights 550VA ultra-compact 230V line interactive UPS Corrects brownouts and overvoltages
More information