HVAC DESIGN REQUIREMENTS FOR DATA CENTERS

Similar documents
DATA CENTER PRECISION COOLING: The Need For A Higher Level Of Service Expertise

Product Brochure DENCO Close Control Units Row-DENCO. High Density Cooling for Data Centres

CHILLED WATER. HIGH PRECISION AIR CONDITIONERS, FROM 7 TO 211 kw

IT COOLING EVAPORATIVE COOLING SYSTEM. 2 STAGE INDIRECT ADIABATIC COOLING SYSTEM FOR LARGE DATA CENTERS FROM 80 TO 320 kw

Reducing Data Center Cooling Costs through Airflow Containment

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat

A) Differences between Precision and Comfort Cooling Here are the major differences exist between precision air conditioning and comfort systems.

Design Considerations for Datacom Equipment Centers

Mission Critical Facilities & Technology Conference November 3, 2011 Cooling 101. Nick Gangemi Regional Sales Manager Data Aire

Data Center Energy Savings By the numbers

Rack cooling solutions for high density racks management, from 10 to 75 kw

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets

ASHRAE IRELAND HVAC FOR DATA CENTRES. Michael Geraghty Building Services Engineer (DipEng) Company owner and managing director

Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency

Introducing the Heat Wheel to the Data Center

Evaporative free air cooling technology Providing evaporative free air cooling solutions.

Cooling. Highly efficient cooling products for any IT application. For More Information: (866) DATA CENTER SOLUTIONS

Is Data Center Free Cooling Feasible in the Middle East? By Noriel Ong, ASEAN Eng., PMP, ATD, PQP

ENCLOSURE HEAT DISSIPATION

Precision Cooling. Precision Cooling Advantages

FREECOOLING, EVAPORATIVE AND ADIABATIC COOLING TECHNOLOGIES IN DATA CENTER. Applications in Diverse Climates within Europe, Middle East and Africa

NREL Validates LCS Technology. PRESENTED BY Herb Zien CEO, LiquidCool Solutions

ZTE ZXCR Series DX In-Row Air Conditioning Product Description

Why would you want to use outdoor air for data center cooling?

Data center cooling evolution. The hottest way to save energy. Lucio Bustaffa: Product Development Manager BlueBox Group

High Efficient Data Center Cooling

Data Center Energy and Cost Saving Evaluation

SOFTWARE TOOLS FROM BUILDINGS ENERGY SIMULATION

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

APC APPLICATION NOTE #114

ecoenergy Innovation Initiative Research and Development Component Public Report

DATA CENTER EFFICIENCY: Data Center Temperature Set-point Impact on Cooling Efficiency

Latex 110 Printer. Site preparation guide

Liquid Cooling Package LCP Cooling Systems

Passive RDHx as a Cost Effective Alternative to CRAH Air Cooling. Jeremiah Stikeleather Applications Engineer

MSYS 4480 AC Systems Winter 2015

High Tech Getting Too Hot? High Density Environments Require A Different Cooling Approach

White paper adaptive IT infrastructures

Energy Saving in Cleanrooms

Scalable, Secure. Jason Rylands

LCP Hybrid Efficient performance with heat pipe technology

RiMatrix S Make easy.

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

LCS Value Proposition November 2014

Indirect Adiabatic and Evaporative Data Center Cooling

Server Room & Data Centre Energy Efficiency. Technology Paper 003

ASHRAE Data Center Standards: An Overview

Google s Green Data Centers: Network POP Case Study

FACT SHEET: IBM NEW ZEALAND DATA CENTRE

Colour Luminous flux Φv Forward voltage Power consumption Tc= 65 C Tc= 25 C Tc= 65 C Tc= 65 C Tc= 65 C

Colour Luminous flux Φv Forward voltage Power consumption Tc= 65 C Tc= 25 C Tc= 65 C Tc= 65 C Tc= 65 C

Thermal Design and Management of Servers

Cooling on Demand - scalable and smart cooling solutions. Marcus Edwards B.Sc.

Cooling Solutions & Considerations for High Performance Computers

A Data Center Heat Removal System That Saves... 80% Discover Inertech s Award-winning Data Center Heat Removal System

MODELING PARTICLE DEPOSITION IN VENTILATION DUCTS

Technology for Constructing Environmentally Friendly Data Centers and Fujitsu s Approach

Running Your Data Center Under Ideal Temperature Conditions

L-iC-282. Tunable White Linear LED Module, L-iC Series. 450 ma, 14.9 V. Electrical specifications. Lifetime specifications

Improving the climate for data centers

HIGH DENSITY RACK COOLING CHOICES

LX-562A. Linear LED Module, LX Series. 450 ma, 62.7 V. Electrical specifications. Lifetime specifications. Operating Conditions and Characteristics

Communication Register Map - Uniflair Cooling

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

PEX (R410A) High Efficiency, Green Solution Precision Cooling for Data Centers

400V MDU POWER MODULE AND MDU CONTROL MODULE SET APPLICATION MANUAL V 1.1

) Forward voltage (V f. Typ. Typ. Typ. Max. Typ. Typ. Typ. [K] [lm] [lm] [V] [V] [lm/w] [lm/w] Operating Tc. current Temp

Thermal management. Thermal management

Rack & Enclosure Systems

Indirect Adiabatic and Evaporative Data Centre Cooling

Total Modular Data Centre Solutions

) Forward voltage (V f. Typ. Max. Typ. [V] [V]

Liebert DCW CATALOGUE

) Forward voltage (V f. Typ. Typ. Typ. Max. Typ. Typ. Typ. [K] [lm] [lm] [V] [V] [lm/w] [lm/w] Operating Tc. current Temp

Environmental Data Center Management and Monitoring

APC APPLICATION NOTE #126

How to Increase Data Center Efficiency

Schneider Electric Cooling Portfolio. Jim Tubbesing Heath Wilson APC/Schneider North Texas Rep Tubbesing Solutions

Ecoflair Air Economizers

Server room guide helps energy managers reduce server consumption

Liebert DM. High Performance, Sensible Cooling for Small Computer Rooms and Network Closets

Case Study The University of Warwick

LED INDUSTRY KIT. LED Industry Kit LED Modules for Industry Lighting WU-M-564 LED INDUSTRY KIT WU-M-564

LED LINEAR ALLROUND GEN. 3

Extreme Weatherproof in Surveillance Cameras

Experimental Study of Airflow Designs for Data Centers

Liquid Cooling Package LCP Cooling Systems

Impact of Air Containment Systems

Moving Containment Inside the Enclosure. Jeff Markle Great Lakes Case & Cabinet

EOS-6000 Series Optical A/B Switch User Manual DC Version

Avoidable Mistakes that Compromise Cooling Performance in Data Centers and Network Rooms

2018 Product overview

Overcoming the Challenges of Server Virtualisation

Review on Performance Metrics for Energy Efficiency in Data Center: The Role of Thermal Management

No. of. Voltage. Power

Future of Cooling High Density Equipment. Steve Madara Vice President and General Manager Liebert Precision Cooling Business Emerson Network Power

Green IT and Green DC

Precision Cooling Mission Critical Air Handling Units

ROOFTOP UNIT NOISE CONTROL SOLUTIONS

Transcription:

Bulletin of the Transilvania University of Braşov CIBv 2015 Vol. 8 (57) Special Issue No. 1-2015 HVAC DESIGN REQUIREMENTS FOR DATA CENTERS C.G. POPOVICI 1 Abstract: One of the things definitive for the HVAC system of a Data Center is represented by the potential, major, risk of uncontrolled heat release. Typically, these applications are vital to equipment installed, imply continuity in supply and impose special requirements for temperature, humidity and air filtration so that their failure could cause overheating and damage. Together, these parameters, called limit parameters, are required for the optimal functioning of these equipment types. Key words: HVAC system of a Data Center, parameters, sample calculation. 1. Introduction In the design of a data center one must take into account that the equipment is periodically replaced with newer technologies during the period of existence. Equipment is supposed to have between 1 and 5 years lifetime, while the data center itself has an estimated lifespan of 10-25 years [1]. So, during its existence, there may be several cycles of replacing equipment, which leads to the need of changing infrastructure or technological requirements (higher installed power need greater cooling, etc.). Parameters to achieve in a data center vary according with equipment manufacturer standards, but ASHRAE, 2011 edition, introduced a classification of equipment types depending on the applications they serve [2]: Class 1: telecommunications equipment servicing critical applications, located in a building with controlled atmosphere (dew point, temperature, relative humidity); Class 2: telecommunications equipment serving media applications placed in a space, office or lab, having a selective control over certain parameters (dew point temperature, and, possibly, relative humidity); Class 3: telecommunications equipment serving small applications, set in spaces, offices or mobile environments having control over a small number of parameters (temperature); Class 4: POS equipment and industrial applications, with special requirements for protection against climatic factors, special requirements for operation in winter and minimum conditions of ventilation in summer. 2. General Design Criteria The following are interior design parameters for Classes 1 and 2 as defined 1 Technical University Gheorghe Asachi of Iasi, Faculty of Civil Engineering and Building Services, Department of Building Services.

406 Bulletin of the Transilvania University of Brasov Vol. 8 (57) Special Issue No.1-2015 Design parameters Table 1. Design parameters for Class 1 and Class 2 Parameter Permissible limits Recommended limits Range of temperature 15 C - 32 C (Class 1) 18 C - 27 C control 10 C - 35 C (Class 2) The maximum rate of 5 K/h change of temperature Range control relative humidity The filtration 20% - 80% 17 C max. Dew point (Class 1) 21 C max. Dew point (Class 2) Dew point 5 C - 15 C relative humidity <60% 65%, minimum 30% (MERV 11, minimum MERV 8)* cf. ASHRAE (Filter M6, minimum Filter M5)* equiv. EU in ASHRAE, 2011 edition, both tabular and diagram ix. Acceptable limits of temperature control represent a matter of functionality, while recommended limits temperature control are a matter of reliability. Consequently, operating equipment subject of high temperatures (and / or sudden changes in temperature gradient) is exposed to a higher rate of failure, decrease of service ability or frequent stops caused by built-in thermal protection [3]. Exceeding the recommended limits for short periods is not a threat, but nearly operation permissible limits for a long time can affect system integrity [4], thus, it is recommended that design of infrastructure conditioning ensure continuous operation within recommended instead of allowed parameters. In Table 2 design parameters are represented by diagrams for permissible limits ix and recommended temperature for Class 1 and Class 2. Table 2. Diagram i-x -Clasa 1 - allowable limits Poin Temperature( C) Temp. Dew point ( C) Relative humidity (%) Moisture content (g/kg) 1 15 C - 6.9 C 20 % 2.10 g/kg 2 15 C 11.6 C 80 % 8.48 g/kg 3 20.6 C 17 C 80 % 12.13 g/kg 4 32 C 17 C 40.8 % 12.13 g/kg 5 32 C 6.2 C 20 % 5.89 g/kg

C.G. POPOVICI: HVAC design requirements for the data centers 407 Diagram i-x for Class 2 - allowable limits Point Temperature( C) Temp. Dew point ( C) Relative humidity (%) Moisture content (g/kg) 1 10 C - 10.6 C 20 % 1.51 g/kg 2 10 C 6.7 C 80 % 6.09 g/kg 3 24.7 C 21 C 80 % 15.65 g/kg 4 35 C 21 C 44.2 % 15.65 g/kg 5 35 C 8.7 C 20 % 6.98 g/kg Diagram i-x -Clasa 1 and Clasa 2 - recommended limits Point Temperature( C) Temp. Dew point ( C) Relative humidity (%) Moisture content (g/kg) 1 18 C 5.5 C 43.8 % 5.60 g/kg 2 18 C 10.1 C 60 % 7.70 g/kg 3 23.2 C 15 C 60 % 10.64 g/kg 4 27 C 15 C 47.8 % 10.64 g/kg 5 27 C 5.5 C 25.4 % 5.60 g/kg Diagram i-x - Class 1 and Clasas2 - allowable and recommended limits ( overlapping areas ) Air density affects the efficiency of cooling equipment. Most equipment installed in data centers are designed to be used up to a maximum altitude of 3050m. Over an altitude of 900m, a correction is applied to the allowable temperature limit, respectively, a decrease of the upper limit of 1K for each 300m, according to the chart.

408 Bulletin of the Transilvania University of Brasov Vol. 8 (57) Special Issue No.1-2015 The maximum temperature variation rate Some equipment manufacturers have established explicit criteria for indoor climate variation rate in order to prevent eventual shocks. Maximum temperature input can have a maximum variation of 5 K / h, according to ASHRAE, 2011 edition, for Classes 1 and 2. Humidity variation rate is important in storage units, where conditions are more stringent: variation of 2K/ h and relative humidity 5%/h. Standard emergency procedures had been developed, considering the main cooling system becomes inoperative, while vital equipment is still operating - a sudden increase in indoor temperature occurs. It is important that the procedure will restore in due time the climate conditions at recommended values in order to avoid thermal shock - overheating. Generally, when not in use, the equipment can be installed in an environment with a wider range of limitations for control parameters, but it is recommended maintaining them within the limits required in order to avoid thermal shock on the components themselves, even if changes in temperature, humidity, etc. do not occur instantaneously. Humidity conditions A high value of relative humidity can lead to defects, excessive wear and corrosion, caused mainly by the appearance of conductive anode filaments (CAF - conductive anodic failures) on electronic boards and deposits of hygroscopic dust (HDF - hygroscopic dust failures) and thus salts. In extreme cases, condense can also occur, especially when equipment are liquid cooled [5]. A low relative humidity can lead to electrostatic discharge (ESD - electrostatic discharge) that can irreparably damage equipment. The filtration Before being introduced into the equipment room, the outdoor air should be filtered to remove impurities (dust, etc.). The particles can affect the integrity of the equipment, thus requiring a higher degree of filtration and an adequate maintenance of the filters installed in the air conditioning system. Classification of filters and correlation between ASHRAE specifications and applicable European Norms (EN 779: 2012 and EN1822: 2009) is shown below: Ventilation The interior must have a constant supply of fresh air to ensure: pressure in the room; correct dilution of pollutants (particularly volatile organic compounds - VOC); maintaining conditions required by ASHRAE 62.1 standard; maintaining conditions required by national and European standards; Providing overpressure will prevent pollutants penetration indoors. Calculations regarding pressurization are highlighted in Chapter 9 of ASHRAE edition 2009. In general, the presence of people inside spaces intended for equipment is minimal, but nonetheless this factor should be taken into account during the design of air conditioning system. Considerations on coating The criteria for choosing the coating type must comply with the requirements of national and European standards, but the main factors to be considered are: The pressurization: a minimum pressure level is provided in order to prevent pollutants penetration inside; Degree of isolation: the rooms are isolated both in terms of indoor climate conditions and safety; Steam absorption: in order to maintain optimum relative humidity, the difference between vapor pressure inside equipment room and adjacent rooms will be taken into

C.G. POPOVICI: HVAC design requirements for the data centers 409 consideration, so that moisture migration is controlled; The tightness: crossing cables and pipelines are insulated with nonhygroscopic materials and access routs are perfectly sealed; The condensation: regarding exterior envelope, for buildings located in very cold areas, the use of double or triple glazed windows and sealed doors is recommended as to prevent condensation and infiltration. It is recommended to design the data center without windows. If an existing building is used, measures for covering the windows will be taken. Conditions for human comfort In data centers, comfort conditions specific to persons are not covered, their presence being a transitory and short-term. Consequently, human comfort is not one of the criteria to be considered in the design theme of the HVAC system. HVAC system flexibility As I stated in the introduction, the technology is under continuous and accelerated transformation, so that equipment is frequently changed, rearranged and added during the period of existence of a data center and as a result, the HVAC system serving the unit must be flexible enough to support changes and expansions without major impact on current activity. For critical applications, the system must be modified without interruption. It is then recommended a modular system that will allow efficient cooling of the various tasks. Acoustic criteria Total acoustic emission on site is given by the sum of IT equipment emissions and HVAC. With increasing power density and thermal loads of IT equipment, HVAC noise emission had also increased. The limit values are regulated in Europe by the European Directive 10/2003 (EC Directive 2003/10) and subsequent amendments setting out maximum values of noise emissions at work and exposure to them. Anti- vibration insulation and seismic conditions The HVAC system must be installed independently to prevent the transmission of vibration to the IT equipment. All the necessary measurement will be taken so that system will be installed in maximum seismic safety and using functional vibration isolators. 3. Heat Release Calculation Heat release calculation for a data center will take into account that the main releases are the sensible heat from IT equipment, representing a major proportion of the total heat cavities (85-90 % to 100 %). q q t Fig.1. Main heat release s SHR = (1) wher: q -is sensibile heat; s qt -is the total heat; Depending on the ratio of sensible heat, cooling systems can be classified into two categories: - Cooling systems to achieve thermal comfort (human); - Precision cooling systems; Therefore, in the case of data center cooling system we will consider a precision system designed to remove the

410 Bulletin of the Transilvania University of Brasov Vol. 8 (57) Special Issue No.1-2015 heat released by the sensitive equipment, and possible moisture ( much less). Calculation procedure of heat release must consider that there may be other heat sources alongside IT equipment, and dimensioning based on W / m2 principle or W/equipment, can leave aside a significant amount of heat (emitted by network of electrical wiring, lighting, other related equipment - UPS, heat inputs from other rooms, etc.). A proper design of a HVAC system account for all kinds of interior heat sources, and establishes long-term energy strategy, in order to identify the degree of modularity of the system. For example, in a new data center, designed to be upgraded regularly, operation in the first part of its life is performed at a partial load capacity and the heat gains through the envelope, the lighting and other sources can be important, not at all negligible in partial capacity operation. To assess the heat releases in the area, there have been developed different methods for fast calculation based on the total amount of emissions of heat from components of the data center : Basic releases - IT equipment, UPS, power distribution system, lighting, human and other HVAC related equipment and possible- releases and other contributions (coating and adjacent spaces ) [6]; Evaluation implies a set of standardized rules and principles. Effectiveness of UPS and power distribution systems determine fixed heat values, proportional with the workload. Releases from lighting and humans are calculated using standard values. Heat dissipation of IT equipment can be concentrated, irregular, distributed or variable. Equipment that generates an important amount of heat has own fans and active cooling system that intakes air from the room and passes it through the machine. Heat from HVAC related equipment present in the room (fans, compressors) are assumed to be discharged directly outside, therefore, they are not usually taken into consideration. Instead, these emissions are taken into account when calculating the total efficiency of the cooling system (it drops by discharging more heat from its own subcomponents). Other heat inputs may exist in a lower percentage: the coating, the adjacent spaces, etc. and it must be quantified only if it is to believe they can influence in a considerable degree over indoor climate. Depending on the input, heat release results will lead to a first conclusion on the cooling system requirement. In general, data centers operate at a reduced electric load factor, electrical power absorbed hovering around an average of 30 % (start value - the first 2 years) and 80-90 % (the end - after 5 years). The efficiency of electrical distribution and UPS decreases once the power absorbed decreases, thus influencing on the amount of heat released and increasing their percentage of the total heat emission. 4. Sample Calculation for a Data Center with the following features: -IT equipment power: 250 kw -UPS installed power: 250 kw -electrical power distribution system: 280 kw -surface: 465 m². -personnel: 20 people

C.G. POPOVICI: HVAC design requirements for the data centers 411 -resulting cooling thermal load: kw 113.63 at 30 % and 265.57 kw at 90%. Weighted load 30% (113.63 kw) dimensioning method, W / square meter, without taking into account the type of equipment served by the system. Weighted load 90% (265.57 kw) Fig. 4. History of IT equipment installed power impressions (W / square meter) Fig. 2. Share of heat release The share of total energy consumption is the energy consumption of IT equipment, with a typical value of about 52% of the total, followed closely by energy consumption of HVAC system, with a typical value of 37 %. The remaining 10 % represent consumption with other systems, including energy losses due to electrical conversion. Fig. 3.The shares of the total consumption - typical values for a data center According to the chart, the amount of power use efficiency (PUE) would be 1.92. The current trend in the field is the steady growth of installed power equipment per square meter, which implicitly leads to higher heat release and the need for accurate projections based on thermal footprint (W / square meter). An unfair practice resulting from such a chart would be using the data for a quick 5. Heating and Reheating Thermal heating demand in a data center is minimal, if we refer only to the equipment room, due to important sensible heat released by them. However, HVAC system design must take into account that these releases may be minimal in the first operational period and may not cover the necessary heat to maintain internal conditions within the recommended range. Therefore, the system must be equipped with a heating mode to compensate for thermal differences in exceptional cases (e.g. small releases of large equipment and envelope losses). Some systems can use reheating to adjust humidity. This process should be closely monitored and controlled as successive processes of heating and air cooling can lead to energy waste. Humidification Humidification and / or dehumidification play an important role in the treatment of indoor air. In most cases, the main contributor of moisture is the outdoor air. Where there is no supply air humidification process, measures against discharges are taken, such as special equipment for earthing personnel.

412 Bulletin of the Transilvania University of Brasov Vol. 8 (57) Special Issue No.1-2015 Thermal density Some equipment that can power a data center may exceed the 30-40 kw heat released. This leads to the need for detailed knowledge of the setup and heat density releases in order to properly design the HVAC system. In such cases, a local cooling system will be provided conjunct with the central system. To conclude, even if the HVAC system as a whole, is covering all cooling demand, uneven heat release neglect can lead to overheating in certain areas and the inability to maintain an appropriate climate. Following the technological advancement of equipment, as well as increased cooling requirements, there may be situations where cooling air no longer represent a viable solution. This is where liquid cooling techniques intervene, which may include: cooling water, refrigerant, or biphasic dielectric fluids. 6. Conclusions A proper design of the HVAC system must take into consideration all types of interior heat sources, focusing on establishing a long-term energy strategy and identification of the modularity degree of the system. The HVAC system serving the unit must be sufficiently flexible, capable to handle changes and expansions without a major impact on the activity. The current trend in the field is the steady growth of installed power equipment per square meter, which implicitly leads to higher heat releases and the need for accurate projections based on thermal impression (W / square meter). In the first period of operation of a data center, the average ratio of cooling load installed and the real demand is five (times), decreasing as the average load capacity increases, and reaching a final value of approximately 2 ( times). The latest data centers are using variable air volume systems, operating based on inlet temperature and / or actual workload. The most significant share of total energy consumption is the energy consumption of IT equipment, with a typical value of about 52% of the total, followed closely by energy consumption of HVAC system, with a typical value of 37 %. The remaining 10 % represent consumption with other systems, including energy losses due to electrical conversion. References 1. "ASHRAE Handbook - HVAC applications SI", 2011 Ed. - author American Society of Heating, Refrigerating and Air Conditioning Engineers. 2. "ASHRAE Handbook - Fundamentals SI",2009 Ed. - author American Society of Heating, Refrigerating and Air Conditioning Engineers. 3. Sawyer R.: Calculating total power requirements for data centers, APC White Paper#23. 4. Niemann, J., Brown, K., Avelar, V: Impact of hot and cold aisle containment on data center temperature and efficiency, APC White Paper 135 5. Evans, T.: The different technologies for cooling data centers, APC White Paper#59 - author 6. Niemann, J., Bean J., Avelar, V: Economizer modes of data center cooling systems, APC White Paper#132