Installation Instructions Model SNC Serial Network Card for USB Application with Windows

Similar documents
Installation Instructions Model NIC-C

Installation Instructions Model ZAM-180

FireFinder. (NCCXP/W7-G/-GL and NCCXP/W7WAN Version 7.81) and Maintenanc. Siemens Industry, Inc. Building Technologies Division Florham Park, NJ

Installation Instructions Model FMT

Installation Instructions Model RNI

Installation Instructions Model PSX-12

The Model Scalance X204-2 Multimode and X204--2LD Single

Installation Instructions Model PSC-17C

INSTALLATION INSTRUCTIONS Model VCA2002-A1 Card Cage

Cerberus Division. Installation Instructions CERBERUS PYROTRONICS TM Model RDM-MXL. (Remote Diagnostics Module)

INSTALLATION INSTRUCTIONS Model VCC2002-A1 Voice input/output Card

and Network Interface Modules Installation Instructions

Installation Instructions Models CC-5 / CC-2

Installing the DX LCD Display

Installation Instructions Model LPB

INSTALLATION INSTRUCTIONS Model VTO2001-U2/U3 Option Module (24 Switches)

MXL / MXLV Rack-Mount Fire-Alarm Equipment

APPENDIX FOR AccuLINK (CSG-M) Revision 17.01

INDUSTRIAL POE SWITCH

Installation Instructions Models FCM-6 / LCM-8 / SCM-8 Model CSB

NFS NFS-3030 NFS2-640 NFS-640 NFS-320 NCA NCA-2 DVC-EM ONYXWorks

RS-422/485 PCIe Card

RS-422/485 PCI Card User Manual Ver All brand names and trademarks are properties of their respective owners.

4100/ VDC Converter Installation Instructions

LED Maintenance Instructions

4100/4120-Series and 4010ES Relay Modules Installation Instructions

Cisco ONS CL Shelf Assembly Hardware

EP/2 Installation Instructions

Megatouch FORCE Monitor Chassis Board Replacement

Manual Documentation Number EIR418-2SFP-T 0912m

USER MANUAL MODEL 2017P MODEL 2017P60. RS-232 to 20mA and. RS-232 to 60mA Current Loop Converters

EasySYNC Ltd. USB to Serial Converters Manual

PCI-36C QUICK INSTALLATION GUIDE

Installation Instructions

Product Manual. USB to Optical Adapter Industrial Isolated RS- 232/422/485. Coolgear, Inc. Version 2.1 December 2018 Model Number: USB-COMi-Si-M

CONTENTS. 1. Motherboard installation Install 3½ and 5¼ drives Install PCI components Connect case leads to motherboard...

TEC VAV with 0-10V AO Heat. Modulation and CO2 Monitoring. Controller. Control Applications. Product Description. Accessories.

Quadrature Encoder User's Manual. Specification and Installation Guide. NetLinc, TLAser400 & PTRBe. Oct 2015

INSTALLATION INSTRUCTIONS. ACB-100 Audio Control Board. This document describes the installation procedure for the ACB-100 Audio Control Board.

Installing the H2 -EBC(100), H2 -EBC -F or H4 -EBC( -F)

4100/4120-Series Class A / Class B Zone Modules Installation Instructions

EasySYNC Ltd. USB to Serial Converters Manual

CAB-BATT, CAB-BATT-R, CAB2-BB, CAB2-BD, CAB3-BB, CAB3-BD, CAB-MP, ID-MP, ID-SP, ID-FP, BCM, OD-LP, OD-BP, OD-GP, REMBOX2, REMBOX4, XLS-MLE6-ADPT,

DMC2. Installation Guide Version 1.0. Area for main photograph. Area for insert photo. W: 46.1mm up to 79 mm H: 46.1mm

This Datasheet for the IC670ALG310. Analog Output Voltage, 8 Channel, +/-10V, 0 to 10V.

Room Pressurization Controller Pneumatic Output

Computer Assembly (Installing Mother Board & CPU)

Videum Duo & Quattro Xpress

QTech 3G Cellular Modem CM910. Quick Start Guide

Room Pressurization Controller Electronic Output

MXL/MXLV 19 Rack Mount Fire Alarm Equipment Models: MXL-RK1, ACM-RK, MKB-RK, MMB-RK, MOM-RK, MPS-RK, TSP-RK, VSM-RK, CABLES-RK, MKB-3

How To Install: C4000 EMV Upgrade Kit

EP-ELVCTL Elevator Control (NION-16C48M)

Page

TSMIU Wireless Bridge Installation and Configuration

Data Isolation Cards. ADSL High Voltage Isolation Card. Single Line Voice Isolation Card With CID, CW & MWI. Floated 130VDC or 120VAC Input P30121

USB-COMi-TB USB to Industrial Single RS-422 / 485 Adapter Manual. Specifications and Features

Quick Start. This document describes how to install the Juniper Networks PTX5000 Packet Transport

Open Desktop WorkStation System Components Items Labeled in RED are ESD Sensitive

USER MANUAL. RC-54DL KNET Auxiliary Control Panel MODEL: P/N: Rev 2

Chapter 3 Installation

ABB Drives. User s Manual Modbus Adapter Module FMBA-01

E2460GS Oscilloscope Upgrade Kit

CHASSIS INSTALLATION GUIDE

PIX 515/515E. PIX 515/515E Product Overview CHAPTER

3710 ACM 3750 PDC 3800 RTU. ISOCOM Communications Card Retrofit Instructions

Siemens TEC Extended I/O Controller

MXL / MXLV Enclosures & Equipment

Series 3700 Screw Terminal Assemblies Installation Instructions

Total Reach ISDN/DDS Isolation Card P30101

ME778C-RJ45 MAIN MODULE (FRONT CARD) MAIN MODULE. Line: RJ-45. Line: RJ-45 INTERFACE MODULE (REAR CARD) Serial: 10-Pin RJ.

Product Manual. 2 Port USB to RS-422 /485 Optical Isolated Adapter. Coolgear, Inc. Version 1.1 March 2018 Model Number: USB-2COMi-Si-M

Sure Coat Modular Gun Control System Part C: UCS ProfiBus Interface Card. Customer Product Manual Part B

Replacing the SATA PCI Controller Card

Quick Start Installation Guide

CyberSerial Dual PCIe-DB Quick Installation Guide

Quick Start Guide MC-III TM Flow Analyzer

CO-485USB USB to RS-485 CONVERTER TECHNICAL REFERENCE

INSTRUCTION MANUAL RA 59 RACK ADAPTER. 1) This manual is valid for the following Model and associated serial numbers: MODEL SERIAL NO. REV. NO.

Installation and Configuration Quick Guide R3000. Industrial Dual SIM Cellular VPN Router 2 Eth + 1 RS RS USB Host.

Package Contents. GP Options (Made by Digital)

Computer Assembly Step by Step DRAFT

NFS NFS-3030 NFS2-640 NFS-640 NFS-320 NCA NCA-2 DVC-EM ONYXWorks

PLC Racks IC697CHS782/783

FA-2448 SIX POSITION Filter Wheel

S7999D SOLA Operator Interface Display

Installation & Operation Guide

MEC-COM-M134. User s Manual

Redundant Master Controller Installation Instructions

Page

INSTALLATION INSTRUCTIONS. FST-420 Fiber Station Transceiver

Table of Contents Quick Install Guide page Introduction Safety Rack System Precautions ESD Precautions...

BACnet PTEC Heat Pump Multi-Stage Controller. Control Applications. Product Description. Product Numbers. Warning/Caution Notation

DS1 Isolation Cards. P Wire Card P Wire Card. Description & Installation

Procedure to Upgrade from B&W Maintenance Panel to TIB Color Touchscreen Door in a Working Maxum or Maxum II Analyzer Equipped With a SYSCON2

USER MANUAL. MODEL 1225 ParaLink TM Parallel Short Range Modem. SALES OFFICE (301) TECHNICAL SUPPORT (301)

Hypercable injecteur HPOE - Industrial IEEE 802.3at Gigabit PoE Injector. User Manual. v.1.0 Jun Mail :

7760 LCD Glass Keypad

FPA-1000-V2 Network Cards FPE-1000-NE, FPE-1000-NF, and FPE-1000-NW

Hi-Speed USB 5-Port PCI

Transcription:

Installation Instructions Model SNC Serial Network Card for USB Application with Windows OPERATION The Model SNC from Siemens Industry, Inc. (as shown in Figure 1) is a USB-compliant network card used with the Siemens Management Stations. The SNC allows the user to interface networked MXL and/or XLS fire panels to Desigo CCs/Cerberus DMS and/or NCCs on XNET. The SNC can also provide an interface to WAN components, including the HUB-4 over HNET. An SNC can provide connectivity to either XNET or HNET, or both XNET and HNET using two cards. The SNC may also be used in an FVNET setup inside the VNT. This allows for interfacing HNET and XNET between multiple XLS systems. The SNC provides a supervised RS-485 network connection. The SNC operates in both Style 4 (Class B) and Class X (formerly Style 7). The module fits in any available PCI or PCI Express compliant slot. The card is NOT dependent on the slot connection and the tab is only used for additional support. The tab can be scored off if connectivity problems are encountered. The module comes pre-installed in Management Station computers. Hardware installation instructions for the SNC, when it is not factory installed, can be found in the Physical Installation section of this document. Controls and Indicators The LEDs are located above X1 and are, in top to bottom order. See Figure 1 for more details. LED Color Description NET OK (DS2) HOST OK (DS1) CH A (DS4) CH B (DS5) Green Green Yellow Yellow Blinks to indicate network is receiving data. Blinks to indicate data to transmit. Blinks* to indicate individual Channel A select. Blinks* to indicate individual Channel B select. * If LED is steady, indicates a Class X (formerly Style 7) fault on that channel. Siemens Industry, Inc.

NET OK HOST OK CH A CH B DS2 DS1 DS4 DS5 X3 1 2 3 4 5 1 5 TB1 SNC S1 RESET S2 SIDE VIEW Figure 1 SNC Module Board CONFIGURATION The SNC is assigned to a standard COM port by Windows when the drivers are installed. The drivers usually come pre-installed in NCC for other computers (Desigo CC/Cerberus DMS). The SNC driver installations are covered in the Driver Installation section of this document. The COM port assigned to the SNC can be viewed in the Windows Device Manager. One SNC card occupies one COM port. On Windows XP systems, the used COM port will be the first (or lower) numbered port assigned for the SNC card. On Windows 7 systems, the used COM port is the USB serial port assigned with the FTDI driver available. The Device Manager is accessible in Windows as follows: WINDOWS 7 Open the Start menu, and then click Control Panel; this will open a new window on the Desktop, showing the Control Panel options. The Address bar of the Control Panel window should end with the Control Panel location, followed by a right-arrow. Click the right-arrow to display the available additional locations, and then select and click All Control Panel Item. On the updated screen, select and click Device Manager. 2

Figure 2 shows a sample Windows 7 Device Manager view and a typical assignment of COM ports on a PC with two SNC boards installed (COM13 and COM14). The port assignments for the SNC are labeled USB Serial Port, once installed and under Properties, the FTDI driver is identified. Figure 2 Device Manager View The port assignment can be changed to agree with any port assignment at the time of install or update. Either board can handle XNET and either board can handle HNET. There is no difference in the boards. However, XNET and HNET are different protocols, so HNET wiring should go to the board with the COM port assigned to HNET and, likewise, XNET wiring should go to the board with the COM port assigned to XNET. 3

PHYSICAL INSTALLATION NOTE 1: Remove all Windows PC power before installation. NOTE 2: The SNC connects to the motherboard internal USB2.0 connector via a cable harness provided (see Step 7 below). On most motherboards, the USB2.0 header/pin-out consists of nine pins arranged in two rows which allows for two USB connections. Normally, but NOT always, the pins for USB1 and USB2 are in separate rows as shown below. TYPICAL PIN ASSIGNMENTS Pin 5 S-GND is also colored black and it is NOT required. When the cable assembly provided is connected to the 4-pins row, simply leave the S-GND position unplugged. On some motherboards, 10 pins (2 x 5) or 8 pins (2 x 4) headers may be present. Connect as shown above. NOTE: USB2.0 connectivity verified for Comark 2 nd and 4 th generation motherboards. WARNING: The SNC only interfaces with motherboards that use the internal USB2.0 connector as shown above. Other motherboard s connections are NOT compatible. Verify its pin assignments before use. To install the SNC in a computer in which it is not factory installed, follow the steps listed below: 1. Unscrew the two knurled knobs on the rear of the computer (computer enclosure may have different physical characteristics). 2. Slide the cover back an inch or so and lift it off. 3. The SNC installs into any free PCI or PCI Express compliant slot in the computer. Select a slot and remove the blank cover, keeping the screw. NOTE: The card is NOT dependent on the slot connection and the tab is only used for additional support. The tab can be scored off if connectivity problems are encountered. 4. Remove the terminal block from the SNC by removing the two screws that hold it to the bracket. 5. Place the SNC into the open slot so that the SNC card edge extends through the opening in the back of the PC. 6. Align the SNC with the card edge connector in the computer and press it firmly into place. 7. Connect the SNC (via X3 connector) to the mother board internal USB connection with the cable harness, P/N A5Q00070675, provided. 8. Secure the SNC by installing the screw that held the blank cover (Refer to Step 3). 9. Replace the computer cover and tighten the knurled knobs (or equivalent). 10. Reattach the terminal block by sliding it onto the SNC card edge and install the two screws. This is a keyed connection and will only install one way. 11. After the SNC is installed, install the SNC drivers following the instructions in the Driver Installation section of this document. 4

ELECTRICAL CONNECTIONS The HNET/XNET connections are made on terminals 1-4 of the terminal block on the front of the SNC (see Step 4 in Physical Installation). The primary pair (or network A) is on terminals 1 and 2. The secondary pair (or network B) is on terminals 3 and 4. Install a 120 ohm EOLR, P/N 140-820350, on terminals 1 and 2, as well as terminals 3 and 4. For Style 4 networks, connect only the primary pairs (Network A). For Class X (Formerly Style 7) networks, connect to both the primary (Network A) and secondary (Network B) pairs. Network (XNET) See Figure 3 for wiring details. Network (HNET) See Figure 4 for wiring details. Network (HNET-VNT) See Figure 5 for wiring details. 5

PAIR A POWER LIMITED PAIR B (OMIT FOR CLASS-B/STYLE 4) POWER LIMITED TO ADDITIONAL NIM-1Rs, NIM-1Ws, SNCs OR NIC-Cs 1 2 3 4 5 6 7 8 1 2 3 4 5 9 10 11 12 13 14 15 16 SEE NOTE 8 NIC-C (MUST BE IN SAME ENCLOSURE AS THE PMI) ONE SLOT OF CC-5 SNC LOCATED INSIDE NCC/DESIGO CC/CERBERUS DMS/VNT NOTE: IF THE NCC/DESIGO CC/ CERBERUS DMS/VNT IS LOCATED AT THE END OF THE XNET NETWORK, INSTALL EOLR P/N 140-820350 ACROSS TERMINALS 1 & 2 AND 3 & 4 1 2 3 4 NIM-1R / NIM-1W MOM-4 TB3 OR TB4 17 18 19 20 21 22 23 24 Figure 3 SNC XNET Connections Refer to the Wiring Specification for MXL, MXL-IQ and MXLV Systems, P/N 315-092772 revision 6 or higher, for additional wiring information. NOTES: 1. No EOLR required for NIC-C. 2. The screw terminals can accommodate one 12-24AWG or two 16-24AWG. 3. From the SNC to NIM-1R, NIM-1W or SNC: 80 Ohms max. per pair. Unshielded twisted pair -.5µF line to line Shielded twisted pair -.3µF line to line,.4µf line to shield 4. From the SNC to NIC-C: 2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s. Unshielded twisted pair.25µf max. line to line Shielded twisted pair.15µf max. line to line.2µf max. line to shield 5. Use twisted pair or twisted shielded pair. 6. Terminate shields at one end only. 7. Power limited to NFPA 70 per NEC 760. 8. CC-5 terminals 9-14 are not connected and can be used to tie shields together. 9. Positive or negative ground fault detected at <10K ohms on pins 3-4, 7-8 of the NIC-C. 10. Each pair independently supervised. 11. Maximum voltage 8V P-P. 12. Maximum current 75mA during message transmission. 6

* * EOLR 120 OHMS, 1/2W, 5% P/N 140-820350 * NETWORK A (PRIMARY) NETWORK B (SECONDARY) OMIT THIS PAIR FOR STYLE 4 1 2 3 4 5 6 7 8 NETWORK A (PRIMARY) SNC 9 10 11 12 13 14 15 16 NIC-C ONE SLOT OF CC-5 Figure 4 SNC HNET Connections NOTES: 1. The screw terminals can accommodate one 12-24AWG or two16-24awg. 2. From the SNC to NIC-C: 2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s. Unshielded twisted pair.25µf max. line to line Shielded twisted pair.15µf max. line to line.2µf max. line to shield 3. Use twisted pair or twisted shielded pair. 4. Terminate shields at one and only one NIC-C. 5. Power limited to NFPA 70 per NEC 760. 6. Maximum voltage 8V P-P. 7. Maximum current 75mA during message transmission. 8. Each pair independently supervised. 9. Positive or negative ground fault detected at <10K ohms on pins 1-2, 3-4, 5-6, 7-8 of the NIC-C. 7

* * EOLR 120 OHMS, 1/2W, 5% P/N 140-820350 * NETWORK A (PRIMARY) NETWORK B (SECONDARY) OMIT THIS PAIR FOR STYLE 4 * * EOLR 120 OHMS, 1/2W, 5% P/N 140-820350 * NETWORK A (PRIMARY) 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 SNC 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 SEE NOTE 7 SEE NOTE 7 SEE NOTE 7 FIRST NIC-C LAST NIC-C ONE SLOT OF CC-5/CC-2 ONE SLOT OF CC-5/CC-2 ONE SLOT OF CC-5/CC-2 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 17 18 19 20 21 22 23 24 Figure 5 SNC-HNET-VNT Wiring on FCC Only NOTES: 1. The screw terminals can accommodate one 12-24AWG or two16-24awg. 2. From the SNC to NIC-C: 2000 feet (33.8 ohms) max. per pair between CC-5s/CC-2s. Unshielded twisted pair.25µf max. line to line Shielded twisted pair.15µf max. line to line.2µf max. line to shield 3. Use twisted pair or twisted shielded pair. 4. Terminate shields at one and only one NIC-C. 5. Power limited to NFPA 70 per NEC 760. 6. Maximum voltage 8V P-P. 7. Maximum current 75mA during message transmission. 8. Each pair independently supervised. 9. Positive or negative ground fault detected at <10K ohms on pins 1-2, 3-4, 5-6, 7-8 of the NIC-C. 10. For Style 4, remove jumper P2 on all NIC-Cs except on the NIC-C that is connected to the SNC card. For Class X (Formerly Style 7), remove jumpers P2 and P4 on all NIC-Cs except on the NIC-C that is connected to the SNC card. 8

Shields Shields for the XNET/HNET must be connected at ONE end of the network. Earth Ground A good earth ground must be provided for proper transient protection of the SNC and the computer. Connect a separate ground to terminal 5 on the SNC. See Figures 3, 4, or 5 as applicable. Ground Fault Detection The SNC provides electrical isolation between the NCC or Desigo CC/Cerberus DMS computer and the XNET. This allows for ground fault detection to be enabled on the XNET. Ground fault detection is only possible if ALL NCC or Desigo CC/Cerberus DMS computers in the system are connected to XNET with a SNC (or NCC-1F and NCC-2F for existing NCC systems). Ground fault detection must be enabled at a NIM-1R/-1W or NIC-C. Select one NIM-1R/ -1W or NIC-C in the system where the ground fault is to be detected. You must locate the NIM-1R/-1W in a cabinet with either an MMB, SMB or a PSR-1. See Figure 6 for the wiring diagram. If the XNET is divided into multiple sections of copper wire using fiber optic segments, ground fault detection can be enabled at one NIM-1R/-1W or NIC-C for each section of copper wire. Refer to the NIC- C Installation Instructions, P/N 315-033240, if you wish to use the NIC-C to provide ground fault detection. For ground fault detection on HNET systems, refer to the NIC-C Installation Instructions, P/N 315-033240. 12 13 14 15 16 TB3 NIM-1R/-1W IN TB3 MOM-4 TB5 2 1 _ + USE ONLY ONE 12 13 14 15 16 TB4 NIM-1R/-1W IN TB4 MOM-2 TB7 TB4 1 1 2 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 _ + Figure 6 Wiring for Ground Fault Detection (XNET) 9

DRIVER INSTALLATION The drivers usually come pre-installed in NCC computers. In case the drivers need to be installed in another computer, follow the instructions below. The products which utilize the SNC cards run on Microsoft Windows7 operating system (OS). When a PC with an SNC card is first started, the card is detected by Windows. Windows Installation The installation of SNC drivers begins by properly installing the SNC into the computer as indicated previously in the Physical Installation section. Afterwards, follow the procedure below: 1. Go to your authorized Siemens website, https://iknow.ww004.siemens.net/infolink/fire%20safety/fire%20safety.htm (Branch), or https://extranet.w3.siemens.com/buildingtechnologies/partner/fsusen/techs/techsupport (VAPs), and download the file: CDM20828_setup.exe (Driver provided by FTDI Chip Limited) 2. Double click the CDM20828_setup.exe file to install the driver. 3. Go to PC Start Menu > Settings > Control Panel > System > Hardware > Device Manager > Ports. Listed is the USB Serial Port. Write down the COM port number for future reference. 10

NRC BASED XNET CONNECTION When an NCC or Desigo CC/Cerberus DMS connects to a NRC-based XNET network of FireFinder-XLS products, the SNC card requires additional interface hardware. In such an installation, the SNC card connects to a NIC-C module, which in turn is connected to a dedicated NRC module. Connect a NCC or Desigo CC/Cerberus DMS to an XLS network system (rev. PMI07.00 or higher) using NRC network cards instead of a NIC-C as described in the following information. Add a separate CC-2 or CC-5 card cage to one node on the XLS network system. Connect this cage to the XLS network system node using a 60-pin ribbon cable (BCL). At the added CC-2 or CC-5 card cage, add and secure into connector P1 an Interface Isolation Card (IIC) (refer to Installation Instructions, P/N 315-050328.) Plug the other end of the 60-pin cable into the male ribbon cable receptacle on the IIC. Insert another NRC and a NIC-C into this isolated card cage. Do not enter these cards into the Zeus configuration for this node or for the network system. Only the NCC or Desigo CC/Cerberus DMS is added to the Zeus configuration as a network node. Note that this NRC is another (second NRC) card required for communicating with the NCC or Desigo CC/Cerberus DMS. Wire the NRC so that it is inserted into the XLS network ring. Refer to the NRC Installation Instructions, P/N 315-050337. Connect the SNC to the NIC-C as shown in Figure 7 and 8. Connect Pair A for Style 4 and Pairs A and B for Class X (formerly Style 7). Address the NIC-C at address 003. FROM PREVIOUS NRC TO NEXT NRC TO NCC/DESIGO CC/CERBERUS DMS STYLE 4/CLASS X (FORMERLY STYLE 7) CC-2/CC-5 60 PIN CABLE FROM PREVIOUS XLS CARD CAGE NRC NIC-C IIC NIC ADDRESS NOT USED SET AT 003 INTERFACE ISOLATION CARD (ISOLATES CARD CAGE SO ONLY POWER IS USED FROM LOCAL NODE) Figure 7 NRC to NCC/Desigo CC/Cerberus DMS Card Cage Connections 11

PAIR B POWER LIMITED FROM NRC IN LOCAL XLS B1 A1 B2 A2 TO NEXT NRC PAIR A POWER LIMITED 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 SNC 9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16 NRC NIC-C ONE SLOT OF CC-5 ONE SLOT OF CC-5 Figure 8 NRC XNET to SNC Connections ELECTRICAL RATINGS All connections are supervised and power limited unless stated otherwise. Input Voltage: 5V (from USB) Input Current: 80mA Max 12

Cyber security disclaimer Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are important components of a comprehensive security concept. It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is customized to individual security needs. Such a security concept may result in additional sitespecific preventive action to ensure that the building comfort, fire safety, security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc. For additional information on building technology security and our offerings, contact your Siemens sales or project department. We strongly recommend customers to follow our security advisories, which provide information on the latest security threats, patches and other mitigation measures. http://www.siemens.com/cert/en/cert-security-advisories.htm 13

THIS PAGE HAS BEEN LEFT INTENTIONALLY BLANK. Siemens Industry, Inc. 8 Fernwood Rd. Florham Park, NJ 07932 Siemens Canada, Ltd. 1577 North Service Road East Oakville, Ontario L6H 0H6 Canada Document ID P/N A5Q00068394