University of Strathclyde

Similar documents
University of Strathclyde

Power Networks Demonstration Centre

IDE4L project overview and ANM concept. Distributed automation system

emegasim Real-Time Digital Simulator: A Unique Smart Grid Lab and Energy Storage Bed at Newcastle University Success Story

Real-Time Hardware-in-the- Loop Co-Simulation Platform for Microgrid Analysis

Alarming and Operations of openpdc at ISO-NE

Power System Network Simulator (PSNsim)

Microgrid Testbed. Rein in microgrid complexity. With ease.

Teleprotection with MPLS Ethernet Communications - Development and Testing of Practical Installations

Control, Protection, and Realtime Simulation of Microgrids

PSC 2014 CLEMSON UNIVERSITY

Integrated Smart Grid Performance Testing: NIST Research and SG Testbed

Demonstration Test Bed for Advanced Control Systems

Blair, Steven Macpherson and Booth, Campbell (2013) Real-time teleprotection testing using IP/MPLS over xdsl. [Report], Strathprints

p. 1 p. 9 p. 26 p. 56 p. 62 p. 68

Reason DR Manager Reason Digital Recorders Management and Traveling Wave Fault Location

ACTIVE NETWORK MANAGEMENT FACILITATING THE CONNECTION OF DISTRIBUTED GENERATION AND ENHANCING SECURITY OF SUPPLY IN DENSE URBAN DISTRIBUTION NETWORKS

Cyber Security of Power Grids

BIDELEK SAREAK PROJECT: SMARTER GRIDS FOR BILBAO. Amsterdam, 5th November, 2014

Tait GridLink THE INTELLIGENT CHOICE FOR DISTRIBUTION AUTOMATION. harris.com #harriscorp

Benefits, offering and references

Technical Spotlight DEMO6-S6

Validating Secure and Reliable IP/MPLS Communications for Current Differential Protection

Voltage Regulated Distribution Transformer

Smart Grid Communications. WFCS 2016 May 3-6, 2016, Aveiro, Portugal

Teleprotection with MPLS Ethernet Communications - Development and Testing of Practical Installations

Disclaimer Executive Summary Introduction Overall Application of Attachment Generation Transmission...

POWER GRID AUTOMATION. Pág.. n. RMU Automation

Achieving Smarter Grid Operation With On-Line DSA Technology

PMU Time Source Security

PMU Communication Network Analysis

Resilient Smart Grids

IEC unites low-and medium-voltage

Next Generation Scada Architectures

Metrology and Tools for Interoperability Testing of Precision Time Protocol (PTP) in Power Systems Communication Networks

Catching Falling Conductors in Midair Detecting and Tripping Broken Distribution Circuit Conductors at Protection Speeds

Smart grid control based on heterogeneous communications and adaptive layers

DRTS-DRTS Link for Distributed Real Time Simulation. Dr. Rob Hovsapian

Energy Systems Integration

Synchrophasors and Next Generation Energy Management Systems (EMS)

INCREASING electrical network interconnection is

SCE WASAS Combined Disturbance Fault Recorder (DFR) and Phasor Measurement Unit (PMU) Specifications. Anthony Johnson

Technology Innovation Delivering Value to BPA Organized, Disciplined, Focused

Solving the challenge

Holistic Assessment of Cyber-physical Energy Systems Facilitated by Distributed Real-time Coupling of Hardware and Simulators

Evaluation of different solutions of faulted phase earthing technique for an earth fault current limitation

Data and Forecasting Summary

LineScope. Smart Power Monitor. Bulletin DB50C18. US Patent Nos , , and B2

Transformer Protection and Control RET630 Numerical transformer protection in medium voltage networks

How smart can the grid really be?

Real Time Requirements and Closed-Loop Testing of Wide Area Protection and Control Schemes

Est Constant Current Regulator MC4 3kW 30kW

Advanced Monitoring Solutions for Critical Electric Power Transmission & Distribution Assets

Transmission Infrastructure Investment & Development in Vietnam

Minimising the Impact of Disturbances in Future Highly-Distributed Power Systems

Schneider Electric Easy UPS 3S

Measurement Based Dynamic Load Modeling in Power Systems

ATV310HU30N4E variable speed drive ATV310-3 kw - 4 hp V - 3 phase

Socomec Netys PR RT U P S TOWER / RACK MOUNT

Special Publication. Power Quality is the Key. Volkswagen (VW) banks on A. Eberle's PQI-D solution to monitor its grid. We take care of it.

USE CASE 14 CONTROLLED ISLANDING

Third Generation System of the Future

Quantum Chargers Enhanced AC Line Transient Immunity

Voltage control in MV and LV grid Distributed automation solution. Sami Repo Tampere University of Technology, Finland Coordinator of IDE4L project

Schneider Electric Easy UPS 3S

Business continuity made easy

ATV310H075N4E variable speed drive ATV kw - 1 hp V - 3 phase

Typhoon HIL604.

An expert solution is within your reach. EORSys. We take care of it.

Cybersecurity Test and Evaluation Facilities at Texas A&M

ATV12P037F1 variable speed drive ATV kW hp V - 1ph - on base plate

Blueprint Data Center

Transmission Distribution Microgrid - DER

2015 The MathWorks, Inc. 1

Wind Plant Systems Grid Integration Plant and Turbine Controls SCADA

MiCOM P220, P225 and P226C

Modernizing Power Grids with Distributed Intelligence and Smart Grid-Ready Instrumentation

Geomagnetic Induced Current (GIC) Mitigation System Summary for the White Paper

Your Power Grid Your Conditions

MGE Galaxy /30/40/60/80/100/120 kva. The recommended power protection for all critical applications.

Smart Power Flow Monitoring and Control

ATV12H018M2 variable speed drive ATV kW hp V - 1ph

Application of Real-time Phasor Domain Simulation for Wide Area Protection in Large-Scale Power Systems

The Efficient Way. SVC PLUS Innovation meets experience. Answers for energy.

HIL POWER SYSTEM RESEARCH FROM SIMULATION TO FIELD DEMONSTRATION Center for Electromechanics University of Texas at Austin

M2M communications architecture for large-scale AMI deployments

siemens.com/energy/transformers FITformer REG The adaptable distribution transformer Answers for energy.

9 th Electricity Conference at CMU

Optimal Power System Management with SIGUARD

GRID/PRSHT/MU320/EN/1.2014/GBR/1894 ALSTOM All rights reserved.

Trends in Distribution Automation for Active Distribution Grids. Univ.-Prof. Antonello Monti, Ph.D.

Galaxy VX. From 500 to 1500 kw N+1 Parallel solutions up to 4000 kw 380V / 400V / 415V / 440V. schneider-electric.com/ups

Smart Grid Operations - Combining the Power of Smart Meters and The Control Room ADMS

Real-time Cyber-Physical Co-simulation of Power Grids. Vahid Jalili-Marandi, Ph.D., OPAL-RT Technologies, Montreal, Canada April 2018

Karl Iliev, San Diego Gas & Electric Company

The current state of the electrical grid And the technologies that will enable its transformation

Christian PAYERL, Poznan, 20 th May, 2009 ABB FACTS Grid connection of Wind Farms. ABB Group May 22, 2009 Slide 1

Testing an IEC61850 compliant voltage control algorithm, using a real-time simulation

Electric Power HIL Controls Collaborative

Line Current Differential Protection Using Broadband Power Line Carrier Technology

Transcription:

University of Strathclyde Validation of the EFCC scheme at the Power Networks Demonstration Centre (PNDC) Dr Qiteng Hong, Dr Ibrahim Abdulhadi and Prof Campbell Booth 0

Overview Brief introduction to PNDC Role of PNDC in the testing of the EFCC scheme Testing configurations and test results Wide area mode tests Communication impact tests Local mode tests Key learnings and findings Conclusions and future work 1 1

PNDC what we do? Provide a realistic and flexible platform for the accelerated testing of smart grid innovations PNDC Field Trials PNDC Experiments Demonstration Ideas Knowledge Evaluation & Dissemination Innovation and roll-out 2

Main facilities at PNDC 11 kv system Urban cables Overhead lines Main facilities at PNDC 500 kva Triphase converter Mock Primary substation Load impedance banks and LV MG network set Control 6-rack room RTDS http://pndc.co.uk/ 3

Overview of the EFCC scheme Region 1 Wind farms Region 2 DSR Region 3 EFCC scheme PV Fast, coordinated response closest to the disturbance PMUs Energy storage CCGT 4

Role of PNDC in the EFCC project Tests at the University of Manchester: EFCC controllers connected to pure simulated signal sources Tests at the University of Strathclyde (PNDC): Controllers interfaced with physical network and an actual PMU unit Both wide-area and local back up modes are tested Performance of the EFCC scheme evaluated under different communication quality conditions 5

Wide area mode test setup: Simulated resource IEC 61850 GOOSE RA1 LC1 RA2 Wide Area Communication Network LC2 Resource information RA3 IEEE C37.118.2 Emulated CS PMUs P-HiL synchronisation PMU Modbus Physical PMU PNDC resource 6

PNDC setup Running RTDS Communication emulator EFCC controllers Configuration using IEC 61850 PMU Injection using amplifier Straton and PhasorPoint Communication switch 7

Wide area mode test cases: 2025-2026 About 100 GVAs Most common inertia level: 220 GVAs 2016-2017 49.65 Hz 49.25 Hz 8

Wide area mode test cases: Region 1 Region 2 Region 3 PMUs LC1: 300 MW (Battery) Event 1 (Scotland) Event 2 (England) Inertia level: 100 GVAs Event: loss of generation Size: 1000 MW Testing effectiveness of fast frequency response from EFCC Evaluating EFCC s response to events at different locations LC2: 300 MW (Demand) 9

Case 1: 1 GW loss, Region 1 (LC1 location), 100 GVAs Frequency (Hz) Local RoCoF (Hz/s) Event detection LC1: closer to the event LC2 Power command (MW) Resource Power (MW) 10

Case 1: 1 GW loss, Region 1 (LC1 location), 100 GVAs 49.47 Hz 49.19 Hz Frequency measured in RAs Comparison: with and without EFCC response 11

Case 2: 1 GW loss, Region 3 (LC2 location), 100 GVAs Frequency (Hz) Local RoCoF (Hz/s) Event detection LC2: closer to the event LC1 Power command (MW) Resource Power (MW) 12

Case 2: 1 GW loss, Region 3 (LC2 location), 100 GVAs 49.49 Hz 49.23 Hz Frequency measured in RA Comparison: with and without EFCC response 13

Communication tests Aimed at evaluating the impact of communication performance of the operation of the EFCC scheme EFCC tested under different levels of latency (delay), jitter (variation in delay), loss of packet, bit error rates, etc. 14

Impact of communication latency (delay) Link1: 77ms Link1: 78ms Link2: 78ms RA1 RA2 Link1 Link2 LC1 RA3 Link 3 Maximum tolerable latency 78ms for 100ms buffering window Latency larger than the limit will lead to packets being discarded, i.e. risking in loosing wide-area visibility 15

Probability Impact of communication jitter Jitter is the change in communication delay Higher jitter levels could lead to higher risks of the violating maximum tolerable latency limit Max tolerable latency limit: 78ms Mean latency: 60ms Normal distribution of latency level Probability of latency larger than the max limit 16

RoCoF Quality Conf Level Latency with jitter tests RA1 Link1 RA2 Link2 LC1 Link1: 12ms Link1: 14ms Link1: 16ms RA3 Link 3 Mean latency: 50 ms Link2: 12ms Link3: 12ms Link2: 14ms Link3: 14ms Link2: 16ms Link3: 16ms Gradually increase latency level in three communication links to LC1 LC1 capable of handling of the jitter level with expected RoCoF measured 17

EFCC operation with mean latency 60 ms and 18 ms jitter Loss of Packets/delay exceeding threshold Frequency (Hz) RoCoF (Hz/s) Event detection Power command (MW) 18

Local mode operation: Local mode: used when wide-area connection is lost or data quality is not sufficiently high for wide-area operation mode Acting as backup mode only using local measurement Test setup: Motor-Generator (MG) set controlled to emulate frequency disturbances Actual faults are also applied in the physical network PNDC network 19

Under-frequency event : 49.7Hz 49.6Hz 49.5Hz Frequency RoCoF Event detection Positive response Response Load reduction Load level 20

Fault tests: Actual faults have been applied in the physical network Testing the LC s capability to remain stable to the faults Fault resistors Fault types tested: Ph-E Ph-Ph Ph-Ph-E 3Ph-E Fault thrower Fault control 21

Fault tests in local mode: 3Ph-E fault Associated settings Voltage threshold: 80% Event detection RoCoF threshold: 0.1Hz/s Event detection frequency threshold: 49.7 Hz 80% threshold Frequency RoCoF Voltage Fault detection Fault details Bolted fault Fault duration: 150ms Event detection Response 1 2 3 22

Key learnings and findings Wide area mode tests: Location of disturbances and the response power both have impact on the frequency profiles electrical distances and regional inertia. Frequency and RoCoF are different at different parts of the network, thus important to have wide-area visibility for fast frequency control Fast frequency response: more effective compared to the same volume of conventional primary response RoCoF measurement can be significantly different with different PMUs, so testing the scheme using actual PMU in physical network before actual implementation is essential EFCC scheme capable of instructing fast, coordinated response in the tests effective in enhancing frequency control in a low-inertia system 23

Key learnings and findings Communication tests: Size of data buffering window directly determines EFCC s capability to handle degraded communication performance Increasing buffering window can mitigate the risk of loosing packets, but can compromise the response speed At the PNDC tests, the requirements for communication performance has been quantified EFCC scheme appears to be robust in degraded communication conditions Local mode tests: Essential in case of wide area communication failure Action should be slower compared to wide area mode due to lack of wide-area visibility 24

Conclusions and future work PNDC s role: comprehensive validation of the EFCC scheme using the established realistic testbed The EFCC scheme have been tested under a wide range of operating conditions and disturbances o o o wide area mode impact of communication performance local mode as backup EFCC scheme capable of instructing fast and coordinated response to enhance frequency control in low-inertia systems Future work o o finish wide-area mode and communication tests knowledge dissemination 25

26