Softstarters. Type PSTX Fieldbus communication, Anybus Modbus TCP. 1SFC132087M0201 March SFC132087M0201 1

Similar documents
Softstarters. Type PSTX Fieldbus communication, Fieldbus Plug Modbus RTU

Softstarters. Type PSTX Fieldbus communication, Anybus EtherNet/IP

Softstarters. Type PSTX Fieldbus communication, Fieldbus Plug Modbus RTU. 1SFC132092M0201 June SFC132092M0201 1

Softstarters. Type PSTX Fieldbus communication, Fieldbus Plug Profibus DPV0/DPV1. 1SFC132091M0201 June SFC132091M0201 1

Softstarters Type PSTX Fieldbus communication, Anybus CompactCom DeviceNet

Softstarters. Type PSTX Fieldbus communication, Anybus CompactCom PROFINET. 1SFC132094M0201 June SFC132094M0201 1

Softstarters. Type PSE Fieldbus Communication Fieldbus Plug DeviceNet. 1SFC132066M0201 January SFC132066M0201 1

Softstarters. Type PST/PSTB Fieldbus communication DeviceNet for PST sw CU SFC132072M0201 February SFC132072M0201 1

Softstarters. Type PST/PSTB Fieldbus communication Profibus DP V0 / V1. 1SFC132013M0201 January SFC132013M0201 1

Optidrive Applications Support Library

Optidrive Applications Support Library

Instructions. Modbus RTU Card (WSIQ-COM-MB)

E2 Modbus RTU Register Map Revision History Version Comments Author Date 1.02 Previous version PAE 11/06/ Revised to new format PAE 09/03/09

MODBUS RTU MODULE INSTRUCTIONS. for use with WSIQ2/WSE

Copyright: December 2017 Nidec Issue: E

Power Xpert C445 Motor Management Relay Cheat Sheets

E2 Modbus RTU Register Map

RSGD 75mm Modbus Protocol

Optidrive VTC Modbus RTU Register Map

1SFC132081M0201. Softstarters Type PSTX30...PSTX1250 Installation and commissioning manual

4 Is this model available for special primary current and special primary voltage?

Connect the UMC100.3 to an Allen-Bradley PLC over EtherNet/IP using the EIU32.0

1. Introduction. 2. Installation MODBUS INTERFACE

MCD 200 MCD 500. Remove the Profibus Module using the following procedure: 1. Remove power from the module.

Copyright: December 2017 Nidec Issue: E

Profinet Module. User Manual. Contents

ABB LVP&S Training AC500 to EMAX Modbus RTU ABB Automation Technologies

Universal Motor Controller UMC22-FBP. Excellent motor protection and control ATEX ABB

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

3GV M Modbus RTU Register Map

1SFC132081M2201 EN, Rev C. Softstarters Type PSTX30...PSTX370 Installation and commissioning manual

It is the installer's responsibility to follow all instructions in this manual and to follow correct electrical practice.

Overview This section describes how to use the LTM R controller via the network port using the Modbus protocol.

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

User Guide. Modbus Module. For Digistart soft starters. Part Number: Issue: 3.

REVO C Serial Communication Manual

PROFINET MODULE. Communications module. User Guide. This manual is to be given to the end user en / a. Power. Error. Status.

Modbus RTU/TCP Installation and Programming Guide PC3400 Particle Counter

SMART RELAY SRW 01 V4.0X

3G3FV SI-P Option Card for Profibus-DP Instructions 02/16/00

Ethernet/IP Module. User Manual. Contents

Real Time Clock with Temperature Sensor and RS485/Modbus Comunications

MODBUS TCP MODULE INSTRUCTIONS. for use with WSIQ2/WSE

CURRENT PROTECTION RELAY SMPR-1

Interface Definition RISH EM 2340/1320/30/ _Rev. D - 8/2016

AC Variable Speed Drive 0.75kW 250kW / 1HP 350HP Volt 1 & 3 Phase. Advanced User Guide Revision 1.10


Motors Automation Energy Transmission & Distribution Coatings. Profibus DP SRW 01. User s Manual

ACS Stepper _10_Modbus LINEAR SOLUTIONS MADE EASY

MODBUS Protocol for MiCOM P30 Series

DNP3 Communications Protocol

PM130 Powermeters Reference Guide Modbus Communications Protocol

Appendix to the Operating Instructions RMx621 with ModBus Interface V Connection to ModBus-IDA System

SAFETY PRECAUTIONS. Throughout this manual we use the following two illustrations to make you aware of safety considerations:

User Guide IM/C250 MOD_3. Modbus (RTU) Communications Option C250 and V250

Emotron Fieldbus HMS Gateway Anybus Communicator

CAN-Transceiver Data Register Map MODBUS Slave RTU

Metasys N2 Instruction Manual VLT Adjustable Frequency Drive. 12/ Revision B

SPM33. MODBUS Protocol and register List V1.5

MODBUS APPLICATION MANUAL DFC-0124

CPU ONE PLC PLC USER S MANUAL

INSTRUCTION MANUAL RVT communication How to use RS485 USB Ethernet RVT connections

VERIS H8035 and H8036

DeviceNet Drive Profile CFW-09

G5 Weighing Instrument

Golander Peristaltic Pump MODBUS Communication Instruction

SITRAIN. Introduction TIA Portal. Siemens AG All rights reserved. Unrestricted

Modbus RTU Option Card for VLT 5000/6000 Adjustable Frequency Drive

FC 300 DeviceNet and Allen Bradley Control logix 5550

Tongta Inverter TDS-F8

vacon nx ac drives brake chopper unit (bcu) application user s manual

Conto D1 MODBUS COMMUNICATION PROTOCOL

ModBus Communication protocol. The ModBus protocol is an industrial communications and distributed control system

PROGRAMMING MANUAL IM262R00. AQUAVAR Intelligent Pump Controller START-UP GENIE PROGRAMMING MANUAL

Motors I Automation I Energy I Transmission & Distribution I Coatings. CANopen CFW500. User s Manual

Before using the product, thank you for using our Ethernet module board. Safety Instruction

THERMOSALD ISX RS485 MODBUS (V5) 3E S.r.l. - Via del Maccabreccia 37/a LIPPO DI CALDERARA (BOLOGNA) THERMOREGULATOR for PULSE WELDING

CANopen CFW-11. Communication Manual. Phone: Fax: Web:

Modbus Protocol. for VASCO, VASCO Solar and MIDA devices. manmodbus_eng_00

MPU-32 AND FPU-32 TIA-485 NETWORK

TrueString Gateway MODBUS Map. June 2017 Version 1.01

ECHO Process Instrumentation, Inc. Modbus RS485 Module. Operating Instructions. Version 1.0 June 2010

Chapter 5: Communications 5 1 SR55 Communications Overview 5 2

User Guide Supplement Modbus TM Serial Data Communications Option IM/C100 MOD_6. /8 DIN Process Indicators and Controllers C100, C150, C160 and V100

DT7000 Communication I/O Gateway User s Guide Version 2.6

5800 Series Non-IntelliTEAM Universal Automatic Switch Control PG&E SCADA Points List

MODBUS- Adress-table BR7000-I Version 4.1 (issue 10/16)

FREQUENCY CONVERTER FC102 (QUICK GUIDE)

OPTIDRIVE PLUS 3 GV 3 rd Generation Vector Control AC Variable Speed Drive kW

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

Profibus DP CFW-11. Communication Manual. Phone: Fax: Web:

Motors I Automation I Energy I Transmission & Distribution I Coatings N2 CFW501. User s Manual

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160

D-100 FLOW DISPLAY MODBUS Network Interface Installation Guide

PowerFlex 4 / 40 Custom Firmware

NF760 Batch Controller

GNM3D Series COMMUNICATION PROTOCOL. Version 1 Revision 0

RS-FS-N01 Wind speed transmitter user's Guide (485type)

R1M-GH THERMOCOUPLE & DC INPUT MODULE MODEL. Remote I/O R1M Series. (16 points)

IntesisBox. v.0.1. User Manual Issue Date: 12/2017 r1.3 EN

Transcription:

Softstarters Type PSTX Fieldbus communication, Anybus Modbus TCP 1SFC132087M0201 March 2015 1SFC132087M0201 1

1 Modbus TCP The Modbus protocol is a fieldbus protocol that provides full control and status information of the softstarter, reading as well as writing of parameters. Through the fieldbus it is possible to start and stop the motor, read out currents and frequency, achieve information about protections, warnings, faults and much more. See chapter 8 in the Installation and commissioning manual, document 1SFC132081M0201, for available fieldbus related settings. Before the Modbus RTU can be taken in operation following parameters must be set in the softstarter: Parameter FB interface connector set to Anybus Parameter Fieldbus control set to On The parameters controlling the Anybus IP settings needs to be set to match existing network configuration: o o o o Fieldbus IP address Fieldbus IP gateway Fieldbus IP net mask Fieldbus IP DHCP client Caution! The motor may start unexpectedly if there is a start signal present when doing any of the actions listed below. Switching from one type of control to another (fieldbus control/hardwire control) Reset all Settings 1SFC132087M0201 2

1.1 Digital input telegram To PLC from the softstarter. Word in input data area Digital input byte Bit Data Description 0 0 0 Auto Mode status 1 0 = softstarter control from fieldbus not allowed 1 Event status 0 = No active fault/warning/protection 2 Ready To Start 0 = A start will probably cause a fault, 1 = A start will probably not cause a fault 3 FBT Response 0 See Fieldbus Tasks 4 FBT Response 1 See Fieldbus Tasks 5 FBT Toggle Bit See Fieldbus Tasks 6 Programmable Digital Input 1 Function of programmable digital input, 7 Programmable Digital Input 2 1 8 (0) Programmable Digital Input 3 9 (1) Programmable Digital Input 4 10 (2) Programmable Digital Input 5 11 (3) Programmable Digital Input 6 12 (4) Programmable Digital Input 7 13 (5) Programmable Digital Input 8 14 (6) Programmable Digital Input 9 15 (7) Programmable Digital Input 10 see table 1.2 1) Auto mode reflects the control state of the Softstarter. This is affected by a combination of: The Auto mode input signal from the PLC (Digital output telegram). The state of the Local/Remote switch on the Fieldbus Plug Accessory. The state of the Local/Remote switch on the HMI. The parameter Fieldbus control. The digital input Fieldbus disable. 1SFC132087M0201 3

1.2 Programmable Digital Inputs The functions of the programmable Digital inputs are controlled by the parameters Fieldbus DI 1 through Fieldbus DI 10. The following functions are available for selection: Function Data None Value is set to 0. Start feedback Status of Start signal. Stop feedback Status of Stop signal. Fault reset feedback Status of Reset signal. Slow speed reverse feedback Status of Slow speed reverse signal. Slow speed forward feedback Status of Slow speed forward signal. Start 1 feedback Status of Start 1 signal. Start 2 feedback Status of Start 2 signal. Start 3 feedback Status of Start 3 signal. Motor heating feedback Status Motor heating signal. User defined feedback Status of User defined protection signal. Stand still brake feedback Status of Stand still brake signal. Emergency mode feedback Status of Emergency mode signal. Start reverse feedback Status of Start reverse signal. Run status 1 = Indicates when the softstarter gives voltage to the motor. TOR status Top of Ramp. 1 = Indicates that motor runs on full voltage. Line or Inside Delta Connection 0 = Line, 1 = Delta. Phase sequence 0 = L1, L2, L3; 1 = L1, L3, L2. Event group 0 status 0 = No active events present in group 0. Event group 1 status 0 = No active events present in group 1. Event group 2 status 0 = No active events present in group 2. Event group 3 status 0 = No active events present in group 3. Event group 4 status 0 = No active events present in group 4. Event group 5 status 0 = No active events present in group 5. Event group 6 status 0 = No active events present in group 6. Sequence 1 Run status Run status of sequence connected motor 1. Sequence 2 Run status Run status of sequence connected motor 2. Sequence 3 Run status Run status of sequence connected motor 3. Sequence 1 TOR status Top of Ramp status of sequence connected motor 1. Sequence 2 TOR status Top of Ramp status of sequence connected motor 2. Sequence 3 TOR status Top of Ramp status of sequence connected motor 3. Run reverse status 1 = Indicates when the softstarter gives voltage to the motor after a reverse start. 1SFC132087M0201 4

1.3 Analog input telegram To PLC from the softstarter. All analog data is represented as 16-bit values. A protocol for Fieldbus tasks is used to read and write parameters. It is applicable for all Fieldbuses. Word in input Analog Data Representation data area input word 1 0 FBT Return Value See Fieldbus Tasks 2 1 Programmable Analog Input 1 Function of programmable 3 2 Programmable Analog Input 2 analog input, see table 1.4. 4 3 Programmable Analog Input 3 5 4 Programmable Analog Input 4 6 5 Programmable Analog Input 5 7 6 Programmable Analog Input 6 8 7 Programmable Analog Input 7 9 8 Programmable Analog Input 8 10 9 Programmable Analog Input 9 11 10 Programmable Analog Input 10 1SFC132087M0201 5

1.4 Programmable Analog Inputs The functions of the programmable analog inputs are controlled by the parameters Fieldbus AI 1 through Fieldbus AI 10. The following functions are available for selection: Function Representation None Value is set to 0 Phase L1 current 1 Value = 1000 100A Phase L2 current 1 Value = 1000 100A Phase L3 current 1 Value = 1000 100A Active power (HP) Value = 1000 10hp Active power Value = 1000 10kW Apparent power Value = 1000 10VA Mains voltage Value = 1000 100V Power factor Value = 100 1 Example: 87 0.87 Motor voltage Value = 100 100% Active energy (resettable) Value = 1000 10kW EOL time to trip Value = 100 100s Value = 65535 No overload Value = 0 Trip already occurred Mains frequency Value = 1000 100Hz Max phase current 1 Value = 1000 100A Motor current Value = 1000 100A Motor run time (resettable) Value = 100 1000h Motor temperature Value = 100 100 Motor temperature percent Value = 100 100% Number of starts (resettable) Value = 1 100 Phase sequence Value = 0 L1->L2->L3 Value = 1 L1->L3->L2 Value = 2 No sequence detected PT100 temperature Value = n n/10 50 Example: 750 25 PTC resistance Value = 100 100Ω Reactive energy (resettable) Value = 1000 10kVAr Reactive power Value = 1000 100VAr Remaining time to start Value = 100 100s Thyristor temperature Value = 100 100 Thyristor temperature percent Value = 100 100% EOL time to cool Value = 100 100s Top event code Value = 1000 1000 Motor current in percent of IE. Value = 100 100% Thyristor run time (resettable) Value = 1 10h Motor connection Value = 0 auto Value = 1 In-line Value = 2 Inside delta UI Value = 3 Inside delta IU Value = 4 2-phase L1 shorted Value = 5 2-phase L2 shorted Value = 6 >= 2-phase L3 shorted 1) Phase current L1, L2 and L3 indicate the current through the softstarter, while the Max phase current is always the line current. 1SFC132087M0201 6

1.5 Digital output telegram From PLC to the softstarter. Word in output data area Digital output byte Bit Data Description 0 0 0 Start Commence a start when signal is set. 1 Stop Commence a stop when signal is negated. 2 Fault reset Reset signal for possible events. 3 Auto mode This must be set for controlling the motor. 4 Slow speed reverse Perform slow speed reverse when signal is set. 5 Slow speed forward Perform slow speed when signal is set. 6 Spare 7 Start1 Start1 if sequence start. 1 8 (0) Start2 Start2 if sequence start. 9 (1) Start3 Start3 if sequence start. 10 (2) Motor heating Perform motor heating when signal is set. 11 (3) Stand still brake Perform stand still brake when signal is set. 12 (4) Start reverse Commence a reverse start when signal is set. 13 (5) Spare 14 (6) Emergency mode Set to 1 to enable emergency mode. 15 (7) FBT toggle bit See Fieldbus Tasks. 1 2 16 (0) User defined trip Set to 1 to trigger user defined protection. 17 (1) Switch to remote control Switch to remote control when signal is set (edge triggered). 18 (2) Spare 19 (3) Spare 20 (4) Spare 21 (5) Spare 22 (6) Spare 23 (7) Spare 3 24 (0) Spare 25 (1) Spare 26 (2) Spare 27 (3) Spare 28 (4) Spare 29 (5) Spare 30 (6) Spare 31 (7) Spare 1.6 Analog output telegram From PLC to the softstarter. All analog data is represented as 16-bit values. Word in output data area Analog output word Data Representation 2 0 FBT Control Word See Fieldbus Tasks 3 1 FBT Argument 2 See Fieldbus Tasks 4 2 FBT Argument 3 See Fieldbus Tasks 1SFC132087M0201 7

1.7 Input address map 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 Digital In, Byte 1 Digital In, Byte 0 1 Analog In, Word 0 2 Analog In, Word 1 3 Analog In, Word 2 4 Analog In, Word 3 5 Analog In, Word 4 6 Analog In, Word 5 7 Analog In, Word 6 8 Analog In, Word 7 9 Analog In, Word 8 10 Analog In, Word 9 11 Analog In, Word 10 1.8 Output address map 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 0 Digital Out, Byte 1 Digital Out, Byte 0 1 Digital Out, Byte 3 Digital Out, Byte 2 2 Analog Out, Word 0 3 Analog Out, Word 1 4 Analog Out, Word 2 1SFC132087M0201 8

2 Modbus TCP - A set-up example 2.1 Softstarter PST Modbus TCP communication This document describes an application example between a Modbus TCP master (PLC CPU, PC, etc.) and the ABB softstarter PSTX using the built-in Modbus TCP interface. Please always use the actual softstarter manuals. In this particular example following documents has been used: Softstarter PSTX Installation and commissioning manual, document 1SFC132081M0201 2.2 Settings 1. Set the softstarter address and field bus communication. Change the address of the softstarter to 47 (Fieldbus Address) and enable fieldbus control (Fieldbus control = On). 2. Set the communication parameters. Change the communication parameters baud rate, parity, stop bits to match the Modbus network settings. 3. Select the FBP interface. The previous changes are taken in effect when the fieldbus interface is changed. Change parameter Com3 function to Modbus RTU Slave and change parameter FB interface connector to Modbus RTU. 1SFC132087M0201 9

Slave 47 5FC = 02 2 Byte Byte 0 Byte 1 CRC Slave 47 5FC = 02 Address 16 bit CRC 2.3 Read binary input telegram FC =2 Address: 0000H RTU Anybus Modbus Slave NR.47 Modbus Master Request RTUS485 / Modbus RTU Softstarter Response E.g: Read 16 bit starting at the address: 0000H Request: 2F 02 00 00 00 10 7F 88 Response: 2F 02 02 00 00 51 BE 1SFC132087M0201 10

Slave 47 5FC = 15 Address 16 bit CRC Slave 47 FC = 15 Address 16 bit 2 Byte Output CRC 2.4 Write binary output telegram FC =15 Address: =0000H Modbus Master Request RTU Anybus Modbus Slave NR.47 RTUS485 / Modbus RTU Softstarter Response E.g: Write 16 bit starting at the address: 0000H Request: 2F 0F 00 00 00 10 02 00 00 37 88 Response: 2F 0F 00 00 00 10 52 49 1SFC132087M0201 11

Slave 47 FC = 04 4 Byte W0 W1 CRC Slave 47 FC = 04 Address 2 words CRC 2.5 Read analog input telegram FC =4 Address: 0001H RTU Anybus Modbus Slave NR.47 Modbus Master Request RTUS485 / Modbus RTU Softstarter Response E.g: Read analog output words 2 & 3. Phase L1 current and Phase L2 current with default settings. Request: 2F 04 00 02 00 02 D6 45 Response: 2F 04 04 00 00 00 00 35 86 W0: Phase L1 current W1: Phase L2 current 1SFC132087M0201 12

Slave 47 FC = 16 Address 2 words CRC Slave 47 FC = 16 Address 2 words 4 Byte W0 W1 CRC 2.6 Write analog output telegram FC =16 Address: 0002H RTU Anybus Modbus Slave NR.47 Modbus Master Request RTUS485 / Modbus RTU Softstarter Response E.g: Write analog output words 1 & 2. FBT Control Word and FBT Argument 2. Request: 2F 10 00 02 00 02 04 00 00 00 00 ED 5E Response: 2F 10 00 02 00 02 E6 46 W0: FBT Control Word W1: FBT Argument 2 1SFC132087M0201 13

3 Fieldbus Tasks By using Fieldbus Tasks it is possible to read/write parameters and set the real-time clock. Which task to execute is selected by filling in the FBT Control Word. There are three signals for arguments to the task: FBT Argument 1 is packed together with the Task ID in the FBT Control Word. There are two additional 16-bit arguments in separate analog output signals, FBT Argument 2 and FBT Argument 3. To control when the task is executed, the digital output signal FBT Toggle Bit is changed. The softstarter will detect the change, execute the task, fill in the return values, and toggle the digital input signal FBT Toggle Bit as acknowledgement. Thus, the return values must be disregarded if the two toggle bits have different value. 3.1 FBT Control Word The control word is a 16-bit analog output value sent from the PLC to the softstarter. It consists of a Task ID and an 11-bit argument packed together. 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Task ID Argument 1 3.2 Task ID The task identifier controls which function should be performed. Response ID Task ID Task Positive Negative 0 No task 0-1 Request parameter value 1 2 2 Change parameter value 1 2 3 Set date and time 1 2 3.3 Response ID The response ID is the softstarter response to a task. It tells whether a task was executed successfully. If there was an error, an additional error code is returned in the FBT Return Value analog input. The Response ID is transmitted as two digital input signals, FBT Response 0 and FBT Response 1. Response ID FBT Response 1 FBT Response 0 Explanation 0 0 0 No response 1 0 1 Task executed 2 1 0 Task cannot be executed (with error number) 3 1 1 Reserved. 3.4 Error codes The following error codes are sent when a task cannot be executed. Error code Explanation 0 Illegal parameter number 1 Parameter value cannot be changed 3 Lower or upper limit violated 4 Invalid argument 5 No error 1SFC132087M0201 14

3.5 Request parameter value This task reads the current value of specified parameter. See chapter for parameter number and value scaling. 3.5.1 Arguments FBT Argument 1: parameter number. 3.5.2 Return Value Response ID 1 and parameter value in FBT Return Value on success. Response ID 2 and error number in FBT Return Value on failure. 3.6 Change parameter value This task writes a specified value to a parameter. See chapter for parameter number and value scaling. 3.6.1 Arguments FBT Argument 1: parameter number. FBT Argument 2: parameter value 3.6.2 Return Value Response ID 1 on success. Response ID 2 and error number in FBT Return Value on failure. 3.7 Set date and time This task updates the real-time clock on the softstarter. The date and time fields have the following limits: Year: 0-63 (2000-2063) Month: 1-12 Day: 1-31 Hour:0-23 Minute:0-59 Second:0-59 3.7.1 Arguments FBT Argument 2: year, month, day and least significant bit of seconds 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 s0 year month day FBT Argument 3: hour, minute, seconds, bit 1-5 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 hour minute seconds, bit 1-5 3.7.2 Return Value Response ID 1 on success. Response ID 2 and error number in FBT Return Value on failure. In case the supplied time didn t differ from the set time, error code 5 (no error) is used. 1SFC132087M0201 15

3.8 Parameter numbers and values To access parameters from the fieldbus, a unique parameter number is needed, this can be found in document 1SFC132081M0201, Chapter 7.19 Complete parameter list, Table 5. Since the parameter values need to be represented as integers on the fieldbus while, the parameter values with greater precision need to be scaled. In document 1SFC132081M0201, Chapter 7.19 Complete parameter list, Table 5, there is a column specifying the number of decimals for each parameter. Parameter values that are read from the fieldbus needs to be divided by 10 numbers of decimals. Parameters values that are written from the fieldbus needs to be multiplied by 10 numbers of decimals. For example: The parameter Kick start time has parameter number 24 and 2 decimals. To read this parameter: 1. Set FBT Task ID to 1. 2. Set FBT Argument 1 to 24. 3. Toggle FBT Toggle Bit output and wait for the FBT Toggle Bit input to update. 4. Response ID 1 should now contain value 1, indicating success. 5. FBT Return Value contains the value 50 (this is an example and depends on the actual set value). 6. The return value should be interpreted as 50/10 2 = 0.5s. To change the Kick start time parameter to 1s: 1. Set FBT Task ID to 2. 2. Set FBT Argument 1 to 24. 3. Set FBT Argument 2 to 1*10 2 = 100. 4. Toggle FBT Toggle Bit output and wait for the FBT Toggle Bit input to update. 5. Response ID 1 should now contain value 1, indicating success ABB AB Control Products Low Voltage Products S-721 61 Västerås, SWEDEN www.abb.com/lowvoltage 1SFC132087M0201 16