SENSE Instruments CO., LTD. Production address: # 1515 Chuanqiao RD.Jinqiao Export processing Industrial Zone Pudong New Area 201206 Shanghai China Telefon: +86(21) 5854 0878 Telefax: +86(21) 5899 3196 E-mail: sense.oversea@sen-tek.com sense.oversea@sen-tec.com Internet: Data sheet STK336 Page 1 / 6 Differential Pressure Transmitter STK336 Features and Benefits M NEW Maximum range turndown 100:1 Non-Intrusive Magnetic Controls Backlight LCD display for the dark environment Separate electronics and connection compartments O Housing can be rotated through 330 Excellent stability S Z Application Areas For application in the process engineering Suit for liquids, vapour, or gases Preferred areas of use are: Process engineering chemical industry Technical data Measuring range Code 3S 4S 5S 6S 7S 8S On request Nominal pressure 6KPa 7.5KPa 40KPa 200KPa 700KPa 2000KPa 2100KPa 7000KPa Lower(LRL) -6KPa -7.5KPa Power supply (polarity protected) Supply voltage Output signal 2-wire-system Signal range-4 to 20 ma Signal on alarm Measurement limit Upper(URL) 6KPa 7.5KPa Overload 13MPa Min.operating pressure 0.12Kpa -40KPa 40KPa 13MPa 0.40Kpa -200KPa 200KPa 13MPa 2Kpa -700KPa 700KPa 13MPa 7Kpa -2000KPa 2100KPa 13MPa 21Kpa -2100KPa 2100KPa 13MPa 21Kpa -7000KPa 7000KPa 125% of range 70Kpa 12.5...45 VDC 4...20 ma with superimposed signal for HART protocol digital communication 3.8mA...22.8mA 3.8mA/ 22.8mA/Others on request
Data sheet STK336 Page 2 / 6 Performance Accuracy Static pressure effect Power supply effect Vibration effect Installation position effect Thermal effect Static pressure Stability Switch on delay Cycle time/updater time Damping Response time Self stability configuration Filter configured Electrical protection Insulation resistance Short-Circuit protection Reverse polarity protection Overvoltage protection Intrinsic safety Humidity Ambient and operation Storage Ingress protection Electromagnetic compatibility(emc) Physical specifications Diaphragms Flange Drain/vent valve Media wetted o-rings Electronic housing Flange screws, identification plate Mounting brackets (Option) Sight glass Filling fluid 3S 0.1% accuracy for range trundown 5:1 (0.1+0.01XURL/Span) between 1/5 and 1/50 of measuring 4S...7S 0.075% accuracy for range trundown 10:1 (0.075+0.00751XURL/Span) between 1/10 and 1/100 of measuring 8S 0.2% accuracy for range trundown 10:1 (0.2+0.01XURL/Span) between 1/10 and 1/100 of measuring Zero error: 0.1%/7Mpa Span error: 0.2%/7Mpa Negligible <0.01% of URL /g when tested 200Hz in any axis relative Zero shift which can be calibrated out, no span effect 0.45%/55 30bar...130bar 0.1% of URL/1 year 5s 0.25s 0 to 100s, step: 0.1s 200 ms (without consideration of electronic damping) 0 to 2% 0 to 160 ua >250M Permanent No damage, and no function 500 V Exia Ct4~T6 5...98% -40-100 (without display), -20-100 (with display) -40-85 IP 65 Interference immunity and interference emission according to GB/T17626.2-1998), compliance with IEC 61000-4-3:1995. Stainless steel 316L, Others on request Stainless steel 316 Stainless steel 316 FKM, others on request Die-cast aluminium Carbon steel with Zinc coating Carbon steel with Zinc coating or with painting Laminated safety glass Silicon oil/others on request
Data sheet STK336 Page 3 / 6 Others Display Type Display Range Weight Exploded View Visible range 32.5X22.5mm; 5-digit 7-segment main display, digit height 8mm, 8-digit 14segment additional display, digit height 5mm; 52 bars meter with 2% resolution -1.9.9.9.9. To 9.9.9.9.9. Standard model approx. 3.8kg Certification Label Electronics Housing Nameplate Cover O-ring Electronics Board Cover O-ring Cover Terminal Block Nameplate Cover O-ring Flange Alignment Screw Flange Adapter O-Ring Differential pressure sensor Flange Adapters Flange Bolts
0.0% 0.0% Data sheet STK336 Page 4 / 6 Dimensions Electrical Connection Wiring Diagrams 4-20mA 24V - + 1-5V - + 24V P A + - + 5 4 3 2 1 - + 5 4 3 2 1 1-5V I R - HART Talker RS232 PC Operation The STK336 can be operated in the following ways: Using the three keys above the instrument directly at the mounting point for calibrating zero point and span at the touch of a button. Or Operating remotely using the HART protocols -e.g. via HARTTalker and a PC with the SENSE operating programm HARTTran or -using the PDA Software SENSE offers two configuration software. They can be used the PC and PDA. Operation of push buttons The STK336 can be programmed via three buttons. Following parameters can be adjusted: scaling, decimal point, damping, display model, fix output current, and reset. HART-commnication via HART-protocol the possibility of setting zero and span value is given. HART-communicatin, which can run via PC, note-book, PDA, measured values and parameters become transparent and are available on every step of the signal circuit.
Data sheet STK336 Page 5 / 6 Manual of the Three Keys Manual of the Three Keys ZERO(Z), SPAN(S), MODE(M) OPEN THE LOCK Press<Z>and for 5 seconds then can open the lock. (LCD screen showing :OPEN) 4mA Rerange With Pressure Set the present input to zero reference level, press <Z>for 2 seconds, the transmitter will output 4.000mA.(LCD screen showing: LSET) 20mA Rerange With Pressure Set the present input to span reference level, presskey for 2 seconds, the transmitter will output 20.000mA.(LCD screen showing: HEST) PV=0 Set the transmitter under the atmosphere, press <Z>and keys for 2 seconds. it can get PV=0. (LCD screen showing :PV=0) NOTE: If the PV/RANGE>0.5, it can not get PV=0. LCD screen showing PVER RESET Turn off the power, Press <Z>, then turn on the power to the transmitter, continue to press<z> for 5 seconds, if LCD screen shows OK, the transmitter get reset. NOTE: If LCD screen shows FAIL, the transmitter can not get reset (Maybe because the data has not been backup to the transmitter in factory ). MODE configure low range value <Z> choose the number or the position adjust the number or the position configure high range value <Z> choose the number or the position adjust the number or the position Configure damp time <Z> choose the number or the position adjust the number or the position Configure display mode Choose the display mode pressure, current, percent Fix output current Choose the fixed current value(3.6,4,8,12,16,20,22.8ma NOTE If there is no key pressed in 2 minutes during the setting procedure, it will return the measure mode
Data sheet STK336 Page 6 / 6 Ordering code STK336 For example:stk336-2dh14s21dcn1b... -40...40Kpa Model Output Pressure Type Comm.type Fill fluid Meas. Range Wetted parts material Process connections Electrical connection LCD indicator Display Mode Mounting bracket Label Explosion Protection Suffix Codes 2--- 3--- D--- G--- A--- H- 1----- 2----- 3----- 2--- 3--- 4--- 5--- 6--- 7--- 8--- 9--- 0--- S H------ C 1----- 2----- 1-- 2-- N------ D------ C----- R----- P----- A---- B---- N---- 1-0- B------ D------ 4...20mA/2-wire system 1...5V/3-wire system Differential pressure Gauge pressure Absolute pressure HART Protocol Fill fluid Silicone oil Silicone oil Flurocarbon oil SUS 316L SST Hastelloy C276 Hastelloy C276 None With LCD display Cleansing treatment Standard flat type (for horizontal piping) L type (for vertical piping) None Intrinsically safe Approval Flameproof Approval Descrip tion Degrease cleansing treatment Degrease cleansing treatment Differential Gauge Absolute -1.5kPa~-0.05~0~0.05~1.5kPa -6kPa~-0.12~0~0.12~6kPa 0~0.12~6kPa -40kPa~-0.40~0~0.40~40kPa 0~0.40~40kPa 0~1~40kPa -200kPa~-2~0~2~200kPa 0~2~200kPa 0~5~200kPa -700kPa~-7~0~7~700kPa 0~7~700kPa 0~17.5~700kPa -2.1MPa~-0.021~0~0.021~2.1MPa 0~0.021~2.1MPa 0~0.05~2.1MPa -7MPa~-0.07~0~0.07~7MPa 0~0.07~7MPa 0~0.175~7MPa 0~0.21~21MPa 0~0.41~41MPa Isolating diaphragm Process Connection Wetted Parts SUS 316 SST SUS 316 SST Hastelloy C276 without process connector (1/4 NPT female on the cover flanges) 1/2 NPT female, two electrical connections M20*1.5 female, two electrical connections 1/2-14 NPT, female, two electrical connections Current % range PV Standard Customer This ordering code contains product specification; properties are not guaranteed. Subject to change without notice.