Application Note (Revision NEW) Original Instructions. Upgrading DRFDs to SPCs

Similar documents
Input Power Selector Switch. Product Manual (Revision NEW) Original Instructions for use with Generator Set Control Assembly

Application Note (Revision NEW) Original Instructions. Wiring Instructions for 2301A Controls Replacing Caterpillar 2301 Controls

Wiring Instructions for Replacement of 2301A Load Sharing and Speed Controls with 2301D Load Sharing and Speed Controls

RVDT Setup and Polarity Checking Tool for EG Governors. Product Manual (Revision B) Original Instructions T87444

Application Note (Revision NEW) Original Instructions. EGCP-2 Differences

Application Note (Revision NEW) Original Instructions EGCP-3 LS Using an EGCP-3 in a Single-Phase Zig Zag Generator Application

EGCP-3 LS Revision R Software Revision M. Application Note (Revision NEW, 6/2009) Original Instructions

Application Note (Revision A, 6/2002) Original Instructions. 723PLUS/DSLC Network Binding Procedure. LonMaker for DOS

LVDT Test Device. Product Manual (Revision B) Original Instructions. Testing and Calibration of LVDT Feedback Devices on PG Governors

EGCP-3 LS Revision L. Application Note (Revision NEW, 12/2006) Original Instructions

easygen-3000 Series (Packages P2) Genset Control

Replacement of GCP-10 Series with easygen-1500 Application Note

ProTech-SX Simplex System. Product Manual 26546V2 (Revision A) Original Instructions , Volume 2 Programming and Configuration

Application Note (Revision C) Original Instructions. Application Solutions for Wear Mitigation of the 3103 EM-35MR Actuator

OpView Operator Interface for Woodward 505 and 505E Controls. Product Manual (Revision B) Original Instructions

Digital Speed Matching Synchronizer (DSM) Product Manual (Revision L) Original Instructions

Application Note (Revision NEW, 9/2004) Original Instructions Simple Generator Drive Steam Turbine Applications

Installation and Operation Manual. OpView Operator Interface for Woodward 505 and 505E Controls. Manual (Revision B)

OpFamily Software. Product Manual (Revision A) Original Instructions

723PLUS Digital Speed Control for Reciprocating Engines DSLC Compatible

723PLUS Digital Speed Control for Reciprocating Engines Analog Load Sharing. Product Manual (Revision B) Original Instructions

Application Note (Revision NEW) Original Instructions. Replacing the EGS-01 Gas Engine Control with an EGS Full Authority Control System

Product Manual (Revision E) Original Instructions. EG Actuator Tester. Models and Operation Manual

Product Manual (Revision A) Original Instructions. LINKnet Option for use with 723 Digital Controls. Operation Manual

Application Note (Revision NEW) Original Instructions. Using the proconx GCP-MG Communication Gateway with the GCP-30 and LS-4 Controls

Installation and Operation Manual 723 POSITION CONTROL. Part No ,

Application Note (Revision C, 9/2014) Original Instructions ProAct Gen 1 Position Sensor Update

EGCP-2. Application Note (Revision NEW, 4/2003) Original Instructions

DCN0114 ATS Remote Annunciator Operation Manual. Automatic Transfer Switch Annunciator. Operation Manual. DCN0114 Rev 1

DPG-23XX-00X Digital Controllers. Technical Manual (Revision G) Original Instructions

Product Manual Original Instructions. 733 Digital Speed Control Oil India. Application and Hardware Manual

2301E ST Steam Turbine Control for Small Generator Applications

Product Manual (Revision G, 8/2015) Original Instructions. ProAct II Electric Powered Actuator and Driver. Installation and Operation Manual

505 Digital Control for Steam Turbines. Product Manual 26839V2 (Revision NEW, 2/2015) Original Instructions , ,

Using the proconx GCP-MG Communication Gateway with the GCP-30 and LS-4 Controls. Application Note 51306

Application Note (Revision NEW) Original Instructions PLCs for Turbine Control Systems

Installation Guide SMT 2200/3000 VA Input/Output Hardwire Kit

2301D ST Digital Load Sharing and Speed Control

Installation and Operation Manual. GTC250A Gas Turbine Control for Generator or Compressor Applications Manual 26433

Product Manual (Revision D, 1/2013) Original Instructions. 505LST Digital Control System /-170/-171. Installation and Operation Manual

2300 Digital Electronic Load Sharing and Speed Control. Product Manual (Revision C) Original Instructions

SPC Servo Position Controller. Technical Manual (Revision P) Original Instructions

Resolver to Digital Expansion Board

SPM-D10/YB Synchronizing Unit

MicroNet Plus Turbine Control Panel for LM6000PA/PB/PC/PD/PF Gas Turbines

OPERATING PROCEDURES for the UPS-S2 Universal Power Supply Series 2

SCADA Protocol Configuration Tool Manual SCADAP-1.0-EN-MAN

MicroNet TMR Control System

H Series PLC. ! : Indicates Compulsion. EH-150 Analog input module EH-AXH8M Instruction manual. Safety precautions DANGER CAUTION COMPULSION

2301D-ST Digital Electronic Load Sharing & Speed Control for Small Steam Turbines. Product Manual (Revision G) Original Instructions

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

Scanner 2000 Steam Mass Flow Transmitter

ProAct Digital Plus Electric Actuator with Integral Driver. Product Manual (Revision W, 7/2016) Original Instructions

PS/IO Circuit Board Retrofit

DeviceNet PCI Card Instructions Manual

easygen-2000 Series easygen-2500 Rental (Option K33) Software Version 1.00xx 37537

easygen-300 Genset Control

User Manual. APECS 500 Single Speed Electronic Engine Controller. Manual (replaces SE-4107)

S Contents. Figure 1. Kyle Form 4C Analog Current Metering Accessory KME

Customer Replacement Procedure

505 Enhanced Digital Control for Steam Turbines (with Redundancy)

Customer Replacement Procedure

SUN2000P-375 W Smart PV Optimizer. User Manual. Issue 01. Date HUAWEI TECHNOLOGIES CO., LTD.

P216. Condenser fan speed controller. Product bulletin. Features

MTP INSTRUCTION MANUAL

EGCP-2 Engine Generator Control Package. Product Manual (Revision E) Original Instructions

Installation Instructions

Product Manual (Revision C) Original Instructions. In-Pulse Plus Electronic Fuel Injection Control. Installation and Operation Manual

Installation Job Aid for Ethernet Routing Switch 5900 Series

ProTech 203 Overspeed Protection System. Installation and Operation Manual , -201, -202, -203, -204, -205, , -345

Installation and Operation Manual. ProAct Digital Plus Electric Actuator with Integral Driver. Manual (Revision M)

User's Guide. MiniTec TM Series Model MN25 MultiMeter

Altivar 61/71 Adjustable Speed Drives Heatsink Fan Kits VZ3V1212 and VZ3V1216

GV3000/SE Operator Interface Module (OIM) User Guide Version 2.0 M/N 2RK3000

ProTech 203 Overspeed Protection System. Installation and Operation Manual , -207, -208, -209, -210, -211, , -347

DX200 OPTIONS INSTRUCTIONS

APPLICATION NOTES H-coupling

RP RP-3000 Software Version 1.xxxx or higher 37534C

MC-12 Software Installation Instructions

PTB 01 ATEX 2064 U, IECEx PTB U. Example / Beispiel / Exemple: Type Operating Instructions

Installation Instructions

User s Guide. 600A AC Clamp Meter. Model 38387

DX200 OPTIONS INSTRUCTIONS

ProTech-GII Overspeed Protection Device with Voted Inputs. Product Manual (Revision E, 5/2015) Original Instructions

APECS 500 Electronic Engine Speed Governing System

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

Intel Server Board S2600BP Intel Compute Module HNS2600BP Product Family

Customer Replacement Procedure

B63/ NS MS. EtherNet/IP LINK

Installation Job Aid for Ethernet Routing Switch 3600 Series

Line reactors SINAMICS. SINAMICS G120P Line reactors. Safety information 1. General. Mechanical installation 3. Electrical installation 4

GENERAL PRECAUTIONS GENERAL DESCRIPTION... 6

COMFORT CONTROL CENTER SERVICE INSTRUCTIONS

PTB 01 ATEX Example / Beispiel / Exemple. Type Operating Instructions

Primary Injection Test Procedure

MDM 011-Z1 Regen Resistor

This document provides information on: important pre-installation considerations installing the memory cartridge replacing the battery specifications

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

Siemens Industrial s

SINAMICS G130. Voltage Sensing Module 10 (VSM10) Operating Instructions 05/2010 SINAMICS

Transcription:

Application Note 51322 (Revision NEW) Original Instructions

General Precautions Read this entire manual and all other publications pertaining to the work to be performed before installing, operating, or servicing this equipment. Practice all plant and safety instructions and precautions. Failure to follow instructions can cause personal injury and/or property damage. Revisions This publication may have been revised or updated since this copy was produced. To verify that you have the latest revision, check manual 26311, Revision Status & Distribution Restrictions of Woodward Technical Publications, on the publications page of the Woodward website: www.woodward.com/publications The latest version of most publications is available on the publications page. If your publication is not there, please contact your customer service representative to get the latest copy. Proper Use Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical, or other operating limits may cause personal injury and/or property damage, including damage to the equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or "negligence" within the meaning of the product warranty thereby excluding warranty coverage for any resulting damage, and (ii) invalidate product certifications or listings. Translated Publications If the cover of this publication states "Translation of the Original Instructions" please note: The original source of this publication may have been updated since this translation was made. Be sure to check manual 26311, Revision Status & Distribution Restrictions of Woodward Technical Publications, to verify whether this translation is up to date. Out-of-date translations are marked with compare with the original for technical specifications and for proper and safe installation and operation procedures.. Always Revisions Changes in this publication since the last revision are indicated by a black line alongside the text. Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly undertaken. Copyright Woodward 2008 All Rights Reserved

Application Note 51322 Warnings and Notices Important Definitions This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE Indicates a hazard that could result in property damage only (including damage to the control). IMPORTANT Designates an operating tip or maintenance suggestion. Overspeed / Overtemperature / Overpressure The engine, turbine, or other type of prime mover should be equipped with an overspeed shutdown device to protect against runaway or damage to the prime mover with possible personal injury, loss of life, or property damage. The overspeed shutdown device must be totally independent of the prime mover control system. An overtemperature or overpressure shutdown device may also be needed for safety, as appropriate. Personal Protective Equipment The products described in this publication may present risks that could lead to personal injury, loss of life, or property damage. Always wear the appropriate personal protective equipment (PPE) for the job at hand. Equipment that should be considered includes but is not limited to: Eye Protection Hearing Protection Hard Hat Gloves Safety Boots Respirator Always read the proper Material Safety Data Sheet (MSDS) for any working fluid(s) and comply with recommended safety equipment. Start-up Be prepared to make an emergency shutdown when starting the engine, turbine, or other type of prime mover, to protect against runaway or overspeed with possible personal injury, loss of life, or property damage. Automotive Applications On- and off-highway Mobile Applications: Unless Woodward's control functions as the supervisory control, customer should install a system totally independent of the prime mover control system that monitors for supervisory control of engine (and takes appropriate action if supervisory control is lost) to protect against loss of engine control with possible personal injury, loss of life, or property damage. Woodward 1

Application Note 51322 Battery Charging Device To prevent damage to a control system that uses an alternator or battery-charging device, make sure the charging device is turned off before disconnecting the battery from the system. Electrostatic Discharge Awareness Electrostatic Precautions Electronic controls contain static-sensitive parts. Observe the following precautions to prevent damage to these parts: Discharge body static before handling the control (with power to the control turned off, contact a grounded surface and maintain contact while handling the control). Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit boards. Do not touch the components or conductors on a printed circuit board with your hands or with conductive devices. To prevent damage to electronic components caused by improper handling, read and observe the precautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards, and Modules. Follow these precautions when working with or near the control. 1. Avoid the build-up of static electricity on your body by not wearing clothing made of synthetic materials. Wear cotton or cotton-blend materials as much as possible because these do not store static electric charges as much as synthetics. 2. Do not remove the printed circuit board (PCB) from the control cabinet unless absolutely necessary. If you must remove the PCB from the control cabinet, follow these precautions: Do not touch any part of the PCB except the edges. Do not touch the electrical conductors, the connectors, or the components with conductive devices or with your hands. When replacing a PCB, keep the new PCB in the plastic antistatic protective bag it comes in until you are ready to install it. Immediately after removing the old PCB from the control cabinet, place it in the antistatic protective bag. 2 Woodward

Application Note 51322 Actions The Woodward Servo Position Controller (SPC) was designed to accurately position turbine servo valves, and can be used to replace Woodward's older Digital Remote Final Drivers (DRFD) line of products. Although the SPC can be used to replace DRFD units, it was not designed as a drop-in replacement for the DRFD. Because of the differences between these two products, Woodward recommends that engineers consider the following product differences when developing their new SPC replacement application design: Environmental Rating Differences Input Power Source Differences Feedback Transducer Power Differences Maximum Actuator Output Drive Current Differences GE Oil-Gear Servo Interface Differences Shutdown Status Indication Relay Output Differences Forward or Reverse-Acting Action Considerations Turbine Controller Dynamic Setting Re-adjustment Considerations Environmental Rating Differences / Recommendations The DRFD is designed for NEMA 4 or IP54 rated environments, and the SPC is designed for NEMA 12 or IP20 environments, thus designed accordingly to meet application requirements. The DRFD may have redundant power supplies built in (typically 120 Vac and 132 Vdc). However, the SPC has a single 24 Vdc input (the SPC isn t sold with redundant power supplies). If redundant power supplies are needed, you will need to install two external power supplies, and run them through a diode block to the SPC. Input Power Source Differences / Recommendations: The DRFD accepts 90 140 Vdc or 88 132 Vac, while the SPC only accepts 18 32 Vdc Many DRFDs accept redundant power sources, while the SPC only accepts a single input power source. If it is desired to continue to use redundant power sources into the SPC, to provide the same level of availability as the DRFD configuration had, Woodward recommends that external power supplies be added using a high-signal-selection diode design. Refer to Figure 2 in this document for an example wiring diagram. If redundant power supplies are used and power supply health indication is required, Woodward recommends that external power supply indication relays or logic be added. Refer to Figure 2 in this document for an example wiring diagram. Woodward 3

Application Note 51322 Feedback Transducer Power Differences Depending on the specific DRFD part number used, the DRFD can output an AC LVDT/RVDT excitation source, or a 24 Vdc output source or ±15 Vdc power source to power feedback transducers or signal conditioners. The SPC outputs an AC LVDT/RVDT excitation source, but does not have 24 Vdc or ±15 Vdc power output sources. If a 24 Vdc power source is required by the system feedback device, Woodward recommends that the same 24 Vdc input power source used to power the SPC be used to power the system feedback device. If a ±15 Vdc power source is required by the system feedback device or signal conditioner, Woodward recommends that an external power supply be provided to power the system feedback device. The SPC outputs 18 Vdc (120 ma max) when configured for DC voltage feedback devices. The 18 Vdc output is provided to power devices requiring 0 to 10 Vdc power at 120 ma (max), but Woodward highly recommends that an external power supply be used for all 24 Vdc devices. Maximum Actuator Output Drive Current Differences The DRFD is designed to output a maximum drive current of ±400 ma; however, the SPC is designed to output only ±250 ma. If a maximum drive current of ±400 ma is required, Woodward recommends that the SPC not be utilized. GE Oil-Gear Servo Interface Differences The GE Oil-Gear Servo is quite different from other types of pilot-valve servos, in that it also has a feedback signal from the pilot valve. DRFD part number 8238-005 was designed to accept both pilot-valve-position and servo-valveposition feedback as was required by many types of GE Oil-Gear Servos. Although the SPC does accept two feedback signals, it does not manage these two feedback signals like DRFD 8239-005. Although several companies have used two SPCs with one cascaded into the other SPC as is displayed in Figure 2-3 of Woodward manual 26236, Woodward has no official recommendation for DRFD 8239-005 replacements. Shutdown Status Indication Relay Output Differences The DRFD's Shutdown Status Indication Relay has "Normally Open" and "Normally Closed" contacts rated for 120 Vac voltages; however, the SPC's Shutdown Status Indication Relay has only a "Normally Open" contact, and is only rated for 18 32 Vdc voltages. 4 Woodward

Application Note 51322 Forward or Reverse-Acting Action Considerations A DRFD functions in a forward- or reverse-acting manner, dependent upon the specific part number, and dependent upon the type of feedback (0 100% = 10 0 Vdc feedback signal). The SPC is software-configurable to function in a forwardor reverse-acting manner, but this setting will determine the SPC's output direction, not its feedback direction, like the DRFD. Ultimately the SPC can be configured to function and fail in the correct direction, however depending on the application, it may be required to configure it for forward action instead of reverse action like the DRFD. Turbine Controller Dynamic Setting Re-adjustment Considerations Because the response of the turbine valve control loop has a direct influence on the turbine speed control loop, after the SPC has been successfully installed and dynamically tuned, Woodward recommends that the turbine speed control loop's dynamic settings be tested and, if necessary, re-adjusted. In some cases, these system dynamic response differences are the result of the faster performance of the SPC as compared to the DRFD's previous dynamic response. Publications These are available via www.woodward.com/publications: 03254 SPC product specification 26115 SPC technical manual (8200-220/-221) 26236 SPC technical manual (8200-224/-225/-226) [includes a DRFD-to-SPC cross-reference table in Appendix A] Service bulletins are available via e-business with a password or on the Woodward ActiveNet (intranet): 01222 TI DSP Recall SPC 01259 SPC Input Demand Current Range Modification 01261 SPC/TM25 Compatibility 01263 SPC Application Software Revision 01352 SPC Service Tool Woodward 5

Application Note 51322 Figure 1. Photo of Example Conversion 6 Woodward

Application Note 51322 Figure 2. Example Conversion Wiring Changes Woodward 7

We appreciate your comments about the content of our publications. Send comments to: icinfo@woodward.com Please reference publication 51322. PO Box 1519, Fort Collins CO 80522-1519, USA 1000 East Drake Road, Fort Collins CO 80525, USA Phone +1 (970) 482-5811 Fax +1 (970) 498-3058 Email and Website www.woodward.com Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address / phone / fax / email information for all locations is available on our website. 2012/12/Colorado