T7560A1036 Digital Wall Module

Similar documents
T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module

C7110C1001A / C7110D1009A WALL MODULES

T7270B2009 WIRELESS WALL MODULE

T7460A,B,C,D,E,F WALL MODULES

T7270B1009 WIRELESS WALL MODULE

T7460A,B,C,D,E,F WALL MODULES

CTR21, CTR22, CTR23, and CTR24 Wall Modules

Separate mounting base for easy installation. Tamper resistant locking cover.

N0524/N1024, N POS/N POS

BA/BS4S Temperature Sensor Installation & Operating Instructions

N05010/N10010 NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR MODULATING AND FLOATING / 2-POSITION CONTROL SPECIFICATIONS

Excel Smart I/O Compact

Allure EC-Smart-Comfort Series

N20010, N NON-SPRING RETURN DAMPER ACTUATOR 20/34 Nm (177/300 lb-in) FOR MODULATING CONTROL SPECIFICATIONS GENERAL FEATURES PRODUCT DATA

Allure EC-Smart-Comfort Series

Excel 10 W7754K,P,Q FAN COIL UNIT CONTROLLERS

CDD4 Series Room CO2 Transmitter Installation Instructions

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Table of Contents. General Information. Document Sure-Aire Flow Monitoring System. User and Service Manual WARNING CAUTION

Room Temperature Controller

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

Excel 10 W7754K,P,Q,R,S,T,V FAN COIL UNIT CONTROLLERS

ML7421A,B Electric Linear Valve Actuators

CDD Carbon Dioxide Transmitter

LOCAL DISPLAY UNIT (LDU)

RS-WMB, RD-WMB Wallbus Room Sensors and Displays

Room unit with PPS2 interface

Installation & Operation Guide

Free Energy Band RCC30U Room Temperature Controller for Four-pipe Fan Coil Unit

Room unit with PPS2 interface

Zone Pressure Touch (ZPT) Sensor - Standard Range

TEC Unit Conditioner Controller

LTEC Heat Pump DDC Controller

BACnet PTEC Terminal Box (VAV) Controller. Control Applications. Product Numbers. Product Description. Warning/Caution Notation

TAC Xenta 101-VF. 3-Speed Fan Coil Controller. TAC Xenta

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

RCM Room Command Module New Style

Autoranging True RMS Multimeter User Manual

UNT1100 Series. Binary Output Jumpers AO2 AO1 AO3 AO4 AOCM AOCM AOCM AOCM AO1. AI Switches Job Information N2 Address. Ref N2+ N2- ADDR 0 = ALL OPEN

Zone Pressure Touch Sensor - Standard Range

Specification Sheet For electronically commutated motors

Installation and Operation Guide

rcc.1081 Installation Instructions

ETM-2050/ETM-2051 Service Manual

Instruction Manual. M Pump Motor Controller. For file reference, please record the following data:

H7625A, H7635A Humidity/Temperature Sensors

ExactLogic BACnet Communicating Pressure Dependent VAV Damper Control with Heat EXL01820 Sequence Datasheet

Zone Pressure Touch (ZPT) Sensor with Attached Tube (-AT) - Low Pressure Range Unit Installation and Operation Instructions

Content. Product Description

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

NT10 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

Multi-Point Gas Detection and Control System

PLEASE READ INSTRUCTIONS CAREFULLY BEFORE INSTALLATION!

Room Temperature Controllers

CDD4 Duct Carbon Dioxide Transmitter

LTEC Unit Ventilator DDC Controller

Satellite INSTALLATION GUIDE

Installation Guide. Carbon Dioxide (CO 2. ) Detectors. General Information. Mounting WARNING CAUTION. SAE-1011/1012 Space Mount SAE-1011/1012/1062

Global Plasma Solutions. 10 Mall Terrace, Bldg C Savannah, GA (912) ph (877) fax

Room Temperature Controller

Custom Controller Installation Instructions

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

VAV Modular Assembly (VMA) 1410/1420

SmartBlock I/O Module HE579MIX102 Isolated 6 Relay, 12 DC Inputs, 4 Analog Inputs

Installation, Start-up and Operating Instructions

Carbon Monoxide Sensor - ModBus

NT50 Series RS485 Modbus RTU Networking LCD Fan Coil Thermostat

Zone Manager INSTALLATION MANUAL 40KMC KMQ QNC QNQ

AL168 Series Multi-Output Power Supplies

QAX50.1 QAX50.5 QAX51.1 QAX51.5. Flexible room unit. Desigo RXC

Field selectable application type and room module series, via dip-switches on controller

Cables. U.S. Registered Trademark EN0B-0341GE51 R0402 Copyright 2002 Honeywell Inc. All rights reserved

Non-communicating room controllers

Installation and Operation. Tracer MP501 Controller CNT-SVX08B-EN

ExactLogic BACnet Communicating Zone Damper EXL01710 Sequence Datasheet

TEC Terminal Box (VAV) Controller

RWD68U Universal Controller

BACnet. b3810 Series Local Controllers

HE-6800 Series Humidity Transmitters with Temperature Sensor

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

Multi-Point Gas Detection and Control System

Overview. Integrated fail-safe mode in case of communication or power failure to comply with most regulation requirements

Room unit with PPS2 interface

ECONOMIZERS. Z1ECON30B-1 ECONOMIZER (Cat No. 10Z29) INSTALLATION INSTRUCTIONS FOR ECONOMIZERS USED WITH ZC,ZG,ZH UNITS CAUTION WARNING

EYE 200: DDC single-room controller, ecos200

Suitable for a wide range of installations with wall-mount, flush-mount and hand-held remote control options.

Multi-Point Gas Detection and Control System

FOR SERVICE TECHNICIAN S USE ONLY

CDR-RH Room CO 2, Temperature and Humidity Sensors (Controllers)

BACnet PTEC Unit Conditioner/Fan Coil P. Controller. Control Applications. Accessories. Product Description. Warning/Caution Notation

KRAMER ELECTRONICS LTD. USER MANUAL MODEL: RC-76R/RC-78R Room Controllers. P/N: Rev 5

S-14 S-14. Compact Digital Multimeter. Compact Digital Multimeter

MOD-IO9 Modbus Input / Output Modules, Wall Mounted

ASI Systems ML5740A Series

USER MANUAL. RC-76R/RC-78R Room Controllers MODEL: P/N: Rev 2

BlueWave ~ Intelligent Energy Control. Installation and User Manual for BW2/C and BW3/C versions. Quick Guide

Transcription:

T7560A1036 Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. T7560A1036 wiring can be sized from 16 to 22 AWG (1.5 to 0.34 mm 2 ), depending on the application. The max. length of wire from a device to a T7560A1036 is 164 ft (50 m). Twisted pair wire is recommended for wire runs longer than 100 ft (30.5 m). CAUTION EMI Noise Introduction. Risk of erratic system operation. Keep wiring at least one ft (305 mm) away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels. During installations, try to avoid areas of high EMI noise. Run T7560A1036 wiring separately from 50 Vac or greater power wiring. INSTALLATION INSTRUCTIONS DISASSEMBLY The T7560A1036 comes packed with a sub-base that mounts separately for ease of installation. The cover is fixed by a latch on the underside of the unit. Remove the cover as shown in Fig. 1. 1. Insert the tip of an awl or a similar narrow, pointed object into the small hole in the latch. 2. Pry off the cover. 1 2 WARNING / CAUTION Risk of electric shock or equipment damage! Do not touch any live parts inside the T7560A1036 housing. Disconnect the power supply before making connections to or removing connections from the terminals of the T7560A1036. Do not reconnect the power supply until you have completed the installation. If the T7560A1036 is powered via terminal 8 and connected to earth ground, then the cable must be shielded. Observe precautions for handling electrostatic sensitive devices. Fig. 1. T7560A1036 disassembly INSTALLATION Mount the T7560A1036 on an inside wall approximately 54 in. (1.3 m) from the floor (or as specified on the installation drawings) to allow exposure to the average zone temperature. Do not mount the T7560A1036 on an outside wall, on a wall containing water pipes or near air ducts. Avoid locations that are exposed to discharge air from registers or radiation from lights, appliances, or the sun. The T7560A1036 is furnished with a terminal block; all field wiring connections are made to these eight terminals. The T7560A1036 must be mounted in vertical position with the LCD display to the top. Mount the subbase directly on a wall (see Fig. 2) using the type of screws appropriate for the wall material. U.S. Registered Trademark Copyright 2013 Honeywell Inc. All Rights Reserved

FRONT COVER WIRING Wire the terminal blocks as follows: 1. Strip 3/16 in. (5 mm) of insulation from the conductor. 2. Insert the wire in the required terminal location and tighten the screw to complete the termination. IMPORTANT Deviation from this rule can result in improper electrical contact. See Fig. 4. 3. Verify T7560A1036 is wired according to Fig. 4. SUBBASE Fig. 2. Mounting of T7560A1036 Terminals Wiring to XL12, for Square Frère Orban functionality or replacement of T75601000KBC set P5 to P5:1 1 = Common 2 = Temperature sensor 3 = Setpoint 4 = Lights on/off (left and middle button) 5 = LED input / powering, see next page 6 = Bypass (right button) 7 = Do not connect 8 = 24Vac powering, see next page 1 2 3 4 5 6 7 8 3-7/16 (86) 4 (100) 2 MAX 0.2 Nm (2.2 lb-in.) Wiring to XL10, for Berlaymont functionality set P5 to P5:2 1 = Common 2 = Temperature sensor 3 = Setpoint 4 = Lights on/dim up (left button) 5 = LED input / powering, see next page 6 = Lights off/dim down (middle button) 7 = Bypass (right button) 8 = 24Vac powering, see next page 2-11/16 (68) 3-7/8 (97) 3-15/16 (99) 1-1/16 (27) 1 Wiring to XL10, for replacement of T75601000GAL set P5 to P5:2 1 = Common 2 = Temperature sensor 3 = Setpoint 4 = Analog value for light control (left button) 5 = LED input / powering, see next page 6 = Sunblind up (o.c. output) (center button) 7 = Sunblind down (GND, power) Fig. 4. Wiring of T7560A1036 See also section "Entering Configuration Mode" on pg. 4 for information on how to set P5. 4-1/8 (104) 1-3/16 (30) POWERING VIA 5 V LED INPUT Powering is preferably via the 5 V LED input (terminal 5), supplied by the LED output of any Excel 10/12 controller. IMPORTANT In the case of those Excel 10/12 controllers listed in Table 1, the SW version listed in Table 1 or higher must apply, and the Excel 10/12 controller must be configured for LCD_DISPLAY (LED output continuously ON). Fig. 3. T7560A1036 dimensions in inches (mm) Input Ratings for terminal 5: min. 5 Vdc, I max 3 ma, max. 15 Vdc, I max 4 ma, or 2

Table 1. Controller SW requirements for powering via terminal 5 and new LCD signaling VAV W7751H Fan Coil Unit W7752 W7754 Hydronic W7762 Chilled Ceiling W7763 1.02.15 1.00.04 1.00.02 1.00.03 1.00.03 Excel 12 W7704xxxx All versions 2 Besides the Excel 10/12 controllers, controllers with the following output ratings can be connected to terminal 5 (ratings are met by all Excel 10 controllers): 5 V with 389 Ω 4.3 V with 100 Ω 14.3 V with 1.5kΩ POWERING WITH 24VAC Alternatively to powering via the 5 V LED input, powering with 24Vac via terminal 8 is also possible. Input Ratings for terminal 8: min. 18 Vac, I max 2.4 ma 24 Vac, I max 6 ma max. 27 Vac, I max 10 ma, Use up to 16 AWG (1.5 mm 2 ) with a minimum of 18 AWG (1.0 mm 2 ) wire for connecting 24 Vac power to terminal 8. CAUTION Low Voltage Equipment. Risk of equipment damage. The 24 Vac power source for the T7560A1036 must be a Class II Power Source. To conform to Class II restrictions, transformers must not be larger than 100 VA. A transformer that is CE certified and meets the Low Voltage Device (LVD) requirements must be used in Europe for all installations of this product. The T7560A1036 power usage is 0.2 VA at 24 Vac. The T7560A1036 does not require a dedicated transformer. The T7560A1036 can get power from any convenient location in the 24 Vac power circuit. The 24 Vac power can come from the 24 Vac power terminals on the nearest controller or directly from a 24 Vac transformer, whichever is closer. When all wiring is complete, attach the cover of the T7560A1036 as is shown in Fig. 5. Fig. 5. Mounting cover of T7560A1036 NOTE: Make sure that the latch on the underside of the T7560A1036 engages properly and that the three control buttons protrude through the holes completely. CONFIGURATION After installation, the T7560A1036 must be configured in order to perform as desired. This is done by using the buttons and the setpoint wheel (see Fig. 6). LCD DISPLAY LIGHTS - ON/OFF/DIM BYPASS SETPT. WHEEL COVER SETPT. WHEEL Fig. 6. Control elements of T7560A1036 1 3

Normal Operating Mode After the T7560A1036 is powered up by the controller, it will display the room temperature and will operate as configured by default. After power-up, all display segments are switched on for approx. one second (see Fig. 7). AUTO MANU PROG Fig. 7. Display of all segments after power-up Entering Configuration Mode 1. Press the left button for at least 5 seconds. 2. Press the middle button, then release the left button and hold the middle button down for at least another 5 seconds. 3. Release the middle button. RESULT: The display shows and the T7560A1036 is ready for configuration (see below). 4. Press and hold down the left button while turning the setpoint wheel to select the parameter number. RESULT: The parameters with their currently set values are displayed; the behind the value indicates the currently set value (see below for values). 5. Release the left button and turn the setpoint wheel to select the parameter value. 6. Confirm selection by pressing the middle button. 7. Repeat steps 4 to 6 to configure next parameter, or press BYPASS to leave the configuration mode. NOTE: After approx. 10 seconds without further action, the T7560A1036 automatically reverts to normal mode. In the following, the respective default setting is marked with an asterisk (*). P1 Setpoint type setting / scale type setting Fahrenheit relative Fahrenheit absolute * Celsius relative Celsius absolute P2 Room temperature setting Do not display room temperature (setpoint, only) * Display room temperature Display room temperature and humidity, alternating every 5 seconds (T7560B, only) P3 P4 Bargraph use setting * No Fan (Square Frère Orban) Auto, Off, On Auto, Off, 2 Speeds Auto, Off, 3 Speeds Controller type setting * New LCD signaling from controller (only for controllers and SW versions as listed in Table 1 or higher, in which case this setting must be selected; set Excel 10 controller to LCD_DISPLAY) LED override mode from controller, U.S. signaling (100 ms pulses); with controllers W7750, W7751, W7753, W7761, and XL12 LED override mode from controller, European signaling (500 ms pulses); with controllers W7752, W7762, W7763, and XL12 (in the case of SW versions listed in Table 1 or higher, select ). LED occupancy mode from controller, European signaling (500 ms pulses); with controllers W7752, W7762, W7763, and XL12 Same as Excel 500 signaling from controller (10 V, 8 V, 6 V) P5 Pin 4, 6 and 7 grounding (Frère Orban/Berlaymont) This parameter defines the grounding and functionality required for the installations at Square Frère Orban or Berlaymont. Specifically, this parameter defines what happens when the left/middle/right button of the T7560A1036 is pressed. * Square Frère Orban functionality Press left button: Short pin 4 to GND Press middle button: Short pin 4 to GND Press right button: Short pin 6 to GND Berlaymont or sunblind functionality Press left button: Short pin 4 to GND Press middle button: Short pin 6 to GND Press right button: Short pin 7 to GND Release right button: Set pin 7 to max. voltage (4.5V 5.0V) Reserved Do not use this option! 4

P6 Device type This item configures different devices. IMPORTANT: Keep the setting P6:1 and do not change to other configurations. P7 Temperature offset * Temperature offset; values of 0 through 99 are valid. 50 = no change (default), 49 = -0.1 C, 51 = +0.1 C, etc. This offset varies the LCD display value, only. In order for this offset to have the proper effect, it must be set in the controller, too. P8 Remote reset of temperature setpoint overrides and fan speed overrides * disable remote reset of temperature setpoint override and disable remote reset of fan speed override. enable remote reset of temperature setpoint override and disable remote reset of fan speed override (takes effect ONLY if or has been selected AND or has been selected) disable remote reset of temperature setpoint override and enable remote reset of fan speed override (takes effect ONLY if or has been selected) enable remote reset of temperature setpoint override and enable remote reset of fan speed override (takes effect ONLY if or has been selected AND or has been selected) Important: In addition to setting parameter P8, also the parameters P1 and P4 must be set accordingly for the wall module see above! Explanation: The goal of this action is to reset those overrides, which a room user has done at the wall module. In hotels and office buildings, a typical requirement is to remotely reset the wall module setpoint override to zero, and to remotely reset the wall module fan speed override to Auto. NOTE: If the wall module has been set to OFF by the room user, it cannot be reset to auto. With Excel 50 controllers, this reset can be done by sending 6 Volt (= unoccupied ) to the LED input of the wall module: As long as sending 6V to the LED input Wall module is in unoccupied Local setpoint and/or fan speed setting is reset and disabled. As long as sending 10V to the LED input Wall module is in occupied Local setpoint and/or fan speed setting is enabled. With Excel 10 controllers, this reset can be done by switching from occupied to unoccupied. This will send a special coded Excel 10 signal to the LED input of the wall module. "Unoccupied" means: Effective Unoccupied (moon on continuously), or Override Unoccupied (moon flashing). "Occupied" means: Effective Occupied (sun on continuously), or Override Occupied (sun flashing). P9 Limit setpoint - Limit setpoint to ±0 5 C (if set to Celsius) or to ±0 9 F (if set to Fahrenheit). Default (if set to Celsius): Default (if set to Fahrenheit): Example (units set to Celsius): A setting of means that the setpoint offset is limited to -3 to +3 C. Example (units set to Fahrenheit): A setting of means that the setpoint offset is limited to -8 to +8 F. PA Limit for humidity low limit output value This parameter is not applicable for the T7560A1036! - Limit the output value to 10 20% relative humidity in steps of 5%. This affects the output voltage at pin 7, only, and has no effect upon values appearing in the display. = 10%, = 15%, = 20% (default). Resetting to Factory Defaults To reset the wall module to its factory default settings, first power down the wall module. Then press and hold down all three buttons simultaneously and power up the wall module. The wall module settings will then be automatically set to their factory default values, and the display will show. To complete the process, release all three buttons and power up the wall module again. How to Check the Software Version To check the wall module's software version, press and hold down the left and right buttons simultaneously for at least 5 seconds. The display test (see Fig. 7) is then automatically performed, after which the wall module's software version (e.g., "7.00") is displayed. 5

ACCESSORIES T7460LONJACK The T7460-LONJACK is a small board with a 3.5 mm jack socket for a 3.5 mm jack plug. It and allows easy access to LONWORKS or BACnet via the correspondingly wired wall module (apply appropriate wiring guidelines for LONWORKS or BACnet networks, as the case may be). Order quantity: Set with 5 pieces LonWorks connection terminals T7560 Blinds Same material and color as housing; for covering nonoperational pushbuttons. Order quantity: bulk pack of 50 pieces. White Setpoint Wheel Covers Instead of the standard blue setpoint wheel covers, white setpoint wheel covers (order no.: WMSPS-4) are also available. Order quantity: bulk pack of 25 pieces White Setpoint Wheels Instead of the standard blue setpoint wheels, white setpoint wheels (order no.: WMSPS-6) are also available. Order quantity: bulk pack of 25 pieces PC connection (3.5 mm jack plug) Fig. 8. T7460LONJACK SETPT. WHEEL COVER SETPT. WHEEL Fig. 10. White setpoint wheel and wheel cover Housings with Special Printing Instead of housings with the standard printing, for some customer-specific applications (sunblind control, etc.), housings with corresponding printing are available. Please contact our TAC hotline for more information: tac-care-ge51@honeywell.com Fig. 9. Mounting the T7460-LONJACK Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative: Automation and Control Solutions Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany