Automatic Transfer Switch OTM_C20D

Similar documents
Automatic Transfer Switch OTM_C_20D. Installation and Operation Instructions

34OTM_F_C rev. F / 1SCC303009M0206. Motorized change-over switches OTM_F_C Installation and operating instructions

Motorized switch-disconnectors OTM_F_. Installation instruction 34OTM_F_ / 1SCC303010M0202

PGR-4700 MANUAL SENSITIVE GROUND-FAULT RELAY

MG24434 Supplementary Protector SUPPLEMENTARY PROTECTOR, 240VAC, 16A, CIRCUIT BREAKER TYPE: STANDARD

Flexible Rogowski Coil Integrator Kit with 4-20mA and 0-20mA. User's Manual

SAFETY RELAY YRB-4EML-31S MAIN FEATURES

RIK-5A Flexible Current Tranformer User's Manual

Safety Switching Devices SNO 4003K. Basic device for Emergency-Stop and Safety Gate Applications PI E

PGR-6101 MANUAL GROUND-FAULT & INSULATION MONITOR

SERIES 230 A2ADTL Transfer Switch User Manual

Installation, Testing, and Operating Procedures 30 AMP PORTABLE AND PERMANENT SERIES GFCI SINGLE and MULTIPHASE

PSR-SCP- 24DC/SDC4/2X1/B PSR-SPP- 24DC/SDC4/2X1/B

PSR UC/ESAM4/3X1/1X2/B

IV-30 Operating Manual for Pulse Distributor Cassette with potential separation

PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR

Allen-Bradley 1492-RCDA4A40

PSR-PC50. SIL 3 coupling relay for safety-related switch on. Data sheet. 1 Description

SERIES 230 C2ADTL Transfer Switch User Manual

PSR-SCP- 24DC/URM4/4X1/2X2/B PSR-SPP- 24DC/URM4/4X1/2X2/B

Operating instructions. Speed monitor D / / 2014

Rhino Redundancy Module PSM24-REM360S. Operating Instructions

INSTRUCTION MANUAL TRIP CIRCUIT SUPERVISION RELAY GKAD1

Rhino Buffer Module PSM24-BFM600S. Operating Instructions

Operating instructions. Switching amplifier DN0210 DN / / 2015

DRT-301 A/D. User manual. Three phase four wire DIN rail energy meter. (Seven modules) 1.1 Safety instruction. 1.2 Foreword. 1.3 Performance criteria

Serial Data DIN Fiber Link System

Residual Current Devices drcm Digital

PGR-3200 MANUAL INSULATION MONITOR

FL MC 2000T. Fiber optic converter for 10/100Base-Tx to single- or multi-mode fiberglass with SC-duplex and ST connections. Data sheet 3379_en_B

REDUNDANCY MODULE TSP-REM360 AND TSP-REM600

Disconnect Switches. Safe Switching and Disconnecting

LINETRAXX RCMS150. Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems)

SERIES 230 Automatic Transfer Switch C1000 Intelligent Controller User Manual

DALI Professional Controller-4. Control unit Operating instructions

1 Safety instructions. 2 Device components. 3 Function. IC00P01DAL - DALI gateway. DALI gateway. Operating instructions

SMS 3xxx/SMS 4xxx Safety switch with separate actuator

PSR-MS60. Safety relay for emergency stop, safety door and light grid monitoring. Data sheet. 1 Description

Electrical devices may only be mounted and connected by electrically skilled persons.

FL MC 2000E (SM40) LC

EM-F-7G Safety Extension Module

Operating instructions Hinge safety switch TV.S 335 TV.S About this document. Content

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

MSR Level Control Relay Module Operating Instructions for Level Control Relay Module Model: MSR

HITACHI. EH-150 series PLC EH-RTD8 Resistance Temperature Detective input module Instruction manual. Safety precautions

PSR DC/ESP4/2X1/1X2

GCI-5K INSTALLATION AND OPERATOR S MANUAL

Quick Start Guide TS A

Residual Current Devices FRCdM Type B, B+ and Bfq Digital

Twido Programmable Controllers Discrete I/O Modules

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

MULTI 9 System Catalog UL Recognized NC100H Supplementary Protectors

Operating instructions Safety-monitoring module AES 1235 AES About this document. Content

SDM120 SERIES. SDM120 series User Manual. Single phase two wire DIN rail energy meter (One module)

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL:

Automatic transfer switches. TruONE ATS, OX_ _. 34OX_ rev. A / 1SCC303011M0201. Automatic transfer switches

LXEM145 SERIES Lanx Australis single Phase KWh Meter 45Amp. User manual

Catalog Number Identification with Elements Explained V V V V X 347 V Hz

Voltage Dip-Proofing Inverter

TOS-SN-1 Extended Panel Operation Manual

Datasheet - SLB 200-C04-1R

By-pass and transfer switches OT_Y. Installation instruction 34OT_Y_ / 1SCC301080M001

9212i INSTALLATION. Stand-Alone Keypad. Instructions

VFI RTG PDU 6-10K. Installation and user manual. Service and support: Call your local service representative

SINAMICS G130. Terminal Module 150 (TM150) Operating Instructions 03/2013 SINAMICS

60103 Circuit Breaker

QUINT-BUFFER/24DC/24DC/40

MSR178DP. Description. Features. Specifications

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

D6030S - D6030D INSTRUCTION MANUAL. D SIL 3 Switch/Proximity Detector Repeater Relay Output. Models D6030S, D6030D

VAMP 221. Table of Contents

USER MANUAL VIBRATION CONTROL RMA-POWER-BOX 107/230

PCT2000. User Manual. Precision current transducer 2000 A

BNS SERIES - COMPATIBLE SERIES AES SAFETY CONTROLLERS SELECTION CHART AVAILABLE STANDARD MODELS

ICPDAS FSM-510G Series Ethernet Management Switch Quick Start

MU110-6U. Analog output module 6 channel. User guide

Voltage Dip-Proofing Inverter

MULTI-POLE PHOTOVOLTAIC SYSTEMS. COMPACT and MODULAR Housing

KNX DALI Gateway Plus - User Manual

SMVector Additional I/O Module Installation and Operation Manual

Options for ABB drives, converters and inverters. User s manual FEA-03 F-series extension adapter

8-Port IP40 IEEE802.3af PoE Unmanaged Industrial Switch User s Manual

Operating instructions Safe AS-i input module ASIM-C-M About this document. Content

Safe timer relay/contact expansion modules

PGR-4300 MANUAL GENERATOR GROUND-FAULT RELAY

AS-i Safety Relay Output Module with Diagnostic Slave

Safety Control. FS1A Multi-function Safety Relay. Optional Parts. Connecting Tool. Marked Cable Tie. DIN Rail BNDN1000 Aluminum, 1m 35mm wide

Safety Control. FS1A Multi-function Safety Relay. Optional Parts. Marked Cable Tie. DIN Rail BNDN1000 Aluminum, 1m 35mm wide

Safety Control Relay Product Catalog

Operating and Installation Manual. EASYLAB Expansion modules Type EM-TRF for 230 V AC mains voltage

Residual Current Devices FRCdM Type B, B+ and Bfq Digital

Safety Relays 3TK2845 Multifunction Device

Safety Relay F 121 Emergency-Stop Relay, Safety Gate Monitor

63 to 125 A. Functions. Conformity standards. General characteristics. Changeover switches SIRCO VM1 changeover switches.

RS-232 Industrial Media Converter

Redundancy unit CP-A RU

Language of the manual

Making Hazardous Operations Safe and Productive

EX-RC1 Remote I/O Adapter

E-STOP relays, safety gate monitors

Transcription:

v Read through this instruction carefully before working on the switch, and keep this instruction for later reference v The images provided in this instruction book are for illustration purposes only and may not match the actual product exactly v This instruction is subject to change for product updates without prior notice Automatic Transfer Switch OTM_C20D Installation and Operation Instructions ABB Xinhui Low Voltage Switchgear Company Limited Jinguzhou Industrial Zone, Xinhui District, Jiangmen City, Guangdong Province, PRC Postal code: 529100 Tel: +86-750-6322200 Fax: +86-750-6677526 http://www.abb.com.cn 2TFR700031A1001-A

9 Appendix 9.1 Wiring diagram Figure 20 Wiring Diagram 16

8 Maintenance and troubleshooting 8.1 Maintenance To ensure the operation reliability of switches, regular switching tests should be performed (once every 3 months) to confirm normal function. 8.2 Troubleshooting No. Fault Description Fault Analysis Troubleshooting Method 1 Power supply functioning normally, but LED not ON Control unit power supply terminal not connected with switch wiring terminal Check and connect the switch wiring terminal. 2 Power supply LED functioning normally but Auto LED OFF, or no response with AUTO button pressed 3 Transition failure in case of faulty power supply 4 EMRG OFF function failure 5 Auto LED blinking with all other LEDs OFF No response from buttons Handle not pulled out or electrical padlock not removed 1. Switch not operating in AUTO mode 2. Both LN1 and LN2 malfunctioning 1. Check if the EMRG OFF signal is 24V DC 2. Too short duration of EMRG OFF signal DIP switch for poles number of power supply set to 00 6 I or II LED blinking Operation failure during switching, thus expected result not achieved Table 5 Troubleshooting Pull out the handle or remove the padlock, and then press the AUTO button. Make sure the switch is working in AUTO mode. Check and make sure both LN1 and LN2 are not malfunctioning simultaneously. Correctly switch on the EMRG OFF signal, which should only be 24V DC with the duration 1 s. Check if the DIP switch setup matches the phase number of switch power supply. Manually set the switch to Position O, and press the AUTO button to reset. Contents 1 SYMBOLS & TERMS... 1 1.1 USE OF SYMBOLS... 1 1.2 EXPLANATIONS OF ABBREVIATIONS AND TERMS... 1 2 PRODUCT OVERVIEW... 2 2.1 PRODUCT OVERVIEW AND PACKING... 2 2.2 OTM_C20D SWITCHING SEQUENCE...3 2.2.1 Line 1 Priority (default mode)...3 2.2.2 No line priority...3 3 QUICK START... 4 3.1 OPERATING THE SWITCH MANUALLY (LOCAL OPERATION)... 4 3.2 AUTOMATIC OPERATION... 5 3.3 LOCAL TEST OPERATION... 6 3.4 LOCKING... 7 3.4.1 Locking the electrical operation... 7 3.4.2 Locking the manual operation... 7 4 INTERFACE AND SETTINGS... 8 4.1 BUTTONS... 8 4.2 LEDS... 8 4.3 DIP SWITCH SETTING... 9 4.4 TERMINAL... 9 5 TECHNICAL DATA... 10 6 INSTALLATION... 10 6.1 INSTALLATION METHOD... 10 6.2 INSTALLATION DIMENSIONS... 12 7 OPTIONAL ACCESSORIES... 13 7.1 BRIDGING BARS... 13 7.2 TERMINAL SHROUDS... 14 7.3 AUXILIARY CONTACT BLOCKS... 14 8 MAINTENANCE AND TROUBLESHOOTING... 15 8.1 MAINTENANCE... 15 8.2 TROUBLESHOOTING... 15 9 APPENDIX... 16 9.1 WIRING DIAGRAM... 16 15

1 Symbols & Terms 7.2 Terminal shrouds 1.1 Use of symbols Hazardous voltage: warns about a situation where a hazardous voltage may cause physical injury to a person or damage to equipment. 1 OTS125T3 General warning: warns about a situation where something other than electrical equipment may cause physical injury to a person or damage to equipment. 3 2 Caution: provides important information or warns about a situation that may have a detrimental effect on equipment. Information: provides important information about the equipment. 4 OTS125T1 Figure 18 Terminal shrouds 7.3 Auxiliary contact blocks 1.2 Explanations of abbreviations and terms OTM_C20D LN1 LN2 EMRG OFF Automatic transfer switch, the type name Power supply line, the primary line Power supply line, the secondary line used in emergency cases Used to drive the automatic transfer switch transfers to the O position when receiving EMRG OFF signal. 0.75-2.5 mm2 18 14 AWG 0.8Nm AUTO TEST Automatic mode The switch performs switching cycle test as the pre-set program Table 1 Explanations of abbreviations and terms Hazardous voltage! The operation, installation and servicing of this appliance must be carried out by a qualified electrician applying the relevant rules of the art, Installation standards and safety regulations. Do not touch live parts. Danger! OA7G10 OA1G01 Contact NO NC I O II Max 2 pcs Figure 19 Auxiliary contact blocks OA1G10 OA8G01 Contact NO NC I O II Max 2 pcs 1 14

7 Optional accessories 7.1 Bridging bars 2 Product overview 2.1 Product overview and packing The OTM_C20D automatic transfer switches can be used as a source transfer switch in a three-phase or single-phase networks. Monitored conditions are, novoltage and phase-loss. You can operate the switch, either manually with the handle or automatically by the AUTO mode. The automatic operation modes include Line 1 priority and no line priority. 4 5 6 10 OTM32~125F2C20D OTM32~125F3C20D OTM32~125F4C20D OMZC03 OMZC04 8 1 3 7 2 6 Nm 6 Nm 9 Figure 1 OTM_C20D automatic transfer switch 1. Handle for manual operation 2. Place for auxiliary contact blocks 3. Push button 4. Mimic panel 5. Voltage sensing connections 6. Locking clip for padlock 7. Locking latch for releasing the handle and locking electrical control 8. Locking clip for locking manual operation 9. DIP switches 10. Connecting terminal 17 Number of conductors 2 Number of conductors 2 10-70 mm 2 00 AWG 10-70 mm 2, 8-00 AWG The standard package includes: 1.automatic transfer switch, 2.handle, 3.handle storage clip 4.terminal plug, 5.mounting kit Figure 17 Bridging bars 13 2

2.2 OTM_C20D switching sequence 6.2 Installation dimensions 2.2.1 Line 1 Priority (default mode) The switching sequence can be summarized in following steps: A fault occurs on LN1, while LN2 functions normally Transfer switch (Switch I) to the position 0 Transfer switch (Switch II) to the position II And the back switching sequence can be summarized in the following steps: The LN1 will start the normal functioning Transfer switch (Switch II) to the position 0 Transfer switch (Switch I) to the position I 2.2.2 No line priority Figure 2 Automatic Switching Sequences in OTM_C20D, Line 1 priority The switching sequence can be summarized in following steps: A fault occurs on LN1, while LN2 functions normally Transfer switch (Switch I) to the position 0 Transfer switch (Switch II) to the position II And the back switching sequence can be summarized in the following steps: The LN1 will start the normal functioning Transfer switch stays in position II A fault occurs on the LN2 Transfer switch (Switch II) to the position 0 Transfer switch (Switch I) to the position I Figure 3 Automatic Switching Sequences in OTM_C20D, No line priority 3 Figure 16 Dimensions 12

The DIN rail installation mode is as follows: First pry out the latch with an appropriate tool. 3 Quick start 3.1 Operating the switch manually (local operation) To operate the switch manually: 1. Attach the handle to the switch panel. You can attach the handle in any position. 2. When the handle is attached, the automatic transfer switch will automatically be in Manual mode and won t operate automatically in case of line failure. The Auto LED on the mimic panel is OFF. Figure 14 Installation of OTM_C20D, DIN rail After attaching the switch to the DIN rail, push the latch back to lock it. Figure 4 Operating the switch manually When the handle is inserted into the switch, the switch will enter Manual mode with the automatic operation disabled. Push back Figure 15 Installation of OTM_C20D, DIN rail After attaching the switch to the DIN rail, make sure you push the latch back to the lock position, otherwise the switch may fall off. Do not adjust wires when the transfer switch is being energized. Before the power-on operation of the transfer switch, please operate the switch manually to confirm it is in normal function. With the power supply function in normal without the handle inserted and EMRG OFF signals, the initially energized switch will enter AUTO mode and transfer to the main line. Keep the handle inserted if you do not want the switch to be in AUTO mode upon initial energization. 11 4

3.2 Automatic operation OTM_C20D must be in AUTO mode and the Auto LED is ON in order that the switch can perform automatic transfer cycles according to the pre-set operating mode. To operate the switch automatically: If the handle inserted, 1. Press handle locking clip and remove the handle from the switch. 2. Press AUTO button and the Auto LED will be ON, indicating AUTO mode. If handle is not inserted 1. If Auto LED blinks or OFF, press AUTO button and the Auto LED will be ON, indicating AUTO mode. 2. Automatic operation includes two operating modes: Line 1 priority (default setting) and No line priority. 5 Technical data Automatic transfer switch Parameters Rated operational voltage U e 220~240VAC(2P) 380~415VAC(3P/4P) 50~60 Hz Operating voltage range 0.8~1.2 U e Accuracy ±5% Operating angle 90 ( O-I, I-O, O-II, II-O) 180 ( I-O-II, II-O-I) OFF time 610 ms ± 10% Electromagnetic compatibility Class B Ingress Protection Rating IP20, front panel Rated impulse withstand voltage U imp 8 kv (6 kv for control circuit, disconnect the power line of the control circuit before the dielectric voltage withstand test) Operating temperature -25~55 Transportation and storage temperature Altitude -40~70 Max. 2000 m Table 4 Technical data 1 2 3 6 Installation 6.1 Installation method The switch can be installed using screws or a DIN rail. The fixed installation mode on the base board is as follows: Figure 5 operate the automatic transfer OTM_C20D to Auto mode Figure 13 Installation of OTM_C20D, screw M4 2 Nm 5 10

4.3 DIP switch setting The DIP switch is used to set the operation modes and poles of transfer switch. Figure 11 DIP switch No. Function Setting 1, 2 Pole 01 10 11 00 setting 2 poles 3 poles 4 poles Invalid setting 3 Mode 0 1 setting No line priority Line 1 priority Table 3 DIP switch 3.3 Local test operation In AUTO mode, Auto LED is ON and you can press the TEST button on the panel to lead it to TEST mode: Operation sequence: 1. Ensure switch in AUTO mode 2. Press the TEST button and the Auto LED will blink, indicating the activation of TEST mode. Under TEST mode, the automatic transfer switch will transfer by one cycle and finally return to its original position. e.g., when the switch is in Position I: Press the TEST button; the switch transfers to Position O to Position II to Position O to Position I. During process, pressing the TEST button again will be invalid until it returns to its original position. During TEST process, press the AUTO button will cancel TEST mode and return to AUTO mode. 3. After test, press AUTO button to return the automatic operation. The 3-bit DIP switch is used to control the switch for circuit testing, and the mismatch with the load power supply will result in testing and transfer failure. Therefore, carefully read this guide and set correct parameters based on the actual situation before using this product. 4.4 Terminal EMRG OFF: Input the 24VDC EMRG OFF signals (no distinction between the positive and negative) for at least 1s until the switch transfers to the O position and the EMRG OFF LED is on. At this time, the switch cannot enter the AUTO or TEST mode and only manual operation is allowed. After the signal is canceled, press "AUTO" to quit EMRG OFF mode. Figure 6 Local test of OTM_C20D In the test sequence, the main power supply circuit will be closed. If the test sequence is interrupted due to power failure, the automatic transfer switch will enter AUTO mode after power recovery. Figure 12 EMRG OFF terminal 9 6

3.4 Locking 3.4.1 Locking the electrical operation The switch can be padlocked in any position, causing that all operating modes and test operations are disabled and handle cannot be inserted. See below for operation: 4 Interface and Settings 4.1 Buttons Figure 9 Buttons of OTM_C20D 1 Figure 7 Locking the electrical operation 3.4.2 Locking the manual operation 2 φ 5-6 mm By default, the manual operation can only be locked in position O. The handle can be padlocked by pulling out the clip from the handle and placing the padlock on the handle. Maximum 3 padlocks. 3 4 AUTO button It can lead to AUTO mode. When the switch is in Test mode or fault status, press the AUTO button until the Auto LED on. TEST button It can lead to TEST mode. First it must on AUTO mode, then press the TEST button while the Auto LED blinking. You must press the AUTO button after the test is complete. 4.2 LEDs Figure 10 LEDs of OTM_C20D φ 5-6 mm Figure 8 Locking the manual operation LED Display Status description LN1/LN2 ON Power normally Blinking Phase loss OFF No voltage I/II ON Switch I or II closed OFF Switch I or II open Blinking Switching failure. Auto ON Transfer switch in AUTO mode Blinking Transfer switch in TEST mode or invalid setting OFF Transfer switch in manual mode EMRG OFF ON Received emergency signals OFF No emergency signals input Table 2 LEDs 7 8