DSTHM-2 COMBINED T AND RH DUCT TRANSMITTER. Mounting and operating instructions

Similar documents
DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

HPS-M -2 DIFFERENTIAL PRESSURE TRANSMITTER. Mounting and operating instructions

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

RXTH DUAL ROOM SENSOR / SWITCH

RXTP ROOM TEMPERATURE

CNVT-USB-RS485 MODBUS TO USB CONVERTER. Operating instructions

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

RTT2 ROOM TEMPERATURE SWITCH. Mounting and operating instructions

RТTH DUAL ROOM SWITCH

STR-3 STANDARD 3-PHASE 230 VAC TRANSFORMER CONTROLLER. Mounting and operating instructions

DPOM8-24/20 DIN RAIL POWER OVER MODBUS MODULE. Mounting and operating instructions

DWYER INSTRUMENTS, INC. Series AVUL Air Velocity Transmitter. Specifications - Installation and Operating Instructions.

Instruction Manual. T3110 T3110L T3110Ex

Duct humidity and temperature sensor for all HVAC duct applications. Designed for control and monitoring applications.

Application. Types Available. Duct sensor for air quality, temperature and humidity (optional) Datasheet

Output Signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power Supply DC V, ±10%, 0.3 W

Output Signal Active Note DC V. Electrical Data Power Supply DC V, ±10%, 1.4 W

GREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26

Carbon Monoxide Sensor - ModBus

DIFFERENTIAL PRESSURE TRANSMITTER with MODBUS interface Optional Input module

RHT-WM-485-LCD Transmitter and RHT-DM-485-LCD Transmitter

Output Signal. Temperature 22DTH-56M BACnet DC V, DC V. Electrical Data Power Supply DC V, ±10%, 0.7 W

TRANSDUCER T4311, T4411

Room unit with PPS2 interface

Output signal. 22DTM-16 BACnet DC V, DC V. Electrical data Power supply DC V, ±10%, 0.3 W

CDD4 Duct Carbon Dioxide Transmitter

Please Read Instruction Carefully Before Installation! Figure 1: A/CO2-DUCT

MU110-6U. Analog output module 6 channel. User guide

LED PANEL. User Manual Please read the instructions carefully before use LED-7TC. Innovation, Quality, Performance 15-

Page 1 MRK-D-0011, V2.0 Aeroqual SM50 User Guide

Data sheet GCM MOD GMM EC.1 Communications module Modbus for GMM EC

Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature with calibration certificates

Transmitters RHT-WM-485-LCD, RHT-DM-485-LCD and RHT-P LCD

GREISINGER electronic GmbH D Regenstauf, Hans-Sachs-Straße 26

DPA+ LCD. Application. Types Available. Differential Pressure Transmitter. Datasheet

Page 1 MRK-D-0011, V1.1 Aeroqual SM50 User Guide

InBin-P Pressure switches from 5 Pa Pa

ON/OFF HUMIDIFIER CONTROL (ROOM 0R DUCT SENSOR) WITH OUTDOOR TEMPERATURE RESET OVERVIEW WALL CONTROLLER INSTALLATION (TCY-BH-T-U)

TEMPERATURE AND HUMIDITY TRANSDUCER P18 TYPE USER S MANUAL

asense m III in industrial wall mounted housing / CO sensor with built-in general purpose controller

USER GUIDE PEL 8K / PEL 8K-M

B63/ NS MS. EtherNet/IP LINK

english S-5EC Potentiometer 5-step Operating Instructions Keep for reference! L-BAL-E265-GB 1608 Index 002

USER GUIDE PEL / PEL-M

LED PANEL. User Manual Please read the instructions carefully before use LED-212RGB TABLE OF CONTENTS. 1. Safety Instructions

Expansion module EM-BAC-MOD-01. Installation manual

OZONE SWITCH Model OS-6. OS-6 Features

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Programmable temperature transducer from Pt1000 sensor to current loop 4-20 ma Instruction Manual

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

EE160 - Humidity and Temperature Transmitter for HVAC Applications

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

EE671 - Miniature Air Flow Transmitter

Room sensors QFA4160 QFA41 D AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

TraceTek Leak Detection Master Module Installation Instructions TOOLS REQUIRED STORAGE

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Installation manual for for Schleifenbauer DPM3

OPERATION AND MAINTENANCE MANUAL

ETM-2050/ETM-2051 Service Manual

Temperature and humidity regulator H3020 H3021 H3023 H3027. Instruction Manual

INSTALLATION DKM-409 NETWORK ANALYSER WITH HARMONIC MEASUREMENT AND SCOPEMETER. Before installation:

thanos RS485 Modbus Application Functions Multifunction Room Operating Unit Datasheet

SAMURAI SCAN 50 LED-SC50D. User Guide. Innovation, Quality, Performance. Professional Entertainment Technology 19-

Soft Starter Remote Operator. Section 1.0 Introduction 1.1 Important user information General Manual description...2.

ADC7520 SERIES. 1600W Battery Chargers and Power Supplies

L Series Humidity/-temperature sensors for use in heating, ventilation and air conditioning Technical data Humidity

Chameleon Stand-alone

IGLOO IGLOO EASY INSTRUCTION MANUAL

PMCG - MANUAL PMCG ORIGINAL INSTRUCTIONS. Preservatech Europe sp z o.o. Równa 1, Bydgoszcz, Poland

USER S GUIDE. EE210 - Humidity and Temperature Transmitter for demanding Climate Control Applications GENERAL

SolConeX extra-low voltage flange socket

Installation manual plugs and connectors with screw connection (16/32 A)

LED W RGBA User Manual

HygroClip M22 Series. 2-wire loop powered humidity temperature transmitters INSTRUCTION MANUAL

1. Safety Precautions

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

RTD-NET Installation Instructions

T2214. Instruction Manual

Ultrasound Controller DP36 Level Switch PSF Manual

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

BW-108. Building Wash BW-108. User Guide. Advanced LED Technology

T2314, T2414. Instruction Manual

Please read the instructions carefully before use LED PYRAMID LED-904D. Innovation, Quality, Performance 15-

LZR - U920/-U921. LASER MEASUREMENT DEVICE with bidirectional bus communication. User s Guide for product version 0500 and more

Procon A1M. INSTALLATION MANUAL Version MITSUBISHI ELECTRIC FOR INSTALLERS

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

Model HU-224/225. Technical Information TI.224/ Humidity Transduce r FOR ADDITIONAL INFORMATION SEE HU-224/225 DATA SHEET

VC3000 Series Line Voltage Switching Relay Pack Controllers Installation Guide

LCD LCDS LCDRI CONTROLLER OPERATING MANUAL

Room unit with PPS2 interface

Configurable Network Paging Console. Product Instructions. Model: X-NPMI

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

Polymer Electric. Operating Instructions. Control Unit SG-TRS 3X8. Version 1

AGROWtEK Technology to Help You Grow

DP2500 DP0250. Differential Pressure Transmitter. Product Bulletin

EE80 Series. HVAC Room Transmitter and Switches for CO 2, Relative Humidity and Temperature EE80. Applications. Typical

Sapling Converter Box

60W Power over Ethernet Waterproof Adapter PoE IEEE BT Single Port Injector for Outdoor Application

Product manual plug, sockets and coupler 16 A.- Z0251

Air Quality Solutions

Transcription:

Mounting and operating instructions

Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 4 OPERATIONAL DIAGRAMS 5 WIRING AND CONNECTIONS 5 MOUNTING & OPERATING INSTRUCTIONS IN STEPS 5 OPERATING INSTRUCTIONS 8 VERIFICATION OF INSTALLATION INSTRUCTIONS 9 MODBUS REGISTER MAPS 9 TRANSPORT AND STOCK KEEPING INFORMATION 10 WARRANTY AND RESTRICTIONS 10 MAINTENANCE 10 MIW--EN-000-16 / 05 / 2018 www.sentera.eu 2-10

SAFETY AND PRECAUTIONS Read all the information, the datasheet, mounting and operating instructions and study the wiring and connection diagram before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product. For safety and licensing (CE) reasons, unauthorised conversion and / or modifications of the product are inadmissible. The product should not be exposed to abnormal conditions, such as: extreme temperatures, direct sunlight or vibrations. Long-term exposure to chemical vapours in high concentration can affect the product performance. Make sure the work environment is as dry as possible; avoid condensation. All installations shall comply with local health and safety regulations and local electrical standards and approved codes. This product can only be installed by an engineer or a technician who has expert knowledge of the product and safety precautions. Avoid contacts with energised electrical parts; always treat the product as if it is live. Always disconnect the power supply before connecting, servicing or repairing the product. Always verify that you apply appropriate power supply to the product and use appropriate wire size and characteristics. Make sure that all the screws and nuts are well tightened and fuses (if any) are fitted well. Recycling of equipment and packaging should be taken into consideration and these should be disposed of in accordance with local and national legislation / regulations. In case there are any questions that are not answered, please contact your technical support or consult a professional. MIW--EN-000-16 / 05 / 2018 www.sentera.eu 3-10

PRODUCT DESCRIPTION The series are combined duct transmitters which measure temperature and relative humidity. They are Power over Modbus supplied and all parameters are accessible via Modbus RTU. ARTICLE CODES Code Supply Connection Power over Modbus, 24 VDC RJ45 INTENDED AREA OF USE Monitoring duct temperature and relative humidity in HVAC applications TECHNICAL DATA Selectable temperature and relative humidity ranges Selectable temperature range: 0 50 C Selectable relative humidity range: 5 85 % Accuracy: ±0,4 C (0 50 C); ±3 % rh (5 85 % rh), depending on the selected parameter Option for uploading a new firmware via Modbus RTU Minimum airflow velocity required: 1 m/s Enclosure and probe material: ASA, grey (RAL9002) Protection standard: Enclosure: IP54, Probe: IP20 Operating ambient conditions: temperature: 0 50 C rel. humidity: 5 85 % rh, (non-condensing) Storage temperature: -10 60 C STANDARDS EMC Directive 2014/30/EC: EN 61326-1:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General requirements EN 61326-2-3:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 2-3: Particular requirements - Test configuration, operational conditions and performance criteria for transducers with integrated or remote signal conditioning WEEE Directive 2012/19/EC RoHs Directive 2011/65/EC MIW--EN-000-16 / 05 / 2018 www.sentera.eu 4-10

OPERATIONAL DIAGRAMS Input register 1 [%] 100 Input register 2 [%] 100 0 0 Min. range Max. range 50 T [ C] 0 5 Min. range Max. range 85 rh [%] WIRING AND CONNECTIONS Pins 1 & 2 Pins 3 & 4 Pins 5 & 6 Pins 7 & 8 24 VDC A /B GND Supply voltage (24 VDC) RS485, Modbus RTU communication, signal A RS485, Modbus RTU communication, signal /B Supply voltage, ground 24 VDC 8 mm A /B GND 8 mm 8 mm 8 mm 1 2 3 4 5 6 7 8 RJ45 1 2 3 4 5 6 7 8 MOUNTING & OPERATING INSTRUCTIONS IN STEPS Before you start mounting the duct transmitter, read carefully Safety and Precautions. 1. When preparing to mount the, bear in mind that the unit itself must be installed onto the outer surface of the duct both via fixing the flexible flange or directly the unit enclosure, while the probe must be inserted inside the duct, see Fig. 1 and Fig. 2 below. MIW--EN-000-16 / 05 / 2018 www.sentera.eu 5-10

Fig. 1 Mounting dimensions With flange Without flange 50 Ø 12 2x Ø 5 60 18,5 285 42,3 86,8 100 70 4x Ø 4,4 105 80 66 34,5 Fig. 2 Mounting position Correct Incorrect AIR FLOW AIR FLOW 2. Having selected the appropriate mounting location, proceed with the following steps: 2.1 Drill a Ø 13 mm hole into the duct and insert the probe. Apply an air-tight sealing between probe and duct. 2.2 Fix the flange onto the duct outer surface using the self-drilling screws delivered with the unit. If you do not intend to use the flange, insert the tube and fix the enclosure onto the duct. Mind the airflow direction (see Fig. 2 and Fig. 3). MIW--EN-000-16 / 05 / 2018 www.sentera.eu 6-10

Fig. 3 Mounting requirements 7,5*D (1) 3,5*D (1) D = Duct diameter ATTENTION Installation requirements: The must not be installed in turbulent air zones. Ensure sufficiently long settling zones upstream and downstream of the tapping point. A settling zone consists of a straight section of pipe or duct with no obstructions. Avoid installation near filters, cooling coils, fans, etc. The sensor will achieve the optimal result when the measurement is taken at least 7,5 duct diameters downstream and at least 3 duct diameters upstream from any turns or flow obstructions. ATTENTION Installation of the unit near high EMI-emitting devices may lead to faulty measurements. Use shielded wiring in areas with high EMI. ATTENTION Keep at least 15 cm distance between the sensor lines and the 230 VAC power lines. 2.3 Install the tube at the desired depth and, in case you use the flange, fix it via the plastic white screw in the flexible flange. 2.4 Unscrew the cover of the unit to remove it and insert the connecting cable through the cable gland of the unit. 2.5 Crimp the RJ45 cable and plug it into the socket, see Fig. 4 and section Wiring and connections above. Fig. 4 Wiring and connections 3. Customise the factory settings to the desired ones via the 3SModbus software or Sensistant (if necessary). For the default factory setting see Table Modbus register maps. MIW--EN-000-16 / 05 / 2018 www.sentera.eu 7-10

Optional settings If your unit is the first or the last unit on the Modbus RTU network (see Example 1 and Example 2), enable the NBT resistor via 3SModbus or Sensistant (Holding Register 30). If your device is not an end device, leave the NBT disabled (default Modbus setting). Example 1 Example 2 Slave 1 NBT NBT RX ТX Master NBT RX ТX NBT Slave 2 Master NBT Slave n Slave 1 Slave 2 Slave n 4. Close the enclosure and fix the cover. 5. Switch on the power supply. CAUTION Do not expose to direct sunlight! OPERATING INSTRUCTIONS Calibration procedure: Both the relative humidity and temperature sensor elements are factory calibrated. Recalibration is not necessary. Bootloader Thanks to the bootloader functionality, the sensor firmware can be updated via Modbus RTU communication. To enter Boot mode, put a jumper onto pins 3 and 4 of the P1 header and restart the power supply (see Fig. 5). Once Boot mode is activated, the firmware can be updated via SM Boot application (part of 3SModbus software suite) or Sensistant. Fig. 5 P1 header 1 2 3 4 5 1 2 3 4 5 Put a jumper onto pins 1 and 2 and wait for at least 5 seconds to reset the Modbus communication parameters Put a jumper onto pins 3 and 4 and restart the supply to enter bootloader mode MIW--EN-000-16 / 05 / 2018 www.sentera.eu 8-10

VERIFICATION OF INSTALLATION INSTRUCTIONS If your unit does not function as expected, please check the connections. MODBUS REGISTER MAPS INPUT REGISTERS Data type Description Data Values 1 Temperature signed int. Actual temperature level -300 700 50 50,0 C 2 Relative humidity Actual relative humidity level 0 1.000 1.00 100,0 % rh 3 Dew point signed int. Calculated dew point -700 700 20 20,0 C 4 10 Reserved, return 0 11 Output value 1 (T) Output value - temperature 0 1.000 12 Output value 1 (rh) Output value - relative humidity 0 1.000 13 Reserved, returns 0 14 Temperature alert flag 15 Relative humidity alert flag 16 Reserved, returns 0 17 18 Temperature range limit flag Relative humidity range limit flag 19 Reserved, returns 0 20 Humidity / temperature sensor fault HOLDING REGISTERS Flag indicates that measured temperature is outside set alert values. Set to 1 when the measured value is outside the temperature alert values defined by holding registers 20 and 21. Flag indicates that measured relative humidity is outside set alert values. Set to 1 when the measured value is outside the relative humidity alert values defined by holding registers 22 and 23 Flag indicates that measured temperature is outside set range limit values. Set to 1 when the measured value is outside the temperature range limit values defined by holding registers 14 and 15 Flag indicates that measured relative humidity is outside set range limit values. Set to 1 when the measured value is outside the relative humidity limit range values defined by holding registers 16 and 17 Flag indicates if the communication with the temperature and humidity sensor is lost 0 1 0 1 0 1 1.00 1.00 Data type Description Data Default Values 1 Device slave address Modbus device address 1 247 1 2 Modbus baud rate Modbus communication baud rate 0 6 2 3 Modbus parity mode Parity check mode 0 2 1 4 Device type Device type (Read only) = 1100 0 1 0 1 0 % 100 % 0 % 100 % Measured temperature is OK Measured temperature is too high/ low Measured rh is OK Measured rh is too high/ low Temperature range is OK Temperature range is too high/ low rh range is OK rh range is too high/ low 5 HW version Hardware version of the device (Read only) XXXX 0x010 HW version 1.00 6 FW version Firmware version of the device (Read only) XXXX 0x010 FW version 1.00 7 13 Reserved, return 0 14 15 16 17 Minimum temperature range Maximum temperature range Minimum relative humidity range Maximum relative humidity range 18 19 Reserved, return 0 20 21 22 23 Minimum temperature alert Maximum temperature alert Minimum relative humidity alert Maximum relative humidity alert Minimum value of the temperature range; cannot be set higher than max. temperature range minus 5ºC Maximum value of temperature range; cannot be set lower than min. temperature rang e plus 5ºC Minimum value of the rh range; cannot be set higher than max. rh range minus 5% Maximum value of rh range; cannot be set lower than min. rh range plus 5% Minimum temperature alarm value Maximum temperature alarm value Minimum relative humidity alarm value Maximum relative humidity alarm value 24 29 Reserved, return 0 30 Modbus network resistor termination (NBT) 2 = 3 = 4 = 5 = 6 = 2 = No Yes 4.800 9.600 19.200 38.400 57.600 115.200 230.400 8N1 8E1 8O1 0 (Max. range - 50) 0 10 10,0 C (Min. range + 50) 500 500 50 50,0 C 50 (Max. range 50) 50 20 20,0 % rh (Min. range + 50) 850 850 850= 85,0 % rh Min. temperature range Max. temperature alarm Min. temperature alarm Max. temperature range Min. relative humidity range Max. relative humidity alarm Min. relative humidity alarm Max. relative humidity range Set device as ending the line or not by connecting NBT 0 1 0 31 35 Reserved, returns 0. 36 Modbus registers reset 37 40 Reserved, return 0. Resets Modbus Holding registers to default values. When finished this register is automatically reset to 0 If you want to find out more about Modbus over serial line, please visit: http://www.modbus.org/docs/modbus_over_serial_line_v1_02.pdf 0 1 0 0 10 10,0 ºC 500 50 50,0 ºC 50 20 20,0 % rh 850 85 85,0 % rh NBT disconnected NBT connected Idle Reset Modbus registers MIW--EN-000-16 / 05 / 2018 www.sentera.eu 9-10

TRANSPORT AND STOCK KEEPING INFORMATION Avoid shocks and extreme conditions; store in original packing. WARRANTY AND RESTRICTIONS Two years from the delivery date against defects in manufacturing. Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities. The manufacturer bears no responsibility for any misprints or mistakes in this data. MAINTENANCE In normal conditions this product is maintenance-free. If soiled, clean with a dry or damp cloth. In case of heavy pollution, clean with a non aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completely dry. MIW--EN-000-16 / 05 / 2018 www.sentera.eu 10-10