EY-EM : Remote I/O module, ecolink

Similar documents
I/O module, universal, digital, S0 inputs, modu533

I/O module, digital and universal inputs, modu530

EYE 200: DDC single-room controller, ecos200

EY-RU : Room operating unit, ecounit

I/O module, digital outputs (open collector), modu551

I/O module, digital outputs (relays), modu550

I/O module, analogue outputs and universal inputs

EY-RC 500: Room automation station, ecos500

EY-RU : Room operating unit, ecounit

EY-IO 534: I/O module, analogue inputs with galvanic isolation, modu534

EY-RU : Room operating unit, ecounit

EY-RU : Room operating unit, ecounit

EY-RC 208, 209: Room automation stations, ecos208, 209

EY-RU 355: Room operating unit, ecounit355

EY-RC 311: Programmable controller, ecos311

EY-SU 358: Push-button unit for room operating unit, ecounit358

EY-AS 521: Compact automation station, modu521

modu : Local override and indicating units

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

modunet292: novanet-ethernet interface

EY-WS 500: Web server for moduweb Vision and moduweb500 BACnet networks

EY-AS 524, 525: Modular automation station, modu524/525

EY-AS 524, 525: Modular automation station, modu524/525

EY-CM 721: Communication module with EIA-232 and EIA-485 interfaces, modu721

EY-AS 525: Modular automation station, modu525

AVM 321, 322: Valve actuator

Non-communicating room controllers

Sauter Systems

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

RXM39.1. PL-Link IO Block. Desigo TRA. Use with PXC3 series room automation station

9.5 nominal torque 4.5 W 16 VA. Min. 30 nominal voltage Min. 30 Nm. Reversible with switch By mounting. MIN (minimum position)

ASV215BF152*: VAV compact controller for laboratory and pharmaceutical applications

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

RXB39.1. Room controller RXB. Communicating room controller for fan-coil applications FC-13

RXC39.5. Room controller. Building Technologies. Desigo RXC. Communicating room controller for fan-coil applications

Operating instructions. Standstill monitor A / / 2011

Content. Product Description

Non-communicating room controllers

FCU-4 FAN COIL CONTROLLER

Operating instructions. Speed monitor D / / 2014

EY-RU : Room operating unit with EnOcean wireless technology, ecounit

Temperature Controller (Heat Pumps)

EY-RU : Room operating unit with EnOcean wireless technology, ecounit

Overview of types. Technical data

Automation stations compact model

DESIGO RX Individual room controllers. for fan-coil systems, chilled ceilings and radiators, with LONMARK-compatible bus communications

Universal Modules. Synco 700. Extension modules for use with controls of the Synco 700 family. Use

Operating instructions. Switching amplifier DN0210 DN / / 2015

NMID. Remote control. SAPIM I/O number. SAPIM I/O number NBRN (RS485) ZM100. Relay, 24 VDC - + UO07 UI11 UI10 UI09 UI08 UI07 UI06 UI05 UI04 UI03 UI02

Universal Controller

Temperature controller Ducted systems

Extension module for lighting control

AIAS. Technical description

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

SRQ24A. Technical data. Safety notes. Rotary actuator for ball valves Torque 16Nm Nominal voltage AC/DC 24V Control: Open-close Running time 9s

Compact Universal Controllers

Heating Circuit Controller

LM24A-MOD. Cable 1 m, 6 x 0.75 mm 2 RJ12 socket

Datasheet. ECB-PTU Series. 1/14. BACnet B-ASC Powered Terminal Unit Programmable Controllers. Overview

IQ21x Series Controllers

RMZ782B RMZ783B. Extension Modules. Building Technologies HVAC Products. Synco 700. for heating controller RMH760B

AVM321S, 322S: Actuator SAUTER vialoq AVM 1000 with SAUTER Universal Technology (SUT )

FCU-4 FAN COIL CONTROLLER

OP10. Pre-programmed, configurable controller for simple applications

EY-RC 504/505: Room automation station, ecos504/505

RXB10.1. Room controller. Siemens Building Technologies Building Automation DESIGO RXB. for chilled ceilings and radiators with EIB bus communication

Expansion Module HZS 541-1S

QXA2000 QXA2001. Condensation Monitor QXA2001 QXA2000 AQX2000

Brief description. Type overview

TAC Xenta 301. Controller, Freely Programmable

ABB i-bus KNX Fan Coil Actuator, PWM, MDRC FCA/S , 2CDG110195R0011

MIC-2 MKII, Multi-instrument DATA SHEET

Datasheet RCUXXYY EAE KNX Room Control Unit RCUXXYY DT R1.0. General Description. EAE Technology Page 1/10

Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG R0011

MXIO. Compact I/O module. Summary. Application Compact I/O module for data acquisition and HVAC control systems. Function

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

AVF 125S: SUT valve actuator with spring return

RXL24.1. Room controller RXL. Communicating controller for chilled ceiling and radiator applications CC-02

ecounit : Room operating unit with EnOcean wireless technology

Heating Circuit Controller

TM172PBG42R Modicon M172 Performance Blind 42 I/Os, Ethernet, Modbus

Products no longer available

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Specification Sheet For electronically commutated motors

General information. Display. Supply voltage. Input current. Encoder supply. Power losses

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Functional data Factory settings Variable Setting Torque Inhibiting torque

SAX.. ACVATIX Electromotive actuators for valves. with a 20 mm stroke

TXM1.8T. Triac module Used for Thermic and motor-driven actuators (AC 24 V) TX-I/O

General information. Display. Supply voltage. Input current. Encoder supply. Output current

AB Axis Industries. Use

Products no longer available

TRACKER 240 SERIES. Load Cell and Weighing Indicators. A Precision Measurement Instrument with Outstanding Features

General information. Display. Supply voltage

XT-9100 Technical Bulletin

Brief description. Type overview

General information. Display. Supply voltage. Input current. Encoder supply. Output current

Technical data. Safety notes. Product features

CONTENTS CONTROLLERS room controllers room units control units PRODUAL 3 CATALOGUE

General information. Supply voltage. Input current. Encoder supply. Power loss. Memory

Transcription:

EY-EM 510...512: Remote I/O module, ecolink510...512 How energy efficiency is improved Optimum adjustment to applications by means of module technology. Reduction in wiring Features Part of the SAUTER EY-modulo 5 system family Regulation, control, monitoring and optimisation of operational systems, e.g. room automation or HVAC engineering Remote I/O module for ecos500 and modu521 Communicative connection of actuators to automation stations Can be located up to 500 m from automation stations EY-EM510F001 Technical data Power supply Power supply Current consumption Power consumption 24 V~, ±20%, 50...60 Hz 0.2 A, without load current from Triac and relay outputs 6.6 VA Triac outputs without load, 48 VA Triac outputs with rated load Power loss 5 W (typically approx. 0.5 W) Ambient conditions Operating temperature 0...45 C Storage and transport temperature 25...70 C Admissible ambient humidity 10...85% rh, no condensation Inputs/Outputs Analogue/digital inputs Type 0...10 V/O-I Ni1000/Pt1000 inputs Typ -20...100 C Relay outputs Type 0-I, NO contacts Load 1) Switching frequency 230 V~, 5 A (total max. 10 A) > 3 10 5 cycles Triac outputs Type 0-I, 24 V~/0.5 A Analogue outputs Type 0...10 V, 2 ma Interfaces and communication Interface Protocol Control Connection to ecos500 2) RS485 SLC From ecos500 or modu521 500 m (depending on type of cable) Construction Dimensions W x H x D Weight 105 95 60 mm 0.22 kg Standards and directives Type of protection 3) IP 00 (EN 60730) Protection class II (EN 60730-1) for EY-EM 510, III (EN 60730-1) for EY-EM 511, EY-EM 512 Environment class 3K3 (IEC 60721) CE conformity according to EMC directive 2004/108/EC 4) EN 61000-6-1, EN 61000-6-2 EN 61000-6-3, EN 61000-6-4 Low-voltage directive 2006/95/EC EN 60730-1 1) See the section Digital outputs (relays). 2) See the section Engineering notes 3) IP 20 with terminal cover (accessory 0900240020); IP 40 at front when mounted 4) EN 61000-6-2: In order to meet the European standard, the power cables for the inputs and outputs should not exceed 30 metres in length Right of amendment reserved 2015 Fr. Sauter AG 6.1 1/8

Overview of types Type Description EY-EM510F001 Remote I/O module, 24 V~, 3 relays, 3 Triacs EY-EM511F001 Remote I/O module, 24 V~, 3 Triacs EY-EM512F001 Remote I/O module, 24 V~, 2 Triacs Overview of I/O mix EY-EM 510 EY-EM 511 EY-EM 512 Relay 3 0 0 Triac 3 3 2 0...10 V Out 3 3 2 Ni1000/Pt1000 2 2 0 0...10 V In, Digital In 4 4 4 Accessories Type Description 0900240020 Terminal cover 0450573001 Transformer 230 V~/24 V~ 42 VA; for 35 mm top-hat rail (EN 50022) Description of operation Regulation, control, monitoring and optimisation of operational systems in HVAC engineering. The ecolink family is comprised of a range of remote I/O modules for operating on room controllers of the ecos 5 system family. ecolink modules can be used to expand the I/O mix of ecos 5 room controllers. Due to the positioning of the modules directly beside the actuators or sensors in the room and the digital RS485 connection to the ecos 5, the wiring can be reduced considerably. The inputs/outputs (I/Os) of the modules are controlled directly by the automation program of the ecos 5 room controller. No additional programming of the ecolink modules is required. The modules of the ecolink series 510...512 are typically used for fan coil units and to actuate valve drives or are used on VAV (variable air volume) controllers. Intended use This product is only suitable for the purpose intended by the manufacturer, as described in the Description of operation section. All related product documents must also be adhered to. Changing or converting the product is not admissible. Engineering notes The ecolink field modules can be assembled using a top-hat rail directly in the cabinet or at a suitable location in the system. The plant devices are connected using screw terminals. The work may only be carried out when the system is disconnected from the electrical supply. ) Note: In the case of the ecolink modules, the ground wire (MM) is connected with the technical ground (GND), the protective earth and the Common (c) connection of the RS 485 interface. On the EY-modulo 5 ecos, the technical earth is connected with the protective earth. When using an external 24 V~ transformer, one 24 V side is thus automatically earthed. If third-party devices are used, disconnection measures may be required to avoid a short circuit. Transformers with low outputs sometimes generate excess voltage which can destroy the ecolink modules. It is, therefore, essential that the transformer from the list of accessories in this product data sheet is used for outputs up to 42 VA. Transformers with a rating of 62 VA or above are uncritical. To this end, transformers of a good industrial quality can be used. The output voltage of the transformer, taking into account the full tolerance range of the mains voltage (230 V, ±10%), must always lie within the specified input voltage range of the ecolink modules. The max. admissible bus length depends on the cable type used and the correct termination with terminating resistors. For Ethernet CAT-5 cables, as well as IYST-Y cables, a bus length of up to 500 m is possible. Bus cabling must follow line topology. Star, tree or branch topologies are not recommended. On the ecos500 room automation station, a 3-core bus connection to the RS-485 B interface is made. Observe the correct polarity. The devices do not have internal terminating resistors. Parallel laying of sensor lines and high-power current-carrying cables is to be avoided. For the conduction of analogue signals, such as 0...10 V inputs/outputs and Ni/Pt1000 inputs, a separate grounding must be planned for every input and output from the ecolink module to the relevant sensor or actuator. Shared ground wires lead to measurement errors that may arise particularly with small measuring signals. 2/8 6.1 Right of amendment reserved 2015 Fr. Sauter AG

Addressing/baud rate Up to 16 modules can be connected to a bus line. These must be addressed uniquely. An 8 DIL switch is planned to this end. S1: 1-8: Valid address range: 1-16. Address 15 is set as an example in the image. The baud rate is fixed at 115 kbaud. Fitting and power supply ecolink field modules are compact units suitable for wall mounting or for DIN 43880 installation on a 35 mm top-hat rail. The plant devices are connected using screw terminals. The following conditions must be observed: Connection may only be performed when the system is disconnected from the electrical supply. The unit must be protected against contact. The ground terminals are connected internally to the earth connection (PELV electrical circuits). Protective earth is connected to the relevant terminal. Cross-section of the wire: min. 0.8 mm² (AWG 18), max. 2.5 mm² (AWG 13), taking standards and national installation regulations into account. Communication wires must be laid professionally and must be kept at a distance from other live wires. In series to the terminal LS, the 24V~ power supply, a suitable external protection in accordance with applicable installation regulations is to be included. Special standards such as IEC/EN 61508, IEC/EN 61511, IEC/EN 61131-1 and -2 were not taken into account. Local requirements regarding installation, usage, access, access rights, accident prevention, safety, dismantling and disposal must be taken into account. Installation standards EN 50178, 50310, 50110, 50274, 61140 and similar must be observed. For further information, see the fitting instructions P100007169. Terminal cover B12144 Accessory 0900240020. When the cover is on, together with the ecolink module, it ensures protection class IP 20. When mounted, the protection class on the front is IP 40. Technical specification of the inputs and outputs Inputs In the full version, 6 inputs are available: 2 Ni1000/Pt1000 and 4 analogue inputs for active signals. If the analogue inputs (0...10 V) are to be used as digital inputs, these are to be switched against the 15 V external terminal. With this circuitry, the inputs are defined as digital inputs via CASE Tool. These 15 V are intended exclusively for the digital input. Right of amendment reserved 2015 Fr. Sauter AG 6.1 3/8

Type of inputs: (software coding) Protection against external voltage: Ni/Pt/U/DI Resolution Scan rate Update rate Measuring ranges: Voltage (U) Current (I) (via ext. R) Temperature: Ni1000 Resolution Pt1000 Resolution Digital input Ni1000 (DIN 43760) Pt1000 (IEC 751) Voltage measurement (U) Current measurement (I) (with external resistance) Digital input (DI) ±30 V/24 V~ (without destruction) 10 bits 100 ms (analogue/digital values) 300 ms (EY-modulo 5 ecos) 0 (2)...10 V= 0 (4)...20 ma -20 +100 C < 0.5 K -20... +100 C < 0.5 K Temperature measurement (Ni/Pt) Potential-free contacts, with 15 V connection. As a counter input, max. 2 Hz (min. pulse duration 250 ms) The Ni/Pt1000 sensors are connected using two wires between one of the input terminals and a ground terminal. The inputs require no calibration and can be used directly. Line resistance of 2 Ω is pre-compensated as standard. With the correct line resistance of 2 Ω (cable cross-section 1.5 mm²), the power cable (wire) may be no more than 85 m. Larger line resistances can be compensated by the software. The input circuitry is designed to ensure that the connected sensors are resolved to the nearest 1 Ω with the 10-bit AD converter in the aforementioned measuring range. Voltage measurement (U) The voltage to be measured is connected between an input terminal and a ground terminal. The signal must be potential-free. The internal resistance R i of the input (load) is 100 kω. Current measurement (I) A current measurement 0(4) 20 ma is possible via external resistance (e.g. 500 Ω). The current to be measured is connected parallel to the resistance at one of the input terminals and a ground terminal. The current signal must be potential-free. A separate ground terminal must be used for the current measurement. Otherwise, zero-point shifts may lead to imprecise measurements in the case of other measuring signals. Digital inputs (DI) The information (alarm/status) is connected between an input terminal and the 15 V external terminal. If a contact is open, this usually corresponds to an INACTIVE state (bit = 0). If a contact is closed, there is an ACTIVE state (bit = 1) and 15 V is applied at the input, giving a current of approximately ~0.3 ma. Every input can be defined individually as an alarm or a status by setting software parameters. Outputs In the full version, 9 outputs are available: 3 relays, 3 Triacs, 3 analogue (0...10 V) The outputs are updated by the ecos system (EY-RC 500) every 200 ms. Digital outputs (relay) Number of outputs Type of outputs Load on outputs Switching frequency Max. 3 (DO) Relay, normally-open contacts (0-I) 230 V~/5 A > 3 10 5 cycles Switching voltage 24...250 V The relay contacts are intended to actuate FCU fans. The relays have an increased start-up current compatibility. Peak inrush current at relay contact NO (work contact) 80 A for a maximum of 20 ms. The feed is via the shared terminal 24. In the operating status, the total current across this terminal may not exceed 10 A. The digital outputs can be defined for single- or multi-layered functions. Real feedback is only possible via digital inputs (BACnet COMMAND FAILURE) 4/8 6.1 Right of amendment reserved 2015 Fr. Sauter AG

Digital outputs (Triac) Number of outputs Type of outputs Max. 3 (DO) Triac, normally-open contacts (0-I Load on outputs 24 V~/0.5 A (resistive load) The actuator to be switched (e.g. thermal actuator) is connected directly to the Triac terminals. The Triacs are earthed and can be defined for single- or multi-level functions. Real feedback is only possible via digital inputs (BACnet COMMAND FAILURE) For thermal actuators, the power supply can be taken from the LS terminals. Analogue outputs Number of outputs Type of outputs Load Settling time Resolution Max. 3 (AO) 0(2)...10 V 2 ma 1 s 0.1 V Signal deviation < +4% of the set value The output voltage is taken from between the relevant output terminal and a ground terminal. The outputs are designed as push-pull outputs with active sink capability. Every output can be subjected to a load of 2 ma. The analogue output is short circuit-proof and grounded but not protected against external voltages. Permanent short-circuiting of multiple outputs leads to their thermal destruction. There is still protection against static discharges. LED indicator Status LED off Green light Flashing green Red light Flashing red Pulsating red Description Device out of service Device in operation Device is communicating with the ecos500 but is not being addressed Device is not functional (no program loaded) Device is not communicating with the ecos500 Internal device error Orange light Power-up phase, configuration The multi-colour LED on the ecolink module indicates the operating status. Start-up behaviour/monitoring functions The communication between the ecos500 and the ecolink modules is monitored. If the communication fails for longer than the 10s monitoring time, the affected ecolink modules switch to the safety status. The data points in the ecos500 are marked with the unreliable state. All outputs of the affected ecolink modules are switched to the defined value for the safety state ( relinquish default ). 0-I transitions (i.e. not actuated actuated) of relays and Triacs are delayed by 1s. This applies both when reaching and when leaving the safety state. This can prevent damage due to immediate switchovers of actuators such as window blinds. The inputs of the affected modules remain frozen on their last value while the safety state is in force. Additionally, if there are internal device errors, appropriate data points are mapped via the Reliability property. The start-up behaviours (power-up) of the ecos500 and ecolink are different. The power-up timer parameter in the ecolink (default value = 1 s) defines the waiting time of the ecolink until the communication monitoring starts. This parameter can be set individually for each ecolink module (value range 1...254 s). Settings are made using the SAUTER CASE Suite software. Until the power-up timer runs out, the outputs will be maintained in the same manner as when the device is without power. The power-up timer parameter can be used to define a start-up sequence for the ecolink modules or to synchronise the start-up behaviour with the ecos500. A distinction is made between the following operation behaviours: a) ecos500 in operation, ecolink module power-up The ecolink module maintains its outputs in a powerless state during power-up. If the ecos500 detects the ecolink module, communication with this module starts immediately. After the parameterised power-up timer has elapsed and communication with the ecos500 is successful, the module Right of amendment reserved 2015 Fr. Sauter AG 6.1 5/8

switches to normal operation. If communication with the ecos500 cannot be established within the monitoring time, the module switches to the safety state. b) ecos500 and ecolink module power-up Start-up proceeds in the same manner as the process described under a). Because ecos500 start-up takes longer than the monitoring period, the ecolink modules will enter the safety state until the ecos500 has started completely, after which they switch to the normal mode. If this is not desired, the power-up timer parameter can be set to a value > 120s. c) ecolink in operation, ecos500 power-down A power-down of the ecos500 has the same effect as an interruption in communications (see communication monitoring). If the ecos500 is then powered up, communication with the ecolink modules is automatically established. The modules leave the safety state as previously described. Integration of ecolink modules via CASE Suite The ecolink modules are engineered using CASE Suite. Depending on whether the ecos500 is designed for one, two or four function segments, the device addresses 1-16, 1-8 or 1-4 are displayed in a table. In the case of two or four segments, the device addresses are mirrored. These addresses can then each be assigned with an ecolink module. Data points are then defined and assigned to the relevant modules with their channel connections. This allows the inputs and outputs to be mapped directly to BACnet data points. ecos500 device addresses 1 segment 2 segments 4 segments 1 2 1=9 3 2=10 4 3=11 1=5= 9=13 5 4=12 2=6=10=14 6 5=13 3=7=11=15 7 6=14 4=8=12=16 8 7=15 9 8=16 16 Additional information Fitting instructions P100007169 Declaration on materials and the environment MD 92.845 Dimension drawing Connection diagram EY-EM510 EY-EM511 EY-EM512 Disposal M11463 A10653 A10654 A10655 When disposing of the product, observe the currently applicable local laws. More information on materials can be found in the Declaration on materials and the environment for this product. 6/8 6.1 Right of amendment reserved 2015 Fr. Sauter AG

EY-EM 510 connection diagram 4 AT I I max max 5 A 10 A 10 AT 1) 50...500 Ω A10653a EY-EM 511 connection diagram Right of amendment reserved 2015 Fr. Sauter AG 6.1 7/8

EY-EM 512 connection diagram Dimension drawing Fr. Sauter AG Im Surinam 55 CH-4016 Basel Tel. +41 61-695 55 55 www.sauter-controls.com 8/8 6.1 Right of amendment reserved 2015 Fr. Sauter AG