ELSETA IOMOD 8DI8DO. User manual. Elseta 3/2017 V1.0

Similar documents
ELSETA IOMOD 8DI8DO. User manual. Elseta V1.0

DKG-210 UNIVERSAL INTERNET GATEWAY UNIT

ICF-1150 Series Quick Installation Guide

Hardware Reference IO/5640. Analog/Digital I/O-Extension

ICF-1150 Series Quick Installation Guide

K107A / K107B Half-duplex RS485 serial bus with 3-point insulation

HARDWARE MANUAL MMS100. M-BUS TO MODBUS GATEWAY Series 07 / 2017 MIKRODEV_HM_MMS100_EN

NetBiter I/O Extender User Manual

RS485 MODBUS Module 6RO

SDM-6RO. Expansion Module 6 relay outputs. Manufactured for

RTU300 SERIES HARDWARE MANUAL

AS-i Safety Relay Output Module with Diagnostic Slave

RS 485 Mini Modbus 1AO

SDM-8AO. Expansion Module 8 analog outputs. Manufactured for

RS485 MODBUS Module 8I8O

RS485 MODBUS Module 8AO

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

RXTP ROOM TEMPERATURE

AS-i Safety Relay Output Module with Diagnostic Slave

Operating Manual. English. Digital-Analog Converter DACON8-UMB.

MP211 HARDWARE MANUAL

SATEL I-LINK 100 MB I/O-converter User Guide, Version 1.1

USB to RS232 Converter USB-013 (Rev3) User s Manual Ver. 1.2 HuMANDATA LTD.

USER MANUAL. Longo programmable controller LPC-2.MC8 Main module. Version 10

Operating Manual UMB ISO Converter ISOCON Order Number: 8160.UISO

ABB Drives. User s Manual. Modbus Adapter Module RMBA-01

USER MANUAL. WBV412U01 AC voltage transducer

DXTH DUCT SENSOR / SWITCH FOR TEMPERATURE AND HUMIDITY. Mounting and operating instructions

P3-SCM. General Specifications

INSTALLATION MANUAL. LC 200 Electronic Overload Guard. Software versione PW0501 R 0.3

RST ROOM TEMPERATURE TRANSMITTER. Mounting and operating instructions

Anybus Communicator STARTUP GUIDE. IIoT. SP en-us ENGLISH

RS485 MODBUS Module 16I-M

Data sheet GCM MOD GMM EC.1 Communications module Modbus for GMM EC

Industrial 2-port RS422/485 Modbus Gateway

RXTH DUAL ROOM SENSOR / SWITCH

Fieldgate SFG500. Technical Information. Intelligent Ethernet/PROFIBUS gateway

CMU 100 RS485 to 7x, 6x, 5x, 4x Multimode Fiber Optic Star Coupler User Manual

USER MANUAL. WBI414F21 AC current transducer

CONTROL MICROSYSTEMS SDI-12 Interface Module. Hardware Manual

MGate MB3000 Modbus Gateway User Manual

DF PROFI II PC/104-Plus

ACCESS 9340/9360 Meter Input/Output Module

MODEL CIO-EN MODBUS/TCP, MODBUS/RTU I/O MODULE

CANx / LoRa 433 MHz 8 x Analog inputs / Digital ouputs

USER MANUAL FOR FIOA-0402-U-16

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

MC 11 EB-2 Power supply cabinet with external bus, AC version

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Modbus communication module for TCX2: AEX-MOD

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

Features and Benefits. Certifications

Technical Documentation

XPSMF35. Product data sheet Characteristics. Preventa safety PLC compact - Profibus DP protocol. Main. Complementary. Safety module name

User Manual Gateway component for EtherNet/IP

IntesisBox Modbus Server KILSEN KSA-7xx. User s Manual 08/2013 r1.2 eng

See instructions to download and install the latest version of LinkBoxMB and the user's manual at

USER MANUAL. WBI412F41 AC current transducer

MVS RAIL ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

CEM M-RS485 INSTRUCTION MANUAL (M014B A)

General Specifications. P2-SCM Serial Communications

User Manual for TeraRanger Evo single point distance sensors and backboards

MGate MB3000 Modbus Gateway User s Manual

RS485 MODBUS Module 8I8RO

Industrial RS-232/ RS-422/ RS-485 over Ethernet Media Converter

Instruction Manual IF2004/USB. 4-Channel RS422/USB Converter

Intech Micro 2300-A8VI analogue input station MODBUS RTU slave application supplementary manual.

Industrial 1-port RS422/485 Modbus Gateway

BARIX IO12. I/O to RS-485 Modbus converter for commercial interfacing, control and home automation applications PRO D UCT MANUAL. Version: 2.

Manual Industry Interfaces

RAD-DO8-IFS. I/O extension module, eight digital transistor outputs. Data sheet. 1 Description

RTU511. Binary Output 23BO62. Characteristics. Application. Data Sheet Binary Output 23BO62. The binary output is made via relay contacts.

Dupline. Data Logger. Types G , G Product Description. Ordering Key G Type Selection. Input/Output Specifications

iologik R1200 Series User s Manual

MGate TM EIP3000 DF1 to EtherNet/IP Gateway User s Manual

DPOM8-24/20 DIN RAIL POWER OVER MODBUS MODULE. Mounting and operating instructions

SDM-8I8O. Expansion Module 8 digital inputs, 8 digital outputs. Manufactured for

OTB1S0DM9LP I/O distributed module OTB - Modbus non isolated serial link m

Island bus expansion module

PCAN-MicroMod Digital 1 & 2 Application-specific PCAN-MicroMod Motherboard. User Manual V1.10.0

Installation and commissioning guide SmartLink Host Communication Module (HCM-GPU)

Intech Micro 2300-RTD6 analogue input station MODBUS RTU slave application supplementary manual.

MM-IM. Large works automation And data gateway. PRODUCT DATASHEET

PCAN-Router FD Universal, programmable Converter for CAN FD and CAN. User Manual. Document version ( )

SD328AU68S2 motion control stepper motor drive - SD328 - <= 6.8 A

iologik E1200H Series

UNIVERSAL TRANSDUCER AR594

TCF-142 Quick Installation Guide

TP32MTT.03 TP32MTT [ GB ] Probes for soil thermal profile measurement

Operating Guide MODBUS (RTU) Communications Option IM/L150 MOD_2. Level Indicator L150 and L160

Installation and Maintenance Manual IM 969-5

DF PROFI II CPCI. Installation Instructions V Project No.: 5302 Doc-ID.: DF PROFI II CPCI KUNBUS

DF PROFI II PCIe. Installation Instructions V Project No.: 5302 Doc-ID.: DF PROFI II PCIe KUNBUS

User Manual Revision English

RAD-DI8-IFS. I/O extension module with 8 digital inputs or 2 pulse inputs. INTERFACE Data sheet. 1 Description

Intech Micro 2300-RO4 analogue input station MODBUS RTU slave application supplementary manual.

USER MANUAL Z-8NTC 8 CHANNELS NTC TEMPERATURE SENSOR CONVERTER WITH USB / RS485 PORT AND MODBUS RTU PROTOCOL

See instructions to download and install the latest version of LinkBoxEIB and the user's manual at

PCAN-Repeater DR CAN Repeater for the Decoupling of Bus Segments. User Manual. Document version ( )

XPSMF40. Main. Safety module name. Monitoring safety detection discrete input Monitoring safety dialogue discrete output

Transcription:

ELSETA User manual Elseta 3/2017 V1.0

COPYRIGHTS AND TRADEMARKS Elseta is UAB Aedilis trademark that identifies UAB Aedilis manufactured products. All of the products copyright belongs to "Aedilis. These documents and the product properties can not be changed without company Aedilis' knowledge and written consent. User manual may be modified by company Aedilis' without additional notice. DECLARATION OF CONFORMITY (in accordance with ISO / IEC Guide 22 and EN Section 45014) Manufacturer: UAB Aedilis Address of the manufacturer L. Zamenhofo st. 5 LT Vilnius, Lithuania We claim that: The device Conforms to the following standards: EMC: Radiation EN 55022 (Class A) 1 emitted radiation (30-1000MHz) Second radiation conductors (0.15-30MHz) EN 50082-1 immunity test 1 IEC 801-3: Radio-frequency electromagnetic field 2 IEC 801-2: Electrostatic discharge. 3 IEC 801-4: Quick periodic electrostatic discharges Additional information: "The device complies with the Low Voltage Directive 73/23 / EEC and EMC Directive 89/336 / EEC. Device assembly complies with the RoHS Directive. Manufacturer contact: Equipment quality controller UAB Aedilis " Address: L. Zamenhofo g. 5, LT 06332, Vilnius, Lithuania Phone: +370 5 2742707 E-mail. Email: support@elseta.com V1.0 ELSETA

SAFETY REQUIREMENTS This equipment Operating notes, which must be met for your personal safety, as well as to avoid damage to the equipment. These notes are marked with a warning triangle symbol and the various degrees of risk of falling within signs. All work related to electronic systems design, installation, commissioning, adjustment and maintenance should be carried out in accordance with the safety requirements. EQUIPMENT S MANUAL USES SYMBOLS Danger - important notice, which may affect the safety of the user or device. Warning of the danger. The work may be performed only by a qualified professional. Equipment installation, commissioning and maintenance may only Attention be performed - notice on by possible a qualified problems professional. that may If the arise safety in individual notes cases. this manual, the term refers to persons qualified specialists authorized to perform commissioning, grounding and labeling devices, systems and circuits. The person must: Be aware of occupational safety in the workplace. Information Notice - the information that is useful advice or special places. Need to understand the equipment components. Electrical equipment. Have the knowledge and skills to identify a component beneath the voltage. To maintain the equipment necessary to always turn off the power supply before installing or dismantling works. It must be in mind that even though alone equipment, but can have a common ground connection. Always before connecting the power supply, cables and interconnect components must be inspected. This product can not be implemented, or resold to install in areas that are high-security as nuclear power plants, aircraft navigation, military equipment, transport traffic in management. In areas where equipment failure can result in of nature and human injury. Do not operate the equipment in extreme weather conditions, as they may affect the operation of the equipment. V1.0 ELSETA

TABLE OF CONTENTS COPYRIGHTS AND TRADEMARKS...2 DECLARATION OF CONFORMITY...2 SAFETY REQUIREMENTS... 3 EQUIPMENT S MANUAL USES SYMBOLS...3 TABLE OF CONTENTS... 4 1. Introduction... 5 2. Features... 5 3. Device working information...5 a. MODBUS working information...5 Supported MODBUS functions...6 Modbus registers... 6 Testing With THE VINCI software...6 b. IEC 60870-5-103 working information...7 IEC 60870-5-103 telegram description...8 Testing With THE VINCI software...9 4. Technical information... 10 5. Mounting and installation guide...11 a. RS485 interface...11 b. inputs... 11 c. outputs...12 6. Configuration over USB...13 a. Driver installation... 13 b. IOMOD configuration with PuTTY terminal...14 c. Main Menu... 15 d. Protocol simulator... 15 e. Firmware upgrade over USB...16 7. Information of the equipment manufacturer...17 8. Document history... 18 V1.0 ELSETA

1.Introduction is small sized stand-alone Modbus (RTU) or IEC 60870-5-103 digital input and digital output controller. IOMOD is used for industrial applications, where digital signaling is used and robust communication is needed. IOMOD is ideal solution for applications such as data acquisition, observation, control, process monitoring, testing and measurement at remote places. It is controlled over Modbus or IEC 60870-5-103 protocol, and can be used with any SCADA system. 2.Features 8 digital inputs with configurable active signal polarity, or input inversion 8 digital open collector outputs for relays Galvanically isolated inputs and outputs Configurable over USB Drag And Drop firmware upgrade over USB RS485 communication LED input / output indications, + Data transmission (Rx and Tx) indication. Spring contact connectors Small sized case with removable front panel DIN rail mount Operating temperature Power Requirements: 12-24 VDC 3.Device working information uses Modbus (RTU) or IEC 60870-5-103 protocol over RS485 interface. Protocol used by device can be changed by uploading corresponding firmware. Default communication settings are: 9600 baudrate, 8N1, Slave address - 1. MODBUS working information To read output status, send 01 Modbus command (Read Coils) with resolution of first register (0), and size of 8. Returned value will show all 8 output states (1- turned On, 0- turned Off). To read input status, send 02 Modbus command (Read Discrete Inputs) with resolution of first register (0) and size of 8. Returned value will show 8 input states. To turn single output on or off, send command 05 (Write Single Coil), with output address (0 to 7). To turn output on send hex value FF00; to turn off hex value 0000. To turn multiple outputs on or off, use command 15 (Write Multiple Coils), and send binary coded value for 8 coils at address (0) and length 8. To invert input states by software, or to use pull-up resistors on inputs, configure device over USB terminal. Useable Modbus commands shown in table below. V1.0 ELSETA

Supported MODBUS functions 01 (0x01) Read Coils Status Reads status of relays (Off or On). has 8 digital outputs from address 0 to address 7. 02 (0x02) Read Discrete Inputs Reads status of digital inputs (Off or On). has 8 digital inputs from address 0 to address 7; These inputs are active-high by default; user can turn on pull-up resistors (through USB) to these inputs to make them active-low. 05 (0x05) Write Single Coil Sets single digital output On or Off. Output addresses from 0 to 7 (first output address 0, last output address 7). 15 (0x0F) Write Multiple Coils Sets multiple digital output On or Off. Output addresses from 0 to 7 (first output address 0, last output address 7). Modbus registers Function Register Name Description Values range 01 00000-00007 Read Coils Status Returns Output status 0-255 (decimal) 02 00000-00007 Read Discrete Inputs Returns Input status 0-255 (decimal) 05 00000-00007 Write Single Coil Forces single Output 0000 / FF00 (off/on) 15 00000-00007 Write Multiple Coils Forces multiple Outputs 0-255 (decimal) Testing With THE VINCI software To test IOMOD with default settings, user connects device through RS485 to Modbus master. Example using The Vinci Expert device as serial interface converter and adapter to PC with The Vinci software. Default settings for Modbus 9600 baudrate; 8 data, no parity, 1 stop bit. When opening The Vinci software, choose Modbus serial Master mode. In settings tab, choose station number (default 1); configure tags (as described in section 2. Device working information); Press start and go to Statistic tab: V1.0 ELSETA

Fig. 3.1 V1.0 ELSETA

4.Technical information System 1. 2. 3. 4. Dimensions Case Working environment Working temperature 101 x 119 x 17.5, mm ABS, black Indoors -20 +70 C 5. Recommended operating conditions 5 60 C and 20 80%RH; 6. 7. Configuration Firmware upgrade USB USB mass storage device 8. 9. 10. 11. Electrical specifications Inputs Outputs Power Power Supply Current consumption 8 X 3kV isolated 12-24VDC; Selectable inversion. 8 X 3kV isolated open collector outputs (300mA each, Max 50V); 9V to 33V 130 ma V1.0 ELSETA

5.Mounting and installation guide a. RS485 interface has integrated 120Ω termination resistor which can be enabled or disabled over USB configuration. It is recommended to use termination at each end of the RS485 cable. See typical connection diagram on Fig. 5.1. Fig. 5.1 has 1/8 Unit load receiver which allows to have up to 256 units on line (compared to standard 32 units). To reduce reflections, keep the stubs (cable distance from main RS485 bus line) as short as possible when connecting device. b. inputs Typical application of inputs is shown on Fig. 5.2. When default configuration for inputs is applied, user will see inputs connected to +12-24V as high or state 1 and input status LED will glow. Fig. 5.2 V1.0 ELSETA

User also can configure to enable pull-up resistors (function is applied for all inputs) and software input inversion. With this configuration, user will see inputs connected to 0V (see Fig. 5.3) as high or state 1, input status LED will NOT glow. Fig. 5.3 c. outputs has 8 open collector digital outputs. Internal clamp diodes are connected to each output which makes ideal for driving inductive loads like relays. Maximum 300mA per output is allowed. For higher loads outputs can be connected in parallel. Make sure your power supply can provide enough power. Typical application of outputs is shown on Fig. 5.4 Fig. 5.4 V1.0 ELSETA 10

6.Configuration over USB a.driver installation Device requires USB drivers to work as virtual com port. First-time connection between device and computer could result in Device driver software was not successfully installed error. Fig. 6.1 User then manually installs drivers by selecting downloaded driver folder: Go to Control Panel -> Device Manager; Select failed device; Press Update driver software ; following screen should appear: Fig. 6.2 Select x86 driver for 32bit machine, or x64 for 64bit machine. If not sure, select root folder (folder in which x64 and x86 lays inside). V1.0 ELSETA 11

Fig. 6.3 b.iomod configuration with PuTTY terminal Configuration of IOMOD device is done through CLI (Command Line Interface) on virtual COM port. Drivers needed for MS Windows to install VCOM will be provided. To open up CLI simply connect to specific V-COM port with terminal software (advised to use PuTTY terminal software. If other software is being used, user might need to send <return> symbol after each command). When connected user should immediately see main screen: Fig. 6.4 Navigation is performed by sending number to terminal. User then proceeds by following further onscreen instructions. For example, to set Baudrate, press [2] to enter Baudrate screen; press [1] to edit; enter new configuration; press [RETURN] to save, or [ESC] to cancel changes. When done, press [0] (exit) before disconnecting device. Default values is set by pressing [6] on main screen, and confirming changes [1]. If accidentally closed the terminal window, user can connect terminal program again, and press any key on keyboard to show up main menu. V1.0 ELSETA 12

c. Main Menu Menu Name Function Values Default Values 1. Slave Address Modbus Slave address / ID 1-247 (default: 1) 2. Modbus Baudrate Modbus Baudrate 100-256000 (default: 9600) 3. Data, Stop and Parity bits Data, Stop and Parity bits 8+1 or 8+2 (Data+Stop), None, Odd, Even, Mark, Space (Parity) 8+1, None 4. RS485 Terminating Resistor 5. Input pull-up enable 6. Input State Inversion RS485 120 Ohms Terminating Resistor Enables input pull-up resistor. Inputs then activated by low signal Input inversion (Inverts input states in modbus) 0-1 (off/on) (default: 0) 0-1 (off/on) (default: 1) 0-1 (off/on) (default: 0) 7. Set Default Settings Sets Default Settings (1 to confirm, 0 to cancel) - 8. Firmware Upgrade Mass Storage Device Firmware Upgrade (1 to confirm, 0 to cancel) - 9. Diagnostics Input / Output states - - 0. Exit Exit and disconnect - - d.protocol simulator When entered diagnostics screen, user can turn on protocol simulator by pressing [9]. When protocol simulator is turned on, device will communicate through USB port rather than RS-485 line. Communication on RS-485 line is closed and all Modbus commands will be accepted only from USB. To exit this mode user must restart device. V1.0 ELSETA 13

e.firmware upgrade over USB To update device firmware user must enter main configuration menu. Enter Firmware update screen by pressing [4]; Confirm update by pressing [1]; Device now enters Firmware Upgrade mode. It is recommended to close terminal window when entered firmware upgrade mode. Device reconnects as mass storage device: Fig. 6.5 User then must delete existing file firmware.bin, and simply upload new firmware file by drag and drop. Fig. 6.5 V1.0 ELSETA 14

Reconnect device and check firmware version. V1.0 ELSETA 15

7.Information of the equipment manufacturer Office address: L. Zamenhofo st. 5 LT-06332 Vilnius Lithuania Tel.: +370 5 2742707, +370 5 2032302 Fax: +370 5 2058584 Email: support@elseta.com In the web: www.aedilis.lt Work hours: I-V 8:00-17:00 V1.0 ELSETA 16

8.Document history Version Date Author Description v0.1 2015.12.15 L.S. First version v0.8 2016.05.10 L.S. Major update. Added IEC-103 description. V0.9 2017.01.13 L.S. Minor updates. Added protocol simulator description. V1.0 2017.03.23 L.S. Minor updates. Removed IEC-103 description. V1.0 ELSETA 17