SS-PRC009-EN Split System Cooling Product & Performance Data 2TTA2030-060A 2½ 5 Tons PUB. NO. 22-1735-01-0302 (EN)
General Features Split System Cooling Units... The Evolution Continues 2TTA2 split systems represent a product that is not only an engineer s dream, it s also a customer s dream. The design team s mission and accomplishment is enhanced performance and efficiency, improved reliability and durability, and improved installability and serviceability. Trane s experienced design team applied six sigma principles, the latest computer technology and customer research to develop the next generation of leadership products. Couple the Trane reputation for reliability and durability with the above mentioned mission and accomplishments and you continue to have systems that prove It s Hard to Stop a Trane. 2002 American Standard Inc. All Rights Reserved 2 22-1735-01-0302 (EN)
Contents General Features 2 Features and Benefits 4 Optional Equipment 5 Low Outdoor Ambient Cooling 5 A.R.I. Standard Capacity Rating Conditions 5 Selection Procedure 6 Model Number Nomenclature 6 General Data 7 2TTA2030A3/4000A 7 2TTA2036A3/4000A 10 2TTA2042A3/4000A 13 2TTA2048A3/4000A 15 2TTA2060A3/4000A 17 Ratings with Auxiliary Devices 19 Performance Data Cooling 22 2TTA2030A3/4 22 2TTA2036A3/4 25 2TTA2042A3/4 28 2TTA2048A3/4 31 2TTA2060A3/4 34 Electrical Data 36 Dimensions 39 Mechanical Specification Options 40 22-1735-01-0302 (EN) 3
Features and Benefits Climatuff compressor All aluminum Spine Fin coil Duratuff base, fast complete drain, weather proof WeatherGuard fasteners New appearance, polystate gray color Quick-Sess cabinet, service access and refrigerant connections with full coil protection Corrosion resistant finish High/low pressure & temperature protection internal to compressor Low pressure switch Liquid line filter-drier Comfort R mode approved Easy single side service Multi-use liquid and suction line service valves Compressor sump heat Easy top & fan removal Sure Fast seams louver panel removal HCFC-22 refrigerant 5-year limited warranty on compressor & coil, and 1 year on parts (residential use) Extended warranties available S.E.E.T. design testing 100% line run test Low ambient to 55 F as shipped Low ambient to 40 F with EDC accessory AY28X079 Low ambient to 30 F with EDC accessory AY28X079 and TXV Low ambient cooling to 0 F with TXV and BAYLOAM103 4 22-1735-01-0302 (EN)
Features and Benefits Optional Equipment OPTIONAL EQUIPMENT FOR CONDENSING UNITS (Check mark [ ] indicates accessories included). Indoor Thermostats Htg./Clg. Programmable Thermostat... TAYSTAT300C [ ] Electronic, 2-Stg. Htg./1 Clg.... TAYSTAT302C [ ] Prog., 5/2 Day, Manual, 1 Htg./1 Clg.... TAYSTAT340 [ ] Prog., 5/2 Day, Manual, 2 (Gas) 1 Htg./1 Clg.... TAYSTAT350 [ ] Electronic, 1 Htg. (Gas)/1 Clg. (Non Prog.)... TAYSTAT370 [ ] Electronic, 1 Htg. (Elec.)/1 Clg. (Non Prog.)2... TAYSTAT371 [ ] Electronic, 2 Htg. (Gas)/1 Clg. (Non Prog.)... TAYSTAT380 [ ] Manual, 2-Stg. Htg./1 Clg.... TAYSTAT241 [ ] Heating/Cooling Horizontal... AY28X092 [ ] Cooling Only with Fan Switch... BAYSTAT304 [ ] Heating/Cooling Vertical... BAYSTAT305 [ ] Two-Stage Heating/Cooling Horizontal1... BAY28X183 [ ] One-Stage Heating/Cooling Horizontal1... BAY28X182 [ ] Thermostat Locking Cover3... BAY28X190 [ ] Outdoor Thermostat... TAYSTAT250B [ ] Sub-base BAY28X182, 183 (Manual changeover)2... BAY28X185 [ ] Evaporator Defrost Control... AY28X079 [ ] Fan Delay Relay Kit... BAY24X045 [ ] 5 Minute Delay Relay... TAYASCT501A [ ] Outdoor Temperature Sensor (used with TAYSTAT300C,302C)... TAYSENS100A [ ] Extreme Conditions Mounting Kit... BAYECMT001 [ ] Seacoast Kit...BAYSEAC001 [ ] Electronic Head Pressure Control... BAYLOAM103 [ ] 1 Requires sub-base 2 Specifically designed for electric heat applications (instant on fan) 3 Not for use with programmable thermostats BRAZED TUBING REFRIGERANT LINE SETS (All Suction Lines are Insulated.) 3/4" ODM (90 bend, one end), 3/4" and 5/16" tubing... TAYREFLN2 * [ ] 7/8" ODM (90 bend, one end), 7/8" and 3/8" tubing... TAYREFLN3 * [ ] 1-1/8" ODM (90 bend, one end), 1-1/8" and 3/8" tubing... TAYREFLN4 * [ ] * Line lengths: 15, 20, 25, 30, 40 & 50 ft. Insert desired line length in catalog number at right for the complete number. Example: TAYREFLN220 Low Outdoor Ambient Cooling Low Ambient As Evaporator Cooling Manufactured Defrost Control FCCV Accutron 55 F 40 F Thermal Expansion Valve (TXV) 55 F 30 F A.R.I. Standard Capacity Rating Conditions A.R.I. STANDARD 210/240 RATING CONDITIONS (A) Cooling 80 F. D.B., 67 F. W.B. air entering indoor coil, 95 F. D.B. air entering outdoor coil. (B) High Temperature Heating 47 F. D.B., 43 F. W.B. air entering outdoor coil, 70 F. D.B. air entering indoor coil. (C) Low Temperature Heating 17 F. D.B., 15 F. W.B. air entering outdoor coil, 70 F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. A.R.I. STANDARD 270 RATING CONDITIONS (Noise rating numbers are determined with the unit in cooling operation.) Standard Noise Rating number is at 95 F. outdoor air. 22-1735-01-0302 (EN) 5
Selection Procedure Model Number Nomenclature 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 2 T T A 2 0 3 6 A 3 0 0 0 A A Refrigerant Type 2 = R-22 4 = R-410A TRANE Product Type W = Split Heat Pump T = Split Cooling Product Family Z = LEADERSHIP - 2 STAGE X = LEADERSHIP R = REPLACEMENT / RETAIL B = BASIC A = LIGHT COMMERCIAL Family SEER 0 = 10 2 = 12 4 = 14 1 = 11 3 = 13 6 = 16 8 = 18 Secondary Function Unit Parts Identifier Minor Design Modifications Power Supply 1 = 200-230 / 1 / 60 or 208-230 / 1 / 60 3 = 200-230 / 3 / 60 4 = 460 / 3 / 60 Major Design Modifications Nominal Capacity in 000 s of BTU s Split System Connections 1-6 Tons 0 = Brazed 6 22-1735-01-0302 (EN)
General Data 2TTA2030A3/4000A OUTDOOR UNIT 12 2TTA2030A3000A 2TTA2030A4000A SOUND RATING (DECIBELS) 29 79 79 1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER POWER CONNS. V/PH/HZ 3 200/230/3/60 460 /3/60 EQUIPMENT CERTIFICATION PROGRAM WHICH IS BASED ON MIN. BRCH. CIR. AMPACITY 12 6 A.R.I. STANDARD 210/240. BR. CIR. MAX. (AMPS) 20 15 2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270. PROT. RTG. } MIN. (AMPS) 20 15 3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE. COMPRESSOR CLIMATUFF - SCROLL CLIMATUFF - SCROLL ONLY USE HACR CIRCUIT BREAKERS OR FUSES. NO. USED - NO. SPEEDS 1-1 1-1 4 STANDARD AIR - DRY COIL - OUTDOOR VOLTS/PH/HZ 200/230/3/60 460/3/60 5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT R.L. AMPS 7 - L.R. AMPS 9-63 4.5-31 NAMEPLATE AND SERVICE INSTRUCTION. FACTORY INSTALLED START COMPONENTS 8 NO NO 6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR - INSULATION/SOUND BLANKET NO NO 60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID COMPRESSOR HEAT YES YES 60 FT. FOR GREATER LENGTH REFER TO REFRIGERANT PIPING SOFTWARE PUB. NO. 32-3312-01. OUTDOOR FAN TYPE PROPELLER PROPELLER DIA. (IN.) - NO. USED 19-1 19-1 7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT TYPE DRIVE - NO. SPEEDS DIRECT - 1 DIRECT - 1 NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO CFM @ 0.0 IN. W.G. 4 2500 2500 COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUM FUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUIT NO. MOTORS - HP. 1-1/8 1-1/8 SELECTION CURRENT. MOTOR SPEED R.P.M. 1075 1075 VOLTS/PH/HZ 200/230/3/60 460/3/60 8 NO MEANS NO START COMPONENTS F.L. AMPS 0.9 0.5 YES MEANS QUICK START KIT COMPONENTS PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER. OUTDOOR COIL TYPE SPINE FIN SPINE FIN ROWS - F.P.I. 1-24 1-24 9 RATED IN ACCORDANCE WITH ARI STANDARD 270/SECTION 5.3.6. FACE AREA (SQ. FT.) 13.75 13.75 TUBE SIZE (IN.) 3/8 3/8 REFRIGERANT R-22 R-22 (O.D. UNIT) NP CHRG. 5 4/04-LB/OZ 4/04-LB/OZ FACTORY SUPPLIED YES YES LINE SIZE - IN. O.D. GAS 6 3/4 3/4 LINE SIZE - IN. O.D. LIQ. 6 5/16 5/16 FCCV RESTRICTOR ORIFICE SIZE 0.065 0.065 DIMENSIONS H X W X D H X W X D SPLIT SYSTEM OUTDOOR UNIT CRATED (IN.) 33.2 X 26.7 X 30.2 33.2 X 26.7 X 30.2 UNCRATED SEE OUTLINE DWG. SEE OUTLINE DWG. WEIGHT SHIPPING (LBS.) 177 180 NET (LBS.) 158 160 CONDENSING UNIT WITH COOLING COILS CCBA30A4AC CUBA30A4AC TXA025C4 TXA030C4 TXA031C4 TXA035C4 TXA036C4 EXPANSION TYPE FIXED ORIFICE FIXED ORIFICE CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 BTUH (TOTAL) 27600 27600 28400 29200 29800 29600 30400 BTUH (SENSIBLE) 19700 19700 20000 21200 21700 22100 22900 INDOOR AIRFLOW (CFM) 950 950 900 1000 1000 1100 1125 SYSTEM POWER (KW) 2.67 2.67 2.69 2.74 2.85 2.79 2.83 EER/SEER (BTU/WATT-HR.) 10.35/11.25 10.35/11.25 10.55/11.50 10.65/11.50 10.45/11.50 10.60/11.50 10.75/11.75 TXA037C4 TXA042C4 TXA043C4 TXC025C4 TXC025D4 TXC030C4 TXC030D4 EXPANSION TYPE CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 BTUH (TOTAL) 30400 30600 30600 28400 28400 29200 29200 BTUH (SENSIBLE) 22900 23100 23100 20000 20000 21200 21200 INDOOR AIRFLOW (CFM) 1125 1125 1125 900 900 1000 1000 SYSTEM POWER (KW) 2.83 2.83 2.83 2.69 2.69 2.74 2.74 EER/SEER (BTU/WATT-HR.) 10.75/11.75 10.80/11.75 10.80/11.75 10.55/11.50 10.55/11.50 10.65/11.50 10.65/11.50 TXC031C4 TXC031D4 TXC031E5 TXC031S3 TXC035C4 TXC035D4 TXC036C4 EXPANSION TYPE CHG TO 65 CHG TO 65 TXV-NB TXV-NB CHG TO 65 CHG TO 65 CHG TO 65 BTUH (TOTAL) 29800 29800 30200 30200 29600 29600 30400 BTUH (SENSIBLE) 21700 21700 22200 22200 22100 22100 22900 INDOOR AIRFLOW (CFM) 1000 1000 1000 1000 1100 1100 1125 SYSTEM POWER (KW) 2.85 2.85 2.76 2.76 2.79 2.79 2.83 EER/SEER (BTU/WATT-HR.) 10.45/11.50 10.45/11.50 10.95/12.25 10.95/12.50 10.60/11.50 10.60/11.50 10.75/11.75 See page 19 for combinations with Auxiliary Devices. 22-1735-01-0302 (EN) 7
General Data 2TTA2030A3/4000A CONDENSING UNIT WITH COOLING COILS TXC036D4 TXC036E5 TXC036S3 TXC037C4 TXC037E5 TXC037S3 TXC042C4 EXPANSION TYPE CHG TO 65 TXV-NB TXV-NB CHG TO 65 TXV-NB TXV-NB CHG TO 65 BTUH (TOTAL) 30400 31200 31200 30400 31200 31200 30600 BTUH (SENSIBLE) 22900 23800 24000 22900 24000 24000 23100 INDOOR AIRFLOW (CFM) 1125 1125 1125 1125 1125 1125 1125 SYSTEM POWER (KW) 2.83 2.82 2.82 2.83 2.82 2.82 2.83 EER/SEER (BTU/WATT-HR.) 10.75/11.75 11.05/12.25 11.05/12.75 10.75/11.75 11.05/12.25 11.05/12.75 10.80/11.75 TXC043C4 TXH025A4 TXH033A4 TXH041A4 EXPANSION TYPE CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 BTUH (TOTAL) 30600 28000 29400 31200 BTUH (SENSIBLE) 23100 19600 22000 23900 INDOOR AIRFLOW (CFM) 1125 900 1000 1125 SYSTEM POWER (KW) 2.83 2.68 2.75 2.85 EER/SEER (BTU/WATT-HR.) 10.80/11.75 10.45/11.50 10.70/11.75 10.95/12.00 CONDENSING UNIT WITH AIR HANDLERS TVF024A14 TVF025A14 TVF030A14 TVF036A14 TWE024P13 TWE030C14 TWE030P13 EXPANSION TYPE CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 TXV-NB CHG TO 65 TXV-NB BTUH (TOTAL) 28400 29200 30200 31000 29200 28800 29600 BTUH (SENSIBLE) 19500 21100 22500 24000 20900 20600 21400 INDOOR AIRFLOW (CFM) 775 900 1000 1125 900 945 940 SYSTEM POWER (KW) 2.63 2.72 2.75 2.87 2.69 2.68 2.68 EER/SEER (BTU/WATT-HR.) 10.80/12.00 10.75/12.00 11.00/12.25 10.80/12.00 10.85/12.50 10.75/12.00 11.05/12.75 TWE031E13 TWE036C14 TWE036P13 TWE037E13 TWE040E13 TWE042C14 TWE042P13 EXPANSION TYPE TXV-NB CHG TO 65 TXV-NB TXV-NB TXV-NB CHG TO 65 TXV-NB BTUH (TOTAL) 30000 30200 30200 30600 32200 30800 31000 BTUH (SENSIBLE) 22400 23300 23000 22700 24300 23600 23700 INDOOR AIRFLOW (CFM) 1020 1125 1125 1000 1010 1125 1125 SYSTEM POWER (KW) 2.62 2.81 2.80 2.54 2.59 2.84 2.83 EER/SEER (BTU/WATT-HR.) 11.45/13.25 10.75/12.00 10.80/12.25 12.05/14.00 12.45/14.00 10.85/12.00 10.95/12.50 TWG025A14 TWG030A14 TWG036A14 TWG037A14 TWG042A14 EXPANSION TYPE CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 CHG TO 65 BTUH (TOTAL) 28400 29000 30000 30000 29600 BTUH (SENSIBLE) 20500 21500 23100 23100 22300 INDOOR AIRFLOW (CFM) 900 1000 1125 1125 1110 SYSTEM POWER (KW) 2.62 2.71 2.79 2.78 2.78 EER/SEER (BTU/WATT-HR.) 10.85/12.25 10.70/12.00 10.75/12.00 10.80/12.00 10.65/11.75 CONDENSING UNIT WITH FURNACES & COILS TDD060R9V3 TDD060R9V3 TDD080R9V3 TDD080R9V3 TDY060R9V3 TDY060R9V3 TDY080R9V3 +TXC031S3 +TXC036S3 +TXC031S3 +TXC036S3 +TXC031S3 +TXC036S3 +TXC036S3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 30600 31200 30400 31000 30200 30600 30600 BTUH (SENSIBLE) 22600 23100 22000 22500 21400 21600 21600 INDOOR AIRFLOW (CFM) 1000 1000 945 945 880 875 875 SYSTEM POWER (KW) 2.62 2.60 2.58 2.57 2.57 2.55 2.58 EER/SEER (BTU/WATT-HR.) 11.70/13.50 12.00/14.00 11.80/13.75 12.05/14.00 11.75/13.75 12.00/14.00 11.85/13.75 See page 19 for combinations with Auxiliary Devices. 8 22-1735-01-0302 (EN)
General Data 2TTA2030A3/4000A CONDENSING UNIT WITH FURNACES & COILS TUD060R9V3 TUD060R9V3 TUD060R9V3 TUD080R9V3 TUD080R9V3 TUY060R9V3 TUY060R9V3 +TXC031E5 +TXC031S3 +TXC036S3 +TXC031S3 +TXC036S3 +TXC031S3 +TXC036S3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 30600 30600 31200 30600 31200 30000 30600 BTUH (SENSIBLE) 22700 23000 23200 22600 23100 21200 21600 INDOOR AIRFLOW (CFM) 1025 1050 1020 1000 1000 875 875 SYSTEM POWER (KW) 2.66 2.66 2.66 2.62 2.60 2.56 2.57 EER/SEER (BTU/WATT-HR.) 11.50/13.25 11.50/13.25 11.75/13.50 11.70/13.50 12.00/14.00 11.70/13.50 11.90/13.75 TUY080R9V3 TUY080R9V3 +TXC031S3 +TXC036S3 EXPANSION TYPE TXV-NB TXV-NB BTUH (TOTAL) 30000 30600 BTUH (SENSIBLE) 21100 21500 INDOOR AIRFLOW (CFM) 860 860 SYSTEM POWER (KW) 2.55 2.55 EER/SEER (BTU/WATT-HR.) 11.75/13.50 12.00/14.00 See page 19 for combinations with Auxiliary Devices. 22-1735-01-0302 (EN) 9
General Data 2TTA2036A3/4000A OUTDOOR UNIT 12 2TTA2036A3000A 2TTA2036A4000A SOUND RATING (DECIBELS) 29 79 79 1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER POWER CONNS. V/PH/HZ 3 200/230/3/60 460/3/60 EQUIPMENT CERTIFICATION PROGRAM WHICH IS BASED ON MIN. BRCH. CIR. AMPACITY 15 8 A.R.I. STANDARD 210/240. BR. CIR. MAX. (AMPS) 25 15 2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270. PROT. RTG. } MIN. (AMPS) 20 15 3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE. COMPRESSOR CLIMATUFF - SCROLL CLIMATUFF - SCROLL ONLY USE HACR CIRCUIT BREAKERS OR FUSES. NO. USED - NO. SPEEDS 1-1 1-1 4 STANDARD AIR - DRY COIL - OUTDOOR VOLTS/PH/HZ 200/230/3/60 460/3/60 5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT R.L. AMPS 7 - L.R. AMPS 11-77 5.6-39 NAMEPLATE AND SERVICE INSTRUCTION. FACTORY INSTALLED START COMPONENTS 8 NO NO 6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR - INSULATION/SOUND BLANKET NO NO 60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID COMPRESSOR HEAT YES YES 60 FT. FOR GREATER LENGTH REFER TO REFRIGERANT PIPING SOFTWARE PUB. NO. 32-3312-01. OUTDOOR FAN TYPE PROPELLER PROPELLER DIA. (IN.) - NO. USED 19-1 19-1 7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT TYPE DRIVE - NO. SPEEDS DIRECT - 1 DIRECT - 1 NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO CFM @ 0.0 IN. W.G. 4 2500 2500 COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUM FUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUIT NO. MOTORS - HP. 1-1/8 1-1/8 SELECTION CURRENT. MOTOR SPEED R.P.M. 1075 1075 VOLTS/PH/HZ 200/230/3/60 460/3/60 8 NO MEANS NO START COMPONENTS F.L. AMPS 0.9 0.5 YES MEANS QUICK START KIT COMPONENTS PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER. OUTDOOR COIL TYPE SPINE FIN SPINE FIN ROWS - F.P.I. 1-24 1-24 9 RATED IN ACCORDANCE WITH ARI STANDARD 270/SECTION 5.3.6. FACE AREA (SQ. FT.) 15.86 15.86 TUBE SIZE (IN.) 3/8 3/8 REFRIGERANT R-22 R-22 (O.D. UNIT) NP CHRG. 5 6/00-LB/OZ 6/00-LB/OZ FACTORY SUPPLIED YES YES LINE SIZE - IN. O.D. GAS 6 7/8 7/8 LINE SIZE - IN. O.D. LIQ. 6 3/8 3/8 FCCV RESTRICTOR ORIFICE SIZE 0.071 0.071 DIMENSIONS H X W X D H X W X D SPLIT SYSTEM OUTDOOR UNIT CRATED (IN.) 37.2 X 26.7 X 30.2 37.2 X 26.7 X 30.2 UNCRATED SEE OUTLINE DWG. SEE OUTLINE DWG. WEIGHT SHIPPING (LBS.) 192 191 NET (LBS.) 171 171 CONDENSING UNIT WITH COOLING COILS CCBA36A4AC CCBB36A4AC CUBA36A4AC CUBB36A4AC CUBC36A4AC TXA031C4 TXA035C4 EXPANSION TYPE FIXED ORIFICE FIXED ORIFICE FIXED ORIFICE FIXED ORIFICE FIXED ORIFICE CHG TO 71 FACT INS 71 BTUH (TOTAL) 34200 34400 34200 34400 34400 34400 34200 BTUH (SENSIBLE) 24100 24400 24100 24400 24400 24400 24100 INDOOR AIRFLOW (CFM) 1100 1100 1100 1100 1100 1100 1100 SYSTEM POWER (KW) 3.26 3.26 3.26 3.26 3.26 3.26 3.26 EER/SEER (BTU/WATT-HR.) 10.50/11.50 10.55/11.75 10.50/11.50 10.55/11.75 10.55/11.75 10.55/11.75 10.50/11.50 TXA036C4 TXA037C4 TXA042C4 TXA043C4 TXA048C4 TXC031C4 TXC031D4 EXPANSION TYPE FACT INS 71 FACT INS 71 CHG TO 71 CHG TO 71 CHG TO 71 CHG TO 71 CHG TO 71 BTUH (TOTAL) 36200 35800 36200 36800 37200 34400 34400 BTUH (SENSIBLE) 26200 25900 26100 27700 28000 24400 24400 INDOOR AIRFLOW (CFM) 1200 1200 1200 1350 1350 1100 1100 SYSTEM POWER (KW) 3.42 3.35 3.37 3.44 3.44 3.26 3.26 EER/SEER (BTU/WATT-HR.) 10.60/11.50 10.70/11.75 10.75/11.75 10.70/11.75 10.80/11.75 10.55/11.75 10.55/11.75 TXC031E5 TXC031S3 TXC035C4 TXC035D4 TXC036C4 TXC036D4 TXC036E5 EXPANSION TYPE TXV-NB TXV-NB FACT INS 71 FACT INS 71 FACT INS 71 FACT INS 71 TXV-NB BTUH (TOTAL) 35800 35800 34200 34200 36200 36200 36800 BTUH (SENSIBLE) 25600 25600 24100 24100 26200 26200 26800 INDOOR AIRFLOW (CFM) 1110 1110 1100 1100 1200 1200 1200 SYSTEM POWER (KW) 3.30 3.30 3.26 3.26 3.42 3.42 3.35 EER/SEER (BTU/WATT-HR.) 10.85/12.25 10.85/12.50 10.50/11.50 10.50/11.50 10.60/11.50 10.60/11.50 11.00/12.25 See pages 19 and 20 for combinations with Auxiliary Devices. 10 22-1735-01-0302 (EN)
General Data 2TTA2036A3/4000A CONDENSING UNIT WITH COOLING COILS TXC036S3 TXC037C4 TXC037E5 TXC037S3 TXC042C4 TXC043C4 TXC048C4 EXPANSION TYPE TXV-NB FACT INS 71 TXV-NB TXV-NB CHG TO 71 CHG TO 71 CHG TO 71 BTUH (TOTAL) 36800 35800 36800 36800 36200 36800 37200 BTUH (SENSIBLE) 27000 25900 27000 27000 26100 27700 28000 INDOOR AIRFLOW (CFM) 1200 1200 1200 1200 1200 1350 1350 SYSTEM POWER (KW) 3.35 3.35 3.35 3.35 3.37 3.44 3.44 EER/SEER (BTU/WATT-HR.) 11.00/12.75 10.70/11.75 11.00/12.25 11.00/12.75 10.75/11.75 10.70/11.75 10.80/11.75 TXH033A4 TXH041A4 EXPANSION TYPE CHG TO 71 CHG TO 71 BTUH (TOTAL) 34400 37400 BTUH (SENSIBLE) 25400 28600 INDOOR AIRFLOW (CFM) 1125 1350 SYSTEM POWER (KW) 3.28 3.46 EER/SEER (BTU/WATT-HR.) 10.50/11.50 10.80/12.00 CONDENSING UNIT WITH AIR HANDLERS TVF030A14 TVF036A14 TWE030C14 TWE030P13 TWE031E13 TWE036C14 TWE036P13 EXPANSION TYPE CHG TO 71 FACT INS 71 CHG TO 71 TXV-NB TXV-NB FACT INS 71 TXV-NB BTUH (TOTAL) 35400 36600 33000 34200 35400 35600 35600 BTUH (SENSIBLE) 25900 27100 22400 23400 26300 26100 25800 INDOOR AIRFLOW (CFM) 1125 1200 945 940 1220 1200 1200 SYSTEM POWER (KW) 3.34 3.40 3.13 3.15 3.26 3.33 3.31 EER/SEER (BTU/WATT-HR.) 10.60/12.00 10.75/12.00 10.55/12.00 10.85/12.50 10.85/12.50 10.70/12.00 10.75/12.25 TWE037E13 TWE040E13 TWE042C14 TWE042P13 TWE048C14 TWE048P13 TWE049E13 EXPANSION TYPE TXV-NB TXV-NB CHG TO 71 TXV-NB CHG TO 71 TXV-NB TXV-NB BTUH (TOTAL) 36400 38500 36800 37000 37400 39000 39000 BTUH (SENSIBLE) 26500 28900 28100 28300 28600 30200 29100 INDOOR AIRFLOW (CFM) 1160 1200 1350 1350 1350 1350 1200 SYSTEM POWER (KW) 3.15 3.20 3.44 3.41 3.50 3.39 3.17 EER/SEER (BTU/WATT-HR.) 11.55/13.50 12.05/14.00 10.70/12.00 10.85/12.50 10.70/12.00 11.50/13.25 12.30/14.00 TWG030A14 TWG036A14 TWG037A14 TWG042A14 TWG048A14 EXPANSION TYPE CHG TO 71 FACT INS 71 FACT INS 71 CHG TO 71 CHG TO 71 BTUH (TOTAL) 34000 34600 35000 35400 37600 BTUH (SENSIBLE) 24400 25100 25800 26500 28600 INDOOR AIRFLOW (CFM) 1100 1150 1200 1325 1350 SYSTEM POWER (KW) 3.22 3.34 3.27 3.34 3.43 EER/SEER (BTU/WATT-HR.) 10.55/11.75 10.35/11.50 10.70/12.00 10.60/12.00 10.95/12.25 CONDENSING UNIT WITH FURNACES & COILS TDD060R9V3 TDD060R9V3 TDD080R9V3 TDD080R9V3 TDD100R9V5 TDY060R9V3 TDY060R9V3 +TXC031S3 +TXC036S3 +TXC031S3 +TXC036S3 +TXC037S3 +TXC031S3 +TXC036S3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 36200 37200 36200 37000 37400 36000 36800 BTUH (SENSIBLE) 26600 27400 26000 26700 27400 25600 26200 INDOOR AIRFLOW (CFM) 1200 1200 1120 1130 1180 1090 1085 SYSTEM POWER (KW) 3.25 3.25 3.20 3.19 3.13 3.20 3.20 EER/SEER (BTU/WATT-HR.) 11.15/13.00 11.45/13.25 11.30/13.00 11.60/13.50 11.95/14.00 11.25/13.00 11.50/13.25 See pages 19 and 20 for combinations with Auxiliary Devices. 22-1735-01-0302 (EN) 11
General Data 2TTA2036A3/4000A CONDENSING UNIT WITH FURNACES & COILS TDY080R9V3 TDY080R9V3 TDY100R9V4 TUD060R9V3 TUD060R9V3 TUD080R9V3 TUD080R9V3 +TXC031S3 +TXC036S3 +TXC037S3 +TXC031S3 +TXC036S3 +TXC031S3 +TXC036S3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 35600 36400 36600 36200 37000 36200 37000 BTUH (SENSIBLE) 25000 25600 25800 26600 27200 26600 27200 INDOOR AIRFLOW (CFM) 1050 1050 1050 1200 1200 1200 1200 SYSTEM POWER (KW) 3.22 3.22 3.16 3.28 3.29 3.26 3.29 EER/SEER (BTU/WATT-HR.) 11.05/12.75 11.30/13.00 11.60/13.50 11.05/12.75 11.25/13.00 11.10/12.75 11.25/13.00 TUD100R9V5 TUY060R9V3 TUY060R9V3 TUY080R9V3 TUY080R9V3 TUY100R9V4 +TXC037S3 +TXC031S3 +TXC036S3 +TXC031S3 +TXC036S3 +TXC037S3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 37400 35800 36400 35800 36400 36800 BTUH (SENSIBLE) 27600 25200 25600 25100 25600 26100 INDOOR AIRFLOW (CFM) 1200 1050 1050 1040 1040 1060 SYSTEM POWER (KW) 3.16 3.18 3.17 3.15 3.15 3.09 EER/SEER (BTU/WATT-HR.) 11.85/13.75 11.25/13.00 11.50/13.25 11.35/13.25 11.55/13.50 11.90/14.00 See pages 19 and 20 for combinations with Auxiliary Devices. 12 22-1735-01-0302 (EN)
General Data 2TTA2042A3/4000A OUTDOOR UNIT 12 2TTA2042A3000A 2TTA2042A4000A SOUND RATING (DECIBELS) 29 79 79 1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER POWER CONNS. V/PH/HZ 3 200/230/3/60 460 /3/60 EQUIPMENT CERTIFICATION PROGRAM WHICH IS BASED ON MIN. BRCH. CIR. AMPACITY 17 8 A.R.I. STANDARD 210/240. BR. CIR. MAX. (AMPS) 25 15 2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270. PROT. RTG. } MIN. (AMPS) 20 15 3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE. COMPRESSOR CLIMATUFF - SCROLL CLIMATUFF - SCROLL ONLY USE HACR CIRCUIT BREAKERS OR FUSES. NO. USED - NO. SPEEDS 1-1 1-1 4 STANDARD AIR - DRY COIL - OUTDOOR VOLTS/PH/HZ 200/230/3/60 460/3/60 5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT R.L. AMPS 7 - L.R. AMPS 12.4-88 5.8-44 NAMEPLATE AND SERVICE INSTRUCTION. FACTORY INSTALLED START COMPONENTS 8 NO NO 6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR - INSULATION/SOUND BLANKET NO NO 60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID COMPRESSOR HEAT YES YES 60 FT. FOR GREATER LENGTH REFER TO REFRIGERANT PIPING SOFTWARE PUB. NO. 32-3312-01. OUTDOOR FAN TYPE PROPELLER PROPELLER DIA. (IN.) - NO. USED 23-1 23-1 7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT TYPE DRIVE - NO. SPEEDS DIRECT - 1 DIRECT - 1 NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO CFM @ 0.0 IN. W.G. 4 3400 3400 COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUM FUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUIT NO. MOTORS - HP. 1-1/6 1-1/6 SELECTION CURRENT. MOTOR SPEED R.P.M. 825 825 VOLTS/PH/HZ 200/230/3/60 460/3/60 8 NO MEANS NO START COMPONENTS F.L. AMPS 1.4 0.7 YES MEANS QUICK START KIT COMPONENTS PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER. OUTDOOR COIL TYPE SPINE FIN SPINE FIN ROWS - F.P.I. 1-24 1-24 9 RATED IN ACCORDANCE WITH ARI STANDARD 270/SECTION 5.3.6. FACE AREA (SQ. FT.) 18.75 18.75 TUBE SIZE (IN.) 3/8 3/8 REFRIGERANT R-22 R-22 (O.D. UNIT) NP CHRG. 5 5/15-LB/OZ 5/15-LB/OZ FACTORY SUPPLIED YES YES LINE SIZE - IN. O.D. GAS 6 7/8 7/8 LINE SIZE - IN. O.D. LIQ. 6 3/8 3/8 FCCV RESTRICTOR ORIFICE SIZE 0.077 0.077 DIMENSIONS H X W X D H X W X D SPLIT SYSTEM OUTDOOR UNIT CRATED (IN.) 38 X 30.1 X 33.8 38 X 30.1 X 33.8 UNCRATED SEE OUTLINE DWG. SEE OUTLINE DWG. WEIGHT SHIPPING (LBS.) 224 224 NET (LBS.) 196 196 CONDENSING UNIT WITH COOLING COILS CCBB42A4AC CUBB42A4AC CUBC42A4AC TXA036C4 TXA037C4 TXA042C4 TXA043C4 EXPANSION TYPE FIXED ORIFICE FIXED ORIFICE FIXED ORIFICE CHG TO 77 CHG TO 77 CHG TO 77 CHG TO 77 BTUH (TOTAL) 40500 40500 40500 41000 42000 41500 42000 BTUH (SENSIBLE) 27900 27900 27900 28100 29900 28400 30200 INDOOR AIRFLOW (CFM) 1200 1200 1200 1200 1350 1200 1400 SYSTEM POWER (KW) 3.67 3.67 3.67 3.69 3.80 3.72 3.78 EER/SEER (BTU/WATT-HR.) 11.05/12.00 11.05/12.00 11.05/12.00 11.10/12.25 11.05/12.25 11.15/12.25 11.10/12.50 TXA048C4 TXC036C4 TXC036D4 TXC036E5 TXC036S3 TXC037C4 TXC037E5 EXPANSION TYPE CHG TO 77 CHG TO 77 CHG TO 77 TXV-NB TXV-NB CHG TO 77 TXV-NB BTUH (TOTAL) 43000 41000 41000 42500 42500 42000 43000 BTUH (SENSIBLE) 30600 28100 28100 30000 30100 29900 31000 INDOOR AIRFLOW (CFM) 1350 1200 1200 1280 1280 1350 1350 SYSTEM POWER (KW) 3.82 3.69 3.69 3.73 3.73 3.80 3.77 EER/SEER (BTU/WATT-HR.) 11.25/12.25 11.10/12.25 11.10/12.25 11.40/12.75 11.40/13.00 11.05/12.25 11.40/12.75 TXC037S3 TXC042C4 TXC043C4 TXC048C4 TXC054S3 TXH041A4 TXH054A4 EXPANSION TYPE TXV-NB CHG TO 77 CHG TO 77 CHG TO 77 TXV-NB CHG TO 77 CHG TO 77 BTUH (TOTAL) 43000 41500 42000 43000 43500 43500 45500 BTUH (SENSIBLE) 31000 28400 30200 30600 32600 31700 35100 INDOOR AIRFLOW (CFM) 1350 1200 1400 1350 1575 1400 1575 SYSTEM POWER (KW) 3.77 3.72 3.78 3.82 3.87 3.87 3.99 EER/SEER (BTU/WATT-HR.) 11.40/13.00 11.15/12.25 11.10/12.50 11.25/12.25 11.25/13.00 11.25/12.50 11.40/12.50 See page 20 for combinations with Auxiliary Devices. 22-1735-01-0302 (EN) 13
General Data 2TTA2042A3/4000A CONDENSING UNIT WITH AIR HANDLERS TVF036A14 TWE036C14 TWE036P13 TWE037E13 TWE040E13 TWE042C14 TWE042P13 EXPANSION TYPE CHG TO 77 CHG TO 77 TXV-NB TXV-NB TXV-NB CHG TO 77 TXV-NB BTUH (TOTAL) 42500 41500 41500 42500 44500 42500 43000 BTUH (SENSIBLE) 31000 30000 29600 30700 33500 31000 31400 INDOOR AIRFLOW (CFM) 1350 1350 1350 1350 1425 1400 1400 SYSTEM POWER (KW) 3.92 3.82 3.81 3.66 3.66 3.83 3.79 EER/SEER (BTU/WATT-HR.) 10.85/12.00 10.85/12.00 10.90/12.50 11.60/13.25 12.15/14.00 11.10/12.50 11.35/13.00 TWE048C14 TWE048P13 TWE049E13 TWE060A TWG036A14 TWG037A14 TWG042A14 EXPANSION TYPE CHG TO 77 TXV-NB TXV-NB TXV-NB CHG TO 77 CHG TO 77 CHG TO 77 BTUH (TOTAL) 44000 45500 45500 43500 39500 40500 41000 BTUH (SENSIBLE) 33400 35100 33700 32400 27300 28900 29400 INDOOR AIRFLOW (CFM) 1575 1575 1400 1575 1150 1275 1400 SYSTEM POWER (KW) 3.96 3.86 3.68 3.72 3.71 3.72 3.73 EER/SEER (BTU/WATT-HR.) 11.10/12.25 11.80/13.50 12.35/14.00 11.70/13.00 10.65/12.00 10.90/12.25 11.00/12.25 TWG048A14 EXPANSION TYPE CHG TO 77 BTUH (TOTAL) 44000 BTUH (SENSIBLE) 33400 INDOOR AIRFLOW (CFM) 1575 SYSTEM POWER (KW) 3.93 EER/SEER (BTU/WATT-HR.) 11.20/12.50 CONDENSING UNIT WITH FURNACES & COILS TDD080R9V3 TDD100R9V5 TDD100R9V5 TDY100R9V4 TDY100R9V4 TUD080R9V3 TUD100R9V5 +TXC036S3 +TXC037S3 +TXC054S3 +TXC037S3 +TXC054S3 +TXC036S3 +TXC037S3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 43000 43500 43000 42500 42500 43000 43500 BTUH (SENSIBLE) 30900 31800 31000 29800 29500 31400 31800 INDOOR AIRFLOW (CFM) 1330 1390 1390 1225 1230 1400 1400 SYSTEM POWER (KW) 3.69 3.67 3.63 3.62 3.62 3.79 3.75 EER/SEER (BTU/WATT-HR.) 11.65/13.50 11.85/13.75 11.85/13.75 11.75/13.50 11.75/13.50 11.35/13.00 11.60/13.25 TUD100R9V5 TUY080R9V3 TUY100R9V4 TUY100R9V4 +TXC054S3 +TXC036S3 +TXC037S3 +TXC054S3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 43000 42500 43000 42500 BTUH (SENSIBLE) 31100 29700 30000 29400 INDOOR AIRFLOW (CFM) 1400 1225 1200 1200 SYSTEM POWER (KW) 3.71 3.65 3.57 3.56 EER/SEER (BTU/WATT-HR.) 11.60/13.25 11.65/13.50 12.05/14.00 11.95/14.00 See page 20 for combinations with Auxiliary Devices. 14 22-1735-01-0302 (EN)
General Data 2TTA2048A3/4000A OUTDOOR UNIT 12 2TTA2048A3000A 2TTA2048A4000A SOUND RATING (DECIBELS) 29 78 78 1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER POWER CONNS. V/PH/HZ 3 200/230/3/60 460 /3/60 EQUIPMENT CERTIFICATION PROGRAM WHICH IS BASED ON MIN. BRCH. CIR. AMPACITY 20 10 A.R.I. STANDARD 210/240. BR. CIR. MAX. (AMPS) 35 15 2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270. PROT. RTG. } MIN. (AMPS) 30 15 3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE. COMPRESSOR CLIMATUFF - SCROLL CLIMATUFF - SCROLL ONLY USE HACR CIRCUIT BREAKERS OR FUSES. NO. USED - NO. SPEEDS 1-1 1-1 4 STANDARD AIR - DRY COIL - OUTDOOR VOLTS/PH/HZ 200/230/3/60 460/3/60 5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT R.L. AMPS 7 - L.R. AMPS 15-91 7.1-50 NAMEPLATE AND SERVICE INSTRUCTION. FACTORY INSTALLED START COMPONENTS 8 NO NO 6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR - INSULATION/SOUND BLANKET NO NO 60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID COMPRESSOR HEAT YES YES 60 FT. FOR GREATER LENGTH REFER TO REFRIGERANT PIPING SOFTWARE PUB. NO. 32-3312-01. OUTDOOR FAN TYPE PROPELLER PROPELLER DIA. (IN.) - NO. USED 23-1 23-1 7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT TYPE DRIVE - NO. SPEEDS DIRECT - 1 DIRECT - 1 NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO CFM @ 0.0 IN. W.G. 4 3400 3400 COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUM FUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUIT NO. MOTORS - HP. 1-1/6 1-1/6 SELECTION CURRENT. MOTOR SPEED R.P.M. 825 825 VOLTS/PH/HZ 200/230/3/60 460/3/60 8 NO MEANS NO START COMPONENTS F.L. AMPS 1.4 0.7 YES MEANS QUICK START KIT COMPONENTS PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER. OUTDOOR COIL TYPE SPINE FIN SPINE FIN ROWS - F.P.I. 1-24 1-24 9 RATED IN ACCORDANCE WITH ARI STANDARD 270/SECTION 5.3.6. FACE AREA (SQ. FT.) 21.25 21.25 TUBE SIZE (IN.) 3/8 3/8 REFRIGERANT R-22 R-22 (O.D. UNIT) NP CHRG. 5 7/08-LB/OZ 7/08-LB/OZ FACTORY SUPPLIED YES YES LINE SIZE - IN. O.D. GAS 6 1-1/8 1-1/8 LINE SIZE - IN. O.D. LIQ. 6 3/8 3/8 FCCV RESTRICTOR ORIFICE SIZE 0.086 0.086 DIMENSIONS H X W X D H X W X D SPLIT SYSTEM OUTDOOR UNIT CRATED (IN.) 42 X 30.1 X 33.8 42 X 30.1 X 33.8 UNCRATED SEE OUTLINE DWG. SEE OUTLINE DWG. WEIGHT SHIPPING (LBS.) 242 241 NET (LBS.) 213 213 CONDENSING UNIT WITH COOLING COILS CCBD60A5AC CUBD60A5AC TXA043C4 TXA048C4 TXA049C4 TXA050C4 TXA060C5 EXPANSION TYPE TXV-B TXV-B CHG TO 86 CHG TO 86 CHG TO 86 CHG TO 86 TXV-NB BTUH (TOTAL) 50500 50500 48000 47500 48500 48500 50000 BTUH (SENSIBLE) 37300 37300 34300 32500 34900 34900 36200 INDOOR AIRFLOW (CFM) 1800 1800 1575 1350 1600 1600 1700 SYSTEM POWER (KW) 4.68 4.68 4.53 4.44 4.53 4.53 4.63 EER/SEER (BTU/WATT-HR.) 10.80/12.00 10.80/12.00 10.60/11.75 10.70/11.75 10.70/12.00 10.70/12.00 10.80/12.00 TXA061C5 TXC043C4 TXC048C4 TXC049C4 TXC050C4 TXC054S3 TXC060C5 EXPANSION TYPE TXV-NB CHG TO 86 CHG TO 86 CHG TO 86 CHG TO 86 TXV-NB TXV-NB BTUH (TOTAL) 51000 48000 47500 48500 48500 49500 50000 BTUH (SENSIBLE) 38400 34300 32500 34900 34900 36200 36200 INDOOR AIRFLOW (CFM) 1800 1575 1350 1600 1600 1700 1700 SYSTEM POWER (KW) 4.68 4.53 4.44 4.53 4.53 4.60 4.63 EER/SEER (BTU/WATT-HR.) 10.90/12.25 10.60/11.75 10.70/11.75 10.70/12.00 10.70/12.00 10.75/12.50 10.80/12.00 TXC061C5 TXC065S3 TXH041A4 TXH054A4 TXH063P3 EXPANSION TYPE TXV-NB TXV-NB CHG TO 86 CHG TO 86 TXV-NB BTUH (TOTAL) 51000 51500 49000 52000 52500 BTUH (SENSIBLE) 38400 38600 35500 39100 40100 INDOOR AIRFLOW (CFM) 1800 1800 1575 1700 1800 SYSTEM POWER (KW) 4.68 4.68 4.54 4.68 4.69 EER/SEER (BTU/WATT-HR.) 10.90/12.25 11.00/12.75 10.80/12.00 11.10/12.25 11.20/13.00 See pages 20 and 21 for combinations with Auxiliary Devices. 22-1735-01-0302 (EN) 15
General Data 2TTA2048A3/4000A CONDENSING UNIT WITH AIR HANDLERS TWE042P13 TWE048C14 TWE048P13 TWE049E13 TWE060C/D15 TWE060P13 TWE065E13 EXPANSION TYPE TXV-NB CHG TO 86 TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 49000 49500 52000 52000 50500 52500 53000 BTUH (SENSIBLE) 35400 35900 38100 37500 37800 40400 39400 INDOOR AIRFLOW (CFM) 1575 1600 1600 1500 1800 1800 1640 SYSTEM POWER (KW) 4.60 4.60 4.66 4.37 4.88 4.71 4.53 EER/SEER (BTU/WATT-HR.) 10.65/12.25 10.75/12.00 11.15/13.00 11.90/14.00 10.35/11.75 11.15/13.00 11.70/13.75 TWG048A14 TWG060A15 EXPANSION TYPE CHG TO 86 TXV-NB BTUH (TOTAL) 49000 50500 BTUH (SENSIBLE) 35600 37800 INDOOR AIRFLOW (CFM) 1600 1800 SYSTEM POWER (KW) 4.58 4.76 EER/SEER (BTU/WATT-HR.) 10.70/12.00 10.60/12.00 CONDENSING UNIT WITH FURNACES & COILS TDD100R9V5 TDD100R9V5 TDD100R9V5 TDD120R9V5 TDY100R9V4 TDY100R9V4 TDY100R9V4 +TXC037S3 +TXC054S3 +TXH063P3 +TXH063P3 +TXC037S3 +TXC054S3 +TXH063P3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 50000 49500 52500 52500 49000 48500 51500 BTUH (SENSIBLE) 36500 35800 38500 38800 34500 33800 36400 INDOOR AIRFLOW (CFM) 1620 1620 1600 1625 1450 1450 1450 SYSTEM POWER (KW) 4.52 4.50 4.55 4.45 4.50 4.49 4.52 EER/SEER (BTU/WATT-HR.) 11.05/12.75 11.00/12.75 11.55/13.50 11.80/13.75 10.90/12.50 10.80/12.50 11.40/13.25 TDY120R9V5 TUD100R9V5 TUD100R9V5 TUD100R9V5 TUD120R9V5 TUD120R9V5 TUD140R9V5 +TXH063P3 +TXC037S3 +TXC054S3 +TXH063P3 +TXC065S3 +TXH063P3 +TXC065S3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 51500 50000 49500 52000 51500 52500 51500 BTUH (SENSIBLE) 36100 36900 36000 38000 37400 38700 37200 INDOOR AIRFLOW (CFM) 1405 1670 1670 1600 1625 1625 1600 SYSTEM POWER (KW) 4.46 4.57 4.58 4.58 4.48 4.49 4.48 EER/SEER (BTU/WATT-HR.) 11.55/13.50 10.95/12.75 10.80/12.50 11.35/13.00 11.50/13.25 11.70/13.50 11.50/13.25 TUD140R9V5 TUY100R9V4 TUY100R9V4 TUY100R9V4 TUY120R9V5 TUY120R9V5 +TXH063P3 +TXC037S3 +TXC054S3 +TXH063P3 +TXC065S3 +TXH063P3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 52500 49000 48500 51500 50500 51500 BTUH (SENSIBLE) 38500 34400 33700 36200 35000 36000 INDOOR AIRFLOW (CFM) 1600 1430 1430 1425 1400 1400 SYSTEM POWER (KW) 4.47 4.45 4.43 4.46 4.39 4.42 EER/SEER (BTU/WATT-HR.) 11.75/13.75 11.00/12.75 10.95/12.75 11.55/13.50 11.50/13.25 11.65/13.50 See pages 20 and 21 for combinations with Auxiliary Devices. 16 22-1735-01-0302 (EN)
General Data 2TTA2060A3/4000A OUTDOOR UNIT 12 2TTA2060A3000A 2TTA2060A4000A SOUND RATING (DECIBELS) 29 79 79 1 CERTIFIED IN ACCORDANCE WITH THE UNITARY AIR-CONDITIONER POWER CONNS. V/PH/HZ 3 200/230/3/60 460 /3/60 EQUIPMENT CERTIFICATION PROGRAM WHICH IS BASED ON MIN. BRCH. CIR. AMPACITY 24 12 A.R.I. STANDARD 210/240. BR. CIR. MAX. (AMPS) 40 20 2 RATED IN ACCORDANCE WITH A.R.I. STANDARD 270. PROT. RTG. } MIN. (AMPS) 40 20 3 CALCULATED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE. COMPRESSOR CLIMATUFF - SCROLL CLIMATUFF - SCROLL ONLY USE HACR CIRCUIT BREAKERS OR FUSES. NO. USED - NO. SPEEDS 1-1 1-1 4 STANDARD AIR - DRY COIL - OUTDOOR VOLTS/PH/HZ 200/230/3/60 460/3/60 5 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT R.L. AMPS 7 - L.R. AMPS 17.5-123 9-62 NAMEPLATE AND SERVICE INSTRUCTION. FACTORY INSTALLED START COMPONENTS 8 NO NO 6 MAX. LINEAR LENGTH: 80 FT WITH RECIPROCATING COMPRESSOR - INSULATION/SOUND BLANKET NO NO 60 FT WITH SCROLL. MAX. LIFT - SUCTION 60 FT; MAX LIFT - LIQUID COMPRESSOR HEAT YES YES 60 FT. FOR GREATER LENGTH REFER TO REFRIGERANT PIPING SOFTWARE PUB. NO. 32-3312-01. OUTDOOR FAN TYPE PROPELLER PROPELLER DIA. (IN.) - NO. USED 23-1 23-1 7 THE VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT TYPE DRIVE - NO. SPEEDS DIRECT - 1 DIRECT - 1 NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO CFM @ 0.0 IN. W.G. 4 3900 3900 COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAXIMUM FUSE SIZE. THE VALUE SHOWN IS THE BRANCH CIRCUIT NO. MOTORS - HP. 1-1/4 1-1/4 SELECTION CURRENT. MOTOR SPEED R.P.M. 825 825 VOLTS/PH/HZ 200/230/3/60 460/3/60 8 NO MEANS NO START COMPONENTS F.L. AMPS 1.9 1 YES MEANS QUICK START KIT COMPONENTS PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER. OUTDOOR COIL TYPE SPINE FIN SPINE FIN ROWS - F.P.I. 1-24 1-24 9 RATED IN ACCORDANCE WITH ARI STANDARD 270/SECTION 5.3.6. FACE AREA (SQ. FT.) 21.25 21.25 TUBE SIZE (IN.) 3/8 3/8 REFRIGERANT R-22 R-22 (O.D. UNIT) NP CHRG. 5 7/13-LB/OZ 7/13-LB/OZ FACTORY SUPPLIED YES YES LINE SIZE - IN. O.D. GAS 6 1-1/8 1-1/8 LINE SIZE - IN. O.D. LIQ. 6 3/8 3/8 FCCV RESTRICTOR ORIFICE SIZE 0.095 0.095 DIMENSIONS H X W X D H X W X D SPLIT SYSTEM OUTDOOR UNIT CRATED (IN.) 42 X 30.1 X 33.8 42 X 30.1 X 33.8 UNCRATED SEE OUTLINE DWG. SEE OUTLINE DWG. WEIGHT SHIPPING (LBS.) 258 258 NET (LBS.) 229 229 CONDENSING UNIT WITH COOLING COILS CCBC60A4AC CCBD60A5AC CUBD60A5AC TXA043C4 TXA048C4 TXA049C4 TXA050C4 EXPANSION TYPE FIXED ORIFICE TXV-B TXV-B CHG TO 95 CHG TO 95 CHG TO 95 CHG TO 95 BTUH (TOTAL) 56000 58500 58500 54000 53000 55500 55500 BTUH (SENSIBLE) 38800 42300 42300 36900 34900 38700 38700 INDOOR AIRFLOW (CFM) 1675 2000 2000 1575 1350 1675 1675 SYSTEM POWER (KW) 5.26 5.44 5.44 5.14 5.05 5.21 5.21 EER/SEER (BTU/WATT-HR.) 10.65/12.00 10.75/12.00 10.75/12.25 10.50/11.75 10.50/11.75 10.65/11.75 10.65/11.75 TXA060C5 TXA061C5 TXC043C4 TXC048C4 TXC049C4 TXC050C4 TXC054E5 EXPANSION TYPE TXV-NB TXV-NB CHG TO 95 CHG TO 95 CHG TO 95 CHG TO 95 TXV-NB BTUH (TOTAL) 57500 58500 54000 53000 55500 55500 56500 BTUH (SENSIBLE) 39500 41500 36900 34900 38700 38700 39200 INDOOR AIRFLOW (CFM) 1700 1800 1575 1350 1675 1675 1700 SYSTEM POWER (KW) 5.32 5.47 5.14 5.05 5.21 5.21 5.28 EER/SEER (BTU/WATT-HR.) 10.80/12.25 10.70/12.00 10.50/11.75 10.50/11.75 10.65/11.75 10.65/11.75 10.70/12.00 TXC054S3 TXC060C5 TXC061C5 TXC065S3 TXH054A4 TXH063P3 EXPANSION TYPE TXV-NB TXV-NB TXV-NB TXV-NB CHG TO 95 TXV-NB BTUH (TOTAL) 56500 57500 58500 60500 59500 61500 BTUH (SENSIBLE) 39200 39500 41500 44400 42300 46000 INDOOR AIRFLOW (CFM) 1700 1700 1800 2000 1700 2000 SYSTEM POWER (KW) 5.28 5.32 5.47 5.50 5.34 5.49 EER/SEER (BTU/WATT-HR.) 10.70/12.50 10.80/12.25 10.70/12.00 11.00/12.75 11.15/12.50 11.20/13.00 See page 21 for combinations with Auxiliary Devices. 22-1735-01-0302 (EN) 17
General Data 2TTA2060A3/4000A CONDENSING UNIT WITH AIR HANDLERS TWE042P13 TWE048C14 TWE048P13 TWE049E13 TWE060A TWE060C/D15 TWE060P13 EXPANSION TYPE TXV-NB CHG TO 95 TXV-NB TXV-NB TXV-NB TXV-NB TXV-NB BTUH (TOTAL) 56000 57500 60500 60500 58000 58500 60500 BTUH (SENSIBLE) 38500 41100 43700 43700 42000 42400 43800 INDOOR AIRFLOW (CFM) 1575 1800 1800 1800 2000 1945 1800 SYSTEM POWER (KW) 5.28 5.42 5.40 5.45 5.25 5.63 5.40 EER/SEER (BTU/WATT-HR.) 10.60/12.25 10.60/12.00 11.20/13.00 11.10/13.00 11.05/12.50 10.40/12.00 11.20/13.00 TWE063P13 TWE065E13 TWG048A14 TWG060A15 EXPANSION TYPE TXV-NB TXV-NB CHG TO 95 TXV-NB BTUH (TOTAL) 61000 61000 55500 59000 BTUH (SENSIBLE) 45700 44200 38600 43200 INDOOR AIRFLOW (CFM) 2000 1800 1625 2000 SYSTEM POWER (KW) 5.73 5.33 5.21 5.59 EER/SEER (BTU/WATT-HR.) 10.65/12.25 11.45/13.25 10.65/12.00 10.55/12.00 See page 21 for combinations with Auxiliary Devices. 18 22-1735-01-0302 (EN)
Ratings with Auxiliary Devices COMBINATIONS WITH FAN DELAY RELAY KIT AND/OR TXV KIT When models are matched with an indoor air handler or coil that has a flow control check valve or expansion valve flow control, the addition of an indoor fan delay relay and/or TXV kit may increase the system SEER. See charts below for ratings. FAN OUTDOOR INDOOR DELAY TXV COOLING MODEL MODEL KIT KIT CFM SEER CAPACITY 2TTA2030A3/4 CCBB30A4AC Y NO 1000 12.00 29000 2TTA2030A3/4 CUBB30A4AC Y NO 1000 12.00 29000 2TTA2030A3/4 TDD060R9V3 FI NB 1000 13.50 29800 +TXH033A4 2TTA2030A3/4 TDD080R9V3 FI NB 950 13.50 29600 +TXH033A4 2TTA2030A3/4 TDY060R9V3 FI NB 870 13.50 29200 +TXH033A4 2TTA2030A3/4 TDY080R9V3 FI NB 890 13.25 29400 +TXH033A4 2TTA2030A3/4 TUD060R9V3 FI NB 1000 13.25 29800 +TXH033A4 2TTA2030A3/4 TUD080R9V3 FI NB 1000 13.50 29800 +TXH033A4 2TTA2030A3/4 TUY060R9V3 FI NB 880 13.25 29200 +TXH033A4 2TTA2030A3/4 TUY080R9V3 FI NB 855 13.50 29200 +TXH033A4 2TTA2030A3/4 TWE024C14 FI NB 900 12.00 27400 2TTA2030A3/4 TXA025C4 N NB 900 12.25 28400 2TTA2030A3/4 TXA030C4 N NB 1000 12.25 29000 2TTA2030A3/4 TXA031C4 N NB 1000 12.25 29600 2TTA2030A3/4 TXA035C4 N NB 1100 12.25 29400 2TTA2030A3/4 TXA036C4 N NB 1125 12.25 30200 2TTA2030A3/4 TXA037C4 N NB 1125 12.25 30200 2TTA2030A3/4 TXA042C4 N NB 1125 12.50 30200 2TTA2030A3/4 TXA043C4 N NB 1125 12.50 30200 2TTA2030A3/4 TXC025C4 N NB 900 12.00 28400 2TTA2030A3/4 TXC025D4 N NB 900 12.25 28400 2TTA2030A3/4 TXC030C4 N NB 1000 12.25 29000 2TTA2030A3/4 TXC030D4 N NB 1000 12.25 29000 2TTA2030A3/4 TXC031C4 N NB 1000 12.25 29600 2TTA2030A3/4 TXC031D4 N NB 1000 12.25 29600 2TTA2030A3/4 TXC035C4 N NB 1100 12.20 29400 2TTA2030A3/4 TXC035D4 N NB 1100 12.25 29400 2TTA2030A3/4 TXC036C4 N NB 1125 12.25 30200 2TTA2030A3/4 TXC036D4 N NB 1125 12.25 30200 2TTA2030A3/4 TXC037C4 N NB 1125 12.25 30200 2TTA2030A3/4 TXC042C4 N NB 1125 12.50 30200 2TTA2030A3/4 TXC043C4 N NB 1125 12.50 30200 2TTA2030A3/4 TXH025A4 N NB 900 12.00 28000 2TTA2030A3/4 TXH033A4 N NB 1000 12.25 29400 2TTA2030A3/4 TXH041A4 N NB 1125 12.50 30800 2TTA2036A3/4 CCBB36A4AC Y NO 1100 12.00 34400 2TTA2036A3/4 CUBB36A4AC Y NO 1100 12.00 34400 2TTA2036A3/4 TDD060R9V3 FI NB 1200 12.75 35000 +TXH033A4 2TTA2036A3/4 TDD060R9V3 FI NB 1200 13.50 37000 FI - FACTORY INSTALLED B - BLEED TXV NB - NON-BLEED TXV 22-1735-01-0302 (EN) 19 FAN OUTDOOR INDOOR DELAY TXV COOLING MODEL MODEL KIT KIT CFM SEER CAPACITY 2TTA2036A3/4 TDD080R9V3 FI NB 1125 12.75 34800 +TXH033A4 2TTA2036A3/4 TDD080R9V3 FI NB 1140 13.50 36600 2TTA2036A3/4 TDD100R9V5 FI NB 1130 12.75 34800 +TXH033A4 2TTA2036A3/4 TDD100R9V5 FI NB 1200 14.00 37200 2TTA2036A3/4 TDY060R9V3 FI NB 1080 12.75 34600 +TXH033A4 2TTA2036A3/4 TDY060R9V3 FI NB 1075 13.25 36400 2TTA2036A3/4 TDY080R9V3 FI NB 1100 12.50 34400 +TXH033A4 2TTA2036A3/4 TDY080R9V3 FI NB 1100 13.00 36400 2TTA2036A3/4 TDY100R9V4 FI NB 1050 13.00 34600 +TXH033A4 2TTA2036A3/4 TDY100R9V4 FI NB 1050 13.50 36200 2TTA2036A3/4 TUD060R9V3 FI NB 1250 12.25 35000 +TXH033A4 2TTA2036A3/4 TUD060R9V3 FI NB 1250 13.00 36800 2TTA2036A3/4 TUD080R9V3 FI NB 1200 12.50 35000 +TXH033A4 2TTA2036A3/4 TUD080R9V3 FI NB 1200 13.25 36800 2TTA2036A3/4 TUD100R9V5 FI NB 1200 13.00 35200 +TXH033A4 2TTA2036A3/4 TUD100R9V5 FI NB 1200 13.75 37200 2TTA2036A3/4 TUY060R9V3 FI NB 1070 12.75 34400 +TXH033A4 2TTA2036A3/4 TUY060R9V3 FI NB 1025 13.50 36200 2TTA2036A3/4 TUY080R9V3 FI NB 1000 13.00 34200 +TXH033A4 2TTA2036A3/4 TUY080R9V3 FI NB 1025 13.50 36200 2TTA2036A3/4 TUY100R9V4 FI NB 1050 13.00 34600 +TXH033A4 2TTA2036A3/4 TUY100R9V4 FI NB 1050 13.50 36400 2TTA2036A3/4 TXA031C4 N NB 1100 12.25 34400 2TTA2036A3/4 TXA035C4 N NB 1100 12.00 34200 2TTA2036A3/4 TXA036C4 N NB 1200 12.00 35800 2TTA2036A3/4 TXA037C4 N NB 1200 12.25 35400 2TTA2036A3/4 TXA042C4 N NB 1200 12.50 35800 2TTA2036A3/4 TXA043C4 N NB 1350 12.25 36200 2TTA2036A3/4 TXA048C4 N NB 1350 12.50 36800 2TTA2036A3/4 TXC031C4 N NB 1100 12.25 34400
Ratings with Auxiliary Devices COMBINATIONS WITH FAN DELAY RELAY KIT AND/OR TXV KIT When models are matched with an indoor air handler or coil that has a flow control check valve or expansion valve flow control, the addition of an indoor fan delay relay and/or TXV kit may increase the system SEER. See charts below for ratings. FAN OUTDOOR INDOOR DELAY TXV COOLING MODEL MODEL KIT KIT CFM SEER CAPACITY 2TTA2036A3/4 TXC031D4 N NB 1100 12.25 34400 2TTA2036A3/4 TXC035C4 N NB 1100 12.00 34200 2TTA2036A3/4 TXC035D4 N NB 1100 12.00 34200 2TTA2036A3/4 TXC036C4 N NB 1200 12.00 35800 2TTA2036A3/4 TXC036D4 N NB 1200 12.00 35800 2TTA2036A3/4 TXC037C4 N NB 1200 12.25 35400 2TTA2036A3/4 TXC042C4 N NB 1200 12.50 35800 2TTA2036A3/4 TXC043C4 N NB 1350 12.25 36200 2TTA2036A3/4 TXC048C4 N NB 1350 12.50 36800 2TTA2036A3/4 TXH033A4 N NB 1125 12.00 34400 2TTA2036A3/4 TXH041A4 N NB 1350 12.50 36800 2TTA2042A3/4 TDD080R9V3 FI NB 1340 13.25 43000 2TTA2042A3/4 TDD080R9V3 FI NB 1340 13.50 44000 +TXH054A4 2TTA2042A3/4 TDD100R9V5 FI NB 1400 14.00 43500 2TTA2042A3/4 TDD100R9V5 FI NB 1400 14.00 44500 +TXH054A4 2TTA2042A3/4 TDD120R9V5 FI NB 1400 14.00 43500 2TTA2042A3/4 TDD120R9V5 FI NB 1400 14.00 45000 +TXH054A4 2TTA2042A3/4 TDY120R9V5 FI NB 1215 13.75 42500 2TTA2042A3/4 TDY120R9V5 FI NB 1210 14.00 44000 +TXH054A4 2TTA2042A3/4 TUD080R9V3 FI NB 1400 13.00 43000 2TTA2042A3/4 TUD080R9V3 FI NB 1400 13.25 44000 +TXH054A4 2TTA2042A3/4 TUD100R9V5 FI NB 1465 13.75 43500 2TTA2042A3/4 TUD100R9V5 FI NB 1450 14.00 45000 +TXH054A4 2TTA2042A3/4 TUD120R9V5 FI NB 1400 14.00 43500 2TTA2042A3/4 TUD120R9V5 FI NB 1400 14.00 45000 +TXH054A4 2TTA2042A3/4 TUD140R9V5 FI NB 1375 14.00 43500 2TTA2042A3/4 TUD140R9V5 FI NB 1400 14.00 45000 +TXH054A4 2TTA2042A3/4 TUY080R9V3 FI NB 1210 13.50 42500 2TTA2042A3/4 TUY080R9V3 FI NB 1215 13.75 43500 +TXH054A4 2TTA2042A3/4 TUY100R9V4 FI NB 1220 13.75 42500 2TTA2042A3/4 TUY100R9V4 FI NB 1225 14.00 44000 +TXH054A4 FI - FACTORY INSTALLED B - BLEED TXV NB - NON-BLEED TXV FAN OUTDOOR INDOOR DELAY TXV COOLING MODEL MODEL KIT KIT CFM SEER CAPACITY 2TTA2042A3/4 TUY120R9V5 FI NB 1225 14.00 42500 2TTA2042A3/4 TUY120R9V5 FI NB 1225 14.00 44000 +TXH054A4 2TTA2042A3/4 TXA036C4 N NB 1200 12.75 40500 2TTA2042A3/4 TXA037C4 N NB 1350 12.75 41500 2TTA2042A3/4 TXA042C4 N NB 1200 13.00 41000 2TTA2042A3/4 TXA043C4 N NB 1400 13.00 41500 2TTA2042A3/4 TXA048C4 N NB 1350 13.00 42500 2TTA2042A3/4 TXC036C4 N NB 1200 12.75 40500 2TTA2042A3/4 TXC036D4 N NB 1200 12.75 40500 2TTA2042A3/4 TXC036E5 Y NO 1280 13.00 42500 2TTA2042A3/4 TXC037C4 N NB 1350 12.75 41500 2TTA2042A3/4 TXC037E5 Y NO 1350 13.00 43000 2TTA2042A3/4 TXC042C4 N NB 1200 13.00 41000 2TTA2042A3/4 TXC043C4 N NB 1400 13.00 41500 2TTA2042A3/4 TXC048C4 N NB 1350 13.00 42500 2TTA2042A3/4 TXH041A4 N NB 1400 13.00 42500 2TTA2042A3/4 TXH054A4 N NB 1575 13.25 45000 2TTA2048A3/4 CCBB48A4AC Y NO 1250 12.00 46500 2TTA2048A3/4 CCBC48A4AC Y NO 1600 12.00 48500 2TTA2048A3/4 CUBB48A4AC Y NO 1250 12.00 46500 2TTA2048A3/4 CUBC48A4AC Y NO 1600 12.00 48500 2TTA2048A3/4 CUBD48A4AC Y NO 1600 12.00 48500 2TTA2048A3/4 TDD100R9V5 FI NB 1600 13.00 49500 2TTA2048A3/4 TDD100R9V5 FI NB 1600 13.00 51500 +TXH054A4 2TTA2048A3/4 TDD120R9V5 FI NB 1600 13.00 50000 2TTA2048A3/4 TDD120R9V5 FI NB 1600 13.25 51500 +TXH054A4 2TTA2048A3/4 TDY100R9V4 FI NB 1450 12.50 48500 2TTA2048A3/4 TDY100R9V4 FI NB 1450 13.00 50500 +TXH054A4 2TTA2048A3/4 TDY120R9V5 FI NB 1410 12.75 48500 2TTA2048A3/4 TDY120R9V5 FI NB 1415 13.00 50500 +TXH054A4 2TTA2048A3/4 TUD100R9V5 FI NB 1670 12.75 49500 2TTA2048A3/4 TUD100R9V5 FI NB 1650 13.00 51500 +TXH054A4 2TTA2048A3/4 TUD120R9V5 FI NB 1625 13.00 49500 2TTA2048A3/4 TUD120R9V5 FI NB 1625 13.25 51500 +TXH054A4 2TTA2048A3/4 TUD140R9V5 FI NB 1600 13.00 49500 20 22-1735-01-0302 (EN)
Ratings with Auxiliary Devices COMBINATIONS WITH FAN DELAY RELAY KIT AND/OR TXV KIT When models are matched with an indoor air handler or coil that has a flow control check valve or expansion valve flow control, the addition of an indoor fan delay relay and/or TXV kit may increase the system SEER. See charts below for ratings. FAN OUTDOOR INDOOR DELAY TXV COOLING MODEL MODEL KIT KIT CFM SEER CAPACITY 2TTA2048A3/4 TUD140R9V5 FI NB 1600 13.25 51500 +TXH054A4 2TTA2048A3/4 TUY100R9V4 FI NB 1425 12.75 48500 2TTA2048A3/4 TUY100R9V4 FI NB 1430 13.00 50500 +TXH054A4 2TTA2048A3/4 TUY120R9V5 FI NB 1400 13.00 48500 2TTA2048A3/4 TUY120R9V5 FI NB 1425 13.25 50500 +TXH054A4 2TTA2048A3/4 TWE042C14 FI NB 1575 12.00 48000 2TTA2048A3/4 TWE060A Y NO 1800 13.00 50000 2TTA2048A3/4 TWG042A14 FI NB 1500 12.00 46000 2TTA2048A3/4 TXA043C4 N NB 1575 12.25 48000 2TTA2048A3/4 TXA048C4 N NB 1350 12.50 47500 2TTA2048A3/4 TXA049C4 N NB 1600 12.50 48500 2TTA2048A3/4 TXA050C4 N NB 1600 12.75 48500 2TTA2048A3/4 TXC043C4 N NB 1575 12.25 48000 2TTA2048A3/4 TXC048C4 N NB 1350 12.50 47500 FAN OUTDOOR INDOOR DELAY TXV COOLING MODEL MODEL KIT KIT CFM SEER CAPACITY 2TTA2048A3/4 TXC049C4 N NB 1600 12.50 48500 2TTA2048A3/4 TXC050C4 N NB 1600 12.75 48500 2TTA2048A3/4 TXH041A4 N NB 1575 12.50 49000 2TTA2048A3/4 TXH054A4 N NB 1700 13.00 51500 2TTA2060A3/4 CUBC60A4AC Y NO 1675 12.00 56000 2TTA2060A3/4 TWE060A Y NO 2000 13.00 58000 2TTA2060A3/4 TWG042A14 FI NB 1500 12.00 52500 2TTA2060A3/4 TXA043C4 N NB 1575 12.25 55000 2TTA2060A3/4 TXA048C4 N NB 1350 12.25 54000 2TTA2060A3/4 TXA049C4 N NB 1675 12.25 56000 2TTA2060A3/4 TXA050C4 N NB 1675 12.25 56000 2TTA2060A3/4 TXC043C4 N NB 1575 12.25 55000 2TTA2060A3/4 TXC048C4 N NB 1350 12.25 54000 2TTA2060A3/4 TXC049C4 N NB 1675 12.25 56000 2TTA2060A3/4 TXC050C4 N NB 1675 12.25 56000 2TTA2060A3/4 TXH054A4 N NB 1700 13.00 59000 FI - FACTORY INSTALLED B - BLEED TXV NB - NON-BLEED TXV 22-1735-01-0302 (EN) 21
Performance Data Cooling 2TTA2030A3/4 2TTA2030A3/4 WITH TXC031C4+TAYTXV-3 AT 1000 CFM O.D. I.D. TOT. SENS. CAP. AT ENTERING D.B. TEMP. TOTAL D.B. W.B. CAP. 72 75 78 80 KW 59 26.4 22.1 24.9 26.8* 27.5* 2.51 85 63 28.4 18.6 21.3 24.0 25.9 2.53 67 30.6 14.6 17.4 20.1 21.9 2.56 71 32.8 10.6 13.3 16.0 17.9 2.59 59 25.6 21.8 24.5 26.2* 26.9* 2.77 95 63 27.6 18.2 20.9 23.7 25.5 2.80 67 29.6 14.2 17.0 19.7 21.5 2.83 71 31.7 10.2 12.9 15.6 17.5 2.86 59 24.6 21.3 23.9 25.4* 26.0* 3.06 105 63 26.4 17.7 20.4 23.2 25.0 3.10 67 28.4 13.7 16.5 19.2 21.0 3.14 71 30.4 9.7 12.4 15.2 17.0 3.18 59 23.5 20.9 23.3 24.5* 25.1* 3.34 115 63 25.3 17.2 20.0 22.7 24.5 3.39 67 27.2 13.3 16.0 18.7 20.6 3.44 71 29.1 9.2 11.9 14.7 16.5 3.49 CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR) AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY LOW 875 0.98 0.94 HIGH 1125 1.01 1.05 NOTE: ALL TABLES ABOVE ARE AT ARI RATING CONDITIONS RATED WITH 25 FEET OF REFRIGERANT LINES. * DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE VALID ONLY FOR WET COIL. ALL TEMPERATURES IN DEGREES F. CCBA30A4AC RATED 1000 0.92 0.93 0.94 LOW 875 0.90 0.89 0.95 HIGH 1125 0.93 0.98 0.94 CCBB30A4AC+BAY24X045 RATED 1000 0.96 0.98 0.96 LOW 875 0.94 0.92 0.96 HIGH 1125 0.98 1.02 0.95 CUBA30A4AC RATED 1000 0.92 0.93 0.94 LOW 875 0.90 0.89 0.95 HIGH 1125 0.93 0.98 0.94 CUBB30A4AC+BAY24X045 RATED 1000 0.96 0.98 0.96 LOW 875 0.94 0.92 0.96 HIGH 1125 0.98 1.02 0.95 TDD060R9V3+TXC031S3 RATED 1000 1.03 1.05 0.92 LOW 875 1.01 0.98 0.92 HIGH 1125 1.04 1.10 0.92 TDD060R9V3+TXC036S3 RATED 1000 1.05 1.07 0.92 LOW 875 1.03 1.00 0.92 HIGH 1125 1.07 1.13 0.92 TDD060R9V3+TXH033A4+TAYTXV-3 RATED 1000 1.01 1.03 0.91 LOW 875 0.99 0.97 0.91 HIGH 1125 1.02 1.08 0.91 TDD080R9V3+TXC031S3 RATED 900 1.02 1.00 0.91 LOW 775 1.00 0.94 0.91 HIGH 1025 1.04 1.06 0.91 TDD080R9V3+TXC036S3 RATED 900 1.04 1.02 0.91 LOW 775 1.02 0.95 0.91 HIGH 1025 1.06 1.08 0.91 TDD080R9V3+TXH033A4+TAYTXV-3 RATED 1000 1.01 1.04 0.91 LOW 875 0.99 0.98 0.91 HIGH 1125 1.02 1.09 0.91 TDY060R9V3+TXC031S3 RATED 900 1.02 1.01 0.91 LOW 775 1.00 0.95 0.91 HIGH 1025 1.05 1.07 0.91 TDY060R9V3+TXC036S3 RATED 900 1.04 1.02 0.90 LOW 775 1.01 0.95 0.90 HIGH 1025 1.06 1.08 0.90 TDY060R9V3+TXH033A4+TAYTXV-3 RATED 900 0.99 0.99 0.90 LOW 775 0.97 0.93 0.90 HIGH 1025 1.01 1.05 0.90 TDY080R9V3+TXC036S3 RATED 900 1.04 1.02 0.92 LOW 775 1.01 0.95 0.92 HIGH 1025 1.06 1.08 0.92 TDY080R9V3+TXH033A4+TAYTXV-3 RATED 900 0.99 0.99 0.91 LOW 775 0.97 0.93 0.91 HIGH 1025 1.01 1.05 0.91 TUD060R9V3+TXC031E5 RATED 1000 1.03 1.04 0.94 LOW 875 1.01 0.98 0.94 HIGH 1125 1.04 1.09 0.94 TUD060R9V3+TXC031S3 RATED 1100 1.04 1.09 0.94 LOW 950 1.02 1.02 0.94 HIGH 1250 1.05 1.15 0.94 TUD060R9V3+TXC036S3 RATED 1000 1.05 1.06 0.94 LOW 875 1.03 1.00 0.94 HIGH 1125 1.06 1.13 0.94 TUD060R9V3+TXH033A4+TAYTXV-3 RATED 1000 1.01 1.03 0.93 LOW 875 0.99 0.97 0.93 HIGH 1125 1.02 1.08 0.93 TUD080R9V3+TXC031S3 RATED 1000 1.03 1.05 0.92 LOW 875 1.01 0.98 0.92 HIGH 1125 1.04 1.10 0.92 TUD080R9V3+TXC036S3 RATED 1000 1.05 1.07 0.92 LOW 875 1.03 1.00 0.92 HIGH 1125 1.07 1.13 0.92 TUD080R9V3+TXH033A4+TAYTXV-3 RATED 1000 1.01 1.03 0.92 LOW 875 0.99 0.97 0.92 HIGH 1125 1.02 1.08 0.92 TUY060R9V3+TXC031S3 RATED 900 1.02 1.00 0.91 LOW 775 1.00 0.94 0.91 HIGH 1025 1.04 1.06 0.91 TUY060R9V3+TXC036S3 RATED 900 1.04 1.02 0.91 LOW 775 1.01 0.95 0.91 HIGH 1025 1.06 1.08 0.91 TUY060R9V3+TXH033A4+TAYTXV-3 RATED 900 0.99 0.99 0.90 LOW 775 0.97 0.93 0.90 HIGH 1025 1.01 1.05 0.90 TUY080R9V3+TXC031S3 RATED 900 1.02 1.00 0.91 LOW 775 0.99 0.94 0.91 HIGH 1025 1.04 1.07 0.91 TUY080R9V3+TXC036S3 RATED 900 1.04 1.02 0.91 LOW 775 1.01 0.95 0.91 HIGH 1025 1.06 1.09 0.91 TUY080R9V3+TXH033A4+TAYTXV-3 RATED 900 0.99 0.99 0.90 LOW 775 0.97 0.93 0.90 HIGH 1025 1.01 1.05 0.90 TVF024A14 RATED 800 0.95 0.92 0.93 LOW 700 0.92 0.86 0.94 HIGH 900 0.97 0.96 0.92 TVF025A14 RATED 900 0.97 0.97 0.95 LOW 775 0.94 0.91 0.96 HIGH 1025 0.99 1.03 0.94 TVF030A14 RATED 1000 1.01 1.03 0.96 LOW 875 0.99 0.97 0.97 HIGH 1125 1.02 1.10 0.95 TVF036A14 RATED 1100 1.03 1.08 1.00 LOW 950 1.01 1.01 1.01 HIGH 1250 1.04 1.15 0.99 22 22-1735-01-0302 (EN)